manual ion enterprise

Upload: eduardomoura

Post on 05-Apr-2018

229 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/2/2019 Manual Ion Enterprise

    1/339

    PowerLogic ION Enterprise 5.6

    Power Management Software

    User GuideApril 2007

  • 8/2/2019 Manual Ion Enterprise

    2/339

  • 8/2/2019 Manual Ion Enterprise

    3/339

    NoticesThissectiondescribesthesymbolsusedinthisguide.

    Danger

    Thisalertsyoutothingsthatmaycauseseriousinjurytoaperson.Onlyqualified,properlytrainedpersonnelshouldperformtheseprocedures.

    Caution

    Thisalertsyoutothingsthatmaycauselossofdata,damagetoyourcomputeroryourdevice

    Note

    Anoteprovidesyouwithadditionalinformationthatyoumightwanttoconsider.

    Tip

    Thisdrawsyourattentiontoinformationthatwillhelpyouperformataskmorequicklyoreasily.

    PowerLogic,ION,IONEnterprise,MeterM@ilandModbusareeithertrademarksorregisteredtrademarksofSchneiderElectric.

    Documentation ConventionsThissectiondescribesthetermsusedtodescribecommonmethodsorproceduresusedthroughoutthisguide.

    Clear Place the mouse cursor over the check box, then click the mouse button to removethe check mark from the box.

    Click Place the mouse cursor over the button or item, then press and release the mousebutton.

    Double-click Place the mouse cursor over the button or item, then press and release the mousebutton twice.

    Drag Hold down the mouse button while moving the mouse cursor to hightlight theselection or move the selected item, then release the button.

    Enter Type the information, then press ENTER on the keyboard.

    Point Position the mouse pointer over an item such as a menu command.

    Press Press the specified key or combination of keys (for example, CTRL+ALT+DEL) onyour keyboard.

    Select Place the mouse pointer over a radio button or check box, then click the mousebutton to mark your selection.

    Type Type the information in the space or box. DO NOT press the Enter key.

  • 8/2/2019 Manual Ion Enterprise

    4/339

  • 8/2/2019 Manual Ion Enterprise

    5/339

    Contents

    Chapter 1 Introduction ................................................................ 13

    ION Enterprise Software Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14CoreApplications .................................................... 14

    Administration ....................................................... 14

    Programming ........................................................ 15

    ION Enterprise Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    ION Enterprise Databases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18StartingIONEnterprise ............................................... 18

    LoggingintoIONEnterprise........................................... 18

    Chapter 2 Management Console ................................................. 19

    The Management Console Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20ShortcutMenuSummary .............................................. 21

    Management Console Network Components . . . . . . . . . . . . . . . . . . . . . . . 25

    Detailed Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27AddingaNetworkComponent ......................................... 27

    EditingaNetworkComponent ......................................... 30

    DeletingaNetworkComponent ........................................ 30

    AccessingMeterswithAdvancedSecurity ............................... 30

    ConfiguringtheNetworkthroughSQLStatements ........................ 31ConfiguringConnectionSchedules...................................... 32

    Setting Up Large Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34CreatingMultipleCopiesofanEthernetDevice........................... 34

    CreatingMultipleCopiesofaSerialDevice .............................. 38

    CreatingMultipleCopiesofanOPCDevice .............................. 39

    SelectingMultipleDevicestoConfigure ................................. 40

    UsingtheTableEditingArea ........................................... 42

    Edit,CopyandPaste .................................................. 45

    FindandReplace ..................................................... 46

    Chapter 3 Management Console Tools ......................................... 49 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    User Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51StartingUserManager ................................................ 51

  • 8/2/2019 Manual Ion Enterprise

    6/339

    License Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    Diagnostic Viewer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54StartingDiagnosticViewer............................................. 54

    NavigationPanel ..................................................... 54

    DiagnosticsInformationPanel.......................................... 55

    Usingthe

    Filter

    Editor

    .................................................57

    ServerDiagnostics .................................................... 57

    CommunicationsDiagnostics .......................................... 59

    AdditionalCommands ................................................ 60

    CommunicationStatusvs.SiteStatus.................................... 62

    Device Upgrader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63UsingDeviceUpgrader................................................ 63

    FirmwareUpgradeErrorCodes ........................................ 65

    Remote Modem Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66UsingRemoteModemSetup ........................................... 66

    Virtual Processor Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68ConfiguringtheVirtualProcessorsModbusService....................... 68

    ModifyingtheGlobalParameters ....................................... 73

    Chapter 4 Vista .......................................................................... 75

    Starting Vista . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76EndingYourVistaSession ............................................. 76

    The Vista Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

    Vista User Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78WhatisaUserDiagram? .............................................. 78

    DefaultUserDiagrams ................................................ 79

    Generating, Opening and Closing a User Diagram . . . . . . . . . . . . . . . . . . 80GeneratingaNetworkDiagram ........................................ 80

    OpeningaUserDiagram .............................................. 80

    SpecifyingaVistaDiagramtoOpenforaGivenUser ...................... 80

    ClosingaUserDiagram ............................................... 81

    Navigating a User Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82DisplayModeandEditMode .......................................... 82

    GroupingWindows ................................................... 82

    DisplayFeatures...................................................... 83

    Monitoring Your System in Vista . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84ViewingRealTimeData ............................................... 84

    ViewingLoggedData ................................................. 87

  • 8/2/2019 Manual Ion Enterprise

    7/339

  • 8/2/2019 Manual Ion Enterprise

    8/339

  • 8/2/2019 Manual Ion Enterprise

    9/339

  • 8/2/2019 Manual Ion Enterprise

    10/339

  • 8/2/2019 Manual Ion Enterprise

    11/339

    Chapter 10 Alert Monitor Service ................................................ 319

    Alert Monitor Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320SettingUptheAlertMonitorService ................................... 321

    StartingtheAlertMonitorService...................................... 324

    Chapter 11 Downstream Device Assistant .................................... 325 Detecting Downstream Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326

    Downstream Device Assistant Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327StartingtheDownstreamDeviceAssistant .............................. 327

    BasicView .......................................................... 327

    AdvancedView ..................................................... 328

    DisplayingPhysicalSources........................................... 329

    SortingData ........................................................ 329

    Options ............................................................ 329

    Downstream Device Assistant Functions . . . . . . . . . . . . . . . . . . . . . . . . . . 332RenamingtheAssignedSource ........................................ 332

    CancellingChanges .................................................. 333

    ChangingtheMeasurementMapping .................................. 333

    AddingaNewDownstreamDeviceMapping ........................... 334

    UpdatingtheHistoricalDataataLaterTime ............................ 334

    ActivityLog ........................................................ 335

    Description of Columns and Commands . . . . . . . . . . . . . . . . . . . . . . . . . . 335DownstreamDeviceAssistantColumns ................................ 336

    DownstreamDeviceAssistantCommands .............................. 338

  • 8/2/2019 Manual Ion Enterprise

    12/339

  • 8/2/2019 Manual Ion Enterprise

    13/339

    2007 Schneider Electric. All rights reserved. Page 13

    1 Introduction

    PowerLogicIONEnterprisesoftwareisacompletepowermanagementsolutionforenergysuppliersandconsumers. Itallowsyoutomanageenergyinformationfrommeteringandcontroldevicesinstalledinyourfacilityorotherremotelocations. IONEnterpriseofferscontrolcapabilitiesandcomprehensivepowerqualityandreliabilityanalysistohelpyoureduceenergyrelatedcosts.

    IONEnterpriseiscompatiblewithMicrosoftWindowsServer2003operatingsystem,andsupportsmultiplecommunicationsstandardsandprotocolsavailableonIONmetersandsimilarintelligentmeteringdevices. YoucanalsoconnecttoexistingpowermonitoringsystemsthroughindustrystandardprotocolssuchasModbus,OPC,DNPandXML.

    IONEnterpriseusesMicrosoftSQLServer2005forefficientandsecuredatamanagement.YoucaninstalltheSQLServer2005ExpressEditionthatcomeswithIONEnterprise(4GBmaximumdatabasesize),orforlargerdatabaseneedsyoucanuseanexistingSQLServer2005instance(Standardeditionorbetter)tohosttheIONEnterprisedatabase.

    In This Chapter

    ION Enterprise Software Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14CoreApplications .................................................... 14

    Administration ....................................................... 14

    Programming ........................................................ 15

    ION Enterprise Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    ION Enterprise Databases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18StartingIONEnterprise ............................................... 18

    LoggingintoIONEnterprise........................................... 18

  • 8/2/2019 Manual Ion Enterprise

    14/339

    Chapter 1 - Introduction ION Enterprise 5.6 User Guide

    Page 14 2007 Schneider Electric. All rights reserved.

    ION Enterprise Software ComponentsThissectionoutlinestheIONEnterprisesoftwarecomponents,andhowtheyareusedtobuild,monitor,maintainandcustomizeyourIONEnterprisesystem.

    Core ApplicationsTheseIONEnterpriseprogramsaremostcommonlyusedindaytodaypowermanagementtasks:

    VistaVistaisthemainuserinterfacefordisplayinggraphicalrepresentationsofyourpowermonitoringsystemonacomputermonitor. Vistadisplaysrealtimeandhistoricalinformation,visualobjectsthatindicatethecurrentstatusofyoursystem,andinteractiveobjectsthatyoucanusetoperformcertainactionssuchasacknowledgingalarms.

    WebReachWebReachistheIONEnterprisecomponentthatdisplaysVistadiagramsinawebbrowser.

    ReporterReporteristhetoolyouusetocreateandgeneratecommonenergy,demandorpowerqualityreports.

    AdministrationTheseIONEnterpriseprogramshelpyousetupandmaintainyourpowermanagementsystem:

    Management ConsoleUseManagementConsoletoaddandconfigurenetworkcomponentssuchasservers,sites(communication links)anddevices. ManagementConsolealsoprovidesaccesstosystemanddatabaseapplications,andutilitiesformanaginguseraccountsandupgradingthesoftwarelicensing. Thesearedescribedinthefollowingtopics:

    DatabaseManagementonpage 289

    UserManageronpage 51

    LicenseManageronpage 53

    Designeronpage 195

    DiagnosticVieweronpage 54

  • 8/2/2019 Manual Ion Enterprise

    15/339

    ION Enterprise 5.6 User Guide Chapter 1 - Introduction

    2007 Schneider Electric. All rights reserved. Page 15

    DeviceUpgraderonpage 63

    RemoteModemSetuponpage 66

    VirtualProcessorSetuponpage 68

    ModbusDeviceImporteronpage 259

    ThefollowingcommandsareavailablefromtheManagementConsoleToolsmenuwhentheseaddoncomponentsareorderedandactivated:

    Update OPC Server

    ThiscommandchecksthenetworkfornewsourcesofcommonortypicalmeasurementstobeexposedtotheOPCServer;thisisonlyavailablewiththeoptionalOPCServerlicense.

    PQDIF Exporter

    ThiscommandletsyouexportdatatoPowerQualityDataInterchangeFormat(PQDIF)andsetregularscheduledexportswithnotification;thisisonlyavailablewiththeoptionalPQDIFExporterlicense.

