MC3000 SeriesInstallation and Operation Manual
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1 .1 PRODUCTSCOVEREDINTHISMANUAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1 .2 PRODUCTCHANGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1 .3 WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1 .4 RECEIVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1 .5 CUSTOMERMODIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1 .6 SAFETYINFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1 .6 .1 EXPLOSIONPROOFAPPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1 .6 .2 EN61800-5-1COMPLIANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1 .6 .3 PICTOGRAPHSUSEDINTHESEINSTRUCTIONS . . . . . . . . . . . . . . . . . . . 2
2 MC3000SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 MC3000MODELDESIGNATIONCODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 MC3000DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 .1 CHASSISANDTYPE1ENCLOSED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 .2 TYPE4,4X,AND12ENCLOSED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 MC3000RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6 THEORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6 .1 DESCRIPTIONOFACMOTOROPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6 .2 DRIVEFUNCTIONDESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6 .2 .1 DRIVEOPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6 .2 .2 CIRCUITDESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6 .2 .3 MC3000INPUTSANDOUTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7 .1 INSTALLATIONAFTERALONGPERIODOFSTORAGE . . . . . . . . . . . . . . . . . . . . . 17
7 .2 EXPLOSIONPROOFAPPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8 INPUTACREQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8 .1 INPUTACPOWERREQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8 .1 .1 VOLTAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8 .1 .2 SUPPLYTRANSFORMERkVARATINGS . . . . . . . . . . . . . . . . . . . . . . . . . 18
8 .2 INPUTFUSINGANDDISCONNECTREQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . 18
9 VOLTAGESELECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9 .1 INPUTVOLTAGERATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
10 POWERWIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
10 .1 WIRINGFORSINGLEPHASEORTHREEPHASEINPUT . . . . . . . . . . . . . . . . . . . . 20
11 MC3000POWERWIRINGDIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
12 INITIALPOWERUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
13 kEYPADCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
13 .1 kEYPADFUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
13 .2 MC3000DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
13 .2 .1 MC3000DISPLAYINSTOPMODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
13 .2 .2 MC3000DISPLAYINRUNMODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
13 .2 .3 MC3000DISPLAYINFAULTMODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
13 .2 .4 MC3000DISPLAYINAUXILIARYMODE . . . . . . . . . . . . . . . . . . . . . . . . . . 28
CONTENTS
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
14 CONTROLWIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
14 .1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
14 .1 .1 kEYPADCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
14 .1 .2 CONTROLWIRINGVS .POWERWIRING . . . . . . . . . . . . . . . . . . . . . . . . . 29
14 .1 .3 TB-2:CIRCUITCOMMON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
14 .1 .4 SURGESUPPRESSIONONRELAYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
14 .2 START/STOPANDSPEEDCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
14 .2 .1 REMOTEMODESELECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
14 .2 .2 TWO-WIRESTART/STOPCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
14 .2 .3 THREE-WIRESTART/STOPCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
14 .2 .4 SPEEDREFERENCESIGNALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
14 .2 .5 SPEEDREFERENCESELECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
14 .2 .6 ANALOGOUTPUTSIGNALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
14 .2 .7 DRIVESTATUSOUTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
15 MC3000CONTROLWIRINGDIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
15 .1 MC3000TERMINALSTRIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
15 .2 TWO-WIRESTART/STOPCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
15 .3 THREE-WIRESTART/STOPCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
15 .4 SPEEDPOTANDPRESETSPEEDCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
16 PROGRAMMINGTHEMC3000DRIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
16 .1 PROGRAMMINGTHEPARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
16 .2 PARAMETERACCESSUSINGSPEEDDIAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
17 PARAMETERMENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
18 DESCRIPTIONOFPARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
19 MC3000PIDSETPOINTCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
19 .1 FEEDBACkDEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
19 .2 THESYSTEM-DIRECTANDREVERSEACTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
19 .3 PIDCONTROL-DIRECTANDREVERSEACTING . . . . . . . . . . . . . . . . . . . . . . . . . . 68
19 .4 SETPOINTREFERENCESOURCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
19 .5 TUNINGTHEPIDCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
19 .6 MC3000DISPLAYINPIDMODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
20 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
21 USERSETTINGRECORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
CONTENTS
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 1
1 GENERAL
1 .1 PRODUCTSCOVEREDINTHISMANUAL
ThismanualcoverstheLenzeACTechMC3000VariableFrequencyDrive .
1 .2 PRODUCTCHANGES
LenzeACTechCorporationreservestherighttodiscontinueormakemodificationstothedesignofitsproductsandmanualswithoutpriornotice,andholdsnoobligationtomakemodificationstoproductssoldpreviously .LenzeACTechCorporationalsoholdsnoliabilityforlossesofanykindwhichmayresultfromthisaction .Instructionmanualswiththemostup-to-dateinformationareavailablefordownloadfromtheLenzeAmericaswebsite(www .lenzeamericas .com) .
1 .3 WARRANTY
LenzeACTechCorporationwarrantstheMCSeriesACmotorcontroltobefreeofdefectsinmaterialandworkmanshipforaperiodoftwoyearsfromthedateofshipmentfromLenzeAmericas'factory .AnMCSeriescontrol,oranycomponentcontainedtherein,whichundernormaluse,becomesdefectivewithinthestatedwarrantytimeperiod,shallbe returned toLenzeACTechCorporation, freightprepaid, forexamination (contactLenzeACTechCorporationforauthorizationpriortoreturninganyproduct) .LenzeACTechCorporationreservestherighttomakethefinaldeterminationastothevalidityofawarrantyclaim,andsoleobligationistorepairorreplaceonlycomponentswhichhavebeenrendereddefectiveduetofaultymaterialorworkmanship .Nowarrantyclaimwillbeacceptedforcomponentswhichhavebeendamagedduetomishandling,improperinstallation, unauthorized repair and/or alterationof theproduct, operation in excessof design specifications or other misuse, or improper maintenance . Lenze AC TechCorporationmakesnowarrantythatitsproductsarecompatiblewithanyotherequipment,ortoanyspecificapplication,towhichtheymaybeappliedandshallnotbeheldliableforanyotherconsequentialdamageorinjuryarisingfromtheuseofitsproducts .
Thiswarrantyisinlieuofallotherwarranties,expressedorimplied.Nootherperson,firmorcorporationisauthorizedtoassume,forLenzeACTechCorporation,anyotherliabilityinconnectionwiththedemonstrationorsaleofitsproducts.
1 .4 RECEIVING
Inspect all cartons for damage which may have occurred during shipping . Carefullyunpackequipmentandinspectthoroughlyfordamageorshortage .Reportanydamagetocarrierand/orshortagestosupplier .Allmajorcomponentsandconnectionsshouldbeexaminedfordamageandtightness,withspecialattentiongiventoPCboards,plugs,knobsandswitches .
1 .5 CUSTOMERMODIFICATION
LenzeACTechCorporation, its sales representativesanddistributors,welcome theopportunitytoassistourcustomersinapplyingourproducts .Manycustomizingoptionsareavailabletoaidinthisfunction .LenzeACTechCorporationcannotassumeresponsibilityforanymodificationsnotauthorizedbyitsengineeringdepartment .
1 .6 SAFETYINFORMATION
SomepartsofLenzeACTechcontrollerscanbeelectricallyliveandsomesurfacescanbehot .Non-authorizedremovaloftherequiredcover,inappropriateuse,andincorrectinstallationoroperationcreatestheriskofsevereinjurytopersonneland/ordamagetoequipment .Alloperationsconcerningtransport,installation,andcommissioningaswellasmaintenancemustbecarriedoutbyqualified,skilledpersonnelwhoarefamiliarwiththe installation,assembly,commissioning,andoperationofvariable frequencydrivesandtheapplicationforwhichitisbeingused .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
2 M301L
1 .6 .1 EXPLOSIONPROOFAPPLICATIONS
Explosionproofmotorsthatarenotratedforinverteruselosetheircertificationwhenusedforvariablespeed .Duetothemanyareasofliabilitythatmaybeencounteredwhendealingwiththeseapplications,thefollowingstatementofpolicyapplies:
LenzeACTechCorporationinverterproductsaresoldwithnowarrantyoffitnessforaparticularpurposeorwarrantyofsuitabilityforusewithexplosionproofmotors .LenzeACTechCorporationacceptsnoresponsibilityforanydirect,incidentalorconsequentialloss,costordamagethatmayarisethroughtheuseofACinverterproductsintheseapplications .Thepurchaserexpresslyagrees toassumeall riskofany loss, costordamagethatmayarisefromsuchapplication .
1 .6 .2 EN61800-5-1COMPLIANCE
WARNING!Thisproductcancausead .c .currentintheprotectiveearthing(PE)conductor .Wherearesidualcurrent-operated(RCD)ormonitoring(RCM)deviceisusedforprotectionincaseofdirectorindirectcontact,onlyanRCDorRCMTypeBisallowedonthesupplysideofthisproduct .
WARNING!LeakageCurrentmayexceed3 .5mAAC .Theminimumsizeoftheprotectiveearth(PE)conductorshallcomplywithlocalsafetyregulationsforhighleakagecurrentequipment .
DANGER!HazardofElectricShockCapacitorsretainchargeforapproximately180secondsafterpowerisremoved .Allowatleast3minutesfordischargeofresidualchargebeforetouchingthedrive .
NOTEControl terminalsprovidebasic isolation (insulationperEN61800-5-1, forup to300V to ground) . Protection against contact can only be ensured by additionalmeasures(e .g .supplementalinsulation) .
WARNING!Inadomesticenvironmentthisproductmaycauseradiointerferenceinwhichcasesupplementarymitigationmeasuresmayberequired .
1 .6 .3 PICTOGRAPHSUSEDINTHESEINSTRUCTIONS
ThesafetyinformationprovidedinthisInstallationandOperatingmanualincludesavisualicon,aboldsignalwordandadescription .
SignalWord!(characterizestheseverityofthedanger)Text(describesthedangerandinformsonhowtoproceed)
Icon SignalWord Meaning ConsequencesifignoredDANGER! Hazardouselectricalvoltage Deathorsevereinjuries .
WARNING! Potential,veryhazardoussituationsforpersonsnearmachinery .
Riskofsevereinjurytopersonneland/ordamagetoequipment .
STOP! Potentialdamagetomaterialandequipment .
Damagetothecontroller/driveoritsenvironment .
NOTE Designatesageneral,usefulnote . None .Ifobserved,thenusingthecontrollerismadeeasier .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 3
2 MC3000SPECIFICATIONS
StorageTemperature -20 to70 C
AmbientOperatingTemperature Chassis -10 to55 C(With2 .5,6,and8kHzcarrier, Type1(IP31) -10 to50 Cderateforhighercarriers) Type4(IP65) -10 to40 C Type12(IP54) -10 to40 C
AmbientHumidity Lessthan95%(non-condensing)
Altitude 3300feet(1000m)abovesealevel withoutderating
InputLineVoltages 240/120Vac,240/200Vac, 480/400Vac,and590/480Vac
InputVoltageTolerance +10%,-15%
InputFrequencyTolerance 48to62Hz
OutputWaveForm SineCodedPWM
OutputFrequency 0-120Hz
CarrierFrequency 2 .5kHzto14kHz
FrequencyStability +0 .00006%/ C
ServiceFactor 1 .00
Efficiency >97%throughoutspeedrange
PowerFactor(displacement) >0 .96
OverloadCurrentCapacity 150%ofoutputratingfor60seconds 180%ofoutputratingfor30seconds
SpeedReferenceFollower 0-10VDC,4-20mA
ControlVoltage 15VDC
AnalogOutputs 0-10VDC,or2-10VDC Proportionaltospeedandload
DigitalOutputs FormCrelay:2Aat28VDCor120Vac Open-collectoroutputs:40mAat30VDC
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
4 M301L
3 MC3000MODELDESIGNATIONCODE
ThemodelnumberofanMC3000Seriesdrivegivesafulldescriptionofthebasicdriveunit(seeexamplebelow) .
