Inteational Conference on Communication and Signal Processing, April 3-5, 2014, India MCS-51 Microcontroller Based Industrial Automation and Control System using CAN protocol A.Devi, G. Gnanavel, G. Antoni gracy Abstract-When we consider an industry of large area the monitoring, controlling of each section involved in the industry is a big task. It involves a large amount of man power and time consumption. To overcome these above factors we developed this technology to make single person for monitoring and controlling the entire network. This can be achieved based on multiprocessor communication by the combination of a wired technology i.e. controller area network (CAN) bus network, and the MCS-51 microcontroller which are the main objectives of our paper. The MCS-51 and the CAN protocol are cost effective, and the CAN protocol is used in various applications like industries, automobiles and home. The software part is done in Keil IDE and Jet Flasher. Hardware is implemented and soſtware porting is done. Index Terms- CAN, GSM, Teerature contl, Gas leakage control, MCS-5J microcontroer I. INTRODUCTION Now a day automation field gets a wide growth in the world wide. So every process control industries, different parameters need to be monitored and controlled simultaneously. Hence there is a need for implementation of separate circuits to measure these different parameters. But it is very difficult to implement such circuits of high complexity. Hence a need arises to reduce this complexity. This led to the use of multichannel process monitoring in a single window. So in order to achieve this, CAN (Controller Area Network) protocol can be chosen. CAN is a vehicle bus standard designed to allow microcontrollers and devices to communicate with each other within a vehicle without a host computer. A. Devi is pursuing M.E. Embedded System Technologies, Department of EEE, VRS College of Engineering and Technology, Villupuram, India (email- [email protected]) G. Gnanavel is working as Assistant professor, Department of EEE, VRS College of Engineering and Technology, Villupuram, India (email- gnanaveI[email protected]) G. Antoni gracy is pursuing M.E. Embedded System Technologies, Department of EEE, VRS College of Engineering and Technology, Villupuram, India (email-antonigracy3[email protected]) 978-1-4799-3358-7114/$31.00 ©20l4 IEEE 061 CAN bus is a message-based protocol, designed specifically for automotive applications. But now also used in other areas such as industrial automation and medical equipment. CAN bus was originally invented in 1983 by Robert Bosch GmbH. Previously, sensor networks consist of small nwnber of sensor nodes that were wired to a central processing station. However, now a days, the focus is more on wireless, distributed, sensing nodes. A typical smart system is made up of both digital and analog components, which allow the sensor data to be captured, transformed, analyzed, and transmitted to other modules in the system. But by applying the CAN protocol to a smart network is a natural progression om existing networks. It will prove itself efficient and economic media for communication. The CAN bus provides an ideal platform for interconnecting modules and allows each module to communicate with any other module. A networked system which requires fast and robust communication and where data should maintain high integrity, CAN can be used. The CAN protocol is robust and uses sophisticated error checking and handling, which allows errors and failures to occur without shutting the entire system down which is usel in the motor control node. The objective of this paper is to design a low cost industrial automation and control system based on multiprocessor communication using CAN protocol. The rest of the paper is organized as follows: working principle of proposed system design is given in section II, detailed view of hardware components is given in section III, monitoring and controlling system design is given in section IV, experimental and simulation results are given in section V, conclusion and ture enhancement are discussed in sections VI and VII. II. PROPOSED SYSTEM DESIGN The block diagram of proposed system is shown in Fig.l. Three slave modules and one master module along with one special slave are present. IEEE Advanng Technology for Humani

Upload: phungnhan

Post on 04-Apr-2018

233 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: MCS-51 Microcontroller Based Industrial Automation and ... · MCS-51 Microcontroller Based Industrial Automation and Control System using ... automobiles and home. ... The microcontroller

International Conference on Communication and Signal Processing, April 3-5, 2014, India

MCS-51 Microcontroller Based Industrial Automation and Control System using

CAN protocol

A.Devi, G. Gnanavel, G. Antoni gracy

Abstract-When we consider an industry of large area the

monitoring, controlling of each section involved in the industry is

a big task. It involves a large amount of man power and time

consumption. To overcome these above factors we developed this

technology to make single person for monitoring and controlling

the entire network. This can be achieved based on multiprocessor

communication by the combination of a wired technology i.e.

controller area network (CAN) bus network, and the MCS-51

microcontroller which are the main objectives of our paper. The

MCS-51 and the CAN protocol are cost effective, and the CAN

protocol is used in various applications like industries,

automobiles and home. The software part is done in Keil IDE

and Jet Flasher. Hardware is implemented and software porting

is done.