    ProgrammingTheseIONEnterpriseprogramshelpyoucustomizeelementsinyoursystemandconfigurethirdpartydevicessothesystemcanrecognizeandutilizethem:

    DesignerUseDesignertoperformawiderangeoffunctions,fromconfiguringsetupregistersofdevicesonyournetwork,tocreationofcomplexframeworksusingacombinationofIONmodulesfromhardwareorsoftwarenodes.

    Modbus Device ImporterUseModbusDeviceImportertointegratethirdpartyModbusdevicesintotheIONEnterprisenetwork.

    Large System Setup Using Management ConsoleRefertoSettingUpLargeSystemsonpage 34tosetuplargesystemsefficiently,usingtheDuplicateandConfigureshortcutcommandfordevicesinManagementConsole.

  • 8/2/2019 Manual Ion Enterprise

    16/339

    Chapter 1 - Introduction ION Enterprise 5.6 User Guide

    Page 16 2007 Schneider Electric. All rights reserved.

    ION Enterprise ServicesManyofIONEnterprisescorecomponentsrunasWindowsServices. Thisallowsyourserverstocontinuemonitoringyourpowermanagementsystemevenwhennousersareloggedon. Intheeventofapoweroutage,yoursystemautomaticallyresumespowermonitoringwhenthepowerisrestored. TheIONEnterpriseservicesarestartedandsetforautomaticstartupbydefault,unlessnotedbelow:

    IONAlertMonitorServicecontinuouslycheckstheIONEnterprisecomputerscommunicationsportsforhighpriorityeventsoccurringatremotemodemsites.Whenthishappens, AlertMonitorinitiatesacommunicationsconnectiontotheremotemodemsite. AlertMonitorisregisteredasamanualservice,andisnotstartedbydefault.

    IONComponentIdentifierServicemanagescommunicationsbetweenlocalandremoteIONEnterprisecomponents.

    IONConnectionManagementServiceisresponsiblefordeterminingtheconnectionstatusoftheIONEnterprisesystemssitesanddevices,aswellas

    handlingresource

    allocation

    such

    as

    modems.

    ThisservicemanagesthestateofconnectivityfortheIONEnterprisesoftwaresystem.Inordertoestablishthemostappropriatestateforthesystem,eachconnectionanddisconnectionrequestisevaluatedagainsttheoverallstateofthesystemandavailabilityofcommunicationschannels.ThesystemstatusisstoredintheNetworkConfigurationDatabase.

    IONDDEServerisresponsibleforprovidingDynamicDataExchange(DDE)connectivitybetweenIONdevicesandDDEcompatibleapplications,suchasExcel. IONDDEServerisregisteredasamanualservice,andisnotstartedbydefault.

    IONLogInserterServiceprovideshistoricaldatastorageforyourpower

    monitoring

    system.

    Refer

    to

    Log

    Inserter

    on

    page 313. IONNetworkRouterServiceisresponsibleforroutingallinformationbetween

    IONsoftwarecomponents,suchasclientworkstationsandtheLogInserter.Theservicedynamicallydetectschangestothenetworkconfiguration,includingtheadditionofnewservers;itisalsocapableofrecognizingnewsoftwarenodes,suchasVista,thatareaddedtoanexistingserver.Thismechanismisusedforautomaticsoftwarenoderegistration.

    NOTE

    ION Network Router Service has many dependent ION software services: the Virtual Processor, ION Log

    Inserter Service, ION Site Service, and DDE services cannot start and operate without it running.

    IONOPC

    Data

    Access

    ServermanagesandisresponsibleforsupplyingOPC

    datatoclientapplications. IONOPCDataAccessServerisregisteredasamanualservice,andisnotstartedbydefault.

    IONPQDIFExporterServicetranslatesIONdatatoPQDIFfileformatandmanagesscheduledPQDIFexports. IONPQDIFExporterServiceisregisteredasamanualservice,andisnotstartedbydefault.

  • 8/2/2019 Manual Ion Enterprise

    17/339

    ION Enterprise 5.6 User Guide Chapter 1 - Introduction

    2007 Schneider Electric. All rights reserved. Page 17

    IONQueryServiceprovideshistoricaldataretrievalforyourpowermonitoringsystem.RefertoConfiguringaDataLogViewerorEventLogVieweronpage 126formoreinformationregardingthisservice.

    IONRealTimeDataServicemanagesandprovidesaccesstorealtimedatafromthepowermanagementsystem.

    ION

    Site

    Service

    manages

    communication

    links

    to

    and

    from

    ION

    Enterprise.

    IONSiteServiceisresponsibleforhandlingpacketcommunicationstosystemdevicesandcontrollingdirectdevicecommunications.Theservicereactstochangesinnetworkconfiguration:forexample,oftenchangestocertainchannels,gates,ports,ordeviceparameterscaninterruptaconnection).Youcanadd,delete,orchangechannels,gates,ports,anddeviceswithouthavingtorestarttheIONSiteService,IONNetworkRouterService,andIONConnectionManagementService.

    IONVirtualProcessorServiceprovidescoordinateddatacollection,dataprocessing,andcontrolfunctionsforgroupsofmeters.FormoreinformationontheVirtualProcessoranditsfunctionality,refertoVirtualProcessorSetuponpage 68.

    IONXML

    Subscription

    Service

    manages

    subscriptions

    to

    XML

    data

    for

    Vista

    diagrams.ThisserviceisusedonlybyWebReach.WhenyouopenaVistadiagraminawebbrowser,theIONXMLSubscriptionServicecreatesasubscriptionanddeliverstherealtimedatainXMLformat.Subscriptionsexpireautomaticallyiftheyarenotrenewed.AbrowserrenewsasubscriptionbyrepeatedlyrequestingXMLdata.

    IONXMLSubscriptionStoreServicekeepstrackofdatasubscriptionstothepowermonitoringdevicesonthenetwork. ThisserviceisusedonlybyWebReach.

    ION Enterprise DatabasesTheIONEnterprisedatabasesaretypicallyinstalledonthePrimaryServerandruninthebackgroundofyourIONEnterprisenetworksystem. IONEnterpriseusestheSQLServer2005instanceyousetuptoconnecttothesedatabases:

    IONDatabase(ION_Data):Thiscontainsloggeddatafromalldevicesonthepowermanagementnetwork.

    NetworkConfigurationDatabase(ION_Network):Thiscontainsinformationaboutyournetworktopologythenetworkconnections,computersandeveryconnecteddevice,includingdialoutmodems.

    System

    Event

    Database

    (ION_SystemLog):

    This

    contains

    records

    of

    all

    system

    events.

  • 8/2/2019 Manual Ion Enterprise

    18/339

    Chapter 1 - Introduction ION Enterprise 5.6 User Guide

    Page 18 2007 Schneider Electric. All rights reserved.

    Getting StartedMostIONEnterpriseprogramsrequireyoutologinbeforeyoucanusethem.

    Starting ION EnterpriseUseoneofthefollowingmethodstostartIONEnterprise:

    OpentheIONEnterpriseToolsfolderonyourdesktopanddoubleclicktheiconoftheprogramyouwanttostart

    DoubleclicktheIONEnterpriseicontoopentheIONEnterpriseTaskpad,thenclickononeofthelinks

    ClickStart>Programs>SchneiderElectric>IONEnterpriseTools.

    Logging in to ION EnterpriseSomeIONEnterpriseprogramsrequireyoutologinbeforeyoucanaccessthem.

    Typeyourusernameandpasswordintheappropriatebox,thenclickOK. Someactionsarerestrictedtocertainusersorgroups,dependingonhowtheirloginpermissionsweresetup. SeeUserManageronpage 51fordetails.

    For read-only access withoutusing a password, click View only.

  • 8/2/2019 Manual Ion Enterprise

    19/339

    2007 Schneider Electric. All rights reserved. Page 19

    2 Management Console

    UseManagementConsoletoadd,removeorconfigurecomponentssuchasmeteringdevicesinyourIONEnterprisepowermanagementsystem. Youcansetupdifferenttypesofsites(communicationlinkssuchasEthernetorserial),andsetupconnectionschedulesforthesesites.

    Inaddition,theManagementConsoleToolsmenuprovidesaccesstodeviceandsystemconfiguration,maintenanceandprogrammingtools. Theseincludeprogramsformanagingthedatabases,useraccountsandsoftwarelicenseupgrades. SeeManagementConsoleToolsonpage 49fordetails.

    CAUTIONUnauthorized changes to the network configuration can result in an unstable or unusable network,

    therefore only users with Operator or Supervisor priv ileges can make changes in Management Console.

    In This Chapter

    The Management Console Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20ShortcutMenuSummary .............................................. 21

    Management Console Network Components . . . . . . . . . . . . . . . . . . . . . . . 25

    Detailed Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27AddingaNetworkComponent ......................................... 27

    EditingaNetworkComponent ......................................... 30

    DeletingaNetworkComponent ........................................ 30

    AccessingMeterswithAdvancedSecurity ............................... 30

    ConfiguringtheNetworkthroughSQLStatements ........................ 31

    ConfiguringConnectionSchedules...................................... 32

    Setting Up Large Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34CreatingMultipleCopiesofanEthernetDevice........................... 34

    CreatingMultipleCopiesofaSerialDevice .............................. 38

    CreatingMultipleCopiesofanOPCDevice .............................. 39

    SelectingMultipleDevicestoConfigure ................................. 40UsingtheTableEditingArea ........................................... 42

    Edit,CopyandPaste .................................................. 45

    FindandReplace ..................................................... 46

  • 8/2/2019 Manual Ion Enterprise

    20/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 20 2007 Schneider Electric. All rights reserved.

    The Management Console InterfaceTostartManagementConsole:

    1. ClickStart>Programs>SchneiderElectric>IONEnterpriseTools>ManagementConsole(ordoubleclicktheIONEnterpriseicononyourdesktoptoopentheIONEnterpriseTaskpad,thenclickontheManagementConsolelink).

    2. TypeyourusernameandpasswordintheLogondialog. Thedefaultusernameisguestwithapasswordof0(zero).

    Window titleThewindowtitledisplaysthetypeofSystemSetupitemcurrentlyselected,thecurrentusersnameandusersecurityaccesslevel,andthenameofthesoftwareprogram:

    System Setup paneTheiconsintheSystemSetuppanerepresentcategoriesofitemsyoucanadd,

    remove,and

    set

    up.

    You

    can

    change

    the

    icon

    size

    by

    right

    clicking

    inside

    the

    SystemSetuppaneandselectingoneoftheoptions.

    Display windowTheDisplaywindowconsistsoftwotabs,PropertiesandEvents. WhenyoufirstselectaSystemSetupicon,theDisplaywindowshowsthePropertiestabbydefault.

    Window title

    Display window.This area displays the contents of

    the selected system setup icon.System Setup paneand icons

    Properties tab &Events tab

    Mouse hover text

    Table title

    Selected SystemSetup item User name Access level Program name

  • 8/2/2019 Manual Ion Enterprise

    21/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 21

    Sorting items in the Display window

    Clickacolumnheadingtosorttheitemsinthatcolumninascendingorder;clickitagaintosorttheitemsindescendingorder.

