maquette1 magnetic circuit (core) instrument transformer u1u1 u2u2 secondary windings primary...
TRANSCRIPT
Maquette 1
Magnetic circuit (core)
Instrument Transformer
U1 U2
Secondary Windings
Primary Windings
Maquette 2
Instrument Transformer
I2
I1
Maquette 3
K : Transformation
ratio
PrimaryU1
Secondary
U2
Voltage Transformer :
Kn
n
U
U
2
1
2
1 1n
2n
Definition of an Instrument Transformer
Maquette 4
PrimaryI1
Secondary I2
Current Transformer :
Kn
n
I
I
I.nI.n
1
2
2
1
2211
Ampere-TurnsConservation
Law
1n
2n
Definition of an Instrument Transformer
K : Transformation
ratio
Maquette 5
K.Us
Instrument Transformer Error
Secondary
Primary
Up
Us
K
:Ratio error
Up (theoretically = k.US)
: Phase error
Voltage Transformer :Voltage Transformer :
s
p
U
Uk
Maquette 6
Secondary
PrimaryIp
Is
K
TC : K=Ip
Is
K.Is :Ratio error
Ip
: Phase error
Current transformer :Current transformer :
Instrument Transformer Error
Maquette 7
1. Oil filling plug
2. Dome
3. Nitrogen filling valve
4. Collar
5. Primary terminal
6. Porcelain insulator
7. Insulated primary
8. Cover plate for tank
9. Tank
10. Secondary cores
Internal details
Eye bolt design
Maquette 8
Manufacturing Process
IT range
Primary steel pipe
Paper insulation
Seconday cores
Maquette 9
Active Part Manufacturing
IT range
Maquette 10
1. Dome
2. Nitrogen filling valve
3. Primary terminal
4. Collar
5. Porcelain insulator
6. Primary conductor with insulation
7. Adaptor cylinder
8. Secondary cores
9. Base
10. Oil drain plug
Hair Pin Design
Hair-Pin design
IT 400 Cross section
Maquette 11
Class
e
Ratio error
at In
Phase
displacemen
t at In
Composite
error at
fL.IN
5 P 1 % 60 min. 5 %
10 P 3 % 10 %
Current TransformersProtection accuracy classes
CEI 600 44-1CEI 600 44-1
Accuracy classes (Protection)Accuracy classes (Protection)Maximum current error in % of IP
Accuracy limit primary current = fL.IN
Burden :SN
Maquette 12
Factors for Protection
Parameters
1. ALF ( accuracy limiting factor)
2. Composite error
Over Current and Earth Fault Protection
Maquette 13
Factors for Protection
1. Accuracy Limiting Factor
What is Accuracy Limiting factor ?
It is the factor of over current above the rated current which determines the capability of CT to maintain the error at such a condition.
2. Composite error
It is the error of the CT when this over current is applied.
Maquette 14
Composite error : Under steady-state conditions, the r.m.s. value of the difference between:a) the instantaneous values of the primary current, andb) the instantaneous values of the actual secondary current multiplied by the rated transformation ratio
CEI 600 44-1CEI 600 44-1
T
psnp
c dtiIKTI 0
2.1100
Current TransformersProtection accuracy classes
Kn is the rated transformation ratio;Ip is the r.m.s. value of the primary current;ip is the instantaneous value or the primary current;is is the instantaneous value of the secondary current;T is the duration of one cycle.
Maquette 15
Factors for Protection1. Accuracy Limiting Factor/composite error
For e.g if the class designation is 5P20
20 is the Accuracy limiting factor which signifies that when 20 times the rated primary current is applied the compositeerror of 5P( +/- 5%) is maintained.
Typical Class designations are
5P10, 5P20, 10P10, 10P20 etc.,
Maquette 16
Factors for Protection
Parameters
1. Knee Point Voltage requirement(Vk)
2. Exciting current ( Io)
3. Resistance of CT (Rct)
Transformer and Busbar Differential Protection
Maquette 17
Current TransformersSaturation curve
10 20 30 40
InductionB [T]
Primary currentIp/In
Protection CT
18500 gauss
Metering CT
8000 gauss
Maquette 18
Factors for Protection1. Knee Point Voltage(Vk):
Knee point voltage is point beyond which an application of 10% of voltage increases the exciting current by 50%.
The typical equations for Vk ( based on relay used)
Vk > 24 In (Rc t+2RL)- for Transformer Differential
Where In: Relay rated currentRL = Total lead ResistanceRc t = CT secondary resistance
Maquette 19
Current TransformersType Tests
IEC 600 44-1IEC 600 44-1
Type tests
a) short-time current tests
b) temperature rise test
c) lightning impulse test
d) switching impulse test
e) wet test for outdoor type transformers
f) determination of errors
Maquette 20
Current TransformerRoutine tests
CEI 600 44-1CEI 60-1
CEI 600 44-1CEI 60-1
Routine tests
The following tests apply to each individual transformers:
a) verification of terminal markings
b) power-frequency withstand test on primary winding
c) partial discharge measurement
d) power-frequency withstand test on secondary windings
e) power-frequency withstand tests, between sections
f) determination of errors
The order of the tests is not standardized, but determination of
errors shall be performed after the other tests.
Maquette 21
CT Failure and remedial action
Remedial actions in CT at site to avoid failures
• Tangent delta and Capacitance measurement from the C terminal at periodic intervals once in three years or during shutdown.
