Page 1: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

Catalogue

Medium Voltage Distribution

MCset 17.5 kVAir insulated switchboardWithdrawable switchgear SF6 or vacuum technology

DEAI02EN_COUV.indd 1DEAI02EN_COUV.indd 1 26/09/07 13:31:4326/09/07 13:31:43

Page 2: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

A new path for achieving your electrical installations

A comprehensive offer

MCset is part of a comprehensive offer of products that are perfectly coordinated to meet all medium and low voltage electrical distribution requirements. All of these products have been designed to work together: electrical, mechanical and communication compatibility.The electrical installation is thus both optimised and has improved performance:

better service continuity,increased personnel and equipment safety,guaranteed upgradeability,effi cient monitoring and control.

You therefore have all the advantages at hand in terms of know-how and creativity for achieving optimised, safe, upgradeable and compliant installations.

Tools for facilitating the design and installation

With Schneider Electric, you have a complete range of tools to help you get to know and install the products whilst complying with current standards and good working practices. These tools, technical sheets and guides, design software, training courses, etc are regularly updated.

bbbb

For a real partnership with you

A universal solution doesn’t exist because each electrical installation is specifi c. The variety of combinations on offer allows you to truly customise the technical solutions.You are able to express your creativity and put your know-how to best advantage when designing, manufacturing and exploiting an electrical installation.

Schneider Electric is associating itself with your know-how and your creativity to produce optimised, safe, upgradeable and compliant installations

DEAI02EN_COUV.indd 2DEAI02EN_COUV.indd 2 26/09/07 13:31:5726/09/07 13:31:57

Page 3: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

1

ContentsMCset 17.5 kV

Presentation 2Field of application 2Continuity of service and complete safety 3MCset, a comprehensive solution 4Quality assurance - environment 7

MCset range 8Description 8Technical characteristics 10Operating conditions 11Protection of people 12Specific applications 13Marine and Navy applications 14Choice of functional units 16

Cubicle description 18AD type cubicles Incomer and feeder 18CL - GL type cubicles Line-up bussectioning 19TT type cubicles Metering - Busbar earthing 20DI type cubicles Fuse switch feeder 21Motorpact Transition cubicle 22Motorpact Motor protection and control 23

Protection, monitoring and control 25Thermal diagnosis 25Protection system Sepam range 26Sepam series 20, series 40, series 80, Sepam 100 27Sepam series 20, series 40, series 80 Selection guide 28Instrument transformers 29

Switchgear 34Withdrawable parts 34

Vacuum type switchgear 36Evolis 17.5 kV circuit breaker 36Evolis HP circuit breaker 44CTV1 contactor 50

SF6 type switchgear 52LF circuit breaker 52Rollarc contactor 58DI switch cubicle 62

Installation 65Extraction withdrawable parts 65Implementation examples 66Connections 68

Appendices 70Cubicle equipment 70Current transformers (Selection guide) 71

A few references 72

Page 4: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

2

MCset adapts to all electrical power distribution requirements from 1 to 17.5 kV

MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations.

MCset offers you:pre-engineered and adaptable solutions tailored to your specifi c

requirements,SF6 and vacuum switching technologies,signifi cantly reduced maintenance,local support centres throughout the world.

MCset gives you the advantages of:continuity of service for your networks,enhanced safety for your staff and operations,optimized investment throughout the life of your installation,the possibility of integrating your medium voltage switchboard

in a monitoring and control system.

ApplicationsProduction and distribution

Electric power stations (thermal, nuclear),Auxiliary substations,Source substations.

IndustryOil & gas,Chemical industry,Paper mills, Metallurgy,Car industry,Mining,Cement plants,…

InfrastructureAirports,Ports,Hospitals,Water treatment,…

Marine and Navy applicationsCruisers,Container ships,Tankers,Offshore platforms, fi xed and mobile, LNG (Liquid Natural Gas),Navy,…

b

v

v

v

v

b

v

v

v

v

bbb

bbbbbbbb

bbbbb

bbbbbbb

Presentation Field of applicationM

T200

51P

E56

579

MT2

0052

PE

5554

0P

E56

580

Page 5: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

3

Presentation Continuity of service and complete safety

MCset is solidly based on extensive experience acquired throughout the world and provides your electrical network with a high level of dependability and safety.MCset integrates a host of innovative solutions designed around proven techniques: high performance switchgear, digital protection, monitoring and control systems, enclosures capable of withstanding internal arcing.From its very conception, MCset has taken account of three key user requirements:

SafetyOperations are all performed from the front, including access to

connections and busbars.Racking in and out is only possible with the door closed.The power-on indicator is situated on the front of the functional unit.The earthing switch has making capacity.One single ‘‘anti-refl ex” handle is used for all MCset operations.Internal arc withstand developed for all functional units.

ReliabilityType testing was carried out for each performance level in the MCset

range.The design, manufacturing and testing of MCset was carried out

according to ISO 9001: 2000 quality standard.Three-dimensional computer modeling techniques were used to study

the electrical fi elds.

Simplicity A user interface which is easily understood by everybody.Interlocks and padlocks preventing operator errors.Sepam-type protection units enabling on-site information retrieval

without any additional devices.Maintenance limited to simple, routine operating checks and cleaning

and greasing every 5 to 10 years.Easy installation due to identical civil engineering dimensions for

all cubicles and installation being possible against a wall.

b

b

b

b

b

b

b

b

b

b

b

b

b

b

PE

5658

1P

E56

386

PE

5658

3P

E56

582

Page 6: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

4

PE

5517

0P

E55

134

MCset provides the most effi cient means to control and protect a wide range of applications.Due to the devices it comprises, MCset can be easily integrated into a monitoring and control system.

Sepam protection and control unitsSepam series 20, series 40 and series 80 digital protection relays take full advantage of Merlin Gerin experience in electrical network protection.Sepam series 20, series 40 and series 80 provides all the necessary functions:

effective protection of people and property,accurate measurements and detailed diagnosis,integral equipment control,local or remote indication and operation.

Easy evolutionAddition of communication, digital I/O’s, analog output, or temperature acquisition are possible due to its modular design.

PowerMeter and Circuit Monitor metering unitsThe PowerLogic PowerMeter replaces a full complement of basic analog meters. This cost effective, high performance meter provides a full complement of accurate true-rms metering values.The PowerLogic series 3000/4000 Circuit Monitor is designed for critical power users and large energy consumers, to provide the information needed to confi dently enter the evolving world of deregulation.It can be adapted to meter almost any time-of-use or real-time rate.

Monitoring and controlMCset can be easily:

integrated into an existing monitoring and control system:communication between Sepam digital relays and PowerMeter/Circuit Monitor metering devices via a standard protocol (Modbus),

integrated into a SMS PowerLogic electrical installation monitoring system.

Thermal diagnosis systemSpecially designed for Schneider Electric MV equipment,this system continuously monitors the temperature rise, using optical fi bres and sensors installed at the heart of the sensitive areas.Thermal diagnosis system reduces the probability of failure and reduces maintenance time.

bbbb

b

b

MT2

0062

PE

5513

6Presentation MCset, a comprehensive solution

Page 7: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

5

PE

5513

7D

E57

492E

N

MCset Transparent Ready™ optionMCset switchboards integrate Web technologies so that you can fi nd out information about your electrical installation as easy as opening a Web page.All you need is a standard Web browser and a PC connected to your local area network.

Simple choiceA simple choice between TRe-1 and TRe-2 service levels allows you to easily order your Transparent Ready™ MCset switchboard.A customized level is also available.Your Transparent Ready™ MCset switchboard comes equipped with a Web server including Web pages dedicated to power equipment data.

Easy commissioningTransparent Ready™ equipment is delivered ready to connect and commission. A Quick Start guide, packaged with your switchboard, provides three easy-to-follow steps.

Functionalities providedTRe-1 TRe-2

Instantaneous readingsDisplays automatically updated meter values

b b

Circuit summary Displays the RMS current 3-phase average (A),the real power (kW), the power factor, the circuit breaker status (if applicable), etc.

b b

Load current summaryDisplays the current RMS value for each phase (A), for all circuits

b b

Demand current summaryDisplays the average demand current value for each phase (A), for all circuits

b b

Power summaryDisplays the present demand (kW), the peak demand (kW) and the times and dates of the records

b b

Energy summary Displays the energy (kWh) the reactive energy (kvarh), and the times and dates of the records

b b

Instantaneous readings, all devices Displays automatically updated meter values for all the communicating devices in the equipment

b

Basic historical data logging, energy and trendingDisplays automatically updated meter values for all the communicating devices in the equipment

b

Log displaysDisplays data as time curves, or tables

b

Export of data tablesAllows data tables to be exported in a standard Windows format

b

PE

5513

8P

E55

139

PE

5514

0

Presentation MCset, a comprehensive solution (cont.)

Sepam

Sepam

CM/PM

TCP/IP over Ethernet

Front socket

Hub

EGX400

MCset switchboard

Page 8: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

6

Presentation MCset, a comprehensive solution (cont.)

MT2

0064

MT2

0065

EN

Schneider Electric Services, by your sidethroughout the life of your installation

SpecifyingWe help you to defi ne your solutions: selection guide, technical assistance, advice…

ImplementingWe oversee the completion and commissioning of your installation: design, cost optimization, guaranteed performances and dependability, commissioning tests, etc.

OperatingWe help run your daily operations in real time: maintenance contract, technical assistance, supply of replacement parts, corrective and preventive maintenance, operation and maintenance training, etc.

ModernizingWe can bring the performance of your installation up to date:installation audit, switchgear diagnosis, adaptation and modifi cation, end of life recycling, etc.

Examples of services providedWarranty extensionA warranty extension is proposed if your installation is checked by ourselves before being commissioned.

Circuit breaker-contactor diagnosisThroughout the life of the equipment, it is possible to carry out routine measurement of its characteristics in order to optimize maintenance. This service may be part of a global installation maintenance contract.

End-of-life recyclingSchneider Electric Services has an operational subsidiary allowing you to recycle your medium voltage switchgear.

Modernizing Operating

Specifying Implementing

Page 9: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

7

Presentation Quality assurance - environmentM

T200

67M

T200

68M

T200

69E

N

Certifi ed quality: ISO 9001 version 2000A major assetIn each of its units, Schneider Electric integrates a functional organization whose main role is to check quality and monitor compliance with standards.This procedure is:

uniform throughout all departments,recognized by many customers and approved organizations.

But above all, it is its strict application that has allowed us to obtain the recognition of an independent organization: The French Quality Assurance Association (AFAQ).The quality system for the design and manufacture of MCset is certifi ed to be in conformity with the requirements of ISO 9001 version 2000 quality assurance standard.

Strict and systematic checksDuring manufacture, each MCset functional unit is subject to systematic routine testing with the aim of checking the quality and conformity of the following features:

measuring of opening and closing speeds,measuring of operating torque,dielectric test,testing of safety systems and interlocks,testing of low voltage components,conformity with drawings and diagrams.

The results obtained are recorded and approved by the quality control department on each device’s test certifi cate.This therefore guarantees product traceability.

Checking SF6 switchgearsealing test,fi lling pressure test.Checking vacuum switchgear

Each vacuum interrupter, sealed and airtight, is checked for the quality of the vacuum obtained. This pressure measurement is based on the proven “magnetron discharge” method. Using this sophisticated procedure, measurement is very precise and does not require access to the inside of the bulb, thus not affecting the airtight seal.

Protected environmentIn order to help you protect the environment and to relieve you of any concerns in terms of stock or dismantling, Schneider Electric Services offers to take back your equipment at the end of its life. MCset has been designed with environmental protection in mind:

the materials used, insulators and conductors are identifi ed, easily separable and recyclable,

the SF6 can be recovered at the end of the equipment’s life and reused after treatment,

production sites are certifi ed to ISO 14001.

b

b

b

b

b

b

b

b

b

v

v

b

b

b

b

DE

5574

5

Page 10: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

8

PE

5655

9

MCset range Description

Sepam

Busbars

Wiithdrawable part

Current transformers

Cablesconnection

LV control cabinet

Voltagetransformerscompartment

Page 11: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

9

MCset range Description (cont.)

Make up of an MCset switchboardMCset switchboards are made up of several interconnected functional units.Power connections are made between functional units within a switchboard via a single busbar.The electrical continuity of all metal frames is provided by the connection of each functional unit’s earthing busbar to the switchboard’s main earthing circuit.Low voltage wiring trays are provided in the switchboard above the low voltage control cabinets.LV cables can enter the switchboard through the top or bottom of each functional unit.

Description of a functional unitA functional unit comprises all equipment in the main and auxiliary circuits which together provide a protection function. Each functional unit combines all the components which are required to fulfi l this function:

the cubicle,the protection, monitoring and control system,the withdrawable part.

The cubicleThe cubicle is of LSC2B (Loss of Service Continuity Category) type as defi ned by IEC standard 62271-200, in other words the medium voltage parts are compartmented using metal partitions (PM class) which are connected to earth and which separate:

the busbars,the withdrawable part (circuit-breaker, fuse-contactor, disconnector truck or

earthing truck),MV connections, earthing switch, current sensors and voltage transformers

as required.MCset guarantees a high level of protection of people; when a compartment containing a main circuit is open, the other compartments and/or functional units may remain energised.The low voltage auxiliaries and monitoring unit are in a control cabinet separated from the medium voltage section.Four basic cubicle layouts are offered:

incomer or feeder ADline up bussection CL - GLbusbar metering and earthing TTswitch-fuse feeder DI

AD and CL cubicles have withdrawable vacuum type circuit-breaker and contactor switchgear.

The protection, monitoring and control systemThis includes:

Sepam, protection, monitoring and control unit,current sensors, which may be of 3 types,conventional current transformers,low voltage toroid type current transformers,LPCT type current transformers.CSP type broad-range current transformers,voltage transformers,zero sequence core balance current transformers (CSH type).