    Properties tab

    AllconfigurationisperformedthroughthePropertiestab. ThePropertiestablistsconfigurationpropertiesofeachsystemiteminarow. TheselectedSystemSetupitemdetermineswhatcolumnheadings(Properties)aredisplayed.

    Events tabTheEventstablistssystemeventsfortheitemscontainedinthePropertiestab.Foreventswithlongdescriptions,youcanresizethecolumnwidth. Youcanalsodoubleclickthatrowtodisplaythedetailsofthateventinsideadialogbox,foreasierreading. Youcanalsocopythedescriptionbyselectingitinthedialogbox,thenpressingCTRL+C.

    PriorityPriorityisanumberornumericrangethatclassifieswhattypeofeventhasoccurred. Thesystemlogdatabaseliststheseeventprioritiesasnumbersintheeventtable. Thevaluecorrespondstotheseverityoftheevent:thehigherthenumber,themoreseveretheeventis. WheneventsareviewedinManagementConsole,theprioritynumberisevaluatedanddisplayedasaprioritystring.Priorityismappedaccordingtothefollowingnumericranges:

    Bydefault,theCutoffsetupregisterofLogInsertersSystemLogControllermoduleissetto192. Thismeansthatsystemeventswithaprioritylessthan192arenottransferredtotheIONdatabaseandthereforecannotbeviewedinVistausingtheGlobalEventViewer. UsetheaboveprioritymappingasaguidetosettheCutoffsetupregistertoalowervalueifyouwanttoviewlowerpriorityeventsinVista.

    NOTE

    The Global Event Viewer includes records retrieved from meter and Virtual Processor event logs, as well

    as records transferred from the system log database.

    Shortcut Menu SummaryShortcutmenusareaccessedbyrightclickingcertainareasintheManagementConsole.Differentareasopendifferentshortcutmenus.ThefollowingareasoftheManagementConsoleprovideaccesstoshortcutmenus:

    Diagnostic 0-5 Warning 21-63 Critical 192-255

    Information 6-20 Error 64-191

  • 8/2/2019 Manual Ion Enterprise

    22/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 22 2007 Schneider Electric. All rights reserved.

    System Setup pane

    RightclicktheSystemSetuppanetoaccessshortcutmenusforadjustingthesizeoftheiconsinthispane.

    Table title

    Tousethetabletitleshortcutmenus,rightclickthetabletitletoaccessthese

    shortcutmenus:

    RefreshmanuallyupdatestheManagementConsole(i.e.reloadsitscontents).

    ViewFieldallowsyoutoselectanitemanddisplaythevalueofaparticularfieldinadialogbox. Thisisusefulforviewingtextthatistoolongtofitwithinthecolumnswidth. TheViewFieldoptionschange,dependingonwhichtabyouhaveselectedPropertiestaborEventstab.

    Propertiesopensthepropertysheet(Optionsdialogbox)fortheDisplayWindow,whereyoucanchangethesettingsoftheColumnPropertiesorRowProperties.

    ColumnPropertiestab: Youcancontrolwhichcolumns(fields)areshown

    inthedisplaywindow. Selectthecheckboxbesidethefieldtodisplaythatcolumn,orclearittohidethatcolumn. Youcanalsocontrolwhichitems(rows)aredisplayedbyusingtextfilteringonaparticularcolumn. Clickthenameofthecolumn(field)toselectit,thenclicktheSetFilterbutton. IntheFilterSetupdialogbox,typethetextyouwanttosearchforintheFilterText

    box,thenselectwhetheryouwantthesearchtomatchthetextExactly,orCombinedwithothertext. ClickOKtoapplythefilter. Textfilteringisusefulinsituationswheretherearetoomanyrowsshowninthedisplaywindow. ClickClearFiltertoturnoffthefiltering.

    RowPropertiestab: ThisletsyoucontroltheappearanceoftherowsintheEvent

    tab. Youcanenableordisablerowhighlighting,andspecifywhichhighlightcolortouse. Rowhighlightingappliesthecoloryouspecifytoeveryotherrow,todistinguishthembetter. Youcanalsosethowmanyrecenteventrecordstoretrieve,andspecifywhetherornottoconvertthetimestampstolocaldateandtime.

  • 8/2/2019 Manual Ion Enterprise

    23/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 23

    Display Window

    ToaccessshortcutmenusintheDisplayWindow,firstselecttheSystemSetupitembyclickingitsicon. Then,rightclickinthedisplaywindowareatodisplaytheshortcutmenu.

    Newdisplaystheoptionsavailableforaddingnewnetworkitems. ConnectandDisconnectletsyoumanuallyconnectordisconnecttheselectedsite. Similarly,ConnectEthernetandDisconnectEthernetmanuallyconnectsordisconnectstheselectedEthernetdevice. Notethatyoucannotconnectordisconnectan

    individualserialdeviceinasite;youcanonlyconnectordisconnectthesiteforthatserialdevice.

    Security...accessestheAdvancedMeterSecuritySettingsdialogbox.Thisisusedbythesoftwaretogainaccesstosecurityenableddevices(e.g.ION8600orION7650);itisonlyavailablefromtheshortcutmenufortheDevicesDisplayWindow.SelectingProperties...opensthepropertysheet(options)fortheselectedserver,site,ordevice.Mandatorypropertiesarehighlightedinredyoumustselectorentertheappropriatevalueforthese.

    Devices

    Servers

    Sites

  • 8/2/2019 Manual Ion Enterprise

    24/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 24 2007 Schneider Electric. All rights reserved.

    Duplicatecreatesoneormorecopiesofaselecteditem.

    NOTE

    For the Duplicate command, each one of the duplicates needs to be opened individually in order toconfigure them. Duplicate and Configure cuts setup time by creating and setting up multiple devices atthe same time.

    Deleteremovestheselecteditems.

    DuplicateandConfigure...letsyouperformbatchcloningofdevicesarealtimesaverwhencommissioninglargesystems. Whenmultipledevicesareselected,thisrightclickshortcutbecomesConfigureSelectedDevices...whichletsyouperformusefulsetupfunctionssuchasbatchrenamingofdevices.

    Component Property Sheet Shortcut Menus

    Thisshortcutmenuisaccessedfromapropertysheet(Optionsdialogbox) foraserver,site,device,ordialoutmodem. SelectingPropertyDetails...opensawindowcontaininginformationontheselectedproperty,includingminimumandmaximumallowablevalues,ifapplicable. AdvancedPropertiesexposesalltheremainingpropertyfieldsthatwerehiddeninthedefault(basic)view. ResetAllToDefaultresetsallpropertiestotheiroriginalvalues.

    Select a property to display itsdescription in the PropertyDescription field, as shownhere.

  • 8/2/2019 Manual Ion Enterprise

    25/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 25

    Management Console Network ComponentsThissectiondescribesthedifferentnetworkitemsinManagementConsole.

    ServersAserverisacomputerinanIONEnterprisesystemrunningadministrativesoftwarethatcontrolsaccesstothenetworkanditsresources,suchasIONdevices.Aserverprovidesresourcestoothercomputers(workstations)onthenetwork.TheserverrunsservicecomponentsfortaskssuchascreatingcommunicationandsoftwarelinksbetweenIONsystemcomponents,andcreatinglinksintoIONdatabases.

    SitesAsiteisagroupofdevicesintheIONEnterprisesystemthatshareacommoncommunicationslink. Asitecanbeadirectsite,amodemsite,Ethernetgatewaysite,orOPCsite.

    Direct Site

    Inadirectsite,serialcommunicationsoccurbetweenacomputerandoneormoremeters. Tosetupadirectsite,youmustspecifyaserialcommunicationsportonthecomputer. ThestandardsmostcommonlyusedoncomputersareRS232(forconnectingonedevice)andRS485(forconnectingaloopofupto32devices).Whenconnectingtomorethanoneserialdevice,useanRS232toRS485converter.

    Modem Site

    Inamodemsite,communicationsoccurbetweenaremotemodem(attheModemSite)andalocalmodem(onthePrimaryServer).

    NOTE

    Remote sites that use radio modems or leased-line modems are configured as Direct (Serial) Sites, not as

    Modem Sites.

    Modemsitescanincludetraditionalhardwaremodems(thosethatareconfiguredandcontrolledbyIONEnterprise),orWinModems(Windowsmodems). Ifmultiplemodemsaresetupinthemodemsite,IONEnterprisechoosesthefirstavailablemodemtoestablishcommunications(thisisreferredtoasmodempooling).

    Ethernet Gateway SiteEthernetgatewaysitesconsistofanRS485chainofdevicesthatcommunicateswithanEthernetnetworkviaanEthernetDevicethatconvertsRS232/RS485communicationstoandfromEthernet. TheEthernetDevicethenhasadirectconnectiontothenetworkofserialdevicesthroughoneofitsserialcommunicationsports. TheEthernetdeviceactsasagatewaythattransfersdata

    betweenanEthernetnetworkandanRS485chainofconnecteddevices. ForEthernetgatewaysites,theTCP/IPAddressfieldandTCP/IPPortfieldmustbefilledin. TheTCP/IPPortcanidentifywhichcommunicationsportisusedfor

  • 8/2/2019 Manual Ion Enterprise

    26/339

  • 8/2/2019 Manual Ion Enterprise

    27/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 27

    Detailed OperationThePrimaryServercontainsalltheIONEnterpriseprogramsandcontrolstheoveralloperationofyourenergymanagementsystem. TheprimaryserverisdisplayedwhenyoufirststartManagementConsole.

    Tostartbuildingyoursystem,addandsetupyoursitesanddevices.

    Adding a Network ComponentFollowtheprocedurebelowtoaddanewnetworkcomponent:

    1. SelecttheSystemSetupitemthatyouwanttoaddbyclickingitsicon(i.e.,Server,Site,Device,DialOutModem,orConnectionSchedule).

    2. Rightclickinthedisplaywindow,selectNew,andthenselectthespecifictypeofnetworkcomponentfromtheshortcutmenu. Theoptionsdifferdepending

    on

    which

    system

    setup

    item

    you

    have

    selected.3. Configurethepropertiesusingthedropdownmenus;mandatoryitemsare

    highlightedinredtheymustbefilledin.

    Ifyouwanttoconfigureadvancedproperties,rightclickinthedialogboxandselectAdvancedProperties.

    4. ClickOKwhenyouaredone.

    Adding a ServerClicktheServersicon,rightclickinthedisplaywindowandselectNew > Computer,thenfillinallthemandatoryfields.

    Right-click a field andselect Property Detailsfor more information ona particular property.

    Right-click and selectAdvanced Propertiesto display all properties.

    This area displays thedescription of theselected property.

  • 8/2/2019 Manual Ion Enterprise

    28/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 28 2007 Schneider Electric. All rights reserved.

