manual mj8 residential load calculation

87
Manual MJ8 Residential Load Calculation

Upload: moanna

Post on 23-Jan-2016

133 views

Category:

Documents


10 download

DESCRIPTION

Manual MJ8 Residential Load Calculation. Appendix 1 – Sections 1 thru 4. Three Levels of Expertise Section A1-5. Level 1: Those with Manual J, System Installation and HVAC Service Experience Level 2: Those with System Installation and HVAC Service Experience - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Manual  MJ8 Residential Load Calculation

Manual MJ8

Residential Load Calculation

Page 2: Manual  MJ8 Residential Load Calculation
Page 3: Manual  MJ8 Residential Load Calculation

Manual J seventh ed.

Manual J8

American National Standards Institute (ANSI) Standard

Manual J8AE

• Subset of MJ8

• Capabilities and sensitivities

Appendix 1 – Sections 1 thru 4

Page 4: Manual  MJ8 Residential Load Calculation

Three Levels of ExpertiseSection A1-5

• Level 1: Those with Manual J, System Installation

and HVAC Service Experience

• Level 2: Those with System Installation and HVAC

Service Experience

• Level 3: Those with NO Experience with

Calculations, System Installation or Service

Page 5: Manual  MJ8 Residential Load Calculation

Assignment(s)• Due next week: must have your text, CCAC

NetID, storage device, Green Building Project question sheet completed and the MJ8 Spreadsheet Instruction Sheet completed.

• Due in two weeks:

– Read Appendix 5

– Read Section 1

– Answers to questions on ‘Introduction Worksheet’

Page 6: Manual  MJ8 Residential Load Calculation

MJ8AE

Capabilities

and

Sensitivities

Appendix 2

Page 7: Manual  MJ8 Residential Load Calculation

• MJ8 provides both an introduction (MJ8AE – Part 1) and

advanced procedures (MJ8 – Part 2) to residential heat

loss and heat gain.

• Mastery of the introductory material is a prerequisite for

more advanced building designs.

• Mastery of the introductory material is a prerequisite for

using third party software products that perform Manual

J calculations.

• MJ8 assumes the practitioner is acquainted with the

basic principles of mathematics and heat transfer.

Page 8: Manual  MJ8 Residential Load Calculation

Limitations

and

Guidelines

Page 9: Manual  MJ8 Residential Load Calculation

System design plays an important role in the

comfort, health and safety of the occupants.

MJ8 may be used to estimate heat loss and

heat gain for residential applications that

have the following attributes.

Page 10: Manual  MJ8 Residential Load Calculation

• Cooling is provided by a central, single-zone, constant

volume system (MJ8AE shall not be used for zoned

systems).

• Single family detached dwellings shall have a normal

amount of fenestration (total area of windows, glass

doors and skylights shall not be more than 15 percent of

the floor area).

• Windows and glass doors shall be equitably distributed

around all sides of the dwelling.

• There shall be no large skylights in any room (skylight

load area does not exceed 5% of floor area).

Page 11: Manual  MJ8 Residential Load Calculation

• The dwelling shall have adequate exposure diversity

(see MJ8 Appendix 3).

• There shall be no excursion adjustment for the sensible

gain produced by the fenestration (see MJ8 Appendix 3).

• Windows and glass doors shall have clear glass;

skylights shall have a clear glazing.

• The dwelling shall have wood frame or block (concrete

or cinder) walls with brick, stucco or siding.

• The dwelling shall have a dark shingle roof.

Page 12: Manual  MJ8 Residential Load Calculation

• Attics shall be vented to FHA standards and shall have

no radiant barrier.

• Envelope leakage shall be estimated by the Table 5A air

change method (see MJ8, Section 3-10).

Page 13: Manual  MJ8 Residential Load Calculation
Page 14: Manual  MJ8 Residential Load Calculation

• Simple default values for the appliance load shall be

used to estimate internal gains.

• A duct system shall be entirely in the conditioned space,

or shall be compatible with one of the system scenarios

summarized by Figure 1-1 of MJ8 Section 1.

• Duct run leakage shall be equal to the default values (for

sealed ducts and unsealed ducts), unless verified by a

field leakage test (see MJ8, Section 3-12).

Page 15: Manual  MJ8 Residential Load Calculation
Page 16: Manual  MJ8 Residential Load Calculation

• Engineered ventilation can be provided by piping a small

amount (50 cfm or less) of fresh air to the return side of

the duct system (see MJ8, Section 3-13).

• Heating shall be provided by a hot air system or electric

baseboard heat.

Page 17: Manual  MJ8 Residential Load Calculation

Procedural

Defaults

Page 18: Manual  MJ8 Residential Load Calculation

Procedural complexity increases in proportion to sensitivity

to variations in construction detail. Defaults simplify the

procedure and make hand calculations possible. The

defaults that apply to MJ8ae are listed here.

