matthew larue, abb drives product manager …...“swinging” choke design provides enhanced light...

46
© ABB Group October 21, 2013 | Slide 1 A Common Cure for Harmonics: ABB Ultra Low Harmonic Drives Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia

Upload: others

Post on 01-Apr-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

© ABB Group October 21, 2013 | Slide 1

A Common Cure for Harmonics:ABB Ultra Low Harmonic Drives

Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia

Page 2: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Session Goals

� Understand what harmonics are

� Understand why harmonics may be a concern

� Provide simple guidelines for when to be

concerned

© ABB Group October 21, 2013 | Slide 2

concerned

� Understand what options are available for addressing harmonic issues

Page 3: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonics —

What?

© ABB Group October 21, 2013 | Slide 3

What?

Page 4: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

� Non-linear loads draw non-sinusoidal current from a sinusoidal line (current doesn’t look like voltage):

� Non-incandescent lighting

� Computers

� Uninterruptible power supplies

� Telecommunications equipment

Harmonics — What?

© ABB Group October 21, 2013 | Slide 4

� Telecommunications equipment

� Copy machines

� Battery chargers

� Any load with a solid state AC to DC power converter

� Electronic variable speed drives

Page 5: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonics — Key Concepts

� Non-linear loads draw current in a periodic

non-sinusoidal or distorted manner

� Line transients are not harmonics

� Harmonics or harmonic content is a mathematical conceptimplemented to allow quantification and simplified analysis of non-

linear waveforms

© ABB Group October 21, 2013 | Slide 5

linear waveforms

� Harmonics are typically present in both network currents and

network voltages

� Non-linear current draw creates non-linear voltage as it flows through the electrical network

� Current harmonics → Voltage harmonics

Page 6: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

The Real World, 6- Pulse Drive

PWM Drive Input Current

© ABB Group October 21, 2013 | Slide 6

Page 7: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

The Theory: Fundamental, 5th and 7th Harmonics

0 0.005 0.01 0.015 0.02 0.025 0.031

0.5

0

0.5

1

i1 t( )

i5 t( )

i7 t( )

Fundamental5th

7th

Components

© ABB Group October 21, 2013 | Slide 7

0 0.005 0.01 0.015 0.02 0.025 0.031

0 0.005 0.01 0.015 0.02 0.025 0.031.5

1

0.5

0

0.5

1

1.5

iT t( )

t

Summation

Page 8: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonic Content, 6- Pulse Drive

PWM Drive Harmonic Input Spectrum

Fundamental

© ABB Group October 21, 2013 | Slide 8

5th

7th11th

13th

Page 9: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonics —

Why worry?

© ABB Group October 21, 2013 | Slide 9

Why worry?

Page 10: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

� Harmonic Current Distortion —

� Added heating in transformers and cables, reduces available capacity

� May stimulate a PF correction resonance condition

� Excessive voltage

Harmonics — Why worry?

© ABB Group October 21, 2013 | Slide 10

� Excessive voltage

� Overheating of capacitors

� Tripping of protection equipment

� Shutdown / damage to electronic equipment

� May cause telephone or electronic interference

Page 11: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Beware Harmonic Resonance

© ABB Group October 21, 2013 | Slide 11

Undamped power factor correction capacitors on the same bus as nonlinear loads may create a resonance condition with consequent severe bus voltage

distortion and excessive peak voltage

Page 12: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

� Harmonic Voltage Distortion —

� Increased heating in motors and other electromagnetic equipment

� Noisy operation of electromagnetic equipment

� Malfunction of sensitive electronics

Harmonics — Why worry? (cont.)

© ABB Group October 21, 2013 | Slide 12

� Nuisance tripping of electronic circuit breakers

� Equipment downtime

� Premature component failures

� Failed transformers, motors and capacitors

� Compliance with codes or specifications

Page 13: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonics, Important Terminology

(definitions per IEEE 519-1992)

• Harmonic - A sinusoidal component of a periodic wave or quantity having

a frequency that is an integral multiple of the fundamental frequency.

