mcquay enfinity horizontal water source heat pumps r ......installation & maintenance data...
TRANSCRIPT
Installation & Maintenance Data
Group: WSHP
Part Number: 910108372
Date: March 2010
IM 1049-1
©2010 McQuay International
®
McQuay® Enfinity™ Horizontal Water Source Heat PumpsR-410A RefrigerantModel CCH, CCW Unit Sizes 007 – 070
Page 2 of 36 / IM 1049-1
Note: For illustration purposes only. Not all options available with all models. PleaseconsultMcQuaySalesRepresentativeforspecificavailability.
W CCH 1 019 B E Y L S
Product CategoryW = WSHP
Product IdentifierWCCH = Ceiling Mounted/Standard RangeWCCW = Ceiling Mounted/Geothermal
Design Series1 = A Design2 = B Design3 = C Design4 = D Design
Nominal Capacity007 = 7,000 BTU/h009 = 9,000 BTU/h012 = 12,000 BTU/h015 = 15,000 BTU/h019 = 19,000 BTU/h024 = 24,000 BTU/h030 = 30,000 BTU/h036 = 36,000 BTU/h042 = 42,000 BTU/h048 = 48,000 BTU/h060 = 60,000 BTU/h070 = 70,000 BTU/h
Discharge AirS = StraightE = End
Return AirL = LeftR = Right
Future(None)
VoltageA = 115/60/1E = 208-230/60/1F = 208-230/60/3J = 265/60/1K = 460/60/3L = 575/60/350 HzM = 230/50/1N = 380/50/3
ControlsB - MicroTech IIIC - MicroTech III With LonWorksD - MicroTech III With BACnet
Enfinity™ Horizontal Ceiling Unit (Size 007 - 070)
Table of ContentsModelNomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 HorizontalCeilingUnitCCH-CCW . . . . . . . . . . . . . . . 2
Receiving,Storage&Handling . . . . . . . . . . . . . . . . . . . . . 3 UnitLocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FilterAccess . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 AirDischargeConversion . . . . . . . . . . . . . . . . . . . . . 5-6 Ductwork&Attenuation . . . . . . . . . . . . . . . . . . . . . . 7-8 VentilationAir . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 ElectricalData . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 FanAssembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10 Cleaning&Flushing . . . . . . . . . . . . . . . . . . . . . . . . .10-11 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-12 OperatingLimits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 AdditionalInformationforInitialStart-up . . . . . . . . . . 12
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-19 MicroTechIIIControllerTerminalLocations &Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-14 MicroTechIIIUnitController . . . . . . . . . . . . . . . . . . . 15 RemoteResetFeature . . . . . . . . . . . . . . . . . . . . . . . . . . 15 MicroTechIIIControllerwithLonModule . . . . . . . . . 16 MicroTechIIIControllerwithBACnetModule . . . . . 17 MicroTechIIIControllerwithLonModuleon BoardDiagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
ChangingPSCFanMotorSpeed . . . . . . . . . . . . . . . . 19-20 (Optional)ECMMotor-FanSpeed . . . . . . . . . . . . . . 20 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
TypicalWiringDiagrams . . . . . . . . . . . . . . . . . . . . . . 21-25 MicroTechIIIUnitControllerwithPSCMotor
–208/230-60-1UnitSizes015-070 . . . . . . . . . . . . . . . 21 MicroTechIIIUnitControllerwithPSCMotor
–208/230/460/575-60-3UnitSizes024-060 . . . . . . . . 22 MicroTechIIIUnitControllerwithECMMotor
–208/230-60-3UnitSizes024-070 . . . . . . . . . . . . . . . 23 MicroTechIIIUnitControllerwithECMMotor
–208/230-60-1UnitSizes015-070 . . . . . . . . . . . . . . . 24 MicroTechIIIUnitControllerwithECMMotorand
OptionalCommunicationModule–460-60-3 UnitSizes024-070 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
AdditionalAccessories(General) . . . . . . . . . . . . . . . . 26-28 Thermostats&TemperatureSensors . . . . . . . . . . . 26-27 PumpRestartRelayKit . . . . . . . . . . . . . . . . . . . . . . . . 28 MultipleUnitControl . . . . . . . . . . . . . . . . . . . . . . . . . 28
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-33 TheinandoutsofR-410A . . . . . . . . . . . . . . . . . . . . . . 29 TroubleshootingtheRefrigerationCircuit . . . . . . . . . . 30 TypicalRefrigerationCycles . . . . . . . . . . . . . . . . . . . . 31 TroubleshootingtheWSHPUnit . . . . . . . . . . . . . . . . . 32 TroubleshootingtheMicroTechIIIUnitController . . . 33
IM 1049-1 / Page 3 of 36
IMPORTANTThis product was carefully packed and thoroughly inspected before leaving the factory. Responsibility for its safe delivery was assumed by the carrier upon acceptance of the shipment. Claims for loss or damage sustained in transit must therefore be made upon the carrier as follows:VISIBLE LOSS OR DAMAGEAny external evidence of loss or damage must be noted on the freight bill or carrier’s receipt, and signed by the carrier’s agent. Failure to adequately describe such external evidence of loss or damage may result in the carrier’s refusal to honor a damage claim. The form requiredtofilesuchaclaimwillbesuppliedbythecarrier.CONCEALED LOSS OR DAMAGEConcealed loss or damage means loss or damage which does not become apparent until the product has been unpacked. The contents may be damaged in transit due to rough handling even though the carton may not show external damages. When the damage is discovered upon unpacking, make a written request for inspection by the carrier’sagentwithinfifteen(15)daysofthedeliverydateandfileaclaimwiththecarrier.
WARNINGThe installer must determine and follow all applicable codes and regulations. This equipment presents hazards of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow these instructions can result in property damage, severe personal injury or death. This equipment must be installed by experienced, trained personnel only.
Receiving and Storage
Uponreceiptoftheequipment,checkcartonforvisibledamage .Makeanotationontheshipper’sdeliveryticketbeforesigning .Ifthereisanyevidenceofroughhandling,immediatelyopenthecartonstocheckforconcealeddamage .Ifanydamageisfound,notifythecarrierwithin48hourstoestablishyourclaimandrequesttheirinspectionandareport .TheWarrantyClaimsDepartmentshouldthenbecontacted .Donotstandortransportthemachinesonend .Forstoring,eachcartonismarkedwith“up”arrows .Intheeventthatelevatortransfermakesup-endedpositioningunavoidable,donotoperatethemachineuntilithasbeeninthenormaluprightpositionforatleast24hours .Temporarystorageatthejobsitemustbeindoor,completelyshelteredfromrain,snow,etc .Highorlowtemperaturesnaturallyassociatedwithweatherpatternswillnotharmtheunits .Excessivelyhightemperatures,140°F(60°C)andhigher,maydeterioratecertainplasticmaterialsandcausepermanentdamage .
Sharp edges can cause personal injury. Avoid contact with them.
CAUTION
Pre-Installation
1 . Topreventdamage,donotoperatethisequipmentforsupplementaryheatingandcoolingduringtheconstructionperiod .
2. Inspectthecartonforanyspecifictaggingnumbersindicatedbythefactoryperarequestfromtheinstallingcontractor .Atthistimethevoltage,phaseandcapacityshouldbecheckedagainsttheplans .
3 . Checktheunitsizeagainsttheplanstoverifythattheunitisbeinginstalledinthecorrectlocation .
4 . Beforeinstallation,checktheavailableceilingheightversustheheightoftheunit .
5 . Notethelocationandroutingofwaterpiping,condensatedrainpiping,andelectricalwiring .Thelocationsoftheseitemsareclearlymarkedonsubmittaldrawings .
6. Theinstallingcontractorwillfinditbeneficialtoconferwithpiping,sheetmetal,andelectricalforemenbeforeinstallinganyunit .
Note: Check the unit data plate for correct voltage with the plans before installing the equipment. Also, make sure all electrical ground connections are made in accordance with local code. 7 . Thecontractorshallcovertheunitstoprotectthe
machinesduringfinishingofthebuilding.Thisiscriticalwhilesprayingfireproofingmaterialonbarjoists,sandblasting,spraypaintingandplastering .Ifplasticfilmisnotavailable,theshippingcartonmaybemodifiedtocovertheunitsduringconstruction.
8 . Removeallshippingblocksinthefanwheel .
9. Changetheairflowdirectionfromstraightdischargetoenddischargeorviceversabeforetheunitisinstalledintheceiling .Refertothepage5forAirDischargeConversionInstructions .
Page 4 of 36 / IM 1049-1
UNIT DIMENSIONS (mm) SIZE A B C D E 007 – 009 445 864 559 864 508 012 445 1016 559 1016 508 015 – 024 445 1016 559 1016 508 030 – 036 470 1168 584 1168 533 042 – 070 648 1321 762 1321 711
UNIT DIMENSIONS (INCHES) SIZE A B C D E 007 – 009 17.5 34 22 34 20 012 17.5 40 22 40 20 015 – 024 17.5 40 22 40 20 030 – 036 18.5 46 23 46 21 042 – 070 25.5 52 30 52 28
Filter AccessEachunitisshippedwithafilterbracketforsidefilterremoval.Forbottomremovalpushthefilterupintotopbrackettogainclearanceofbottombracketandremovethefilter.Also,asheetmetalductfilterretainercanbefabricatedwhenreturnairductworkisused .
Figure 1: Hanger Bracket Location Dimensions - Sizes 007 thru 060
Figure 2: Hanger Bracket Details - Sizes 007 thru 060
Unit Location1 . Locatetheunitinanareathatallowsforeasy
removalofthefilterandaccesspanels.Leaveaminimumof18"ofclearancearoundtheheatpumpforeasyremoval,andtoperformroutinemaintenance,ortroubleshooting .Providesufficientroomtomakewater,electricalandductconnections .
2 . Thecontractorshouldmakesurethatadequateceilingpanelaccessexists,includingclearanceforhangerbrackets,ductcollarsandfittingsatwaterandelectricalconnections .
3 . Allowadequateroombelowtheunitforacondensatetrapanddonotlocatetheunitabovepipes .
4 . Eachunitissuspendedfromtheceilingbyfourthreadedrods .Therodsareattachedtotheunitcornersbyahangerbracketthrougharubberisolator .
Do not use rods smaller than shown in Figure 2. The rods must be securely anchored to the ceiling or to the bar joists.