Page 19: Manual  MJ8 Residential Load Calculation

Design

Conditions

Page 20: Manual  MJ8 Residential Load Calculation

INDOOR

• Heating = 70 F

• Cooling = 75 F and 50% RH, unless

superceded by code.

Page 21: Manual  MJ8 Residential Load Calculation

OUTDOOR

Use values in Table 1A of this guide, unless

superceded by code.

Page 22: Manual  MJ8 Residential Load Calculation
Page 23: Manual  MJ8 Residential Load Calculation

Windows

and

Glass Doors

Page 24: Manual  MJ8 Residential Load Calculation

• Window and glass doors shall have clear (single, double

or triple pane) glass.

• Window and glass door framing shall be metal, metal

with break, wood or vinyl.

• Windows can have fixed or operable sash (sliding glass

doors have an operable sash).

• Purpose built daylight windows and skylights shall have

no internal shade.

• All other windows and glass doors shall have internal

shade.

Page 25: Manual  MJ8 Residential Load Calculation

• The default assumption for internal shade is a medium

color blind with the slats at 45 degrees.

• Windows and glass doors shall not be equipped with

external sunscreens.

• An overhang adjustment shall be applied to all windows

and glass doors.

• When the information is available, use the actual

geometry or use the default geometry.

• The default length of the overhang is one foot; the

default height above the glazing is one foot.

Page 26: Manual  MJ8 Residential Load Calculation
Page 27: Manual  MJ8 Residential Load Calculation

• The heat gain adjustment for any type of bug screen

shall be 0.90.

• The heat loss and gain adjustment for a bay window

shall be 1.15.

• The heat loss adjustment for a garden window shall be

2.75 and the heat gain adjustment shall be 2.00.

• The heat gain adjustment for a French door shall be

0.70.

• The foreground reflectance for window and glass door

heat gain shall be 0.20.

Page 28: Manual  MJ8 Residential Load Calculation

Skylights

Page 29: Manual  MJ8 Residential Load Calculation

• Skylights glazing shall be flat.

• Skylights shall have clear (single pane or double pane)

glass.

• Curb construction shall default to (un-insulated) wood 2 x

4; four inches high.

• Skylights shall not be equipped with an internal shade.

• Skylights shall not be equipped with a light shaft.

Page 30: Manual  MJ8 Residential Load Calculation

Wood

and

Metal Doors

Page 31: Manual  MJ8 Residential Load Calculation

• Door glass area shall be ignored if the door glass area is

less than or equal to 50% of the total door area.

• The French door option shall apply if the door glass area

is more than 50% of the total door area.

Page 32: Manual  MJ8 Residential Load Calculation

Walls

Page 33: Manual  MJ8 Residential Load Calculation

• Above grade wall construction shall be wood stud frame

or empty core block.

• Exterior finish options shall be brick or stucco/siding.

• Interior finish shall default to gypsum board (i.e. plaster

board, dry wall, sheet rock, etc.)

• Below grade wall construction shall default to empty core

block.

• Block walls may have board insulation and/or wood stud

framing with blanket or fill insulation.

Page 34: Manual  MJ8 Residential Load Calculation

Ceilings

and

Attic Knee Walls

Page 35: Manual  MJ8 Residential Load Calculation

• The ceiling options shall be: attic, ceiling, ceiling on

exposed beams or joist ceiling sandwich.

• The roofing material shall be dark shingles.

• The roof deck material shall default to plywood for all

types of roof construction.

• Attic construction shall default to FHA-vented with no

radiant barrier.

• Knee walls shall be installed in a FHA-vented attic

space.

• Insulation shall be blanket and/or board or fill (as

appropriate for the type of roof construction).

Page 36: Manual  MJ8 Residential Load Calculation

Floors

Page 37: Manual  MJ8 Residential Load Calculation

• All floors shall be passive (no heating elements below

the floor).

• Floors over an open space shall have carpet or tile cover

with floor insulation options.

Floor joist

open crawl space

openings in wall

floor

Page 38: Manual  MJ8 Residential Load Calculation

• Slab floors shall have vertical insulation that covers the

edge, or no insulation.

• Slab floor soil conditions shall be heavy-moist; heavy-

dry; light-wet; or light-dry.

Slab floor

with insulation

to a depth of ?no insulation

soil conditions

footer

Page 39: Manual  MJ8 Residential Load Calculation

• Basement floors shall be un-insulated.

• Floors over a closed space shall default to no wall

insulation (for closed space), with floor insulation

options.