• Harmonic, characteristic - Those harmonics produced by

semiconductor converter equipment in the course of normal operation.

h = kq ± 1

© ABB Group October 21, 2013 | Slide 13

k = any integer

q = pulse number of the converter

• Point of common coupling (PCC)

Def. 1 - “point of common coupling (PCC) with the consumer-utility

interface.” (current harmonic emphasis)

Def. 2 - “Within an industrial plant the point of common coupling is the

point between the nonlinear load and other loads.” (voltage harmonic

emphasis)

Page 14: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

PCC Example

13.8 KV

4.16 KV

PCC1 (Harmonic Current Distortion)

PCC2 (HarmonicVoltage Distortion)

Substation Transformer

To other utility customersTo other utility customers

© ABB Group October 21, 2013 | Slide 14

M M

LV

PWM

M

LV

PWM

M

M

M

MV PWM

480 V

Page 15: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonics, Important Terminology (cont.)

• ISC/IL - The ratio of the short-circuit current available at the point of

common coupling, to the maximum fundamental load current.

• Total harmonic distortion (THD) or distortion factor - The ratio of the root-mean-square of the harmonic content to the root-

mean-square value of the fundamental quantity, expressed as a

percent of the fundamental.

© ABB Group October 21, 2013 | Slide 15

• Total demand distortion (TDD) - The root-sum-square harmonic

current distortion, in percent of the maximum demand load current

(15 or 30 min demand).

THD DF= =sum of the squares of amplitudes of all harmonics

square of amplitude of fundamental*100%

Page 16: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Effect of Short Circuit Ratio on HarmonicsISC

IL~ 400

ISC

IL~ 8

© ABB Group October 21, 2013 | Slide 16

LINE CURRENT, NO FILTER

Fig. 1 THID = 108%

LINE VOLTAGE, NO FILTER

Fig. 3 THVD = 2.2%

LINE CURRENT, NO FILTER

Fig. 5 THID = 25.8%

LINE VOLTAGE, NO FILTER

Fig. 7 THVD = 13.8%

Page 17: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

� Harmonics produced by an individual load are only important to the extent

that they represent a significant portion of the total connected load (Harmonics

are expressed as a percentage)

� Linear loads help reduce system harmonic levels (percentages)

� TDD (Total Demand Distortion) equals the THD (Total Harmonic Distortion) of the

nonlinear load multiplied by the ratio of nonlinear load to the total (demand)

load:

Harmonics - A System Issue!

© ABB Group October 21, 2013 | Slide 17

TL

NLTHDTDD

NL⋅=

Where TDD = TDD of the system

THDNL

= THD of the nonlinear loads

NL = kVA of nonlinear loadTL = kVA of total load

(nonlinear + linear)

Page 18: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonics — By the Numbers

Table 10.2Low-Voltage System Classification and Distortion Limits

SpecialApplications

GeneralSystem

DedicatedSystem

IEEE 519 - 1992

© ABB Group October 21, 2013 | Slide 18

Notch Depth 10% 20% 50%

THD (Voltage) 3% 5% 10%

Notch Area, µVs 16,400 22,800 36,500

Note: Notch area for other than 480 V systems should be multiplied by V / 480.

Page 19: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonics — By the Numbers (cont.)

Table 10.3Current Distortion Limits for General Distribution Systems

ISC / IL <11 11≤≤≤≤h<17 17≤≤≤≤h<23 23≤≤≤≤h<35 35≤≤≤≤h TDD

<20 4.0 2.0 1.5 0.6 0.3 5.0

IEEE 519 - 1992RSC

© ABB Group October 21, 2013 | Slide 19

20<50 7.0 3.5 2.5 1.0 0.5 8.0

50<100 10.0 4.5 4.0 1.5 0.7 12.0

100<1000 12.0 5.5 5.0 2.0 1.0 15.0

Note: All harmonic current levels are in percent with fundamental current IL as the base.

Page 20: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Table 10.3 - Calc 1

Current Distortion Limits for General Distribution Systems

Modified to Reflect 12 Pulse Rectifier Requirements

For Characteristic Harmonic Orders (11,13,23,25,35,37,47,49, etc.)

ISC/IL <11 11≤≤≤≤h<17 17≤≤≤≤h<23 23≤≤≤≤h<35 35≤≤≤≤h

<20 na 2.83 na 0.85 0.42

20<50 na 4.95 na 1.41 0.71

50<100 na 6.36 na 2.12 0.99

100<1000 na 7.78 na 2.83 1.41

Harmonics — By the Numbers (cont.)

