masterpact str units

Upload: 322399mk7086

Post on 14-Oct-2015

48 views

Category:

Documents


0 download

DESCRIPTION

LV Protection unit

TRANSCRIPT

  • Instruction Bulletin48049-071-03

    01/2002Cedar Rapids, IA, USA

    MASTERPACT MP, MF and MC Circuit Breakers

    Retain for future use.

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Instruction Bulletin 01/2002

    19982002 Schneider Electric All Rights Reserved.2

    NOTICE Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

    Provides additional information to clarify or simplify a procedure.

    PLEASE NOTE Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. This document is not intended as an instruction manual for untrained persons.

    FCC NOTICE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

    DANGERDANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

    WARNINGWARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.

    CAUTIONCAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.

    CAUTIONCAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in property damage.

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Table of Contents

    19982002 Schneider Electric All Rights Reserved 3

    TABLE OF CONTENTSSECTION 1: INSTALLATION Recommendations for Storing ..................................................................... 5

    Temperature Limits ................................................................................ 5Circuit Breaker Status ............................................................................ 5Covering ................................................................................................. 5Maximum Stacking ................................................................................. 5

    Identifying the Circuit Breaker ...................................................................... 6Unpacking .................................................................................................... 7

    MP40 to MP63 Drawout-mounted Circuit Breakers ............................... 8Handling ....................................................................................................... 9

    MP08 to MP30 and MC08 to MC20 Circuit Breakers ............................. 9MC32 Circuit Breakers ......................................................................... 10MP40 to MP63 and MC40 to MC50 Circuit Breakers ........................... 11MF12, MF20 and MF30 Circuit Breakers ............................................. 12

    Attaching Rear Terminals .......................................................................... 13Mounting .................................................................................................... 14

    Cable Connection ................................................................................. 14Bus Bar Connection ............................................................................. 15

    Control Wiring ............................................................................................ 16Fixed-mounted Circuit Breakers ........................................................... 16Drawout-mounted Circuit Breakers ...................................................... 17

    SECTION 2: OPERATION Disconnecting and Connecting Instructions ............................................... 19Disconnecting Instructions ................................................................... 20Installing the Circuit Breaker in the Stationary Assembly ..................... 21Connecting Instructions ........................................................................ 22

    Operating ................................................................................................... 23Charging Instructions ........................................................................... 23Closing Instructions .............................................................................. 23Opening Instructions ............................................................................ 24Resetting Instructions ........................................................................... 24

    Locking ...................................................................................................... 24Locking by Key Interlock ...................................................................... 24Locking by Padlock .............................................................................. 25Locking by Door Interlock ..................................................................... 25Spring Interlock .................................................................................... 26

    SECTION 3: CONTROL UNIT TYPES STR 18 M Control Unit ............................................................................... 28STR 28 D Control Unit ............................................................................... 30STR 38 S Control Unit ............................................................................... 32STR 58 U Control Unit ............................................................................... 34Control Unit Options .................................................................................. 36

    Pre-trip and Overload Indication Option ............................................... 36Thermal Memory Limitation .................................................................. 37Ammeter Option ................................................................................... 38Fault Indication Option ......................................................................... 39Battery Option ...................................................................................... 40Load Monitoring Option ........................................................................ 40Segregated Alarm Switch Option ......................................................... 41Ground-fault Protection Option ............................................................ 41Zone-selective Interlocking Option ....................................................... 42Transmit Data from Trip Unit Option .................................................... 42

  • Document Subtitle (In header) 48049-071-03Table of Contents 01/2002

    19982002 Schneider Electric All Rights Reserved4

    SECTION 4: MAINTENANCE Routing Inspections .................................................................................... 44Electrical Maintenance ............................................................................... 44Check Arc Chutes ...................................................................................... 45

    Check Contacts .................................................................................... 45Wiring Diagram .......................................................................................... 46

    SECTION 5: SET-UP GUIDE Minimum Enclosure .................................................................................... 48Clearance Information ................................................................................ 49Stacking Configurations .............................................................................50Cumulative Loading ................................................................................... 51Temperature Derating ................................................................................ 52Power Dissipation ...................................................................................... 53Resistance ................................................................................................. 53Altitude Correction Factors ......................................................................... 53

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 1Installation

    19982002 Schneider Electric All Rights Reserved 5

    SECTION 1 INSTALLATION

    Hex-head wrenches Straight-blade screwdrivers (large and small) Wire stripper

    RECOMMENDATIONS FOR STORING

    Do not store circuit breakers in a corrosive or salt-air environment.

    Temperature Limits Store from -60 F (-50 C) min. to +160 F (+70 C) max.

    Circuit Breaker Status Store with: Main contacts open Spring discharged Connected position

    Covering Store the circuit breaker only in the original shipping carton or other protective weatherproof covering.

    Maximum Stacking

    DANGERHAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This equipment must be installed and

    serviced only by qualified electrical personnel.

    Turn off all power supplying this equipment before working on or inside equipment.

    Always use a properly rated voltage sensing device to confirm power is off.

    Replace all devices, doors and covers before turning on power to this equipment.

    Failure to follow this instruction will result in death or serious injury.

    0631

    3219

    0631

    3220 MP08 to MP30

    3

    MP40 to MP63 2

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 1Installation 01/2002

    19982002 Schneider Electric All Rights Reserved6

    IDENTIFYING THE CIRCUIT BREAKER

    Figure 1: Location of Markings on Circuit Breaker

    Figure 2: Location of Markings on Stationary Assembly

    0631

    3221

    Serial:Control diagram no.:Sensor. . .In:Instantaneous override:

    Electrical accessories identification label (fixed mounting)

    Name label giving rating, interrupting ratings and rated voltage

    Manufacturing no.Wiring diagram no.Sensor ratingInstantaneous pickup

    0631

    3222

    Circuit breaker stationary assemblyA max. Accepts frame size: MP/MC

    Wiring diagram no.

    Serial

    Frame sizeType

    Standard or specific diagram no.

    Manufacturing no.

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 1Installation

    19982002 Schneider Electric All Rights Reserved 7

    UNPACKING

    MP08 to MP30 and MC08 to MC32 Fixed-mounted Circuit BreakersThe circuit breaker stationary assembly is secured to its shipping pallet with four bolts, nuts and washers. However, on the drawout mounting, withdrawal of the circuit breaker is required to access the hardware.Disconnect and remove the circuit breaker from the stationary assembly (refer to Disconnection Instructions, page 20).

    Drawout-mounted Circuit Breaker with Stationary Assembly

    Figure 3: Unpacking Drawout-mounted Circuit Breaker

    Drawout-mounted Circuit Breaker without Stationary AssemblyCircuit breaker is delivered upside down. Place another pallet next to shipping pallet. Rotate circuit breaker onto terminals, then onto its bottom on other pallet.

    Figure 4: Unpacking Drawout-mounted Circuit Breaker Delivered without Stationary Assembly

    0631

    3223

    Connected

    Disconnected

    0631

    3225

    0631

    3226

    0631

    3224

    Remove four bolts, nuts and washers.

    Remove four bolts, nuts and washers.

    0631

    3227

    0631

    3228

    0631

    3231

    0631

    3232

    Remove four bolts, nuts and washers.

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 1Installation 01/2002

    19982002 Schneider Electric All Rights Reserved8

    Stationary Assembly OnlyIf present, remove strapping tape holding the clusters.

    Figure 5: Unpacking Stationary Assembly

    MP40 to MP63 Drawout-mounted Circuit Breakers

    1. Remove four bolts, nuts and washers.2. Position another pallet and rotate circuit

    breaker.3. Remove plastic shipping caps.

    Figure 6: Unpacking Stationary Assembly

    Remove four bolts, nuts and washers.06

    3132

    29

    0631

    3230

    0631

    3233

    1

    2 1 2

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 1Installation

    19982002 Schneider Electric All Rights Reserved 9

    HANDLING

    MP08 to MP30 and MC08 to MC20 Circuit Breakers

    Both the circuit breaker frame and stationary assembly have notched lifting flanges for lifting. To reduce the total weight and ease installation of the stationary assembly, remove the circuit breaker from the stationary assembly (refer to Disconnecting Instructions, page 20). To lift the circuit breaker using a lifting device, use an overhead lifting device attached to the lifting flanges.

    DANGERHAZARD OF CIRCUIT BREAKER FALLING Be sure equipment has adequate lifting

    capacity for the unit being lifted. Follow manufacturers instructions for use of

    lifting equipment. Wear hard hat, safety shoes and heavy

    gloves.

    Failure to follow this instruction will result in death or serious injury.

    Table 1: 3-pole Circuit Breaker Weights

    Circuit Breaker Type

    Stationary Assemblylbs. (kg)

    Circuit Breakerlbs. (kg)

    Terminals

    lbs. (kg)MP08 51 (23) 102 (46) 13 (6)*MP12 51 (23) 102 (46) 13 (6)*MP16 51 (23) 102 (46) 13 (6)MP20 60 (27) 121 (55) 36 (16)MP25 110 (50) 176 (80) 89 (40)MP30 110 (50) 176 (80) 89 (40)MC08 51 (23) 102 (46) 13 (6*)MC16 51 (23) 102 (46) 13 (6)MC20 60 (27) 121 (55) 36 (16)*Optional terminals.

    Figure 7: Using the Lifting Flanges

    Figure 8: Using a Lifting Sling

    0631

    3234

    Circuit Breaker Stationary assembly

    0631

    3235

    Cable slings 0.40 in. (10 mm) dia. max.

    Circuit Breaker Stationary assembly

    CAUTIONHAZARD OF EQUIPMENT DAMAGEDo not let the forks of a fork lift protude past the rear of the circuit breaker.Failure to follow this instruction can result in equipment damage.

    Figure 9: Using an Electrical or Mechanical Platform Lift

    0631

    3236

    Circuit Breaker

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 1Installation 01/2002

    19982002 Schneider Electric All Rights Reserved10

    MC32 Circuit BreakersThe circuit breaker and its stationary assembly have lifting flanges for lifting. Before handling the circuit breaker, remove it from the stationary assembly. To lift the circuit breaker as shown, use an overhead lifting device attached to the notched lifting flanges.