5 . Eachunitisfurnishedwithahangerkit .Thekitisshippedunassembledandincludeshangerbrackets,rubberisolators,washers,boltsandlockwashers .LayoutthethreadedrodsperthedimensioninFigures1and2 .
6 . Whenattachingthehangerrodstotheunit,adoublenutisrecommendedsincevibrationcouldloosenasinglenut .Theinstallerisresponsibleforprovidingthehexnutswheninstallinghangerrods .
7 . Leaveminimum3"(76mm)extrathreadedrodbelowthedoublenutsorminimum3"(76mm)clearancebetweentopofunitandceilingabovetofacilitatetoppanelremovalforservicing .
3/8" Threaded Rod(By Others)
Vibration Isolator
Washer
Hex Nuts(By Others)
Bolt & Lock Washer
B
CoilAirflow
E C
D
Comp
ControlBox
FanAssembly
A
CAUTION
IM 1049-1 / Page 5 of 36
Air Discharge ConversionUnitsizes007thru070arestockedasstraightdischarge .Astraightdischargeunitmaybeconvertedtoanenddischargebydoingthefollowing:
Note: The information covered in this section of the blower assembly orientation is typical of McQuay units. Regardless, if you are changing end to straight or straight to end the blower assembly has to turn 90 degrees and simultaneously rotate 180 degrees to achieve the proper orientation. Not all McQuay units will have the same air discharge location but will have the same general results when following the instructions.
1 . Turnoffpowertotheunitatthebreakerbox .
2 . Removethetoppanelbyremovingthescrewsaroundtheperimeterofthetopsecuringittothelowercabinet(Figure3) .
Note: Retain all screws for reinstalling.
Figure 3: Remove Top and Access Panel to Fan Motor
3 . Removetheaccesspaneltothefanmotorbyremovingthetwo(2)screwsatthebottomholdingthepanel(Figure3) .Removethepieceofinsulationatthebottomonthesideofthebottompanel .
4 . Iftheunitbeingconvertedisinstalledandhasbeenoperating,dischargethecapacitor .ReleasethewireclipshowninFigure4toprovideslackinthewires .Ifnecessaryremovethewiretietoprovideadditionalfreewirelength(Figure4) .
Figure 4: Discharge Capacitor and Release Wire Clip
5 . Removethescrewssecuringthefandischargepanelassembly(Figure3) .
DANGERHazardous Voltage!Disconnect all electric power including remote disconnects before servicing. Failure to disconnect power before servicing can cause severe personal injury or death.
Sharp edges can cause personal injury. Avoid contact with them.
CAUTION
Release wire clip to provide slack in wiring
Discharge Capacitor
Capacitor
Remove screws around the perimeter of top
Remove two (2) screws at bottom of access panel to fan motor
Remove Top
Remove Access Panel to Fan Assembly
Fan Discharge Panel Assembly (Bottom-Horizontal Orientation)
Unit Size 019-024 shown to illustrate
Page 6 of 36 / IM 1049-1
6 . Liftthefanassemblyoutrotatingit180degreesandpositionitwithintheopeningattheendoftheunit(Figure5) .Withthefanmotorintheenddischargepositionthefanandhousingorientationistop-horizontal .AStraightairdischargearrangementthehousingisinthebottom-horizontalorientation .
Figure 5: Lift Out the Fan Assembly Turn 90 degrees and Rotate 180°
7 . Securethefanassemblytotheunitframewiththescrewsremovedpreviously .
8 . Reinstalltheaccesspanelinthefanmotoraccessopening(Figure6) .
9 . Reinstallthetoppanelandsecurewithscrewsremovedpreviously .
Note: If installed correctly the fan motor should be accessible when the fan motor access panel is removed.
Figure 6: Reinstall the Top and Access Panel to Motor
Remove screws securing the fan assembly to the cabinet. Note bottom-horizontal orientation of fan assembly
Position the fan assembly in the end opening with the fan in the “top-horizontal” orientation
Rotate the Fan Assembly 180º
Reinstall Access Panel to Fan Motor
Reinstall Top
Completed End Discharge Assembly
Straight Discharge Arrangement(Bottom-Horizontal) Orientation
End Discharge Arrangement(Top-Horizontal) Orientation
IM 1049-1 / Page 7 of 36
Flexible Connector
Acoustic/Thermal Lining
Two 90° Turns(DuctworkSizedBasedonAirflow)
Diffuser
Diffuser
Acoustic/Thermal Lining3ft. (.9m) to 5ft. (1.5m)
Ductwork Supported Independent of Unit
Two 90° Turns Prior to the Intake(DuctworkSizedBasedonAirflow)
Flexible ConnectorAcoustic/Thermal Lining 10ft. (3 meters)
Ductwork Supported Independent of Unit
Acoustic/Thermal Lining
Figure 7: Suggested Supply Ducting per ASHRAE and SMACNA Publications
Figure 8: Suggested Return Ducting per ASHRAE and SMACNA Publications
Acoustic/Thermal Lining
Return Air Intake Located
Away from the Unit Blower
Flexible Connector
Ductwork & AttenuationDischargeductworkisnormallyusedwiththeseconditioners .Returnairductworkmayalsoberequired .
AllductworkshouldconformtoindustrystandardsofgoodpracticeasdescribedintheASHRAESystemsGuide .
Thedischargeductsystemwillnormallyconsistofaflexibleconnectorattheunit,atransitionpiecetothefullductsize,ashortrunofduct,anelbowwithoutvanes,andatrunkductteeingintoabranchductwithdischargediffusersasshowninFigure7 .Thetransitionpiecemustnothaveanglestotalingmorethan30°orseverelossofairperformancecanresult .
Donotconnectthefullductsizetotheunitwithoutusingatransitionpiecedowntothesizeofthedischargecollarontheunit .Withmetalductmaterial,thesidesonlyoftheelbowandentirebranchductshouldbeinternallylinedwithacousticfibrousinsulationforsoundattenuation.Glassfiberductboardmaterialismoreabsorbingandmaypermitomissionofthecanvasconnector .
Asageneralrecommendation,theacousticfibrousinsulationshouldbeatleast1/2inchthickovertheentireductrun(Figure8) .Forbettersoundattenuation,linethelastfivediametersofductbeforeeachregisterwithaone-inchthicksoundblanket .Elbows,teesanddamperscancreateturbulenceordistortionintheairflow.Placeastraightlengthofduct,5to10timestheductwidth,beforethenextfittingtosmoothoutairflow.Diffusersthatarelocatedinthebottomofatrunkductcanalsoproducenoise .Forthissamereason,volumecontroldampersshouldbelocatedseveralductwidthsupstreamfromanairoutlet .
ForHotel,Motel,DormitoryorNursingHomeapplicationsthatuseasingleductdischarge,avelocityof500to600fpmissuggested .Theseapplicationstypicallyhavestaticpressuresaslowas0 .05inchesofwaterandductlengthsapproximatelysixfeetinlength .Thedischargeductmustbefullylinedandhaveasquareelbowwithoutturningvanes .Returnairfortheseapplicationsshouldenterthrougha“low”sidewallfiltergrilleandrouteupthestudspacetoaceilingplenum .Forhorizontalheatpumpsmountedfromtheceiling,aninsulatedreturnplenumissometimesplacedatthereturnairopeningtofurtherattenuateline-of-sightsoundtransmissionthroughreturnopenings .
Page 8 of 36 / IM 1049-1
Returnairductworkcanbeconnectedtothestandardfilterrack.SeeFigure9(sidefilterremovalshown).Thefilterrackcanbeinstalledforbottomfilterremovalorsidefilterremovalbylocatingthebrackets.Forsidefilterremovalthebracketsshouldbelocatedonthebottom,leftside,andtop.Forbottomfilterremovalthebracketsshouldbemountedontheleftsidetopandrightsidewiththespringclipssupportingthefilter.
Donotusesheetmetalscrewsdirectlyintotheunitcabinetforconnectionofsupplyorreturnairductwork,especiallyreturnairductworkwhichcanhitthedrainpanortheaircoil .
Ventilation AirVentilationmayrequireoutsideair .Thetemperatureoftheventilationairmustbecontrolledsothatmixtureofoutsideairandreturnairenteringtheconditionerdoesnotexceedconditionerapplicationlimits .Itisalsotypicaltocloseofftheventilationairsystemduringunoccupiedperiods(nightsetback) .
Theventilationairsystemisgenerallyaseparatebuildingsubsystemwithdistributionductwork .Simpleintroductionoftheoutsideairintoeachreturnairplenumchamberreasonablyclosetotheconditionerairinletisrecommended .Donotductoutsideairdirectlytotheconditionerinlet.Providesufficientdistanceforthoroughmixingofoutsideandreturnair .SeeOperatingLimitsonpage12 .
Figure 9: Standard 1"(25mm) Filter rack/return air duct collar
Standard 1" (25mm)
Figure 10: Optional 2"(51mm) Filter rack/return air duct collar
Tool-less Filter Removal
IM 1049-1 / Page 9 of 36
Piping1 . Allunitsshouldbeconnectedtosupplyandreturn
pipinginatwo-pipereversereturnconfiguration.Areversereturnsystemisinherentlyself-balancingandrequiresonlytrimbalancingwheremultiplequantitiesofunitswithdifferentflowandpressuredropcharacteristicsexistinthesameloop .Checkforproperwaterbalancebymeasuringdifferentialtemperaturereadingacrossthewaterconnections .Toinsureproperwaterflow,thedifferentialflowshouldbe10°Fto14°F(5°Cto8°C)forunitsincoolingmode .
Adirectreturnsystemmayalsoworkacceptably,butproperwaterflowbalancingismoredifficulttoachieveandmaintain .
2 . Thepipingcanbesteel,copperorPVC .3 . Supplyandreturnrunoutsusuallyjointheunitvia
shortlengthsofhighpressureflexiblehosewhicharesoundattenuatorsforbothunitoperatingnoiseandhydraulicpumpingnoise .Oneendofthehoseshouldhaveaswivelfittingtofacilitateremovalforservice .Hardpipingcanalsobebroughtdirectlytotheunit .Thisoptionisnotrecommendedsincenovibrationornoiseattenuationcanbeaccomplished .Thehardpipingmusthaveunionstofacilitateunitremoval .SeeFigure11fortypicalpipingsetup .