IEEE 519 - 1992

© ABB Group October 21, 2013 | Slide 20

Table 10.3 - Calc 3

Current Distortion Limits for General Distribution Systems

Modified to Reflect 12 / 24 Pulse Rectifier Requirements

For Even and Noncharacteristic Harmonic Orders

ISC/IL <11 11≤≤≤≤h<17 17≤≤≤≤h<23 23≤≤≤≤h<35 35≤≤≤≤h

<20 1.00 0.50 0.38 0.15 0.08

20<50 1.75 0.88 0.63 0.25 0.13

50<100 2.50 1.13 1.00 0.38 0.18

100<1000 3.00 1.38 1.25 0.50 0.25

Page 21: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonics —

Will it be a problem?

© ABB Group October 21, 2013 | Slide 21

Will it be a problem?

Page 22: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonic Voltage, Will it be a problem?

� THD (Voltage) will be acceptable (<5%) if the % drive load times the % impedance feeding the drive load is <3%

%DriveLoad x %Impedance < 3%

� E.g. a 45% drive load fed from 6% impedance feeder bus:

© ABB Group October 21, 2013 | Slide 22

(Approximate rule of thumb for 6-pulse drives with 3% reactor, all other loads assumed to be linear)

� E.g. a 45% drive load fed from 6% impedance feeder bus:45% x 6% = 2.7% 2.7% < 3% → Acceptable

� E.g. a 70% drive load fed from 5% impedance feeder bus:70% x 5% = 3.5% 3.5% > 3% → Not Acceptable

Page 23: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonic Current, Will it be a problem?

� THD (Current) on a network with a short circuit ratio <20 (20<50, 50<100,

100<1000) will be acceptable if the % drive load times 45% is <5% (<8%, <12%,

<15%)

%DriveLoad x 45% < 5% (RSC <20)

%DriveLoad x 45% < 8% (RSC 20<50)

%DriveLoad x 45% < 12% (RSC 50<100)

© ABB Group October 21, 2013 | Slide 23

%DriveLoad x 45% < 12% (RSC 50<100)

%DriveLoad x 45% < 15% (RSC 100<1000)

(Rule of thumb for 6-pulse drives with 3% reactor,, all other loads assumed to be linear)

� E.g. a network with a short circuit ratio of 35 has 15% drive load:15% x 45% = 6.75% 6.75% < 8% → Acceptable

� E.g. a network with a short circuit ratio of 65 has 30% drive load:30% x 45% = 13.5% 13.5% > 12% → Not Acceptable

Page 24: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonics —

What can I do?

© ABB Group October 21, 2013 | Slide 24

What can I do?

Page 25: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonics — What can I do?

� Reactors (Chokes)

� Passive Filters

� Harmonic Trap

� Hybrid

© ABB Group October 21, 2013 | Slide 25

� Hybrid

� High Pulse Count Rectification

� Active Filters

� Stand Alone

� Drive Active Front End

Page 26: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Reactors (Chokes)

� Simplest and least expensive harmonic reduction technique

� May be included in base drive package

� Often meet harmonic needs provided drive load is a small portion of total connected load

� May be implemented with AC line reactors or with DC link reactors

© ABB Group October 21, 2013 | Slide 26

� AC line reactors provide better input protection

� DC link reactors provide load insensitive drive output voltage

� Both types provide similar harmonic benefits

� “Swinging” choke design provides enhanced light load harmonic

performance

Page 27: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Reactors, AC Line or DC Link

AC Line

Reactor

M

DC Link

� Different design

techniques

� Equal harmonic reduction

for same normalized

% reactance

� Typical full load THD

(current) at drive input

© ABB Group October 21, 2013 | Slide 27

DC Link

Reactor

M

(current) at drive input

terminals

28% → 46%

Existence - not position - is what is important

Page 28: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Reactor Effectiveness

THD (Current) vs. % Reactor

80

100

120

%T

HD

(C

urr

en

t)

Current harmonic content (THD) at drive

input terminals as a function of normalized %

reactance and network short circuit ratio

© ABB Group October 21, 2013 | Slide 28

0

20

40

60

0 1 2 3 4 5 6 7 8 9

% Reactor

%T

HD

(C

urr

en

t)