The withdrawable partThis includes:

the circuit-breaker, contactor or the earthing truck with its closing and opening mechanism, or the disconnector truck,

the lever-type propulsion mechanism for racking in-out,interlocks to fi x the withdrawable part on the fi xed part either in service position

or disconnected.

bbb

bb

b

bbbb

bbvvvvbb

b

bb

LSC2B (Loss of Service Continuity IEC 62271-200):this category defi nes the possibility of keeping other compartments energised (in service) when opening a main circuit compartment.

Page 12: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

10

MCset range Technical characteristicsM

T200

71

IAC (internal arc classifi cation):The metal enclosed switchgear may have different types of accessibility on the various sides of its enclosure. For identify purpose of different sides of the enclosure, the following code shall be used (according to IEC 62271-200 standard).A: restricted access to authorized personnel onlyF: access to the front sideL: access to the lateral sideR: access to the rear side.

The values below are given for normal operating conditions as defi ned in IEC 62271-200 and 60694.

Rated voltage (kV)7.2 12 17.5 (7)

Rated insulation levelPower frequency withstand voltage 50 Hz - 1 min (r ms kV) 20 28 38 (9)

Lightning impulse withstand voltage 1.2/50 µs (kV peak) 60 75 95

Nominal current and maximum short time withstand current (1)

Functional unit with circuit breakerShort time withstand current

Ith max. (kA/3 s) 25 25 2531.5 31.5 31.540 40 40

(kA/3 s) (8) 50 50 50 (7)

Rated current In max. busbar (A) 4000 4000 4000Rated current In CB (A) 1250 1250 1250

2500 2500 25003150 3150 31504000 (2) (5) 4000 (2) (5) 4000 (2) (5)

Functional unit with fuse-contactor (3)

Short time withstand current

Ith max. (kA) 50 (4) 50 (4) (6)

Rated current In max. (A) 250 200 (6)

Functional unit with switch-fuse (DI cubicle)Short time withstand current

Ith max. (kA) 50 (4) 50 (4) 31,5 (4)

Rated current In max. ≤ (A) 200 200 200Internal arc withstand (maximum value)

(kA/1 s) 50 50 50

(1) For functional units equipped with circuit breakers or fuse-contactors,the breaking capacity is equal to the short time withstand current. In all cases, the device peak making capacity is equal to 2.5 times the short time withstand current. (2) With fan. (3) Lightning impulse dielectric withstand voltage = 60 kV peak.(4) Limited by fuses.(5) With LF circuit breaker (with Evolis circuit breaker, consult us).(6) With Rollarc contactor.(7) Limited to 15 kV - 50 kA with Evolis HP circuit breaker. Limited to 17.5 kV - 40 kA with LF circuit breaker.(8) Limited to 1 s for In circuit breaker: 1250 A.(9) For Evolis HP circuit breaker: 42 kV.

Page 13: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

11

MCset range Operating conditionsM

T200

72 Operating conditionsNormal operating conditions, according to IEC 62271-1 for indoor switchgear

Ambient air temperature:less than or equal to 40°C,less than or equal to 35°C on average over 24 hours,greater than or equal to – 5°C.Altitude:less than or equal to 1000 m,above 1000 m, a derating coeffi cient is applied (please consult us).Atmosphere:no dust, smoke or corrosive or infl ammable gas and vapor, or salt

(clean industrial air).Humidity:average relative humidity over a 24 hour period ≤ 95%,average relative humidity over a 1 month period ≤ 90%,average vapor pressure over a 24 hour period ≤ 2.2 kPa,average vapor pressure over a 1 month period ≤ 1.8 kPa.

Specifi c operating conditions (please consult us)MCset has been developed to meet the following specifi c conditions:

temperature (possible derating),corrosive atmospheres, vibrations, (possible adaptation).

Storage conditionsIn order to retain all of the functional unit’s qualities when stored for prolonged periods, we recommend that the equipment is stored in its original packaging, in dry conditions sheltered from the sun and rain at a temperature of between – 25°C and + 55°C.

StandardsThe MCset range meets the following international standards:

IEC 60694: clauses common to high voltage switchgear,IEC 62271-200 (60298): metal-enclosed switchgear for alternating current

at rated voltages of between 1 and 52 kV,IEC 62271-100 (60056): high voltage alternating current circuit breakers,IEC 60470 : high voltage alternating current contactors, IEC 60265-1: high voltage switches,IEC 60282-2: high voltage fuses,IEC 62271-102 (60129): alternating current disconnectors and earthing switches,IEC 60255: measurement relay and protection unit,IEC 60044-1: current transformers,IEC 60044-2: voltage transformers.

bvvvbvvbv

bvvvv

bb

bb

bbbbbbbb

Page 14: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

12

MCset range Protection of peopleM

T200

76

MCset switchboard with tunnel

MCset internal arcBasic version (gas exhaust) MCset is designed to eliminate the effects of internal arcing in total safety, due to:

metal fl aps positioned above the enclosure, which in the case of internal fault, limit overpressure in the compartments.

nonfl ammable materials used for the cubicle.Internal arc versionMCset is designed to withstand and protect operators in the case of failure due to an internal arc. MCset has been successfully tested using type tests.Protection against internal arcing is available on 25 kA, 31.5 kA, 40 kA and 50 kA ratings.MCset proposes several options to install an internal arc switchboard.

3-sided internal arc protection For an MCset switchboard fi tted against a wall, access to the rear of the cubicle is impossible. Internal arc protection on 3 sides is suffi cient.

4-sided internal arc protectionIn the case of an MCset switchboard installed in the middle of a room, internal arc protection on 4 sides is necessary in order to protect an operator who goes behind the cubicle.

Installation in a room with limited ceiling height:height exceeding 2.8 m, potential for installing a tunnel above the switchboard to

prevent refl ection of hot gases on the ceiling.Ceiling height Tunnel2.8 m < h < 4 m Mandatoryh > 4 m Not mandatory

Internal arcing detector MCset has 2 systems that can detect internal arcing and switch off the power supply so as to limit the fault duration.

electromechanical detectorThis system employs a positive security electromechanical tripping circuit, positioned on the cubicle’s fl ap valves. This set transmits the information to the Sepam to give the opening order to the circuit breaker located upstream of the fault.

optic detector (VAMP system)Internal arcing is detected by optical sensors which will measure the light caused by the initiation of arcing. Based on this information, an electronic module, after processing the information, will give the opening order to the circuit breaker located upstream of the fault.

Dependable mechanical control devicesAll operations are carried out from the front face, including access to connections and busbars.The user is guided through icon-diagrams on each front panel making it easy to understand the operating sequence and device status.Interlocks and padlocks prevent operator errors.Several additional levels of security also protect operators:

racking in and out is only possible with the door closed.locking of the MV door open if the LV plug of the circuit breaker is not plug-in.the very extensive set of mechanical and electrical interlocks do not allow operator

error. These can be added to by key locks or padlocks according to specifi c operating procedures. Each selector can be fi tted with one to three padlocks.

all operations are carried out from the front face including access to connections and busbars.

the voltage present indicator is located on the front face of the functional unit, in the immediate vicinity of the earthing switch control.

disarming of circuit breaker when racking out. This function enables the circuit breaker control springs to be disarmed during the extraction operation.

locking of withdrawable part/cable compartment. This function disables the possibility of racking the withdrawable part in if the front panel (cable compartment) is not installed.

b

b

b

b

bv

b

v

v

bbb

b

b

b

b

MT2

0077

Page 15: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

13

MCset range Specifi c applications

NuclearThe medium voltage electrical distribution switchgear in a nuclear power station must meet the most stringent requirements. Schneider Electric’s experience in this area over more than 30 years is proposed to you via the MCset range. Certifi ed by the chief nuclear standards (IEC, RCCE), MCset provides you with:

Optimized personal safety,Solidity of electrical and mechanical solutions,Switchgear subjected to various tests:seismic,electrodynamic,switch-off.Panel of compact cubicles.

Seismic areasMCset meets international seismic specifi cations. Test procedures follow IEC 60068-3-3 standard.MCset is qualifi ed following the standards:

UBC 97,IBC 2000,MSK 64,ENDESA.

DEP ShellMCset switchboards are certifi ed by Shell n compliance with DEP 33.67.51.31 Gen (July 1998) for MV equipments.

GOST R certifi cation (Russia)The GOST R certifi cation system applies to most of the products sold and used in Russia.As far as electrical equipment is concerned, this certifi cate applies when the equipment is used under the following conditions:

electrical equipment designed for use in an explosive environment and in mines,equipment related to the oil and gas industries: prospecting, exploration, refi ning,

transportation, storage,equipment used in the chemical and petrochemical industries and considered

to be potentially hazardous because it operates in a toxic, explosive and aggressive environment,

electrical heating equipment used to produce ferrous and non-ferrous metal casting.This certifi cation is drawn up by an organisation external to Schneider Electric from all the product technical documents and must conform to the following Russian standards:

GOST 2.601-95PB 03-576-03PB 03-584-03.

The entire MCset range meets the GOST certifi cation requirements.

bbbvvvb

bbbb

bb

b

b

bbb

PE

5657

6

Page 16: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

14

MCset range Marine and Navy applications

Derived from standard MCset, a Marine version has been developed to meet specifi c conditions when used on ships or offshore platforms (vibrations/impacts, slant, etc.).This version carries over the electrical and dimensional characteristics of the standard range, adapted to marine requirements:

metalclad compartmented cubicle (LSC2B type),front access,withdrawable circuit breaker,Sepam protection and control chain,internal arc withstand,thermal diagnosis (optional).

Environmental conditionsAmbient temperature –5 to +45°CHumidity On 24 h 95%

On 1 month 90%Vibrations(IEC 60068-2-6)

Frequency range2 to 13.2 Hz 1 mm13.2 to 100 Hz 0.7 g

Certifi cationsMCset Marine (*) is approved by:

Lloyds Register (LR),Bureau Veritas (BV),Det Norske Veritas (DNV),Germanischer Lloyd (GL),Registro Italiano Navale (RINA).

(*) With LF circuit breaker (For Evolis circuit breaker, consult us).

bbbbbb

bbbbb

PE

5657

8P

E56

577

PE

5656

9

Page 17: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

15

Compact versionTo meet space constraints (clearance under ceiling) that are sometimes indispensable, a specifi c version is proposed.

Rated voltage (kV)7.2 12 17.5

Rated insulation levelPower frequency withstand voltage 50 Hz - 1 min (r ms kV) 20 28 38Lightning impulse withstand voltage 1.2/50 µs (kV peak) 60 75 95

Nominal current and maximum short time withstand current (1)

Functional unit with circuit breakerShort time withstand current

Ith max. (kA/3 s) 25 25 25

Rated current In max. busbar (A) 3150 3150 3150Rated current In CB (A) 1250 1250 1250

2500 2500 25003150 3150 3150

Functional unit with Rollarc fuse-contactor (3)

Short time withstand current

Ith max. (kA) 50 (4) 50 (4)

Rated current In max. (A) 250 200

Internal arc withstand (maximum value) AFLR(kA/1 s) 25 25 25

(1) For functional units equipped with circuit breakers or fuse-contactors,the breaking capacity is equal to the short time withstand current. In all cases, the device peak making capacity is equal to 2.5 times the short time withstand current. (3) Lightning impulse dielectric withstand voltage = 60 kV peak.(4) Limited by fuses.

Internal arcing withstand is ensured by the use of a tunnel specifi cally designed for marine applications. Located above the cubicle, it can evacuate gases due to arcing effects.

A low voltage control cabinet has also been designed to meet the need for using numerous control and monitoring systems and LV components.

The cubicles are provided with switchgear employing SF6 or vacuum technology (please consult us).

The incoming/outgoing feeder cubicles are connected by cables through the bottom.

Skids are available on option to group together several cubicles on a platform for improved rigidity and to absorb vibrations by means of dampers. They also facilitate handling and installation of the switchboard.

Motor starter applications: see Motorpact catalogue (page 23).

b

b

b

b

b

b

MCset range Marine and Navy applications (cont.)

2530

1200

85

DE

5679

2 Tunnel for internal arcing gasesAuxiliary cable duct

Higher low voltage control cabinet (640 mm)

“Anti-rolling” handle

Skid (option)

Page 18: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

16

MCset range Choice of functional units

Function Incomer (1) Feeder

Line Transformer Generator Line Transformer Transformer

Functional unit LI-B TI-B GI-B LF-B TF-B TF-S

Cubicle AD1-2-3 AD1-2-3 AD1-2-3 AD1-2-3 AD1-2-3 DI 2

Device Circuit breaker Circuit breaker Circuit breaker Circuit breaker Circuit breaker Fuse-switch

Sepam protection relayApplications Substation Transformer Generator Substation Transformer TransformerSingle line diagrams

MT2

0080

Sepam

MT2

0081

Sepam

MT2

0082

The MCset range comprises 13 functional applications.The table below can be used to link requirements to functional units and gives basic information on the general composition of each unit.Selection guide:You want to supply power to a transformer.The chosen solution is a transformer feeder/breaker.The corresponding functional unit will therefore be a TF-B, comprising a AD cubicle equipped with a withdrawable circuit breaker, and transformer application Sepam.

(1) The direct incomer (functional unit without circuit breaker, equipped with a fi xed busbar bridge) is produced using cubicles AD1-2-3.(2) Transition cubicle for MCC application (Motorpact).

Page 19: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

17

MCset range Choice of functional units (cont.)

