massachusetts plumbers continuing education servicesmpcesonline.com/files/40236407.pdfo 248 cmr 4.03...

96
Massachusetts Plumbers Continuing Education Services 781-686-4788 Massachusetts Plumbers Continuing Education Services Your one stop continuing Education Provider Continuing Education at it’s best Classroom www.mpces.net Online www.mpcesonline.com May 1, 2010 – April 30, 2012 Session III Instructors: David Brogan John Macdonald [email protected] [email protected]

Upload: others

Post on 27-Jan-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

  • Massachusetts Plumbers Continuing Education Services

    781-686-4788

    Massachusetts Plumbers Continuing Education Services Your one stop continuing Education Provider

    Continuing Education at it’s best

    Classroom www.mpces.net

    Online

    www.mpcesonline.com

    May 1, 2010 – April 30, 2012

    Session III

    Instructors: David Brogan John Macdonald [email protected] [email protected]

    http://www.mpces.net/http://www.mpcesonline.com/mailto:[email protected]:[email protected]

  • Massachusetts

    Plumbers Continuing Education Services

    1-781-686-4788

    Massachusetts Plumbers Continuing Education Services

    This continuing education course material has been approved by the Massachusetts State Board of Plumbers and Gasfitters

    By approval of this course material, the Board does not assume any responsibility for the accuracy of the contents.

    This course material is not being published by nor is a publication of the Board

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text1

  • Home UserTypewritten Text2

  • Massachusetts Plumbing Continuing Education Services

    Massachusetts Plumbers Continuing Education Services

    Session III

    Introductions Section 11 Updates

    1099 Board Policy

    Requirements for Inspections

    CSST Update

    Air for Combustion and Ventilation

    Furnace Plenums & Air Ducts

    Requirements for Elevated Gas

    How to cross reference Section

    248 CMR 5.0 Mass modifications Gas Pipe Sizing

    Residential Sidewall Venting

    Decorative Appliances

    Vent free Requirements

    MGL Chapter 148 25E Restrictions on Piloted

    Appliances

    Home UserTypewritten Text3

  • DEVAL L. PATRICK GOVERNOR

    TIMOTHY P. MURRAY LIEUTENANT GOVERNOR

    DANIEL O'CONNELL

    SECRETARY OF HOUSING AND ECONOMIC DEVELOPMENT

    Commonwealth of Massachusetts

    Division of Professional Licensure Board of Examiners of Plumbers and Gasfitters

    239 Causeway Street Boston Massachusetts 02114

    DANIEL C. CRANE

    DIRECTOR, OFFICE OF CONSUMER AFFAIRS & BUSINESS

    REGULATION

    GEORGE K. WEBER DIRECTOR, DIVISION OF

    PROFESSIONAL LICENSURE

    TELEPHONE: 617 727-9952 FAX: 617 727-1944 TTY/TDD: 617.727.2099 http://www.mass.gov/dpl

    MAY 1, 2010- APRIL 30, 2011 CONTINUING EDUCATION

    ADMINISTRATIVE & GAS CURRICULUM – 3 HOURS Suggested times listed are being provided as a guideline only

    - Introductions 5 min - Section 11 update highlighting revisions

    o Enforcement of CE requirements for license renewal 15 min - 1099 Board Policy explanation (provide handout) 10 min - Changes in the Plumbing & Gas permit applications 5 min - Requirements for Inspection

    o Emergency Installations - 248 CMR 4.03 Rule 3 248 CMR 3.05 (1) (a) 6. a, b & c

    o Notification - 248 CMR 3.05 (3) (d) 1, 2 & 3 Page 19 o Covering of Work - 248 CMR 3.05 (3) (f) 1 & 2 15 min

    - CSST update – bonding requirements & Counterstrike (provide handout) 5 min - Hood Interlock for Commercial Kitchens – Revised Diagram (provide handout) 15 min - Air for Combustion and Ventilation NFPA54-2002

    o 8.3.1 General Requirements o 8.3.2 Indoor Combustion Air o 8.3.3 Outdoor Combustion Air o 8.3.4 Combination Indoor & Outdoor Air 15 min

    - Furnace Plenums & Air Ducts NFPA54-2002 - 9.10.5 Circulating Air 5 min - Requirements for Elevated Gas (Handout Special Permission Application)

    o 248 CMR 4.03 Rule 1 o 248 CMR 3.04.3 Special Permission o 248 CMR 5.02 (2) Modifications to NFPA54 Chapter 1 o 248 CMR 5.03 (3) Modifications to NFPA54 Chapter 3 o 248 CMR 7.03 (1) Pertains to items listed on application only 15 min

    - How to cross reference 248 CMR 5.00 and 7.00 with NFPA54 5 min - Gas Pipe Sizing Methods – NFPA54 12.1

    o 12.1.1 Longest Length Method (Include sizing worksheet) Annex C – C.3.1

    o 12.1.2 Branch Method Sizing (Include sizing worksheet) Annex C – C.3.2 30 min

    - Residential Sidewall Venting Requirements 248 CMR 5.08 2 10 min - Decorative Appliances 248 CMR - 5.07 (3) NFPA54 – 3.3.61 5 min - Vent Free Requirements 248 CMR – 5.07 (12) 5 min - MGL Chapter 148 25e – Restrictions on Piloted Appliances 15 min

    Home UserTypewritten Text4

  • Massachusetts Plumbing Continuing Education Services

    Massachusetts Plumbers Continuing Education Services

    Session III

    Section 11 Revisions

    Home UserTypewritten Text5

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    11.04: Mandatory Continuing Education (MCE) Requirements for Master and Journeymen Plumbers, Master and Journeyman Gasfitters and for Undiluted Liquefied Petroleum Gas Installers.

    (1) General Continuing Education Provisions.

    (a) Effective for all licenses expiring on or after April 30, 2010, Commonwealth of Massachusetts licensed plumbers, gasfitters, and undiluted liquefied petroleum gas installers, shall during every two year license cycle complete a course of continuing education without repetition. Apprentices shall not be required to complete continuing education.

    (b) Continuing education policies, procedures, course content, and providers are subject to Board approval and must adhere to Board rules, regulations and policies. Continuing education courses shall focus on the Rules and Regulations of 248 CMR 3.00 through 11.00. In addition, the Board may approve continuing education courses that may include industry related business, law, technology or other subject matters.

    (2) Requirements for License Renewal.

    (a) Except as otherwise permitted in 248 CMR 11.00, each journeyman and master plumber, journeyman and master gasfitter ,or undiluted liquefied petroleum gas installer shall, as a condition of license renewal, complete the following as applicable:

    1. 12-clock hours of approved continuing education courses for plumbers with an approved provider; and

    2. six-clock hours of approved continuing education courses for gasfitters or undiluted liquefied petroleum gas installers with an approved provider

    (b) Each licensee shall retain all Mandatory Continuing Education documentation for no less than three renewal cycles and shall furnish this documentation to the Board for verification of completion of the Continuing Education requirements if requested by the Board.

    (c) Online and correspondence courses.

    1. Licensees shall only be allowed to take Board approved online or correspondence courses. The Board may deny the right to take online or correspondence courses to individuals whose licenses have lapsed or have been subject to discipline.

    2. The Board may impose additional requirements on Board approved online or correspondence courses, these requirements may include successfully completing an examination.

    (d) It shall be the licensee's responsibility to ensure that their Provider has been authorized by the Board.

    (3) Licensee Qualifications for Exemption of the (MCE) Mandatory Continuing Education Requirement.