Rsc = 20 Rsc = 60 Rsc = 200

Page 29: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Swinging Chokes

� Provide increased inductance at reduced current

� Reduce harmonics up to 30%

more than traditional designs

© ABB Group October 21, 2013 | Slide 29

more than traditional designs

� “Swing” portion of choke

characteristic significantly

improves harmonic performance at reduced loads

Page 30: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Swinging DC Link Choke

� Designed to reduce harmonics at full and partial loads

� Perfect for Variable Torque Centrifugal Loads

� Equivalent to 5% line reactor

� More inductance per volume/weight of material

© ABB Group October 21, 2013 | Slide 30

Page 31: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Swinging Choke Vs. Fixed Choke

Current Distortion vs % Speed for Variable Torque Load

25

30

35

40

45

%T

DD

(C

urr

en

t)

© ABB Group October 21, 2013 | Slide 31

0

5

10

15

20

0% 20% 40% 60% 80% 100% 120%

% Speed

%T

DD

(C

urr

en

t)

5% Swinging Choke 3% Fixed Choke

Page 32: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonic Trap Filter

� Installs in series with

drive input

� May feed multiple drives

� Improves power factor

(may go leading)

Optional

© ABB Group October 21, 2013 | Slide 32

� Typical full load THD

(current) at filter input

terminals (line side)

10% → 14%

� Performance reduced by

line imbalance

Page 33: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Hybrid Filter

� Installs in series with

drive input

� May feed multiple drives

� Improves power factor

(may go leading)

� Typical full load THD

© ABB Group October 21, 2013 | Slide 33

(current) at filter input

terminals (line side)

5% → 8%

� Relatively unaffected by

line imbalance

Page 34: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

High Pulse Count Rectification

� Typical configurations are either 12 pulse or 18 pulse

� Phase shifting transformer is required

� Additional drive input bridges are needed

� Typical full load THD (current) at transformer primary 8% →

12% (12 pulse), 4% → 6% (18 pulse)

© ABB Group October 21, 2013 | Slide 34

� Performance significantly reduced by line imbalance (voltage or

phase)

� Excellent choice if stepdown transformer is already required

Page 35: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

High Pulse Count Rectification (cont.)

� 6 pulse rectifier

Transformer (if included) and cabling simple

DC/AC

DC/AC

� 12 pulse rectifier

� 18 pulse rectifier

DC/AC

Transformer and cabling complicated

© ABB Group October 21, 2013 | Slide 35

Current quite distortedIthd 32% to 48% with 3% reactor (depending on network impedance)

Transformer and cabling more complicated

Current slightly distortedIthd 8% to 12% (depending on network impedance)

Current wave form goodIthd 4% to 6% (depending on network impedance)

Page 36: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

E1Ysec

E1∆∆∆∆sec

30°

12 Pulse Configuration

Transformer with delta primary anddelta / wye secondary produces a 30°

phase shift between the twosecondaries.

Harmonic Cancellation, 5th

© ABB Group October 21, 2013 | Slide 36

E5∆∆∆∆sec

( 0° )

E5Ysec

( 180° )

-5 x 30° = -150°

-5 x 0° = 0°

E5∆∆∆∆sec

+ E5Ysec

= Null

5th harmonic has

negative sequence

Page 37: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

E1Ysec

E1∆∆∆∆sec

30°

12 Pulse Configuration

Transformer with delta primary anddelta / wye secondary produces a 30°phase shift between the twosecondaries.

Harmonic Cancellation, 7th

© ABB Group October 21, 2013 | Slide 37

E7∆∆∆∆sec

( 0° )

E7Ysec

( 180° )

7 x 30° = 210°

7 x 0° = 0°

E7∆∆∆∆sec

+ E7Ysec

= Null

7th harmonic haspositive sequence

Page 38: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Active Front End Filter

© ABB Group October 21, 2013 | Slide 38

Page 39: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Active Filter Front End with LCL Filter

LCL filter

Line inverter

(rectifier)

Motor inverter

Motor

L L

C

M

DCLink

Drive

© ABB Group October 21, 2013 | Slide 39

� Active Filter Line Inverter removes low frequencies < 1kHz

� LCL Filter (passive filter) removes high frequencies >1 kHz.