EXAMPLE:M3450BP
(MC3000,480Vac,5HP,Type1Enclosure,withaRemotekeypadAssembly)
M3 4 50 B P
Series:
M3 = M3000 Series Variable Speed AC Motor DriveInput Voltage:
1 = 240/120 Vac (For 110, 115, 120, 230 and 240 Vac; 50 or 60 Hz)
2 = 240/200 Vac (For 208, 230, and 240 Vac; 50 or 60 Hz)4 = 480/400 Vac (For 380, 415, 440, 460 and 480 Vac; 50 or 60 Hz)5 = 590/480 Vac (For 440, 460, 480, 575 and 600 Vac; 50 or 60 Hz)
Rating:03 = ¼ HP (0.18 kW) 50 / 51 = 5 HP (3.7 kW) 300 = 30 HP (22 kW)05 = ½ HP (0.37 kW) 75 = 7½ HP (5.5 kW) 400 = 40 HP (30 kW)10 = 1 HP (0.75 kW) 100 = 10 HP (7.5 kW) 500 = 50 HP (37.5 kW)15 = 1½ HP (1.1 kW) 150 = 15 HP (11 kW) 600 = 60 HP (45 kW)20 = 2 HP (1.5 kW) 200 = 20 HP (15 kW)30 = 3 HP (2.2 kW) 250 = 25 HP (18.5 kW)
Input Phase:S = Single phase input only.
No character indicates three phase input onlyEnclosure Type:
A = Chassis - Open Enclosure with Cover RemovedB = NEMA 1 - General Purpose, ventedC = NEMA 4 - Water-tight and Dust-tightD = NEMA 12 - Oil-tight and Dust-tightE = NEMA 4X - Water-tight, Dust-tight, and Corrosion Resistant (Stainless Steel)
Standard Options:H = Additional Form C Relay circuit boardJ = Dynamic Braking circuit boardK = Dynamic Braking & Additional Form C Relay board (not available on all HP sizes - consult factory)
No character when this type of option is not specifiedInterface Options:
P = Remote keypad assemblyNo character when this type of option is not specified
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 5
4 MC3000DIMENSIONS
4 .1 CHASSISANDTYPE1ENCLOSEDD
H
V
1 .00"
RT
MountingTabDetail
Dia .Slot
R
W
P
N
Q Q SDia .
SDia .
ConduitHoles:
0 .88"Dia .
W UIFW<7 .86"T=0 .20"U=0 .34"V=0 .19"
IFW=10 .26"T=0 .28"U=0 .44"V=0 .24"
HP (kW)
INPUT VOLTAGE MODEL H W D N P Q R S
0.25(0.18) 240 / 120 M3103S 7.50 4.70 3.33 2.35 1.60 1.37 5.50 0.88
0.5(0.37)
240 / 120 M3105S 7.50 6.12 3.63 3.77 1.80 1.37 5.50 0.88240 M3205S 7.50 4.70 3.63 2.35 1.90 1.37 5.50 0.88
240/200 M3205 7.50 4.70 3.63 2.35 1.90 1.37 5.50 0.88
1(0.75)
240 / 120 M3110S 7.50 6.12 4.22 3.77 2.40 1.37 5.50 0.88240 M3210S 7.50 4.70 4.33 2.35 2.60 1.37 5.50 0.88
240 / 200 M3210 7.50 4.70 4.33 2.35 2.60 1.37 5.50 0.88480 / 400 M3410 7.50 4.70 3.63 2.35 1.90 1.37 5.50 0.88
590 M3510 7.50 4.70 3.63 2.35 1.90 1.37 5.50 0.88
1.5(1.1)
240/120 M3115S 7.50 6.12 4.22 3.77 2.40 1.37 5.50 0.88240 M3215S 7.50 6.12 4.22 3.77 2.40 1.37 5.50 0.88
240/200 M3215 7.50 4.70 4.33 2.35 2.60 1.37 5.50 0.88
2(1.5)
240 M3220S 7.50 6.12 5.12 3.77 3.30 1.37 5.50 0.88240 / 200 M3220 7.50 6.12 5.12 3.77 3.30 1.37 5.50 0.88480/400 M3420 7.50 6.12 4.22 3.77 2.40 1.37 5.50 0.88
590 M3520 7.50 6.12 4.22 3.77 2.40 1.37 5.50 0.88
3(2.2)
240 M3230S 7.50 6.12 5.12 3.77 3.30 1.37 5.50 0.88240 / 200 M3230 7.50 6.12 5.12 3.77 3.30 1.37 5.50 0.88480 / 400 M3430 7.50 6.12 5.12 3.77 3.30 1.37 5.50 0.88
590 M3530 7.50 6.12 5.12 3.77 3.30 1.37 5.50 0.88
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
6 M301L
HP (kW)
INPUT VOLTAGE MODEL H W D N P Q R S
5(3.7)
240 / 200 M3250 7.88 7.86 5.94 5.13 3.95 1.50 5.88 1.13480 / 400 M3450 7.50 6.12 5.12 3.77 3.30 1.37 5.50 0.88
590 M3551 7.88 7.86 5.94 5.13 3.95 1.50 5.88 1.13
7.5(5.5)
240 / 200 M3275 9.38 7.86 6.84 3.93 4.19 2.00 5.88 1.13480 / 400 M3475 9.38 7.86 6.25 5.13 3.95 1.50 7.38 1.13
590 M3575 9.38 7.86 6.25 5.13 3.95 1.50 7.38 1.13
10(7.5)
240 / 200 M32100 11.25 7.86 6.84 3.93 4.19 2.00 7.75 1.38480 / 400 M34100 9.38 7.86 6.84 3.93 4.19 2.00 5.88 1.13
590 M35100 9.38 7.86 7.40 3.93 4.19 2.00 5.88 1.13
15(11)
240/200 M32150 12.75 7.86 6.84 3.93 4.19 2.00 9.25 1.38480/400 M34150 11.25 7.86 6.84 3.93 4.19 2.00 7.75 1.38
590 M35150 12.75 7.86 6.84 3.93 4.19 2.00 9.25 1.38
20(15)
240 / 200 M32200 12.75 10.26 7.74 5.13 5.00 2.50 9.25 1.38480/400 M34200 12.75 7.86 6.84 3.93 4.19 2.00 9.25 1.38
590 M35200 12.75 7.86 7.40 3.93 4.19 2.00 9.25 1.38
25(18.5)
240 / 200 M32250 15.75 10.26 8.35 5.13 5.00 2.50 12.25 1.38480/400 M34250 12.75 10.26 7.74 5.13 5.00 2.50 9.25 1.38
590 M35250 12.75 10.26 7.74 5.13 5.00 2.50 9.25 1.38
30(22)
240 / 200 M32300 15.75 10.26 8.35 5.13 5.00 2.50 12.25 1.38480/400 M34300 12.75 10.26 7.74 5.13 5.00 2.50 9.25 1.38
590 M35300 12.75 10.26 8.25 5.13 5.00 2.50 9.25 1.38
40(30)
480/400 M34400 15.75 10.26 8.35 5.13 5.00 2.50 12.25 1.38590 M35400 15.75 10.26 8.35 5.13 5.00 2.50 12.25 1.38
50(37.5)
480/400 M34500 19.75 10.26 8.55 5.13 5.75 2.50 16.25 1.75590 M35500 19.75 10.26 8.55 5.13 5.75 2.50 16.25 1.75
60(45)
480/400 M34600 19.75 10.26 8.55 5.13 5.75 2.50 16.25 1.75590 M35600 19.75 10.26 8.55 5.13 5.75 2.50 16.25 1.75
DIMENSIONS-CHASSISANDTYPE1ENCLOSED(continued)
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 7
4 .2 TYPE4,4X,AND12ENCLOSED
1 .00"
W
H
RT
D
MountingTabDetail
V
Dia .Slot
ConduitHoles:
SDia .0 .88"Dia .SDia .
N
P
Q Q
R
W
UIFW<7 .86"T=0 .20"U=0 .34"V=0 .19"
IFW>10 .26"T=0 .28"U=0 .44"V=0 .24"
HP (kW)
INPUT VOLTAGE MODEL H W D N P Q R S
0.25(0.18) 240 / 120 M3103S 7.88 6.12 3.63 3.06 2.00 1.37 5.88 0.88
0.5(0.37)
240 / 120 M3105S 7.88 7.86 3.75 4.80 2.10 1.37 5.88 0.88240 M3205S 7.88 6.12 4.35 3.06 2.70 1.37 5.88 0.88
240/200 M3205 7.88 6.12 4.35 3.06 2.70 1.37 5.88 0.88
1(0.75)
240 / 120 M3110S 7.88 7.86 4.90 4.80 3.25 1.37 5.88 0.88240 M3210S 7.88 6.12 4.35 3.06 2.70 1.37 5.88 0.88
240 / 200 M3210 7.88 6.12 4.35 3.06 2.70 1.37 5.88 0.88480 / 400 M3410 7.88 6.12 4.35 3.06 2.70 1.37 5.88 0.88
590 M3510 7.88 6.12 4.35 3.06 2.70 1.37 5.88 0.88
1.5(1.1)
240/120 M3115S 7.88 7.86 4.90 4.80 3.25 1.37 5.88 0.88240 M3215S 7.88 7.86 4.90 4.80 3.25 1.37 5.88 0.88
240/200 M3215 7.88 6.12 5.25 3.06 3.60 1.37 5.88 0.88
2(1.5)
240 M3220S 7.88 7.86 4.90 4.80 3.25 1.37 5.88 0.88240 / 200 M3220 7.88 7.86 4.90 4.80 3.25 1.37 5.88 0.88480/400 M3420 7.88 7.86 4.90 4.80 3.25 1.37 5.88 0.88
590 M3520 7.88 7.86 4.90 4.80 3.25 1.37 5.88 0.88
3(2.2)
240 M3230S 7.88 7.86 5.90 4.80 4.25 1.37 5.88 0.88240 / 200 M3230 7.88 7.86 5.90 4.80 4.25 1.37 5.88 0.88480 / 400 M3430 7.88 7.86 4.90 4.80 3.25 1.37 5.88 0.88
590 M3530 7.88 7.86 4.90 4.80 3.25 1.37 5.88 0.88
5(3.7)
240 / 200 M3250 9.75 10.26 7.20 5.13 5.25 2.00 7.75 1.13480 / 400 M3450 7.88 7.86 5.90 4.80 4.25 1.37 5.88 0.88
590 M3550 7.88 7.86 5.90 4.80 4.25 1.37 5.88 0.88
7.5(5.5)
240 / 200 M3275 11.75 10.26 8.35 5.13 5.75 2.00 9.75 1.13480 / 400 M3475 9.75 10.26 7.20 5.13 5.25 2.00 7.75 1.13
590 M3575 9.75 10.26 7.20 5.13 5.25 2.00 7.75 1.13
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
8 M301L
HP (kW)
INPUT VOLTAGE MODEL H W D N P Q R S
10(7.5)
240 / 200 M32100 13.75 10.26 8.35 5.13 5.75 2.00 11.75 1.38480 / 400 M34100 11.75 10.26 8.35 5.13 5.75 2.00 9.75 1.13
590 M35100 11.75 10.26 8.35 5.13 5.75 2.00 9.75 1.13
15(11)
240/200 M32150 15.75 10.26 8.35 5.13 5.75 2.00 13.75 1.38480/400 M34150 13.75 10.26 8.35 5.13 5.75 2.00 11.75 1.38
590 M35150 13.75 10.26 8.35 5.13 5.75 2.00 11.75 1.38
20(15)
240 / 200 M32200* 15.75 10.26 8.35 5.13 5.75 2.00 11.75 1.38480/400 M34200 15.75 10.26 8.35 5.13 5.75 2.00 13.75 1.38
590 M35200 15.75 10.26 8.35 5.13 5.75 2.00 13.75 1.38
25(18.5)
240 / 200 M32250* 20.25 10.26 8.35 5.13 5.75 2.00 16.25 1.38480/400 M34250* 15.75 10.26 8.35 5.13 5.75 2.00 11.75 1.38
590 M35250* 15.75 10.26 8.35 5.13 5.75 2.00 11.75 1.38
30(22)
240 / 200 M32300* 20.25 10.26 8.35 5.13 5.75 2.00 16.25 1.38480/400 M34300* 15.75 10.26 8.35 5.13 5.75 2.00 11.75 1.38
590 M35300* 15.75 10.26 8.35 5.13 5.75 2.00 11.75 1.38
40(30)
480/400 M34400* 20.25 10.26 8.35 5.13 5.75 2.00 16.25 1.38590 M35400* 20.25 10.26 8.35 5.13 5.75 2.00 16.25 1.38
50(37.5)
480/400 M34500* 21.00 13.72 8.35 5.13 6.10 2.00 16.25 1.38590 M35500* 21.00 13.72 8.35 5.13 6.10 2.00 16.25 1.38
60(45)
480/400 M34600* 21.00 13.72 8.35 5.13 6.10 2.00 16.25 1.38590 M35600* 21.00 13.72 8.35 5.13 6.10 2.00 16.25 1.38
*Models available in NEMA 12 only
DIMENSIONS-TYPE4,4X,AND12ENCLOSED(continued)
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 9
5 MC3000RATINGS
ThefollowingtablesindicatetheinputandoutputratingsoftheMC3000Seriesdrive .