• Floors over a closed space shall default to construction

19A (Table 4A, MJ8)

Floor joist

closed crawl space

no openings in wall

floor

noinsulation

Page 40: Manual  MJ8 Residential Load Calculation

Infiltration

Page 41: Manual  MJ8 Residential Load Calculation

• All infiltration estimates shall be based on the ACH

values provided by Table 5A of this guide.

• Dwellings shall be rated: very-tight, semi-tight, average,

semi-loose and loose (definitions are provided).

• There shall be no space pressure adjustment for

engineered ventilation that affects space pressure.

• Infiltration induced or reduced by duct runs in an

unconditioned space is evaluated by the duct table

factors.

Page 42: Manual  MJ8 Residential Load Calculation

Internal

Gains

Page 43: Manual  MJ8 Residential Load Calculation

• The number occupants shall equal the number of

bedrooms plus one.

• The internal appliance gain options are 1,200 BTU/h or

2,400 BTU/h.

• The latent gain produced by plants shall be evaluated.

Page 44: Manual  MJ8 Residential Load Calculation

Duct

Systems

Page 45: Manual  MJ8 Residential Load Calculation

• All duct runs shall be in the conditioned space, or shall

conform to one of the Table 7 scenarios.

• Duct runs (trunks and runouts) shall be (essentially)

installed in one horizontal plane.

• Leakage rates for sealed ducts shall default to 0.12

(supply-side) and 0.24 (return-side) CFM per Ft2 unless a

tighter rating is justified by a duct leakage test.

• The supply air temperature for heating shall default to

100oF (worst case for the heating load factor).

Page 46: Manual  MJ8 Residential Load Calculation

Engineered

Ventilation

Page 47: Manual  MJ8 Residential Load Calculation

• Engineered ventilation is mandatory when required by

code (the ventilation rate also may be determined by

code).

• Table 8 shall be used to evaluate the fresh air

requirement (ventilation rate) when there is no code

requirement.

• Table 8 offers guidance with no expressed or implied

guarantee or warrantee; compliance is not mandatory.

Page 48: Manual  MJ8 Residential Load Calculation

• The system designer shall evaluate (by tests specified in

codes and standards) the potential for pressure

conditions that could cause combustion appliance back-

drafting.

• If the designer elects to provide engineered ventilation,

fresh air shall be provided by piping outdoor air to the

return-side of the duct system (refer to the unabridged

version of Manual J if the flow rate of outdoor air

exceeds 50 CFM).

Page 49: Manual  MJ8 Residential Load Calculation

Blower

Heat

Page 50: Manual  MJ8 Residential Load Calculation

• A blower heat adjustment shall be made when

manufacturer’s performance data is not discounted for

blower heat.

• The blower heat adjustment shall be 500 Watts (1,707

BTU/h).

Page 51: Manual  MJ8 Residential Load Calculation

Limitation

Page 52: Manual  MJ8 Residential Load Calculation

The principles and procedures presented in this

guide apply to any dwelling that is 100 percent

compatible with preceding list of limitations,

guidelines and defaults. The unabridged version of

Manual J shall be used for any and all dwellings that

are not compatible with the above list.

Page 53: Manual  MJ8 Residential Load Calculation

Application

Page 54: Manual  MJ8 Residential Load Calculation

A heat loss and heat gain estimate is the mandatory

first-step in the system design process. This

information is used to select heating and cooling

equipment. This information and the information

provided by equipment manufacturer performance

data is used to determine system airflow rate and

room airflow rates, supply outlet and return grille

sizes and duct sizes (per Manual S, D and T

protocols).

Page 55: Manual  MJ8 Residential Load Calculation

Appendix 4

You will be responsible for the following

paragraphs in Appendix 4:

2 – 6, 8 – 14, 17 – 19 and 29 – 31

Due in TWO WEEKS

Page 56: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

The basic formula for heat gain and loss calculations,

where:

• Q = Btu/h

• A = Area (see Section A4-2)

• U = Over-all-heat transfer coefficient (see Section A4-12)

• TD = Temperature Difference (see Section A4-17)

Page 57: Manual  MJ8 Residential Load Calculation

U = Transmission Coefficient

• Transmission coefficients (U values) are expressed in

Btuh/Sq Ft oF and are tabulated for common types of

construction.

• The U-value is calculated by computing the reciprocal of

the R-value.1

U = --------R

• So what is the R value?

Page 58: Manual  MJ8 Residential Load Calculation

• Resistance per Inch = the heat resistance performance

of one inch of material (see page 417)

• Thermal Resistance = specified when the thickness is

other than one inch (see page 417), so:

• Resistance = Resistance per inch x thickness

• Now go to Table A4-3 beginning on page 431:

– Check out the R-Value for 1a and 1b.

– Check out the R-value for 2d.