    Setting Up Devices for Direct Serial CommunicationsTosetupdevicesforRS232orRS485communicationsonadirectserialloop,firstyouneedtosetupadirectsite. SerialdevicesyoucanaddtoadirectsiteincludethosethatcommunicateusingIONorModbusRTUprotocol.

    Adding a Direct Site

    ClicktheSitesicon. RightclickinthedisplaywindowandselectNew > DirectSite. FillintheNameandSerialPortfields,andconfiguretheotherfieldsasrequired.

    Adding a Device to the Direct Site

    ClicktheDevicesicon. RightclickinthedisplaywindowandselectNew > SerialDeviceonDirectSite. Fillinthesefields:

    Group(selectoneorsetupanewonebyselecting[AddNewGroup])

    Name

    DeviceType(forserialModbusdevices,selecttheonewithModRTUin

    brackets) UnitID(rangeis19999forIONdevices,or1247forModbusRTUdevices)

    Site(selecttheDirectSiteyoupreviouslysetup)

    Configuretheotherfieldsasrequired.

    Setting Up Devices for Ethernet Gateway CommunicationsTosetupdevicesforEthernetgatewaycommunications,firstyouneedtosetupanEthernetgatewaysite. EthernetgatewaysthatcanbeusedincludethosethataresimpleEthernettoSerialconverters,oranygatewayordataconcentratorthatprovidesModbusTCPcommunications.

    Adding an Ethernet Gateway Site

    ClicktheSitesicon. RightclickinthedisplaywindowandselectNew > EthernetGatewaySite. FillintheName,TCP/IPAddressandTCP/IPPortfields,andconfiguretheotherfieldsasrequired.

    Adding a Device to the Ethernet Gateway Site

    ClicktheDevicesicon. RightclickinthedisplaywindowandselectNew > SerialDeviceonEthernetGatewaySite. Fillinthesefields:

    Group(selectoneorsetupanewonebyselecting[AddNewGroup])

    Name

    DeviceType(forModbusTCPgateways,selectadevicetypewith ModTCP in

    brackets)

    UnitID(rangeis19999forIONdevices,or1247forModbusTCPdevices)

    Site(selecttheEthernetGatewaysiteyoupreviouslysetup)

    Configuretheotherfieldsasrequired.

  • 8/2/2019 Manual Ion Enterprise

    29/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 29

    Adding an Ethernet DeviceClicktheDevicesicon. RightclickinthedisplaywindowandselectNew > EthernetDevice. FillintheGroup,Name,DeviceTypeandTCP/IPAddressfields,andconfiguretheotherfieldsasrequired.

    NOTE

    When configuring Ethernet or Ethernet Gateway devices, you can specify either a hostname or an

    IP address in the TCP/IP Address field.

    Setting Up Devices for OPC Communications

    NOTE

    At least one OPC Device Type needs to be preconfigured before an OPC Device can be created in

    Management Console. Contact Technical Support for assistance.

    TosetupdevicesforOPCcommunications,firstyouneedtosetupanOPCsite.

    Adding an OPC Site

    ClicktheSitesicon.RightclickinthedisplaywindowandselectNew > OPCSite.FillintheNameandAddressfields,andconfiguretheotherfieldsasrequired.

    MakesureyoufollowthecorrectsyntaxwhenfillingintheaddressfortheOPCsite. SelecttheAddressfieldtoseeanexampleadressinthePropertyDescriptionarea(nearthebottomoftheOPCSiteOptionsdialog).

    Adding a Device to the OPC Site

    ClicktheDevicesicon. RightclickinthedisplaywindowandselectNew > OPCDevice. FillintheGroup,Name,DeviceTypeandSite(selecttheOPCsiteyoupreviouslysetup),andconfiguretheotherfieldsasrequired.

    Adding a Modem1. ClicktheDialOutModemsicon,rightclickinthedisplaywindowandselect

    New,thenselecteitherSerialModem...(hardwaremodem),orWinModem...(Windowsmodem).

    2. Fillinthevaluesforallrequiredfieldsinthepropertiesdialogbox:

    Forserialmodem,selecttheModemTypefromthelist. Ifyourmodemisnotinthislist,selectGenericIONModem Other. SelecttheSerialPortwhereyourmodemisconnected.

    ForWinModems,selecttheModemNamefromthelist.

    3. ClickOK.

    WinModem Installation Notes

    BeforeyoucanuseaWinModem,youmustfirstinstallitonyourcomputer(followtheinstructionsthatcamewiththeWinModemproduct). Afterrebootingthecomputer,setuptheWinModem:

  • 8/2/2019 Manual Ion Enterprise

    30/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 30 2007 Schneider Electric. All rights reserved.

    1. ClickStart>Settings>ControlPanel,thendoubleclickPhoneandModemOptions.

    2. ClicktheModemstab,selectyourWinModem,thenclickProperties.

    3. ClicktheAdvancedtab,thenclickChangeDefaultPreference.

    4. SetPortspeedtomatchthebaudratethatisusedbetweenthemeterandthe

    modemontheremoteendoftheconnection(i.e.bothmodemsmustbesettothesamebaudrate).

    5. SetFlowControltoNone.

    6. ClickOKtoapplythechanges.

    NOTE

    You may need to reboot your machine for the settings to take effect.

    Editing a Network Component1. ClicktheappropriateSystemSetupicon.

    2. Inthedisplaywindow,rightclickthenetworkcomponentyouwanttoeditandselectProperties.

    3. Maketherequiredchanges. Todisplayallconfigurablefields,rightclickinthepropertiesdialogboxandselectAdvancedProperties.

    Deleting a Network Component1. ClicktheappropriateSystemSetupicon.

    2. Inthe

    display

    window,

    right

    click

    the

    network

    component

    you

    want

    to

    delete

    andselectDelete(orselecttheitemandpresstheDeletekey).

    3. ClickYestoconfirmthedeletion.

    CAUTION

    When deleting a Site or a Server, all devices associated with it are also deleted.

    Accessing Meters with Advanced Security

    If

    you

    have

    a

    meter

    in

    your

    network

    with

    Advanced

    Security,

    use

    Management

    ConsoletoconfigurethesecuritysettingssothatIONRealTimeDataServicecanaccessthemeter:

    1. RightclickthedevicethathasAdvancedSecurityenabledandselectSecurity....

  • 8/2/2019 Manual Ion Enterprise

    31/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 31

    1. Setuptheappropriateaccesslevel.

    2. ClickOK.

    Configuring the Network through SQL StatementsYoucanuseManagementConsoletomanuallyconfigurethenetworkcomponents

    byexecutingSQLstatements.

    CAUTION

    Altering the network configuration using SQL satements is for advanced users only.

    1. WhileholdingdowntheCTRLkey,rightclickthetabletitle(shadedareaabovethedisplaywindow)andselectCustomSQL.Awarningdisplays(thiswarningappearsonlyoncepersession):

    2. ClickOKtocontinue.

    3. TypeyourSQLstatementintheCustomSQLbox.

    4. ClickExecute.

    TheresultsoftheSQLstatementexecutionappearinthedisplaywindow.

  • 8/2/2019 Manual Ion Enterprise

    32/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 32 2007 Schneider Electric. All rights reserved.

    Configuring Connection SchedulesYoucanschedulethetimeswhentheserverconnectstoaSite.

    1. ClicktheConnectionSchedulesicon,rightclickinthedisplaywindow,thenselectNew.

    2. Enterthenameofyourconnectionschedule(forexampleDailyReading).

    3. SelecttheSitestab,thenclickChangeSelection...

    4. IntheAvailableSitesarea,clickthesitesorindividualdevicesyouwanttoincludeintheschedule,thenclicktherightarrowbuttonneartheIncludeSitesareatomovetheselectedsitethere. YoucanalsosetsitesordevicesyouwanttoexcludebymovingthemtotheExcludeSitesarea. ClickOK.

  • 8/2/2019 Manual Ion Enterprise

    33/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 33

    5. MakeyourchangesintheSiteConnectionSettingssection,thenclicktheScheduletab.

    6. Setyourscheduleforthesiteconnection,thenclickOK. Ifyouconfigureafull

    day(i.e.

    24

    hour)

    daily

    schedule,

    make

    sure

    you

    allow

    enough

    time

    between

    the

    endtimeandthestartofthenextconnectiontoavoidconnectionproblems. Forexample,toadda2minutegaptoa24hourschedule,settheStartTimeto0:00:00andtheEndTimeto23:58:00.

  • 8/2/2019 Manual Ion Enterprise

    34/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 34 2007 Schneider Electric. All rights reserved.

    Setting Up Large SystemsApowermonitoringnetworkthatcontainsmanydevicesofthesametype(suchasaparticularbrandandmodelnumberofabranchcircuitmonitor)typicallyusesalogicalnamingschemeforthedevices. Forexample,youcanuseaschemelikeFL1_PNL1A.CCT01tonameadevicethatisinstalledonthe1stFloorofthe

    building,electricalpanel1A,andCircuitbreaker#1.

    Toperformbatchnetworksetupofdevices,createthefirstdeviceinManagementConsole(refertotheprevioussection,AddingaNetworkComponentonpage 27). Aftercreatingthisfirstdevice,youcanthenuseittocreatemultipleduplicatesandconfiguretheirproperities.

    NOTE

    Only users with Supervisor or Operator privileges can create and configure devices.

    Creating Multiple Copies of an Ethernet Device1. SelecttheDevicesiconontheSystemSetuppaneinManagementConsole.

    2. RightclickinthedisplaywindowandselectNew>EthernetDevice,thenconfigurethefirstEthernetdeviceusingyourlogicalnamingscheme. Forexample,clicktheGroupdropdownboxandselect[AddNewGroup],thenenterthegroupname(e.g.FL1_PNL1A)intheAddGroupbox. TypethedeviceName(e.g.CCT01),selecttheDeviceType,typetheIPaddress,thenclickOK.

    3. RightclicktheEthernetdeviceyouwanttoduplicateandselectDuplicateandConfigure.

    Scroll left Scroll right

    Table Editingarea

    Duplicate andConfigure area

    Hide/ShowColumns area

    Start & End spin box

  • 8/2/2019 Manual Ion Enterprise

    35/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 35

    TheDuplicateandConfigureareacontainsthesesections:

    ConfigureNames:Usethissectiontocreatetheduplicates.

    ConfigureTCP/IPAddresses:UsethissectiontocreateasequenceofIPaddressestoassigntotheduplicatesaftertheyhavebeencreated.

    ConfigureTCP/IPPort:Theportnumberusedintheoriginaldeviceis

    automatically

    assigned

    to

    all

    the

    duplicates.

    If

    required,

    you

    can

    use

    this

    sectiontoselectadifferentportnumberforallthedisplayeddevicesintheTableEditingarea(notethatchangesmadehereareappliedtoalldevices,includingtheoriginal).

    ConfigureUnitID:Thissectionisdisabledbydefault,sinceunitIDsdonotapplytotypicalEthernetdevices. (Toenablethissection,youmustfirstsetuptheTableEditingareasothattheUnitIDcolumnisshowing).

