mbci
DESCRIPTION
relayTRANSCRIPT
-
Customer Benefits
High stability forthrough faults
Fast operation for inzone faults
Simultaneous trippingof relays at each lineend
Low current transformerrequirements
T&D
MBCI Differential Feeder and Transformer Feeder Protection
PROTECTION
Differential feeder protection requires acomparison of the currents entering andleaving the protected zone. Two MBCI relaysare therefore required, one for each end of thefeeder. A pair of pilot wires is used to transmitinformation between the two relays so thateach may be able to compare the currentflowing at its respective end with the current atthe other.
The pilot wire carries analogue circulatingcurrent - allowing correct operation even forlow specification or ageing pilots.
When applying this protection to overheadlines the limiting factor is generally the lengthof the pilot circuits: for cable feeders thelimiting factors are more likely to be the level of line charging current and the method ofsystem earthing.
MODELS AVAILABLE
> MBCI 01 - Private pilots> MBCI 02 - Telephone type
OPTIONAL EXTRAS
> MRTP supervision relay Alarm and indication of pilot failure and supervision supply failure Suitable for pilot circuits insulated for 5kV or 15kV with pilot isolation
transformers
> MVTW destabilising and Intertripping relay Destabilises the feeder protection so that tripping occurs Intertripping: injects ac voltage into pilot circuit so that tripping occurs
> MCRI instantaneous Overcurrent and start/check relay High speed operation Two phase and earth fault relay
> MCTH transformer inrush Current detector Allows MBCI to be applied to transformer feeders Blocks operation of the MBCI relay during transformer inrush conditions
A
B
C
Rs
Ts
Tt
RVD
Trip
cT1
T2
To Pilot wires
Ro
Rpp
Tr
Ro
Rpp
To
Tr
RVD
c
V
T2Trip
RsT1
ToTrTrRo
- Operating winding- Restraining winding- Tertiary winding- Linear resistor
Rppc
- Pilots padding resistor- Phase comparator
T1T2RVDTs
- Summation transformer- Auxiliary transformer- Non linear resistor- Secondary winding
V
Figure 1 Basic circuit arrangement
-
> Pilot supervision
Correct interchange of information over the pilot circuitis essential for the proper functioning of any differentialfeeder protection. The most common pilot failure is tothe open circuit state, caused by the accidentalexcavation of buried pilots or storm damage tooverhead pilots. With the pilots open circuited thedifferential protection will be unstable and will trip thefeeder if sufficient through current is flowing. For thisreason the circulating current system is often preferredas such schemes will fail safe and trip so that attentionis immediately drawn to the fault.
> Destabilising/intertripping
The remote unit of the differential feeder protection canbe caused to operate, provided sufficient line current isflowing, by open circuiting the pilots. If line current isnot flowing, the remote unit can be operated(intertripped) by injecting a current into the pilots.
> Overcurrent check/starting
Although the supervision scheme provides indicationof pilot failure it does not prevent the protectionoperating if primary current above setting is flowing.Where this hazard is unacceptable it is necessary toadd an overcurrent check feature to verify faultpresence.
> Emergency use for overcurrent protection
In the event of a pilot failure which cannot quickly berectified, the Translay S scheme may be adapted foruse as a definite time overcurrent relay.
2>3
RL11
PilotWires
Trip/Alarm
Outputs
MBCI
IA
IB
ICIN
RSSee
Note 5
SeeNote 2
VX
+PowerSupplyCircuits
Enable
Enable
RL12
RL22
RL31
Protected Zone
RES
OP
LevelDetector
Squarer
Squarer
KS
&
&
IA
IB
IN
MBCI
PhaseRotation
RS
Protected Zone
SeeNote 4
ABC
RO
Case EarthSee Note 3
A
BC
Moduleterminal blockviewed fromrear
(a) C.T. shorting links make before (b) & (c) disconnect.(b) Short terminals break before (c)(c) Long terminal.
RPP
Kt
3. Earthing connections are typical only.4. C.T. connections are typical only.5. For overcurrent start schemes, terminal 12 must be connected directly to D.C. +VE to provide a supply for the L.E.D. and reset circuits.
1.
2. Link terminals 11 and 13 except when used with overcurrent check replay type MCRI.
23
RL12
RL21
RL22
IC
Notes
19
18
1710
8
97
642
531
11
14
1312
282726252423
P2 P1S2 S1
2425
2627
28
P1 P2S1 S2
1 23 45 67 89 1011 1213 1415 1617 18
19 20
21 22
23 24
25 26
27 28
Case earth
RL41135
Output Contacts Change state for pilot fail
See Note 7
Module terminal blockviewed from rear
Note 1.(a) C.T. shorting links make before (b) & (c) disconnect.(b) Short terminals break before (c).(c) Long terminal.