Index Terms- CAN, GSM, Temperature control, Gas leakage

control, MCS-5J microcontroller

I. INTRODUCTION

Now a day automation field gets a wide growth in the world wide. So every process control industries, different parameters need to be monitored and controlled simultaneously. Hence there is a need for implementation of separate circuits to measure these different parameters. But it is very difficult to implement such circuits of high complexity. Hence a need arises to reduce this complexity. This led to the use of multichannel process monitoring in a single window. So in order to achieve this, CAN (Controller Area Network) protocol can be chosen. CAN is a vehicle bus standard designed to allow microcontrollers and devices to communicate with each other within a vehicle without a host computer.

A. Devi is pursuing M.E. Embedded System Technologies, Department of EEE, VRS College of Engineering and Technology, Villupuram, India (email­[email protected])

G. Gnanavel is working as Assistant professor, Department of EEE, VRS College of Engineering and Technology, Villupuram, India (email­[email protected])

G. Antoni gracy is pursuing M.E. Embedded System Technologies, Department of EEE, VRS College of Engineering and Technology, Villupuram, India ([email protected])

978-1-4799-3358-7114/$31.00 ©20l4 IEEE

061

CAN bus is a message-based protocol, designed specifically for automotive applications. But now also used in other areas such as industrial automation and medical equipment. CAN bus was originally invented in 1983 by Robert Bosch GmbH. Previously, sensor networks consist of small nwnber of sensor nodes that were wired to a central processing station. However, now a days, the focus is more on wireless, distributed, sensing nodes. A typical smart system is made up of both digital and analog components, which allow the sensor data to be captured, transformed, analyzed, and transmitted to other modules in the system. But by applying the CAN protocol to a smart network is a natural progression from existing networks. It will prove itself efficient and economic media for communication.

The CAN bus provides an ideal platform for interconnecting modules and allows each module to communicate with any other module. A networked system which requires fast and robust communication and where data should maintain high integrity, CAN can be used. The CAN protocol is robust and uses sophisticated error checking and handling, which allows errors and failures to occur without shutting the entire system down which is useful in the motor control node.

The objective of this paper is to design a low cost industrial automation and control system based on multiprocessor communication using CAN protocol.

The rest of the paper is organized as follows: working principle of proposed system design is given in section II, detailed view of hardware components is given in section III, monitoring and controlling system design is given in section IV, experimental and simulation results are given in section V, conclusion and future enhancement are discussed in sections VI and VII.

II. PROPOSED SYSTEM DESIGN

The block diagram of proposed system is shown in Fig.l. Three slave modules and one master module along with one special slave are present.

+-IEEE Advancing Technology

for Humanity

Page 2: MCS-51 Microcontroller Based Industrial Automation and ... · MCS-51 Microcontroller Based Industrial Automation and Control System using ... automobiles and home. ... The microcontroller

FA.I.� (I emp control)

DC motor (Gas/fire control)

MCS-51

Special slave

Buzzer

MCS-51 Slave 2

CAN-H

CA.I.�-L

Fig. 1 Block diagram of proposed system using CAN protocol

Always master only initiates the communication. Whenever the master asks for the temperature, the slave 1 measures temperature level value of the boiler and senses the those values to the master module via CAN protocol after converting values into digital values via AID converter. Similarly the slave 2 is used to measure the smoke/gas level of the boiler and senses those values to the master module after converting those valves into digital values. The master module displays both temperature and gas/smoke values on the LCD.

If the temperature level of the boiler is higher than a threshold value, the cooling fan is automatically turned ON and the relay is made to tum off the boiler, and simultaneously the message will be sent to a higher authority or supervisor regarding the abnormal situation via GSM (global system for mobile communication). If the temperature value is lower than the threshold value, the relay is turned to ON in order to heat the boiler. Similarly if smoke/gas level of the boiler is higher than the threshold value, the buzzer is turned ON to indicate the abnormal condition and DC motors connected to window opening mechanism are rotated for fIre and gas leakage control.

III. HARDWARE DESIGN

Totally fIve MCS-Sl are present among which slave 1 and 2 are parameter processing modules, slave 3 is relay module and slave 4 is a special module for sending message to higher authority person or supervisor. These parameter processing

062

modules, relay modules and special module are connected to the master module which controlling all the modules.