    DANGERHAZARD OF CIRCUIT BREAKER FALLING Be sure equipment has adequate lifting

    capacity for the unit being lifted. Follow manufacturers instructions for use of

    lifting equipment. Wear hard hat, safety shoes and heavy

    gloves.

    Failure to follow this instruction will result in death or serious injury.

    Figure 10: Using a Lifting Sling for Circuit Breaker

    0631

    3237

    Compensation bar not supplied; hooks supplied upon request.

    Table 2: 3-pole Circuit Breaker Weights

    Type StationaryAssembly

    Circuit Breaker

    Terminals

    lbs. (kg) lbs. (kg) lbs. (kg)MC32 132 (60) 198 (90) 88 (40)

    Figure 11: Using a Lifting Sling for Stationary Assembly

    0631

    3238

    Cable slings: 0.40 in.[10 mm] dia. max.

    Rod dia.: 0.48 in. [12 mm]

    CAUTIONHAZARD OF EQUIPMENT DAMAGEClearance inside the switchboard is minimal. To avoid damage to the load terminals, be sure they clear the lower edge of the switchboard enclosure before attempting installation.Failure to follow this instruction can result in equipment damage.

    Figure 12: Using an Electrical or Mechanical Platform Lift

    Assembly

    3.92 in. (100 mm) max.

    H = 22 in.(559 mm)

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 1Installation

    19982002 Schneider Electric All Rights Reserved 11

    MP40 to MP63 and MC40 to MC50 Circuit Breakers

    To lift the circuit breaker as shown below, use an overhead lifting device attached to the notched lifting flanges. Compensation bars not supplied, hooks can be supplied upon request.

    DANGERHAZARD OF CIRCUIT BREAKER FALLING Be sure equipment has adequate lifting

    capacity for the unit being lifted. Follow manufacturers instructions for use of

    lifting equipment. Wear hard hat, safety shoes and heavy

    gloves.

    Failure to follow this instruction will result in death or serious injury.

    Figure 13: Using a Lifting Sling for Circuit Breaker

    0631

    3240

    Cable slings: 0.40 in. [10 mm] dia. max. 30 in. [800 mm] min.

    Table 3: 3-pole Circuit Breaker Weights

    Type StationaryAssembly

    Circuit Breaker

    Terminals

    lbs (kg) lbs (kg) lbs (kg)MP40 198 (90) 264 (120) 88 (40)MP50 198 (90) 264 (120) 177 (80)MP63 242 (110) 308 (140) 177 (80)MC40 198 (90) 264 (120) 88 (40)MC50 198 (90) 264 (120) 177 (80)

    Figure 14: Using a Lifting Sling for Stationary Assembly06

    3132

    41

    Cable slings: 0.40 in. [10 mm] dia. max. 30 in. [800 mm] min.

    CAUTIONHAZARD OF EQUIPMENT DAMAGE Do not let the forks of a fork lift protude past

    the rear of the circuit breaker. Place a chock as shown. Remove it as soon

    as the forks lean on the switchboard floor.Failure to follow this instruction can result in equipment damage.

    Figure 15: Using an Electrical or Mechanical Platform Lift

    0631

    3239

    0631

    3239

    Frame Stationary assembly

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 1Installation 01/2002

    19982002 Schneider Electric All Rights Reserved12

    MF12, MF20 and MF30 Circuit BreakersTo lift the circuit breaker as shown, use an overhead lifting device attached to the notched lifting flanges. Compensation bar not supplied, hooks supplied upon request.

    DANGERHAZARD OF CIRCUIT BREAKER FALLING Be sure equipment has adequate lifting

    capacity for the unit being lifted. Follow manufacturers instructions for use of

    lifting equipment. Wear hard hat, safety shoes and heavy

    gloves.

    Failure to follow this instruction will result in death or serious injury.

    Figure 16: Using a Lifting Sling (MF12 and MF20 Circuit Breakers)

    1

    0631

    3243

    1

    Cable slings: 0.40 in. [10 mm] dia. max.

    CAUTIONHAZARD OF EQUIPMENT DAMAGEClearance inside the switchboard is minimal. To avoid damage to the load terminals, be sure they clear the lower edge of the switchboard enclosure before attempting installation.Failure to follow this instruction can result in equipment damage.

    Figure 17: Using a Lifting Sling (MF30 Circuit Breaker)

    0631

    3245

    Cable slings: 0.40 in. [10 mm] dia. max.

    Table 4: 3-pole Circuit Breaker Weights

    Typelbs. (kg)

    Circuit Breaker lbs. (kg)

    Terminalslbs. (kg)

    MF12 121 (55) 58 (26)MF20 176 (80) 76 (34)MF30 264 (120) 187 (85)

    Figure 18: Using an Electrical or Mechanical Platform Lift (Fixed-mounted MF12, MF20 and MF30 Circuit Breaker)

    0631

    3246

    Use a sling to support the circuit breaker.

    H = 21 in.[533 mm]H = 25 in.[635 mm]

    MF12 Circuit Breaker

    MF20 and MF30 Circuit Breakers

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 1Installation

    19982002 Schneider Electric All Rights Reserved 13

    ATTACHING REAR TERMINALSTable 5: Circuit Breaker Types and Attachment

    Drawout Circuit Breakers Fixed Circuit Breakers Attaching Rear Terminals*MP08, MP12, MP16 and MC08 to MC16

    MP08, MP12, MP16

    MP20 and MC20 MP20

    MP25 to MP32 MP25 to MP32

    MP40 and MC40

    MP50, MP63 and MC50 MP50, MP63 and MC50

    *Rear terminal must be installed on fixed-mounted and drawout-mounted circuit breakers rated 1600 A and above. The terminals provided with the circuit breaker must be mounted as indicated.

    0631

    3248

    0631

    3248

    0631

    3247

    Screws: M10, 2-2/5 in. [60 mm] long.Tightening torque = 375 lb-in (42 Nm).Use 11/16 in. hex-head wrench.

    0631

    3249

    0631

    3249

    0631

    3250

    0631

    3250

    0631

    3250

    Screws: M10, 2-2/5 in. [60 mm] long.Use 11/16 in. hex-head wrench.Tightening torque = 375 lb-in. (42 Nm).

    Fixed-mounted

    Drawout-mounted

    0631

    3254

    or

    0631

    3254

    or

    0631

    3255

    0631

    3255

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 1Installation 01/2002

    19982002 Schneider Electric All Rights Reserved14

    MOUNTINGDistribute weight of the equipment uniformly over a rigid mounting surface (such as crossbeams or a metal floor).The mounting plate should be perfectly flat. This eliminates any risk of deformation which could interfere with correct operation of the circuit breaker.

    Cable ConnectionIt is essential that mechanical stresses are not applied to the circuit breaker terminal pads if a cable connection is used. Vertical terminal pads are recommended, and should be installed as indicated below.

    With bus bar extensions: if the circuit has only a single cable, use method (A). if the circuit has several cables, use method similar to (B).

    In all cases, the same general rules apply for cables that apply for bus bars: position cable ends correctly before the bolts are inserted, and attach cables securely to framework (C).

    \

    CAUTIONHAZARD OF EQUIPMENT DAMAGEDistribute weight over a rigid mounting surface.Failure to follow this instruction can result in equipment damage. Figure 19: Weight Distribution on Mounting Plate

    0631

    3259

    DANGERHAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION This equipment must be installed and

    serviced only by qualified electrical personnel.

    Turn off all power supplying this equipment before working on or inside equipment.

    Always use a properly rated voltage sensing device to confirm power is off.

    Replace all devices, doors and covers before turning on power to this equipment.

    Failure to follow this instruction will result in death or serious injury.

    CAUTIONHAZARD OF EQUIPMENT DAMAGECarefully follow all instructions for making electrical connections and supporting and clamping bus bars.Failure to follow this instruction can result in equipment damage.

    Figure 20: Cable Connections

    0631

    3260

    A

    C

    B

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 1Installation

    19982002 Schneider Electric All Rights Reserved 15

    Bus Bar ConnectionBus bar dimensions shown in Table 6, Bus Bars have been extrapolated from test data based on UL 891. They should be used only as a guide and not replace industrial experience or a temperature rise test.

    Correct clamping of bus bars depends on, among other things, the torque used to tighten the nuts and bolts. Excessive torque may cause the same problems as insufficient torque.

    The bus bars should be adjusted to ensure that the mounting holes (A, see Figure 21, page 15) are aligned with the terminal pads before the bolts are inserted. The bus bar is held by support (B) which is attached to the framework of the switchboard, so that the terminal pads do not have to support the weight of the bus bar. Dimension (C) must be maintained (Table 7, next page) to withstand the electrodynamic stresses between phases in the event of a short circuit.

    DANGERHAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This equipment must be installed and

    serviced only by qualified electrical personnel.

    Turn off all power supplying this equipment before working on or inside equipment.

    Always use a properly rated voltage sensing device to confirm power is off.

    Replace all devices, doors and covers before turning on power to this equipment.

    Failure to follow this instruction will result in death or serious injury.

    Table 6: Bus Bars

    Circuit Breaker Copper Bus Bars

    Quantity Dimension in. (mm)MP08, MC08 1 0.25 x 3.00 (6 x 76)MP12 2 0.25 x 3.00 (6 x 76)MP16, MC16 2 0.25 x 3.00 (6 x 76)MP20, MC20 2 0.25 x 4.00 (6 x 102)MP25 2 or 4 0.25 x 5.00 (6 x 127)

    0.25 x 2.50 (6 x 64)MP30 4 or 3 0.25 x 4.00 (6 x 102)

    0.25 x 6.00 (6 x 152)MC32 3 0.25 x 6.00 (6 x 152)MP40, MC40 4 or 5 0.25 x 5.00 (6 x 127)

    0.25 x 4.00 (6 x 102)MP50, MC50 6 or 5 0.25 x 5.00 (6 x 127)

    0.25 x 6.00 (6 x 152)MP63 6 0.25 x 6.00 (6 x 152)

    Table 7: Tightening Torque

    Tightening Torque

    Bolt Size Hole Diameter Grooved or Flat Washer Belleville Washer0.38 in. (10mm) 0.44 in. (11mm) 28 lb-ft (38 Nm) 31 lb-ft (43 Nm)

    CAUTIONHAZARD OF EQUIPMENT DAMAGECarefully follow all instructions for making electrical connections and supporting end clamping bus bars.Failure to follow this instruction can result in equipment damage.