Feeder Bussectioning Metering and busbar earthing

Motorpact transition (2)

Motor Motor Capacitor Capacitor Switchboard Substation Motor control

MF-B MF-C CB-B CB-C BS-B SS-B BB-V

AD1-2-3 AD1CMotorpact

AD1-2-3 AD1CMotorpact

CL1-2-3 et GL1-2-3

AD1-2-3 TT1-2

Circuit breaker Fuse contactor Circuit breaker Fuse contactor Circuit breaker Circuit breaker

Motor Motor Capacitor Capacitor Busbar Substation

MT2

0081

Sepam

MT2

0083

Sepam

MT2

0081

Sepam

MT2

0083

Sepam

MT2

0084

DE

5507

6

MT2

0078

DE

6016

7

Page 20: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

18

Cubicle description AD type cubicles Incomer and feeder

DE

5677

5

DE

5508

2

AD1, AD2, AD3

MV compartments1 Busbars for cubicle interconnection2 Withdrawable part3 MV connections by cables accessible from the front face4 Earthing switch5 Current sensors6 Voltage transformers (optionally equipped with withdrawable fuses).LV control cabinet7 Low voltage auxiliaries and the protection, monitoring and control unit are in a control cabinet which is separated from the medium voltage part.

1

7

2

54

6

3

MT2

0080

Sepam

MT2

0081

D

H

W

Characteristics (for more details, see the pages on the switchgear in question)

AD1 AD2 AD3Rated voltage (kV) 7.2 12 7.2 12 17.5 7.2 12 17.5Breaking capacity (kA) 25 31.5 50

(1)25 31.5 50

(1)40 50 40 25 31.5 25 31.5 40 50 25 31.5 40 50 25 31.5 40 50

Rated current (A)Evolis circuit breaker

630 b b b b b b b b

1250 b b b b b b b b b

2500 b b b b b b b b b

Evolis HP circuit breaker

1250 b b (5)

2500 b b b (5)

3150 b b b b b b b b b (5) b (5) b (5) b (5)

4000 (3) b (5) b (5) b (5) b (5)

CTV1 contactor 200 b

LF circuit breaker 630 b b b b b b b b b

1250 b b b b b b b b b b

2500 b b b b b b b b b b b

3150 b b b b b b b b b

4000 (6) b b b

Rollarc contactor 200 b b

250 b

Short-circuit making current Ip (kA peak)

50 Hz 63 79 63 79 100 125 100 63 79 63 79 100 125 63 79 100 125 63 79 100 12560 Hz 65 82 65 82 104 130 104 65 82 65 82 104 130 65 82 104 130 65 82 104 130

Dimensions (mm) H 2300 2300 2300W 570 700 900D (2) 1550 1550 1550

Weight (kg) (4) 850 1000 1300

(1) Limited by fuses.(2) Overall + 175 mm for 4-sided internal arcing protected switchboards, for 3150 A, for 4000 A or 2 sets of CT’s.(3) With fan (consult us).(4) Approximate weight fully equipped cubicle.(5) Limited at 15 kV.(6) With fan.

Page 21: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

19

DE

5748

9

Cubicle description CL - GL type cubicles Line-up bussectioning

DE

5677

6

DE

5677

7

MT2

0084

The bussectioning functional unit comprises 2 cubicles mounted side by side (one cubicle equipped with a circuit breaker, the other with a busbar return). CL1, CL2, CL3 GL1, GL2, GL3

CL1-2-3 or GL1-2-3

MV compartments1 Busbars to connect the bussectioning functional unit with other switchboard functional units2 Withdrawable part3 Current sensors4 Voltage transformers (optionally equipped with withdrawable fuses).LV control cabinet5 Low voltage auxiliaries and protection, monitoring and control unit are in one control cabinet, separated from the medium voltage part.

1

2

5

1

53

4

D

H

W W D

Characteristics (for more details, see the pages on the switchgear in question)

CL1-GL1 CL2-GL2 CL3-GL3Rated voltage (kV) 7.2 12 7.2 12 17.5 7.2 12 17.5Breaking capacity (kA) 25 31.5 25 31.5 40 50 40 25 31.5 25 31.5 40 50 25 31.5 40 50 25 31.5 40 50Rated current (A)Evolis circuit breaker

630 b b b b b b b b

1250 b b b b b b b b b

2500 b b b b b b b b b

Evolis HP circuit breaker

1250 b b (5)

2500 b b b (5)

3150 b b b b b b b b b (5) b (5) b (5) b (5)

4000 (3) b (5) b (5) b (5) b (5)

LF circuit breaker 630 b b b b b b b b b

1250 b b b b b b b b b b

2500 b b b b b b b b b b b

3150 b b b b b b b b b

4000 (6) b b b

Short-circuit making current Ip (kA peak)

50 Hz 63 79 63 79 100 125 100 63 79 63 79 100 125 63 79 100 125 63 79 100 12560 Hz 65 82 65 82 104 130 104 65 82 65 82 104 130 65 82 104 130 65 82 104 130

Dimensions (mm) H 2300 2300 2300W 570 (x 2) 700 (x 2) 900 (x 2)D (2) 1550 1550 1550

Weight (kg) (4) 1300 (CL1 + GL1) 1500 (CL2 + GL2) 1700 (CL3 + GL3)

(2) Overall + 175 mm for 4-sided internal arcing protected switchboards, for 3150 A, for 4000 A or 2 sets of CT’s.(3) With fan (consult us).(4) Approximate weight fully equipped cubicle.(5) Limited at 15 kV.(6) With fan.

Page 22: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

20

Cubicle description TT type cubiclesMetering Busbar earthing

DE

5509

3

DE

5677

8

MT2

0078 MV compartments

1 Busbars to connect the TT functional unit with other switchboard cubicles2 Earthing switch3 Voltage transformers (optionally equipped with withdrawable fuses).LV control cabinet4 Low voltage auxiliaries and the protection, monitoring and control unit are in a control cabinet which is separated from the medium voltage part.

CharacteristicsTT1 TT2

Rated voltage kV 7.2 12 7.2 12 17.5Insulation voltage kV r ms 50 Hz - 1 min 20 28 20 28 38

kV impulse 1.2/50 µs 60 75 60 75 95Rated current A 630 b b b b b b

(busbar intensity)) 1250 b b b b b b

2500 b b b b b b

3150 b b b b b b

4000 (2) b b b b b b

Short time withstand current kA r ms 1 s 31.5 31.5 50 50 31.5 40 kA r ms 3 s 31.5 31.5 40 40 31.5 40Dimensions (mm) H 2300 2300

W 570 700D (1) 1550 1550

Weight (kg) 500 550

(1) Overall + 175 mm for 4-sided internal arcing protected switchboards.(2) With LF circuit breaker only.

TT1-2

1

4

2

3

D

H

W

Page 23: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

21

4

1

2

3

Cubicle description DI type cubicles Fuse switch feeder

DE

5509

8

DE

5677

9

MT2

0082 MV compartments

1 Busbars to connect the DI functional unit with other switchboard cubicles2 Switch - earthing switch3 MV fusesLV control cabinet4 Low voltage auxiliaries and protection, monitoring and control unit are in one control cabinet, separated from the medium voltage part.

CharacteristicsDI2

Rated voltage kV 7.2 12 17.5Insulation voltage kV r ms 50 Hz - 1 min 20 28 38

kV impulse 1.2/50 µs 60 75 95Rated current A 200 b b b

Breaking capacity kA (2) 50 50 31.5Short time withstand current kA r ms (2) 50 50 31.5Dimensions (mm) H 2300

W 700D (1) 1550

Weight (kg) 500

(1) Overall + 175 mm for switchboard internal arcing 4 sides.(2) Limited by fuses.

DI cubicles including a fuse switch are used to supply power and protect low power transformers.E.g.: auxiliary service transformers in primary substations.All operations are carried out from the front face, including access to connections and busbars. All functional interlocks meet recommendations in IEC 62271-200:

the switch is only possible to close if the earthing switch is open and the connection access panel is in place,

closing of the earthing switch is only possible if the switch is open, opening of the access panel to medium voltage connections and fuses is only

possible of the earthing switches upstream and downstream of the fuses are closed,the switch is locked in the open position when the access panel is taken off.

The voltage presence indicator is situated on the front face of the functional unit, integrated in the switch’s control panel.

b

bb

b

DI2

D

H

W

Page 24: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

22

Cubicle description MotorpactMotorpact transition cubicle

DE

5679

0

DE

5679

1

DE

6016

7 CompositionBasic equipment

1 enclosure (standard IP3X),1 set of busbars in separate compartment,1 removable front panel.

OptionsInternal arc withstand,IP4X or IPX1 enclosure,Encapsulated busbars.

bbb

bbb

Characteristics

Maximum rated voltage 7.2 kVInsulation voltage

Power frequency withstand (1 min) 20 kVLightning impulse withstand (1.2/50 µs, peak value) 60 kV

Busbars rating 630 A1250 A2500 A3150 A

Dimensions H 2300 mmW 375 mmD 1550 mm

Approximate weight 1250 A 240 kg2500 A 275 kg3150 A 310 kg

D

H

W

Page 25: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

23

Cubicle description MotorpactMotor protection and control

PE

5514

1P

E55

253

Motorpact, an innovative range of motor starters, with vacuum technology contactor Motorpact is a motor monitoring and control switchboard that can be combined with an MCset switchboard by means of a transition cubicle.Main characteristics:

rated voltage 7.2 kV,maximum busbars rating: 2500 A,rated short time withstand current: 40 kA 3 s,internal arc withstand: 25 kA 1 s

40 kA 0.5 s 50 kA 0.25 s,

rated operational current: 400 A,maximum fuse rating: 2 x 250 A.

Note: for details, see Motorpact catalogue no. AMTED302059.

Motorpact motor starters provide a wide range of applications including reduced voltage starting:

FVNR: direct on line motor starter,RVAT: reduced voltage autotransformer motor starter,RVSS: reduced voltage SoftStart motor starter.

They are suitable for all MV motor applications in markets such as: oil & gas, mining, water, pulp and paper, for starting:

pumps,fans,compressors,crushers,conveyors, etc.

CompactnessCompact dimensions thanks to a 375 mm width.Softarter and Autotransfo built into the switchboard.

SafetyFull cubicle protection for internal arc withstand (AFLR 4 sides).Electrical and mechanical interlocking, closed door operation.Visible insulation by means of portholes.

ReliabilityFewer components and fasteners.

Less maintenanceCorrosive atmosphere withstand.Maintenance free disconnector (capacity: 5000 operations).Front access to compartments.

Characteristics

Installation Indoor typeMaximum rated voltage 7.2 kV Insulation voltage

Power frequency withstand (1 mn) 20 kV Impulse withstand voltage (1.2/50 µs, peak value) 60 kV

Maximum rated short time withstand current (busbars) 40 kA 3 s 50 kA 2 s*

Rated frequency 50/60 HzMaximum busbars rating 2500 A

3150 A*Degree of protection

Enclosure IP3X, IP4X, IPX1, IPX2Between compartments IP2XC

* for stand-alone applications or when lined up with LF circuit breaker MCset switchgear

bbbb

bb

bbb

bbbbb

bb

bbb

b

bbb

MCset lined up with Motorpact

Page 26: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

24

FVNRFull voltage non reversing asynchronous motor starter

DE

5708

6

SepamM20

M

LPCT

DE

5679

3

DE

5679

4

7

5

1

4

6

2

3

MV compartment1 Line disconnector 2 Busbars3 Fuses 4 Contactor 5 Earthing switch6 Current sensors LPCT,current transformer and earth fault sensor

LV control cabinet7 LV protection, measurement and control devices

RVATAuto-transformer asynchronous motor starter

DE

5708

8

SepamM41

M

LPCT

DE

5679

5

DE

5679

6

1

3

2

1 Run and start vacuum contactor 2 Busbars3 Auto-transformer

RVSSSoftstart asynchronous motor starter

DE

5709

0FR

Sepam

LPCT

M

Relais de protectionSoftStart

DE

5679

7

DE

5679

8

1

3

2

1 By-pass vacuum contactor 2 Busbars3 SoftStart power stack

The Motorpact range includes 3 types of motor starter

Cubicle description MotorpactMotor protection and control (cont.)

Page 27: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

25

Thermal diagnosis systemUseTo reduce maintenance costs in MV substations.It continuously monitors temperature rise using optical fi bres and sensors installed at the heart of the sensitive areas.The sensors are located on cable connections and on top MV fuse holders.

PresentationThermal diagnosis is based on the principle of temperature measurement of energized circuits. By using optical fi bres, the system doesn’t introduce any risks in terms of insulation.It provides:

permanent monitoring of the temperature rise in power circuits at the connections,tripping of a “pre-alarm”, then an “alarm” by activating dry contact outputs,indication of the zone and circuit involved.

The standard solution is composed of the MDT module and two probes as described hereunder.

Probes CFO733The optical fi bre probes are factory-built assemblies comprising:

3 sensors attached to the power circuit,the optical connections,a connector linked to the module.

This connector incorporates the opto-electrical conversion unit thus eliminating any optical connections when assembling.

MDT107 moduleThe MDT107 electronic module is mounted in the low voltage compartment of the cubicle. It provides the following functions:

monitoring of temperature rise in 2 zones,triggering of the pre-alarm,triggering of the alarm,self-monitoring of the module,self monitoring of the temperature probes.

Technical characteristicsOptical fi bre probes CF0733

Maximum equipment voltage 17.5 kVRated power frequency voltage 38 kVImpulse voltage 95 kVMaximum fi bre/sensor temperature 120°CMDT107 module

Temperature rise setting To be defi nedStorage temperature –25°C to +70°CValues of maximum absolute thresholds Pre-alarm = 115°C

Alarm = 120°CDIN profi le width 10.5 cmModule power 24/250 Vdc, 110/240 VacDry contact voltage Voltage 24, 48, 127, 220 Vdc

110 to 240 VacCurrent 5 A permanent (pre-alarm)

8 A permanent (alarm)Consumption (standby-max.) AC < 1.2 W (standby) - < 3.4 W (max.)

DC < 4.4 VA (standby) - < 6.6 VA (max.)

bbb

bbb

bbbbb

Protection, monitoring and control

Thermal diagnosisP

E55

160

DE

5678

0

Continuity of service is of prime importance for electrical power supplies, particularly.for heavy industries.By using the new thermal diagnosis system developed for MCset, we offer you the possibility of monitoring on an on-going basis, thus reducing the probability of failure and reducing maintenance time.