NOTE: Theoutputcurrentratingsarebasedonoperationatcarrierfrequenciesof8kHzandbelow .Atfullambienttemperature,operationatcarrierfrequenciesabove8kHzrequiresderatingthedrivebymultiplyingtheoutputcurrentratingbythefollowingfactors:0 .94at10kHz,0 .89at12kHz,and0 .83at14kHz .RefertoParameter23-CARRIERinSection18-DESCRIPTIONOFPARAMETERS .
M3100 SERIES RATINGS
MODELINPUT OUTPUT
(200/240 Vac, 50 - 60 Hz) (0 - 200/230 Vac)
MODEL NUMBER1
FOR MOTORSRATED INPUT
PHASE
NOMINALCURRENT2
(AMPS)POWER(KVA)
NOMINALCURRENT(AMPS)
POWER(KVA)HP kW
M3103S 0.25 0.18 1 6.0 / 3.0 0.7 1.4 0.56
M3105S 0.5 0.37 1 9.2 / 4.6 1.1 2.2 0.88
M3110S 1 0.75 1 16.2 / 8.1 1.9 4.0 1.6
M3115S 1.5 1.1 1 21 / 10.4 2.5 5.2 2.11RefertoSection3formodelnumberbreakdown .2RefertoSection8forrecommendedfusetype .
M3200 SERIES RATINGS
MODELINPUT OUTPUT
(200/240 Vac, 50 - 60 Hz) (0 - 200/230 Vac)
MODEL NUMBER1
FOR MOTORSRATED INPUT
PHASE
NOMINALCURRENT2
(AMPS)POWER(KVA)
NOMINALCURRENT(AMPS)
POWER(KVA)HP kW
M3205S 0.5 0.37 1 5.8 / 5.0 1.2 2.5 / 2.2 0.9
M3205 0.5 0.37 3 3.1 / 2.7 1.1 2.5 / 2.2 0.9
M3210S 1 0.75 1 10.3 / 9.0 2.2 4.6 / 4.0 1.6
M3210 1 0.75 3 5.5 / 4.8 2.0 4.6 / 4.0 1.6
M3215S 1.5 1.1 1 13.3 / 11.6 2.8 6.0 / 5.2 2.1
M3215 1.5 1.1 3 7.1 / 6.2 2.6 6.0 / 5.2 2.1
M3220S 2 1.5 1 17.1 / 14.9 3.6 7.8 / 6.8 2.7
M3220 2 1.5 3 9.3 / 8.1 3.4 7.8 / 6.8 2.7
M3230S 3 2.2 1 24 / 21 5.0 11.0 / 9.6 3.8
M3230 3 2.2 3 13.0 / 11.3 4.7 11.0 / 9.6 3.8
M3250 5 3.7 3 20 / 17.7 7.4 17.5 / 15.2 6.1
M3275 7.5 5.5 3 30 / 26 10.6 25 / 22 8.8
M32100 10 7.5 3 37 / 32 13.2 32 / 28 11.2
M32150 15 11 3 55 / 48 19.8 48 / 42 16.7
M32200 20 15 3 70 / 61 25.3 62 / 54 21.5
M32250 25 18.5 3 89 / 77 32.0 78 / 68 27.1
M32300 30 22 3 104 / 90 37.6 92 / 80 31.91RefertoSection3formodelnumberbreakdown .2RefertoSection8forrecommendedfusetype .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
10 M301L
M3400 SERIES RATINGS
MODELINPUT OUTPUT
(400/480 Vac, 50 - 60 Hz) (0 - 400/460 Vac)
MODEL NUMBER1
FOR MOTORSRATED
INPUT PHASE
NOMINALCURRENT2
(AMPS)POWER(KVA)
NOMINALCURRENT(AMPS)
POWER(KVA)HP kW
M3410 1 0.75 3 2.8 / 2.4 2.0 2.3 / 2.0 1.6
M3420 2 1.5 3 4.7 / 4.1 3.4 3.9 / 3.4 2.7
M3430 3 2.2 3 6.6 / 5.7 4.7 5.5 / 4.8 3.8
M3450 5 3.7 3 10.2 / 8.9 7.3 8.7 / 7.6 6.1
M3475 7.5 5.5 3 14.7 / 12.8 10.6 12.6 / 11.0 8.8
M34100 10 7.5 3 18.3 / 15.9 13.2 16.0 / 14.0 11.2
M34150 15 11 3 28 / 24 19.8 24 / 21 16.7
M34200 20 15 3 36 / 31 25.3 31 / 27 21.5
M34250 25 18.5 3 44 / 38 31.9 39 / 34 27.1
M34300 30 22 3 52 / 45 37.6 46 / 40 31.9
M34400 40 30 3 68 / 59 49.0 60 / 52 41.4
M34500 50 37.5 3 85 / 74 61.5 75 / 65 51.8
M34600 60 45 3 100 / 87 72.3 88 / 77 61.3
1RefertoSection3formodelnumberbreakdown .2RefertoSection8forrecommendedfusetype .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 11
M3500 SERIES RATINGS
MODELINPUT OUTPUT
(480/590 Vac, 50 - 60 Hz) (0 - 460/575 Vac)
MODEL NUMBER1
FOR MOTORSRATED
INPUT PHASE
NOMINALCURRENT2
(AMPS)POWER(KVA)
NOMINALCURRENT(AMPS)
POWER(KVA)HP kW
M3510 1 0.75 3 1.9 / 1.9 1.9 1.6 / 1.6 1.6
M3520 2 1.5 3 3.3 / 3.3 3.4 2.7 / 2.7 2.7
M3530 3 2.2 3 4.6 / 4.6 4.7 3.9 / 3.9 3.9
M3550/51 5 3.7 3 7.1 / 7.1 7.3 6.1 / 6.1 6.1
M3575 7.5 5.5 3 10.5 / 10.5 10.7 9.0 / 9.0 8.8
M35100 10 7.5 3 12.5 / 12.5 12.8 11.0 / 11.0 11.0
M35150 15 11 3 19.3 / 19.3 19.7 17.0 / 17.0 16.9
M35200 20 15 3 25 / 25 25.4 22 / 22 21.5
M35250 25 18.5 3 31 / 31 31.2 27 / 27 26.9
M35300 30 22 3 36 / 36 37.1 32 / 32 31.9
M35400 40 30 3 47 / 47 47.5 41 / 41 40.8
M35500 50 37.5 3 59 / 59 60.3 52 / 52 51.8
M35600 60 45 3 71 / 71 72.5 62 / 62 61.7
1RefertoSection3formodelnumberbreakdown .2RefertoSection8forrecommendedfusetype .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
12 M301L
6 THEORY
6 .1 DESCRIPTIONOFACMOTOROPERATION
ThreephaseACmotorsarecomprisedoftwomajorcomponents,thestatorandtherotor .Thestatorisasetofthreeelectricalwindingsheldstationaryinthemotorhousing .Therotorisametalcylinder,fixedtothemotordriveshaft,whichrotateswithinthestator .ThearrangementofthestatorcoilsandthepresenceofthreephaseACvoltagegiverisetoarotatingmagneticfieldwhichdrivestherotor .Thespeedatwhichthemagneticfieldrotatesisknownasthesynchronousspeedofthemotor .Synchronousspeedisafunctionofthefrequencyatwhichthevoltageisalternatingandthenumberofpolesinthestatorwindings .
Thefollowingequationgivestherelationbetweensynchronousspeed,frequency,andthenumberofpoles:
Ss=120f/p
Where: Ss= Synchronousspeed(rpm) f= frequency(Hz) p= numberofpoles
Inthreephaseinductionmotorstheactualshaftspeeddiffersfromthesynchronousspeedasloadisapplied .Thisdifferenceisknownas“slip” .Slipiscommonlyexpressedasapercentageofsynchronousspeed .Atypicalvalueisthreepercentatfullload .
Thestrengthofthemagneticfieldinthegapbetweentherotorandstatorisproportionaltotheamplitudeofthevoltageatagivenfrequency .Theoutputtorquecapabilityofthemotor is, therefore,a functionof theappliedvoltageamplitudeatagiven frequency .Whenoperatedbelowbase (rated) speed,ACmotors run in the rangeof “constanttorque” .Constant torqueoutput is obtainedbymaintaininga constant ratiobetweenvoltageamplitude(Volts)andfrequency(Hertz) .For60Hzmotorsratedat230,460,and575Vac,commonvaluesforthisV/Hzratioare3 .83,7 .66,and9 .58respectively .OperatingwiththeseV/Hzratiosgenerallyyieldsoptimumtorquecapability .Operatingatlowerratiovaluesresultsinlowertorqueandpowercapability .Operatingathigherratiovalueswillcausethemotortooverheat .Moststandardmotorsarecapableofprovidingfulltorqueoutputfrom3to60Hz .However,atlowerspeeds,wheremotorcoolingfansbecomelesseffective,supplementalcoolingmaybeneededtooperateat full torqueoutputcontinuously .
Ifthefrequencyappliedtothemotorisincreasedwhilethevoltageremainsconstant,torque capability will decrease as speed increases . This will cause the horsepowercapabilityofthemotortoremainapproximatelyconstant .Motorsruninthismodewhenoperated above base speed, where drive output voltage is limited by the input linevoltage .Thisoperatingrangeisknownasthe“constanthorsepower”range .Thetypicalmaximumrangeforconstanthorsepowerisabout2 .3to1(60to140Hz) .ThediagrambelowdepictsthecharacteristicsofatypicalACinductionmotorwitha60Hzbasespeed .
WARNING!
Consultmotormanufacturer beforeoperatingmotor and/or drivenequipmentabovebasespeed .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 13
CONSTANTTORQUE CONSTANT HP
TORQUE HORSEPOWER
HORS
EPOW
ER
TORQUE
FREQUENCY(Hz)
TO
RQ
UE
(%
)
20 40 60 80 100 120
150
130
110
90
70
50
30
10
6 .1 .1 VARIABLETORQUEVS .CONSTANTTORQUE
Variablefrequencydrives,andtheloadstheyareappliedto,cangenerallybedividedinto twogroups:constant torqueandvariable torque .Constant torque loads include:vibratingconveyors,punchpresses,rockcrushers,machinetools,andjustabouteveryotherapplicationthat isnotconsideredvariabletorque .Variabletorqueloadsincludecentrifugalpumpsandfans,whichmakeupthemajorityofHVACapplications .