    Figure 21: Bus Bar Connection

    0631

    3261

    *Dimension C is the maximum distance between circuit breaker horizontal terminals (connection point of the extensions) and the first support or spacer, based on the expected short-circuit current (see Table 8, page 16).

    A B

    C*

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 1Installation 01/2002

    19982002 Schneider Electric All Rights Reserved16

    CONTROL WIRING

    Connect each terminal using one stranded #18 to #14 AWG (0.6 to 2.5 mm2) copper wire. Cable strip length: 3/8 in. (9mm).

    Fixed-mounted Circuit Breakers 1. Install conductor.

    2. Remove transparent shield.

    Table 8: Bus Bar Connection

    Expected Short-circuit Current (kA rms)30 50 65 80 100 150

    MP08 to MP16 and MC08 to MC16 Circuit BreakersDimension C in.

    (mm)13.75(350)

    11.88(300)

    9.88(250)

    7.89(200)

    6.00(150)

    6.00(150)

    MP20 to MP63 and MC20 to MC50 Circuit BreakersDimension C in.

    (mm)13.75(350)

    11.89(300)

    9.88(250)

    7.88(200)

    7.88(200)

    7.88(200)

    DANGERHAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION This equipment must be installed and

    serviced only by qualified electrical personnel.

    Turn off all power supplying this equipment before working on or inside equipment.

    Always use a properly rated voltage sensing device to confirm power is off.

    Replace all devices, doors and covers before turning on power to this equipment.

    Failure to follow this instruction will result in death or serious injury.

    0631

    3262

    11

    2

    0631

    3262

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 1Installation

    19982002 Schneider Electric All Rights Reserved 17

    3. Connect control wires according to wiring diagrams shown on the label. Use a small screwdriver to open the spring clips and install wires. Wiring diagrams are also located at the end of this bulletin.

    4. Route control wires away from the arc chutes. Replace the transparent cover.

    Drawout-mounted Circuit Breakers 1. Remove the front terminal cover.

    2. Determine the terminal number (1) according to the wiring label (2). Wiring diagrams are also located at the end of this bulletin.

    0631

    3262

    1 1

    2

    3

    3

    2

    CAUTIONHAZARD OF EQUIPMENT DAMAGEDo not route control wires close to the arc chutes venting holes. If this is done, wire insulation may melt and/or softening occur during circuit breaker interruption.Failure to follow this instruction can result in equipment damage.

    0613

    3263

    0613

    3263

    2

    1

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 1Installation 01/2002

    19982002 Schneider Electric All Rights Reserved18

    3. Connect the control wires using a small screwdriver and replace the front terminal cover.

    4. Route control wires away from arc chutes.

    0631

    3264

    F1 F2

    WT FV R

    Z C MNR

    Z11

    Z12

    Z21

    Z22

    e+ e- D4

    D1

    254

    262

    or2nd MX

    C12

    C11

    orMX XF MN PAF MCH OF1 OF2 OF3 OF4

    T1 T2 V V R1

    R2 C or

    F F O O SDE LT alarm

    211

    212

    221

    222

    241

    244

    231

    234

    81 82 LR1

    LR2

    84 C2 C1 A4 A1 D4 D1

    252

    251

    262

    B4 B1 14 11 12 24 21 22 34 31 32 44 41 42254

    Accessories (Right-hand Side)Control Unit (Left-hand Side)

    1

    2

    3

    1

    3

    2

    CAUTIONHAZARD OF EQUIPMENT DAMAGEDo not let wires interfere with action of the disconnecting block.Failure to follow this instruction can result in equipment damage.

    0631

    3265

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 2Operation

    19982002 Schneider Electric All Rights Reserved 19

    SECTION 2 OPERATION

    DISCONNECTING AND CONNECTING INSTRUCTIONS. The circuit breaker has four drawout positions and can be operated in all four

    positions. The circuit breaker is captive in all positions except WITHDRAWN.

    A closed circuit breaker is automatically opened prior to being connected or disconnected during a racking in or racking out operation.

    Connection or disconnection of the circuit breaker requires insertion of the racking crank. Insertion of the racking crank can be prevented by the following stationary assembly accessories: Padlock Key lock Racking interlock

    Disconnecting and connecting instructions are summarized on the label provided with the installation instructions. The label must be affixed to the door of the switchboard.

    In the CONNECTED position, the primary and secondary disconnecting terminals are engaged, and the circuit breaker is ready for service.

    In the TEST position, the primary terminals are disengaged, however, control contacts are connected to permit operation of the circuit breaker. The TEST position is used for testing circuit breaker operation and control system functions. In this position, the circuit breaker is not suitable for internal inspection or any maintenance function.

    In the DISCONNECTED position, the primary and secondary disconnect terminals are disengaged and separated by a safe distance from the corresponding stationary terminals.

    In the WITHDRAWN position, both primary and secondary contacts are disconnected. The circuit breaker may be removed for complete accessibility.

    When a racking crank remains inserted or a circuit breaker is not completely disconnected, the extraction of the right rail is prevented.

    0631

    3266

    CONNECTED position

    TEST position

    DISCONNECTED position

    WITHDRAWN position

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 2Operation 01/2002

    19982002 Schneider Electric All Rights Reserved20

    Disconnecting Instructions

    If the circuit breaker is not opened before disconnecting, it will open automatically during disconnection.

    1. Remove the racking crank from its storage hole, insert it into the racking slot, and engage the mechanism.

    In the case of a racking interlock, press the compartment door closed sensor located at the front of the drawout mechanism to simulate a closed door.

    2. To reach the DISCONNECTED position, turn the racking crank counterclockwise until first the TEST, and then DISCONNECTED indication are shown on the position indicator.

    3. Remove the racking crank and insert it into the storage hole.

    If the racking crank is not removed, the right rail will not fully extend.

    4. Using the two extension rail handles, pull the circuit breaker out.5. Remove the circuit breaker using one of the lifting methods explained in

    Handling, page 9.

    DANGERHAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This equipment must be installed and

    serviced only by qualified electrical personnel.

    Turn off all power supplying this equipment before working on or inside equipment.

    Always use a properly rated voltage sensing device to confirm power is off.

    Replace all devices, doors and covers before turning on power to this equipment.

    Failure to follow this instruction will result in death or serious injury.

    0631

    3267

    1 2

    connected

    test

    disconnected

    0631

    3267

    0631

    3267

    es

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 2Operation

    19982002 Schneider Electric All Rights Reserved 21

    Installing the Circuit Breaker in the Stationary Assembly

    1. Pull out the two extension rails by their handles.

    When either the racking crank remains inserted in the racking slot or the circuit breaker is not fully disconnected, extraction of the right extension rail is not possible.

    2. Install the circuit breaker onto both extension rails, being sure that the two circuit breaker supports located on either side are fully engaged in the rail slots. Refer to Handling, page 9, for methods of lifting the circuit breaker.

    3. To move the circuit breaker from the WITHDRAWN position to the DISCONNECTED position, push the extension rail handles into the stationary assembly until they stop.

    0631

    3268

    CAUTIONHAZARD OF EQUIPMENT DAMAGEDo not let the forks of a fork lift protrude past the rear of the circuit breaker.Do not press on the control unit while pushing the circuit breaker into the stationary assembly.Failure to follow this instruction can result in equipment damage.

    0631

    3268

    0631

    3268

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 2Operation 01/2002

    19982002 Schneider Electric All Rights Reserved22

    Connecting Instructions

    1. Insert and engage racking crank into the racking slot.NOTE: This procedure is possible only if: circuit breaker is in DISCONNECTED position, drawout mechanism padlocks have been removed, key interlock has been unlocked and compartment door is closed.

    In case of racking interlock, press the compartment door closed sensor located at the drawout mechanism to simulate a closed door.

    2. Turn the racking crank clockwise until the CONNECTED position is reached on the position indicator. Continue cranking until two click sounds are heard indicating the circuit breaker is locked in the connected position.

    As the CONNECTED position is neared, more effort will be required to turn the crank.

    3. Remove the racking crank and insert it back into the storage hole.

    DANGERHAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This equipment must be installed and

    serviced only by qualified electrical personnel.

    Turn off all power supplying this equipment before working on or inside equipment.

    Always use a properly rated voltage sensing device to confirm power is off.

    Replace all devices, doors and covers before turning on power to this equipment.

    Failure to follow this instruction will result in death or serious injury.

    0631

    3267

    1 2

    0631

    3269

    0631

    3269 1

    2

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 2Operation

    19982002 Schneider Electric All Rights Reserved 23

    OPERATING

    Charging Instructions All basic circuit breaker and drawout operations can be performed from the front of the circuit breaker. Suitable electrical and mechanical interlocks are provided to prevent incorrect operation of the circuit breaker. To manually charge an electrically- or manually-operated circuit breaker, push or pull down on the charging handle, six full strokes should be used. When the spring is fully charged, the yellow charged indicator will appear in the stored-energy window on the circuit breaker front cover, the handle stops, and it will return to normal position when released.

    Closing Instructions All that is required to close the circuit breaker locally is to push the mechanical push ON button. Pre-charged circuit breakers may be closed remotely via a spring-released solenoid which is standard for electrically operated circuit breakers and optional for manually-operated circuit breakers. Before attempting to close the circuit breaker locally, the stored-energy indicator window must show a yellow charged.''

    Circuit breaker can be closed only if: It is opened It is charged Pop-out type fault indicator is correctly reset No remote opening order is intended.