4. Someflexiblehosethreadedfittingsaresuppliedwithsealantcompound.Ifnot,applyTeflontapetoassureatightseal .
Figure 11: (Sizes 007 through 070 shown)
Note: Do not overtorque fittings. The maximum torque without damage to fit-tings is 30 foot pounds. If a torque wrench is not available, use as a rule of thumb, finger-tight plus one quarter turn.
Electrical DataGeneral1 . Verifythecompatibilitybetweenthevoltageand
phaseoftheavailablepowerandthatshownontheunitserialplate .LineandlowvoltagewiringmustcomplywithlocalcodesortheNationalElectricalCode,whicheverapplies .
2. Applycorrectlinevoltagetotheunit.A7⁄8"(22mm)holeand/ora1-1⁄8"(29mm)knockoutissuppliedonthesideoftheunit .Adisconnectswitchneartheunitisrequiredbycode .Powertotheunitmustbesizedcorrectlyandhavedualelement(ClassRK5)fusesoranHACRcircuitbreakerforbranchcircuitovercurrentprotection .Seethenameplateforcorrectratings .
3 . Threephase50cycleunits,380/50-3,requireaneutralwirefor230/50-1powertothefancircuit .
4 . Connectthethermostat/subbasewiringwiththepower“off”totheunit .
5 . FieldsuppliedrelaysinstalledontheinputterminalsW1,W2,Y1,Y2orGmayintroduceelectricalnoise .Neverinstallrelaycoilsinserieswiththeinputs .
230 Volt OperationAll208-230voltsingle-phaseandthree-phaseunitsarefactorywiredfor208voltoperation .For230phaseoperation,thelinevoltagetaponthe24volttransformermustbechanged .Disconnectandcaptheredleadwireandinterchangeitwiththeorangeleadwireontheprimaryofthe24volttransformer(sizes007-060) .
Fan AssemblyUnitsizes007through060utilizeastandardmulti-speedPSCmotor .AnECMmotorisstandardonunitsize070andoptionalonunitsizes019through060 .Allfanmotorshaveintegralmountingbracketsandthermaloverloadprotection .Themotorisisolatedfromthefanhousingforminimumvibrationtransmission .PSCFanmotorshaveaterminalstriponthemotorbodyforsimplemotorspeedchangewithoutgoingbacktothecontrolbox .
ForinstructionstoadjustPSCfanspeedsee"ChangingPSCFanSpeed"onpages19-20 .
Allthefan/motorassemblieshavearemovableorificeringonthehousingtoaccommodatemotorandfanwheelremovalwithoutdisconnectingtheductwork .Thefanhousingprotrudesthroughthecabinetallowingadequatematerialforconnectionofflexibleduct.Eachmodelunitisshippedfromthefactoryformaximumperformanceandminimumsoundrequirements .Fansoundlevelsandperformancecanbeaffectedbyexternalstaticpressure .
BallValves
SupplyRiser
Return Riser
CondensateRiser
Supply Air
Hanger Kits (4)
Flex Hoses
Electrical Access Panel
Page 10 of 36 / IM 1049-1
5 . Supplyandreturnshutoffvalvesarerequiredateachconditioner .Thereturnvalveisusedforbalancingandshouldhavea“memorystop”sothatitcanalwaysbeclosedoffbutcanonlybereopenedtotheproperpositionfortheflowrequired.
6 . Nounitshouldbeconnectedtothesupplyandreturnpipinguntilthewatersystemhasbeencleanedandflushedcompletely.Afterthecleaningandflushinghastakenplace,theinitialconnectionshouldhaveallvalveswideopeninpreparationforwatersystemflushing.
7 . Condensatepipingcanbesteel,copperorPVC .Eachunitincludesacondensateconnection .
8 . Thecondensatedisposalpipingmustbetrapped .Thepipingmustbepitchedawayfromtheunitnotlessthan1⁄4"perfoot.Theunithasa3/4inchfemalepipefittingoneachwatersourceheatpumptoaccommodatethecondensedrainconnection .Factorysuppliedcondensatehoseassemblieshaveapipethreadfittingtofacilitateconnectionofaflexiblevinylorsteelbraidedhose.AcompletecopperorPVCcondensesystemcanbeused.UnionfittingsinthecopperorPVClinesshouldbeappliedtofacilitateremoval .
Figure 12: Condensate disposal trapping detail
9 . Donotlocateanypointinthedrainsystemabovethedrainconnectionofanyunit .
10.Automaticflowcontrolleddevicesmustnotbeinstalledpriortosystemcleaningandflushing.
11 .Ahighpointofthepipingsystemmustbevented .12.Checklocalcodefortheneedfordielectricfittings.
Optional Field Installed Vent
11⁄2"(38 mm)
11⁄2"(38 mm)
1⁄4" Per Foot(21 mm Per Meter)
Return Runout
Supply Runout
Mains
Flexible Hose
Runouts InitiallyConnected Together
Cleaning & Flushing System1. Priortofirstoperationofanyconditioner,thewater
circulatingsystemmustbecleanedandflushedofallconstructiondirtanddebris .
Iftheconditionersareequippedwithwatershutoffvalves,eitherelectricorpressureoperated,thesupplyandreturnrunoutsmustbeconnectedtogetherateachconditionerlocation .Thiswillpreventtheintroductionofdirtintotheunit .SeeFigure13 .
Figure 13: Supply & return runouts connected together
2 . Fillthesystematthecitywatermakeupconnectionwithallairventsopen.Afterfilling,closeallairvents .
Thecontractorshouldstartmaincirculatorwiththepressurereducingvalveopen .Checkventsinsequencetobleedoffanytrappedair,ensuringcirculationthroughallcomponentsofthesystem .
Powertotheheatrejectorunitshouldbeoff,andthesupplementaryheatcontrolsetat80°F(27°C) .
Whilecirculatingwater,thecontractorshouldcheckandrepairanyleaksinthepiping .Drainsatthelowestpoint(s)inthesystemshouldbeopenedforinitialflushandblowdown,makingsurecitywaterfillvalvesaresettomakeupwateratthesamerate .Checkthepressuregaugeatpumpsuctionandmanuallyadjustthemakeuptoholdthesamepositivesteadypressurebothbeforeandafteropeningthedrainvalves .Flushshouldcontinueforatleasttwohours,orlongerifrequired,toseeclear,cleandrainwater .
3 . Shutoffsupplementalheaterandcirculatorpumpandopenalldrainsandventstocompletelydraindownthesystem .Shortcircuitedsupplyandreturnrunoutsshouldnowbeconnectedtotheconditionersupplyandreturnconnections .Donotusesealersattheswivelflareconnectionsofhoses.
IM 1049-1 / Page 11 of 36
4 . Trisodiumphosphatewasformerlyrecommendedasacleaningagentduringflushing.However,manystatesandlocalitiesbantheintroductionofphosphatesintotheirsewagesystems .Thecurrentrecommendationistosimplyflushlongerwithwarm80°F(27°C)water .
5. Refillthesystemwithcleanwater.Testthewaterusinglitmuspaperforacidity,andtreatasrequiredtoleavethewaterslightlyalkaline(pH7 .5to8 .5) .Thespecifiedpercentageofantifreezemayalsobeaddedatthistime .UsecommercialgradeantifreezedesignedforHVACsystemsonly .Donotuseautomotivegradeantifreeze .
Oncethesystemhasbeenfilledwithcleanwaterandantifreeze(ifused),precautionsshouldbetakentoprotectthesystemfromdirtywaterconditions .Dirtywaterwillresultinsystemwidedegradationofperformanceandsolidsmayclogvalves,strainers,flowregulators,etc.Additionally,theheatexchangermaybecomecloggedwhichreducescompressorservicelifeorcausesprematurefailure .
6 . Settheloopwatercontrollerheataddsetpointto70°F(21°C)andtheheatrejectionsetpointto85°F(29°C) .Supplypowertoallmotorsandstartthecirculatingpumps.Afterfullflowhasbeenestablishedthroughallcomponentsincludingtheheatrejector(regardlessofseason)andairventedandlooptemperaturesstabilized,eachoftheconditionerswillbereadyforcheck,testandstart-up,airbalancing,andwaterbalancing .
Start-up1 . Openallvalvestofullopenpositionandturnon
powertotheconditioner .2 . Setthermostatfor“FanOnly”operationby
selecting“Off”atthesystemswitchand“On”atthefanswitch .If“Auto”fanoperationisselected,thefanwillcyclewiththecompressor .Checkforproperairdelivery .
3 . Forthoseunitsthathavetwo-speedmotors,reconnectforlowspeedoperationifnecessary .
4 . Setthermostatto“Cool .”Ifthethermostatisanautomaticchangeovertype,simplysetthecoolingtemperaturetothecoolestposition .Onmanualchangeovertypesadditionallyselect“Cool”atthesystemswitch .
Again,manyconditionershavetimedelayswhichprotectthecompressor(s)againstshortcycling .Afterafewminutesofoperation,checkthedischargegrillesforcoolairdelivery .Measurethetemperaturedifferencebetweenenteringandleavingwater .Itshouldbeapproximately1½timesgreaterthanthe
heatingmodetemperaturedifference .Forexample,ifthecoolingtemperaturedifferenceis15°F(8°C),theheatingtemperaturedifferenceshouldhavebeen10°F(5°C) .
Withoutautomaticflowcontrolvalves,targetacoolingtemperaturedifferenceof10°Fto14°F(5°Cto8°C) .Adjustthecombinationshutoff/balancingvalveinthereturnlinetoawaterflowratewhichwillresultinthe10˚Fto14°F(5°Cto8°C)difference .
5 . Setthermostatto“Heat .”Ifthethermostatistheautomaticchangeovertype,setsystemswitchtothe“Auto”positionanddepresstheheatsettingtothewarmestselection .Someconditionershavebuilt-intimedelayswhichpreventthecompressorfromimmediatelystarting .Withmostcontrolschemes,thefanwillstartimmediately .Afterafewminutesofcompressoroperation,checkforwarmairdeliveryatdischargegrille .Ifthisisa“coldbuilding”start-up,leaveunitrunninguntilreturnairtotheunitisatleast65°F(18°C) .
Measurethetemperaturedifferencebetweenenteringandleavingairandenteringandleavingwater .Withenteringwaterof60°Fto80°F(16°Cto27°C),leavingwatershouldbe6°Fto12°F(3 .3°Cto6 .6°C)cooler,andtheairtemperaturerisethroughthemachineshouldnotexceed35°F(19°C) .Iftheairtemperatureexceeds35°F(19°C),thenthewaterflowrateisinadequate.