Variabletorqueloadsaregovernedbytheaffinitylaws,whichdefinetherelationshipsbetween speed, flow, torque and horsepower . The diagram below illustrates theserelationships:
0%
25%
50%
75%
100%
100%75%50%25%0%
%SPEED
%TOR
QUE
%HOR
SEPO
WER
%FLO
W
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
14 M301L
“Variabletorque”referstothefactthatthetorquerequiredvarieswiththesquareofthespeed .Also,thehorsepowerrequiredvarieswiththecubeofthespeed,resultinginalargereductioninhorsepowerforevenasmallreductioninspeed .Itiseasilyseenthatsubstantialenergysavingscanbeachievedbyreducingthespeedofafanorpump .Forexample,reducingthespeedto50%resultsina50HPmotorhavingtoproduceonly12 .5%ofratedhorsepower,or6 .25HP .Variabletorquedrivesusuallyhavealowoverloadcapacity(110%-120%for60seconds),becausevariabletorqueapplicationsrarelyexperienceoverloadconditions .Tooptimizeefficiencyandenergysavings,variabletorquedrivesareusuallyprogrammedtofollowavariableV/Hzratio .
Theterm“constanttorque”isnotentirelyaccurateintermsoftheactualtorquerequiredforanapplication .Manyconstant torqueapplicationshave reciprocating loads, suchasvibratingconveyorsandpunchpresses,wheretherotationalmotionofthemotorisbeingconvertedtoalinearmotion .Insuchcases,thetorquerequiredcanvarygreatlyatdifferentpointsinthecycle .Forconstanttorqueloads,thisfluctuationintorqueisnotadirectfunctionofspeed,asitiswithavariabletorqueload .Asaresult,constanttorquedrivestypicallyhaveahighoverloadrating(150%for60seconds)inordertohandlethehigherpeaktorquedemands .Toachievemaximumtorque,constanttorquedrivesfollowaconstantV/Hzratio .
BothMCSeriesproductlines(MC1000andMC3000)havefulloverloadcapacity(150%for60seconds,180%for30seconds),sothateitheronecanbeusedforeithertypeofapplication .TheV/Hzratiocanalsobechangedtooptimizeperformanceforeithertypeofapplication .
6 .2 DRIVEFUNCTIONDESCRIPTION
TheMCSeriesisa16bitmicroprocessorbased,keypadprogrammable,variablespeedACmotordrive .Therearefourmajorsections:aninputdiodebridgeandfilter,apowerboard,acontrolboard,andanoutputintelligentpowermodule .
6 .2 .1 DRIVEOPERATION
IncomingAC line voltage is converted to apulsatingDCvoltageby the input diodebridge .TheDCvoltageissuppliedtothebusfiltercapacitorsthroughachargecircuitwhichlimitsinrushcurrenttothecapacitorsduringpower-up .ThepulsatingDCvoltageisfilteredbythebuscapacitorswhichreducestheripplelevel .ThefilteredDCvoltageenterstheinvertersectionofthedrive,composedofsixoutputintelligentinsulatedgatebi-polartransistors(IGBTs)whichmakeupthethreeoutputlegsofthedrive .EachleghasoneintelligentIGBTconnectedtothepositivebusvoltageandoneconnectedtothenegativebusvoltage .Alternatelyswitchingoneachleg,theintelligentIGBTproducesanalternatingvoltageoneachofthecorrespondingmotorwindings .Byswitchingeachoutput intelligent IGBTataveryhigh frequency (knownas thecarrier frequency) forvaryingtimeintervals,theinverterisabletoproduceasmooth,threephase,sinusoidaloutputcurrentwavewhichoptimizesmotorperformance .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 15
6 .2 .2 CIRCUITDESCRIPTION
Thecontrolsectionconsistsofacontrolboardwitha16bitmicroprocessor,keypadanddisplay .Driveprogrammingisaccomplishedviathekeypadortheserialcommunicationsport .Duringoperationthedrivecanbecontrolledviathekeypad,bycontroldeviceswiredtothecontrolterminalstrip,orbythetheserialcommunicationsport .ThePowerBoardcontainsthecontrolandprotectioncircuitswhichgovernthesixoutputIGBTs .ThePowerBoardalsocontainsachargingcircuitforthebusfiltercapacitors,amotorcurrentfeedbackcircuit,avoltagefeedbackcircuit,andafaultsignalcircuit .Thedrivehasseveralbuiltinprotectioncircuits .Theseincludephase-to-phaseandphase-to-groundshortcircuitprotection,highandlowlinevoltageprotection,protectionagainstexcessiveambienttemperature,andprotectionagainstcontinuousexcessiveoutputcurrent .Activationofanyofthesecircuitswillcausethedrivetoshutdowninafaultcondition .
6 .2 .3 MC3000INPUTSANDOUTPUTS
Thedrivehastwoanaloginputs(0-10VDCand4-20mA)thatcanbeusedforspeedreference,PIDsetpointreference,orPIDfeedback .Aspeedpotentiometer(10,000ohm)canbeusedwiththe0-10VDCinput .
Therearealsotwoanalogoutputs:oneisproportionaltospeed(frequency),andtheotherisproportionaltoload .
Thedrivehasthreeprogrammableoutputsforstatusindication:oneFormCrelayandtwoopen-collectoroutputs .
RefertoSections14-CONTROLWIRINGand15-CONTROLWIRINGDIAGRAMSformoreinformation .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
16 M301L
7 INSTALLATION
WARNING!
Drives must NOT be installed where subjected to adverseenvironmental conditions! Drives must not be installed wheresubjectedtocombustible,oily,orhazardousvaporsordust;excessivemoistureordirt;strongvibration;excessiveambienttemperatures .ConsultLenzeACTechformoreinformationonthesuitabilityofadrivetoaparticularenvironment .
Thedriveshouldbemountedonasmoothverticalsurfacecapableofsafelysupportingtheunitwithoutvibrating .TheLCDdisplayhasanoptimumfieldofview,thisshouldbeconsideredwhendeterminingthemountingposition .
Chassismodelsmustbeinstalledinanelectricalenclosurethatwillprovidecompletemechanicalprotectionandmaintainuniforminternaltemperaturewithinthedrive’sambientoperatingtemperaturerating .AlldrivemodelsMUSTbemountedinaverticalpositionforproperheatsinkcooling .
Maintainaminimumspacingaroundthedriveasfollows:
SPACING REQUIREMENTS
HPSPACING
INCHES mm
0.25 - 5 2 50
7.5 - 25 4 100
30 - 60 6 150
AlldrivemodelsMUSTbemounted inaverticalpositionforproperheatsinkcooling .Fansorblowersshouldbeusedtoinsurepropercoolingintightquarters .Donotmountdrivesaboveotherdrivesorheatproducingequipmentthatwouldimpedethecoolingofthedrive .Notetheambientoperatingtemperatureratingsforeachdrivemodel .
Ifitisnecessarytodrillorcutthedriveenclosureorpanel,extremecaremustbetakentoavoiddamagingdrivecomponentsorcontaminatingthedrivewithmetalfragments(whichcauseshortingofelectricalcircuits) .Coverdrivecomponentswithacleanclothtokeepoutmetalchipsandotherdebris .Useavacuumcleanertocleandrivecomponentsafterdrilling,evenifchipsdonotappeartobepresent .Donotattempttousepositiveairpressuretoblowchipsoutofdrive,asthis tendsto lodgedebrisunderelectroniccomponents .Contaminatingthedrivewithmetalchipscancausedrivefailureandwillvoidthewarranty .
TheMC3000SeriesisULapprovedforsolidstatemotoroverloadprotection .Therefore,aseparatethermaloverloadrelayisnotrequiredforsinglemotorapplications .Inapplicationswhereonedriveisoperatingmorethanonemotor,aseparatethermaloverloadrelayisrequiredforeachmotorperNEC .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 17
7 .1 INSTALLATIONAFTERALONGPERIODOFSTORAGE
WARNING!
Severedamagetothedrivecanresultifit isoperatedafteralongperiodofstorageorinactivitywithoutreformingtheDCbuscapacitors!
If inputpowerhasnotbeenappliedto thedrive foraperiodof timeexceedingthreeyears(duetostorage,etc),theelectrolyticDCbuscapacitorswithinthedrivecanchangeinternally,resultinginexcessiveleakagecurrent .Thiscanresultinprematurefailureofthecapacitorsifthedriveisoperatedaftersuchalongperiodofinactivityorstorage .
Inordertoreformthecapacitorsandpreparethedriveforoperationafteralongperiodof inactivity,apply inputpower to thedrive for8hoursprior toactuallyoperating thedrive/motorsystem .
7 .2 EXPLOSIONPROOFAPPLICATIONS
Explosionproofmotorsthatarenotratedforinverteruselosetheircertificationwhenusedforvariablespeed .Duetothemanyareasofliabilitythatmaybeencounteredwhendealingwiththeseapplications,thefollowingstatementofpolicyapplies:
"LenzeACTechCorporationinverterproductsaresoldwithnowarrantyoffitnessforaparticularpurposeorwarrantyofsuitabilityforusewithexplosionproofmotors .LenzeACTechCorporationacceptsnoresponsibilityforanydirect,incidentalorconsequentialloss,cost,ordamagethatmayarisethroughtheuseofitsACinverterproductsintheseapplications .Thepurchaserexpresslyagrees toassumeall riskofany loss,cost,ordamagethatmayarisefromsuchapplication ."
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
18 M301L
8 INPUTACREQUIREMENTS
WARNING!
Hazard of electrical shock! Disconnect incoming power and waitthreeminutesbeforeservicing thedrive .Capacitors retainchargeafterpowerisremoved .
8 .1 INPUTACPOWERREQUIREMENTS
8 .1 .1 VOLTAGE
Theinputvoltagemustmatchthedrive’snameplatevoltagerating .Voltagefluctuationmustnotvarybygreaterthan10%overvoltageor15%undervoltage .
NOTE
Driveswith dual rated input voltagemust beprogrammed for thepropersupplyvoltage-seeParameter0-LINEVOLTSinSection18-DESCRIPTIONOFPARAMETERS .
TheULfileforthisdriveshowsthatitissuitableforuseonacircuitcapableofdeliveringnotmorethan200,000RMSsymmetricalamperes,atthedrive’sratedvoltage .TheCSAfileidentifiesashort-circuitwithstandratingof5,000RMSsymmetricalamperesatthedrivesratedvoltage .
Threephasevoltage imbalancemustbe less than2 .0%phase tophase .Excessivephasetophaseimbalancecancauseseveredamagetothedrive’spowercomponents .
Motorvoltageshouldmatchlinevoltageinnormalapplications .Thedrive’smaximumoutputvoltagewillequaltheinputvoltage .Useextremecautionwhenusingamotorwithavoltageratingwhichisdifferentfromtheinputlinevoltage .
8 .1 .2 SUPPLYTRANSFORMERkVARATINGS
IfthekVAratingoftheACsupplytransformerisgreaterthantentimestheinputkVAratingofthedrive,adriveisolationtransformer,ora2-3%inputlinereactor(alsoknownasachoke)mustbeadded .
8 .2 INPUTFUSINGANDDISCONNECTREQUIREMENTS
AcircuitbreakeroradisconnectswitchwithfusesmustbeprovidedinaccordancewiththeNationalElectricCode(NEC)andalllocalcodes .
TheMC3000driveiscapableofwithstandingupto150%currentoverloadfor60seconds .Selectafuseormagnetictripcircuitbreakerratedat1 .5timestheinputcurrentratingofthedrive(theminimumsizeshouldbe10amps,regardlessofinputcurrentrating) .RefertoSection5–MC3000RATINGS .
Minimumvoltageratingoftheprotectiondeviceshouldbe250Vacfor240/120Vacand240/200Vacrateddrives,and600Vacfor480/400Vacand590/480Vacdrives .
Currentlimitingtypefusesshouldbeusedwheninputfusingisrequired .Selectfuseswith low I2T values, ratedat200,000AIC .Recommended fusesareBussman typekTk-R,JJNorJJS .Similarfuseswithequivalentratingsbyothermanufacturersmayalsobeacceptable .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 19
9 VOLTAGESELECTION
9 .1 INPUTVOLTAGERATINGS
M3100Seriesdrivesareratedfor240/120Vac,50-60Hzinput .Thedrivewillfunctionwithinputvoltageof120Vac(+10%,-15%)at48to62Hzwhenwiredfor120Vacinput,orwithinputvoltageof240Vac(+10%,-15%),at48to62Hz,whenwiredfor240Vacinput .