– Check out the R-value for 4b, and 4c.

– Check out the R-value for 5a and 5c.

– Check out the R-value for 8a.

Page 59: Manual  MJ8 Residential Load Calculation

Now let’s apply

Q = A x U x TD

Page 60: Manual  MJ8 Residential Load Calculation

How many Btu’s would be required to maintain 70oF inside a 1 ft. cube constructed from ½” plywood when it is 0oF outside?

Page 61: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

Page 62: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

Page 63: Manual  MJ8 Residential Load Calculation

1U = ------- = R

R = inside air film + outside air film + plywood

R = 0.68 + 0.17 + 0.62 =

1U = ----------- =

1.47

U = 0.68

Page 64: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

• Q = 6 Ft.2 x 0.68 x TD

Page 65: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

• Q = 6 Ft.2 x 0.68 x TD

• Q = 6 Ft.2 x 0.68 x 70

Page 66: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

• Q = 6 Ft.2 x 0.68 x TD

• Q = 6 Ft.2 x 0.68 x 70

• Q = 285 Btuh

Page 67: Manual  MJ8 Residential Load Calculation

How many Btu’s would be required to maintain 70oF inside a 1 ft. cube constructed from ½” plywood PLUS permeable felt when it is 0oF outside?

Page 68: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

Page 69: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

Page 70: Manual  MJ8 Residential Load Calculation

1U = ------ = R

R = 1.47 + 0.06

1U = ---------- =

1.53

U = 0.65

Page 71: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

• Q = 6 Ft.2 x 0.65 x TD

Page 72: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

• Q = 6 Ft.2 x 0.65 x TD

• Q = 6 Ft.2 x 0.65 x 70

Page 73: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

• Q = 6 Ft.2 x 0.65 x TD

• Q = 6 Ft.2 x 0.65 x 70

• Q = 273 Btuh

Page 74: Manual  MJ8 Residential Load Calculation

How many Btu’s would be required to maintain 70oF inside a 1 ft. cube constructed from ½” plywood, permeable felt PLUS extruded polystyrene when it is 0oF outside?

Page 75: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

Page 76: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

Page 77: Manual  MJ8 Residential Load Calculation

1U = ------ = R

R = 1.53 + 5.00

1U = ---------- =

6.53

U = 0.153

Page 78: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

• Q = 6 Ft.2 x 0.153 x TD

Page 79: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

• Q = 6 Ft.2 x 0.153 x TD

• Q = 6 Ft.2 x 0.153 x 70

Page 80: Manual  MJ8 Residential Load Calculation

Q = A x U x TD

• Q = A x U x TD

• Q = 6 Ft.2 x U x TD

• Q = 6 Ft.2 x 0.153 x TD

• Q = 6 Ft.2 x 0.153 x 70

• Q = 64 Btuh

Page 81: Manual  MJ8 Residential Load Calculation

Now go to Section A4 – 19 on page 424

HTM

Heat Transfer Multiplier

Page 82: Manual  MJ8 Residential Load Calculation

• Heat Transfer Multiplier is an acronym for heat flux.

• This multiplier represents the amount of heat that

flows through one square foot of a building

surface when exposed to a specific temperature

difference.

• Q = A x U x TD

HTM

Page 83: Manual  MJ8 Residential Load Calculation

• Go to page 61.

– Now go to the top left corner.

– To the right of the ACCA logo, you will see ‘Indoor db

Heating’ of 70 degrees.

– Drop down to row 6A – a and move your eyes to the

right to the column labeled ‘Heating HTM.’

– Move two more columns to your right labeled ‘Net

Area.’

– Take your calculator and multiply the ‘Area’ x ‘Heating

HTM’ x ‘Indoor db Heating’ and you should arrive at

the answer found in the column ‘Btuh Heating.’

Page 84: Manual  MJ8 Residential Load Calculation

Daily Range

• The daily range for a location is the average

difference between the daily high and low

temperatures.

• Go to Table 1 and look up Pittsburgh, PA daily

range.

Page 85: Manual  MJ8 Residential Load Calculation

Thus far we have:

– Assigned or completed section 1

– Assigned or completed Appendix 1

– Assigned or completed Appendix 2

– Assigned or completed Appendix 4

– Assigned or completed Appendix 5

Page 86: Manual  MJ8 Residential Load Calculation

• We are now going to move ahead with heat gain and

heat loss calculations using the examples in Sections 7,

8 and 9.

• We will use Sections 2 through 6 on an as needed basis.

Sections 2 through 6 actually set the stage for Sections

7, 8 and 9. I prefer going right to the worksheets and

apply the methods that lead up to Sections 7, 8 and 9.

Page 87: Manual  MJ8 Residential Load Calculation

SO,

onto the

first project