Page 28: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

26

PE

5517

0

DE

5678

1Each MCset functional unit can be equipped with a comprehensive protection, monitoring and control system comprising:b instrument transformers (*) to measure the necessary electrical values (phase current, residual current, voltages, etc.)b protection relays, providing functions adapted to the part of the network to be protectedb metering equipment, to inform operatorsb low voltage relaying, i.e. to provide control of the breaking device (contactor and circuit breaker) of the withdrawable partb various auxiliaries: secondary circuit test units, etc.

(*) Please check in the Sepam catalogue the sensor to use.

Protection relaysmetering equipment

Switchgear (circuit breaker and contactor)

Instrument transformers

Sepam: protection digital relaysSepam, is a range of digital monitoring protection and control units.Sepam is at the centre of the protection, monitoring and control system for MCset functional units: all the necessary protection, metering, control, monitoring and signalling functions are carried out by Sepam.

Like the MCset range, the Sepam range is a range of units defi ned to provide an optimal solution for each application, and includes (eg):

Sepam S, substation incomer and feeder,Sepam B, bussectioning,Sepam T, transformer feeder,Sepam M, motor feeder,Sepam G, generator feeder,Sepam C, capacitor feeder.

The Sepam range consists of Sepam series 20, series 40 and series 80, a range of modular protection relays to adapt precisely to your need.

bbbbbb

Sepam advantagesReliability

Over 20 years of experience in multi-function digital protection relays.Over 150,000 Sepam units in service in more than 90 countries.

QualityQuality design based on dependability studies and strict defi nition of

environmental constraints: temperature, pollution, EMC, dielectric strength…Quality manufacturing based on procurement agreements with suppliers

and inspection throughout all manufacturing phases.Simplicity of use

Local operation facilitated by the ergonomic User Machine Interface informing the operator fully and clearly in his own language.

Ease of setup thanks to the fl exibility and user-friendliness of the parameters setup software.

bb

b

b

b

b

Protection, monitoring and control

Protection system Sepam range

Page 29: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

27

PE

5638

4

Sepam 100 MI Sepam 100 LD Sepam 100 LA

PE

6011

6

PE

6011

7

PE

6011

8

The Sepam range of protection relays is designed for the operation of machines and electrical distribution networks of industrial installations and utility substations at all levels of voltage.It includes 3 families: b Sepam series 20, for usual applications.b Sepam series 40,for demanding applications.b Sepam series 80, for custom applications.To cover all needs, from the simplest to the most complete.

Sepam multifunction protection relaysA range of solutions adapted to your application

Substation protection (incomers, feeders, busbars),Transformer protection,Motor and generator protection.

All of the necessary functions for your application Effective protection of people and property,Accurate measurements and detailed diagnosis,Integral equipment control,Local or remote indication and operation.

Flexibility and upgrading capabilityTo adapt to as many situations as possible, and allow for future installation upgrading, optional modules may be added to Sepam at any time for new functions.

bbb

bbbb

Sepam series 80 modular architecture1- Base unit, with integrated or remote advanced User Machine Interface.2- Parameter and protection settings saved on removable memory cartridge.3- 42 logic inputs and 23 outputs relays with 3 optional modules providing 14 inputs and 6 outputs.4- 2 independent Modbus communication ports.b Direct connection to 2-wire RS 485, 4-wire RS 485 and fi ber optic networks.b Connection to Ethernet TCP/IP network via PowerLogicSystem webserver (Transparent Ready™).5- Processing of data from 16 temperature sensors.6- 1 low level analog output, 0-10 mA, 4-20 mA or 0-20 mA.7- Synchro-check module.8- Software tools:b Sepam parameter and protection setting and control logic customization,b local or remote installation operation,b retrieval and display of disturbance recording data.

Sepam 100 additional unitsSepam 100 units round off the Sepam range and can be installed either separately or combined with either Sepam series 20, series 40 and series 80.Sepam 100 has several variants:

Sepam 100 MI, local breaking device control and signalling modules (many different line diagram types are available):

Sepam 100 LD, high impedance differential protection Sepam 100 LA, self-powering protection (back-up protection without auxiliary

power supply).

b

bb

Protection, monitoring and control

Sepam series 20, series 40, series 80, Sepam 100

Page 30: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

28

Sepam Protections ApplicationsBasic Specifi c Substation Transformer Motor Generator Busbar Capacitor

Sepam series 2010 logic inputs8 relay outputs1 communication port8 temperature sensor

inputs

bbbb

DE

5749

3 Current protection

S20 T20 M20

Breakerfailer

S23 T23

DE

5749

4 Voltage and frequency protection

B21

Loss of mains (ROCOF)

B22

Sepam series 4010 logic inputs8 relay outputsLogic equation editor1 communication port 16 temperature sensor

inputs

bbbbb

DE

5749

5 Current,voltage and frequency protection

S40 T40 G40

Directional earth fault

S41 M41

Directional earth fault and phase overcurrent

S42 T42

Sepam series 8042 logic inputs23 relay outputsLogic equation editor2 communication ports,

for multi-master or redundant architecture

16 temperature sensor inputs

Removable memory cartridge with parameters and settings for quick commissioning after replacement

Battery to save disturbance recording and event logging data

Mimic-based User Machine Interface for safe local equipment control

Logipam programming software (optional), to program specifi c functions

bbbb

b

b

b

b

b

DE

5749

6 Current,voltage and frequency protection

S80 B80

Directional earth fault

S81 T81 M81

Directional earth fault and phase overcurrent

S82 T82 G82

Loss of mains (ROCOF)

S84

DE

5749

7 Transformer or machine transformer- differential

T87 M88 G88

Machine differential

M87 G87

DE

5749

8 Voltage and frequency protection for two sets of busbars

B83

DE

5749

9 Capacitor bank unbalance

C86

Protection, monitoring and control

Sepam series 20, series 40, series 80Selection guide

Page 31: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

29

E28

676

E74

399

E74

400

ARJP1, 2 or 3

ARJA1

ARO1

Conventional current transformers Conventional current transformers are used to provide power to metering, measuring or control devices. They measure the value of primary current from 10 A to 3150 A. Schneider Electric has drawn up a list of current transformers which are appropriate for use with digital protection devices in order to make it easier to determine accuracy characteristics. This list is available in the selection guide on page 75.

For contactor cubicle AD1Transformer ARJP1/N2J

Single primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

bbI1n (A) 10 20 30 50 75 100 150 200 250Ith (kA) 1.2 2.4 3.6 6 10 10 10 10 10t (s) 1 1 1 1 1 1 1 1 1Measuring* Protection*

cl.0.5 15 VA5P20 2.5 VA

For cubicles AD1-CL1-GL1-AD2-CL2-GL2Transformer ARJP2/N2J

Double primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

bbI1n (A) 50-100 75-150 100-200 150-300 200-400 250-500 600 750Ith (kA) 40 40 31.5-40 40 40 40 50 50t (s) 1 1 1 1 1 1 1 1Measuring* Protection*

cl.0.5 5-10VA 10-20 VA 7.5-15VA 10-20 VA 20VA 20VA5P20 2.5-5VA 2.5-5VA 2.5-5VA 2.5-5VA 5-10VA 5-10VA 7.5VA 7.5VA

For cubicles AD1-CL1-GL1-AD2-CL2-GL2Transformer ARJP3/N2J

Single primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

bbI1n (A) 1000 1250Ith (kA) 50 50t (s) 1 1Measuring* Protection*

cl.0.5 30 VA 30 VA5P20 10 VA 10 VA

For cubicles AD3-CL3-GL3Transformer ARJA1/N2J

Single primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

bbI1n (A) 1500 2000 2500Ith (kA) 50 50 50t (s) 1 1 1measuring* protection*

cl.0.5 30 VA 30 VA 30 VA5P20 15 VA 15 VA 15 VA

For cubicles AD3-CL3-GL3Transformer ARO1a/N3

Single primary current, triple secondary current for measurement or protectionFrequency 50-60 Hz

bbI1n (A) 3150Ith (kA) 50t (s) 1Measuring* Protection*

cl.0.5 30 VA5P20 7.5 VA

* The secondary current for measuring and protection can be of 1 A or 5 A.

Protection, monitoring and control

Instrument transformers

Page 32: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

30

Protection, monitoring and control

Instrument transformers (cont.)

LPCT in cubicle

LPCT’s (Low Power Current Transformers) meet IEC standard IEC 60044-8.These are CT’s with a direct voltage output which has the advantage of having a very wide range of applications, simplifying selection.

LCPT low power current transformers LPCT’s are specifi c current sensors with a direct voltage output of the “Low Power Current Transformers” type, in conformity with standard IEC 60044-8.LPCT’s provide metering and protection functions.They are defi ned by:

the rated primary currentthe extended primary currentthe accuracy limit primary current or the accuracy limit factor.

These have a linear response over a large current range and do not start to saturate until beyond the currents to be broken.

PE

5656

1

PE

5656

3

CLP1 CLP3

AD1 - AD1C 630/1250 A b

AD2 630 A b

AD3 1250 A b

2500 A b

bbb

Type Primary current Secondary voltage

Accuracy class

Accuracy limit factor

Thermal resistance

Rated insulation Frequency Secondary connectorrated extended

(A) (A) (mV)FLP

(kA - 1 s)Ur(kV)

Ud(kV - 1 min)

Up(kV peak) (Hz)

CLP1 100 1250 22.5 0.5 - 5P 500 50 17.5 38 95 50/60 RJ45 - 8 ptsCLP3 2500 400 40

Page 33: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

31

Protection, monitoring and control

Instrument transformers (cont.)E

7296

5 Low voltage toroid type current transformersFor cubicles AD1-AD2 with one single-pole cableTransformer ARC2

Single primary current, single secondary current for protectionFrequency 50-60 Hz

I1n (A) 75 100 150 200 250 300 400Ith (kA) 50 50 50 50 50 50 50t (s) 1 1 1 1 1 1 1Protection 5P20 2.5 VA 2.5 VA 5 VA 5 VA 5 VA 5 VA 5 VA

Single primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

I1n (A) 200 250 300 400 600Ith (kA) 50 50 50 50 50t (s) 1MeasuringProtection

5 VA cl.1 10 VA cl.0.5 10 VA cl.0.5 15 VA cl.0.5 15 VA cl.0.55P20 2.5 VA 5 VA 5 VA 5 VA 5 VA

For cubicles AD1-AD2 with two single-pole cablesTransformer ARC3

Single primary current, double secondary current for measurement or protectionFrequency 50-60 Hz

I1n (A) 750 1000 1250Ith (kA) 50 50 50t (s) 1MeasuringProtection

cl.0.5 20 VA 30 VA 30 VA5P20 7.5 VA 10 VA 10 VA

Zero sequence core balance current transformers (CSH type)CSH 120 and CSH 200 core balance CT’s, provide more sensitive protection by direct measurement of earth fault currents.Specifi cally designed for the Sepam range, they can be directly connected to the Sepam “residual current” input.They are only different in terms of their diameter:

CSH 120 - 120 mm internal diameter,CSH 200 - 200 mm internal diameter.

bb

bb

bb

bb

E28

678

Zero sequence core balance CT (CSH type)

Page 34: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

32

Protection, monitoring and control

Instrument transformers (cont.)E

2868

0E

2867

9

Voltage transformersThese supply power to:

measuring, metering and monitoring devices,relays or protective devices,auxiliary LV sources for various types of switchgear; all these devices are

protected and insulated from the MV section.They are installed at the bottom of the functional unit. In the withdrawable fuse version, the voltage transformers are attached to a side wall. The energized part is entirely encapsulated in an epoxy resin, which provides both electrical insulation and excellent mechanical strength.They include the following models:

with one insulated MV terminal, for connection between neutral and phase conductors in three-phase systems with withdrawable MV fuses,

with two insulated MV terminals, for connection between phase conductors.

For cubicles AD1-CL1-GL1-TT1-AD2-CL2-GL2-AD3-CL3-GL3Transformer VRQ3n/S2

Phase-earthFrequency 50-60 Hz

Primary voltage (kV)

3/3 3.3/3 5.5/3 6/3 6.6/3 10/3 11/3 13.8/3 15/3

1st secondary voltage (V)

100/3 110/3 110/3 100/3 110/3 100/3 110/3 110/3 100/3

2nd secondary voltage (V)

100/3 110/3 110/3 100/3 110/3 100/3 110/3 110/3 100/3

1st secondary accuracy class (VA)

30-50 VA cl.0.5

2nd secondary accuracy class (VA)

50 VA cl.0.5

For cubicles AD2-CL2-GL2-TT2-AD3-CL3-GL3Transformer VRC1/S1F

Phase-phaseFrequency 50-60 Hz

Primary voltage (kV) 3.3 5.5 6,6 11 13.8 15Secondary voltage (V) 110 110 110 110 110 100Accuracy class (VA) 75 VA cl.0.5

For cubicle AD1 contactorThis transformer provides power to the coil in order to keep the magnetic circuit of the contactor closed.Transformer VRCR/S1

Phase-phaseFrequency 50-60 Hz

Primary voltage (kV) 3.3 5.5 6.6Secondary voltage (V) 110 110 110Accuracy class (VA) 50 VA cl.0.5

bbb

b

b

bb

bb

bb

VRQ3

VRC1/S1F

MT2

0104

VRCR

Page 35: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

33

Page 36: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

34

PE

5504

8

Extraction table

Withdrawable part

Switchgear Withdrawable parts

Page 37: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

35

These include:the circuit breaker or contactor, the disconnector truck or the earthing truck,the lever-type propulsion mechanism for racking in-out,interlocks to fi x the withdrawable parts onto the fi xed part.