M3200Seriesdrivesareratedfor240/200Vac,50-60Hzinput .Thedrivewillfunctionwithinputvoltagesof200to240Vac(+10%,-15%),at48to62Hz .
M3400Seriesdrivesareratedfor480/400Vac,50-60Hzinput .Thedrivewillfunctionwithinputvoltagesof400to480Vac(+10%,-15%),at48to62Hz .
M3500Seriesdrivesareratedfor590/480Vac,50-60Hzinput .Thedrivewillfunctionwithinputvoltagesof480to590Vac(+10%,-15%),at48to62Hz .
Toselecttheproperinputvoltageon240/200VAC30-60Hpmodels,400/480VAC75-150Hpand480/590VAC75-150HpmodelsthePL2plugmustbeinthecorrectposition .PL2islocatedeitheratthelowerrightcorner,orupperrightcornerofthepowerboard,dependingonhorsepower .ThePL2plugisusedtoselectthecorrectinputvoltage .PlugPL2intothetopandmiddlepinstoselect240,480,or590VACorthemiddleandbottompinstoselect200,400,or480 .
NOTE:Inadditiontothevoltageplugselection,Parameter0–LINEVOLTSmustalsobeprogrammedforthepropervoltage .RefertoSection18-DESCRIPTIONOFPARAMETERS .
VoltageSelectionPlug(PL2)
MODELCODE
120014001500
200V400V480V
240V480V590V
240 / 480 / 590 Vac INPUT
MODELCODE
120014001500
200V400V480V
240V480V590V
200 / 400 / 480 Vac INPUT
PL2 PL2
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
20 M301L
10 POWERWIRING
WARNING!
Hazard of electrical shock! Disconnect incoming power and waitthreeminutesbeforeservicing thedrive .Capacitors retainchargeafterpowerisremoved .
Notethedriveinputandoutputcurrentratingsandcheckapplicableelectricalcodesforrequiredwiretypeandsize,groundingrequirements,overcurrentprotection,andincomingpowerdisconnect,beforewiringthedrive .Sizeconservativelytominimizevoltagedrop .
InputfusingandapowerdisconnectswitchorcontactorMUSTbewiredinserieswithterminalsL1,L2,andL3(L1andL2ifinputissinglephase) .IfonehasnotbeensuppliedbyLenzeACTechCorporation,adisconnectmeansmustbewiredduringinstallation .Thisdisconnectmustbeused topowerdown thedrivewhenservicing,orwhen thedriveisnottobeoperatedforalongperiodoftime,butshouldnotbeusedtostartandstopthemotor .
Repetitivecyclingofadisconnectorinputcontactor(morethanonceeverytwominutes)maycausedamagetothedrive.
10 .1 WIRINGFORSINGLEPHASEORTHREEPHASEINPUT
Ifthedriveisnameplatedfor240/120Vacsinglephaseinput,wiretheinputtoterminalsL1andNandjumperterminalsL1toL2for120Vacinputvoltage,orwiretoterminalsL1andL2(donotwiretoN)for240Vacinputvoltage .RefertoSection11-MC3000POWERWIRINGDIAGRAM .
Ifthedriveisnameplatedforthreephaseinputonly,wiretheinputtoterminalsL1,L2,andL3 .
Allthreepoweroutputwires,fromterminalsT1,T2,andT3tothemotor,mustbekepttightlybundledandruninaseparateconduitawayfromallotherpowerandcontrolwiring .
Itisnotrecommendedtoinstallcontactorsordisconnectswitchesbetweenthedriveandmotor .Operatingsuchdeviceswhilethedriveisrunningcanpotentiallycausedamagetothedrive'spowercomponents .Ifsuchadeviceisrequired,itshouldonlybeoperatedwhenthedriveisinaSTOPstate .Ifthereispotentialforthedevicetobeopenedwhilethedriveisrunning,thedrivemustbeprogrammedforCOASTTOSTOP(seeParameter26-STOP),andanauxiliarycontactonthedevicemustbeinterlockedwiththedrive'sruncircuit .Thiswillgivethedriveastopcommandatthesametimethedeviceopens,andwillnotallowthedrivetostartagainuntilthedeviceisclosed .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 21
11 MC3000POWERWIRINGDIAGRAM
T1 T2 T3 L1 L2 L3
FUSEDINPUTVOLTAGE
GNDGND
GND
DISCONNECTMEANS
(REQUIRED)THREEPHASEACMOTOR
240VacSINGLEPHASEINPUT
WIRINGDIAGRAM
120VacSINGLEPHASEINPUT
WIRINGDIAGRAM
L1 L2 N
L1 L2 N
WARNING!
DoNOTconnectincomingACpowertooutputterminalsT1,T2orT3 .Severedamagetothedrivewillresult .
INSTALL,WIRE,ANDGROUNDINACCORDANCEWITHALLAPPLICABLECODES .
NOTES:1 . Wirethemotorforthepropervoltagepertheoutputratingofthedrive .Motorwires
MUSTberuninaseparatesteelconduitawayfromcontrolwiringandincomingACpowerwiring .
2 . DonotinstallcontactorsbetweenthedriveandthemotorwithoutconsultingLenzeACTechformoreinformation .Failuretodosomayresultindrivedamage .
3 . Remove any existing, and do not install, power factor correction capacitorsbetweenthedriveandthemotor .Failuretodosowillresultindrivedamage .
4 . UseonlyULandCSAlistedandapprovedwire .5 . Minimumwirevoltageratings:300Vfor120,200and240Vacsystems,and600
Vfor400,480,and590Vacsystems .6 . Wiregaugemustbebasedonaminimumof125%of the rated input/output
currentofthedrive,andaminimum75 Cinsulationrating .Usecopperwireonly .7 . WireandgroundinaccordancewithNECorCEC,andallapplicablelocalcodes .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
22 M301L
12 INITIALPOWERUP
WARNING!
Hazard of electrical shock! Disconnect incoming power and waitthreeminutesbeforeservicing thedrive .Capacitors retainchargeafterpowerisremoved .
Beforeattemptingtooperatethedrive,motor,anddrivenequipmentbesureallprocedurespertainingtoinstallationandwiringhavebeenproperlyfollowed .
WARNING!
Severedamagetothedrivecanresultifit isoperatedafteralongperiodofstorageorinactivitywithoutreformingtheDCbuscapacitors!
If inputpowerhasnotbeenappliedto thedrive foraperiodof timeexceedingthreeyears(duetostorage,etc),theelectrolyticDCbuscapacitorswithinthedrivecanchangeinternally,resultinginexcessiveleakagecurrent .Thiscanresultinprematurefailureofthecapacitorsifthedriveisoperatedaftersuchalongperiodofinactivityorstorage .
Inordertoreformthecapacitorsandpreparethedriveforoperationafteralongperiodof inactivity,apply inputpower to thedrive for8hoursprior toactuallyoperating thedrive/motorsystem .
Disconnectthedrivenloadfromthemotor .Verifythatthedriveinputterminals(L1,L2,andL3)arewiredtotheproperinputvoltageperthenameplateratingofthedrive .
WARNING!
DoNOTconnectincomingACpowertooutputterminalsT1,T2orT3 .Severedamagetothedrivewillresult .
Energizetheincomingpowerline .TheLCDdisplayshouldlightandflash“TESTING”andthenshowthevoltageandhorsepowerratingofthedrive .Thedisplayshouldthenshow“STOP20 .00HZ”whichindicatesthatthedriveisinaSTOPcondition,andthespeedsetpointis20 .00Hz:
STOP > 20.00 HZ
Ifthedisplaydoesnotappear,removetheincomingpower,waitthreeminutesforthebuscapacitorstodischarge,andverifycorrectinstallationandwiring .Ifthewiringiscorrect,re-applyincomingpowerandnotethedisplayfordrivestatus .Ifthedisplaystilldoesnotappearcallthefactoryforassistance .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 23
Ifthedrivepowersupcorrectly,followtheproceduregivenbelowtocheckthemotorrotation:
1 . VerifythatthereisawirejumperbetweenterminalsTB-1andTB-2ontheMainControlBoard .Thedriveshouldhavethis jumper fromthefactory . If it isnotpresent,addone,otherwisethedrivewillnotstart .
2 . Usethekeytodecreasethespeedsetpointtotheminimumvalueallowed(0 .50HzifParameter10-MINFRQhasnotbeenchanged) .
3 . PresstheSTARTkey .ThedriveshouldindicateRUN,butifthespeedsetpointis0 .50Hz,themotormaynotrotate .Pressthekeyto increasethespeedsetpointuntilthemotorstartstorotate .
4 . Ifthemotorisrotatinginthewrongdirection,presstheSTOPkeyandremovepowerfromthedrive .Waitthreeminutesforthebuscapacitorstodischarge,andswapanytwoofthemotorwiresconnectedtoT1,T2,andT3 .
NOTE1: The drive is phase insensitive with respect to incoming line voltage .Therefore,tochangethemotorrotation,thephasesmustbeswappedatthedriveoutputterminalsoratthemotor .
NOTE2: Ifthedrive'sdisplayisblankwhenpowerisapplied,andthedriveisequippedwithfansatthebottomoftheheatsink,makesurethefansarespinningandarefreeofanyobstruction .Ifanyofthefansarecloggedwithdebris,itwillcauseablankdisplaywhenpowerisapplied .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
24 M301L
13 KEYPADCONTROL
Thedrivecanbeoperatedinanumberofdifferentways:keypad(LOCAL),controldeviceswiredtotheterminalstrip(REMOTE),serialcommunications(SERIAL),orcombinationsofeach .Thedriveshouldfirstbeoperatedfromthekeypadduringinitialstart-up .RefertoSections14-CONTROLWIRING,and18-DESCRIPTIONOFPARAMETERSforinformationonremoteoperation .
13 .1 kEYPADFUNCTIONS
START/STOP Tostartthedrive,presstheSTARTkey .Tostopthedrive,presstheSTOPkey .NOTE1: AjumpermayneedtobeinstalledbetweenTB-1and
TB-2 inorder toSTART thedrive inLOCALmode(refertoParameter30-CONTROL) .
NOTE2: TheSTOPkeyisactiveinbothLOCALandREMOTEmodes .
SPEEDSETPOINT Toincreasethespeedsetpoint,pressthekey .Todecreasethespeedsetpoint,pressthekey .NOTE: Theandkeysareonlyactiveifanotherspeed
referencesourceisnotselected .
LOCAL/REMOTE To toggle between LOCAL and REMOTE mode, press theLOCAL/REMOTEkeytoselectthedesiredmode,andthenpresstheENTERkeywithinthreesecondstoconfirmthechange .NOTE: Parameter30-CONTROLmustbesettokEYPAD
orkEYPAD2forthiskeytobeactive .
AUTO/MANUAL TotogglebetweenAUTOMATIC(terminalstrip)andMANUAL(keypad) speed control, press the AUTO/MAN key to selectthedesiredmode,andthenpresstheENTERkeywithinthreesecondstoconfirmthechange .NOTE: Parameter28-AUTO/MANmustbesettoA/MLOC
orA/MSPDforthiskeytobeactive .RefertoSection14-CONTROLWIRINGforinformationonautomaticspeedreferencesources .
FAULTRESET Use theSTOPkey to reseta fault . If the fault conditionhaspassed,pressingtheSTOPkeywillclearthefaultandreturnthedrivetoaSTOPcondition .NOTE: IfanOUTPUTfaultoccurs,therewillbea30second
delaybeforethefaultcanbeclearedusingtheSTOPkey .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 25
13 .2 MC3000DISPLAY
ThefollowingdescribesthepossibledisplayconfigurationsfortheMC3000Seriesdrivewhenoperatingasastandarddrive(withoutPIDcontrol) .RefertoSection19-MC3000PIDSETPOINTCONTROLforacompletedescriptionofdriveoperationwhenusingPIDcontrol .
13 .2 .1 MC3000DISPLAYINSTOPMODE
WhenthedriveisintheSTOPmode,therearethreepossibledisplays .ThefirstistheSPEEDdisplay,whichlookslikethis:
STOP > 60.00 HZ
DRIVESTATUS
SPEEDSETPOINT
SPEEDUNITS
DIRECTION(FORWARD)
NOTE
RefertoParameter31-UNITSfortheSPEEDUNITSdisplayoptions .