    4. IntheConfigureNamesarea,thedevicenameisdisplayedsuchthateachletterandnumberisselectable. Agroupofnumbersistreatedasasingleentity. Forexample,thenameMY8600isdisplayedsotheentitiesyoucanselectareM,Yand8600. Leadingzeroesarealsosupported,soyoucansetsequencessuchas01,02,03or001,002,003.

    5. Selectaletter

    or

    number

    in

    the

    device

    name.

    This

    action

    fills

    in

    the

    Start

    box

    with

    thatvalue,soyoucanstartsettingasequentialrange.

    Forexample,ifyouselectthefirst1fromtheexamplenamingschemeandsettheEndspinboxto2,twonameswillbegenerated(theoriginal,plusoneduplicate). IfyouselectaletterandsetitsStartvaluetoAandtheEndvaluetoC,threenameswillbegenerated(theoriginal,plustwoduplicates).

    Thetotalnumberofgeneratednamesistheproductofthefirstrangemultipliedbythenext,andsoonuntilthelastrange,asindicatedinthegraphicbelow.

    TheStartboxdisplaystheselectednumber/letter,whichisthestartvalue. Usetheupordownarrowinthespinboxtochangethestartvalue,orsimplytypeitinthebox.

    6. Click

    the

    up

    arrow

    on

    the

    End

    box

    to

    increase

    the

    range,

    or

    type

    the

    end

    value

    inthebox. Tocleartherangeandstartover,clickRemoveParameters.

    7. Tosetexceptionsforindividualvaluesorarangeofvalues,refertothesection,SettingExceptionstoGeneratedSequencesonpage 37.Exceptionsreducethenumberofnamescreated(i.e.totalgeneratednamesminustheexceptions).

    8. Whenyouarefinishedsettingtheexceptions,clickOKtoapplyyourchangesandclosethedialogbox.

    The total generated names is the product:[2 x 3 x 10] = 60

  • 8/2/2019 Manual Ion Enterprise

    36/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 36 2007 Schneider Electric. All rights reserved.

    9. ClickDuplicate. TheduplicateddevicesappearintheTableEditingarea.

    10. ScrolltotherightintheDuplicateandConfigureareaandrepeattheproceduretosettheIPaddressesfortheduplicateddevices.

    11. ClickConfiguretosetthevaluesforthedevices.

    Asterisks indicate pending changesthat have not yet been saved.

    Original device

    Text color is red if the number of itemsdoes not match the number of items inthe Table Editing area. If the numbersmatch, the text color is black.

    Duplicated devices are alwaysdisabled when they are added to

    Management Console

  • 8/2/2019 Manual Ion Enterprise

    37/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 37

    NOTE

    To discard your changes up until the last saved state, click Revert. You can also press CTRL+Z to undothe last action. To redo, the last action, press SHIFT+CTRL+Z. You can only undo your last action (one

    undo).

    12. ClickApplytosaveyourchangesandleavethewindowopentocontinueworking,orclickOKsaveyourchangesandreturntoManagementConsole,orclickCanceltodiscardyourchanges.Adialogpromptsyouiftherearepending(unsaved)changeswhenyouclickCancel. ClickYestodiscardthechangesandreturntoManagementConsole,orNotoreturntotheconfigurationwindowandcontinueediting.

    NOTE

    If inappropriate values (such as a device that is renamed with the same name as another existing device)

    are encountered, a message displays with error details. You cannot save the configuration changes until

    you have corrected the errors.

    Setting Exceptions to Generated SequencesTheExceptionsoptionappliestotheConfigureNamesandConfigureIPaddressessectionsonly.

    1. Tosetexceptionstotherangeofgeneratedvalues,clickEdit.

    Click this to editexceptions

  • 8/2/2019 Manual Ion Enterprise

    38/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 38 2007 Schneider Electric. All rights reserved.

    2. UsetheAddnumber(orAddcharacter)spinboxtosetavaluetoexcludefromtherangeyouhavespecified,thenclickAdd. Repeattosetadditionalvaluestoexclude. Tosetarangeofvaluestoexclude,selectAddnumberrange(orAddcharacterrange),thenusetheStartandEndspinboxestosettherangetoexclude. ClickAdd. Repeattosetadditionalrangesofvaluestoexclude.

    NOTE

    You cannot add the same number or letter to the list of exceptions more than once. If theAdd button isdisabled, check that the numbers or letters are not already included in the exceptions list near the top of

    the window.

    3. UsetheRemovenumber(orRemovecharacter)spinboxtoremovetheexceptionthatwassetforagivenvalue(i.e.putitbackinasanacceptablevalue).UsetheRemovenumberrange(orRemovecharacterrange)spinboxestoremovetheexceptionthatwassetforarangeofvalues.

    Creating Multiple Copies of a Serial Device1. CreateandconfigureaDirectSiteorEthernetGatewaySiteinManagement

    Console.

    2. SelecttheDevicesiconontheSystemSetuppaneinManagementConsole.

    3. RightclickinthedisplaywindowandselectNew>SerialDeviceonDirectSiteorNew > SerialDeviceonEthernetGatewaySite(asappropriate),thenconfigurethefirstserialdeviceusingyourlogicalnamingscheme.Forexample,clicktheGroupdropdownboxandselect[AddNewGroup],thenenterthegroupname(e.g.DS1_FL1)intheAddGroupbox. TypethedeviceName(e.g.P6200_01),selecttheDeviceType,typetheUnitID,selecttheSite,thenclickOK.

    4. Rightclick

    the

    new

    serial

    device

    and

    select

    Duplicate

    and

    Configure.

    TheDuplicateandConfigureareacontainsthesesections:

    ConfigureNames:Usethissectiontocreatetheduplicates.

    ConfigureUnitIDs:UsethissectiontocreateasequenceofunitIDstoassigntotheduplicatesaftertheyhavebeencreated.

    ConfigureSerialSites:Theserialsiteusedintheoriginaldeviceisautomaticallyassignedtoalltheduplicates. Ifrequired,youcanusethissectiontoselectadifferentserialsiteforallthedisplayeddevicesintheTableEditingarea(notethatchangesmadehereareappliedtoalldevices,includingtheoriginal).

    5. UsetheConfigureNamessectiontoduplicatetheserialdevice. Followthe

    procedureasdescribedintheprevioussection,CreatingMultipleCopiesofanEthernetDeviceonpage 34.

  • 8/2/2019 Manual Ion Enterprise

    39/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 39

    6. OntheConfigureUnitIDssection,settheUnitIDsoftheserialdevicesusingthepreviousprocedure.

    7. ClickApplyorOK.

    Creating Multiple Copies of an OPC Device

    1. CreateandconfigureanOPCSiteinManagementConsole.

    2. SelecttheDevicesiconontheSystemSetuppaneinManagementConsole.

    3. RightclickinthedisplaywindowandselectNew>OPCDevice,thenconfigurethefirstOPCdeviceusingyourlogicalnamingscheme. Mandatoryfieldsare:Group,Name,DeviceType,andSite.

    4. RightclickthenewOPCdeviceandselectDuplicateandConfigure.

    TheDuplicateandConfigureareacontainsthesesections:

    ConfigureNames:Usethissectiontocreatetheduplicates.

    ConfigureAddress:Usethissectiontocreateasequenceofaddressestoassigntotheduplicatesaftertheyhavebeencreated.

    ConfigureOPC

    Sites:TheOPCsiteusedintheoriginaldeviceis

    automaticallyassignedtoalltheduplicates. Ifrequired,youcanusethissectiontoselectadifferentOPCsiteforallthedisplayeddevicesintheTableEditingarea(notethatchangesmadehereareappliedtoalldevices,includingtheoriginal).

    5. UsetheConfigureNamessectiontoduplicatetheOPCdevice. Followtheprocedureasdescribedintheprevioussection,CreatingMultipleCopiesofanEthernetDeviceonpage 34.

  • 8/2/2019 Manual Ion Enterprise

    40/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 40 2007 Schneider Electric. All rights reserved.

    6. OntheConfigureAddresssection,settheaddressesoftheOPCdevicesusingthepreviousprocedure.

    7. ClickApplyorOK.

    Selecting Multiple Devices to ConfigureAfteryouhaveduplicatedthedevices,youcanselectandconfigureanyorallofthem.

    1. SelecttheDevicesiconontheSystemSetuppaneinManagementConsole.

    2. Selectthedevicesyouwanttoconfigure. Toselectacontiguousrange,clickthefirstdevice,holddowntheSHIFTkey,thenclickthelastdevice. Toselectanoncontiguousrange,holddowntheCTRLkeywhileclickingeachdevice.

    3. RightclickandselectConfigureSelectedDevices.Thisoptionisonlyavailableifmultipledevicesareselected.

    4. Usethedifferentsectionsinthewindowtomakeyourconfigurationchanges.Forexample: Withserialdevices,youcanusetheStartandEndspinboxesintheConfigureUnitIDssectiontoconfiguretherangeofunitIDs. ClickConfiguretoapplythechangestothedisplayeddevicesintheTableEditingarea(changesareappliedfromtoptobottom).

    TIP

    Configuration changes only affect the devices that are currently displayed in the Table Editing area. Usethe column sorting and filtering features, described in the next section, to control which devices aredisplayed in the table.

  • 8/2/2019 Manual Ion Enterprise

    41/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 41

    5. Repeatthepreviousconfigurationstepfortheotherpropertiesyouwanttochange. Forinstance,ifyouwanttoassignadifferentsiteforthedevices,selectthesiteintheConfigureSerialSitesection. ClickConfiguretoapplythechangestoalldisplayeddevicesintheTableEditingarea.

  • 8/2/2019 Manual Ion Enterprise

    42/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 42 2007 Schneider Electric. All rights reserved.

    NOTE

    Devices affected by a configuration change (that has not been saved) are identified by an asterisk in the

    first column of the Table Editing area.

    6. ClickApplytosaveyourchanges. Ifyouchangedthenameofoneormore

    devices,awarningdisplayswithalistofdevicesthatwillberenamed. IfdataforthosedevicesalreadyexistintheIONdatabaseandyoustillproceedwiththerenaming,thentheexistingdataassociatedwiththeolddevicenamewillbelost(orphaned). ClickContinuetoproceed,orCanceltogobackandeditthedeviceconfiguration.

    7. Whenyouhavefinishedmakingyourchanges,clickOKtosavethemandreturntoManagementConsole.

    Using the Table Editing AreaYoucancustomizethewaydataisdisplayedintheTableEditingarea. Whenmakingconfigurationchanges,thesechangesareappliedonlytotherowsthatarevisibleintheTableEditingarea.

    Column Sorting and FilteringClickacolumntosorttheinformationinthetableinascendingordescendingorder(indicatedbyanupordownarrow,respectively). Tocancelsortingandreturnthecolumntoitsdefaultstate,rightclickthecolumnandselectClear

    Sorting.