The live parts are housed in an insulating enclosure in the sealed pressure system in compliance with IEC 62271-100.The devices used to equip the MCset range of functional units have outstanding features:

long service life,maintenance-free live parts,high electrical endurance,operating safety,insensitivity to the environment.

bbb

bbbbb

Switchgear Withdrawable parts (cont.)

Withdrawable parts

DE

5678

2 Circuit breaker A circuit breaker is a safety device enabling switching and protection of electrical distribution networks. Installed in the MCset cubicle, it protects all components situated downstream during a short-circuit.

EvolisEvolis HPLF.

bbb

PE

5678

3 ContactorThe contactor is a motor control and protection device.

CTV1Rollarc.

bb

PE

5678

4 Earthing truck The earthing truck is a safety feature which allows the cubicle busbar to be earthed. It is installed instead of the circuit breaker and has the same interlock possibilities.

PE

5678

5 Disconnector truck The disconnector truck enables the upper and lower part of the cubicle to be short-circuited. It is installed instead of the circuit breaker and has the same interlock possibilities.

Page 38: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

36

Vacuum type switchgear Evolis 17.5 kV circuit breakerPresentation

PresentationThe Evolis circuit breaker is used to equip AD1-2-3 and CL1-2-3 cubicles for rated values of 7.2kV to 17.5kV.

High electrical enduranceA magnetic fi eld is applied in the axis of the interrupter contacts.This process maintains the arc in diffuse mode, even at high current values. It ensures optimal distribution of energy over the contact surface and avoids localized temperature rise.The advantages of this technique are:

a very compact interrupter unit,low dissipation of arc energy in the interrupters.

Evolis is in conformity with the highest electrical endurance class (IEC60056: class E2).

High mechanical enduranceThis magnetic fi eld is generated by a patented outside coil which surrounds the contact area. This solution has many advantages:

a simplifi ed and therefore reliable interrupter unit,heavy duty contacts which do not distort during repeated switching operations.

For the fi rst time the control mechanism in a low voltage device is being integrated in a medium voltage circuit breaker. The Masterpact control unit used on Evolis gives us the benefi t of a system that has proved its value over more than ten years in hundreds of thousands of installations.Evolis is in conformity with the most demanding mechanical endurance class (IEC60056: class M2).

bb

bb

PE

5656

5

Page 39: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

37

Vacuum type switchgear Evolis 17.5 kV circuit breakerCharacteristics

Characterisitics of Evolis circuit breakers in MCset cubiclesThe electrical characteristics are given on the circuit breaker designation (rating plate).

Electrical characteristics according to IEC 62271-100Evolis/MCset 1 Evolis/MCset 2

Phase to phase mm 145 185Rated voltage Ur kV 50/60 Hz 7.2 12 7.2 12 17.5Insulation level- power frequency withstand Ud kV 50 Hz 1 min (*) 20 28 20 28 38- lightning impulse withstand Up kV peak 60 75 60 75 95Rated current Ir A 630 b b b b b b b b b b

1250 b b b b b b b b b b

25 31.5 25 31.5 31.5 40 31.5 40 25 31.5Short circuit current Isc kA 25 31.5 25 31.5 31.5 40 31.5 40 25 31.5Short time withstand current Ik/tk kA/3 s 50 Hz 63 79 63 79 79 100 79 100 63 79Short-circuit making current Ip kA peak 60 Hz 65 82 65 82 82 104 82 104 65 82

Evolis/MCset 3Entre phases mm 240Rated voltage Ur kV 50/60 Hz 7.2 12 17.5Insulation level- power frequency withstand Ud kV 50 Hz 1 min (*) 20 28 38- lightning impulse withstand Up kV peak 60 75 95Rated current Ir A 630 – – b – – b – – –

1250 – – b – – b – – b

2500 b b b b b b b b b

Short circuit current Isc kA 25 31.5 40 25 31.5 40 25 31.5 40Short time withstand current Ik/tk kA/3 s 25 31.5 40 25 31.5 40 25 31.5 40Short-circuit making current Ip kA peak 50 Hz 63 79 100 63 79 100 63 79 100

60 Hz 65 82 104 65 82 104 65 82 104

Common characteristics according to IEC 62271-100Rated switching sequence O-3 min-CO-3 min-CO b

O-0.3 s-CO-3 min-CO b

O-0.3 s-CO-15 s-CO b

Operating times Opening < 50 msBreaking < 60 msClosing < 71 ms

Service temperature T °C – 25 to + 40Mechanical endurance Class M2

Number of switching operations

10 000

Electrical endurance Class E2Number of switching operations at full Isc value

25 kA 10031.5 kA 5040 kA 30

Capacitive current breaking capacity Class C1Average relative humidity Over 24 h < 95%

Over 1 month < 90%

(*) Circuit breaker tested at Ud 42 kV 50 Hz, 1 minb Available– Not available.

Page 40: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

38

Vacuum type switchgear Evolis 17.5 kV circuit breakerP2 stored energy operating mechanismPresentation

Operation of the P2 stored energy operating mechanismThis mechanism guarantees the device an opening and closing speed unaffected by the operator, for both electric and manual orders. It carries out the O and CO cycles and is automatically recharged by a gear motor after closing. It consists of:

the stored energy operating mechanism which stores in springs the energy required to open and close the device

a gear motor electrical charging device with manual charging by lever(useful on loss of auxiliary supply)

manual order devices by push buttons on the front panel of the device an electrical remote closing device containing a release with an antipumping relayan electrical opening device containing one or more releases, for example:shunt openingUndervoltageMitop, a low consumption release, used only with the Sepam 100 LA

protection relay.an operation counter a position indication device by mechanical indicator

and 3 modules of 4 auxiliary contacts whose availability varies according to the diagram used

a device for indicating “charged” operating mechanism status by mechanical indicator and electrical contact.

Wiring diagram (principle)

b

b

bbbvvv

bb

b

PE

5660

0D

E57

525E

N

Fault Ready to close

Auxiliary contacts

Circuit breaker openOperating mechanism loaded

Remote control

OF24OF23OF22OF21OF14OF13OF12OF11OF4OF3OF2OF1

SDE

or

PF

XF

MX1

MX2

MN

Mitop Reset

Charged

MCH

Page 41: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

39

Vacuum type switchgear Evolis 17.5 kV circuit breakerP2 stored energy operating mechanismOpening circuit

DE

5752

6D

E57

527

Circuit breaker equipped with a shunt opening release (MX)

Shunt opening release (MX1 and MX2)

CompositionThe opening circuit is produced using the following components:

a shunt opening release (MX1)a second shunt opening release (MX2)undervoltage release (MN)time delayed undervoltage release (MNR: MN + time delay).

The time delay, placed outside the circuit breaker, can be disabled by an emergency stop button to give instant circuit breaker opening.

low energy release (Mitop).Note: see the table of the releases’ combinations on the following page.

Shunt opening release (MX1 and MX2)Energizing this release causes instant opening of the circuit breaker.Permanent power supply to the MX unit locks the circuit breaker in the “open” position.

CharacteristicsPower supply V AC 24, 48, 100…130, 200…250

V DC 24…30, 48…60, 100…130, 200…250Threshold 0.7 to 1.1 UrConsumption (VA or W) Triggering 200 (for 200 ms)

Latched 4.5

bbbb

b

Page 42: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

40

Vacuum type switchgear Evolis 17.5 kV circuit breakerP2 stored energy operating mechanismOpening circuit (cont.)

Undervoltage release (MN)

Undervoltage release (MN)This release unit causes the systematic opening of the circuit breaker when itssupply voltage drops below a value less than 35% of the rated voltage, even if thisdrop is slow and gradual. It can open the circuit breaker between 35% and 70% ofits rated voltage. If the release unit is not supplied power, manual or electrical closingof the circuit breaker is impossible. Closing of the circuit breaker is possible whenthe supply voltage of the release unit reaches 85% of its rated voltage.

CharacteristicsPower supply V AC 24, 48, 100…130, 200…250

V DC 24…30, 48 …60, 100…130, 200…250Threshold Opening 0.35 to 0.7 Ur

Closing 0.85 UrConsumption (VA or W) Triggering 200 (for 200 ms)

Latched 4.5

Time delay for MNTo eliminate spurious tripping of the circuit breaker when there are brief voltage drops, the MN action is controlled with a time delay. This function is achieved by adding a time delay unit outside of the undervoltage release (MN) circuit (adjustable time delay).This unit is placed outside the circuit breaker and can be inhibited by an emergency stop button to obtain instant circuit breaker opening.

CharacteristicsPower supply V AC 48…60, 100…130, 200…250

V DC 100…130, 200…250Threshold Opening 0.35 to 0.7 Ur

Closing 0.85 UrConsumption (VA or W) Triggering 200 (for 200 ms)

Latched 4.5Temporisation 0.5 s - 0.9 s - 1.5 s - 3 s

Low energy release (Mitop)This release includes a low consumption unit and is specifi cally used with the Sepam 100LA self-powered unit (“REFLEX MODULE”), or the VIP relay.

CharacteristicsPower supply Direct currentThreshold 0.6 A < I < 3 A

Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact, provided with the Mitop. This release also includes a coil (reset) enabling remote SDE contact reset.Comment:Use of the Mitop low energy release requires adjustment of the protection relay time delay in order to ensure that the circuit breaker trips between 45-50 ms.

Releases combinations tableShunt opening MX1 1 1 1 1 1 1Shunt opening MX2 1 1Undervoltage MN 1 1Mitop 1 1 1

DE

5752

7D

E57

528

Time delay for undervoltage release (MN)

Low energy release (Mitop)

DE

5752

9

Page 43: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

41

Vacuum type switchgear Evolis 17.5 kV circuit breakerP2 stored energy operating mechanismRemote control

FunctionRemote control enables the remote opening and closing of the circuit breaker. The opening order always takes priority over the closing order.In the event of simultaneous opening and closing orders, the mechanism discharges under no load, without moving the main contacts. The circuit breaker remains in the “open” position.In the event of latched opening and closing orders, the mechanism carries out anti-pumping function as standard, by blocking the circuit breaker in the “open” position. Anti-pumping function: after opening on a fault or deliberate opening via the manual or electrical mechanism, the closing order must be interrupted then reactivated to enable reclosing of the circuit breaker.

CompositionThe remote control comprises:

an electrical motor (MCH) equipped with a “spring armed” CH limit switcha shunt closing release (XF).

Electrical motor (MCH)The electrical motor carries out the automatic rearming of the storage energy springs as soon as the circuit breaker closes. This allows instant reclosing of the device after opening. The arming lever is only used as a backup control in the case of the absence of the auxiliary power supply. An electrical motor (MCH) equipped with a “spring armed” CH limit switch.This contact indicates the “armed” position of the mechanism (springs armed).

CharacteristicsPower supply V AC 48…60, 100…130, 200…240

V DC 24, 24…30, 48, 48…60 , 100…130, 200…250Threshold 0,85 to 1.1 UrConsumption (VA or W) 180 Motor overcurrent 2 ot 3 In for 0.1 sArming time 6 s maximumOperating rate 3 cycles maximum per minuteCH contact 10 A/240 V

Shunt closing release (XF)This release allows remote closing of the circuit breaker when the control mechanism is armed. It can be permanently or briefl y supplied power.

Characteristics XFPower supply V AC 100…130, 200…250

V DC 24…30, 48…60, 100…130, 200…250Threshold XF 0.85 to 1.1 UrConsumption (VA or W) Triggering 200 (for 200 ms)

Latched 4.5

bb

Shunt closing release (XF)

DE

5752

7D

E57

530

Circuit breaker equipped with remote control

DE

5753

1

Electrical motor MCH

Page 44: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

42

Vacuum type switchgear Evolis 17.5 kV circuit breakerP2 stored energy operating mechanismIndication

“Open/closed” auxiliary position contacts (OF)These auxiliary contacts indicate the “open” or “closed” position of the circuit breaker.

Rotary type changeover contacts directly controlled by the circuit breaker mechanism.

Indicator contacts are proposed:for standard relaying applicationsfor low level control applications with plc’s or electronic circuits.

This version is compatible with Sepam series 20-40-80 units.CharacteristicsStandard delivery 4Maximum quantity 12Breaking capacity (A) Standard Min. load: 100 mA/24 VCos ϕ: 0,3 V AC 240/380 10/6 *CA12/DC12 480 10/6 *

690 6V DC 24/48 10/6 *

125 10/6 *250 3

Low level Min. load: 2 mA/15 V DCV AC 24/48 6

240 6380 3

V DC 24/48 6125 6250 3

* Standard contacts: 10 A; optional contacts: 6 A (temperature derating)

“Ready to close” PF contactThe circuit breaker is “ready to close” when shown by a mechanical indicator and a PF contact. This information simultaneously indicates that:

the circuit breaker is openthe storage energy springs are armedthere is no permanent closing orderthere is no permanent opening order caused by:a safety opening order (2nd MX or MN)keylocking of the device in the open position.

CharacteristicsStandard delivery 0Maximum quantity 1Breaking capacity (A) Standard Min. load: 100 mA/24 VCos ϕ: 0,3 V AC 240/380 5CA12/DC12 480 5

690 3V DC 24/48 3

125 0.3250 0.15

Low level Min. load: 2 mA/15 V DCV AC 24/48 3

240 3380 3

V DC 24/48 3125 0.3250 0.15

Operation counter (CDM)The operation counter is visible on the front panel. It totalizes the number of switching cycles (CO) that the device has carried out.

b

bvv

bbbbvv

DE

5753

2

Rotary type contacts (OC)

DE

5753

3

“Ready to close” PF contact

DE

5753

4

Operation counter (CDM)

Page 45: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

43

Page 46: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

44

Vacuum type switchgear Evolis HP circuit breakerPresentation

PE

5657

0

Evolis HP circuit breakers withdrawable version

Description of the deviceThe basic withdrawable version of the Evolis HP circuit breaker comprises:

the circuit breaker unit with its operating mechanism:three poles equipped with a vacuum interrupter unit an RI stored energy electrical operating mechanism.