PressingtheENTERkeywillchangethedisplayfromtheSPEEDindicationtothe%LOADindication:
STOP > 0% LOAD
DRIVESTATUS
PERCENTLOAD
DIRECTION(FORWARD)
PressingtheENTERkeyagainwillchangethedisplayfromthe%LOADindicationtotheVAC(motorvoltage)indication:
STOP > 0 VAC
DRIVESTATUS
MOTORVOLTAGE
DIRECTION(FORWARD)
PressingENTERagainwillchangethedisplaybacktotheSPEEDindication .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
26 M301L
ThefollowingtableshowsthepossibleDRIVESTATUSindicationsthatcanappearonthedrivedisplay:
DRIVE STATUS TABLE
DISPLAY DESCRIPTION
STOP Drive to STOP mode - No output to motor.
RUN Drive is in RUN mode and is within + 0.3 Hz of the speed setpoint.
FAULTDrive has shut down due to a FAULT condition. If the fault condition has passed, pressing the STOP key will clear the fault and return thedrive to the STOP mode.
LOCK Drive is in FAULT LOCKOUT after five unsuccessful restart attempts.
BRAKE DC BRAKE is energized.
LIMIT Drive is in CURRENT LIMIT due to an overloaded motor, or ACCEL is set too fast.
F DEC Drive is in DECEL FREEZE because DECEL is set too fast.
13 .2 .2 MC3000DISPLAYINRUNMODE
WhenthedriveisintheRUNmode,thedefaultdisplaywilllooklikethis:
RUN > 60.00 HZ
DRIVESTATUS
SPEEDSETPOINT
SPEEDUNITS
DIRECTION(FORWARD)
AsintheSTOPmode,theENTERkeycanbeusedtotogglethedisplayfromSPEEDto%LOADtoVAC(motorvoltage):
RUN > 85% LOAD
DRIVESTATUS
PERCENTLOAD
DIRECTION(FORWARD)
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 27
RUN > 460 VAC
DRIVESTATUS
MOTORVOLTAGE
DIRECTION(FORWARD)
NOTE
DuringaccelerationanddecelerationtotheSPEEDSETPOINT,theDRIVESTATUSwillshowtheactualdrivespeed .WhentheSPEEDSETPOINTisreached,theDRIVESTATUSwillchangetoRUN(orSTOPifthedriveisdeceleratingtoaSTOP) .
13 .2 .3 MC3000DISPLAYINFAULTMODE
Whenthedrivetripsonafault,thedisplaywillautomaticallychangetotheFAULTdisplay,whichindicatestheFAULTMESSAGE:
FAULT: OVERLOAD
DRIVESTATUS
FAULTMESSAGE
InFAULTmode,theENTERkeywilltogglethedisplaybetweenfourscreens:FAULT,SPEED,%LOADandVAC .TheDRIVESTATUSforthesedisplayswillbeFAULT .AnexampleisshownbelowofthedriveintheFAULTmodedisplayingSPEED .
FAULT > 60.00 HZ
DRIVESTATUS
SPEEDSETPOINT
SPEEDUNITS
DIRECTION(FORWARD)
NOTE
To clear a FAULT, press the STOP key, issue a remote STOPcommandatTB-1,oruseTB-13D(refertoParameter50-TB13D) .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
28 M301L
13 .2 .4 MC3000DISPLAYINAUXILIARYMODE
IftheENTERkeyishelddown,thedisplaywillentertheauxiliarymodeandcyclebetweentwodisplays:aCONTROLdisplaythatindicatesthecontrolsource(LOCAL,REMOTE,orSERIAL),AUTOorMANUALmode,andthespeedreferencesource,andaTIMEdisplaythatindicatestotalelapsedruntime .WhentheENTERkeyisreleased,thedisplaywillreturntothepreviousscreen .Examplesoftheauxiliarymodedisplaysareshownbelow:
CONTROLDISPLAY
LOCAL -- AUTO -- IDC
CONTROLSOURCE
AUTO/MANMODE
SPEEDREFERENCE
SOURCE
TIMEDISPLAY
TIME: 487.2 HRS
ThetablebelowshowsthepossibleSPEEDREFERENCESOURCEindicationsfortheCONTROLdisplayintheauxiliarymode:
SPEED REFERENCE SOURCE TABLE
DISPLAY DESCRIPTION
KEY KEYPAD - and keys.
VDC 0 - 10 VDC analog input at TB-5A (In PID mode, this indicates that the SETPOINT reference is a 0-10 VDC signal).
IDC 4 - 20 mA analog input at TB-5B (In PID mode, this indicates that the SETPOINT reference is a 4-20 mA signal).
SP#1 - SP#4 PRESET SPEED #1 - PRESET SPEED #4
MKBMANUAL KEYBOARD - The and keys are used for speedcontrol. This occurs in PID mode when the drive is put into HAND(open-loop) mode.
AKBAUTO KEYBOARD - The and keys are used as the PIDSETPOINT reference. This occurs in PID mode when the drive is put into AUTO (closed-loop) mode.
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 29
14 CONTROLWIRING
14 .1 GENERAL
14 .1 .1 kEYPADCONTROL
Thedrivecanbecontrolledbythekeypadorbycontroldeviceswiredtotheterminalstrip .Thedrivewillrunfromthekeypad“outofthebox”,aslongasthefactoryjumperbetweenTB-1andTB-2ispresent,asshownbelow .Ifthejumperisnotpresent,addone,otherwisethedrivewillnotstartfromthekeypad .RefertoSection13-kEYPADCONTROL .
FACTORYJUMPER
1 2 5A 5B 6 10A 12A RXA TXB10B 2 13A 13B 13C 13D 14 15 2 16 17 18
14 .1 .2 CONTROLWIRINGVS .POWERWIRING
ExternalcontrolwiringMUSTberuninaseparateconduitawayfromallotherinputandoutputpowerwiring .Ifcontrolwiringisnotkeptseparatefrompowerwiring,electricalnoisemaybegeneratedonthecontrolwiringthatwillcauseerraticdrivebehavior .Usetwistedwiresorshieldedcablegroundedat thedrivechassisONLY .RecommendedcontrolwireisBelden8760(2-wire)or8770(3-wire),orequivalent .
Torquethecontrolterminalsto2lb-in(0 .2Nm) .Becarefulnottoovertorquethecontrolterminals,as thiswill causedamage to the terminal strip .This isnot coveredunderwarrantyandcanonlyberepairedbyreplacingthecontrolboard .
14 .1 .3 TB-2:CIRCUITCOMMON
TheTB-2terminalsareusedascircuitcommonforthestart/stop,inputselect,local/remote,analoginput,andanalogoutputfunctions .TherearethreeTB-2terminalsavailableontheterminalstrip,andtheyareallinternallyconnectedtoeachotheronthemaincontrolboard .IfnecessaryTB-2maybeconnectedtochassisground .
NOTE
TB-2 MUST be connected to chassis ground when using serialcommunications .
14 .1 .4 SURGESUPPRESSIONONRELAYS
Currentandvoltagesurgesandspikesinthecoilsofcontactors,relays,solenoids,etc,nearorconnectedtothedrive,cancauseerraticdriveoperation .Therefore,asnubbercircuitshouldbeusedoncoilsassociatedwiththedrive .ForACcoils,snubbersshouldconsistofaresistorandacapacitorinseriesacrossthecoil .ForDCcoils,afree-wheelingorflybackdiodeshouldbeplacedacrossthecoil .Snubbersaretypicallyavailablefromthemanufacturerofthedevice .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
30 M301L
14 .2 START/STOPANDSPEEDCONTROL
14 .2 .1 REMOTEMODESELECTION
In order to respond to external START/STOP commands, the drive must be in theREMOTEmode .TheREMOTEmodecanbeselectedbyoneofthreemethodsontheMC3000drive:
1 . ProgramParameter30-CONTROLtoREMOTE .
2 . ProgramParameter30-CONTROLtokEYPADorkEYPAD2,whichactivatestheLOCAL/REMOTEkeyon thekeypad .Press theLOCAL/REMOTEkey toselectREMOTEmode,andthenpresstheENTERkeywithinthreeseconds .
3 . ProgramParameter30-CONTROLtoTBSTRIP,andprogramthefunctionofterminalTB-13AorTB-13C(Parameter47or49)toLOCALSELECT .DONOTmakeacontactclosurebetweenTB-13AorTB-13CandTB-2(makingthecontactclosurewillselectLOCALmode) .
14 .2 .2 TWO-WIRESTART/STOPCONTROL
Atwo-wirestart/stopcircuitcanbeaccomplishedasfollows:
1 . SelectREMOTEmode(seeabove) .
2 . ConnectajumperbetweenTB-12AandTB-2toprovideapermanentSTARTcommandtothedrive .
3 . WireanormallyopenmaintainedcontactbetweenTB-1andTB-2 .ClosethiscontacttoRUNthedriveandopenthiscontacttoSTOPthedrive .
RefertothewiringdiagraminSection15 .2 .
14 .2 .3 THREE-WIRESTART/STOPCONTROL
Athree-wirestart/stopcircuitcanbeaccomplishedasfollows:
1 . SelectREMOTEmode(seeabove) .
2 . Wire a normally closed momentary STOP contact between TB-1 and TB-2 .MomentarilyopenthiscontacttoSTOPthedrive .
3 . WireanormallyopenmomentarySTARTcontactbetweenTB-12AandTB-2 .MomentarilyclosethiscontacttoSTARTthedrive .
RefertothewiringdiagraminSection15 .3 .
14 .2 .4 SPEEDREFERENCESIGNALS
Thedriveallowsforthreeanalogspeedreferenceinputs:aspeedpotentiometer(10,000Ohm),0-10VDC,or4-20mA .
SPEEDPOT ConnectthewipertoterminalTB-5A,andconnectthehighandlowendleadstoterminalsTB-6andTB-2,respectively .
0-10VDC WirethepositivetoterminalTB-5AandthenegativetoterminalTB-2 .TB-5Ainputimpedanceis200kilohms .
4-20mA WirethepositivetoterminalTB-5BandthenegativetoterminalTB-2 .TB-5Binputimpedanceis100ohms .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 31
14 .2 .5 SPEEDREFERENCESELECTION
AUTO/MANvs.LOCAL/REMOTE
FortheMC3000Seriesdrive,operatinginstandard(non-PID)mode,AUTO/MANreferstospeedcontrol,andLOCAL/REMOTEreferstoSTART/STOPcontrol .AUTOMATICandMANUALspeedcontrolselectionisaffectedbywhetherthedriveisinLOCALorREMOTEmode,asdescribedbelow .RefertoSection19-MC3000PIDSETPOINTCONTROLforacompletedescriptionofdriveoperationwhenusingthePIDcontrolfunction .
AUTO/MANSELECTIONINLOCALMODE
InLOCALmode (keypadstart/stopcontrol),AUTOMATICandMANUALselection isdeterminedbyParameter28-AUTO/MAN .WhenParameter28issettoA/MLOCorA/MSPD,theAUTO/MANkeyonthekeypadisactiveandcanbeusedtotogglebetweenMANUAL(keypad)andAUTOMATIC(0-10VDC,4-20mA,orpresetspeeds)speedcontrol .ThisisdonebypressingtheAUTO/MANkeytoselectthedesiredmode,andthenpressingtheENTERkeywithinthreesecondstoconfirmthechange .
WhenAUTOMATICmodeisselected,oneoftheTB-13inputselectsmustbeprogrammedtoselectthedesiredspeedreference,andthatTB-13terminalmustbeclosedtoTB-2 .Thedrivewillthenrespondtotheautomaticspeedreference .IfthecontactclosureisnotmadebetweentheTB-13terminalandTB-2,thedrivewillremaininAUTOmode,butspeedcontrolwilldefaulttothekeypad .Therefore,iftheFormCrelayoropen-collectoroutputsaresettoindicateAUTO/MANmode,theywillstillindicateAUTOmode .