    Whenthemouseispositionedoveracolumn,theFiltericonappearsonthetoprightcornerofthecolumnheader. Clickittoselectandapplyafilterconditionto

    SortFilter

  • 8/2/2019 Manual Ion Enterprise

    43/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 43

    thedatainthatcolumn. Select(Custom)toapplyoneortwologicconditionstofilterthedata. Tocancelfilteringandreturnthecolumntoitsdefaultstate,rightclickthecolumnandselectClearFilter.

    NOTE

    When column filtering is on, changes done using the configuration editors on the top pane of the window

    affect only the devices that are visible in the Table Editing area. If you want to apply the changes to all

    devices, clear the filter first before making the changes.

    Adjust Column WidthTochangethewidthofacolumn,pointthemousetotherightedgeofthecolumnheader. Whentheresizehandle(doublearrowpointer)appears,clickanddragtoadjustthewidth. Releasethemousetosetit. Toadjustthewidthforbestfit,pointtotherightedgeofthecolumnheader,thendoubleclickwhentheresizehandleappears.

    Arrange ColumnsTochangetheorderofthecolumns,dragacolumnheadertotheleftorrightofitsoriginalposition,thenreleasethemousetosetitinplace.

    Group by ColumnTogroupdataaccordingtothecontentsofaparticularcolumn,dragthecolumnheadertotheareaaboveit(markedDragacolumnheaderheretogroupbythatcolumn). Expandorcollapsethegroupsbyclickingthe+orbutton. Toexpandorcollapseallgroups,rightclickthecolumnheaderandselectFullExpandorFullCollapse,respectively.

    Toungroup,dragthecolumnheaderbacktoitsoriginalposition(orrightclickthecolumnandselectUngroup).

    Using the Filter EditorTheFilterEditorisanadvanceddatafilteringtool. Touseit:

    1. RightclickacolumnheaderandselectFilterEditor.

    2. SpecifythefilterconditionsintheFilterBuilderwindow. Clickanelementtodisplaytheoptionsavailable,thenselecttheoptionyouwanttouse.

  • 8/2/2019 Manual Ion Enterprise

    44/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 44 2007 Schneider Electric. All rights reserved.

    Theelementsofthefilterbuilderare:

    3. Selecttheandtheyouwanttoapply. Typethetotestfor.

    4. Toadd

    another

    filter,

    click

    the

    +

    button

    on

    the

    top.

    5. Selectalogictoapplytothisnewfilter(inrelationshiptothecurrentlyselectedfilter).

    6. Toremoveafilter,clickthedelete(x)buttonbesideit.

    Inthenextexample,thefilterwillfindalldeviceswhosenamescontainFL1,andwhosetypesbeginwithION.

    Therowsreturnedareasfollows:

    Logic

    Click Edit Filter to configurethe filter conditions

    Select the box to turn the filter on; clear it to turn the filter off.Click the x to cancel and exit the filter mode

  • 8/2/2019 Manual Ion Enterprise

    45/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 45

    Edit, Copy and PasteSometimesdevicenamesdonotfollowanyparticularnamingpattern.Inthiscase,youcanusethecopy/pastefunctiontoapplyconfigurationchangesdirectlytotheTableEditingarea.

    Firstthing

    you

    need

    to

    do

    is

    add

    anew

    device

    in

    Management

    Console,

    then

    create

    asmanyduplicatesofthedeviceasthequantityofitemsyouarepasting.

    IfyouhaveaMicrosoftExcelspreadsheetthatcontainsalistofthesedevicestoaddtoManagementConsole,youcanusetheConfigureNamesareatocreateduplicatesofthatdevicetype,thenusetheTableEditingareatocopyandpastethedevicepropertiesfromtheExcelspreadsheet. Anexampleisshownbelow.

    Copy and Paste 20 Ethernet Devices from Excel

    1. MakesurethenamesintheExcelspreadsheetconformtothenamingconvention,[Group].[DeviceName].

    2. AddthefirstdeviceandsetupitspropertiesinManagementConsole. Youcan

    assignitasimpledevicenamesuchasA.B1sinceitwillbeoverwrittenwhenthevaluesarecopiedandpastedfromExcel. SettheEnabledpropertytoNo(thismakessurethatManagementConsoledoesnotattempttoconnectthedevice).

    3. ClickOKtoaddthedevice.

    4. RightclickthedeviceandselectDuplicateandConfigure.

    5. Selectthe1intheConfigureNamesbox,thenusetheEndspinboxtosetthevalueto20.

    6. OntheHide/ShowColumnsarea,clearallthenoneditablecolumns,i.e.hidethosethatcontaingrayedoutvalues. Alsohidethecolumnsyoudonotwanttopasteover.

    7. OntheExcelspreadsheet,arrangethecolumnssotheymatchtheorderofthecolumnsontheTableEditingarea. HideallcolumnsontheExcelspreadsheetexceptthosecorrespondingcolumnsontheTableEditingarea.

  • 8/2/2019 Manual Ion Enterprise

    46/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 46 2007 Schneider Electric. All rights reserved.

    8. SelectthecellsinExcelandcopythem(CTRL+C).

    9. OntheTableEditingarea,clickonthefirstcellundertheNamecolumntoselectit,thenpastethecontentsoftheclipboard(CTRL+V).

    10. ClickApplytosaveyourchanges,or clickOKsaveyourchangesandreturntoManagementConsole.

    Find and ReplaceUsetheFindandReplacefeaturetomodifymatchingcharactersinthedevicenamesorinanyothereditablecolumnsonthedevicetable. TheFindandReplacefeaturedoesnotworkonreadonlycolumns.

    1. RightclickthedevicetableandselectFindandReplace.

    2. TypethecharactersyouwanttosearchforintheFindbox. Donotusewildcardcharacters(*). Notethatthesearchiscasesensitive.

    3. Incolumnlistsallavailablecolumns. Selectthecolumnyouwanttosearchin.

    4. IntheReplacewithbox,typethecharactersyouwanttousetoreplacethe

    characters

    in

    theFind

    box.

    If

    you

    want

    to

    delete

    characters

    from

    a

    column

    value,

    leavetheReplacewithboxblank.

    5. ClickPreviewtolistthesearchresultsinthetable. TheReplacewithcolumndisplaysthenewnameorvalueresultingfromtheFindandReplaceoperation.

  • 8/2/2019 Manual Ion Enterprise

    47/339

    ION Enterprise 5.6 User Guide Chapter 2 - Management Console

    2007 Schneider Electric. All rights reserved. Page 47

    6. UsethecheckboxintheSelectcolumntoselecttherowsyouwanttochangevaluesfor. YoucanclickSelectAlltoselectalltheitems,orClearSelectedtoclearall.

    7. ClickApplytosaveyourchangesorCanceltodiscardyourchanges

    8. ClickOKtosaveyourchangesandclosetheFindandReplacedialog.

  • 8/2/2019 Manual Ion Enterprise

    48/339

    Chapter 2 - Management Console ION Enterprise 5.6 User Guide

    Page 48 2007 Schneider Electric. All rights reserved.

  • 8/2/2019 Manual Ion Enterprise

    49/339

    2007 Schneider Electric. All rights reserved. Page 49

    3 Management Console Tools

    ManagementConsoletoolsareadditionalprogramsthathelpyoumanageandmonitoryourIONEnterprisenetwork.

    In This Chapter

    Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    User Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51StartingUserManager ................................................ 51

    License Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    Diagnostic Viewer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54StartingDiagnosticViewer............................................. 54

    NavigationPanel ..................................................... 54

    DiagnosticsInformationPanel.......................................... 55

    UsingtheFilterEditor ................................................. 57

    ServerDiagnostics .................................................... 57

    CommunicationsDiagnostics .......................................... 59

    AdditionalCommands ................................................ 60

    CommunicationStatusvs.SiteStatus.................................... 62

    Device Upgrader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63UsingDeviceUpgrader................................................ 63

    FirmwareUpgradeErrorCodes ........................................ 65

    Remote Modem Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66UsingRemoteModemSetup ........................................... 66

    Virtual Processor Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68ConfiguringtheVirtualProcessorsModbusService....................... 68

    ModifyingtheGlobalParameters ....................................... 73

  • 8/2/2019 Manual Ion Enterprise

    50/339

    Chapter 3 - Management Console Tools ION Enterprise 5.6 User Guide

    Page 50 2007 Schneider Electric. All rights reserved.

    IntroductionThefollowingprogramsareavailableinIONEnterprise,andcanbestartedthroughtheManagementConsolesToolsmenu:

    DatabaseManagerhelpsyoumanageandmaintainyourdatabase;seeDatabaseManagementonpage 289

    UserManagerallowsyoutoconfigureIONEnterpriseuserloginnames,accesslevelsandpasswords

    LicenseManagerallowsyoutoupgradeyoursoftwarelicensetoprovideadditionaldevice,clientandsoftwaresupport

    Designerconfiguresdevicesandaddscustomfunctionalitytothem;seeDesigneronpage 195

    DiagnosticViewerprovidesdetailedrecordsofallsystemandnetworkeventsaswellascommunicationstatesandproblems

    DeviceUpgraderuploadsnewfirmwaretonetworkmetersordevices

    RemoteModemSetupconfiguresdialupmodemsthatwillbeusedatremotepowermanagementnetworks

    IONVirtualProcessorSetupconfigurestheIONVirtualProcessorServiceforuserprogrammedfunctionality

    ModbusDeviceImporterenablesModbusdevicestobeaddedtotheIONEnterprisenetwork;seeModbusDeviceImporteronpage 259

    Optional:UpdateOPCServerandPQDIFExporterarecommandsthatappearintheManagementConsole>ToolsmenuifthoseoptionsarepurchasedwithIONEnterprise(oractivatedlaterusingtheappropriateupgradesoftwarelicense).

  • 8/2/2019 Manual Ion Enterprise

    51/339

    ION Enterprise 5.6 User Guide Chapter 3 - Management Console Tools

    2007 Schneider Electric. All rights reserved. Page 51

    User ManagerUserswithsupervisorlevelaccesstoIONEnterprise(suchastheIONadministrator)canaddorremoveuserloginnamesandaddorchangepasswordsofdifferentaccesslevelsinUserManager.

    Starting User Manager1. StartManagementConsole.Loginusingausernamewithsupervisorlevel

    access.

    2. ClickTools>UserManager.

    Adding Users1. ClickAdd.

    2. TypethenewusernameandpasswordintheUsernameandPasswordboxes.Donotusespacesintheseboxes.TypethepasswordagainintheRetypePasswordbox.

    3. AssigntheappropriateAccessLevelaslistedinthetablebelow:

    Access Level

    Type of Operation Allowed for User1 View

    Only

    User

    Controller

    Operator

    Supervisor

    View Vista or Designer diagrams YES YES YES YES YES

    Acknowledge alarms YES YES YES YES

    Trigger events2 YES YES YES YES

    Connect/disconnect sites or devices YES YES YES

    Modify network configuration (using Management Console) YES YES

    Edit Vista or Designer diagrams YES

    Administer software security YES

    1. You can use Vista to set different access levels for the different control operations.

    2. Supervisors can trigger any event (waveform recording, etc), while Operators, Controllers and Users can only

    trigger some events (such as resets).