This gives the device an opening and closing speed that is independent of the operator, for both electrical and manual orders. It enables reclosing cycles to be carried out

a front panel housing the manual operating mechanism and status indicators.the components enabling it to be withdrawable:the circuit breaker is equipped with racking arms and contact fi ngers and mounted

on a racking in/out drive device with a threaded shaft activated by a handle, including all of the safety interlock systems.

a Harting type male LV connector allows connection of the external auxiliary circuits.Each device can optionally be fi tted with:

locking of the circuit breaker in the following positions:open, by a key lock installed on the control panelracked out, by a key lock installed on the drive device.

bvv

vbv

v

bvv

Page 47: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

45

Vacuum type switchgear Evolis HP circuit breakerCharacteristics

Electrical characteristics according to IEC 62271-100Evolis HP/MCset 3

Phase to phase 240Rated voltage Ur kV 50/60 Hz 7.2 12 15Insulation level- power frequency withstand Ud kV 50 Hz 1 min 20 28 38- lightning impulse withstand Up kV peak 60 75 95Rated current Ir A 1250 – – – – – – – b – – – b

2500 – – – b – – – b – – – b

3150 b b b b b b b b b b b b

Short circuit current Isc kA 25 31.5 40 50 25 31.5 40 50 25 31.5 40 50Short time withstand current Ik/tk kA/3 s 25 31.5 40 50 25 31.5 40 50 25 31.5 40 50Short-circuit making current Ip kA peak 50 Hz 63 79 100 125 63 79 100 125 (*) v

60 Hz 65 82 104 130 65 82 104 130 (*) v

Common characteristics according to IEC 62271-100Rated switching sequence O-3 min-CO-3 min-CO b

O-0.3 s-CO-3 min-CO b

O-0.3 s-CO-15 s-CO b

Operating times Opening 48Breaking 70Closing 65

Service temperature T °C – 5 to + 40 (**)Mechanical endurance Class M2

Number of switching operations

10 000

Electrical endurance Class E2Number of switching operations at full Isc value

25 kA 10031.5 kA 5040 kA 3050 kA 30

Capacitive current breaking capacity Class C1Average relative humidity Over 24 h < 95%

Over 1 month < 90%

b Available– Not available (*) 150 kA available on request(**) Possibility up to – 25°C, consult us.

Characterisitics of Evolis HP circuit breakers in MCset cubiclesThe electrical characteristics are given on the circuit breaker designation (rating plate).

Page 48: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

46

Vacuum type switchgear Evolis HP circuit breakerRI stored energy operating mechanismPresentation

Operation of the RI stored energy operating mechanismThis gives the device an opening and closing speed that is independent of the operator whether the order is electrical or manual.The electrical control mechanism carries out reclosing cycles and is automatically recharged by a geared motor each time after closing. It consists of:

the stored energy operating mechanism which stores in springs the energy required to open and close the device

a manual lever-operated spring arming devicea geared electrical arming device which automatically re-arms the control

mechanism as soon as the circuit breaker is closed (optional)manual order devices by push buttons on the front panel of the device an electrical remote closing device containing a release with an antipumping relayan electrical opening order device comprising one or several release units which

can be of the following type:shunt openingundervoltageMitop, a low consumption release, used only with the Sepam 100 LA

protection relay.an operation counteran “open/closed” position indicator device with a mechanical indicator a device for indicating “charged” operating mechanism status by mechanical

indicator and electrical contact (optional)a module of 14 auxiliary contacts whose availability varies according

to the diagram used.

Wiring diagram (principle)

b

bb

bbb

vvv

bbb

b

PE

5582

6

M

YF +anti-pumping

Motor Shunt closingrelease+ anti-pumpingsystem

Remote control

Shunt openingrelease

Under-voltagerelease

Low energyrelease(Mitop)

NO contacts

Changeovercontact

NC contacts

Close CB

Open CB

YM

M3

Mitop

“Control mechanism armed” indicator contact

YO1 YO2

DE

5761

1EN

Page 49: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

47

Vacuum type switchgear Evolis HP circuit breakerRI stored energy operating mechanismOpening circuit

Operating mechanism

CompositionThe opening circuit can be produced using the following components:

shunt opening release (on energizing) (YO1)second shunt opening release (on energizing) (YO2)undervoltage release (YM)low energy release (Mitop).

Note: see the table of the releases’ combinations page 49.

Shunt opening release (YO1 and YO2)Energizing this unit causes instant opening of the circuit breaker.

CharacteristicsPower supply V AC (50 Hz) 110, 220

V AC (60 Hz) 120V DC 24, 48, 110, 125, 220

Threshold V AC 0.85 to 1.1 UrV DC 0.7 to 1.1 Ur

Consumption V AC 160 VAV DC 50 W

Undervoltage release (YM)This release unit causes the systematic opening of the circuit breaker when its supply voltage drops below a value less than 35% of the rated voltage, even if this drop is slow and gradual. It can open the circuit breaker between 35% and 70% of its rated voltage. If the release unit is not supplied power, manual or electrical closing of the circuit breaker is impossible. Closing of the circuit breaker is compulsory when the supply voltage of the release unit reaches 85% of its rated voltage.

CharacteristicsPower supply V AC (50 Hz) 110, 220

V AC (60 Hz) 120V DC 24, 48, 110, 125, 220

Threshold Opening 0.35 to 0.7 UrClosing 0.85 Ur

Consumption Triggering V AC 400 VAV DC 100 W

Latched V AC 100 VAV DC 10 W

Low energy release (Mitop)This specifi c release unit comprises a low consumption unit and is specifi cally used for Sepam 100LA self-powered relays.

CharacteristicsPower supply Direct current Threshold 0.6 A < I < 3 A

Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact.

bbbb

DE

5312

0D

E53

121

DE

5312

2

Shunt opening release (1)

Undervoltage release (2)

Low energy release (3)

DE

5761

2EN

(1) or (3)(2)

Page 50: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

48

Vacuum type switchgear Evolis HP circuit breakerRI stored energy operating mechanismRemote control

DE

5312

4D

E53

125

Operating mechanism

Electrical motor and gearing (4)

Shunt closing release (5)

Operation counter (6)

DE

5312

0

FunctionRemote control enables the remote opening and closing of the circuit breaker.

CompositionThe remote control mechanism comprises:

an electrical motor with gearing a shunt closing release (YF) combined with an anti-pumping devicean operation counter.

Electrical motor with gearing (M)The electrical motor arms and re-arms the stored energy unit as soon as the circuit breaker is closed. This allows the instant closing of the device after opening. The arming lever is only used as a back-up operating mechanism in the case of any auxiliary power supply. The M3 contact indicates the end of arming operations.

CharacteristicsPower supply V AC 48…60, 110…127, 220…250

V DC 24 …32, 48…60, 110…127, 220…250Threshold V AC/V DC 0.85 to 1.1 UrConsumption V AC 380 VA

V DC 380 W

Shunt closing release (YF)This allows the remote closing of the circuit breaker when the operating mechanism is armed.

CharacteristicsPower supply V AC (50 Hz) 110, 220

V AC (60 Hz) 120V DC 24, 48, 110, 125, 220

Threshold V AC 0.85 to 1.1 UrV DC 0.85 to 1.1 Ur

Consumption V AC 160 VAV DC 50 W

The anti-pumping relay enables the guaranteeing of opening priority in the case of a permanent closing order. This therefore avoids the device being caught in a uncontrolled opening-closing loop.

Operation counterThe operation counter is visible on the front panel.It displays the number of switching cycles (CO) that the device has carried out.

bbb

DE

5760

4

Page 51: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

49

Vacuum type switchgear Evolis HP circuit breakerRI stored energy operating mechanismIndication

Operating mechanism

“Open/closed” auxiliary contacts The number of contacts available depends on the options chosen on the operating mechanism.In the basic confi guration, the circuit breaker’s operating mechanism comprises a total of:

5 normally closed contacts (NC)5 normally open contacts (NO)1 changeover contact (CHG).

The usage procedure for auxiliary contacts is given in the following table:

OptionsNC contact NO contact

Shunt opening release (each one) 0 1Undervoltage release 0 0Low energy release (Mitop) 0 0

n order to know the fi nal number of available contacts, you must deduct the total number of contacts included in the circuit breaker (5 NC + 5 NO + 1 CHG), the number of contacts used given in the table above.E.g.: a circuit breaker equipped with a remote control and a shunt trip unit has the following available contacts: 5 NC + 4 NO + 1 CHG. With a undervoltage release instead of the shunt trip, this circuit breaker would have the following available contacts: 5 NC + 5 NO + 1 CHG.

Shunt opening release combination1st release

2nd release

Shunt opening release YO1

Undervoltage release YM

Mitop

Without 5NC + 4NO + 1CHG 5NC + 5NO+ 1CHGShunt opening release YO2

5NC + 3NO + 1CHG 5NC + 4NO+ 1CHG 5NC + 4NO + 1CHG

Undervoltage release YM

5NC + 4NO + 1CHG 5NC + 5NO + 1CHG

Mitop 5NC + 4NO + 1CHG 5NC + 5NO + 1CHG

bbb

DE

5312

9

Auxiliary contacts (7)

DE

5761

3

Page 52: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

50

Vacuum type switchgear CTV1 contactorPresentationCharacteristics

DescriptionThe vacuum type contactor comprises:

3 vacuum interrupters (breaking),an electromagnetic control unit which can be of:magnetic latching type,mechanical latching type.upstream and downstream connection terminals for the power circuit,mechanical contactor locking in the open position in order to avoid racking out

or racking in with the contacts closed,3 HPC fuses with a striker and auxiliary contacts to trip the contactor,the possibility of installing a transformer to provide an independent power supply

for the contactor control unit (option),an indicator on the front panel to show the contactor position,a switching operation counter,auxiliary contacts,interchangeable with the contactors in the Rollarc range.

Electrical characteristicsRated voltage kV (50/60 Hz) 7.2Insulation voltage kV r ms 50 Hz - 1 min 20

kV impulse 1.2/50 µs 60Operating current A 250 (1)

Rated current A 400Short time withstand current

kA r ms 2 s 8kA r ms 12 s 4kA r ms 30 s 2.4

Mechanical endurance (number of operations) 2 500 000 250 000 (2)

Electrical endurance (number of operations) 250 000 250 000 (2)

(1) For greater values: please consult us.(2) Version with mechanical latching.

Control unitSupply voltage (3) V DC: 110, 120 and 220 VV AC: 100, 110, 120 and 220 Vpossible variations: +10% –15%

(3) Possibility of supplying power through an auxiliary transformer, optional (see page 32).

ConsumptionClosing is achieved via the inrush coils. The latching coils are inserted in the circuit at the end of travel. Under 100-110 V Inrush LatchedWith magnetic latching 5 A 0.6 AWith mechanical latching 5.5 A —

Auxiliary contacts The auxiliary contacts are of changeover type with a common point. The following are available :

3 NO + 3 NC for the magnetic latching version,2 NO + 2 NC for the mechanical latching version.

Contact characteristics Operating voltage Max. 480 V, min. 48 VRated current 10 ABreaking capacity: V DC: 60 W (L/R 150 ms)

V AC: 700 VA (cos ϕ 0.35)

bbvvbb

bb

bbbb

vv

PE

5656

7

Page 53: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

51

50

A6

3 A

80

A

16

0 A

12

5 A

20

0 A

25

0 A

100

50 A

250 A

200 A160 A125 A

63 A80 A

Is = Ik 2

Ia = 1.8 Ik

2

100

Vacuum type switchgear CTV1 contactorCharacteristics (cont.)

DE

5747

0D

E57

473

DE

5747

2D

E57

471

Figure 2

Figure 1

Figure 3

Figure 4

Trip curvesThe trip curves for Fusarc CF (fi gure 1) and Ferraz (fi gure 2) fuses are shown above. These are the average curves with an rms current value tolerance I ± 10%.

Limitation curvesFusarc CF (fi gure 3) and Ferraz (fi gure 4) fuses have current limiting capacity. These curves give the maximum value of the limited breaking current Ic (in kA peak), as a function of the value Ip (in kA rms) of the presumed current that would be created if there were no protection. For further details, ask for the fuse catalogues.

Maximum switchable powerCalculation assumptions (motor)

ratio between starting current Id and maximum current In: Id/In = 5 ± 20%,power factor x effi ciency

0.88 x 0.9 = 0.792 for 300 < P < 600 kW0.9 x 0.92 = 0.828 for 600 < P < 1100 kW0.92 x 0.94 = 0.865 for 1100 < P < 5000 kW,

starting time < 10 s,starts per hour ≤ 3 according to IEC 60644.

Operating voltage (kV) Direct starting motor (kW)with 315 A fuses

Transformer (kVA)with 315 A fuses

Capacitor(kvar)with 315 A fuses

3.3 1170 1130 10004.16 1480 1420 12605 1780 1710 15205,5 1960 1880 16706 2130 2050 18206.6 2350 2250 2000

FusesThe fuses used are of the Fusarc CF or Ferraz type (Standard IEC 60282.1 and DIN 43625) with high breaking capacity. Substantial fault current limitation reduces the electrodynamic stresses on the load-side components (contactor, cables, CT, etc).A “blown fuse” device is used to open the three poles of the contactor.

Rated voltage (kV) 7.2Max. fuse rating (A) 315 (*)Breaking capacity (kA) 50* Higher values, please consult us.