    (a) A licensee shall be exempt from completing mandatory continuing education requirements if one of the following applies prior to the end of the renewal cycle unless otherwise specified:

    1. The licensee, as an approved instructor, has taught all courses which, without duplication, would fulfill their continuing education requirement for that renewal cycle;

    Home UserTypewritten Text6

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    2. The licensee is a qualified and duly appointed Inspector, Assistant Inspector or Alternate Inspector of Plumbing and/or Gasfitting appointed pursuant to M.G.L. c. 142, § 11b and has successfully completed the continuing education requirements of M.G.L. c. 142, § 11;

    3. The licensee is a State Inspector/Investigator or is the Executive Director or Associate Executive Director for the Board of Examiners or Plumbers and Gasfitters and employed by the Commonwealth of Massachusetts Division of Professional Licensure (DPL);

    4. The licensee is an appointed member of the Board of Examiners of Plumbers and Gasfitters;

    5. The licensee was issued their license for the first time during the current renewal cycle. However, this exemption shall not relieve a journeyman plumber or gas fitter from the continuing education requirement during a renewal cycle in which they obtain a master’s license.

    6. A Licensee who has appropriately petitioned the Board will be eligible for an exemption from the continuing education requirement starting the first full renewal cycle after the Licensee has attained 65 years of age. The Licensee shall still be responsible for completing continuing education in the renewal cycle in which they turn 65.

    (b) Waivers for Other Good Cause.

    1. The Board or Board authorized designee may consider the granting of a waiver of the mandatory continuing education requirements for other good cause shown. The waiver request shall be in writing and shall be accompanied by other supporting documentation that the licensee desires the Board to consider before ruling on the waiver request

    2. Illness or Disability of the Licensee or Immediate Family Member. A request for a waiver based on illness, disability, or other medically-related condition shall be in writing and accompanied by a letter addressed to the Board written and signed by a licensed medical physician stating the nature of the licensee's or the immediate family member's medical condition and the correlation between that condition and circumstance and the licensee's inability to complete the required continuing education within the required period.

    3. Unless the Board finds good cause for failing to do so, all requests for waiver of continuing education must be submitted prior to the expiration of the renewal cycle in which said education must be complete.

    (4) Failure by a Licensee to Complete (MCE) Mandatory Continuing Education Requirement.

    (a) Any licensee who does not complete the required clock hours of continuing education within the license renewal cycle shall be responsible for completing makeup classes covering the Board approved material for the continuing education missed.

    (b) In addition to any makeup classes, all licensees who fail to complete continuing education requirements for any renewal cycle shall be subject to Board review and disciplinary action that may include, but not be limited to the issuance of fines, denial of a request for renewal, re-examination, suspension or revocation of existing licenses, and denial of applications for additional licenses. The Board is under no obligation to warn a licensee of non-compliance with continuing education requirements prior to commencing disciplinary action, however, said action shall be subject to any hearings required by law.

    Home UserTypewritten Text7

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    (5) Reinstatement of lapsed/expired/suspended licenses.

    (a) Licensees who have failed to renew their licenses must fill out any applications required by the Board and must pay any back or late fees prior to board consideration.

    (b) Licensees whose licenses have lapsed/expired must meet the following additional requirements for reinstating their licenses:

    1. If expired for four years or less, licensees must complete all continuing education hours prior to applying to reinstate their license.

    2. If expired for more than four years, licensees must complete the continuing education hours for the current renewal cycle and pass the full Board examination for their license prior to being reinstated. However, Licensees shall not be required to take the examination if they completed all Board required continuing education requirements for each two year cycle during the period in which their license was expired.

    3. Without special Board approval, no waivers of continuing education granted under any other section of these regulations shall apply for purposes of reinstating a lapsed or expired license.

    (c) Unless a decision or consent agreement explicitly states otherwise, licensees who are suspended must complete all continuing education in order to qualify for reinstating their licenses.

    (d) This section shall not be deemed to sanction unlicensed practice. An individual practicing with an expired or suspended license may face disciplinary action up to and including revocation of the right to renew that license.

    (6) Initial Certificate and Documentation of Completion of (MCE) Mandatory Continuing Education Requirements.

    (a) Upon the successful completion of the clock hours of continuing education each licensee shall receive from his or her board approved continuing education provider a certificate of completion.

    (b) Each licensee shall retain such documentation for three renewal cycles and shall furnish it to the Board for verification of completion of the mandatory continuing education requirements if so requested. Failure to provide proof of required documentation may result in non-renewal of a license or other disciplinary action by the Board.

    (7) Duplicate (MCE) Mandatory Continuing Education Certificate.

    (a) Any licensee whose certificate of completion has been lost or destroyed shall obtain a duplicate certificate from the original provider by forwarding a written request including the reason(s) for the duplicate and any fee required by the Provider.

    (b) It shall be the responsibility of the licensee to make available all certificates to the Board if requested by the Board.

    (8) Falsification of Information or Fraudulent Transfer of Mandatory Continuing Education Certificates of Completion. The falsification of any Mandatory Continuing Education or the transfer of a certificate of completion of continuing education to any individual in order to meet Mandatory Continuing Education license renewal requirements shall be grounds for the initiation of formal disciplinary proceedings against the licensees found to

    Home UserTypewritten Text8

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    have engaged in such misconduct, up to and including suspension or revocation of any license(s) issued by the Board.

    11.05: Qualifications and Requirements for Mandatory Continuing Education Providers and Instructors

    (1) Qualifications and Requirements for Mandatory Continuing Education Providers.

    (a) A Provider of Mandatory Continuing Education seminars or courses may include:

    1. vocational schools;

    2. association-sponsored programs;

    3. labor training programs;

    4. employer training programs;

    5. private program.

    (b) All Providers seeking Board approval to conduct programs for Mandatory Continuing Education shall meet the following requirements:

    1. Complete and submit the Provider Application Form.

    2. Complete and submit the Provider Agreement Form which shall be accompanied by the appropriate application fee.

    3. Provide a detailed outline and lesson plan of each course of study offered, and the names and license numbers of all instructors annually.

    4. Proof of liability insurance satisfactory to the Board shall be provided annually.

    5. The applicant Provider shall provide a copy of an indemnification bond in such form and amount as shall be required by the Board annually.

    6. Providers may need to meet additional requirements, as specified by the Board, to offer online or correspondence courses.

    (c) The Board may withdraw without notice at any time its approval as issued to any Provider or issued for any program, course or instructor who, in the Board's opinion and in its sole discretion, no longer meets the requirements for approval established by the Board.

    (2) Instructor Qualifications to Conduct (MCE) Mandatory Continuing Education Courses.

    (a) Provider instructors shall be approved by the Board and must hold the requisite Board issued license, in good standing, before being authorized to serve as an instructor for any Mandatory Continuing Education course.

    (b) Each Provider shall notify the Board in writing of any change of instructors for any course within ten days of the change.

    Home UserTypewritten Text9

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    (c) Instructors of plumbing courses must have a master plumbers license.

    (d) Instructors of gas-fitting courses must have either a master plumber or master gas fitters license.

    (e) Instructors of undiluted liquefied petroleum gas courses must have a master plumbers license, a master gas-fitters license, or a undiluted liquefied petroleum gas installers license accompanied by evidence of two years work experience.

    (f) Subject to proper disclosure to the Division of Professional Licensure and to the Board, an agent or employee of the Division of Professional Licensure who would otherwise qualify as an instructor under this section may serve, when not on duty, as an instructor for a continuing education course put on by a private or non-profit entity. Such an individual may only serve as such an instructor so long as they take no part in any Board function regarding policies, procedures, approvals, or other official actions which would create a conflict of interest pursuant to relevant public ethics laws.