RL42
RL42 467
RL51 9118
RL52 1012
Output Contacts Change state for supply fail
RL52
RL71
RL61
RL81
SupplyFail
PilotS/C
PilotO/C
RL22
RL32
OPReset
OPReset
OPReset
tRL31
RL21
RL11
+VE
StartRL12
RL22
RL32
RL12
A.C.Auxiliar ySupply
A.C.PowerSupply
D.C.PowerSupply
Case Earth
20
1927
28
13
14Vx
18
17
18
17
MBCI MBCIPilots
MRTP 03
S1
P1
S2
P2
P6P5P4P3P2
P1
S2
X2
X1S1
Supervisionisolation transformer
P6P5P4P3P2
P1
Pilot isolationtransformer
S1
X1
X2
S2
1 23 45 67 89 1011 1213 1415 1617 18
19 2021 2223 2425 2627 28
Case earth2
Pilot isolationtransformer
Simple differential protection - only 2pilot cores, and no MODEMS!
Figure 2 Application diagram: differential feeder protection relay type MBCI
Figure 3 Application diagram: pilot supervision relay 15kV isolation type MRTP 03
-
> Transformer feeders (use of transformer inrush current detector)
The inclusion of a type MCTH relay, designed toprovide a blocking signal in the presence oftransformer inrush currents, enables a pilot wiredifferential protection scheme to be applied to atransformer feeder. Where line and thereforetransformer energisation can occur at one end only ofthe transformer feeder, then a MCTH unit would berequired on that side only.
> Symbols:
15kV isolating transformer
15kV isolating transformer with injection filter
Scheme Pilot Supervision O/CInsulation Start/Check Arrangement of EquipmentLevel (kV) (Viewed from front)
A 5kV
B 15kV
C 5kV
D 15kV
E 5kV
F 15kV
G 5kV
H 15kV
Table 1. Typical scheme arragements for plain feeders. See key below.
Scheme Pilot Supervision TransformerInsulation Arrangement Arrangement of EquipmentLevel (kV) (Viewed from front)
I 5kV
J 15kV
K 5kV
L 15kV
M 5kV
N 15kV
O 5kV
P 15kV
Table 2. Typical scheme arragements for transformer feeders. See key below.
No. Type of relay
1 MBCI 01/02 Differential2 MRTP 01 Pilot supervision and injection filter3 MRTP 02 Injection filter4 MRTP 03 Pilot supervision5 MCRI 01 Overcurrent start/check6 MVTW 01 Destabilising7 MVTW 03 Destabilising and Intertripping
Schemes A to D can be fitted with relay types 6 or 7.Schemes E to H can be fitted with type 6 which will providedestabilising if the overcurrent start/check relays (MCRI 01) haveoperated. Schemes I to L must use type 7 or 8.
8 MCTH 01 Transformer inrush current detector9 MFAC 14 High impedance earth fault relay10 MMLG Test plug/block
It is advisable on all schemes to include the test unit to facilitatecommissioning and routine testing. The unit will be situated on therighthand side of the scheme.
1 1
1 1
2 1 3 1
4 1
1 5 1 5
1 5 1 5
4 1 5 1 5
1
2 1 5 3 51
1 8 9 7 1 8
1 8 9 7 1 8
1 8 2 9 7 1 8 3
1 8 4 9 7 1 8
1 8 1 8
1 8 1 8
1 8 2 1 8 3
1 8 4 1 8
Pilots
-
DESCRIPTION
> Differential protection
The differential feeder protection circuit is derived fromthe well known Merz-Price circulating current system.Figure 1 shows the basic circuit arrangement. Asummation current transformer T1 at each line endproduces a single phase current proportional to thesummated three phase currents in the protected line.The neutral section of the summation winding istapped to provide alternative sensitivities for earthfaults.
In order to maintain the bias characteristic at thedesigned value it is necessary to pad the pilot loopresistance to 1k. A padding resistor Rpp is providedin the relay for this purpose.
> Pilot isolation transformers
When pilot isolation transformers are used, the pilotinsulation level is raised to 15kV.
> Telephone type pilots (MBCI02)
When the pilots to be used are of the telephone type -the pilot differential voltage is limited by a metrosil(MBCI01). An alternative limiter based on a zenerdiode is available (MBCI02).