6 . Checktheelevationandcleanlinessofthecondensateline.Iftheairistoodryforsufficientdehumidification,slowlypourenoughwaterintothecondensatepantoensureproperdrainage .
7 . Iftheconditionerdoesnotoperate,checkthefollowingpoints:
a . Issupplyvoltagetothemachinecompatible? b . Isthermostattypeappropriate? c . Isthermostatwiringcorrect?8 . Iftheconditioneroperatesbutstopsafterabrief
period: a. Isthereproperairflow?Checkfordirtyfilter,
incorrectfanrotation(3-phasefanmotorsonly), orincorrectductwork .
b. Isthereproperwaterflowratewithin temperaturelimits?Checkwaterbalancing; backflushunitifdirt-clogged.
9 . Checkforvibratingrefrigerantpiping,fanwheels,etc .
10.Donotlubricatethefanmotorduringthefirstyearofoperationasitisprelubricatedatthefactory .
11 .FieldsuppliedrelaysinstalledontheinputterminalsW1,W2,Y1,Y2orGmayintroduceelectricalnoise .Neverinstallrelaycoilsinserieswiththeinputs .
Page 12 of 36 / IM 1049-1
Standard Range Geothermal Range Units Units Cooling Heating Cooling Heating Min. Entering... Water 1,2 13ºC 13ºC -1ºC -6ºC Normal Entering Water 29ºC 21ºC 25ºC 4ºC Max Entering Water 43ºC 32ºC 43ºC 32ºC
Standard Range Geothermal Range Units Units Cooling Heating Cooling Heating Min. Entering Water 1,2 55ºF 55ºF 30ºF 20ºF Normal Entering Water 85ºF 70ºF 77ºF 40ºF Max Entering Water 110ºF 90ºF 110ºF 90ºF
Standard Range Geothermal Range Units Units Cooling Heating Cooling Heating Min. Ambient Air 10ºC 10ºC 5ºC 5ºC Normal Ambient Air 27ºC 21ºC 27ºC 21ºC Max Ambient Air 38ºC 29ºC 38ºC 29ºC Min. Entering Air 1,2 10ºC 10ºC 10ºC 5ºC Normal Entering Air db/wb 27/19ºC 21ºC 27/19ºC 21ºC Max Entering Air db/wb 1,2 38/28ºC 27ºC 38/28ºC 27ºC
Standard Range Geothermal Range Units Units Cooling Heating Cooling Heating Min. Ambient Air 50ºF 50ºF 40ºF 40ºF Normal Ambient Air 80ºF 70ºF 80ºF 70ºF Max Ambient Air 100ºF 85ºF 100ºF 85ºF Min. Entering Air 1,2 50ºF 50ºF 50ºF 40ºF Normal Entering Air db/wb 80/67ºF 70ºF 80/67ºF 70ºF Max Entering Air db/wb 1,2 100/83ºF 80ºF 100/83ºF 80ºF
Additional Information For Initial Start-upStandard Range units CCHUnitsaredesignedtostart-upinanambientof50°F(10°C),withenteringairat50°F(10°C),withenteringwaterat70°F(21°C),withbothairandwaterflowratesusedintheISO13256-1ratingtest,forinitialstart-upinwinter .
Note: This is not a normal or continuous operating condition. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.
Geothermal Range units CCWGeothermalheatpumpunitsaredesignedtostart-upinanambientof40°F(5°C),withenteringairat40°F(5°C),withenteringwaterat25°F(-4°C),withbothairandwateratflowratesusedintheISO13256-1ratingtest,forinitialstart-upinwinter .
Note: This is not a normal or continuous operating condition. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.
Operating LimitsEnvironmentThisequipmentisdesignedforindoorinstallationonly .Shelteredlocationssuchasattics,garages,etc.,generallywillnotprovidesufficientprotectionagainstextremesintemperatureand/orhumidity,andequipmentperformance,reliability,andservicelifemaybeadverselyaffected .
At ARI flow rate. Maximum and minimum values may not be co bined. If one
value is at maximum or minimum, the other two conditions may not exceed the normal condition for standard units. Extended range units may combine any two maximum or minimum conditions, but not more than two, with all other conditions being normal conditions.
Table 2: Air Limits - °F (English units)
Table 4: Water - °F (English units)
Table 3: Air Limits - °C (SI units)
Table 5: Water - °C (SI units)
IM 1049-1 / Page 13 of 36
Jumper Description Options JP1 Mode Open for normal operation mode Shorted for service/test operation mode JP2 Fan operation only applies to Open for continuous fan operation network controls Shorted for cycling fan operation JP3 Freeze protection Open for water freeze protection Shorted for antifreeze protection JP4 Future spare Future spare JP5 Set point adjustment range only Open for adjustment range of -3.0° to +3.0° F applies to network controls with a Shorted for 50° to 90° F adjustment range room temperature sensor JP6 Room control type Open for thermostatic room control Shorted for room temperature sensor control, MicroTech III only JP7 Future spare Future spare JP8 Future spare Future spare
Table 6: MicroTech® III Unit Controller Terminals Locations and Descriptions
H1 - 1 24 24 VAC Power Input
H1 - 2 C 24 VAC Common
H2 - 1 SL1 Fan Output - Switched L1
H2 - 2 Blank Terminal
H2 - 3 N Fan Neutral
H3 - 1 HP1-1 High Pressure Switch 1 Input Terminal 1
H3 -2 HP1-2 High Pressure Switch 1 Input Terminal 2
H4 - 1 Discharge Air Temp Common
H4 - 2 Discharge Air Temp Signal
H4 - 3 Leaving Water Temp Common
H4 - 4 Leaving Water Temp Signal
H5 - 1 1 I/O Exp Module Common (Gnd)
H5 - 2 I/O Exp Module Common (Gnd)
H5 - 3 I/O Exp Module +5 VDC
H5 - 4 I/O Exp Module SPI CE1
H5 - 5 I/O Exp Module SPI CLK
H5 - 6 I/O Exp Module SPI OUT
H5 - 7 I/O Exp Module SPI IN
H5 - 8 I/O Exp Module +12 VDC
H5 - 9 I/O Exp Module 24 VAC
H5 - 10 I/O Exp Module 24 VAC
H5 - 11 Spare
H5 - 12 Spare
H6-1 1 CondensateOverflowSignalInput
H6 - 2 Low Temp 1 Sensor Common
H6 - 3 Low Temp 1 Sensor Signal
H6 - 4 Low Pressure Switch 1 Source Voltage
H6 - 5 Low Pressure Switch 1 Signal
H6 - 6 Reversing Valve 1 Common
H6 - 7 Reversing Valve 1 Output
H7 - 1 1 Dummy Terminal
H7 - 2 Dummy Terminal
H7 - 3 Red LED Output
H7 - 4 Green LED Output
H7 - 5 Yellow LED Output
H7 - 6 Red-Green-Yellow LED Common
H8 - 1 1 Isolation Valve/Pump Request Relay N/O
H8 - 2 Isolation Valve/Pump Request Relay N/C
H8 - 3 24 VAC Common
H9 - 1 1 Return Air Temperature Signal
H9 - 2 Return Air Temperature Common
TB1 - 1 1 Room Sensor LED Output
TB1 - 2 2 Fan Mode / Heat-Cool-Auto Input
TB1 - 3 3 Setpoint Adjust Input
TB1 - 4 4 Room Temperature Sensor / Tenant Override
TB1 - 5 5 DC Signal Common
Test-1 R 24 VAC
Test-2 W2 Heat Stage 2 Input
Test-3 W1 Heat Stage 1 Input
Test-4 Y2 Cool Stage 2 Input
Test-5 Y1 Cool Stage 1 Input
Test-6 G Fan
TB2 - 1 R 24 VAC
TB2 - 2 A Alarm Output
TB2 - 3 W2 Heat Stage 2 Input
TB2 - 4 W1 Heat Stage 1 Input
TB2 - 5 Y2 Cool Stage 2 Input
TB2 - 6 Y1 Cool Stage 1 Input
TB2 - 7 G Fan Input
TB2 - 8 O Tenant Override Input
TB2 - 9 C 24 VAC Common
TB3 - 1 E Mark IV Emergency Shutdown Input
TB3 - 2 U Mark IV Unoccupied/Occupied Input
L1 - 1 L1 - 1 Line Voltage Terminal 1
L1 - 2 L1 - 2 Line Voltage Terminal 2
L1 - 3 L1 - 3 Line Voltage Terminal 3
N1 N1 Neutral Terminal 1
N2 N2 Neutral Terminal 2
N3 N3 Neutral Terminal 3
Table 7: Configuration Jumper Settings
Page 14 of 36 / IM 1049-1
Figure 13: MicroTech III Unit Controller Terminal Locations
Figure 14: Location of Configuration Jumpers on the MicroTech III Unit Controller
Note: A random start delay time between 180 and 240 seconds is generated at power up.
The IV/PR(H8) terminals of the MicroTech III unit controller are used for motorized valve / pump restart. This terminal passes a voltage signal whenever the unit compressor is turned on. This signal is detected by a pump restart relay providing a N.O. or N.C. set of contacts for heat pump loop circulation pump or motorized valve control. When used with a system control (by others), the relay operation accommodates turning off circulation pumps during unoccupied periods with a safety override dependent, at minimum, on WSHP’s need. The IV/PR(H8) terminals may be “daisy chained” between 200 units.
IM 1049-1 / Page 15 of 36
Mode / Fault Status LED’s Thermostat Alarm Light Yellow Green Red Output-Terminal “A” Occupied, Bypass, Standby, or Tenant Off On Off Energized Override Unoccupied On On Off Energized CondensateOverflow On Off Off De-engergized High Pressure 1 Fault Off Off Flash De-energized Low Pressure 1 Fault Off Off On De-energized Low Temperature 1 Fault Flash Off Off De-energized Brownout Off Flash Off De-energized Emergency Shutdown Off Flash Off De-energized Room/Return Air or Low
Flash Flash On De-engergized Temp Sensor 1 Failure
Service Test Mode On On Off De-energized
Enabled 1 Serial EEPROM On On On De-energized Corrupted Network“Offline” Off Off Off De-enegized Received
Remote Reset FeatureTheRemoteResetfeatureprovidesthemeanstoremotelyresetautomaticlockoutsgeneratedbyhigh-pressureand/orlow-temperature(inheating)faults .WhentheMicroTechIIIunitcontrollerisinautomaticlockoutduetooneofthesefaults,andthecauseofthefaultconditionhasbeenalleviated,energizingtheO-terminalfor10secondsormorewillforcetheMicroTechIIIunitcontrollertoclearthelockout .Aunitpowercyclecanalsobeusedtoclearanautomaticlockoutiftheconditionscausingthefaulthavebeenalleviated .