    (g) The Board may approve other individuals who would not otherwise qualify as instructors of Mandatory Continuing Education courses where those individuals have a demonstrated competency in subject areas applicable to the plumbing and gas-fitting industry which is substantially equivalent to that held by normally qualified Board approved instructors. Additionally, the Board may approve individuals who possess specialized knowledge relating to the subject being taught.

    (3) Mandatory Continuing Education Record Keeping Requirements.

    (a) Mandatory Continuing Education Records. All authorized Providers shall maintain for a period of no less than three license renewal cycles complete and accurate records for each licensee to whom the provider has issued a Certificate of Completion of Continuing Education. In addition, records of class attendance shall be submitted to the Board electronically at the completion of each renewal cycle or when the provider ceases to provide continuing education courses.

    (b) Mandatory Continuing Education Certificates of Completion. A Certificate of Completion of Mandatory Continuing Education Seminar Course record shall at minimum include all of the following information:

    1. Three digit Provider number as issued by the Board.

    2. Instructor's name and license number.

    3. Instructor's actual or electronic signature signed under pains and penalties of perjury.

    4. Course date and location (city or town)

    5. Classroom clock hours of instruction and course subject matter.

    6. Attendee name, his or her license number and designation.

    (c) Providers shall possess and maintain electronic technology acceptable to the Board.

    (d) Each approved Providers shall, at its own expense and in a format approved by the Board, electronically transmit to the Board or its designee certification of each licensee's completion of the continuing education course within five

    Home UserTypewritten Text10

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    working days of the completion date of the course. The certification shall contain the following data and information:

    1. Names and license number(s) of all licensees attending the continuing education course.

    2. Date of the course.

    (e) The Board may charge course providers a fee to recover costs for software and for training Providers in the use of that software.

    (f) All records maintained by the provider shall be made available to the Board or its designee within ten days upon request.

    (g) Each provider shall be responsible for the security of any Board issued provider numbers and authorization certificates in accordance with 248 CMR 11.00.

    (h) Falsification of any information relating to Mandatory Continuing Education requirements by the Provider shall result in the revocation of any approval provided by the Board to any Provider engaging in such misconduct. In addition, the Board may initiate any other legal action it deems appropriate in the circumstances, including but not limited to criminal prosecution. Any licensee(s) participating in such misconduct shall be the subject of formal disciplinary proceedings, including but not limited to both administrative and criminal proceedings.

    (4) Providers shall offer continuing education courses in any of the following formats:

    (a) No more than six hours of classroom instruction may be presented in one day per instructor.

    (b) No less than three hours of classroom instruction presented in one day per instructor.

    (c) An online learning or written correspondence course approved by the Board.

    (d) Providers shall limit the number of students for any continuing education class to no more than 49.

    (e) Providers shall not advertise or promote the sale of specific goods and/or services during the course of any continuing education class.

    (f) If an application is refused or not approved, written notice explaining the basis for the decision shall be provided to the applicant by the Board or its designee

    (5) Expiration and denial of Board approval

    (a) A provider's approval to offer instruction in Continuing Education expires on the last day of each license renewal cycle.

    (b) The Board may withdraw without notice at any time its approval of any Provider instructor who fails to meet the educational criteria established in 248 CMR 11.00.

    (c) The Board may deny approval of an application from a provider for any of the following reasons:

    1. failure to comply with the provisions of 248 CMR 11.05(4);

    Home UserTypewritten Text11

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    2. inadequate or unprofessional coverage of the materials required to be included in the course materials; or

    3. unsatisfactory evaluations of the course materials by instructors, licensees, the Board or its designee.

    (6) Course Materials. The Board shall approve course materials to be used for Mandatory Continuing Education courses. Course materials are the printed materials that serve as the basis for the Mandatory Continuing Education courses provided to licensees. The following minimum criteria shall be used by the Board in considering approval of course materials:

    (a) The course materials shall provide the basis for a minimum of three classroom hours of instruction per course as approved by the Board.

    (b) Course materials shall not advertise or promote the sale of goods and/or services. Advertisements used in conjunction with course materials must be clearly identifiable as such and clearly labeled as advertising.

    (c) The Board may approve the development of uniform course materials which all providers would be required to use.

    (d) The provider of course materials must have legal ownership of, or the appropriate license for the use of all copyrighted material included within the course materials.

    (e) All Board approved course materials shall contain a prominently displayed approval statement containing the following language: "THIS CONTINUING EDUCATION COURSE MATERIAL HAS BEEN APPROVED BY THE MASSACHUSETTS STATE BOARD OF EXAMINERS OF PLUMBERS AND GASFITTERS. BY APPROVAL OF THIS COURSE MATERIAL, THE BOARD DOES NOT ASSUME ANY RESPONSIBILITY FOR THE ACCURACY OF THE CONTENTS. THIS COURSE MATERIAL IS NOT BEING PUBLISHED BY, NOR IS IT A PUBLICATION OF, THE BOARD

    Home UserTypewritten Text12

  • Massachusetts Plumbing Continuing Education Services

    Massachusetts Plumbers Continuing Education Services

    Session III

    1099 Board Policy Explanation

    Home UserTypewritten Text13

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    Policy regarding Employer Certification of Applicant Hours

    Adopted June 24, 2009

    In general, employers must be able to provide social security records for their employees when those employees seek a license. However, the Board has noted that certain individuals are unable to produce those records and has checked “no” on the relevant form. These records are necessary for the Board as they show a supervisory employment relationship generally necessary for an apprenticeship. When such a situation takes place, the form shall be deemed to be incomplete and the following policy applies: 1. If the records are unavailable because the applicant was unpaid, then the following must

    be provided:

    A. A certification by the supervising master plumber/gas-fitter, under pains and penalties of perjury, that the applicant was not paid for the time that they worked.

    B. A copy of the contract between the master and the applicant showing an

    agreement that the work was unpaid.

    C. A list of jobs, with contact information, to allow the Board to verify independently that the applicant worked on those jobs.

    2. If the records are unavailable because the applicant was issued an IRS 1099 form, thus

    indicating social security was not withheld, the following must occur:

    A. The employing master should be notified that they may contact the relevant tax authorities if the use of the 1099 was in error.

    B. In the event the master does not correct the 1099 issue and become able to

    provide social security records, they must fill in an affidavit approved by the Board regarding the applicant’s employment. In this instance the employer may also be required to appear before the Board.

    3. It is the obligation of all Masters to adhere to this policy when they agree to take on an

    apprentice. Failure to adhere to these provisions constitutes unprofessional conduct and may subject the master to disciplinary action. As the application is considered incomplete without adherence to this policy, an applicant may be subject to having their application being returned as incomplete. Such an applicant may choose to file a complaint against the master. If such a complaint has been filed, the Board would have justification for granting the applicant an appearance before the Board. The Board may then be willing to consider additional evidence by the applicant demonstrating that all laws and regulations have been adhered to and that the applicant has accrued the required experience for the license sought.

    Home UserTypewritten Text14

  • Home UserTypewritten Text15

  • Massachusetts Plumbing Continuing Education Services

    Massachusetts Plumbers Continuing Education Services

    Session III

    Plumbing and Gas Permits

    Requirements for Installations and Inspections

    Home UserTypewritten Text16

  • P

    MASSACHUSETTS UNIFORM APPLICATION FOR PERMIT TO DO PLUMBING City/Town:___________________________, MA. Date:________________ Permit# ________________ Building Location:________________________________ Owners Name: ____________________________ Type of Occupancy: Commercial Educational Industrial Institutional Residential New: Alteration: Renovation: Replacement: Plans Submitted: Yes No

    FIXTURES

    AR

    EA D

    RA

    INS

    BA

    CK

    FLO

    W P

    REV

    ENTE

    R

    BA

    THTU

    BS

    DIS

    HW

    ASH

    ERS

    DIS

    PO

    SER

    S

    FLO

    OR

    DR

    AIN

    S

    HO

    T W

    ATE

    R T

    AN

    KS

    KIT

    CH

    EN S

    INK

    S

    LAU

    ND

    RY

    TR

    AY

    S

    LAV

    ATO

    RIE

    S

    RO

    OF

    DR

    AIN

    S

    SHO

    WER

    STA

    LLS

    SLO

    P S

    INK

    S

    TAN

    KLE

    SS

    UR

    INA

    LS

    WA

    SHIN

    G M

    AC

    H. C

    ON

    N.