4>5
DESTABILISE AND INTERTRIPFACILITIES
> MVTW01
Operation of the destabilising relay results in thesummation current transformer in the differential relaybeing short circuited and the local relay prevented fromtripping.
The remote relay then sees a single end feed conditionand trips, provided the through current exceeds the no-load fault setting of the protection
> MVTW03
The MVTW 03 incorporates a full bridge inverter,which receives signals from an oscillator circuit at afrequency of 80Hz. This frequency was chosenbecause it lies sufficiently far from the pilot frequencyof 50 or 60Hz and cancellation of the intertrippingsignal cannot result.
To ensure intertripping occurs the output relay injects a20mA intertrip current into the pilots; the remote MBCIsees the intertrip current as a differential current whichcauses it to trip.
> Transformer inrush current detector feature
A typical scheme for a delta-star power transformer isshown in figure 4. The line current transformers areconnected in star on the delta side of the transformer.Appropriate choice of CT ratios ensures that fornormal load and through fault conditions, equalcurrents flow into the differential tripping units (MBCI)at each end. A high impedance differential relay (typeMFAC 14) is included in the neutral lead of the star-connected line transformers to provide B-N protectionon the delta side of the power transformer. The MFAC14 high impedance differential relay may be used toinitiate an intertrip unit (type MVTW 02)
Unit protection for lines and cables, including those with in-zone transformers
A
B
C
S1 S2
P2I
II
III
i
ii
iiiyn
A
B
C
P2 P1
S2 S1
N.E.R.
MCTH MCTH
MBCI MBCI
Pilots
MFAC14
RVD3
232425262728
232425262728
232425262728
232425262728
17
18
17
1819
1819
17
1
3
27
28
17
19
17
19
Note1: It is essential that the current transformer connections are earthed at one point only.
11
MVTW
03
Figure 4 Typical application diagram:overall protection of transformer feeders
-
TECHNICAL DATA (MBCI RELAY)
> Current rating (in)1A, 2A or 5A
> Frequency rating
50Hz or 60Hz
> Current withstand ratings
Duration (s) DifferentialContinuous 2In
3 45In2 55In1 80In0.5 100In
> Current circuit burden
Highest phase burden (with three phase rated current)
6VA N = 63.5VA N = 3
At setting current 0.5VA
> Auxiliary supply
Rated Operative Current Drain (mA)Voltage range (V) Quiescent Operated (Vx)24/27 19.2-32.4 30 17.530/34 24-37.5 15 17548/54 37.6-72 15 175110/125 87.5-150 15 90
> Contacts
Contact arrangements2 make and 2 change-over
> Contact ratings
Make and carry for 0.2s 7500VA subject tomaxima of 30A and 300V ac or dc
Carry continuously 5A ac or dc Break ac 1250VA
dc 50W resistive25W inductiveL/R = 0.045s
Subject to maxima of 5A and 300V
Pilot
Volta
ge (V
Peak)
200
160
120
80
40
0 1 0 20 30A-N fault current (x In)
MetrosilLimiter
ZenerLimiter
%In
Through Load (xIn)
100
80
60
40
20
Earth Fault SettingKs = 2.0
N = 3 N = 6
0 0.5 1.0 1.5 2.0
%In
Through Load (xIn)
50
40
30
20
10
Earth Fault SettingKs = 1.0
N = 3 N = 6
0 0.5 1.0 1.5 2.0
60
70
A-N
C-NB-N
C-NB-N
A-N
C-N
A-N
B-N
C-NB-N
A-N
240
200
160
120
80
40
01 2 3 4 5 6 10 20 30 40 50 60 80 100
Kt = 6Kt = 14Kt = 20Kt = 40
Current (multiples of setting)
Opera
tion t
ime (M
illiseco
nds)
Figure 5 Pilot voltage characteristics
Figure 6 Minimum earth fault current for operation with through load
Figure 7 Time characteristics for internal faults
-
6>7
PILOTS
> Pilots isolation
Pilot isolation transformers are required when anylongitudinally induced voltage in the pilot circuit is likelyto exceed 5kV: in effect this means when protectingfeeders operating at voltages in excess of 33kV, unlessthese are short in length.
> Pilot current
The pilot current is typically 30mA for normal throughload conditions and rises to a maximum of 300mAunder through fault conditions.
> Fault settings for plain feeders
The input transformer has a summation ratio of 1.25:1:Nwhere N = 3 for normal use. N = 6 is used where lowearth fault settings are needed. The minimum operatingcurrent will therefore be dependent on the phase orphases involved in the fault. The minimum earth faultcurrent (If) should be greater than twice the leastsensitive earth fault setting to ensure rapid faultclearance.