    The closing coil (XF) withstands a continuous voltage, providing anti-pumping function. If the circuit breaker is not ready to close when the closing order is intended, inhibit it and try again as soon as the circuit breaker is ready to close. To inhibit the anti-pumping function, wire in series the ready-to-close switch (terminals 251-252) with the closing coil.

    0631

    3270

    Manual Charging Electrical Charging

    ON

    0631

    3271

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 2Operation 01/2002

    19982002 Schneider Electric All Rights Reserved24

    Opening Instructions Opening the circuit breaker locally is accomplished by pushing the mechanical push OFF button on the circuit breaker front cover. Circuit breakers may be opened remotely via either a shunt trip or an undervoltage trip device depending upon the application requirements.

    Resetting InstructionsThe mechanical fault indicator (push to reset button) extends to indicate that an overcurrent has occurred and prevents closure of the circuit breaker. Reset by pushing button in.

    LOCKING

    Locking by Key Interlock

    This locking can be in DISCONNECTED position or in all positions: CONNECTED, TEST and DISCONNECTED (upon request).Figure 23: Locking by Key Interlock (VSKC)

    Locking in the DISCONNECTED position:

    1. Disconnect the circuit breaker,2. insert key and turn counterclockwise and3. remove the key.

    OFF

    0631

    3272

    CAUTIONHAZARD OF EQUIPMENT DAMAGEResetting the circuit breaker with an existing overcurrent or ground-fault condition can result in destructive arcing. Be sure any existing faults are cleared prior to resetting.Failure to follow this instruction can result in equipment damage.

    0631

    3273

    Figure 22: Locking by Key Interlock (VSKA)

    OFF

    2

    1

    3Locking in open position:1. Push the push OFF button2. Insert and turn the key counterclockwise3. Remove the key

    2

    3

    0631

    3276

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 2Operation

    19982002 Schneider Electric All Rights Reserved 25

    Locking by Padlock Figure 24: Locking by Padlock (VBP)

    Prevent access to: push OFF (switch open) or push ON (switch close) or both push OFF and push ON buttons of the circuit breaker by attaching a padlock.Figure 25: Locking by Padlock Device (Standard)

    This locking prevents insertion of the racking crank and racking the circuit breaker into its stationary assembly.Figure 26: Locking by Padlocking Device

    Locking by Door Interlock Figure 27: Locking by Door Interlock (VDP)

    The door interlock prevents the door from opening when the circuit breaker is in the CONNECTED and TEST positions.

    sh OFFO ush ON

    I

    O

    sh OFF

    I

    ush ON

    0631

    3275

    Shackle diameter:1/4 to 5/16 in.[6 to 8 mm]

    1 2

    0631

    3277

    Shackle diameter: 1/4 to 5/16 in. [6 to 8 mm]

    0631

    3280

    0631

    3278

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 2Operation 01/2002

    19982002 Schneider Electric All Rights Reserved26

    The hook can be mounted on either side. To change hook location:

    Spring Interlock Figure 28: Spring Charged Interlock

    Before pulling out the circuit breaker, discharge the spring by pressing the push ON button, then the push OFF button.

    When the closing springs are charged, this interlock prevents the circuit breaker from being disconnected by latching it in the stationary assembly. Use of this locking method is not suitable with an undervoltage trip device.

    0631

    3279

    AB AB

    1

    2

    0631

    3281

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 3Control Unit Types

    19982002 Schneider Electric All Rights Reserved 27

    SECTION 3 CONTROL UNIT TYPES

    Opush OFF

    MERLIN GERIN

    MP20H1

    masterpact

    connected

    test

    disconnected

    O OPENdischarged

    Ipush ON

    circuit breaker3 pole600V 50/60Hz

    frame size 2000A

    suitable for continious operation

    at 100% rating in a minimum cubical

    space H17.5 by W21 by D14.1/4 inches

    ventilation is not required

    interrupting ratingmax RMS sym amp

    s

    Volts240480600

    short time rating 75KA

    Amps75K75K75K

    IEC 957-2 690V 50/60Hz

    interrupting ratingIcu 380/440V

    75KA

    660V 75KA

    Icu 380/440V 75KA

    660V 75KA

    short time ratingIcw=75KA 0.5 s

    ec.

    push to reset

    I

    I1 I2 I3

    90%

    50%

    20%

    STR 58 U

    Ir

    90

    105%Ir

    .88.9 .92

    .95

    .981

    .8.85

    xIo

    Im tm

    34 5

    6

    8101.5

    2

    xIo

    .3.4 .3

    .1

    .1.2

    on I2t off

    .2

    0

    Ir fault

    tr

    Im faulttm

    I

    faultIh

    th

    t

    i

    test

    + S

    T +

    T

    F

    Ih th

    400500 600

    800

    1000

    1200250320

    A

    .3.4 .4

    .2

    .1.2

    on I2t off

    .3

    .1

    I

    off2xIn

    Ir :

    Im :

    th :

    IIG LI

    GL

    LG

    LIG

    off

    reset V

    tr60

    120 240

    480

    1530

    at 1,5Ir

    4

    68 12

    17

    22

    Ic1 Ic2

    .86

    .9 .93.95

    .98

    1.8

    .85

    .7.8 .85

    .95

    .5.6

    xIr

    .9

    1

    R

    xIr

    test

    Io=3000A

    cat. no. 54775

    for masterpactwith sensors In

    = 6000A

    E63335UND. LAB. O List.CIRCUIT BREAKE

    R

    Doles. Issue N LM-879200000

    0631

    3282

    Io = Rating plugln = Sensor ratinglr = Long-time pickuptr = Long-time delaylm = Short-time pickuptm = Short-time delayl = Instantaneous pickup

    lh = Ground-fault pickupth = Ground-fault delay

    I8

    12 1419

    22max2

    4

    xIn

    push to reset

    STR 18 M

    test

    +

    push to reset

    II1 I2 I390%

    50%

    20%

    STR 28 D

    90

    105%Ir

    .88.9 .92

    .95

    .981.8

    .85

    xIoIm

    34 5

    6

    8101.5

    2

    xIr

    Ir

    Im

    t

    i

    test

    +

    Ir :

    Im :

    Ir

    push to reset

    II1 I2 I390%

    50%

    20%

    STR 38 S

    Ir90

    105%Ir

    .88.9 .92

    .95

    .981.8

    .85

    xIoIm tm

    34 5

    6

    8101.5

    2

    xIr

    .3.4 .3

    .1.1

    .2

    on I2t off

    .2

    0

    Ir fault

    tr

    Im faulttm

    I

    faultIh

    th

    t

    i

    test

    +

    +

    T

    F

    test

    Ih th

    400500 600

    800

    10001200250

    320

    A

    .3.4 .4

    .2.1

    .2

    on I2t off

    .3

    .1

    I

    offmax.xIn

    Ir :

    Im :

    th :

    overcurrent

    ground

    push to reset I+T L+IIL+T

    L offT

    L+I+T

    II1 I2 I390%

    50%

    20%

    STR 58 U

    Ir tr90

    105

    tr

    %Ir.88

    .9 .92.95

    .981.8

    .85

    xIo

    60120 240

    48015

    30

    at 1.5Ir

    Im tm3

    4 56

    8101.5

    2

    xIr

    .3.4 .3

    .1.1

    .2

    on I2t off

    .2

    0

    Ir fault

    tr

    Im faulttm

    I

    faultIh

    th

    t

    i

    test

    +

    +

    T

    R

    F

    test

    Ih 1200A Max th400

    500 600800

    10001200250

    320

    A

    .3.4 .4

    .2.1

    .2

    on I2t off

    .3

    .1

    I8

    12 1419

    22Max.2

    4

    xIn

    Ic1 Ic2.86

    .9 .93.95

    .981.8

    .85

    xIr

    .7.8 .85

    .95.5

    .6

    .9

    1xIr

    V

    Ir :

    Im :

    th :

    min.norm

    overcurrent

    ground

    reset V

    0631

    3283 STR 18 M

    Control UnitOvercurrent protection

    Instantaneous

    Options

    None

    STR 28 DControl Unit

    Overcurrent protection

    Long-time Instantaneous

    Options

    Ammeter

    STR 38 SControl Unit

    Overcurrent protection

    Long-time Short-time Instantaneous

    Options

    Ammeter Fault Indicators Ground-fault Protection

    STR 58 UControl Unit

    Overcurrent protection

    Long-time Short-time Instantaneous

    Options

    Ammeter Fault Indicators Ground-fault Protection Zone-selective interlocking Load Monitoring Communication

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 3Control Unit Types 01/2002

    19982002 Schneider Electric All Rights Reserved28

    STR 18 M CONTROL UNITDescription

    1. Fault trip indicator reset button prevents reclosing of circuit breaker after fault until reset.

    2. Current sensor rating (ln)3. Instantaneous setting (can be turned OFF on

    N1 and H1 circuit breakers)4. Test the receptacle5. Lock the control unit settings

    (captive nuts)

    push to reset

    STR 18 M

    test

    +

    I8

    12 1419

    22max2

    4

    xIn

    I8

    12 1419

    22max2

    4

    xIn

    0631

    3284

    1

    2

    3

    5

    4

    5

    SettingsInstantaneous Pickup (short-circuit)

    BU ME

    PBD

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 3Control Unit Types

    19982002 Schneider Electric All Rights Reserved 29

    1. Before energizing main circuits, open and discharge circuit breaker.

    2. Adjust control unit.

    3. Close circuit breaker.

    4. Test the control unit.

    connected

    test

    dischargedpush

    OFFO pu

    sh ONI

    OFF

    disconnected

    0631

    3285

    I6 8 1217

    22Max.2

    4

    push to reset

    STR 18 M

    I

    xIn

    0631

    3286

    In=2000 A

    2000 AIn (Example)

    N1-H1(8003200 A)

    2 8

    2 8

    N1-H1(40005000 AH2

    off

    Max

    I = 8 x In = 16000 A

    I 2 to Max

    connected

    test

    push OFF

    O push ON

    I

    ON

    disconnected

    0631

    3287

    push to reset

    STR 18 M

    I

    xIn

    MERLIN GERIN

    I

    xIn

    test+

    BU ME

    0631

    3288 The complete test kit can

    simulate a short circuit.