    WA

    TER

    CLO

    SETS

    WA

    TER

    PIP

    ING

    OTH

    ER F

    IXTU

    RES

    :

    DEDICATED SYSTEMS

    AC

    ID-

    & H

    AZA

    RD

    OU

    S

    GA

    S –

    OIL

    - S

    AN

    D

    GR

    EASE

    GR

    AY

    WA

    TER

    WA

    STE

    WA

    TER

    SUB BSMT. BASEMENT 1ST FLOOR 2ND FLOOR 3RD FLOOR 4TH FLOOR 5TH FLOOR 6TH FLOOR 7TH FLOOR 8TH FLOOR Installing Company Name: ___________________________________________ Address: _______________________ City/Town: __________________ State: ______

    Business Tel: ________________________ Fax: ________________________ Name of Licensed Plumber:

    Check One Only Certificate #

    Corporation ________________

    Partnership ________________

    Firm/Company ________________

    INSURANCE COVERAGE: I have a current liability insurance policy or its substantial equivalent which meets the requirements of MGL. Ch. 142 Yes No If you have checked Yes, please indicate the type of coverage by checking the appropriate box below. A liability insurance policy Other type of indemnity Bond OWNER’S INSURANCE WAIVER: I am aware that the licensee does not have the insurance coverage required by Chapter 142 of the Massachusetts General Laws, and that my signature on this permit application waives this requirement. Check One Only _____________________________________________ Owner Agent Signature of Owner or Owner’s Agent

    I hereby certify that all of the details and information I have submitted (or entered) regarding this application are true and accurate to the best of my Knowledge and that all plumbing work and installations performed under the permit issued for this application will be in compliance with all Pertinent provision of the Massachusetts State Plumbing Code and Chapter 142 of the General Laws.

    By _______________________________ Title _____________________________ City/Town _________________________ APPROVED (OFFICE USE ONLY)

    Type of License:

    Plumber Master Journeyman

    _______________________________________________ Signature of Licensed Plumber License Number: __________________

    Home UserTypewritten Text17

  • MASSACHUSETTS UNIFORM APPLICATION FOR PERMIT TO DO GAS FITTING

    G City/Town:_____________________________, MA. Date:_________________ Permit# ________________ Building Location:_______________________________ Owners Name: _____________________________ Type of Occupancy: Commercial Educational Industrial Institutional Residential New: Alteration: Renovation: Replacement: Plans Submitted: Yes No

    FIXTURES

    CO

    NVE

    RSI

    ON

    BU

    RN

    ER

    DIR

    ECT

    VEN

    T H

    EATE

    RS

    DR

    YER

    S

    FUR

    NA

    CES

    GA

    S G

    ENER

    ATO

    RS

    GR

    ILLE

    S

    HEA

    TER

    RA

    NG

    E

    HEA

    TIN

    G B

    OIL

    ERS

    LAB

    OR

    ATO

    RY

    CO

    CK

    S

    OVE

    NS

    POO

    L H

    EATE

    RS

    RA

    NG

    ES

    RO

    OF

    TOP

    UN

    ITS

    TEST

    S

    UN

    IT H

    EATE

    RS

    UN

    VEN

    TED

    RO

    OM

    HTR

    S.

    VE

    NT

    ED

    RO

    OM

    HT

    RS

    .

    WA

    TER

    HEA

    TER

    S

    OTH

    ER F

    IXTU

    RES

    :

    SUB BSMT. BASEMENT 1ST FLOOR 2ND FLOOR 3RD FLOOR 4TH FLOOR 5TH FLOOR 6TH FLOOR 7TH FLOOR 8TH FLOOR Installing Company Name: ___________________________________________ Address:_____________________ City/Town:________________ State: ______ Business Tel: _______________________ Fax: _______________________ Name of Licensed Plumber/Gas Fitter:

    Check One Only Certificate #

    Corporation ________________

    Partnership ______________

    Firm/Company ______________

    INSURANCE COVERAGE: I have a current liability insurance policy or its substantial equivalent which meets the requirements of MGL. Ch. 142 Yes No If you have checked Yes, please indicate the type of coverage by checking the appropriate box below. A liability insurance policy Other type of indemnity Bond OWNER’S INSURANCE WAIVER: I am aware that the licensee does not have the insurance coverage required by Chapter 142 of the Massachusetts General Laws, and that my signature on this permit application waives this requirement. Check One Only _____________________________________________ Owner Agent Signature of Owner or Owner’s Agent By checking this box ; I hereby certify that all of the details and information I have submitted (or entered) regarding this application are true and accurate to the best of my Knowledge and that all plumbing work and installations performed under the permit issued for this application will be in compliance with all Pertinent provision of the Massachusetts State Plumbing Code and Chapter 142 of the General Laws. By _______________________________ Title _____________________________ City/Town _________________________ APPROVED (OFFICE USE ONLY)

    Type of License: Plumber Gas Fitter Master Journeyman LP Installer

    ________________________________________________ Signature of Licensed Plumber/Gas Fitter License Number: __________________

    Home UserTypewritten Text18

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Requirements for Emergency Installations and Inspections

    Massachusetts Plumbers Continuing Education Services

    248 CMR 4.03 Rule 3. In cases of emergency a gas appliance may be turned on temporarily by the licensed installer provided: a. the installer has tested the piping in accordance with the appropriate section of 248 CMR; b. the installer and the supplier are satisfied that the installation of piping and use of the equipment will assure safe operation; and c. the Inspector (or the chief inspector if more than one inspector) is notified and a regular Inspection is made at the earliest opportunity but not later than the next working day. 248 CMR 3.05 Permits and Inspections 6. In cases of emergency, a plumbing fixture may be turned on temporarily by the licensee provided: a. the installer has tested the piping in accordance with the appropriate requirements of 248 CMR; b. the installer and local water/sewer superintendent (if applicable) are satisfied that the installation of piping and use of equipment will assure safe operation; and c. the Inspector (or the chief inspector if more than one inspector) is notified and a regular inspection is made at the earliest opportunity and in no case later than the next working day. 248 CMR 3.05 (3)(d) Notification. 1. It shall be the duty of the Permit Holder or the licensed plumber or gas fitter employed by the Master Plumber or gas fitter to give notice to the Inspector when plumbing or gas fitting work is ready for Inspection. 2. The licensed plumber or gas fitter or the Permit Holder shall establish that the work will stand the prescribed test and that the roughing-in has been completed as far as practicable before giving the notification. 248 CMR 3.05 (3)(f) Covering of Work. 1. No new plumbing and gas fitting work and such portions of existing systems that may be directly affected by new work shall not be covered until it has been tested if required by the Inspector, and the Inspector has certified that the work is in compliance with M.G.L. c. 142 and 248 CMR 3.00 through 10.00. 2. If new plumbing and gas fitting work and such portions of existing systems that may be directly affected by new work are covered before being tested and approved by the Inspector, the work shall be uncovered for Inspection after the Inspector has issued a notice to uncover the work to the Permit Holder responsible.