AUTO/MANSELECTIONINREMOTEMODE
InREMOTEmode(terminalstripstart/stopcontrol),speedcontroliseitherselectedusingtheAUTO/MANkey(Parameter28-AUTO/MANmustbesettoA/MSPDtodothis),orbyusingtheTB-13inputselects .
IfAUTOMATICmodeisselectedusingtheAUTO/MANkey(Parameter28-AUTO/MANmustbesettoA/MSPDtodothis),andaspeedreferenceisnotselectedusingoneoftheTB-13inputselects,thedrivewillremaininAUTOmode,butspeedcontrolwilldefaulttothekeypad .Therefore,iftheFormCrelayoropen-collectoroutputsaresettoindicateAUTO/MANmode,theywillstillindicateAUTOmode .
IfthedriveisconfiguredtoselectAUTOMATICmodebyusingoneofthetheTB-13inputselects,closingtheTB-13terminaltoTB-2selectsAUTOMATICmode,andopeningtheTB-13terminalselectsMANUAL(keypad)mode .Therefore,iftheTB-13terminalisnotclosedtoTB-2,andtheFormCrelayoropen-collectoroutputsaresettoindicateAUTO/MANmode,theywillindicateMANUALmode .
0-10VDCand4-20mAINPUTSIGNALS
TB-13A,TB-13B,andTB-13Ccanallbeprogrammedtoselect0-10VDCor4-20mAinput .
PRESETSPEEDS
TB-13Acanbeprogrammed toselectSPEED#1,TB-13B toselectSPEED#2,andTB-13C to selectSPEED#3 .Closingany twoof these terminals toTB-2will selectSPEED#4 .RefertoParameters1-4:SPEED#1-#4inSection18-DESCRIPTIONOFPARAMETERS .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
32 M301L
MOP-MOTOROPERATEDPOT
TB-13AandTB-13Bareusedforthisfunction,whichsetsthespeedofthedriveusingcontactswiredtotheterminalstrip .ProgramTB-13AtoselectDECFREQ,andprogramTB-13B to select INC FREQ . Closing TB-13A to TB-2 will activate the DEC FREQfunction,andwillcausethespeedsetpointtodecreaseuntilthecontactisopened .DECFREQwilloperatewhenthedriveisinRUNmodeorSTOPmode .ClosingTB-13BtoTB-2willactivatetheINCFREQfunction,andwillcausethespeedsetpointtoincreaseuntilthecontactisopened .INCFREQwillonlyoperatewhenthedriveisinRUNmode .
NOTE
IfTB-13A,TB-13B,andTB-13Careallprogrammedtoselectspeedreferences, and twoor threeof the terminals are closed toTB-2,the higher terminal has priority and will override the others . Forexample,ifTB-13Aisprogrammedtoselect0-10VDC,andTB-13CisprogrammedtoselectPRESETSPEED#3,closingbothterminalstoTB-2willcausethedrivetorespondtoPRESETSPEED#3,becauseTB-13CoverridesTB-13A .
14 .2 .6 ANALOGOUTPUTSIGNALS
Thereare two terminals thatcansupplyanalogoutputsignalsproportional tooutputfrequencyor load . TerminalTB-10Acanprovidea0-10VDCor a2-10VDCsignalproportionaltooutputfrequency,andTB-10Bcanprovidethesamesignalsproportionaltoload .The2-10VDCsignalscanbeconvertedtoa4-20mAsignalusingaresistorin series with the signal such that the total circuit resistance is 500 ohms . Refer toParameters:42-TB10AOUT,[email protected],44-TB10BOUT,[email protected] .
14 .2 .7 DRIVESTATUSOUTPUTS
ThecontrolboardhasoneFormCrelayatterminalsTB-16,TB-17,andTB-18 .Contactsarerated2ampsat28VDCor120Vac .
Therearealso twoopen-collectoroutputsat terminalsTB-14andTB-15 .Theopen-collectorcircuitisacurrent-sinkingtyperatedat30VDCand40mAmaximum .Anexternalpowersupply(30VDCmax)mustbeusedtopowertheopen-collectoroutputs .Thedrivedoesnothaveadedicatedpowersupplyfortheopen-collectoroutputs .
TheFormCrelayandopen-collectoroutputscanbeprogrammedformanydifferentstatusindications .RefertoParameters52-TB14OUT,53-TB-15OUT,and54-RELAY .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 33
15 MC3000CONTROLWIRINGDIAGRAMS
15 .1 MC3000TERMINALSTRIP
Shownbelowistheterminalstriponthemaincontrolboard,alongwithabriefdescriptionofthefunctionofeachterminal .Wiringshownabovetheterminalstripindicatesinternalwiringonthemaincontrolboard .
FORM CRELAY
1 2 5A 5B 6 10A 12A RXA TXB10B 2 13A 13B 13C 13D 14 15 2 16 17 18
STOPCIRCUIT COM
MON
0-10 VDC SPEED REFERENCE INPUT
10 VDC SUPPLY FOR SPEED POT
0-10 OR 2-10 VDC OUTPUT: FREQUENCY
0-10 OR 2-10 VDC OUTPUT: LOAD
CIRCUIT COMM
ON
START
TB-13A FUNCTION SELECT
TB-13B FUNCTION SELECT
TB-13C FUNCTION SELECT
TB-13D FUNCTION SELECT
OPEN-COLLECTOR OUTPUTOPEN-COLLECTOR OUTPUT
RS-485 SERIALCOM
MUNICATIONS
CIRCUIT COMM
ON
4-20 mA SPEED REFERENCE INPUT
TheTB-2terminalsareinternallytiedtogether
NOTE
The function of terminals TB-10A, TB-10B, TB-13A, TB-13B, TB-13C,TB-13D,TB-14,TB-15,TB-16,andTB-18aredependentontheprogrammingofcertainparameters .Inmostcases,thenameoftheparametermatchesthenumberof the terminal,allowingquickandeasyprogrammingoftheterminalstosuittheapplication .TheexceptionisTB-16andTB-18,whicharegovernedbyParameter54-RELAY .
Acompletedescriptionofoperating thedrive in theREMOTEmodecanbefound inSection14 .2 .Thefollowingdiagramsprovideaquickreferencetowirethedriveforthemostcommonconfigurations .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
34 M301L
15 .2 TWO-WIRESTART/STOPCONTROL
Shownbelowisthewiringdiagramforatypicaltwo-wirestart/stopcontrolscheme,usingonemaintainedcontact(suchasthatfromaPLC)forRUNandSTOPcommands .ClosethecontacttoRUN,andopenthecontacttoSTOP .Alsoshownisthewiringfora0-10VDCor4-20mAspeedreferencesignal .
STOPCIRCUIT COM
MON
0-10 VDC INPUT4-20 m
A INPUT
CIRCUIT COMM
ON
START FORWARD
MAINTAINEDRUN/STOPCONTACT
1 2 5A 5B 6 10A 12A RXA TXB10B 2 13A 13B 13C 13D 14 15 2 16 17 18
START REVERSE0-10 VDC or 4-20 mA SELECT (see Note 3)
FWD REV(see Note 2)
TheTB-2terminalsareinternallytiedtogether
NOTES:
1 . CloseTB-1toTB-2toRUN,andopentoSTOP .
2 . IfREVERSEdirection isrequired,TB-13Cmustbeset toSTARTREVERSE(refer toParameter49-TB13C) . IfREVERSEisnotrequired,simply jumperTB-12AtoTB-2 .
3 . ProgramTB-13A,13B,or13Ctoselecttheappropriatespeedreferencesignalthatwillcontrolthedrivespeed(refertoParameters47,48,and49) .WhenthatTB-13terminalisclosedtoTB-2,thedrivewillrespondtotheselectedspeedreferencesignal .Inthediagramabove,TB-13Aisprogrammedtoselecteithera0-10VDCor4-20mAsignal .
4 . IfthecontactclosureisnotmadebetweenTB-13AandTB-2toselectaspeedreference,thedrivewilldefaulttokeypadspeedcontrol .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 35
15 .3 THREE-WIRESTART/STOPCONTROL
Shownbelowis thewiringdiagramfora typical three-wirestart/stopcontrolscheme,usingmomentarycontacts (suchaspushbuttons) forSTARTandSTOPcommands .Alsoshownisthewiringfora0-10VDCor4-20mAspeedreferencesignal
STOPCIRCUIT COM
MON
0-10 VDC INPUT4-20 m
A INPUT
CIRCUIT COMM
ON
START FORWARD
MOMENTARY STOP CONTACT
1 2 5A 5B 6 10A 12A RXA TXB10B 2 13A 13B 13C 13D 14 15 2 16 17 18
START REVERSE
0-10 VDC or 4-20 mA SELECT (see Note 3)
FWD REV(see Note 2)
MOMENTARY START CONTACT
TheTB-2terminalsareinternallytiedtogether
NOTES:
1 . MomentarilycloseTB-12AtoTB-2toSTART,andmomentarilyopenTB-1toTB-2toSTOP .
2 . IfREVERSEdirection isrequired,TB-13Cmustbeset toSTARTREVERSE(refertoParameter49-TB13C) .IfREVERSEisnotrequired,connecttheothersideofthestartbuttontoTB-12A .
3 . ProgramTB-13A,13B,or13Ctoselecttheappropriatespeedreferencesignalthatwillcontrolthedrivespeed(refertoParameters47,48,and49) .WhenthatTB-13terminalisclosedtoTB-2,thedrivewillrespondtotheselectedspeedreferencesignal .Inthediagramabove,TB-13Aisprogrammedtoselecteithera0-10VDCor4-20mAsignal .
4 . IfthecontactclosureisnotmadebetweenTB-13AandTB-2toselectaspeedreference,thedrivewilldefaulttokeypadspeedcontrol .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
36 M301L
15 .4 SPEEDPOTANDPRESETSPEEDCONTROL
ShownbelowisthewiringdiagramforacontrolschemethatutilizesaspeedpotandPRESETSPEEDSforspeedcontrol,andeitheratwo-wireorthree-wireSTART/STOPcircuit:
STOPCIRCUIT COM
MON
0-10 VDC INPUT
10 VDC SUPPLY
CIRCUIT COMM
ON
START
1 2 5A 5B 6 10A 12A RXA TXB10B 2 13A 13B 13C 13D 14 15 2 16 17 18
PRESET SPEED #3
SPEED POT(10 K)
PRESET SPEED #1
PRESET SPEED #2
CIRCUIT COMM
ON
TheTB-2terminalsareinternallytiedtogether
NOTES:1 . ProgramthePRESETSPEEDS(Parameters1-4)tothedesiredvalues .2 . ProgramTB-13AtoselectSPEED#1,TB-13BtoselectSPEED#2,andTB-13C
toselectSPEED#3(seeParameters47,48and49) .3 . Toselectapresetspeed,closetheappropriatepresetspeedterminaltoTB-2 .
ToselectSPEED#4,closeanytwoofthepresetspeedterminalstoTB-2 .4 . Forspeedpotcontrol,oneoftheTB-13terminalsneedstobeprogrammedto
select0-10VDC .ClosetheselectedTB-13terminaltoTB-2forspeedpotcontrol .Thiswillresultinthelossofoneofthepresetspeeds .
5 . Ifnoneofthepresetspeeds(orthespeedpot)areselectedviacontactclosures,thedrivewilldefaulttokeypadspeedcontrol .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 37
16 PROGRAMMINGTHEMC3000DRIVE
16 .1 PROGRAMMINGTHEPARAMETERS
TheMC3000keypadservestwopurposes:operatingthedrivewhenintheLOCALmode,andprogrammingtheparametersforparticularapplications .Thekeypadisshownbelow,alongwiththedisplaythatshouldappearwhenthedriveisfirstpoweredup:
AUTO
LOCAL
STOP > 20.00 HZ
START
STOPENTERREMOTE
MANPROGRUN
Toprogramthedrive,thePROGRAMmodemustbeenteredbypressingthePROG/RUNbutton .Ifthepasswordprotectionisdisabled,pressingthePROG/RUNbuttonwillresultindirectentryintothePROGRAMmode .Ifthepasswordprotectionisenabled,thePASSWORDpromptwillappearwhenanattemptismadetoenterthePROGRAMmode .ThePASSWORDpromptappearsasfollows:
PASSWORD 0000
CURSOR
Toenterthepassword,usetheUPandDOWNarrowkeystoscroll tothepasswordvalue,andthenpresstheENTERkey .