The range setting of fault settings is shown in table 3.
Table 3
Note: A stabilising resistor is required for single phase protection or when MBCI is fed from delta connected current transformers.
> Reduction of induced pilot loop voltage
Ideally the pilot cores should be wormed (twistedtogether) so that the induced loop voltage is kept to aminimum.
UNIT PROTECTION OFTRANSFORMER FEEDERS
> Fault setting
The relay internal summation is identical to that usedfor plain feeders but the turns ratio used is 2.25:6.This will result in secondary settings as given in thetable below:
Relay setting in amps = Ks x In times the Constant in the table below
A to N 0.44B to N C to N 0.17A to B 0.44B to C 0.17C to A 0.123 Phase 0.14
Table 4
Where Ks = setting multiplier which may be adjustedbetween 0.5 and 2.0
In = relay rated current
NB. The figures quoted in this table are those to beexpected under conditions of secondary injectiontesting.
Note 1: There is a restricted earth fault relay in the neutral of the star connected CTs on the delta side of the power transformer. This provides protection against earth faults on the Delta side of the power transformer when the infeed is into the delta. It will provide settings lower than any of the phase to neutral settings given above.
Note 2: The MBCI relay, when used in the transformer feed application, does not requirea stabilising resistor.
> Cases
Relay type MBCI is provided in case 6 as shown in Figure 8.
Trusted by utilities, industry and railwaysworldwide
Fault Settings(Summation ratio = 1.25/1/N) N = 3 N = 6
Ks is a setting multiplier A - N 0.19Ks.In 0.12Ks.InAnd may be varied B - N 0.25Ks.In 0.14Ks.InFrom 0.5-2.0 C - N 0.33Ks.In 0.17Ks.InIn is the rated relay current A - B 0.8Ks.In
B - C 1.0Ks.InC - A 0.44Ks.InA - B - C 0.5Ks.In
-
INFORMATION REQUIRED WITH ORDER
> Basic scheme reference (refer to table 1)> Types of relay
> Pilot loop resistance and intercore capacitance values. (This information is required to determine whether pilot isolating transformers are required for matching purposes.)
> Pilot insulation level (5kV or 15kV).Is pilot supervision equipment required?
> Is the overcurrent relay required?
> Is the destabilising facility or destabilising /intertrip facility required?
> Pilot voltage:Metrosil (MBCI 01) or Zener limiting (MBCI 02)
> Current rating
> Frequency rating
> Auxiliary dc supply rating
> Auxiliary ac supervision supply rating
> AC intertrip supply rating
Push buttonprojection 10 max
All dimensions in mm
Panel cut-out:Flush mounting fixing details
4 holes 4.4
Flush mounting
149
155
21232 25 min.
11
Reset
157 max.
151
159168
103.624
177
Figure 8 Case outline size 6
48 mm
48mm
2BA connectionscrews
354 mm
310 mm
342 mm
2 holes 6.5 mm
Figure 9 Stabilising resistor
-
AUTO
MAT
ION-
L3-M
BCI-B
R-01
.05-
????
-GB
- -
AREV
A - 2
004.
AREV
A, th
e AR
EVA
logo
and
any
alte
rnativ
e v
ers
ion
ther
eof a
re tr
ade
mar
ks a
nd s
ervi
ce m
arks
of A
REVA
.M
iCO
M is
a re
gist
ered
trade
mar
k of
ARE
VA.A
ll tra
de n
ames
or t
rade
mar
ks m
entio
ned
here
in w
heth
er re
gist
ered
or n
ot, a
re th
e pr
operty
of t
heir
owners
.- 38
9191
982
RCS
PAR
IS -
Prin
ted
in F
rance
- S
ONO
VISI
ON-
ITEP
AREVA T&D Worldwide Contact Centre:http://www.areva-td.com/contactcentre/Tel.: +44 (0) 1785 250 070
www.areva-td.com
AREVA TRACK RECORD - TRANSLAY - S SCHEMES
>> MBCI is the second generation Translay - S product.>> MBCI launched in 1983, with over 13 000 in service worldwide.>> Sister product MHOR analogue differential protection, and
MiCOM P521 numerical unit protection.
Our policy is one of continuous development. Accordingly thedesign of our products may change at any time. Whilst everyeffort is made to produce up to date literature, this brochureshould only be regarded as a guide and is intended forinformation purposes only. Its contents do not constitute an offerfor sale or advise on the application of any product referred to init. We cannot be held responsible for any reliance on anydecisions taken on its contents without specific advice.