    Home UserTypewritten Text19

  • Massachusetts Plumbing Continuing Education Services

    Massachusetts Plumbers Continuing Education Services

    Session III

    CSST UPDATE

    Home UserTypewritten Text20

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    CSST UPDATE REGARDING COUNTERSTRIKE

    In 248 CMR Section 5.02 (4) other standards: It states, in applying NFPA-54, reference should also be made to the manufacturer's instructions. In all CSST installations, bonding requirements shall comply with the manufactures installation instructions, for this reason, it is the manufacturers responsibility to insure that the licensed installer's have the current edition of the installation instructions. This will help to eliminate confusion when and if the instructions are requested by the inspector. Based upon the amended verbiage listed in the latest edition of the Tracpipe installation instructions dated June 2009, in section 4.10A (3) the manufacturer states: unlike Tracpipe, there are no additional bonding requirements for Counterstrike imposed by the manufacturer's installation instructions. Counterstrike is to be bonded in accordance with the National Electrical Code NFPA 70 Article 250.104 in the same manner as the minimum requirements for rigid metal piping. However, installers must always adhere to any local requirements that may conflict with these instructions.

    Home UserTypewritten Text21

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    CSST Update — March 2009 Informational use only. For official Board interpretation, contact the Board of Examiners

    of Plumbers and Gas Fitters at (617) 727-9950 or:

    www.ma. gov/dplfboards/pl

    All CSST piping systems shall be bonded according to manufacturer’s instructions,

    including Trac Pipe’s Counterstrike. The bonding shall be done by a licensed electrician or homeowner (if the municipality

    allows).

    INSTALLER

    Cheek with the local electrical inspector to be sure he will issue permit and inspect the bonding. If he will not issue a permit, DO NOT INSTALL CSST.

    Install the CSST piping system.

    INSPECTOR

    Before inspecting, determine if an electrical permit for the bonding has been issued by the electrical inspector.

    If the permit has been issued, you can inspect the CSST piping system according to the

    Fuel Gas Code. DO NOT INSPECT THE BONDING, since this will be done by the electrical inspector.

    NOTES If replacing an appliance and no ADDITIONAL CSST is installed, the system does NOT

    have to be bonded.

    Any new or additional CSST piping requires bonding.

    If the system has been previously bonded and inspected by the electrical inspector and

    they are adding or modifying the existing system, no additional bonding is required.

    Home UserTypewritten Text22

  • 248 CMR: BOARD OF STATE EXAMINERS

    OF PLUMBERS AND GAS FITTERS

    Commercial Hood Interlock

    Massachusetts Plumbers Continuing Education Services

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextVentilating hoods and exhaust systems shall be permitted to be used to vent gas utilization equipment installed in commercial applications.

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextWhere automatically operated gas utilization equipment is vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the equipment and when the power means of exhaust is in operation.

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text10.3.5* Ventilating Hoods and Exhaust Systems.

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text10.3.5.1

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text10.3.5.2

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text23

  • Massachusetts Plumbing Continuing Education Services

    Massachusetts Plumbers Continuing Education Services

    Session III

    Make Up Air

    Home UserTypewritten Text24

  • NFPA 54 2002 Edition Air for Combustion and Ventilation

    Massachusetts Plumbers Continuing Education Services Copyrighted Sections of NFPA 54 2002 Edition Re-printed with written Permission from NFPA

    8.3.1 General.

    8.3.1.1 Air for combustion, ventilation, and dilution of flue gases for gas utilization equipment installed in buildings shall be obtained by application of one of the methods covered in 8.3.2 through 8.3.6. Where the requirements of 8.3.2 are not met, outdoor air shall be introduced in accordance with methods covered in 8.3.3 through 8.3.6. Exception No. 1: This provision shall not apply to direct vent appliances.

    Exception No. 2: Type I clothes dryers that are provided with makeup air in accordance

    with 9.4.3.

    8.3.2 Indoor Combustion Air. The required volume of indoor air shall be determined in accordance with the method in 8.3.2.1 or 8.3.2.2 except that where the air infiltration rate is known to be less than 0.40 ACH, the method in 8.3.2.2 shall be used. The total required volume shall be the sum of the required volume calculated for all appliances located within the space. Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors, and through combustion air openings sized and located in accordance with 8.3.2.3 are considered a part of the required volume.

    8.3.3 Outdoor Combustion Air. Outdoor combustion air shall be provided through opening(s) to the outdoors in accordance with the methods in 8.3.3.1 or 8.3.3.2. The minimum dimension of air openings shall not be less than 3 in. (80 mm).

    8.3.4 Combination Indoor and Outdoor Combustion Air. The use of a combination of indoor and outdoor combustion air shall be in accordance with (1) through (3) (see example calculation in Annex J): (1) Indoor Openings. Where used, openings connecting the interior spaces shall comply with 8.3.2.3. (2) Outdoor Opening(s) Location. Outdoor opening(s) shall be located in accordance with 8.3.3. (3) Outdoor Opening(s) Size. The outdoor opening(s) size shall be calculated in accordance with the following: (a) The ratio of the interior spaces shall be the available volume of all communicating spaces divided by the required volume. (b) The outdoor size reduction factor shall be 1 minus the ratio of interior spaces. (c) The minimum size of outdoor opening(s) shall be the full size of outdoor opening(s) calculated in accordance with 8.3.3, multiplied by the reduction factor. The minimum dimension of air openings shall not be less than 3 in. (80 mm).

    Home UserTypewritten Text25

  • Massachusetts Plumbers Continuing Education Services Combustion Air Requirements (Make Up Air)

    Massachusetts Plumbers Continuing Education Services

    Combustion air is needed to achieve the most complete combustion from natural gas.

    Type of Space Confined — a space where the volume is less than 50 cubic feet

    per 1,000 BTU’s per hour of the total combined input rating of all the appliances located in that space.

    Unconfined — a space where the volume is not less than 50 cubic feet per 1,000 BTU’s per hour of the total combined input rating of all the appliances located in that space. Rooms without doors directly connected with the space where the appliances are located are considered to be part of the unconfined space.

    Standard method to detect if you have a confined or unconfined space.

    L-X-W-X-H 50 (Divide)

    To convert to BTU’s add 000 after the answer. This will be the total amount

    of BTU’s that may be installed in that space without adding additional makeup air (unconfined space).

    If the total amount of BTU’s from the appliances located in the space is greater than your answer, makeup air must be installed (confined space).

    Example - A boiler room water heater with a combined total BTU input

    of 200,000 BTU’s is going to be installed in a space 25 feet long by 25 feet wide by 8 feet high, is make up air needed?

    25 x 25 x 8 = 5,000

    5,000 / 50 = 100

    (Add 000’s) 100,000 BTU’s

    This basement can support 100,000 BTU’s making it a confined space. Make up air must be added.

    The following pages contain examples of how to obtain the additional 100,000 BTU’s of air.

    Home UserTypewritten Text26

  • Massachusetts Plumbers Continuing Education Services

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextOpenings used to connect indoor spaces shall be sized and located in accordance with the following:(1)* Combining spaces on the same story. Each opening shall have a minimum free area of 1 in.2/1000 Btu/hr (2200 mm2/kW) of the total input rating of all gas utilization equipment in the space, but not less than 100 in.2 (0.06 m2). One opening shall commence within 12 in. (300 mm) of the top, and one opening shall commence within 12 in. (300mm) of the bottom, of the enclosure [see Figure A.8.3.2.3(1)]. The minimum dimension of air openings shall be not less than 3 in. (80 mm). (2) Combining spaces in different stories. The volumes of spaces in different stories shall be considered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 in.2/1000 Btu/hr (4,400mm2/kW) of total input rating of all gas utilization equipment.