NOTE
Thefactorydefaultpasswordis0019 .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
38 M301L
Oncethecorrectpasswordisentered,thePROGRAMmodewillbeenteredandthefirstparameterwillbedisplayed,whichisParameter0-LINEVOLTS .Thisisshownbelow:
LINE VOLTS AUTO
PARAMETERNAME
PARAMETERVALUE
CURSOR
Toscrollthroughtheparameters,usetheandkeysonthekeypad .Whenthedesiredparameterisfound,presstheENTERkeytoshiftthecursorfromtheparameternametotheparametervalue .Inthisexample,thecursorshiftsfromLINEVOLTStoAUTO:
LINE VOLTS AUTO
PARAMETERNAME
PARAMETERVALUE
CURSOR
Theparametervaluecanthenbechangedusingtheandkeys .Iftheparameterhasanumericalvalue,thekeywillincreasethevalueandthekeywilldecreasethevalue .Iftheparameterhasspecificchoicesthatcanbeselected,theandkeyswillscrollthroughthelistofpossiblesettings .Whenthedesiredvalueoroptionisselected,presstheENTERkeytostorethenewsetting .IfthenewsettingisnotENTERED,itwillnottakeeffectandtheoldsettingwillstillbevalid .
IfthePROG/RUNkeyispushedwhilethecursorishighlightingtheparametervalue,thevaluewillchangebacktotheoriginalsetting(ifithadbeenchanged,butnotENTERED),andthecursorwillshiftbacktotheparametername .PressingPROG/RUNagainwillexitthePROGRAMmode .IfthePROGRAMmodeisenteredagainwithintwominutes,thelastparameterthatwasviewed,orchanged,willcomeuponthedisplay .Aftertwominuteshaselapsed,thepasswordwillhavetobeenteredagainwhenattemptingtoaccessthePROGRAMmode .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 39
16 .2 PARAMETERACCESSUSINGSPEEDDIAL
SPEEDDIALisusedtoaccessparametersquicklyusingtheparameternumber .Onceaccessed, theparametercanbeprogrammedasdescribed inSection16 .1 .SPEEDDIALisaccessedbypressingtheAUTO/MANkeywhileinthePROGRAMmode .ThiswillactivatetheSPEEDDIALdisplayasshownbelow:
- SPEED DIAL -
OnceinSPEEDDIAL,theandkeyswillallowtheoperatortoscrollthroughtheparameternumbers .ThedisplaywillcontinuetoshowSPEEDDIALwhilescrollingthroughtheparameternumbers,asshownbelow:
#11 SPEED DIAL
Whenthedesiredparameterisreached,theSPEEDDIALdisplaywillbereplacedbytheparametername:
#11 MAX FRQ
Oncethedesiredparameterisdisplayedonthescreen,presstheENTERkeytodisplaytheparameternameandpresentsetting .TheparametersettingcannowbechangedbythemethoddescribedinSection16 .1 .PresstheAUTO/MANkeytoreturntoSPEEDDIAL .
NOTE
SPEEDDIALisonlyactiveinMC3000driveswhichhavetheModbusserialcommunicationsprotocol .UnitsthathavetheMetasysprotocoldonothavethisfeature .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
40 M301L
17 PARAMETERMENU
PARAMETER MENU
PARAM.NUMBER
PARAMETERNAME
RANGE OFADJUSTMENT
FACTORYDEFAULT
0 LINE VOLTSHIGHLOWAUTO
AUTO
1 SPEED #1 MIN FRQ - MAX FRQ 20.00 Hz
2 SPEED #2 MIN FRQ - MAX FRQ 20.00 Hz
3 SPEED #3 MIN FRQ - MAX FRQ 20.00 Hz
4 SPEED #4 MIN FRQ - MAX FRQ 20.00 Hz
5 SKIP #1 0.00 Hz - MAX FRQ 0.00 Hz
6 SKIP #2 0.00 Hz - MAX FRQ 0.00 Hz
7 BAND WID 0.00 - 10.00 Hz 1.00 Hz
8 ACCEL (NOTE 1) 30.0 SEC
9 DECEL (NOTE 1) 30.0 SEC
10 MIN FRQ 0.00 - MAX FRQ .50 Hz
11 MAX FRQ MIN FRQ - 120.0 Hz 60.00 Hz
12 DC BRAKE (NOTE 1) 0.0 VDC
13 DC TIME 0.0 - 999.9 SEC 0.0 SEC
14 DYN BRAKE OFFON OFF
16 CURRENT 25 - 180 % (NOTE 2) 180%
17 MOTOR OL 25 - 100 % 100%
18 BASE 20.00 - 360.0 Hz 60.00 Hz
19 FX BOOST 0.0 - 30.0 % (NOTE 1)
22 TORQUECONSTANTVARIABLE
CT / NOCMPCONSTANT
23 CARRIER 2.5, 6, 8, 10, 12, 14 kHz 2.5 kHz
25 START
NORMALPOWER UP
AUTO 1AUTO 2AUTO 3
NORMAL
26 STOPCOASTRAMPRAMP2
COAST
NOTE1: RefertoSECTION18-DESCRIPTIONOFPARAMETERS
NOTE2: Iflinevoltsissetto"LOW"(orsetto"AUTO"andtheinputvoltageislow),therangeis25-150% .
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 41
PARAMETER MENU
PARAM.NUMBER
PARAMETERNAME
RANGE OFADJUSTMENT
FACTORYDEFAULT
28 AUTO/MAN
A / M LOCAUTO
MANUALA / M SPD
A / M LOC
30 CONTROL
LOCALREMOTESERIALKEYPADTB STRIPKEYPAD 2
LOCAL
31 UNITS
sp: HERTZ, RPM, % HZ,
speed: HERTZ /SEC, /MIN, /HR, GPH, NONE
pid: %, PSI, FPM, CFM, GPM, IN,FT, /SEC, /MIN, /HR, F, C, MPM,
GPH32 HZ MULT 0.10 - 650.0 1.00
33 UNITS DP
XXXXXXXX.XXX.XXX.XXX.XXXX
XXXXX
34 LOAD MLT 95 - 139 % 100%
35 CONTRASTLOWMEDHIGH
MED
36 SLEEP TH 0.00 - 360.0 Hz 0.00 Hz
37 SLEEP DL 0.0 - 300 SEC 30.0 SEC
38 SLEEP BW FB @ MIN - FB @ MAX 0%
39 TB5 MIN 0.00 - 360.0 Hz 0.00 Hz
40 TB5 MAX 0.00 - 360.0 Hz 60.00 Hz
41 AIN FLTR 0.01 - 10.0 SEC 0.02 SEC
42 TB10A OUTNONE0-10V2-10V
NONE
43 @TB10A 0.00 - 360.0 Hz 60.00 Hz
44 TB10B OUTNONE0-10V2-10V
NONE
45 @TB10B 10 - 200 % 125 %
47 TB13A
NONE, 0-10VDC, 4-20MA,
NONESPEED#1, LOC SEL,
DEC FREQ
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
42 M301L
PARAMETER MENU
PARAM.NUMBER
PARAMETERNAME
RANGE OFADJUSTMENT
FACTORYDEFAULT
48 TB13B
NONE0-10VDC4-20MA NONE
SPEED#2INC FREQ
49 TB13C
NONE0-10VDC4-20MA
SPEED#3LOC SEL
STRT REV
NONE
50 TB13DEXT FAULTEXT/FAULTEXT CLEAR
EXT FAULT
525354
TB14 OUTTB15 OUT
RELAY
NONERUN
FAULT/FAULTLOCK
@ SPEEDABOVE #3
I LIMITAUT/MANFLWR PRMIN/MAX
/ MIN/MAXMIN ALR
/ MIN ALRMAX ALR
/ MAX ALRREVERSE
SLEEPSPD=0Hz
NONE
55 TB5B LOSSNONEFAULTSP#4
FAULT
57 SERIALDISABLEDW/TIMERW/O TIMR
DISABLE
58 ADDRESS 1 - 247 (Modbus)1 - 255 (Metasys) 30
61 PASSWORD 0000 - 9999 0019
63 SOFTWARE (VIEW - ONLY) (N/A)
64 MONITOR OFFON ON
65 PROGRAMMAINTAINRESET 60RESET 50
RESET 60
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
M301L 43
PARAMETER MENU
PARAM.NUMBER
PARAMETERNAME
RANGE OFADJUSTMENT
FACTORYDEFAULT
66 HISTORY MAINTAINCLEAR MAINTAIN
70 PID MODEOFF
NORMALREVERSE
OFF
74 PID FB TB-5ATB-5B TB-5A
75 FB @ MIN -32500 to 32500 0.0%
76 FB @ MAX -32500 to 32500 100.0%
77 P GAIN 0.0 - 999.9% 5.00%
78 I GAIN 0.0 - 10.0 SEC 0.0 SEC
79 D GAIN 0.0 - 10.0 SEC 0.0 SEC
80 PID ACC 0.0 - 100.0 SEC 30.0 SEC
81 MIN ALRM FB @ MIN - FB @ MAX 0.0%
82 MAX ALRM FB @ MIN - FB @ MAX 0.0%
98 LANGUAGE (NOTE 1) ENGLISH
99 FAULT HISTORY (VIEW - ONLY) (N/A)
NOTE1: RefertoSECTION18-DESCRIPTIONOFPARAMETERS
-
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
44 M301L
18 DESCRIPTIONOFPARAMETERS
0 LINEVOLTS (LINEVOLTAGE)
Thisparametercalibratesthedriveforthecorrectinputvoltage,andcanbesettoAUTO,HIGH,orLOW .
WhensettoAUTO,thedrivemeasurestheDCbusvoltagewhenpowerisappliedandautomaticallycalibratesitselfaccordingtothemeasuredvalue(DCbusvoltageisequaltoinputvoltagemultipliedby1 .4) .
Thisparametercanalsobeset“manually”,usingtheHIGHorLOWsettings .Foractuallinevoltagesof220-240Vac(on240/200Vacmodels),460-480Vac(on480/400Vacmodels),or575-600Vac(on590/480Vacmodels),setthisparametertoHIGH .AlsousetheHIGHsettingfor240/120Vacsingle-phaseinputmodels .Refertothetablebelow .
Foractuallinevoltagesof200-208Vac(on240/200Vacmodels),380-415Vac(on480/400Vacmodels),or460-480Vac(on590Vacmodels),setthisparametertoLOW .Refertothetablebelow .
INPUT LINE VOLTAGE SELECTION
MODEL RATED INPUTVOLTAGEINPUTPHASE
ACTUAL INPUTVOLTAGE
PARAM.SETTING
M3100S 240 / 120 Vac 1 220 - 240 Vac HIGH
240 / 120 Vac 1 110 - 120 Vac HIGH
M3200(S) 240 Vac 1 220 - 240 Vac HIGH
240 / 200 Vac 3 220 - 240 Vac HIGH
240 / 200 Vac 3 200 - 208 Vac LOW
M3400 480 / 400 Vac 3 460 - 480 Vac HIGH
480 / 400 Vac 3 380 - 415 Vac LOW
M3500 590 / 480 Vac 3 575 - 600 Vac HIGH
590 / 480 Vac 3 460 - 480 Vac LOW
1-4 SPEED#1-#4 (PRESETSPEEDS#1,#2,#3,AND#4)
PRESETSPEEDSareonlyactivewhenthedriveisinAUTOmode,andareactivatedviacontactclosuresbetweenterminalTB-2andterminalsTB-13A,TB-13B,andTB-13C .TheseterminalsmustbeprogrammedaspresetspeedselectsusingParameters47-49:TB13A,TB13B,andTB13C .
Thepresetspeedscanonlybesettovaluesthatarewithintheoperatingrangedefinedbytheminimumandmaximumfrequency(seeParameters10and11) .
ThefollowingtableshowshoweachpresetspeedisselectedusingtheTB-13terminals .T