A. MCS 51 Microcontroller module

In this system we use low-power, high-performance MCS-Sl microcontroller with 8KB of ISP flash memory. The MCS-Sl is an 8 bit microcontroller and uses nonvolatile memory technology. The 80S1 is designed as a strict Harvard architecture that has the advantage of making such systems immune to most forms of mal ware. On-chip flash allows the program memory to be reprogrammed in-system or by a conventional nonvolatile memory programmer.

The signals from the sensors are given to the microcontroller. The microcontroller also checks the output of the sensor and compares with set values and gives corresponding output to the master via CAN protocol.

Table 1 Features of MCS-51

FEATURE MCS-Sl

RAM (bytes) 128

ROM 4K

Timers 2

Serial port 1

110 ports 40

Interrupt sources 6

Page 3: MCS-51 Microcontroller Based Industrial Automation and ... · MCS-51 Microcontroller Based Industrial Automation and Control System using ... automobiles and home. ... The microcontroller

B. Temperature sensor LM-35

The LM35 is an integrated circuit sensor that can be used to measure temperature with an electrical output proportional to the temperature (in QC). The sensor circuitry is sealed and not subject to oxidation. The LM35 may not require that the output voltage be amplified. It has an output voltage that is proportional to the Celsius temperature. The important characteristic of the LM35 is that it draws only 60 micro amps from its supply and possesses a low self-heating capability.

TIT vcj/' ! �Gnd

Vout

Fig. 2 LM35

C. LPG Gas sensor-MQ-6

Gas sensor used here is MQ-6 which has high sensitivity to Propane, Butane and LPG, and also response to Natural gas. Sensitive material of MQ-6 gas sensor is Sn02, which with lower conductivity in clean air. If V+ >V- , then the output voltage is high and the LED connected to the output is ON. If V+ < V- , then the output voltage is low and LED is OFF. Gas sensor is shown in Fig.3.

Fig.4 Gas sensor

D. LM7805

The operating voltage range of MCS 51 is 5V. So LM7805 which is a +5.0V lA voltage regulator, is used. It is a linear voltage regulator that produces a relatively constant output voltage of +5V DC. The LM7805 is shown in Fig.4.

063

230 V AC IN

E. Cooling fan Fig.4 LM7805 circuit

Ie 1 7805

2 C2 C3

3

0.01uF 0.01 uF Cer Cer

If the received sensor (temperature or smoke/gas) data is higher than the predefined limit, the cooling fan will start rotating continuously. Fan speeds may be controlled manually (a simple potentiometer control, for example), thermally, or by the computer hardware or by software. It is also possible to run many 12V fans from the 5 V supply, at the expense of airflow, but with reduced noise levels.

F. Buzzer

If the DC motors start rotate continuously, the buzzer will turn on to indicate the abnormal condition. As the concentration of gas decreases the sensor output decreases and when it becomes less than the limit the motors will stop automatically.

G. Liquid crystal display

Liquid Crystal Displays (LCDs) are used for displaying current temperature, smoke and gas level of the boiler. A simple 8-bit 16x4 LCD is used to interface with the MCS-51. This means there are 16 characters per line by 4 lines. There are three control signals Register select, Enable and Read/Write. There are two important registers in LCD. Command Code register and Data register. If an 8-bit data bus is used, the LCD will require a total of 11 data lines (3 control lines plus the 8 lines for the data bus).

When RS is low (0), the data is to be treated as a command or a special instructions (such as clear screen, position cursor, etc). When RS is high (1), the data being sent is text data which should be displayed on the screen. RlW input allows the user to write information to LCD or read information from it.

When R W line is low (0), the information on the data bus is being written to the LCD. When RlW is high (1), the program is registers effectively querying (or reading) the LCD. The enable Pin is used by the LCD to latch information at its data pins. When data is supplied to data pins, a high to low pulse must be applied to this pin in order for the LCD to latch the data present in the data pins. We have to prepare an LCD properly before the character we need, has to be displayed. For this a number of commands have to be provided to the LCD.

Page 4: MCS-51 Microcontroller Based Industrial Automation and ... · MCS-51 Microcontroller Based Industrial Automation and Control System using ... automobiles and home. ... The microcontroller

Two ports (PORT 0 and PORT 2) of the MCS-Sl are taken. PORT 2 is used for providing control signals and PORT 0 IS

used for providing data signals.