TheIntelligentresetfeaturehelpstominimizenuisancetripsofautomaticresetlockoutscausedbyhigh-pressureand/orlow-temperature(inheating)faults .Thisfeatureclearsfaultsthefirsttwotimestheyoccurwithina24-hourperiodandtriggersanautomaticlockoutonthe3rdfault .Theretrycountisresettozeroevery24hours .
TheMicroTechIIIunitcontrollerhasbuilt-innightsetbackoperation .A“grounded’signaltothe“U”terminalonTB3oftheunitcontrolputstheunitintotheunoccupiedmodefornightsetbackoperation .FanoperationterminatesandunitcontrolwillonlyrespondtosignalattheW2terminal .Daytimeheatingandcoolingoperationislockedout .+24VACtoW2energizesthecompressorandreversingvalveforheatingoperation .NightsetbackoperationcanbeoverriddenfortwohoursbyenergizingtheOontheTB2terminaloftheunitcontrolfor3seconds .Daythermostatsetpointsthencontroltheheatingandcoolingoperation .TheMicroTechIIIunitcontrolleralsoaccommodatesshutdownoperationonreceiptofa“grounded”signaltothe“E”input,respectively,onTB3inputterminaloftheunitcontrol .
Table 8: MicroTech III unit controller LED & fault outputs
1 Compressor relay/compressor terminal is labeled COMP, switched line of the same electric input as any of the L1 terminals.
MicroTech® III Unit ControllerTheMicroTechIIIUnitControllerincludesbuilt-infeaturessuchasrandomstart,compressortimedelay,shutdown,condensateoverflowprotection,defrostcycle,brownout,andLED/faultoutputs .Table8showstheLEDandfaultoutputsequences .
Theunithasbeendesignedforoperationwithamicroelectronicwallthermostatselectedbythemanufacturer .Donotoperatetheunitwithanyothertypeofwallthermostat .
Eachunithasaprintedcircuitboardcontrolsystem .ThelowvoltageoutputfromthelowvoltageterminalstripisACvoltagetothewallthermostat .RisA/Cvoltageoutputtothewallstat .
The24voltlowvoltageterminalstripissetupsoR-Genergizesthefan,R-Y1energizesthecompressorforcoolingoperation,R-W1energizesthecompressorandreversingvalveforheatingoperation .Thereversingvalveisenergizedintheheatingmode .Thecircuitboardhasafaninterlockcircuittoenergizethefanwheneverthecompressorisonifthethermostatlogicfailstodoso .
TheoutputtothewallstatisACcurrent .Terminal(R)onthewallstatcanbeconnectedtoterminal(R)onthePCboardforACvoltage . R=ACcurrent RtoG=fanonly RtoY1=cooling RtoW1=heatTheMicroTechIIIunitcontrollerhasalockoutcircuittostopcompressoroperationifanyoneofitssafetyswitchesopens(highpressureswitchandlowpressureswitchonunitsizes024through070) .Ifthelowtemperatureswitchopens,theunitwillgointothecoolingmodefor60secondstodefrostanyslushinthewater-to-refrigerantheatexchanger .After60secondsthecompressorislockedout .Ifthecondensatesensordetectsafilleddrainpan,thecompressoroperationwillbesuspendedonlyinthecoolingmode .Theunitisresetbyopeningandclosingthedisconnectswitchonthemainpowersupplytotheunitintheeventtheunitcompressoroperationhasbeensuspendedduetolowtemperature(freezestat)switch,highpressureswitch,orlowpressureswitchonunitsizes019thru070 .Theunitdoesnothavetoberesetonacondensateoverflowdetection .
TheMicroTechIIIunitcontrollerfaultoutputsendsasignaltoanLEDonawallthermostat .Table8showsforwhichfunctionsthefaultoutputis“on”(sendingasignaltotheLED) .
Page 16 of 36 / IM 1049-1
Eachunitcontrollerorchestratesthefollowingunitoperations:
■ Enableheatingandcoolingtomaintainsetpointbasedonaroomsensor .
■ Enablefanandcompressoroperation.■ Monitorallequipmentprotectioncontrols.■ Monitordischargeairtemperature.■ Monitorleavingwatertemperature.■ Relaystatusofallvitalunitfunctions.■ Supportoptionalcontroloutputs.
Anamber,on-boardstatusLEDaidsindiagnosticsbyindicatingthewatersourceheatpumpoperatingmodeandalarmconditions .Iftherearenocurrentalarmcon-ditions,theLEDwillindicatetheunitoperatingmode .Ifthereareoneormorealarmconditionspresent,theLEDwillflashtoindicateanalarmcondition.
MicroTechIIIheatpumpswithaMicroTechIIIunitcontrollerareLonMarkcertifiedanddesignedtobelinkedwithacentralizedbuildingautomationsystemthroughaLonWorkscommunicationsnetworkforcentralizedschedulingandmanagementofmultipleheatpumps .Wall-mountedroomsensorsareavailabletocontroltheheatingandcoolingoperationofeachMicroTechIIIWaterSourceHeatPumpUnitController .Availableroomsensorsinclude:roomsensorwithLEDstatusandtenantoverridebutton,roomsensorwithLEDstatus,timed-overridebutton,roomsensorwithLEDstatus,timed-overridebutton,andsetpointadjust-ment,androomsensorwithLEDstatus,timed-overridebutton,setpointadjustment .
TheMicroTechIIIwatersourceheatpumpunitcon-trollerprovidescontrolofMcQuaywatersourceheatpumps .Thecontrollerenablesthemodeofoperation,monitorsthewaterandairtemperatures,andindicatesfaultconditions .Eachunitcontrollerisfactorypro-grammed,wired,andtestedforeffectiveoperationofyourMcQuaywatersourceheatpump .TheMicroTechIIIwatersourceheatpumpcontrollerusesLonWorkstechnology .Oneofthefollowingtwoversionsoftheapplicationsoftwareisloadedintothecontrolleratthefactory .
LonMark®3.4certifiedapplicationcodeisthecurrentstandardapplicationcodeforMicroTechIIIunits .
MicroTech III Controller With LonWorks® Communication ModuleThismanualcoverstheinstallationofaMcQuayHorizontalCeilingHungUnit-ModelCCH,CCWWaterSourceHeatPump .ForinstallationandoperationinformationonLonWorksCommunicationModuleandotherancillarycontrolcomponents,see:
• IM927-MicroTechIIIWaterSourceHeatPumpLonWorks CommunicationModule
• IM933-LonMakerIntegrationPlug-inTool:ForusewiththeMicroTechIIIUnitController
• IM955-MicroTechIIIWallSensorforusewithMicrotechIIIUnitController
Figure 15: LonWorks Communication Module
TheLonWorks communicationmodulewillplugintotheMicrotechIIIunitcontrollerattheCN_LON1Header(seefigure17onpage18).
EachMcQuaywatersourceheatpumpcanbeequippedwithaLonWorks Communicationmodule .Thecontrol-lerismicroprocessor-basedandisdesignedtocommu-nicateoveraLonWorkscommunicationsnetwork .Theunitcontrollerisfactoryprogrammedandtestedwithallthelogicrequiredtomonitorandcontroltheunit .Thewallthermostatsetstheunitmodeofoperation .Theunitcontrollermonitorswaterandairtemperatures,andcancommunicatefaultconditionstoaLonWorkscommunicationsnetwork .TheMicroTechIIIunitcontrollerwithcommunicationmoduleincludesaunit-mountedreturnair,dischargeairandleavingwatertemperaturesensor .Wallmountedtemperaturesensorsincludesetpointadjustmentandtenantoverride .Theuserhasthecapabilityofsubsti-tutingthewallsensorwithaduct-mountedreturnairsensor .
IM 1049-1 / Page 17 of 36
MicroTech III Controller with BACnet Communication ModuleForinstallationandoperationinformationonMicroTechIIIunitcontrollerandotherancillarycomponents,see:• IM928-MicroTechIIIBACnetCommunication
Module• OM931-MicroTechIIIUnitControllerforWater
SourceHeatPumpsOperationandMaintenanceManual
• IM955-MicroTechIIIWallSensorForusewithMicrotechIIIUnitController
McQuaywatersourceheatpumpsareavailablewithMcQuayBACnetMS/TPcommunicationmodulethatisdesignedtocommunicateoveraBACnetMS/TPcommunicationsnetworktoabuildingautomationsystem(BAS).Itcanbefactoryorfield-installed.
Theunitcontrollerisprogrammedandtestedwithallthelogicrequiredtomonitorandcontroltheunit .Anoptionalwallsensormaybeusedwiththecommunicationmoduletoprovidelimitedlocalcontrolofthewatersourceheatpump .Theunitcontrollermonitorswaterandairtemperaturesandpassesinformationtothecommunicationmodule .ThemodulecommunicateswiththeBAS,toprovidenetworkcontrolofthewatersourceheatpump .
ThemodulemakesoperationaldataandcommandsavailableonacommunicationsnetworkusingBACnetobjectsandproperties: Thenetworkcableisashieldedtwisted-paircable
Networkcommunicationsrunupto76 .8Kbps
DIPswitchesonthecontrollerenabletheMS/TPMACaddresstobesetintherange0-127
FourgreenstatusLEDsonthecommunicationmoduleindicatecommunicationactivityontheMS/TPcommunicationnetworkandwiththeunitcontroller
Figure 16: MicroTech III BACnet Water Source Heat Pump Snap-in Communication Module
MicroTechIIIUnitControllerwithBACnetMS/TP CommunicationModuleorchestratesthefollowingunitoperations:
Enableheatingandcoolingtomaintainsetpointbasedonaroomsensor
Enablefanandcompressoroperation Monitorsallequipmentprotectioncontrols Monitorsroomanddischargeairtemperatures Monitorsleavingwatertemperature Relaysstatusofallvitalunitfunctions
TheMicroTechIIIunitcontrollerwithcommunicationmoduleincludes:
Aunit-mountedreturnairsensor* Aunit-mounteddischargeairsensor* Aleavingwatertemperaturesensor*
* Dischargeairandreturnairsensorsmustbefield-installed per IM 956.