Schematic diagramsMechanical latching contactor

DE

5747

4

DU

YF

X61

X20 32

21

33 4 1 3

6

5

4 1

2

2

3

10 21

YDXU

M2

- C- C

M1

+ C

Sepam

XE

XU

XEXE

verrouillage

enclenchement

closing

interlock

S4

+ C

S61

P61 000O

FU1K1

K1

FU1

FU1

S61K1

K1

K1

40 9 2036

7

Magnetic latching contactor

DE

5747

5

- C

M2

- C

M1

+ C + C

Sepam

XU XE

XE

XUXE

K1

P61

FU1

X61

X20 32

22

2122

21

33 4 1 3

4

5

6

1

2

2

3

K1

000ODU

YF

verrouillage

enclenchement

closing

interlock

S4: release push buttonYD: release coilDU: control componentP61: switching operation counterYF: closing coil

K1: MV contactorS61: latching contactFU1: MV fusesXE: auxiliary control relayXU: auxiliary relay

bb

bb

Page 54: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

52

Description of the deviceThe LF circuit breaker consists of:

the circuit breaker unit with its operating mechanism:3 poles integrated in a “sealed pressure system” type insulating enclosure.

The sealed assembly is fi lled with SF6 gas at low relative pressure (0.15 Mpa/1.5 bars) and equipped with a pressure switch

an RI stored energy electrical operating mechanism.This gives the device an opening and closing speed that is independent of the operator, for both electrical and manual orders. It enables reclosing cycles to be carried out

a front panel housing the manual operating mechanism and status indicators.the components enabling it to be withdrawable:the circuit breaker is equipped with racking arms and contact fi ngers and mounted

on a racking in/out drive device with a threaded shaft activated by a handle, including all of the safety interlock systems.

a Harting type male LV connector allows connection of the external auxiliary circuits.Each device can optionally be fi tted with:

locking of the circuit breaker in the following positions:open, by a key lock installed on the control panelracked out, by a key lock installed on the drive device.

Specifi c applicationsProtection of generators and power station auxiliariesAll circuit breakers in the LF range break short circuit currents with an asymmetry of at least 30%. In cases where the network constant X/R is greater than 45 ms, the asymmetry to be broken is higher; this is often the case of circuit breakers protecting nuclear or thermal power station auxiliaries or circuit breakers that are close to generator sets or large transformers. Specifi c tests have been carried out:Circuit breakers kV kA Asymmetry

LF2 7.2 43.5 50%LF3 7.2 43.5 50%

12 40 50%17.5 25 100%

Switching and protection of capacitor banksLF range circuit breakers are particularly well suited to switching and protection of capacitor banks; they are classed C2 according to standard IEC 62271-100. Tests carried out according to the standard for breaking at 400 A with making and breaking cycles in case of a capacitor bank with a making current of 20 kA.Additional tests have been carried out: please consult us.

bv

v

vbv

v

bvv

PE

5656

6SF6 type switchgear LF circuit breaker

Presentation

Page 55: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

53

SF6 type switchgear LF circuit breakerCharacteristics

Electrical characteristics according to IEC 62271-100LF1/MCset 1 LF2/MCset 2

Rated voltage Ur kV 50/60 Hz 7.2 12 7.2 12 17.5Insulation voltage- power frequency withstand Ud kV 50 Hz 1mn (1) 20 28 20 28 38- lightning impulse withstand Up kV peak 60 75 60 75 95Rated current Ir A 630 b b b b b b b b b

1250 b b b b b b b b b

Short circuit current Isc kA 25 31.5 25 31.5 40 50 40 25 31.5Short time withstand current Ik/tk kA/3 s 25 31.5 25 31.5 40 50 (2) 40 25 31.5Short-circuit making current Ip kA peak 50 Hz 63 79 63 79 100 125 100 63 79

60 Hz 65 82 65 82 104 130 104 65 82Rated switching sequence O-3 mn-CO-3 mn-CO b b b b b b b b b

O-0.3 s-CO-3 mn-CO b b b b b b b b b

O-0.3 s-CO-15 s-CO b b b b b b b b b

LF3/MCset 3Rated voltage Ur kV 50/60 Hz 7.2 12 17.5Insulation voltage- power frequency withstand Ud kV 50 Hz 1mn (1) 20 28 38- lightning impulse withstand Up kV peak 60 75 95Rated current Ir A 1250 – – – – – – – b – – b

2500 b b b b b b b b b b b

3150 – b b b – b b b b b b

4000 (4) – – – b – – – b – – b

Short circuit current Isc kA peak 25 31.5 40 50 25 31.5 40 50 25 31.5 40Short time withstand current Ik/tk kA/3 s 25 31.5 40 50 25 31.5 40 50 (2) 25 31.5 40Short-circuit making current Ip kA 50 Hz 63 79 100 125 63 79 100 125 63 79 100

60 Hz 65 82 104 130 65 82 104 130 65 82 104Rated switching sequence O-3 mn-CO-3 mn-CO b b b b b b b b b b b

O-0.3 s-CO-3 mn-CO b b b b b b b b b b –O-0.3 s-CO-15 s-CO b b b b b b b b b b –

Specifi c applications according to IEC 62271-100Operating times Opening ms 48 ms

Breaking ms 70 msClosing ms 65 ms

Service temperature T °C – 25 to + 40Mechanical endurance Class M2

Number of switching operations

10 000

Electrical endurance Class E2Capacitive current breaking capacity Class C2

(1) Ud 42 kV 50 Hz, 1 min possible.(2) for In ≤ 1250 A, the rated short-circuit breaking duration (tk): 1 s.(3) For other values, please consult us.(4) With fan.b Available.– Not available.

Characteristics of LF circuit breakers in MCset cubiclesThe electrical characteristics are given on the circuit breaker designation (rating plate).

Page 56: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

54

SF6 type switchgear LF circuit breakerRI stored energy operating mechanismPresentation

Operation of the RI stored energy operating mechanismThis gives the device an opening and closing speed that is independent of the operator whether the order is electrical or manual.The electrical control mechanism carries out reclosing cycles and is automatically recharged by a geared motor each time after closing. It consists of:

the stored energy operating mechanism which stores in springs the energy required to open and close the device

a manual lever-operated spring arming devicea geared electrical arming device which automatically re-arms the control

mechanism as soon as the circuit breaker is closed (optional)manual order devices by push buttons on the front panel of the device an electrical remote closing device containing a release with an antipumping relayan electrical opening order device comprising one or several release units which

can be of the following type:shunt openingundervoltageMitop, a low consumption release, used only with the Sepam 100 LA

protection relay.an operation counteran “open/closed” position indicator device with a mechanical indicator a device for indicating “charged” operating mechanism status by mechanical

indicator and electrical contact (optional)a module of 14 auxiliary contacts whose availability varies according

to the diagram useda single contact pressure switch is activated when the gas pressure exceeds

0.1 MPa (relative pressure: 1 bar).

Wiring diagram (principle)

b

bb

bbb

vvv

bbb

b

b

PE

5582

6

Pressureswitch

NO contacts

Changeovercontact

NC contacts

M

YF +anti-pumping

Motor Shunt closingrelease+ anti-pumpingsystem

Remote control

Shunt openingrelease

Under-voltagerelease

Low energyrelease(Mitop)

Close CB

Open CB

YM

M3

Mitop

“Control mechanism armed” indicator contact

YO1 YO2

DE

5744

5EN

Page 57: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

55

SF6 type switchgear LF circuit breakerRI stored energy operating mechanismOpening circuit

CompositionThe opening circuit can be produced using the following components:

shunt opening release (on energizing) (YO1)second shunt opening release (on energizing) (YO2)undervoltage release (YM)low energy release (Mitop).

Note: see the table of the releases’ combinations page 57.

Shunt opening release (YO1 and YO2)Energizing this unit causes instant opening of the circuit breaker.

CharacteristicsPower supply V AC (50 Hz) 48, 110, 220

V AC (60 Hz) 120, 240V DC 24, 30, 48, 60, 110, 125, 220

Threshold V AC 0.85 to 1.1 UrV DC 0.7 to 1.1 Ur

Consumption V AC 160 VAV DC 50 W

Undervoltage release (YM)This release unit causes the systematic opening of the circuit breaker when its supply voltage drops below a value less than 35% of the rated voltage, even if this drop is slow and gradual. It can open the circuit breaker between 35% and 70% of its rated voltage. If the release unit is not supplied power, manual or electrical closing of the circuit breaker is impossible. Closing of the circuit breaker is compulsory when the supply voltage of the release unit reaches 85% of its rated voltage.

CharacteristicsPower supply V AC (50 Hz) 48, 110, 220

V AC (60 Hz) 120, 240V DC 24, 30, 48, 60, 110, 125, 220

Threshold Opening 0.35 to 0.7 UrClosing 0.85 Ur

Consumption Triggering V AC 400 VAV DC 100 W

Latched V AC 100 VAV DC 10 W

Low energy release (Mitop)This specifi c release unit comprises a low consumption unit and is specifi cally used for Sepam 100LA self-powered relays.

CharacteristicsPower supply Direct current Threshold 0.6 A < I < 3 A

Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact.

bbbb

Operating mechanism

DE

5312

0D

E53

121

DE

5312

2

Shunt opening release (1)

Undervoltage release (2)

Low energy release (3)

DE

5761

2EN

(1) or (3)(2)

Page 58: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

56

SF6 type switchgear LF circuit breakerRI stored energy operating mechanismRemote control

DE

5312

4D

E53

125

Operating mechanism

Electrical motor and gearing (4)

Shunt closing release (5)

Operation counter (6)

FunctionRemote control enables the remote opening and closing of the circuit breaker.

CompositionThe remote control mechanism comprises:

an electrical motor with gearing a shunt closing release (YF) combined with an anti-pumping devicean operation counter.

Electrical motor with gearing (M)The electrical motor arms and re-arms the stored energy unit as soon as the circuit breaker is closed. This allows the instant closing of the device after opening. The arming lever is only used as a back-up operating mechanism in the case of any auxiliary power supply. The M3 contact indicates the end of arming operations.

CharacteristicsPower supply V AC 48…60, 110…127, 220…250

V DC 24 …32, 48…60, 110…127, 220…250Threshold V AC/V DC 0.85 to 1.1 UrConsumption V AC 380 VA

V DC 380 W

Shunt closing release (YF)This allows the remote closing of the circuit breaker when the operating mechanism is armed.

CharacteristicsPower supply V AC (50 Hz) 48, 110, 220

V AC (60 Hz) 120, 240V DC 24, 30, 48, 60, 110, 125, 220

Threshold V AC 0.85 to 1.1 UrV DC 0.85 to 1.1 Ur

Consumption V AC 160 VAV DC 50 W

The anti-pumping relay enables the guaranteeing of opening priority in the case of a permanent closing order. This therefore avoids the device being caught in a uncontrolled opening-closing loop.

Operation counterThe operation counter is visible on the front panel.It displays the number of switching cycles (CO) that the device has carried out.

bbb

DE

5312

0D

E57

604

Page 59: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

57

SF6 type switchgear LF circuit breakerRI stored energy operating mechanismIndication and locking/interlocking

DE

5749

1

Operating mechanism

DE

5312

9

Auxiliary contacts (7)

DE

5312

7

Keylocking kit (8)

“Open/closed” auxiliary contacts The number of contacts available depends on the options chosen on the operating mechanism.In the basic confi guration, the circuit breaker’s operating mechanism comprises a total of:

5 normally closed contacts (NC)5 normally open contacts (NO)1 changeover contact (CHG).

The usage procedure for auxiliary contacts is given in the following table:

OptionsNC contact NO contact

Shunt opening release (each one) 0 1Undervoltage release 0 0Low energy release (Mitop) 0 0

In order to know the fi nal number of available contacts, you must deduct the total number of contacts included in the circuit breaker (5 NC + 5 NO + 1 CHG), the number of contacts used given in the table above.E.g.: a circuit breaker equipped with a remote control and a shunt trip unit has the following available contacts: 5 NC + 4 NO + 1 CHG. With a undervoltage release instead of the shunt trip, this circuit breaker would have the following available contacts: 5 NC + 5 NO + 1 CHG.

Shunt opening release combination1st release

2nd release

Shunt opening release YO1

Undervoltage release YM

Mitop

Without 5NC + 4NO + 1CHG 5NC + 5NO+ 1CHG 5NC + 5NO + 1CHGShunt opening release YO2

5NC + 3NO + 1CHG 5NC + 4NO+ 1CHG 5NC + 4NO + 1CHG

Undervoltage release YM

5NC + 4NO + 1CHG 5NC + 5NO + 1CHG

Mitop 5NC + 4NO + 1CHG 5NC + 5NO + 1CHG

Locking the circuit breaker in the “open” positionThis key-operated device allows the circuit breaker to be locked in the “open” position. The circuit breaker is locked in the open position by blocking the opening push button in the “engaged” position.Locking is achieved using a Profalux or Ronis captive key type keylock.

bbb

Page 60: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

58

SF6 type switchgear Rollarc contactorPresentation

DescriptionThree main poles located in the pressurised enclosure,Electromagnetic operating mechanism with:magnetic latching for Rollarc 400,mechanical latching for Rollarc 400D.Upstream and downstream terminals for power circuit connections,Pressure switch equipped with a NO contact for continuous monitoring of SF6,Mechanical interlocking of the contactor in the open position to prevent racking in

or out with the contacts closed,3 HPC fuses with striker pin and auxiliary contact to trip the contactor.