    With the mini test kit

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 3Control Unit Types 01/2002

    19982002 Schneider Electric All Rights Reserved30

    STR 28 D CONTROL UNITDescription

    1. Fault trip indicator reset button prevents reclosing circuit breaker after fault until reset

    2. Measure the current3. Indicates the rate of load (%tr)4. Current sensor rating (In)5. Rating plug (Io)6. Adjust lf (long-time setting)7. Adjust Im (instantaneous)8. Overload indicator9. Control unit setting values10. Test the control unit11. Lock the control unit settings

    push to reset

    II1 I2 I390%

    50%

    20%

    STR 28 D

    90

    105%Ir

    .88.9 .92

    .95

    .981.8

    .85

    xIoIm

    34 5

    6

    8101.5

    2

    xIr

    Ir

    Im

    t

    i

    test

    +

    Ir :

    Im :

    Ir

    .88.9 .92

    .95

    .981.8

    .85

    xIoIm

    34 5

    6

    8101.5

    2

    xIr

    Ir

    0631

    3289 Settings

    AdjustableIr Long-time setting (overload)Im Instantaneous setting (short-circuit)

    Fixedtr Long-time delay

    OptionsOption

    I see page 38

    1

    2

    3

    4

    115

    6

    7

    89

    1011

    I

    I

    ALR

    BU ME

    PBD

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 3Control Unit Types

    19982002 Schneider Electric All Rights Reserved 31

    1. Before energizing main circuits, open and discharge circuit breaker.

    2. Adjust control unit.

    3. Close circuit breaker.

    4. Test the control unit.

    connected

    test

    dischargedpush

    OFFO pu

    sh ONI

    OFF

    disconnected

    0631

    3285

    Io0.63 0.8

    10.5

    I.88

    .9 .92.95.98

    1.8.85

    ImI = 2000 A

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 28 D

    Ir

    xIoIm

    xIot

    i

    test

    I3

    4 568

    101.52

    r

    m

    n

    0631

    3290

    Io = 1600 A

    Example: In = 2000 A; Io = 1600 A; Ir = 1440 A; Im = 7200 A

    2000 A

    1600 A

    In

    Io

    Ir

    Im

    0.8 0.55 0.88 0.90 0.93 0.95 0.98 1.0

    1.5 2.0 3.0 4.0 5.0 6.0 8.0 10.0

    Ir = 0.90 x Io = 1440 A

    Im = 5 x Ir = 7200 A

    Ir

    Im

    0.8 to 1 Io

    1.5 to 10 Ir

    connected

    test

    push OFF

    O push ON

    I

    ON

    disconnected

    0631

    3287

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 28 D

    Ir

    xIoIm

    xIot

    i

    test

    xIot

    i

    MERLIN GERIN

    test+

    MEBU

    0631

    3291

    The complete test kit can simulate:an overloada short-circuit

    With the Mini Test Kit

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 3Control Unit Types 01/2002

    19982002 Schneider Electric All Rights Reserved32

    STR 38 S CONTROL UNITDescription

    1. Fault trip indicator reset button prevents reclosing circuit breaker after fault until reset.

    2. Measure the current.3. Indicates the rate of load (%tr)4. Current sensor rating (In)5. Overload indicator6. Rating plug (Io)7. Adjust Ir (long-time setting)8. Adjust Im (short-time setting)9. Adjust tm (short-time delay)10. Control unit setting values11. Switch on or off the instantaneous

    protection (N1/H1 type only)12. Adjust Ih

    (ground-fault protection)13. Adjust th

    (ground-fault protection delay)14. Fault trip indicator15. Test the control unit16. Lock the control unit settings17. Save fault trip indicator18. Clear fault trip indicator

    and / or check battery level19. Recall the latest fault

    trip indicator

    push to reset

    II1 I2 I390%

    50%

    20%

    STR 38 S

    Ir90

    105%Ir

    .88.9 .92

    .95

    .981.8

    .85

    xIoIm tm

    34 5

    6

    8101.5

    2

    xIr

    .3.4 .3

    .1.1

    .2

    on I2t off

    .2

    0

    Ir fault

    tr

    Im faulttm

    I

    faultIh

    th

    t

    i

    test

    +

    +

    T

    F

    test

    Ih th

    400500 600

    800

    10001200250

    320

    A

    .3.4 .4

    .2.1

    .2

    on I2t off

    .3

    .1

    I

    offmax.xIn

    Ir :

    Im :

    th :

    overcurrent

    ground

    20%

    1

    I

    i

    F

    I

    Ir.88

    .9 .92.95

    .981.8

    .85

    xIoIm tm

    34 5

    6

    8101.5

    2

    xIr

    .3.4 .3

    .1.1

    .2

    on I2t off

    .2

    0

    TIh th

    400500 600

    800

    10001200250

    320

    A

    .3.4 .4

    .2.1

    .2

    on I2t off

    .3

    .1

    I

    offmax.xIn

    I

    F

    T

    W

    0631

    3292

    SettingsAdjustable

    Ir Long-time setting (overload)Im Short-time setting (short-circuit)tm Short-time delay I2t on or off

    OptionsOptionOptionOptionOption

    see page 38see page 39see page 41see page 41

    1

    2

    3

    4

    16567

    89

    101112

    13

    141516

    17

    1819

    I

    I

    ALR

    W T

    W T

    F

    BU ME

    PBD PIL

    + F PIL

    + F PIL

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 3Control Unit Types

    19982002 Schneider Electric All Rights Reserved 33

    1. Before energizing main circuits, open and discharge circuit breaker.

    2. Adjust control unit.

    3. Close circuit breaker.

    4. Test the control circuit.

    connected

    test

    dischargedpush

    OFFO pu

    sh ONI

    OFF

    disconnected

    0631

    3285

    In = 2000 A 0.5 15Im

    34 5

    68

    101.52

    tm.3

    .4.3

    .2

    .10.1

    .2

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 38 S

    Ir

    xIoIm tm

    xIot

    i

    test

    T

    F

    test

    Ih th

    xIn

    I

    xIn

    I

    Io0.63 0.8

    10.5

    Ir.88

    .9 .92.95.98

    1.8.85

    Im tm

    offMax.xIn

    0631

    3293

    lo = 1600 AExample: In = 2000 A; Io = 1600 A; Ir = 1440 A; Im = 7200 A

    2000 A

    1600 A

    In

    Io

    Ir

    Im

    I

    0.8 0.55 0.88 0.90 0.930.95 0.98 1.0

    1.5

    Ir = 0.90 x Io = 1440 A

    2.0 3.0 4.0 5.0 6.0 8.0 10.0

    Im = 5.0 x Ir = 7200 A

    (H1) Max Max Max MaxMax Max Max off

    Ir 0.8 to 1.0 Io

    Im 1.5 to 10.0 Ir

    Max.

    off

    I

    In = 2000 A 0.5 15Im

    34 5

    68

    101.52

    tm.3

    .4.3

    .2

    .10.1

    .2

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 38 S

    Ir

    xIoIm tm

    xIot

    i

    test

    T

    F

    test

    Ih th

    xIn

    I

    xIn

    I

    Io0.63 0.8

    10.5

    Ir.88

    .9 .92.95.98

    1.8.85

    Im tm

    offMax.xIn

    0631

    3293

    Io = 1600 AExample: In = 2000 A; Io = 1600 A; Ir = 1440 A; Im = 7200 A

    2000 A

    1600 A

    In

    IoIr 0.8 0.55 0.88 0.900.93 0.95 0.98 1.0

    Ir = 0.90 x Io = 1440 A

    Im 1.5 2.0 3.0 4.0 5.0 6.0 8.0 10.0

    Im = 5 x Ir = 7200 A

    Ir

    Im

    I H1 Max Max Max Max Max Max Max off I

    0.8 to 1.0 Io

    1.5 to 10.0 Ir

    Max

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 58 U

    Ir

    xIoIm tm

    xIot

    i

    test

    T

    R

    F

    test

    Ih th

    xIn

    I

    xIn

    Ic1 Ic2

    xIr xIr

    tr

    at 1.5Ir

    t

    T

    R

    F

    test

    Ih th

    xIn

    I

    xIn

    Ic1 Ic2

    xIr xIr ground

    overcurrent

    MERLIN GERIN

    test+

    MEBU

    0691

    3298

    connected

    test

    dischargedpush

    OFFO pu

    sh ONI

    OFF

    disconnected

    0631

    3285

    With the Mini Test Kit

    The complete test kit can simulate:an overloada short-circuita ground-fault

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 3Control Unit Types 01/2002

    19982002 Schneider Electric All Rights Reserved34

    STR 58 U CONTROL UNITDescription

    1. Fault trip indicator reset button prevents reclosing of circuit breaker after fault until reset

    2. Select the remote indicated fault trip

    3. Measure the current

    4. Select phase to measure

    5. Indicates the rate of load (%tr)6. Maximum protection rating7. Overload indicator8. Rating plug (Io)9. Adjust lr (long-time setting)10. Adjust tr (long-time delay)11. Adjust lm (short-time setting)12. Adjust tm (short-time delay)13. Decrease thermal memory after tripping14. Adjust I (instantaneous)15. Adjust lh

    (ground-fault protection)16. Adjust th

    (ground-fault protectiondelay)