Thecommunicationmoduleprovidesaccesstosetpointsforoperationalcontrol
Availablewallsensorsinclude:
RoomsensorwithLEDstatusandtenantoverridebutton
RoomsensorwithLEDstatus,tenantoverridebut-ton,and±3°Fsetpointadjustment
RoomsensorwithLEDstatus,tenantoverride button,55°to90°Fsetpointadjustment
Page 18 of 36 / IM 1049-1
Figure 17: LonWorks® Communication Module Placement on MicroTech™ III Unit Controller
IM 1049-1 / Page 19 of 36
Changing PSC Fan Motor Speed Thefanmotorcanbechangedfromhightolowspeedorviceversabyinterchangingthewiresontheblackandredlabeledterminalsonthemotorterminalblock .
Table 9: Fan Motor Voltage and Terminal Slots
Unit Size 007 through 012 (115-60-1), (208/230-60-1) and (265-60-1)Tochangebetweenhighandlowspeed;interchangetheredandblackwires .
Figure 18: Sizes 009 through 012 (115/60-1, (208/230-60-1), (265-60-1)
Unit Size 015 through 036 (208/230-60-1) and (265-60-1)Fanmotorsonunitsizes019-036,inboth208/230-60-1and265-60-1voltages(Figure19)haveafour-positionterminalblock .Tochangebetweenhighandlowspeed,interchangetheredandblackwires .
CCH, CCW R410-A
Unit Size Volts and Number of Terminal Slots Factory
208V 460V 575V Fan Speed
007 n/a n/a n/a n/a 009 n/a n/a n/a Low 012 n/a n/a n/a High 015 4 – – Low
019 4 – – Low 024 4 4 – High 030 4 4 – High 036 4 6 – High 042 4 6 6 High
048 4 6 6 Low 060 4 6 6 High
Figure 19: Sizes 019 through 036 (208/230-60-1), (265-60-1)
Unit Size 030 and 036 (460-60-1)Fanmotorsonunitsizes030and036,460-60-1(Figure20)haveafour-positionterminalblock .Highandlowspeedscanbeinterchangedbyswitchingthewiresontheblackandredterminals .
Figure 20: Sizes 030 through 036 (460-60-1)
Unit Size 042 through 060Fanmotorsonunitsizes042-060(Figure21&22)haveasix-positionterminalblock .Motorsforthesesizesarefactorywiredforhighspeed .Forlowspeedoperation,movetheblackterminal(3)totheredterminal(6)andtheblackandblueterminals(3&4)receiveajumper .
Figure 21: Sizes 042-060 (460/575-60-1) High Speed
Figure 22: Sizes 042-060 (460/575-60-1) Low Speed
Sharp edges can cause personal injury. Avoid contact with them.
CAUTION
WARNINGHazardous Voltage!The installer must determine and follow all applicable codes and regulations. This equipment presents hazards of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow these instructions can result in property damage, severe personal injury or death.
Page 20 of 36 / IM 1049-1
Unit Size 042 through 060 (265-60-1), (208/230-1) & (208/230-3)Fanmotorsonunitsizes042-060involtages265-60-1,208/230-1and208/230-3(Figure23)allhaveafive-positionterminalblock .Inordertochangebetweenhighandlowspeed,interchangethewiresontheblackandredterminals .
Figure 23: Sizes 042-060 (265-60-1), (208/230-1) (208/230-3)
Unit Size 024 through 036 (208/230-3)Fanmotorsonunitsizes024-036involtages208/230-3(Figure24)allhaveafour-positionterminalblock .Inordertochangebetweenhighandlowspeed,interchangethewiresontheblackandredterminals .
Figure 24: Sizes 024-036 (208/230-3)
Notes: All motors have a wiring label that is keyed for proper wiring operation. Check unit wiring diagram (on electrical access panel) for proper unit operation. Not all labels are the same.
Units leaving the factory are wired for high or low fan speed (see table 9 on page 19 for fan speed settings).
Label is located on the back of the terminal block.
(Optional) ECM MotorTheECMmotorwillmaintaintheratedairflowasstaticpressureincreasesordecreaseswithintheunit’soperatingrange .Contactthefactoryat315-253-2771or800-432-1342ifanalternateairflowsettingisrequired.
Start-up
1 . Openallvalvestofullopenpositionandturnonpowertotheunit .
2 . Setthethermostatfor"FanOnly"operationbyselecting"Off"atthesystemswitchand"On"atthefanswitch .If"Auto"fanoperationisselected,thefanwillcyclewiththecompressor .
3 . Forthoseunitsthathavetwo-speedmotors,reconnectforlowspeedoperationifnecessary .
4 . Setthermostatto“Cool .”Ifthethermostatisanautomaticchangeovertype,simplysetthecoolingtemperaturetothelowesttemperature .Onmanualchangeovertypes,additionallyselect“Cool”atthesystemswitch .
Again,manyunitshavetimedelayshelpprotectthecompressor(s)againstshortcycling .
Afterafewminutesofoperation,checkthedischargegrillesforcoolairdelivery .Measurethetemperaturedifferencebetweenenteringandleavingwater.Itshouldbeapproximately1-1⁄2timesgreaterthantheheatingmodetemperaturedifference .Forexample,ifthecoolingtemperaturedifferenceis15°F(8°C),theheatingtemperaturedifferenceshouldbe10°F(5°C) .
Withoutautomaticflowcontrolvalves,targetacoolingtemperaturedifferenceof10°Fto14°F(5°Cto8°C) .Adjustthecombinationshutoff/balancingvalveinthereturnlinetoawaterflowratewhichwillresultinthe10˚Fto14°F(5°Cto8°C)difference .
5 . Setthermostatto“Heat .”Ifthethermostatistheautomaticchangeovertype,setsystemswitchtothe“Auto”positionanddepresstheheatsettingtothehighesttemperature .Someunitshavebuilt-intimedelayswhichpreventthecompressorfromimmediatelystarting .Withmostcontrolschemes,thefanwillstartimmediately .Afterafewminutesofcompressoroperation,checkforwarmairdeliveryatdischargegrille .Ifthisisa“coldbuilding”start-up,leaveunitrunninguntilreturnairtotheunitisatleast65°F(18°C) .
Units must be checked for water leaks upon initial water system start-up. Water leaks may be a result of mishan-dling or damage during shipping. Failure by the installing contractor to check for leaks upon start-up of the water system could result in property damage.
CAUTION
IM 1049-1 / Page 21 of 36
Typical Wiring DiagramFigure 25: MicroTech III Unit Controller with PSC Motor – 208/230-60-1 Unit Sizes 015-060
Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT), Discharge Air (DAT) and Return Air (RAT) Temperature sensorsareshippedorarefieldinstalledonunitsconfiguredwithacommunicationmodule.*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.
Legend Item Description C1 Capacitor-Compressor C2 Capacitor-Fan CC Compressor - Contactor CM Compressor - MotorCOS CondensateOverflowSensor DAT Discharge Air Temp Sensor EWT Entering Water Temp Sensor HP High Pressure SwitchISO-NO Isolation Valve - Normally OpenLED1 LED Annunciator / HarnessLP Low Pressure SwitchSLTS Suction Line Temp SensorLWT Leaving Water Temp SensorMIII MicroTech III Main BoardR1 Relay - Fan MotorRAT Return Air Temp SensorRV Reversing Valve SolenoidTB1 Power Terminal BlockX1 Primary 24VAC Transformer_____ Standard Unit Wiring_ _ _ _ Optional Wiring (by others)
Table B 208V RED 230V ORG
Notes:1. Main board jumpers: JP3 Geothermal
Transformer: Unused wire to be capped.
Drawing No. 668991002
Page 22 of 36 / IM 1049-1
Typical Wiring DiagramFigure 26: MicroTech III Unit Controller with PSC Motor – 208/230/460/575-60-3 Unit Sizes 024-060
Drawing No. 668991202
Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT), Discharge Air (DAT) and Return Air (RAT) Temperature sensorsareshippedorarefieldinstalledonunitsconfiguredwithacommunicationmodule.*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.
Legend Item Description C1 Capacitor-Compressor C2 Capacitor-Fan CC Compressor - Contactor CM Compressor - MotorCOS CondensateOverflowSensor DAT Discharge Air Temp Sensor EWT Entering Water Temp Sensor HP High Pressure Switch ISO-NO Isolation Valve - Normally OpenLED1 LED Annunciator / HarnessLP Low Pressure SwitchSLTS Suction Line Temp SensorLWT Leaving Water Temp SensorMIII MicroTech III Main BoardR1 Relay - Fan MotorRAT Return Air Temp SensorRV Reversing Valve SolenoidTB1 Power Terminal BlockX1 Primary 24VAC Transformer_____ Standard Unit Wiring_ _ _ _ Optional Wiring (by others)
Table B 208V RED 230V ORG 460V BLK/RED 575V BLUE
Notes:1. Main board jumpers: JP3 Geothermal
Transformer: Unused wire to be capped.
IM 1049-1 / Page 23 of 36
Typical Wiring DiagramFigure 27: MicroTech III Unit Controller with ECM Motor – 208/230-60-3 Unit Sizes 024-070
Drawing No. 910104890
Legend Item Description CC Compressor - Contactor CM Compressor - MotorCOS CondensateOverflowSensor HP High Pressure SwitchISO-NC Isolation Valve - Normally Closed ISO-NO Isolation Valve - Normally OpenLED1 LED Annunciator / HarnessLP Low Pressure SwitchSLTS Suction Line Temp SensorLWT Leaving Water Temp SensorMIII MicroTech III Main BoardRAT Return Air Temp SensorRV Reversing Valve SolenoidX1 Transformer_____ Standard Unit Wiring_ _ _ _ Optional Wiring (by others)
Table B 208V RED 230V ORG
Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT) and Discharge Air (DAT) Temperature sensors are shippedorarefieldinstalledonunitsconfiguredwithacommunicationmodule.*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.
Notes:1. Main board jumpers: JP3 Geothermal
Transformer: Unused wire to be capped.