  • 8/2/2019 Manual Ion Enterprise

    52/339

    Chapter 3 - Management Console Tools ION Enterprise 5.6 User Guide

    Page 52 2007 Schneider Electric. All rights reserved.

    4. ClickAddUser.

    5. TypetheSupervisorpasswordwhenprompted.ClickOK.

    6. ClickOKattheprompttoaddtheuser.

    NOTE

    Keep a list of your ION Enterprise user accounts and their associated passwords in a safe place. Update

    the list as you add users, remove accounts, and change passwords, because you cannot recover a lost

    password (i.e. you will need to remove and re-add the user if this happens).

    DuringtheIONEnterprisesoftwareinstallation,twodefaultusernames(guestandsupervisor)werecreated,bothwithadefaultpasswordof0(zero).Boththeseusernameshavesupervisorlevelaccess,sothedefaultpasswordshouldbechangedforsecurityreasons.

    Changing the Password

    1. Select

    the

    user

    name

    associated

    with

    the

    password

    you

    want

    to

    change,

    then

    clickChangePassword.

    2. TypetheoldandnewpasswordintheOldPasswordandNewPasswordboxesrespectively,thentypethenewpasswordagainintheConfirmnewpassword

    box.ClickOK.

    3. ClickOKattheprompttoconfirmthepasswordchange.

    NOTE

    A users access level can only be set when it is added. To change the access level for the guest account,

    you must first remove it.

    Removing a UserTheexamplebelowshowshowtousethedefaultsupervisoraccounttodeletethedefaultguestaccount:

    1. Selectguest,thenclickRemove.

    2. TypetheSupervisorpasswordwhenprompted.ClickOK.

    3. Whenpromptedtoconfirmremovaloftheuser,clickYes.

    4. ClickOKattheprompttoremovetheuser.

    NOTEYou cannot remove the user account that you are currently using.

  • 8/2/2019 Manual Ion Enterprise

    53/339

    ION Enterprise 5.6 User Guide Chapter 3 - Management Console Tools

    2007 Schneider Electric. All rights reserved. Page 53

    License ManagerForadditionaldeviceorclientusersupport(e.g.VistaorReporterclients)foryourIONEnterprisesystem,ortoaddOPCand/orPQDIFoptions,ordertheappropriatelicensefromSchneiderElectric.

    Whenyoureceiveyournewlicense,useLicenseManagertoupgradethenumberofsupporteddevicesandclientusersinyoursystem:

    1. StartManagementConsole. Loginusingausernamewithsupervisorlevelaccess.

    2. ClickTools>LicenseManager.

    3. TypethenewproductkeyintheProductKeybox. ClickOK.

    WhenyourestartLicenseManager,theSystemInfosectionliststheupdatedsupportinformationfromthenewlyactivatedproductkey. Ifthenewkeysupportsadditionalfeaturesoroptions,thesearemadeavailableimmediately,withouthavingtorestartManagementConsole.

    The current product key number,number of devices in the system,and maximum number of devicessupported are listed here.

  • 8/2/2019 Manual Ion Enterprise

    54/339

    Chapter 3 - Management Console Tools ION Enterprise 5.6 User Guide

    Page 54 2007 Schneider Electric. All rights reserved.

    Diagnostic ViewerDiagnosticVieweristheIONEnterprisetoolfortroubleshootingnetworkcommunicationsproblemsandrelatednetworkerrors.

    Starting Diagnostic Viewer1. StartManagementConsole. Loginwithyourusernameandpassword.

    2. ClickTools>System>DiagnosticViewer.

    Navigation PanelThenavigationpaneldisplaysIONEnterprisediagnosticsinatreeviewformat.Clickthethe+toexpandthetree,ortocollapseit.

    Diagnosticsinformationisgroupedasfollows:

    ServerDiagnostics: ContainsdiagnosticsinformationfortheCommunicationsServerandLogInserterservice.

    CommunicationsDiagnostics: ContainsdiagnosticsinformationfortheIONEnterprisesites,hardwaredevicesandsoftwarenodes.

    Selectaniteminthenavigationpaneltodisplayitsdiagnosticsinformation.

    Dock or Hide PanelClickthePin/Unpinbuttononthethenavigationpaneltodock(show)orhideit.

    Whenthenavigationpanelishidden,itisminimizedtoabuttonnamedDiagnosticsontheleftsideofthewindow. YoucantemporarilydisplaythenavigationpanelbymovingthemouseovertheDiagnosticsbutton.

    Pin/Unpin buttonDiagnostics tabs

    Expand/collapsetree

    Diagnostics information panelNavigation panel

  • 8/2/2019 Manual Ion Enterprise

    55/339

    ION Enterprise 5.6 User Guide Chapter 3 - Management Console Tools

    2007 Schneider Electric. All rights reserved. Page 55

    Movethemouseawaytohidethepanelagain,orclickthePin/Unpinbuttonwhilethepanelisdisplayedtodockit.

    Diagnostics Information Panel

    Thediagnostics

    information

    panel

    displays

    detailed

    data

    about

    the

    state

    of

    your

    powermonitoringsystemanddevices.Thefollowingsectionexplainshowyoucanchangethewayinformationispresentedinthediagnosticsinformationpanel.

    Column Sorting and FilteringClickacolumntosorttheinformationinthetableinascendingordescendingorder(indicatedbyanupordownarrow,respectively). Tocancelsortingandreturntoitsdefaultstate,rightclickthecolumnandselectClearSorting.

    Whenthemouseispositionedoveracolumn,theFiltericonappearsonthetoprightcornerofthecolumnheader. Clickittoselectandapplyafilterconditiontothedatainthatcolumn. Select(Custom)toapplyoneortwologicconditionstofilterthedata. Tocancelfilteringandreturnthecolumntoitsdefaultstate,rightclickthecolumnandselectClearFilter.

    Adjust Column WidthTochangethewidthofacolumn,pointthemousetotherightedgeofthecolumnheader. Whentheresizehandle(doublearrowpointer)appears,clickanddragtoadjustthewidth. Releasethemousetosetit. Toadjustthewidthforbestfit,point

    tothe

    right

    edge

    of

    the

    column

    header,

    then

    double

    click

    when

    the

    resize

    handle

    appears.

    Arrange ColumnsTochangetheorderofthecolumns,dragacolumnheadertotheleftorrightofitsoriginalposition,thenreleasethemousetosetitinplace.

    Group by ColumnTogroupdataaccordingtothecontentsofaparticularcolumn,dragthecolumnheadertotheareaaboveit(markedDragacolumnheaderheretogroupbythat

    column).

    Expand

    or

    collapse

    the

    groups

    by

    clicking

    the

    +

    or

    button.

    To

    expandorcollapseallgroups,rightclickthecolumnheaderandselectFullExpandorFullCollapse,respectively.

    Sort

    Filter

  • 8/2/2019 Manual Ion Enterprise

    56/339

    Chapter 3 - Management Console Tools ION Enterprise 5.6 User Guide

    Page 56 2007 Schneider Electric. All rights reserved.

    Toungroup,dragthecolumnheaderbacktoitsoriginalposition(orrightclickthecolumnandselectUngroup).

    Column Shortcut Menu

    Rightclick

    the

    column

    to

    display

    the

    shortcut

    menu.

    It

    contains

    the

    functions

    describedearlier,plustheseadditionalfunctions:

    Group By Box

    Dragacolumnheaderontothisareaabovethecolumnheaders,togroupdataaccordingtodataappearinginthatcolumn.

    Column Chooser

    Thisallowsyoutosetwhichcolumnsareshowninthediagnosticsinfomationpanel. Touseit:

    1. RightclickthecolumnandselectColumnChooser. TheCustomization

    windowdisplays.

    2. DragacolumnheaderyouwanttohideanddropitintheCustomizationwindow. Repeatforothercolumnsyouwanttohide.

    3. Toshowthecolumnagain,simplydragthecolumnheaderanddropitbackinitsoriginalplace.

    Best Fit (all columns)

    Selectthistoadjustallcolumnwidthstothebestfit(i.e.withtheleastamountofwhitespace).

  • 8/2/2019 Manual Ion Enterprise

    57/339

    ION Enterprise 5.6 User Guide Chapter 3 - Management Console Tools

    2007 Schneider Electric. All rights reserved. Page 57

    Using the Filter EditorTheFilterEditorisanadvanceddatafilteringtool. Touseit:

    1. RightclickacolumnheaderandselectFilterEditor.

    2. SpecifythefilterconditionsintheFilterBuilderwindow. Clickanelementtodisplaytheoptionsavailable,thenselecttheoptionyouwanttouse.

    Theelementsofthefilterbuilderare:

    3. Selecttheandtheyouwanttoapply. Typethetotestfor.

    4. Toaddanotherfilter,clickthe+buttononthetop.

    5. Selectalogictoapplytothisnewfilter(inrelationshiptothecurrentlyselectedfilter).

    6. Repeatstep3.

    7. Toremoveafilter,clickthedelete(x)buttonbesideit.

    Server DiagnosticsServerdiagnosticsrecordscommunicationproblemsandsimilareventsoccurringfromIONEnterprisesoftwarecomponents.

    Communications Server DiagnosticsInformationaboutthecommunicationsserverisarrangedinthesetabs:

    ConsoleMessageslistsallNetworkRouterconsolemessagesforthecurrentsession.

    ConnectionStatusdisplaysthecurrentstatusofIONEnterprisesoftwarecomponentsconnectedtoNetworkRouter.

    TreeStatesdisplaysthestatusofallnodes(hardwaredevicesandsoftwarenodes).

    Logic

  • 8/2/2019 Manual Ion Enterprise

    58/339

    Chapter 3 - Management Console Tools ION Enterprise 5.6 User Guide

    Page 58 2007 Schneider Electric. All rights reserved.

    TIP

    The blank area below the Description column header is a dynamic text search field. Type the wildcardcharacter (*) in front of the text you want to search (for example, *warning). The information panelautomatically displays only those records that match the text you typed in the box.

    Log Inserter DiagnosticsTheLogInserterdiagnosticsinformationpanelissplitintotwosections. Thetoppanel(SelectNodes)containstheavailablenodes,whilethebottompanelcontainsthenodedetails.

    Resizing the Top and Bottom Panels

    Toresizethetopandbottompanels,pointthemouseattheborderwherethetwosectionsmeet. Whentheresizehandleappears,clickanddragthemouseupordowntomovethehorizontalborder. Releasethemousetosettheborder.

    Docking or Hiding the Select Nodes Panel

    Similartothenavigationpanel,youcanhidetheSelectNodespanelbyclickingitsPin/Unpinbutton. Whenthispanelishidden,itisminimizedtoabuttonnearthetopleftcorner,namedSelectNodes. PointthemousetothisbuttontotemporarilyshowtheSelectNodespanel.Movethemouseawaytohidethepanel

    again(orclickthePin/Unpinbuttonwhilethepanelisdisplayed,todockit).

    Select Nodes to Display

    IntheSelectNodespanel,selectthecheckboxbesideanodetodisplayitsdiagnosticsinformation. Clearthecheckboxtohidethatnodesdiagnosticsinformation.