    17. Control unit setting values18. Adjust Ic2 (load monitoring)19. Adjust Ic1 (load monitoring)

    20. Test the control unit

    21. Save fault trip indicator22. Lock the control unit

    settings

    23. Clear fault trip indicatorand/or check battery level

    24. Recall the latest fault tripindicator

    25. Fault trip indicator

    push to reset I+T L+IIL+T

    L offT

    L+I+T

    II1 I2 I390%

    50%

    20%

    STR 58 U

    Ir tr90

    105

    tr

    %Ir.88

    .9 .92.95

    .981.8

    .85

    xIo

    60120 240

    48015

    30

    at 1.5Ir

    Im tm3

    4 56

    8101.5

    2

    xIr

    .3.4 .3

    .1.1

    .2

    on I2t off

    .2

    0

    Ir fault

    tr

    Im faulttm

    I

    faultIh

    th

    i

    test

    +

    +

    T

    R

    F

    test

    Ih 1200A Max th400

    500 600800

    10001200250

    320

    A

    .3.4 .4

    .2.1

    .2

    on I2t off

    .3

    .1

    I8

    12 1419

    22Max.2

    4

    xIn

    Ic1 Ic2.86

    .9 .93.95

    .981.8

    .85

    xIr

    .7.8 .85

    .95.5

    .6

    .9

    1xIr

    V

    Ir :

    Im :

    th :

    min.norm

    overcurrent

    ground

    reset V

    Ir tr.88

    .9 .92.95

    .981.8

    .85

    xIo

    60120 240

    48015

    30

    at 1.5Ir

    Im tm3

    4 56

    8101.5

    2

    xIr

    .3.4 .3

    .1.1

    .2

    on I2t off

    .2

    0

    T

    R

    Ih 1200A Max th400

    500 600800

    10001200250

    320

    A

    .3.4 .4

    .2.1

    .2

    on I2t off

    .3

    .1

    I8

    12 1419

    22Max.2

    4

    xIn

    Ic1 Ic2.86

    .9 .93.95

    .981.8

    .85

    xIr

    .7.8 .85

    .95.5

    .6

    .9

    1xIr

    I

    F

    C Z

    W

    T

    R

    FV

    0631

    3295

    1

    2

    3

    4

    5

    67

    891011

    12

    1314

    15

    1617

    18

    1920

    21

    22232425

    SettingsAdjustable

    Ir Long-time setting (overload)tr Long-time delayIm Short-time setting (short-circuit)tm Short-time delay I2t on or off

    OptionsThermal memory

    OptionOptionOptionOptionOptionOptionOptionOption

    see page 38see page 39see page 41see page 40see page 41see page 41see page 42see page 42

    limitation function

    see page 37

    FV

    I

    I

    I

    ALR

    W T

    W T

    R

    R

    BU ME

    PIL

    PBD

    + F PIL

    + F PIL

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 3Control Unit Types

    19982002 Schneider Electric All Rights Reserved 35

    1. Before energizing main circuits, open and discharge circuit breaker.

    2. Adjust control unit.

    3. Close circuit breaker.

    4. Test the control unit.

    connected

    test

    dischargedpush

    OFFO pu

    sh ONI

    OFF

    disconnected

    0631

    3285

    I6

    8 121722

    off24

    In = 2000 A

    Io0.63 0.8

    10.5

    Ir.88

    .9 .92.95.98

    1.8.85

    tr60

    120 240

    48015

    30

    Im tm

    0.5 15

    Im3

    4 568

    101.52

    tm.3

    .4.3

    .2

    .10.1

    .2

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 58 U

    Ir tr

    xIo at 1.5IrIm tm

    xIot

    i

    test

    T

    R

    F

    test

    Ih th

    xIn

    I

    xIn

    Ic1 Ic2

    xIr xIrI

    Max.2

    0631

    3296

    Example: In = 2000 A; Io = 1600 A; Ir = 1440 A; Im = 7200 A

    2000 A

    1600 A

    0.8 0.55 0.88 0.90 0.93 0.95 0.98 1.0

    Ir = 0.90 x Io =1440 A

    1.5 2.0 3.0 4.0 6.0 8.0 10.05.0

    Im = 5 x Ir = 7200 A

    (H2)

    In

    Io

    Ir

    Im

    I(H1)

    2

    2

    Max

    off

    Ir

    Im

    I

    0.8 to 1.0 Io

    1.5 to 10.0 Ir

    2 to Max 2 to off

    Io0.63 0.8

    10.5

    Io0.63 0.8

    10.5

    Ir.88

    .9 .92.95.98

    1.8.85

    t60

    120 240

    48015

    30

    Im3

    4 568

    101.52

    tm.3

    .4.3

    .2

    .10.1

    .2

    Ir.88

    .9 .92.95.98

    1.8.85

    tr60

    120 240

    48015

    30

    Im3

    4 568

    101.52

    t.3

    .4.3

    .2

    .10.1

    .2.3

    .1.2

    .4.3

    .2

    .10

    t

    t

    on I2t

    I2t off

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 58 U

    Ir tr

    xIo at 1.5IrIm tm

    xIot

    i

    test

    T

    R

    F

    test

    Ih th

    xIn

    I

    xIn

    Ic1 Ic2

    xIr xIr

    15480 str

    m

    r

    m

    m

    0691

    3297

    tmI2t off

    0 to 0.4 s

    ontm

    2t

    0.1 to 0.3 s

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 58 U

    Ir

    xIoIm tm

    xIot

    i

    test

    T

    R

    F

    test

    Ih th

    xIn

    I

    xIn

    Ic1 Ic2

    xIr xIr

    tr

    at 1.5Ir

    t

    T

    R

    F

    test

    Ih th

    xIn

    I

    xIn

    Ic1 Ic2

    xIr xIr ground

    overcurrent

    MERLIN GERIN

    test+

    MEBU

    0691

    3298

    connected

    test

    dischargedpush

    OFFO pu

    sh ONI

    OFF

    disconnected

    0631

    3285

    With the Mini Test Kit

    The complete test kit can simulate:an overloada short-circuita ground-fault

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 3Control Unit Types 01/2002

    19982002 Schneider Electric All Rights Reserved36

    CONTROL UNIT OPTIONS

    Pre-trip and Overload Indication OptionThe pre-trip and overload indication is standard with all control units except STR 18 M. The overload indicator is a light-emitting diode (LED) which is: On when the current exceeds 90% of the current setting. Flashing on overload when current exceeds 105120% of current

    setting.

    The pre-trip alarm switch is a contact (LR1LR2) which closes when the circuit breaker is in the overload zone. It opens if the load decreases below the overload zone or if the circuit breaker trips.For wiring diagram, see page 46.

    When a dc power source is used, power has to be temporarily disconnected to reset the optical triac contacts.

    ALR

    0.63Io Ir

    0.8

    0.5 1

    xIn

    .88.9 .92

    .95

    .981.8

    .85

    xIoIm tm

    34 5

    6

    8101.5

    2

    xIr

    .3

    .2

    0.63Io Ir tr

    0.8

    0.5 1

    xIn

    .88.9 .92

    .95

    .981.8

    .85

    xIo

    60120 240

    48015

    30

    at 1.5Ir

    Im tm3

    4 56

    8101.5

    2

    xIr

    .3.4 .3

    .1.1

    .2

    on I2t off

    .2

    0

    90

    105%Ir

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 28 D

    t

    i

    test

    Io Ir

    xIn xIoIm

    xIo

    0.63Io Ir

    0.8

    0.5 1

    xIn

    .88.9 .92

    .95

    .981.8

    .85

    xIoIm

    34 5

    6

    8101.5

    2

    xIr

    90

    105%Ir

    .4 .3

    .1.1

    on I2t off

    .2

    0

    +

    +

    +

    90

    105%Ir

    90

    105%Ir

    0631

    3299

    STR 28 D

    STR 38 S

    STR 58 U

    LED

    OFF:I < 0.9 Ir

    ON:0.9 Ir 1.05 Ir

    Flashing:I > 1.05 Ir

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 3Control Unit Types

    19982002 Schneider Electric All Rights Reserved 37

    Thermal Memory Limitation Thermal memory is standard on the STR 38 S and STR 58 U trip units. The thermal memory function remembers the thermal heating from each time the pickup setting is exceeded.It operates: Before tripping on long-time and ground-fault protection (if provided). After tripping on long-time protection only; the time-constant depends on

    the internal temperature of the circuit breaker.

    Any temporary overload generates an overheating value, which is stored. A series of temporary overloads will be integrated into this overheating value. Storing of this value results in reduced tripping time so the reaction of the trip unit will be closer to the real heating seen by the system. The internal temperature rise of the circuit breaker is measured by thermal resistors. The cooling time constant of the memory depends on the over-temperature condition. The standard version of the control unit STR 58 is fitted with a min/max position switch.The min position cancels the thermal memory and must only be used in emergencies where reclosing on a fault is essential.WARNING

    HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE.Use min position only for emergency, when reclosing on fault is absolutely necessary.Failure to follow this instruction can result in serious personal injury or equipment damage.

    tr

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 58 U

    Ir

    xIo at 1.5IrIm tm

    xIo

    i

    test

    T

    R

    F

    test

    Ih th

    xIn

    I

    xIn

    Ic1 Ic2

    xIr xIr

    xIn

    t

    t

    t

    t

    t

    t

    II

    t

    t

    t

    t

    t norm

    t

    t = f( ACB)

    t

    II

    t

    t norm.

    t min.

    r

    r

    r

    r

    r x

    r

    x

    r r t min.

    r r

    r

    r

    r

    0691

    3300

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 3Control Unit Types 01/2002

    19982002 Schneider Electric All Rights Reserved38

    Ammeter OptionI1, I2, I3: Phase current

    Im: Maximum instantaneous current

    max: Maximum current stored since the last reset

    Ih: Ground-fault current

    I

    STR 38 S

    I

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 38 S

    I

    push to reset

    I1 I2 I390%

    50%

    20%

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 38 S

    I

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 38 S

    I

    IM I1 I2 I3

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 38 S

    I

    max

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 38 S

    I

    max

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 38 S

    I

    max

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 38 S

    I

    Ih

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 38 S

    I

    IN

    push to reset

    I1 I2 I390%

    I

    Im

    Im

    0631

    3301

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 3Control Unit Types

    19982002 Schneider Electric All Rights Reserved 39

    Fault Indication OptionThree light-emitting diodes (LEDs) indicate separately long-time, short-time/instantaneous and ground-fault trip. A flat push button allows resetting of the indicator after tripping.A separate power supply is required to maintain the fault indication after the circuit breaker trips. Two options are offered: Connecting a reliable 24 Vdc control voltage on F1-F2. Auxiliary power

    module is used for other voltages. When the control source is unreliable, a bettery pack (BAT) is added to power module.