Page 24 of 36 / IM 1049-1
Typical Wiring DiagramFigure 28: MicroTech III Unit Controller with ECM Motor – 208/230-60-1 Unit Sizes 015-070
Drawing No. 919194871
Table B 208V RED 230V ORG
Legend Item Description C1 Capacitor-Compressor CC Compressor - Contactor CM Compressor - MotorCOS CondensateOverflowSensor DAT Discharge Air Temp Sensor EWT Entering Water Temp Sensor HP High Pressure SwitchISO-NC Isolation Valve - Normally Closed ISO-NO Isolation Valve - Normally OpenLED1 LED Annunciator / HarnessLP Low Pressure SwitchSLTS Suction Line Temp SensorLWT Leaving Water Temp SensorMIII MicroTech III Main BoardR1 Relay - Fan MotorRAT Return Air Temp SensorRV Reversing Valve SolenoidX1 Transformer_____ Standard Unit Wiring_ _ _ _ Optional Wiring (by others)
Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT) and Discharge Air (DAT) Temperature sensors are shippedorarefieldinstalledonunitsconfiguredwithacommunicationmodule.*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.
Notes:1. Main board jumpers: JP3 Geothermal
Transformer: Unused wire to be capped.
IM 1049-1 / Page 25 of 36
Typical Wiring DiagramFigure 29: MicroTech III Unit Controller with ECM Motor and Optional Communication Module – 460-60-3 Unit Sizes 024-070
Drawing No. 910102101
Legend Item Description CC Compressor - Contactor CM Compressor - MotorCOS CondensateOverflowSensor HP High Pressure SwitchISO-NC Isolation Valve - Normally Closed ISO-NO Isolation Valve - Normally OpenLED1 LED Annunciator / HarnessLP Low Pressure SwitchSLTS Suction Line Temp SensorLWT Leaving Water Temp SensorMIII MicroTech III Main BoardRAT Return Air Temp SensorRV Reversing Valve SolenoidX1 Transformer_____ Standard Unit Wiring_ _ _ _ Optional Wiring (by others)
Table B 460V/N BLK/RED
Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT) and Discharge Air (DAT) Temperature sensors are shippedorarefieldinstalledonunitsconfiguredwithacommunicationmodule.*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.
Notes:1. Main board jumpers: JP3 Geothermal
Transformer: Unused wire to be capped.
3-phase service with a neutral is required for ECM fan motor and 460 VAC operation.
Page 26 of 36 / IM 1049-1
4 . Installtwostrandshieldedwirebetweenremotesensorandthermostat .Shieldedwiremustbeused .
Donotrunremotesensorwireinconduitwithotherwires .• Wire1shouldrunbetweentheS1terminalonthe
thermostatandtheS1terminalontheremotesensor• Wire2shouldrunbetweentheS2terminalonthe
thermostatandtheS2terminalontheremotesensor• ConnecttheshieldingofthewiretotheS2terminal
onthethermostat5 . Disablethemainsensor(R12)onthethermostatby
cuttingitfromthecircuitboard .
Figure 32: Optional Remote Sensor Wiring
MicroTech III Wall-Mounted Room Temperature Sensors (Kit P/N 669529101, 669529201, 669529001)Figure 33: MicroTech III Wall-Mounted Room Temperature Sensors (669529201 Not Shown)
GeneralMicrotechIIIWall-MountedRoomTemperatureSensorsprovideelectronicsensingofroomtemperaturesatwalllocations .Allsensormodelsfeatureathermistor(10kΩ)andagreenLEDforunitstatus.Tenantoverride,setpointadjustmentpotentiometer,thermometer,andacommunicationsportareoptionalfeaturesavailableinanycombination
ThismanualprovidesgeneralinformationfortheMicrotechIIIWall-MountedRoomTemperatureSensors .ForinstallationinstructionsrefertoIM955
Thermostat ConnectionsFigure 30: 7-Day Programmable Electronic Thermostat(P/N 668375301)
Notes: Includes Thermostat and Wall Plate.
Refer to the installation, operation & application guide (LIA265) for thermostat 668375301.
Figure 31: Non-Programmable Electronic Thermostat(P/N 668375401)
Note: Includes Thermostat and Wall Plate.
Refer to the installation, operation & application guide (LIA266) for thermostat 668375401.
*When remote reset of a lockout condition is required at the wall thermostat, it will be necessary to utilize a conductor between terminal "O" on the wall thermostat to terminal "O" on the MicroTech III unit controller (non-programmable stat only).
Optional Remote Sensor (P/N 66720401)1 . Removecoverfromremotesensorhousing .2 . Selectanappropriatelocationformountingthe
remotesensor .3 . Mountremotesensorunitusinghardwareprovided .
MicroTech III Unit Control Board Low Voltage Terminal Strip (Circuit 1)
W1
Y1
W2
Y2
G
Thermostat Terminals
-C
TB2
24VAC
Alarm Output
Heat 2
Heat 1
Cool 2
Cool 1
Fan
Tenant Override
24VAC Common C
O
G
Y1
Y2
W1
W2
A
R
+R
MicroTech III Unit Control Board Low Voltage Terminal Strip (Circuit 1)
W1
Y1
W2
Y2
G
Thermostat Terminals
-C
TB2
24VAC
Alarm Output
Heat 2
Heat 1
Cool 2
Cool 1
Fan
Tenant Override
24VAC Common C
O
G
Y1
Y2
W1
W2
A
R
+R
O
*Override (Optional)
S1 S2
S1 S2
Cut R12 fromcircuit board
Remote Sensor
Thermostat
Wire 1
Wire 2
Sensor 669529101Sensor 669529201 Not Shown
Sensor 669529001
IM 1049-1 / Page 27 of 36
Figure 36: Temperature Sensor Wiring to MicroTech III Unit Controller (669529001)
Additional Accessories – GeneralMotorized Isolation Valve & RelayThemotorizedvalvekitisavailableasafactory-installedandwiredoptionormaybeorderedasafield-installedaccessory .
WiredasshowninFigure37,themotorizedvalvewillopenonacallforcompressoroperation .Valvesforunitsizes007to019are1/2"whileunitsizes024to060are3/4" .
UsingaNormallyClosed(N/C),poweropenvalve,wireasillustratedinfigure37.
Figure 37: Normally Closed, Power Open Motorized Valve
Note: A special harness is provided for use with MicroTech III controlled units. Use of a motorized valve by others will not include the necessary wiring harness.
Figure 34: MicroTech III Wall Sensor Details .
SpecificationsThermistorresistance(10kΩ)(Conformstoadvancethermalproductscurve2)
AmbientTemperatureLimits:
ShippingandStorage:40°Fto160°F(–40°Cto71°C)
Operating:40°Fto140°F(4°Cto60°C)
Humidity:5to95%RH,non-condensing
Locations:NEMAType1,Indooronly
Connections:ColorCodedLeads
Wiring Sensors to the MicroTech III Unit ControllerFigure 35: Temperature Sensor Wiring to MicroTech III Unit Controller (Kit Part No.s 669529101, 669529201)
Fan ControlSlide Switch
Mode ControlSlide Switch
Status LED(Green)
0 to 10 K ohmPotentiometer
Tenant OverrideMomentary Push Button Switch
4.59"
Temperature Sensor Terminals
MicroTech III Unit Controller TB1 Terminals
Actuator &Valve Assembly Anti-short Bushing
Connector Conduit
Pin(s), female connect to terminal H8
Connector
Anti-short Bushing
MicroTech III Unit Controller TB1 Terminals
Temperature Sensor Terminals
Page 28 of 36 / IM 1049-1
Figure 39: Wiring Multiple Unit Control Board (MUCP)
Notes:Dotted lines represent low voltage (Class II) wiring; a color-coded thermostat cable is recommended.
MUCP may be mounted horizontally or vertically on heat pump cabinet or any convenient surface.
Do not use if using night setback.
Thermostat must be A.C. voltage.
Pump Restart Relay Kit P/N 061419001
TheMicroTechIIIunitcontrollerhasaninternalPumpRestartRelayconnectedtoH8,Pin2fortheNormallyOpen(N/O)terminaloftheinternalrelay .
ConnecttoH8,Pin1fortheNormallyClosed(N/C)terminaloftheinternalrelay .
Theoutputoftheinternalpumprestartrelayis24-voltsACandtheoutputisnotavailablewhentheH8connectionisusedtocontrolamotorizedvalve .
Multiple Unit Control (up to 3 units) (P/N 056794201) Themultipleunitcontrolboardisanaccessoryusedwhenupto3-unitsarecontrolledfromasinglethermostat .Typicallythecontrolpanelandboardiscentrallymountedbetweentheunitsandthermostat .Amaximumof2boardsmaybeusedtogetherifupto6-unitsmustbeconnectedandcontrolledfromasinglethermostat .FordetailedinstallationinstructionsrefertoIM952 .ThisversionofthecontrolusesVACrelaysandshouldnotbeusedincombinationwithanyotheraccessoriesorequipmentthatrequireVDCconnections .
Figure 38: Multiple Unit Control Panel and Board
ThemultipleunitcontrolboardprovidesthecomponentsnecessarytoprotecttheMicroTechIIIunitcontrollerfromelectricaldamagethatmayoccurwhenusingstandardoff-the-shelfrelays .Donotusetheunoccupied(U-terminal)featurewiththemultipleunitcontrolboard .
Multiple Unit Control PanelCircuit Board
MicroTech III Unit Control Board Low Voltage Terminal Strip
CGY1Y2W1W2AR O
Thermostat TerminalsW1Y1W2Y2G -C+R
RY
GW
RY
GW
RY
GW
RY
GW
C
K3
K2
K1
TB3
TB4
TB2
TB1
CGY1Y2W1W2AR O
CGY1Y2W1W2AR O
TB2 - Unit #1
TB2 - Unit #2
TB2 - Unit #3
IM 1049-1 / Page 29 of 36
Troubleshooting The in and outs of R-410AR-410Aisanon-ozonedepletingblendoftworefrigerants-HFC-125andHFC-32inafiftypercentmixture .R-410AexhibitshigheroperatingpressureandrefrigerationcapacitythanR-22 .R-410AisintendedforuseinnewairconditioningapplicationsthathavetraditionallybeenusedHCFC-22(R-22) .DuetohighercapacityandpressureofR-410A,itmustnotbeusedinexistingR-22systems .
AlthoughR-410Aisnon-flammableatambienttemperatureandatmosphericpressure,itcanbecomecombustibleunderpressurewhenmixedwithair .
Note: R-410A should not be mixed with air under pressure for leak testing. Pressure mixtures of dry nitrogen and R-410A can be used for leak testing.