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextExample100,000 divided by 1000 = 100100 square inches of free area is neededSee metal grill chart 14x12 = 113 square inches

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextIndoor Air High and Low Grills

    Home UserTypewritten Text

    Home UserTypewritten TextOutside Air Two openings

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text (1)* Where directly communicating with the outdoors or where communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in.2/4000 Btu/hr (550 mm2/kW) of total input rating of all equipment in the enclosure. [See Figure A.8.3.3.1(1)(a) and Figure A.8.3.3.1(1)(b).]

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextExample 100,000 divided by 4000 = 25 square inches2 - 5 x5 square ducts or 2- 6 round ducts

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserRectangle

    Home UserRectangle

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text8.3.3 Outdoor Combustion Air.

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextOutdoor combustion air shall be provided through opening(s) to the outdoors in accordance with the methods in 8.3.3.1 or 8.3.3.2. The minimum dimension of air openings shall not be less than 3 in. (80 mm).

    Home UserTypewritten Text

    Home UserTypewritten Text8.3.3.1 Two Permanent Openings Method.

    Home UserTypewritten Text

    Home UserTypewritten TextTwo permanent openings, one commencing within 12 in. (300 mm) of the top and one commencing within 12 in. (300 mm) of the bottom of the enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors, as follows:

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserRectangle

    Home UserTypewritten Text

    Home UserTypewritten Text8.3.2.3 Indoor Opening Size and Location.

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextBoiler Room Door

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextGrille 12" From Ceiling

    Home UserLine

    Home UserLine

    Home UserTypewritten TextGrille 12"From Floor

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextWater Heater

    Home UserTypewritten TextBoiler

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextDuct 12" from Ceiling

    Home UserTypewritten TextDuct 12"From Floor

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserLine

    Home UserLine

    Home UserTypewritten Text27

  • Home UserTypewritten Text(2)* Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 in.2/2000 Btu/hr (1100 mm2/kW) of total input rating of all equipment in the enclosure. [See Figure A.8.3.3.1(2).]

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextExample 100,000 divided by 2,000 = 50 square inches2 - 5x10 square ducts or 2 - 8 inch round ducts

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextOne permanent opening, commencing within 12 in. (300 mm) of the top of the enclosure, shall be provided. The equipment shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors (see Figure A.8.3.3.2) and shall have a minimum free area of the following:(1) 1 in.2/3000 Btu/hr (700 mm2 per kW) of the total input rating of all equipment locatedin the enclosure, and(2) Not less than the sum of the areas of all vent connectors in the space A.8.3.3.2

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextExample 100,000 dived by 3000 = 33.33 square inches1 -6x6 square duct or 1 - 7 inch round duct

    Home UserTypewritten Text

    Home UserRectangle

    Home UserRectangle

    Home UserTypewritten TextOutside Air One Opening

    Home UserTypewritten TextOutside Air Two Horizontal Ducts

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextBoiler

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextDuct Down 12" From Ceiling

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextDuct Up 12" From Floor

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextWater Heater

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextMassachusetts Plumbers Continuing Education Services

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextAnnex A.8.3.3.1(1)

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text8.3.3.2* One Permanent Opening Method.

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextDuct 12" Down From Ceiling

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserLine

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text28

    Home UserLine

    Home UserLine

    Home UserTypewritten Text

    Home UserLine

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserLine

    Home UserTypewritten TextWater Heater

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextBoiler

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextOpen Space

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text Or Another Room

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserLine

    Home UserLine

  • Combination Indoor and Outdoor Air

    Massachusetts Plumbers Continuing Education Services

    Engineered Systems 8.3.5 Engineered Installations. Engineered combustion air installations shall provide an adequate supply of combustion, ventilation, and dilution air and shall be approved by the authority having jurisdiction.

    Engineers should design the combustion air system for large commercial or industrial applications using the proper engineering calculations and techniques.

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextThe use of a combination of indoor and outdoor combustion air shall be in accordance with (1) through (3) (see example calculation in Annex J):(1) Indoor Openings. Where used, openings connecting the interior spaces shall comply with 8.3.2.3.(2) Outdoor Opening(s) Location. Outdoor opening(s) shall be located in accordance with8.3.3.(3) Outdoor Opening(s) Size. The outdoor opening(s) size shall be calculated in accordancewith the following:(a) The ratio of the interior spaces shall be the available volume of all communicatingspaces divided by the required volume.(b) The outdoor size reduction factor shall be 1 minus the ratio of interior spaces.(c) The minimum size of outdoor opening(s) shall be the full size of outdoor opening(s)calculated in accordance with 8.3.3, multiplied by the reduction factor. The minimum dimension of air openings shall not be less than 3 in. (80 mm).

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextExampleAdditional inside air from outside the space40,000 divided by 1000 = 40 square inches2 - 12x6 GrillsOutside60,000 divided by 4000 = 15 square inches2 4x4 square ducts or 2 5 inch round ducts

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserRectangle

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextBoiler Room Door

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextGrille 12 " From Ceiling

    Home UserTypewritten Text

    Home UserRectangle

    Home UserLine

    Home UserLine

    Home UserTypewritten Text

    Home UserTypewritten TextDuct 12" From Ceiling

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextGrille 12" From Floor

    Home UserTypewritten Text

    Home UserTypewritten TextDuct 12"From Floor

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text8.3.4 Combination Indoor and Outdoor Combustion Air.

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text29

  • Massachusetts Plumbers Continuing Education Services Copyrighted Sections of NFPA 54 2002 Edition Re-printed with written Permission from NFPA

    Massachusetts Plumbers Continuing Education Services

    8.3.6 Mechanical Combustion Air Supply. Where all combustion air is provided by a mechanical air supply system, the combustion air shall be supplied from outdoors at the minimum rate of 0.35 ft3/min per 1000 Btu/hr (0.034 m3/min per kW) for all appliances located within the space.

    8.3 .6.1 Where exhaust fans are installed, additional air shall be provided to replace the exhausted air. A commercial cooking hood will take air from any space available,

    including Draft hoods connected to chimneys introducing carbon monoxide

    into the space.

    8.3.6.2 Each of the appliances served shall be interlocked to the mechanical air

    supply system to prevent main burner operation while the mechanical air supply system is not in operation. Before the equipment fires the mechanical air system shall be activated.

    8.3.6.3 Where combustion air is provided by the building’s mechanical ventilation

    system. the system shall provide the specified combustion air rate in addition to the required ventilation air. The system shall be sized to accommodate all of the air needed for the

    building as well as the combustion air for the gas appliances.

    Home UserTypewritten Text30

  • Massachusetts Plumbers Continuing Education Services

    Massachusetts Plumbers Continuing Education Services Copyrighted Sections of NFPA 54 2002 Edition Re-printed with written Permission from NFPA

    8.3.7.1 The required size of openings for combustion, ventilation, and dilution air shall be based on the net free area of each opening. Where the free area through a design louver or grille is known, it shall be used in calculating the size opening required to provide the free area specified. Where the design and free area are not known, it shall be assumed that wood louvers will have 25% free area, and metal louvers and grills will have 75 % free area. Non-motorized louvers and grilles shall be fixed in the open position.

    Nominal Free Nominal Free Nominal Free Size Area Size Area Size Area (IN.) (Sq. In.) (IN.) (Sq. In.) (IN.) (Sq. In.)