    From a built-in battery module. When no external control source is available, a built-in battery module may be ordered (option PIL). This module integrates battery testing and indicator resetting buttons.

    F

    Ih

    xIn

    xIn

    Ic1

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 58 U

    Ir tr

    xIo at 1.5IrIm tm

    xIo

    test

    T

    R

    th

    I

    Ic2

    xIr xIr

    t

    i

    F

    test

    Ir :

    Im :

    th :tr

    Im faulttm

    I

    faultIh

    th

    t

    i

    test

    Ir faulttr

    Im faulttm

    Ifault

    Ih

    th

    t

    i

    test

    Ir :

    th :

    tm :Ir fault

    F

    test

    tr

    Im faulttmI

    faultIh

    th

    t

    i

    test

    Ir :

    Im :

    th :

    Ir fault

    F

    test

    0631

    3302

    Turns off after two minutes (if internal battery power supply). Call it back then reset it.

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 3Control Unit Types 01/2002

    19982002 Schneider Electric All Rights Reserved40

    Battery Option

    Load Monitoring OptionThe option R provides two independant static contacts which operate when the current exceeds adjustable pickup limits. When the current exceeds the limit Ic1 (or Ic2) the contact C-R1

    (or C-R2) closes, following an inverse time characteristic a. When the current drops below the limit Ic1 (or Ic2) the contact C-R1

    (or C-R2) opens with constant time delay (10 seconds) b.For wiring diagram see page 46.

    \

    tr

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 58 U

    Ir

    xIo at 1.5IrIm tm

    xIo

    i

    test

    T

    R

    Ftest

    Ih th

    xIn

    I

    xIn

    Ic1 Ic2

    xIr xIr

    t

    F Test

    F Test

    F Test

    led

    F Test

    Lithium

    3,5V - 85

    0mA/hS A F

    T

    0631

    3303

    Lithium BatterySize: 3.6 V - 850mA/hType: SAFT LS3

    SONNENSCHEINTEL-S

    Battery Test

    1

    2

    34

    5

    6

    7

    R

    Ih

    xIn

    xIn

    Ic1

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 58 U

    Ir tr

    xIo at 1.5IrIm tm

    xIo

    test

    T

    R

    th

    I

    Ic2

    xIr xIr

    t

    i

    F

    test

    Ir :

    Im :

    th :tr

    Im faulttm

    I

    faultIh

    th

    t

    i

    test

    Ir faulttr

    Im faulttm

    Ifault

    Ih

    th

    t

    i

    test

    Ir :

    th :

    tm :Ir fault

    F

    test

    tr

    Im faulttmI

    faultIh

    th

    t

    i

    test

    Ir :

    Im :

    th :

    Ir fault

    F

    test

    0631

    3302

    Turns off after two minutes (if internal battery power supply).

    Call it back. then reset it.

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 3Control Unit Types

    19982002 Schneider Electric All Rights Reserved 41

    Segregated Alarm Switch OptionThis switch works like the standard overcurrent trip switch (SDE) except a selector switch on the control unit is used to choose the type of fault which will operate the contact: overload, short-circuit, ground-fault or any combination of these types. This option can be used in addition to the SDE switch for remote signaling of particular types of faults.A flat push button allows resetting of the indicator after tripping.

    Ground-fault Protection Option

    Use 24 Vdc module when circuit breaker has ground-fault trip unit and when load is less than 20% of sensor or ground-fault pick-up is set in the red* (lower) zone.

    FV

    F

    testreset V

    I+T L+II

    L+TL off

    T

    L+I+T

    Ih

    xIn

    xIn

    Ic1

    I1 I2 I390%

    50%

    20%

    STR 58 U

    Ir tr

    xIo at 1.5IrIm tm

    xIo

    test

    T

    R

    th

    I

    Ic2

    xIr xIr

    t

    i

    push to reset

    F

    test

    0631

    3305

    Selector Switch

    Fault Type

    Overload Short-circuit Ground-faultL 1 0 0L + T 1 0 1I 0 1 0I + T 0 1 1L + I 1 1 0L + I + T 1 1 1T 0 0 1Off 0 0 0

    To reset remote indicator contact (V output)

    V

    = 0

    V

    V

    V

    V

    V

    = 1

    1 2

    T or W

    xIn

    i RIc1 Ic2

    push to reset

    I1 I2 I390%

    50%

    20%

    STR 58 U

    Ir tr

    xIo at 1.5IrIm tm

    xIot

    test

    F

    test

    I

    xIr xIr

    Ih th

    xIn

    Tth

    400500 600

    800

    10001200250

    320

    A

    .3.4 .4

    .2.1

    .2

    .3

    .1

    Ih 1200A Max

    on I2t off

    TIh 1200A Max th

    400500 600

    800

    10001200250

    320

    A

    .3.4 .4

    .2.1

    .2

    .3

    .1

    on I2t off

    400

    250320

    0631

    3306

    *Red zone

    Ih 0.1 to 1.0 In Max 1200 A

    0.1 to 0.4 sec.

    I2t on

    Ih 0.1 to 1.0 In Max 1200 A

    I2t off0.1 to 0.4 sec.

    thT = Residual sensingW = Source ground return

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 3Control Unit Types 01/2002

    19982002 Schneider Electric All Rights Reserved42

    Zone-selective Interlocking Option Option Z on the STR 58 U trip unit provides selective interlocking of short-time or ground-fault tripping.A control wire links several trip units in the distribution network, as shown in the figure below.In the event of a fault, the trip unit will obey the pre-set delay only if receiving a signal from the downstream unit. If not receiving a signal, tripping will be instantaneous (time delay corresponding to 0.1 setting of short-time protection). The fault is cleared instantaneously by the nearest circuit breaker. Thermal stresses (It) in the network are minimized, without any affect on

    the correct time delay coordination in the installation.NOTE: On drawout circuit breakers, terminals are delivered with in terminals jumpered. Remove the jumper when interlocking with a downstream circuit breaker. The MASTERPACT circuit breaker may also be interlocked with

    COMPACT CK type molded case circuit breakers with zone-selective interlocking option.

    Do not ground.Fault 1

    Circuit breaker (A) will clear the fault instantaneously, regardless of its time delay setting.Fault 2

    Circuit breaker (B) will inform upstream circuit breaker (A) that it is clearing the fault so that circuit breaker (A) does not trip instantaneously. Circuit breaker (A) will trip at the end of its time delay setting if the fault is not cleared during this time.

    Transmit Data from Trip Unit OptionThe DIGIPACT connections communicate over MODBUS (J Bus) and require the STR 58 U control unit with option C (communications) and modules: DC 150: Data concentrator SC150: Product indication and control interface

    Z

    Table 9: Control Cable

    Cable size #18#14 AWG (1.5 mm2)Max. length 60 ft. (20m)

    Wiring Twisted in pairs one turn per 4 in. (10 cm)

    No. of circuit breakers Upstream: 2downstream; no limit

    A

    out

    in in in

    Z12Z11

    Z22Z21

    out

    in

    out

    in

    2

    1

    Z12Z11

    Z22Z21

    Z12Z11

    Z22Z21

    Z12Z11

    Z22Z21

    Z12Z11

    Z22Z21

    Z12Z11

    Z22Z21

    out

    in

    out outB

    0631

    3307

    C

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 3Control Unit Types

    19982002 Schneider Electric All Rights Reserved 43

    PowerLogicCIRCUIT MONITOR

    0631

    3308

    With DIGIPACT Modules

    SC150 DC150Data Concentrator

    SC150

    With POWERLOGIC Circuit MonitorsNetwork (SY/MAX)

    Circuit Monitor

    Table 10: MASTERPACT Communications Functions

    FunctionDIGIPACT POWERLOGIC Circuit Monitors

    SC150 2050 2150 2250 2350Basic Protection and SwitchingStatus (open/closed/tripped) c c c c cRemote control (open/closed) c c c c cPre-trip overload indication c Connected/disconnected position c c c c cLoad monitoring (option R) c Internal temperature alarm c Amps per phase (Ia, Ib, Ic, In) c c c c cTrip time/date c c cTrip type (LS/IG) c c c c cLong-time alarm c c c cMagnitude of current interrupted 1 1 1Trip history c c cTrip unit settings c MeteringAmps-instantaneous c c c cAmps-peak demand c c c cVolts (II and LG) c c c cPower (instantaneous) VA, VAr, W c c c cPower (demand) VA, VAr, W c c c cAdvanced ProtectionVoltage imbalance c c c cCurrent imbalance c c c cReverse power flow c c c cReverse phase c c c cFrequency out of limits c c c cPower Qualitythd (amperages and voltage) c c c cHarmonics (amperages and voltage) c cWaveform (amperages and volts) c cSags/swells cVoltage disturbance c c c c1The circuit monitor input current is limited to 7.5 A. To obtain magnitude of current interrupted,

    the current transformers must be oversized appropriately.

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 4Maintenance 01/2002

    19982002 Schneider Electric All Rights Reserved44

    SECTION 4 MAINTENANCE

    ROUTING INSPECTIONS

    ELECTRICAL MAINTENANCE

    DANGERHAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION This equipment must be installed and

    serviced only by qualified electrical personnel.

    Turn off all power supplying this equipment before working on or inside equipment.

    Always use a properly rated voltage sensing device to confirm power is off.

    Replace all devices, doors, and covers before turning on power to this equipment.

    Failure to follow this instruction will result in death or serious injury.