IV. DESIGN OF MONITORING AND CONTROLLING SYSTEM

A. At the master side

The CAN 2.0B is a network protocol that was specially developed for connecting the sensors and actuators. CAN 2.0B supports data rates from Skbps to 1 Mbps, which allows the CAN network to be used to share status information and real time control. It can transfer up to 8 data bytes within a single message. Values are transferred to microcontrollers from ADC via CAN Protocol at an interval of 10 seconds and is displayed in the LCD. The flowchart for CAN based monitoring in master side is shown in Fig. S.

:>-----i Inform liDe failure to the supervisor via GSM

Seod request to slave for sensor data

Wait for reply [rom slave for IOms

Inform abnormal situtaioD to supervisor

Fig 5. Flow chart for CAN Based monitoring in master side

064

B. At the special slave side

",,'ait for initializtioD from master

NO

Receive information from tbe master

Se,od inJormatioD to mobile number via GSM

Fig 6. Flow chart for interrupts in special slave

C. At the slave side

Start

Wait selection address data from ID.a.ster

Wait for sensor initiaJiztion from DI3II,ster

After initializtioD send sensor data to ma,ster

'Vait for control data from ma,ster for IOms

NO

Work according to control data

Fig 7. Flow chart for parameter processing in slave side

Page 5: MCS-51 Microcontroller Based Industrial Automation and ... · MCS-51 Microcontroller Based Industrial Automation and Control System using ... automobiles and home. ... The microcontroller

V. EXPRIMENT AL AND SIMULA nON RESULTS

Entire automation and control system is divided into two stages. First stage is the industrial parameter processing stage i.e. slave 1 and 2. Second stage is the automation and control stage i.e. master. Fig. 8 is the overall hardware setup of industrial automation and controlling system. In the first stage, temperature sensor and gas sensor are connected to microcontrollers. The LCD is connected to port 0 of the microcontroller in the master order to display the instantaneous values of parameters. Control signals for LCD are obtained from PORT 2. The master is interfaced with special slave for interrupt purpose.

= :: �'It .... . . ...... . . � .. ......

" "" �UII' -II

Fig 9. Simulated output of temperature sensor circuit

065

The fig.9 shows simulated output of one of the processing stage i.e. temperature sensor circuit, using proteus schematic software.

VI. CONCLUSION

This paper is concerned about implementation of low cost system for monitoring parameters of an industrial boiler based on multiprocessor communication. The monitoring parameters are temperature and gas level of the boiler. Transmission of process information from plant to control room is made in fail safe and efficient manner by CAN serial communication protocol. Instantaneous values of process parameter are showed in LCD. Normal and abnormal conditions are viewed in the LCD. Control elements are activated and deactivated as per the program logic.

VII. FUTURE ENHANCEMENT

This project in future can be enhanced for

1. This can be expanded to a multi master multi slave network which will enhance the capabilities of the system to a great extent.

2. Remote sensing of the parameters can be made if they are loaded on to the server.

3. Initially we provide analysis assuming no errors on the CAN bus. This analysis is then extended, to account for errors on the bus.

[II

[21

[31

[41

[51

[61

[71

[81

REFERENCES

Presi.T.P, "P IC Microcontroller Based Vehicle Monitoring System Using Controller Area Network (CAN) Protocol",IEEE international conference 2012. Kumar, M. A.Verma, and A Srividya, Response-Time "Modeling of Controller Area Network (CAN). Distributed Computing and Networking, Lecture Notes in Computer Science Volume 5408, p63-174,2009. Tindell, K., A Burns, and AJ. Wellings, "Calculating controller area network (CAN) message response times", Control engineering Practice, 3(8): p. 1163-1169,2005 . Wilfried Voss, comprehensive guide to controller area network, Copperhill Media Corporation, 2005-2008. John Rinaldi and Vince Leslie, 'The Fast Guide to Controller Area Network (CAN) Application Layers", Real Time Automation, pp. 1-8, December 2003. Dogan Ibrahim, "Microcontroller based temperature monitoring and control", ISBN: 0750655569, Elsevier Science & Technology Books, October 2002. National Semiconductor, "LM35 Precision Centigrade Temperature sensors Data sheet", National Semiconductor Corporation, November 2000. Pazul, "Controller Area Network (CAN) Basics", Microchip technology Inc., AN713, May 1999.