    Iftherearemanynodes,andyouwanttodisplayonlyafewofthem,rightclickthecheckboxarea,thenselectClearAll. Selectthenodesyouwanttodisplay.

    Dynamic text search field

    Hidden navigation panel

    Check boxes

    Pin/Unpin button

    Resize handle

  • 8/2/2019 Manual Ion Enterprise

    59/339

    ION Enterprise 5.6 User Guide Chapter 3 - Management Console Tools

    2007 Schneider Electric. All rights reserved. Page 59

    Todisplayallthenodesagain,rightclickthecheckboxareaandselectSelectAll.

    Node Details

    Thenodedetailsareorganizedinthesetabs:

    NodeInformationdisplaysLogInserterstatisticsfortheselectednodes.

    NodePerformancedisplaysaggregatelogperformancestatisticsfortheselected

    nodes.

    LogPerformancedisplayslogperformancestatisticsforeachlogintheselectednodes.

    Maximizethewindowtoseemoreofthediagnosticstables. Scrollbarsautomaticallyappearwhenthereismoreinformationthancanfitinthewindow.

    Communications DiagnosticsCommunicationsDiagnosticsliststhesitesconnectedtotheworkstation. SiteOverviewsummarizesthediagnosticsinformationfromallsites.

    Site OverviewDiagnosticsinformationforthesitesarecontainedinthesetabs:

    SiteSummarydisplayscommunicationsstatisticsforeachsite.

    NetUserStatusdisplaysthenumberofIONprogramscurrentlyinthequeue(awaitingprocessing),andthetotalnumberofIONprogramsalreadyprocessed.

    NOTE

    Requests and responses transmitted between the ION Enterprise components are referred to as ION

    programs.

    Site/Device DiagnosticsDiagnosticsinformationforsitesandindividualdevicesaresummarizedinthesetabs:

    CommunicationStatusdisplayserrorratesandconnectionstatisticsfortheselecteddevice. ThefollowinginformationisavailablefromtheCommunicationsStatustab:

    Column Description

    Node The device (or software node) name.

    Requests The number of communications requests transmitted to the meter.

    Responses The number of successful responses received.

    Total Errors The total number of errors.

  • 8/2/2019 Manual Ion Enterprise

    60/339

    Chapter 3 - Management Console Tools ION Enterprise 5.6 User Guide

    Page 60 2007 Schneider Electric. All rights reserved.

    SiteStatusdisplayssitestatisticssuchasconnectionstatusandtotals.

    Polling

    Statusdisplays

    the

    number

    of

    programs

    currently

    in

    the

    queue

    (awaitingprocessing)andthetotalnumberofprogramsalreadyprocessed.

    Additional Commands

    Diagnostic DetailsOnthediagnosticsinformationpanel,doubleclickarowtodisplayitsDiagnosticDetailsscreen.

    Total Error Rate The ratio of Total Errors to Requests.

    Sliding Error Rate The error rate in the last 64 requests. This could indicate a trend in communications performance.

    Average Response Average time in seconds for the meter to respond.

    Last Response The last response time, in seconds.Timeouts The number of timeout errors. A timeout occurs when no data is received in response to a request.

    Bad Checksums The number of bad packets received, i.e. those that failed the error-detection checksum.

    Incomplete Frames The number of incomplete packets received, i.e. those that did not have all the expected bytes.

    Bad Frames The number of received packets that had an internal error.

    Broken Connections Number of times the connection was lost to the meters on a site.

    Hardware Errors Number of errors reported by the computers communication hardware.

    Misc Errors Number of other errors that do not fit any of the above descriptions.

    Column Description

    Double-click to displaymore details.

  • 8/2/2019 Manual Ion Enterprise

    61/339

    ION Enterprise 5.6 User Guide Chapter 3 - Management Console Tools

    2007 Schneider Electric. All rights reserved. Page 61

    UsethePreviousandNextbuttonstoviewthedetailsoftheotherdevicesonthatsite.

    Tocopyinformationtotheclipboard,clicktoselectit,thenpressCTRL+C.

    Update/Reset/Copy All/OptionsRightclickthediagnosticsinformationpaneltodisplaytheUpdate,Reset,CopyAll,andOptionscontextmenu.

    Thecommandsperformthefollowingfunctions:

    Refresh Tree ViewIfyouaddanewdeviceinManagementConsolewhileDiagnosticViewerisopen,youcanrefreshthetreeview(todisplaythenewdevice)bycollapsingthenexpandingtherootnodeofthetree(i.e.IONEnterpriseDiagnostics).

    Right-click Option Description

    Update Refreshes the information in the diagnostic table.

    Reset Resets the information in the diagnostic table.

    Copy All Copies all selected information to the clipboard.

    Auto Scroll

    Enabled by default, this Communications Server Diagnostics optionautomatically scrolls and selects the latest console message. Clear thisoption to disable scrolling (i.e. select and view an older console messagewithout jumping to the latest one when Diagnostic Viewer refreshes).

    OptionsDisplays the option to change the diagnostics refresh rate. Note thatchanging this value affects ION Enterprise performance.

  • 8/2/2019 Manual Ion Enterprise

    62/339

    Chapter 3 - Management Console Tools ION Enterprise 5.6 User Guide

    Page 62 2007 Schneider Electric. All rights reserved.

    Communication Status vs. Site StatusThissectionexplainsthedifferencebetweenthestatisticsprovidedontheCommunicationStatustabandthoseontheSiteStatustab.

    TotalErrorsintheCommunicationStatustabisanIONSiteServicederived

    statistic,while

    Bad

    Responses

    in

    the

    Site

    Status

    tab

    is

    aclient

    derived

    statistic.

    Toexplainthisdifference,considerasituationwhereadirectsiteisexperiencingtimeouts. Communicationswiththedevicewillbeattemptedaccordingtotwoparameters:ConnectAttempts(anadvancedsitepropertyintheManagementConsole)andMaximumAttemptsMultiple(anadvanceddevicepropertyintheManagementConsole). Multiplyingthevaluesofthesetwopropertieswilldeterminethenumberofattemptsmadetoreestablishcommunicationswiththedevice.

    Forinstance,ifConnectAttemptsissetto1andMaximumAttemptsMultipleissetto3,thedevicewillgoofflineafter3attempts(i.e.1x3).

    TheTotalErrorsstatisticincreasesbyoneeverytimeIONSiteServicedetectsatimeout. However,theBadResponsesstatisticonlyreportsaproblemifthedevicegoesoffline(i.e.whenConnectAttemptsandMaximumAttemptsMultipleareexceeded).

    Usingtheaboveexample,considerthecasewherefourtimeoutsoccurredandthedevicewentoffline. Inthiscase,TotalErrorswouldincreasebyfour,whileBadResponseswouldonlyincreasebyone. Ifonlytwotimeoutsoccurred,TotalErrorswouldincreasebytwo,whileBadResponseswouldnotchange.

  • 8/2/2019 Manual Ion Enterprise

    63/339

    ION Enterprise 5.6 User Guide Chapter 3 - Management Console Tools

    2007 Schneider Electric. All rights reserved. Page 63

    Device UpgraderUseDeviceUpgradertoupgradethefirmwareonasinglemeter,oronmultiplemetersofthesametype,inasinglesession. Supervisorlevelaccessisrequiredtoupgradedevices.

    NOTE

    To reduce the risk of upgrade errors, make sure the computer power option is set to always stay on and

    screensavers are disabled. If using a laptop, plug it into a wall outlet and set the power option to do

    nothing if the lid is closed.

    Ifyouhavedatainthemeteryouwanttokeep,makesureyousaveitbeforeupgrading. Storeddatainthemetersmemoryiscompletelyerasedduringafirmwareupgrade.Thisdataincludeswaveforms,datarecorders,minandmaxvalues,andintegratorvalues(e.g.kWh).

    Using Device Upgrader1. Obtaintheapplicableupgrade(.upg)filesforyourdevicefromyourTechnical

    SupportcontactatSchneiderElectric.

    2. Savethefilesinaneasilyaccessedfolderonthecomputer.

    3. StartManagementConsole.

    4. ClickTools>System>DeviceUpgrader. Afterreadingthetipsandwarningsabouttheupgradeoperation,clickOK.

  • 8/2/2019 Manual Ion Enterprise

    64/339

    Chapter 3 - Management Console Tools ION Enterprise 5.6 User Guide

    Page 64 2007 Schneider Electric. All rights reserved.

    5. TheDeviceUpgraderwindowdisplays.

    6. SelectyourdevicefromtheListDevicesofTypebox.

    7. IntheSelectRevisionsection,clickSelectFile. Locateandselecttheupgrade(.upg)filethatyousavedinstep2,thenclickOpen.

    8. SelectthedevicenameyouwanttoupgradeintheSelectDevicestoUpgradebox. Toselectmultipledevices,holddownCTRLwhileclickingeachdevice.

    9. TheSave/RestoreFrameworkcheckboxisselectedbydefault. Thiskeepsacopyofyourcurrentframeworktemplateduringtheupgrade.Afterthefirmwareupgradeiscomplete,DeviceUpgraderrestoresyourframeworktemplate.

    NOTE

    The Device Upgrader loads new meter firmware that does not contain any framework templates. If you

    want to preserve customizations you have made to your device framework, make sure Save/Restore

    framework is selected. However, if you intend to replace the existing meter framework with a new one

    (e.g. a new default meter template you downloaded), clear Save/Restore framework.

    10. Ifyouareupgradingmultipledevices,specifyintheFailureHandlingareahowtheDeviceUpgraderrespondstoanunsuccessfulupgrade:

    SelectHaltAfter,thenenteranumberintheboxtospecifyhowmanyattemptsDeviceUpgradershouldmakebeforestoppingduringafailedupgrade. Bydefault,theutilityissettostopafterthefirstfailedupgrade.

    SelectIgnoreAlltoattempttoupgradealloftheselecteddevicesregardlessofthenumberofdevicesthatfailtoupgrade.

    11. ClickUpgradetoupgradetheselecteddevices.

    TheUpgradeStatusboxshowsthestagesoftheupgradeprocess. Thecompletedprogressbarindicateswhatpercentageoftheupgradeiscomplete.EachcompletedupgradeislistedintheUpgradeStatusbox.

  • 8/2/2019 Manual Ion Enterprise

    65/339

    ION Enterprise 5.6 User Guide Chapter 3 - Management Console Tools

    2007 Schneider Electric. All rights reserved. Page 65

    Firmware Upgrade Error CodesThistabledescribesthevariouserrorcodesthatmayoccurwhenyouupgradeyourdevicesfirmware.

    Error Code Description

    0, 1, 2, 3, 4, 5, 6, 7, 8, or 9 Indicates a negative acknowledgment to a request. Contact Technical Services for assistance.

    100Device timed out while downloading firmware. Probable causes include: poor communication or thedevice stopped functioning.

    101, 102, 103, 104, 105 Indicates a bad response to a request. Contact Technical Services for assistance.