    Perform Routine External Inspection: By: Annually for normal operating conditions and After every 1000 operations for harsh

    operating conditions

    Opening and closing the circuit breaker manually Opening and closing the circuit breaker remotely, using the different

    auxiliaries successively Testing operation of the control unit with the mini test kit or the complete

    test kit

    Perform Routine External Inspection: By Checking: After circuit breaker opens on a short circuit

    or

    Every two years for normal operating conditions or

    Annually for harsh operating conditions

    Condition of arc chutes Condition of contacts Tightness of connections Condition of clusters

    Perform Electrical Maintenance: By Replacing: When the maximum allowable electrical

    operation without maintenance is reached When the maximum allowable electrical

    operation with maintenance is reached

    Arc chutes Arc chutes Main contacts

    Perform Electrical Maintenance: By Replacing: When the maximum allowable mechanical

    endurance without maintenance is reached The electrical charging mechanism The main contacts The two toggle return springs Mechanical interlocking

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 4Maintenance

    19982002 Schneider Electric All Rights Reserved 45

    CHECK ARC CHUTES

    Check Contacts Close the circuit breaker to check the wear of the contacts.

    DANGERHAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION This equipment must be installed and

    serviced only by qualified electrical personnel.

    Turn off all power supplying this equipment before working on or inside equipment.

    Always use a properly rated voltage sensing device to confirm power is off.

    Replace all devices, doors and covers before turning on power to this equipment.

    Failure to follow this instruction will result in death or serious injury.

    0631

    3309

    Disconnect power and loosen screws.

    Pry up arc chute.

    0631

    3310

    Lift arc-chute out of circuit breaker.

    Check the condition of the arc chute: arc chute body not broken, separators not corroded, if necessary, replace the arc chute

    0631

    3311

    4000 A x 3Good contacts Worn contacts

    0631

    3312

    4000 A x 4Good contacts Worn contacts

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 4Maintenance 01/2002

    19982002 Schneider Electric All Rights Reserved46

    WIRING DIAGRAM

    Circuit breaker shown in connected, charged and open position, undervoltage release energized.

    0631

    3313

    Drawout Position Switches Auxiliary Switches Remote Operation

    Connected

    Connected

    Disconnected Test Standard Heavy DutyUndervoltage Trip Device or

    Shunt Trip

    Ready-to-close

    Motor Operator

    Disconnected TestClosed

    Open

    Remote Open

    Remote Close

    Spring Charged

    314312

    324322

    334332

    344342

    352354

    362364

    372374

    311 321 321 321 351 361 371

    212222

    234244

    1214

    2224

    3234

    4244

    D4C2

    A4252

    254262

    B4

    F F O O

    standardOF

    M

    MN MX XF

    211221

    231241

    11 21 31 41 D1 C1 A1 251 B1

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 4Maintenance

    19982002 Schneider Electric All Rights Reserved 47

    1

    +_

    0631

    3314

    Remote Fault and Overload Indication

    Ammeter Ground-fault ProtectionLocal Fault Indications and Remote Selected Fault Indication

    Zone-selective Interlocking

    Load Monitoring

    Data Transmission

    Fault Alarm

    Overload Alarm

    82 841 LR2

    S2 S1

    T2 T1

    Selected Fault

    Communication

    Upstream Circuit Breaker

    V Z11 Z12 R1 R2

    Ic1

    Ic2

    e+ e-

    Communication Network3

    SDELT alarm

    I option4 T or W option5

    LT ST Gnd

    F or FV option6 V

    out

    Z optionin

    R option

    C option

    81 LR1 F1 F2

    24 Vdc

    Z212 Z22 C

    Downstream Circuit Breaker

    1 84 terminal not available with Z or C option.

    2 Zone-selective interlocking with downstream circuit breaker requires removal of jumper from drawout circuit breaker.

    3 Communication output through DIGIPACT module.

    4 Use 24 Vdc supply if I max, information is to be retained after the circuit breaker has tripped.

    5 Use 24 Vdc supply for lower setting of ground-fault pickup (red zone), or when load is less than 20% of sensor rating.

    6 Use 24 Vdc supply for F option if not supplied with PIL (battery) option.Use 24 Vdc supply (mandatory) for FV option.

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 5Set-up Guide

    19982002 Schneider Electric All Rights Reserved 48

    SECTION 5 SET-UP GUIDE

    MINIMUM ENCLOSURE The following tables indicate the minimum compartment size in which the circuit breaker has been tested and is suitable for continuous operation at 100% rating.Figure 29: Drawout Circuit Breaker (with Arc Chute Cover)

    Table 11: Dimensions

    Table 12: Ventilation

    0631

    3315

    W D

    H

    X X

    Circuit Breaker Type

    Dimension MP08MP20in. (mm)MP25MP30in. (mm)

    MP40MP50in. (mm)

    MC08MC20in. (mm)

    MC32in. (mm)

    MC40MC50in. (mm)

    H 17.50 (440) 26.00 (660) 26.00 (660) 17.50 (440) 22.00 (560) 26.00 (660)W 21.00 (530) 21.00 (530) 34.00 (670) 21.00 (530) 25.25 (650) 34.00 (670)D 14.25 (360) 14.25 (360) 14.25 (360) 14.25 (360) 14.25 (360) 14.25 (360)X-minimum 0 0 4.30 (110) 0 4.30 (110) 4.30 (110)

    Circuit Breaker Type

    Ventilation MP08MP20in. (mm)MP25MP30in. (mm)

    MP40MP50in. (mm)

    MC08MC20in. (mm)

    MC32in. (mm)

    MC40MC50in. (mm)

    (both top and bottom) None 30.00 (200) 30.00 (200) None 30.00 (200) 30.00 (200)

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 5Set-up Guide

    19982002 Schneider Electric All Rights Reserved 49

    CLEARANCE INFORMATION Dimensions shown are for the maximum interrupting current of the circuit breaker.Figure 30: Drawout Circuit Breaker (with Arc Chute Cover)

    Figure 31: Fixed Circuit Breaker (with Arc Chute Cover)

    0631

    3316 Min. = 0 Min. = 0

    Min. = 0 Min. = 0

    3.94 in.[100 mm]

    0631

    3317

    Min. = 0 Min. = 03.94 in.[100 mm]

    Min. = 0 Min. = 0 7.88 in.[200 mm]

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 5Set-up Guide 01/2002

    19982002 Schneider Electric All Rights Reserved50

    STACKING CONFIGURATIONS The following table shows some possible circuit breaker stacking configurations. These examples apply when the circuit breaker is used either as a main, a tie or a feeder circuit breaker.

    The depth of the circuit breaker zone (14.25 in. [362 mm]) is equal to the depth of the circuit breaker compartment.

    NEC 380-8 requires all switches and circuit breakers used as switches to be located so that they may be operated from a readily accessible location. They shall be installed so that the center of the switch or circuit breaker operating handle grip, when in its highest position, will not be more than 6.5 ft. (1.98 m) above the floor or working platform.

    Customer allowable cumulative loading is as recommended in ANSI C 37.20.1.

    Type MP, which is UL Listed under UL 489, is intended to be mounted in switchboards.

    Type MC, which is UL Listed under UL 1066, is intended to be mounted in switchgear.

    0631

    3318

    90.00 in.[2286 mm]

    MP08 / MP12MP16 / MP20MC08 / MC16MC20

    17.5

    MP08 / MP12MP16 / MP20MC08 / MC16MC20

    17.5

    MP08 / MP12MP16 / MP20MC08 / MC16MC20

    17.5

    MP08 / MP12MP16 / MP20MC08 / MC16MC20

    17.5

    84.00 in.[2134 mm]

    MP25 / Blank

    26

    MP25 / MP30

    26

    MP25 / MP30

    26

    21.00 in.[533 mm]

    21.00 in.[533 mm]

    : Ventilation

    25.25 in.[641 mm]

    34.25 in.[870 mm]

    14.25 in.[362 mm]

    Blank Compartment

    MC32

    22

    22

    MC32

    Blank Compartment

    MP40 / MP50MC40 / MC50

    MP40 / MC40 / Blank

    Circuit Breaker

    Zone

  • 48049-071-03 MASTERPACT MP, MF and MC Circuit Breakers01/2002 Section 5Set-up Guide

    19982002 Schneider Electric All Rights Reserved 51

    CUMULATIVE LOADING

    Allowable cumulative loading can be based on equal loading or higher loading in the lowest compartment.

    Table 13: Allowable Cumulative Loading Values Per Compartment Section

    Circuit Breaker Type Frame Size (A)

    Number of Circuit Breakers Carrying Load

    Allowable Cumulative Load

    MP08 and MC08 800

    1 800*2 1300*3 1800*4 2200*

    MP12 1200

    1 12002 19003 27004 3400

    MP16 and MC16 1600

    1 1600*2 2600*3 3600*4 4500*

    MP20 and MC20 2000

    1 2000*2 3200*3 45004 5600

    MP25 25001 25002 40003 5600

    MP30 30001 3000*2 4800*

    MP32 32001 32002 5100

    MP40 and MC40 40001 4000*2 6400

    MP50 and MC50 5000 1 5000

    *ANSI C37.20.1 values.

  • MASTERPACT MP, MF and MC Circuit Breakers 48049-071-03Section 5Set-up Guide 01/2002

    19982002 Schneider Electric All Rights Reserved52

    TEMPERATURE DERATING The continuous current rating is based on use in a 40C ambient temperature environment, inside an enclosure. Continuous current ratings must be derated for ambient temperatures above 40C, as indicated in the following tables.

    Table 14: Continuous Current Rating Based on Temperature Ambient

    Mounting Ambient TemperatureCircuit Breaker Type

    MP08H MP12H MP16H MP20H MP25H MP30H MP40H MP50H MP63H

    Drawout

    40C45C50C55C60C

    800800800800

    800

    1200120012001150

    1100

    1600160015501450

    1350

    2000200020001900

    1800

    2500250025002400

    2300

    3000290027502600

    2450

    4000390037003500

    3300

    5000500048004500

    4200

    6300600057005400

    5100

    Fixed

    40C45C50C55C60C

    800800800800800

    12001200120012001150

    16001600160015501450

    20002000200020001900

    25002500250025002400

    30003000290026002450

    40004000390037003300

    50005000500048004500

    MC08N MC08H MC16H MC20H MC