    10 X 6 39 16 X 16 174 24 X 8 127 10 X 8 52 18 X 6 71 24 X 10 159 10 X 10 65 18 X 8 95 24 X 12 191 12 X 6 47 18 X 10 119 24 X 14 224 12 X 8 63 18 X 12 144 24 X 16 256 12 X 10 79 18 X 14 167 24 X 18 288 12 X 12 96 18 X 16 192 24 X 20 320 14 X 4 37 18 X 18 216 24 X 24 384 14 X 6 56 20 X 6 77 30 X 4 78 14 X 8 75 20 X 8 104 30 X 6 118 14 X 10 94 20 X 10 130 30 X 8 158 14 X 12 113 20 X 12 156 30 X 10 199 14 X 14 132 20 X 14 182 30 X 12 239 16 X 6 65 20 X 16 209 30 X 14 279 16 X 8 87 20 X 18 235 30 X 16 319 16 X 10 109 20 X 20 262 30 X 18 360 16 X 12 130 24 X 4 63 30 X 20 399 16 X 14 152 24 X 6 95 30 X 24 479

    30 X 30 600

    Home UserTypewritten Text

    Home UserTypewritten TextApproximate Metal Grill Size For Combustion Air

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten TextAPPROXIMATE AREA OF ROUND PIPE IN SQUARE INCHES

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text3” Round =7 Sq In 13” Round = 132 Sq In 4” = 12 14” = 153 5” = 19 15” = 176 6” = 28 16” = 200 7” = 38 17” = 226 8” = 50 18” = 254 9” = 63 19” = 283 10” = 78 20” = 314 11” = 95 21” = 346 12” = 113 22” = 380

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserRectangle

    Home UserTypewritten Text8.3.7 Louvers and Grilles

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text31

  • Massachusetts Plumbers Continuing Education Services Copyrighted Sections of NFPA 54 2002 Edition Re-printed with written Permission from NFPA

    Massachusetts Plumbers Continuing Education Services

    8.3.7.2 Motorized louvers shall be interlocked with the equipment so they are proven in the full open position prior to main burner ignition and during main burner operation. Means shall be provided to prevent the main burner from igniting should the lover fail to open during startup and to shut down the main burner if the louvers close during burner operation.

    The system shall not fire until the damper is 100% in the open position.

    8.3.8 Combustion air ducts. Combustion air ducts shall comply with the following. 8.3.8.1 Ducts shall be of galvanized steel or an equivalent corrosion- resistant material.

    PVC, Stainless Steel, etc....

    Exception: within dwelling units, unobstructed stud and joist spaces shall not be prohibited from conveying combustion air, provided that not more than one fire block is removed. 8.3.8.2 Ducts shall terminate in an unobstructed space, allowing free movement of combustion air to the appliances.

    Do not obstruct the combustion air ducts with large objects

    8.3.8.3 Ducts shall serve a single space. The ducts shall not deliver combustion air to more than 1 space

    8.3.8.4 Ducts shall not serve both upper and lower combustion air openings where both such openings are used. The separation between ducts serving upper and lower combustion air openings shall be maintained to the source of combustion air.

    Do not use the same duct for the high & low application. The lower duct delivers air to the appliance, while the upper duct releases warm air to the outside (convection)

    8.3.8.5. Ducts shall not be screened where terminating in an attic space. Boxes may be placed on top of the screen impeding the delivery of combustion air.

    8.3.8.6 Horizontal upper combustion air ducts shall not slope downward toward the source of combustion air.

    Pitching the duct away from the appliance would create a trap hindering the flow of combustion air.

    8.3.8.7 The remaining space surrounding a chimney liner, gas vent, special gas vent, or plastic piping installed within a masonry, metal, or factory built chimney shall not be used to supply combustion air.

    The B- Vent or liner could leak, emitting carbon monoxide back into the building.

    Exception: direct vent gas fired appliances designed for installation in a solid fuel burning fireplace where installed in accordance with the listing and the manufacturer’s instruction. 8.3.8.8 Combustion air intake openings located on the exterior of the building shall have the lowest side of the combustion air intake openings located at least 12 in (300 mm) vertically from the adjoining grade level.

    The opening may become blocked by snow or leaves. Try to keep the opening as high as possible.

    Home UserTypewritten Text32

  • NFPA 54 2002 Edition Air for Combustion and Ventilation

    Massachusetts Plumbers Continuing Education Services Copyrighted Sections of NFPA 54 2002 Edition Re-printed with written Permission from NFPA

    NFPA 54 9.10.5 Circulating Air. Where a duct furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive-pressure side of the circulating air blower.

    Home UserTypewritten Text33

  • Massachusetts Plumbing Continuing Education Services

    Massachusetts Plumbers Continuing Education Services

    Session III

    Requirements for Elevated Gas

    Home UserTypewritten Text34

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    Requirements for Elevated Gas Permits Requires Special Permission from the Plumbing Board

    248 CMR 4.03 Rule 1. Gas piping systems, in general, shall be low pressure (not in excess of 1/2 pound per square inch or 14 inches water column). 248 CMR 3.04 (3) Special-permission. (a) When safety is of special consideration, provisions of 248 CMR 3.00 through 10.00 may require that a Licensee obtain Special-permission from the Board before installing or using a given product, system, design, or method. (b)To obtain Special-permission an applicant shall: 1. submit a request to the Board; and 2. at the Board’s request, appear at a Board where the request is scheduled to be discussed. c) The Special-permission request shall include: 1. a fee; 2. a completed application; 3. a certification that the system was designed or engineered by a qualified individual; 4. the submission of a set of construction documents that have been stamped by a Massachusetts Registered Professional Engineer; and 5. any other requested documentation. 248 CMR 5.02 (1) Revise NFPA-54 section 1.1.1.1(A) as follows. Coverage of piping systems shall extend form the point of delivery to the connections with each gas utilization device. For other than undiluted liquefied petroleum gas systems, the point of delivery shall be considered the outlet of the service meter assembly or the outlet of the service regulator or service shut off valve where no meter is provided. For undiluted liquefied petroleum gas systems, the point of delivery shall be considered the outlet of the first stage regulator. (2) Revise NFPA-54 section 1.1.1.1(B) as follows. All Gas piping systems, in general for all buildings and structures shall be low pressure (not in excess of ½ P.S.I.G. or 14 inch water column) All low pressure gas piping systems shall be designed using a maximum 0.5 inch water column pressure drop. Special-permission pursuant to 248 CMR 3.00 may be granted for elevated pressure (greater than ½ P.S.I.G. or 14 inch water column) when gas utilization equipment specifically requires higher pressure or when a designed low pressure system requires pipe sizes in excess of four inch I.P.S. An elevated pressure Special-permission request form specified by the Board shall be filled out completely and submitted to the Executive Secretary for the Board. If the Board grants Special permission, a copy shall be filed with the Inspector before the commencement of any work.

    Home UserTypewritten Text35

  • 248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

    Massachusetts Plumbers Continuing Education Services

    248 CMR 5.03 (3) Replace NFPA-54 section 5.5.1 with the following: Elevated Pressure Piping to be Labeled: Piping supplying gas at a pressure greater than ½ P.S.I.G. or 14 inch water column shall be labeled: (a) at a minimum of every ten feet; (b) at all changes of direction; (c) on each side of a penetration through a partition, wall or ceiling; and, (d) at every gas shutoff valve. (e) The labels shall: 1. be colored yellow with black lettering; 2. indicate the type of gas and the pressure contained within the piping system; and 3. the letters shall be sized so that the labeling can be read from a normal line of vision when standing at the main floor level. 248 CMR 7.03: General Provisions (1) Special-permission Required: Special-permission from the Board is required before installation of any all gas-fired boilers, burners, or their accessories. (a) In determining acceptability, the Board would normally base acceptance on compliance with the appropriate Boiler Code and 248 CMR 7.00. (b) The Board of State Examiners of Plumbers and Gas Fitters may also refer to the listings or labeling practices of nationally recognized testing laboratories, i.e., laboratories qualified and equipped to conduct the necessary tests, in a position to determine compliance with appropriate standards for the current production of listed items, and the satisfactory performance of such equipment or materials in actual usage; or the recommendations of a nationally recognized engineering agency specializing in the field of safety to life and property. (c) Before arranging for the selection or installation of a large gas burner or boiler, the licensed plumber or gas fitter shall check with the serving gas supplier as to the availability of gas, specifying the gas input rating and the gas pressure required at the entrance to gas train. (See Figure 3 in 248 CMR 7.02). (d) As required in 248 CMR 3.00, a written permit in a form and manner prescribed by the Inspector shall be obtained by persons performing gas fitting work as defined in M.G.L. c. 142 before commencing each installation.