• Dissolved gas analysis of oil taken out from CT alteast once in five years.
• Thermo vision scanning of CTs of rating 400kV ( or above).
Maquette 22
Partial discharge test COMPARISON OF EXISTING AND NEW METHOD OF PARTIAL
DISCHARGE MEASUREMENTSL STANDARD PRE STRESS VOLTAGE PD MEASURING LIMITS NO VOLTAGE OF PD
1 EXISTING STANDARD 0.8*1.3*Um For One Minute 1.1Um/sqrt3 <10pCIS:2705 eg 151kV for 132kV system 92 kv for 132kV
2 NEW STANDARD 80% of Power frequency 1.2Um/Sqrt3 <5pCIEC 60044-1 voltage for one minute 100.5kVCl 5.1.2.2 & 8.2.2.2 220kV for 132kV system Um = 145kV <10pC
Where Um is the Highest system voltage of the CT.
Maquette 23
Multiple Chopped Impulse test
Application of 100 chopped impulses of negative polarity on CTs of ratings above 300kV. These impulses will be applied at the rate of one impulse per minute. The test Voltage shall be 60% of the rated lightning impulse voltage
Before the test and three days after the test the dissolvedgas analysis of oil taken from CT will be carried out.Analysisprocedure and fault diagnosis shall be as per IEC 60599.
As per IEC 60044-1 ( 2002)
Maquette 24
Special test
A. Thermal Stability test : This involves simultaneous application of rated voltage (1.1Um/Sqrt3) and rated simultaneous current (1.2,1.5 etc) by using a synthetic test circuit.Capacitance, tangent delta, secondary resistance and temperature of primary terminal are recorded until stable values are acquired.
This test demonstrates the insulation capacity ( healthiness)under energised conditions.
Maquette 25
Special test
B. Temperature coefficient test: The CT is heated in a oven to approximately 90Deg C. The tan delta is measured at ambient, 80 and 90 deg C at voltages of 0.3,0.7,1.0 and 1.1Um/Sqrt3.
This test demonstrates the healthiness at high extreme temperature conditions.
Maquette 26
Accurate Measurement of HV
Capacitor Voltage Transformers Coupling Capacitors CCV / CC 72.5 to 765 kV Line protection HF transmission Compliance with IEC, ANSI or equivalent
standards Reduce the slope of the RRRV (Rate of
Rise of Recovery Voltage (Ik >40 kA)
Maquette 27
Capacitor Voltage TransformerDefinitions
Element Pack(or pack)
Element Pack(or pack)
Pile of elements : ± 10 to 25 kV
Maquette 28
Capacitor Voltage TransformerDefinitions
Assembly of elements in an insulating container: ± 245 kV.Can be connected to a HV line
Capacitor Unit(or unit)
Capacitor Unit(or unit)
HV Power line
Ground
Maquette 29
Capacitor Voltage TransformerDefinitions
Capacitor STACK(or stack)
Capacitor STACK(or stack)
Assembly of elements to reach higher voltage levels : ± 800 kV
HV Power line
Ground
In general, the termCAPACITOR
stands for a capacitor elementas well as a capacitor stack.
Maquette 30
Capacitor Voltage Divider( or CVT )
Capacitor Voltage Divider( or CVT )
Connecting an MV inductive voltage transformer to a tap.
HV Power line
Ground
Maquette 31
IntermediateVoltage :
10 to 20 kV/3
S1
S2
P1
P2
C1
C2
Maquette 32
Lµ = Inductance equivalent to magnetic losses of the magnetic circuit.
Rw = Resistance equivalent to the watt losses of the magnetic circuit.
Lfs = Secondary leakage inductance of the magnetic VT.
Rs = Resistance of the secondary winding
Ce La LfsRa Rs
Lμ Rw ZcUsU’P =Vp . C1
k . (C1+C2)
Equivalent DiagramEquivalent Diagram
Maquette 33
Capacitor stack
Inductive VT
Maquette 34
CCV 72.5 to 765 kV
Capacitor elements
Capacitor column
Insulating oil
Insulator flange
Secondary terminal box
Inductance
MV Transformer
Oil expansion device
Damping circuit
Maquette 35
Capacitor Voltage Transformer Capacitor Elements
All Paper Dielectric design Mixed dielectric design
Paper PPR film + paper
Copper tabs forconnection
Aluminum foilfolded for contactwith next element
Maquette 36
ExcessiveFrequencyVariations
Nominal burdenOVER-ESTIMATEDReal load < 25% VAN
Nominal burdenUNDER-ESTIMATEDReal load > 100% VAN
Capacitor Voltage TransformerTypical Error Curve
Typical graph of variation of errors with VA & frequencyTypical graph of variation of errors with VA & frequency
Phase error
Ratio error
f
25% VA
f+f
f -f100% VA
+20’- 20’
+0.5
- 0.5
Maquette 37
Voltage transformersProtection accuracy classesIEC 600 44-2IEC 600 44-2
Accuracy classes (Protection)Maximum error in % of VP
- Voltage between 5 % and fT x VNP
- Burden between 25% and 100% of SN
- Maximum error doubled for VNP=2%
Accuracyclass
Voltage(ratio)error
Phasedisplacement[minutes]
Cl 3P 3 % 120
Cl 6P 6 % 24O