(Current and voltage)

� Full output voltage is available with 80% input voltage

(400VIn = 480VOut)

� Full regenerative capability (ACS800-U11/-17)

� No transformer required

� Not affected by line imbalance

Page 40: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Beauty Instead of Beast

� IGBT line supply controls the current

Sinusoidal line current

Low distortion below switching frequency

� LCL Line filter removes high frequency

Acti

ve s

up

ply

Acti

ve s

up

ply

Acti

ve s

up

ply

© ABB Group October 21, 2013 | Slide 40

distortion

Cleans the waveform above switching frequency

Dio

de

su

pp

ly

Current spectrum of low harmonic drive

0,0001

0,001

0,01

0,1

1

10

100

0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000

Frequency [Hz]

Pe

rce

nta

ge

[%

]

Page 41: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

THD (current) and harmonic components

0

1

2

3

4

5

1 7 13 19 25 31 37 43 49 55 61 67 73 79 85 91 97

Impressive Numbers

� Total current distortion less than 3.5% to 4.5%

� Total voltage distortion less than 5%

� Power factor adjustable from 0.85 (leading or lagging) to 1.0

© ABB Group October 21, 2013 | Slide 41

%THD (Voltage) = f(RSC)

0

1

2

3

4

5

10 20 30 40 50 60 70 80 90 100

RSC

Page 42: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Inverter module

Converter module

Active Front End Drive, Construction

© ABB Group October 21, 2013 | Slide 42

Main switch

Main contactor

LCL-filter module

Page 43: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Product offering

� Wall-mounted low harmonic drive ACS800-U31

10 – 125 HP

© ABB Group October 21, 2013 | Slide 43

� Cabinet-built low harmonic drive ACS800-37

75 - 2800 HP

Page 44: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

18-Pulse Impedance and Imbalance Dependencies

Current Distortion Vs. Line Imbalance

15%

20%

25%

%T

DD

Cu

rren

t D

isto

rtio

n

12/18-Pulse drives have 3% internal reactance.

Drives are only load present.

12-Pulse

0% Voltage Imbalance Reference Curve

10% Total Network Impedance

18-Pulse

10% Total Network Impedance

(Utility + Multi-Phase Transformer)

18-Pulse

5% Total Network Impedance

(Utility + Multi-Phase Transformer)

18 Pulse with

ULH Clearly Superior

© ABB Group October 21, 2013 | Slide 44

0%

5%

10%

0.0% 0.5% 1.0% 1.5% 2.0% 2.5% 3.0%

Voltage Imbalance

%T

DD

Cu

rren

t D

isto

rtio

n

12-Pulse Reference 18-Pulse Direct 18-Pulse Xfmr ULH 1% Net Imp ULH 10% Net Imp

(Utility + Multi-Phase Transformer)

ULH

1% Total Network Impedance

ULH

10% Total Network Impedance

18 Pulse with12 Pulse Performance

Page 45: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link

Harmonic Reduction Summary

Effectiveness of Harmonic Mitigation Techniques (Assuming 100% Nonlinear Loading, ISC / IL = 60)

Technique THD

(Current) Harmonic Reduction

No mitigation (reference level) 72%

3% line reactors (or equivalent DC link reactor) 39% 45.8%

5% line reactors (or equivalent DC link reactor) 33% 54.2%

5% line reactors + 5th harmonic trap filter 12% 83.3%

12 pulse input rectifier with 5% impedance transformer 10% 86.1%

© ABB Group October 21, 2013 | Slide 45

Remember!Even an 80% THD nonlinear load with a will result in only 8% TDD if the nonlinear load is 10% and the linear load is 90%.

(80%•(10%/(10%+90%))=8%)

12 pulse input rectifier with 5% impedance transformer 10% 86.1%

Hybrid filter 7% 90.3%

18 pulse input rectifier with 5% impedance transformer 5% 93.1%

12 pulse input rectifier with 5% impedance transformer + 11th harmonic trap filter

4% 94.4%

Active harmonic filter 3.5% 95.1%

Page 46: Matthew LaRue, ABB Drives Product Manager …...“Swinging” choke design provides enhanced light load harmonic performance Reactors, AC Line or DC Link AC Line Reactor M DC Link