    Home UserTypewritten Text36

  • Home UserTypewritten Text37

  • Home UserTypewritten Text38

  • Home UserTypewritten Text39

  • Home UserTypewritten Text40

  • Massachusetts Plumbing Continuing Education Services

    Massachusetts Plumbers Continuing Education Services

    Session III

    Gas Pipe Sizing

    Home UserTypewritten Text41

    Home UserTypewritten Text

    Home UserTypewritten Text

  • NFPA 54 2002 Edition How to Calculate Gas Pipe using the longest run method

    Massachusetts Plumbers Continuing Education Services Copyrighted Sections of NFPA 54 2002 Edition Re-printed with written Permission from NFPA

    NFPA 54 2002 Edition C.3.1 The Longest Length Method. This sizing method is conservative in its approach by applying the maximum operating conditions in the system as the norm for the system and by setting the length of pipe used to size any given part of the piping system to the maximum value. To determine the size of each section of gas piping in a system within the range of the capacity tables, proceed as follows. (Also see sample calculations included in this annex.) (1) Divide the piping system into appropriate segments consistent with the presence of tees, branch lines, and main runs. For each segment, determine the gas load (assuming all appliances operate simultaneously) and its overall length. An allowance (in equivalent length of pipe) as determined from Table C.2.2, shall be considered for piping segments that include four or more fittings. (2) Determine the gas demand of each appliance to be attached to the piping system. Where Table 12.1 through Table 12.23 are to be used to select the piping size, calculate the gas demand in terms of cubic feet per hour for each piping system outlet. Where Table 12.24 through Table 12.33 are to be used to select the piping size, calculate the gas demand in terms of thousands of Btu per hour for each piping system outlet. (3) Where the piping system is for use with other than undiluted liquefied petroleum gases, determine the design system pressure, the allowable loss in pressure (pressure drop), and specific gravity of the gas to be used in the piping system. (4) Determine the length of piping from the point of delivery to the most remote outlet in the building/piping system. (5) In the appropriate capacity table, select the row showing the measured length or the next longer length if the table does not give the exact length. This is the only length used in determining the size of any section of gas piping. If the gravity factor is to be applied, the values in the selected row of the table are multiplied by the appropriate multiplier from Table C.2.4. (6) Use this horizontal row to locate ALL gas demand figures for this particular system of piping. (7) Starting at the most remote outlet, find the gas demand for that outlet in the horizontal row just selected. If the exact figure of demand is not shown, choose the next larger figure left in the row. (8) Opposite this demand figure, in the first row at the top, the correct size of gas piping will be found. (9) Proceed in a similar manner for each outlet and each section of gas piping. For each section of piping, determine the total gas demand supplied by that section. When a large number of piping components (such as elbows, tees, and valves) are installed in a pipe run, additional pressure loss can be accounted for by the use of equivalent lengths. Pressure loss across any piping component can be equated to the pressure drop through a length of pipe. The equivalent length of a combination of only four elbows/tees can result in a jump to the next larger length row, resulting in a significant reduction in capacity. The equivalent lengths in feet shown in Table C.2.2 have been computed on a basis that the inside diameter corresponds to that of Schedule 40 (standard-weight) steel pipe, which is close enough for most purposes involving other schedules of pipe. Where a more specific solution for equivalent length is desired, this may be made by multiplying the actual inside diameter of the pipe in inches by n/12, or the actual inside diameter in feet by n. N can be read from the table heading. The equivalent length values can be used with reasonable accuracy for copper or brass fittings and bends although the resistance per foot of copper or brass pipe is less than that of steel. For copper or brass valves, however, the equivalent length of pipe should be taken as 45 percent longer than the values in the table, which are for steel pipe.

    Home UserTypewritten Text42

  • E

    A

    C

    G

    200,000btu

    F

    H

    I

    J

    K

    L

    M

    160,000btu

    140,000btu

    150,000btu

    75,000btu

    50,000btu

    Meter

    Table 12.2

    Schedule 40 Metallic Pipe

    .50 PSI or Less - Pressure Drop .50 in. wc

    Longest Run: 190’

    Total BTU Load: 775,000 D

    B

    Longest Length Method

    Home UserTypewritten Text50'

    Home UserTypewritten Text40'

    Home UserTypewritten Text10'

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text20'

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text40'

    Home UserTypewritten Text

    Home UserTypewritten Text30'

    Home UserTypewritten Text20'

    Home UserTypewritten Text40'

    Home UserTypewritten Text20'

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserTypewritten Text40'

    Home UserTypewritten Text50'

    Home UserTypewritten Text20'

    Home UserTypewritten Text

    Home UserTypewritten Text20'

    Home UserTypewritten Text

    Home UserTypewritten Text

    Home UserOval

    Home UserOval

    Home UserOval

    Home UserOval

    Home UserOval

    Home UserOval

    Home UserOval

    Home UserOval

    Home UserOval

    Home UserOval

    Home UserOval

    Home UserOval

    Home UserOval

    Home UserTypewritten Text43

  • NFPA 54 2002 Edition How to Calculate Gas Pipe using the longest run method

    Massachusetts Plumbers Continuing Education Services Copyrighted Sections of NFPA 54 2002 Edition Re-printed with written Permission from NFPA

    Home UserTypewritten Text44

  • NFPA 54 2002 Edition How to Calculate Gas Pipe using the Branch method

    Massachusetts Plumbers Continuing Education Services Copyrighted Sections of NFPA 54 2002 Edition Re-printed with written Permission from NFPA

    C.3.2 The Branch Length Method. This sizing method reduces the amount of conservatism built into the traditional Longest Length Method. The longest length as measured from the meter to the farthest remote appliance is only used to size the initial parts of the overall piping system. The Branch Length Method is applied in the following manner: (1) Determine the gas load for each of the connected appliances. (2) Starting from the meter, divide the piping system into a number of connected segments, and determine the length and amount of gas that each segment would carry assuming that all appliances were operated simultaneously. An allowance (in equivalent length of pipe) as determined from Table C.2.2 should be considered for piping segments that include four or more fittings. (3) Determine the distance from the outlet of the gas meter to the appliance farthest removed from the meter. (4) Using the longest distance (found in Step 3), size each piping segment from the meter to the most remote appliance outlet. (5) For each of these piping segments, use the longest length and the calculated gas load for all of the connected appliances for the segment and begin the sizing process in Steps 6 through 8. (6) Referring to the appropriate sizing table (based on operating conditions and piping material), find the longest length distance in the first column or the next larger distance if the exact distance is not listed. The use of alternative operating pressures and/or pressure drops will require the use of a different sizing table, but will not alter the sizing methodology. In many cases, the use of alternative operating pressures and/or pressure drops will require the approval of both the authority having jurisdiction and the local gas serving utility. (7) Trace across this row until the gas load is found or the closest larger capacity if the exact capacity is not listed. (8) Read up the table column and select the appropriate pipe size in the top row. Repeat Steps 6, 7, and 8 for each pipe segment in the longest run. (9) Size each remaining section of branch piping not previously sized by measuring the