LubricationR-410Ashouldbeusedonlywithpolyester(POE)oil .TheHFCrefrigerantcomponentsinR-410Awillnotbecompatiblewithmineraloiloralkylbenzenelubricants .R-410AsystemswillbechargedwiththeOEMrecommendedlubricant,readyforusewithR-410A .
ChargingDuetothezeotropicnatureofR-410A,itshouldbechargedasaliquid .Insituationswherevaporisnormallychargedintoasystem,avalveshouldbeinstalledinthecharginglinetoflashtheliquidtovaporwhilecharging .
MakecertainthattherecycleorrecoveryequipmentusedisdesignedforR-410A .ThepressureofR-410Arefrigerantisapproximately60percentgreaterthanthatofR-22 .Pressuregaugesrequirearangeupto800PSIGhighsideand250PSIGlowside .Recoverycylindersrequirea400PSIGrating–donotputR-410Aina300PSIGratedcylinder .
Note: Because a water source heat pump operates under a wide range of water and air temperatures, the values printed below are to be taken as suggested pressure and temperatures.) All McQuay water source heat pumps are designed for commercial use. The units are designed for the cooling mode of operation and fail safe to cooling. The reversing valve is energized for the heating mode of operation.
Superheat Head Pressure Water Delta T8 to 14 degrees 335-355 PSIG 10° to 14°
All information above is based on ISO standard 13256-1 and tested at these conditions.
General Maintenance1 . Normalmaintenanceonallunitsisgenerally
limitedtofilterchanges.Unitsareprovidedwithpermanentlylubricatedmotorsandrequirenooilingeventhoughoilcapsmaybeprovided .
2 . Filterchangesarerequiredatregularintervals .Thetimeperiodbetweenchangeswilldependupontheprojectrequirements .Someapplicationssuchasmotelsproducealotoflintfromcarpetingandlinenchanges,andwillrequiremorefrequentfilterchanges.Checkfiltersat60-dayintervalsforthefirstyearuntilexperienceisacquired.Iflightcannotbeseenthroughthefilterwhenhelduptosunlightorabrightlight,itshouldbechanged .Amorecriticalstandardmaybedesirable .
3 . Thecondensatedrainpanshouldbecheckedannuallyandcleanedandflushedasrequired.
4 . Recordperformancemeasurementsofvolts,amps,andwatertemperaturedifferences(bothheatingandcooling) .Acomparisonofloggeddatawithstart-upandotherannualdataisusefulasanindicatorofgeneralequipmentcondition .
5 . Periodiclockoutsalmostalwaysarecausedbyairorwaterproblems .Thelockout(shutdown)oftheunitisanormalprotectiveresult .Checkfordirtinthewatersystem,waterflowrates,watertemperatures,airflowrates(maybeadirtyfilter),andairtemperatures .Ifthelockoutoccursinthemorningfollowingareturnfromnightsetback,enteringairbelowmachinelimitsmaybethecause .
Recycle/recovery equipment must be designated for R-410A. R-410A pressure is greater than R-22. Improper equipment can cause severe injury or death.
WARNING
Page 30 of 36 / IM 1049-1
Table 10: Troubleshooting Refrigeration Circuit
Charge Undercharge System Low Low Low High Low Low Low Low Pressure (Possible Leak)
Overcharge System High High High Normal High Normal High Pressure
Low Air Flow Heating High High High Low High Low High Pressure
Low Air Flow Cooling Low Low Low High High Low Low Temp
Low Water Flow Heating Low Low High Low High Low Temp
Low Water Flow Cooling High High High High Low Low High High Pressure
High Air Flow Heating Low Low Low Low High Low Low Low TempHigh Air Flow Cooling Low High Normal High Low Low Normal High Pressure
High Water Flow Heating Normal Low Normal High Normal Normal Low High PressureHigh Water Flow Cooling Low Low Low Low High Normal Low Low Temp
TXV Restricted High Low High High Low Low
LowNormal
NormalLow
HighNormal
LowNormal
LowNormal
Normal Low
Air Water Safety Head Suction Compressor Super Temp (loops) Temp Lock
Symptom Pressure Pressure Amp Draw Heat
Subcooling Differential Differential Out
IM 1049-1 / Page 31 of 36Page 31 / IM 742
Figure 40: Cooling Mode – (Single Circuit Only Shown)Return Air
Reversing Valve
Conditioned Air – (Cooling)
Thermal Expansion Valve
Co-Axial Heat Exchanger
Blower
Coil – Air to Refrigerant Heat Exchanger
Water In
Water Out
Sensing Bulb and Capillary Tube
Compressor
Figure 41: Heating Mode – (Single Circuit Only Shown)Return Air
Thermal Expansion Valve
Co-Axial Heat Exchanger
Reversing Valve
Conditioned Air – (Heating)
Blower
Water In
Water Out
Sensing Bulb and Capillary Tube
Compressor
Coil – Air to Refrigerant Heat Exchanger
Cooling Refrigeration CycleWhen the wall thermostat is calling for COOLING, the reversing valve directs the flow of the refrigerant, a hot gas, leaving the com-pressor to the water-to-refrigerant heat exchanger. Here the heat is removed by the water and the hot gas condenses to become a liquid. The liquid then flows through a thermal expansion metering system to the air-to-refrigerant heat exchanger coil. The liquid then evaporates becoming a gas, at the same time absorbing heat and cooling the air passing over the surfaces of the coil. The refrigerant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle.
Heating Refrigeration CycleWhen the wall thermostat is calling for HEATING, the reversing valve directs the flow of the refrigerant, a hot gas, leaving the compressor to the air-to-refrigerant heat exchanger coil. Here the heat is removed by the air passing over the surfaces of the coil and the hot gas condenses to become a liquid. The liquid then flows through a capillary thermal expansion metering system to the water-to-refrigerant heat exchanger. The liquid then evaporates becoming a gas, at the same time absorbing heat and cooling the water. The refrigerant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle.
Typical Refrigeration Cycles
Page 32 of 36 / IM 1049-1
Unit
Low voltage, check power supply voltage
Fuse may be blown, circuit breaker is open
Wire may be loose or broken. Replace or tighten wires
Unit control, check thermostat for correct wiring or faulty thermostat
Check wiring - loose or broken and check for faulty connection
Check relays and contacts, also capacitor and wiring
Check high pressure switch, low pressure switch and low temperature switch to see if unit is cycling on the safety
Check to see if the reversing valve is not hung up and is operating correctly
Check condensate overflow switch in cool mode of operation
Compressor attempts to start but does not
Check compressor wiring for defective wiring or loose connection
Check for faulty compressor capacitor
Insufficient cooling or heating
Check for lock rotor amp draw
Check for defective compressor internal windings with ohm meter
Check for proper air flow - filter could be dirty
Check for low refrigerant charge
Check amp draw on blower assembly
Fan operates, compressor does not
Compressor runs in short cycle
Neither fan, nor compressor runs and all LED lights are off
Check capacitor
Check wiring - loose or broken and check for bad connection
High or Low pressure lockout A. Cool mode, check water flowB. Heating mode, check air flowC. Check reversing valve for
proper valve position
Check compressor overload - make sure it is closed
Check compressor to ground, or for internal short to ground
Compressor winding may be open. Check continuity with ohm meter
Check thermostat for improper location
Check blower assembly fordirt or faulty fan motor capacity
Check thermostat forproper location
Check for proper water flowand delta T (°F)
Troubleshooting the Water Source Heat Pump Unit
Figure 42: Troubleshooting Guide - Unit Operation
IM 1049-1 / Page 33 of 36
Troubleshooting the MicroTech III Unit Controller
General Use and InformationTheMicrotechIIIunitcontrollerisprovidedwithtwodriveterminals,R(24VAC)andC(0VAC)thatcanbeusedbytheendusertodrivethethermostatinputs(G,Y1,Y2,W1,andW2)andcontrolinputs(U,E,andO) .Anycombinationofasingleboarddriveterminal(RorC)maybeusedtooperatetheMicroTechIIIunitcontroller’scontrolorthermostatinputs .However,onlyonedriveterminal(RorC)canbeconnectedtoanyindividualinputterminalordamagemayresult .Somecontrolinputsarenotaccessibletotheenduser(forexample,HP,LP,SLTS,andCOF) .
TypicallytheMicrotechIIIunitcontroller’sR(24VAC)terminalisusedtodrivetheboard’sthermostatinputsandcontrolinputsbyconnectingittotheRterminalofanindustrystandardthermostat .ThecontroloutputsofthestandardthermostatarethenconnectedtotheMicrotechIIIunitcontrollerthermostatinputsandcontrolinputsasneeded .Anyremainingboardinput(s)maybeoperatedbyadditionalthermostatoutputsorremoterelays(drycontactsonly) .
AllMicrotechIIIunitcontrollerinputsmustbeoperatedbydrycontactspoweredbythecontrolboard’spowerterminals .Nosolidstatedevices(Triacs)maybeusedtooperatetheMicrotechIIIunitcontrollerinputs .NooutsidepowersourcemaybeusedtooperatetheMicrotechIIIunitcontrollerinputs .
To avoid electrical shock, personal injury or death, be sure that field wiring complies with local and national fire, safety, and electrical codes, and voltage to the system is within the limits shown in the job-specific drawings and unit electrical data plate(s).
Power supply to unit must be disconnected when making field connections. To avoid electrical shock, per-sonal injury or death, be sure to rigorously adhere to field wiring procedures regarding proper lockout and tagout of components.
DANGER
Figure 43: MicroTech III Unit Controller LED Status and Faults Troubleshooting Reference
Flash Yellow LED
Read Outputs
Check Timers
Brownout
HighPressure
R - W 1
R -Y 1
Flash Green LED
Stop Compressor
No
Yes
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
LowPressure
Low SuctTemp Sensor
Low SuctTemp
Room TempSensor Failure
CondensateOverflow
Stop Compressor
Flash Red LED
Stop Compressor
Flash Yellow LEDFlash Green LED
Solid Red LED
Stop Compressor
Heating Mode
Run in Cooling Mode for 1 Min.
No
Yes
Cooling Mode
Turn on Yellow LED
Stop Compressor
ReversingValve On
Time Delay
StartCompressor
30 SecondTime Delay
Request forWater Flow
©2010 McQuay International • www.mcquay.com • 800.432.1342 IM 1049-1 Page 36 of 36 (Rev 3-10)
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
Products Manufactured in an ISO Certified Facility.
McQuay Training and Development
Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority. For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or call 540-248-9646 and ask for the Training Department.