Auxiliaries diagram

Operating mechanism for Rollarc 400 contactors

DE

5748

3

Operating mechanism for Rollarc 400D contactors

DE

5748

4

bbvvbbb

b

PE

5656

8

FU1 MV fusesFUBT LV fuseK1 R400 AC MV contactorP61 Operation counterS61 Locking contact activated

by the pretrip push button and during racking in/out operations

SQ1 Contactor limit switch X20 LV connecter, 42 pins + earthX51 Control plateX61 Contactor terminal blockXAP Instantaneous auxiliary relayXE Instantaneous auxiliary control relayXU 0.6 s time delay auxiliary relayYD Shunt trip coilYF Closing coilsYM Latching coilS4 Trip button

Page 61: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

59

SF6 type switchgear Rollarc contactorCharacteristics

Fig. 1

Fig. 2

Electrical characteristics of the Rollarc R400/R400D (1) in MCset cubicles

Rated voltage Dielectric strength Max. operating current

Rated contactor current

Fuse breaking capacity (2)

Short time withstand current (3)

50 Hz 1 min Impulse 1.2/50 µs(kV) (kV r ms) (kV peak) (A) (A) (kA r ms) (kA r ms) (kA peak)

7.2 20 60 250 400 50 50 12512 28 60 200 400 50 50 125

(1) Rollarc 400: without mechanical latching. Rollarc 400D: with mechanical latching.(2) For operating voltages of 3 to 12 kV.(3) Limited by fuses.

Maximum switchable powerCalculation assumptions (motor)

Ratio between starting current Id and maximum current In: Id/In = 5 ± 20%,Power factor x effi ciency

0.88 x 0.9 = 0.792 for 300 ≤ P < 600 kW0.9 x 0.92 = 0.828 for 600 ≤ P < 1100 kW0.92 x 0.94 = 0.865 for 1100 ≤ P < 5000 kW,

Starting time < 10 s,Starts per hour ≤ 3 according to IEC 60644.

Operating voltage (kV)

Direct starting motor (kW) with 315 A fuses

Transformer(kVA) with 315 A fuses

Capacitor (kvar) with 315 A fuses

3.3 1170 1430 10004.16 1480 1800 12605 1780 2160 15205.5 1960 2380 16706 2130 2600 18206.6 2350 2800 200010 (fus. 200 A) 2000 2250 2000

Operating schemesTemporary service or periodic serviceThe two curve systems (Fig. 1 and 2) can be used to determine the maximum current surges accepted by the Rollarc 400 contactor, in temporary or periodic service.

Temporary service: knowing the steady state current Ip, we determine the maximum duration Ts of a current surge Is from graph 1 (Fig. 2).

Periodic service: knowing 3 of the following 4 parameters:overcurrent Is,overcurrent time Ts,cooling current Ir,cooling time Tr.

We determine the 4th parameter using graph 2 (Fig. 1 and 2).Operating time

Opening time 20 to 35 ms,Arcing time: < 20 ms,Closing time: 80 to 120 ms.

bb

bb

b

bvvvv

bbb

DE

5747

7D

E57

478

Page 62: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

60

50

A6

3 A

80

A

16

0 A

12

5 A

20

0 A

25

0 A

100

50 A

250 A

200 A160 A125 A

63 A80 A

Is = Ik 2

Ia = 1.8 Ik

2

100

SF6 type switchgear Rollarc contactorCharacteristics (cont.)

FusesThe fuses used are of the FUSARC CF or FERRAZ type (Standard IEC 60282.1 and DIN 43625) with high breaking capacity.Substantial fault current limitation reduces the electrodynamic stresses on the load-side components (contactor, cables, CT, etc).A “blown fuse” device is used to open the three poles of the contactor.Rated voltage (kV) 7.2 12Max. fuse rating (A) 315 250*Breaking capacity (kA) 50 50

* please consult us

Trip curvesThe trip curves for FUSARC CF (Fig. 1) and FERRAZ (Fig. 2) fuses are shown opposite.These are the average curves with an rms current value tolerance ± 10%.Limitation curvesFUSARC CF (Fig. 3) and FERRAZ (Fig. 4) fuses have current limiting capacity.These curves give the maximum value of the limited breaking current Ic (in kA peak), as a function of the value Ip (in kA rms) of the presumed current that would be created if there were no protection. For further details ask for the fuse catalogues.

Operating mechanismSupply voltage (1)

DC: 48, 110, 127 and 220 VAC: 50, 100, 110, 127 and 220 VAcceptable variations: +10% –15%

Rollarc 400 contactorThe contactor is closed by the pick-up coils.The latching coils are inserted in the circuit at the end of the stroke of the contactor.Consumption Pick-up LatchedDC 1050 W 30 WAC 900 VA 30 VA

Rollarc 400D contactorThe contacts are mechanically latched in the closed position. They are opened by a shunt trip release which releases the latching.Consumption Pick-up coil (2) Shunt tripDC 1050 W 80 WAC 900 VA 100 VA

(1) Optional supply possible by auxiliary transformer (see page 32).(2) Supply time < 0.12 s.

Auxiliary contactsAuxiliary contacts are of the common point changeover type. The following are available:

9 contacts for the Rollarc 400,8 contacts for the Rollarc 400D.

Contact characteristics: Rated current: 10 ABreaking capacity: DC (L/R ≤ 0.01 s): 2 A at 110 V

AC (cos.ϕ ≥ 0.3): 10 A at 220 V

b

b

bb

DE

5747

0D

E57

473

DE

5747

2D

E57

471

Figure 2

Figure 1

Figure 3

Figure 4

Trip curvesThe trip curves for Fusarc CF (fi gure 1) and Ferraz (fi gure 2) fuses are shown above. These are the average curves with an rms current value tolerance I ± 10%.

Limitation curvesFusarc CF (fi gure 3) and Ferraz (fi gure 4) fuses have current limiting capacity. These curves give the maximum value of the limited breaking current Ic (in kA peak), as a function of the value Ip (in kA rms) of the presumed current that would be created if there were no protection. For further details, ask for the fuse catalogues.

Page 63: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

61

Page 64: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

62

SF6 type switchgear DI switch cubiclePresentation

E74

222 Switch

The three rotating contacts are placed in an enclosure fi lled with gas to a relative pressure of 0.04 MPa (0.4 bars).The system offers maximum operating reliability.Gas tightnessThe SF6 fi lled enclosure is of the “sealed pressure system type”. Sealing tightness is always checked in the factory.Safety

The switch may be in one of three positions: “closed”, “open” or “earthed”, giving a natural interlocking system that prevents operator error.

Moving contact rotation is driven by a fast acting mechanism that is independent of the operator.

The device combines the breaking and disconnecting functions.The SF6-enclosed earthing switch has a short-circuit making capacity

in compliance with standards.Breaking principleThe outstanding qualities of SF6 gas are used to extinguish the electrical arc. To increase cooling of the arc, a relative movement is created between the arc and the gas. The arc strikes when the fi xed and moving contacts separate. The combination of the current and a magnetic fi eld created by a permanent magnet causes the arc to rotate around the fi xed contact, extending and cooling it until it is extinguished at current zero point. The distance between the fi xed and moving contacts is then suffi cient to withstand the recovery voltage.This system is both simple and dependable, and it provides improved electrical endurance due to very low wear of contacts.

DE

5748

6

2 6

5431

1 Enclosure2 Cover3 Operating shaft4 Fixed contact5 Moving contact6 Seal

DE

5512

2

Contacts closed Contacts open Contacts earthed

b

b

bb

Page 65: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

63

SF6 type switchgear DI switch cubicleCharacteristics

0414

97R

0414

96R

Operating mechanism and auxiliariesCI2 double function operating mechanism

Switch function:independent closing in two steps:operating mechanism recharged by a hand lever or motor,stored energy released by a push button (I) or trip unit,independent opening by push button (O) or trip unit.Earthing switch function:independent closing by a hand lever.

Operating energy is provided by the compression of a spring which causes the contacts to close or open after the neutral point is passed.

Auxiliary contacts: switch (2 O + 2 C),switch (2 O + 3 C) and earthing switch (1 O + 1 C),switch (1 C) and earthing switch (1 O + 1 C) if motor option.Motor option Opening release:shunt, undervoltage (option).Closing release: shunt trip.Fuse blown release: any fuse blown trips the opening of the switch.

Motor option and releasesUn DC AC (50 Hz) (1)

Supply (V) 24 48 110 125 220 120 230Motor option

(W) 200(VA) 200(s) < 7 < 7

Opening releasesShunt (W) 200 250 300 300 300

(VA) 400 750Undervoltage Pick-up (W) 160

(VA) 280 550 Latched (W) 4

(VA) 50 40Closing releases

Shunt (W) 200 250 300 300 300(VA) 400 750

(1) Please consult us for other frequencies.

bv--vbv

bvvvbbvvbb

Page 66: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

64

SF6 type switchgear DI switch cubicleFuses

Fuse ratings for MCset protection units depend, among other things, on the following criteria:

service voltagetransformer ratingfuse technology (manufacturer).

Different types of fuses with medium loaded striker maybe installed: Solefuse: fuses as per standard UTE NCF 64.210Fusarc CF: fuses as per IEC recommendation 60.282.1 and DIN dimensions 43.625.

For fuse-switch combination unit, refer only to the selection table and reference list of fuses. For all other type of fuses, consult us.Example: for the protection of a 400 kVA transformer at 22 kV, select either Solefuse fuses rated 16 A or Fusarc CF fuses rated 25 A.

Fuse selection tableRating in A. No overload at –5°C < t < 40°C. Please consult us for overloads and operation over 40°C for France Transfo oil immersed type transformers.

bbb

bb

Type of fuse

Service voltage (kV)

Transformer rating (kVA) Rated voltage (kV)

25 50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500

Solefuse (UTE NFC standards 13.100, 64.210)20 6.3 6.3 6.3 6.3 16 16 16 16 43 43 43 43 43 63 24

Solefuse (general case, UTE NFC standard 13.200)20 6.3 6.3 6.3 6.3 16 16 16 16 31.5 31.5 31.5 43 43 63 2422 6.3 6.3 6.3 6.3 16 16 16 16 16 31.5 31.5 31.5 43 63 63

Fusarc CF and SIBA (1) (general case according to IEC 62271-105)20 6.3 6.3 10 10 16 16 25 25 31.5 40 40 50 50 63 80 100 (1) 125 (1) 2422 6.3 6.3 10 10 10 16 20 25 25 31.5 40 40 50 50 80 80 100 (1)

(1) = SIBA fuses

Fuses dimensionsSolefuse (UTE standards)

DE

5746

6 ø 55

450 23

ø 6

35 35

Ur (kV)

Ir(A)

L(mm)

Ø(mm)

Weight(kg)

24 6.3 to 63 450 55 2

Fusarc CF

DE

5746

7 ø 6ø 45 Ø

33L 23

33

Ur (kV)

Ir(A)

L(mm)

Ø(mm)

Weight(kg)

24 6.3 442 50.5 1.610 442 50.5 1.616 442 50.5 1.620 442 50.5 1.625 442 57 2.231.5 442 57 2.240 442 57 2.250 442 78.5 4.163 442 78.5 4.180 442 86 5.3

SIBA

DE

5746

7 ø 6ø 45 Ø

33L 23

33

Ur (kV)

Ir(A)

L(mm)

Ø(mm)

Weight(kg)

24 100 442 85 5.4

125 442 85 5.4

Page 67: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

65

Installation Extraction withdrawable partsD

E57

582

DE

5748

5

Extraction tableAdaptable to 3 cubicle widths, this extraction table enables:

the withdrawable part to be removed from the cubicle,the withdrawable part to be fi tted into the cubicle.

Extraction and lowering tool - optionAdaptable to 3 cubicle widths, this extraction tool enables:

the withdrawable part to be removed from the cubicle,the withdrawable part to be introduced into the cubicle,the withdrawable part to be lowered to the ground,the withdrawable part to be lifted from the ground.

Racking handleThls handle enables:

the withdrawable part to be racked in/out,the earthing switch to be open/closed.

Marine applicationExtraction and lowering tool - optionAdaptable to 3 cubicle widths, this extraction tool enables:

the withdrawable part to be removed from the cubicle,the withdrawable part to be introduced into the cubicle,the withdrawable part to be lowered to the ground,the withdrawable part to be lifted from the ground.

bb

bbbb

bb

bbbb

DE

5746

8D

E57

469

Page 68: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

66

DE

5748

7

DE

5748

8

500

200

570 570 900 900 900 900 570 570 570 500

1520 (3) - 1720 (4)

2500 2800(1) (1)(5)

1100

810 A420

200 1550

(2)

(1)B

Line up switchboard (2 supplies cubicles and 1 bussection)

Civil engineering with utility space

2 feeders cubicle AD1

Incomer cubicle AD3

Bussection cubicles CL3/GL3

Incomer cubicle AD3

3 feeders cubicle AD1

Roomentrance

(1) Minimum dimensions to be complied with when installing the MCset switchboard.(2) Minimum dimensions to be defi ned according to the cable bending radius.(3) Operating distance.(4) Distance needed to extract a functional unit from the switchboard without moving the other units.(5) Provide an exhaust tunnel above the switchboard when the room height is less than 4 metres (see page 12).A anchor pointB adjustment point

Note: for further information, refer to the civil engineering, user and instruction manual.

Installation Implementation examplesMCset 17.5 line up switchboard

Page 69: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

67

DE

5710

9

Civil engineering with utility space

1520 (3) - 1720 (4)

2500 2800(2) (2)(5)

1200

425825

2081425

804

MCset

(1)

992

Motorpact

Roomentrance

Installation Implementation examplesMCset/Motorpact transition switchboard

(1) Minimum dimensions to be defi ned according to the cable bending radius.

Note for lined up switchboard with MCset(2) Minimum dimensions to be complied with when installing the MCset switchboard.(3) Operating distance.(4) Distance needed to extract a functional unit from the switchboard without moving the other units.(5) Provide an exhaust tunnel above the switchboard when the room height is less than 4 metres.

Note: for further information, refer to the civil engineering, user and instruction manual.

DE

5749

0

Transition switchboard (2 supplies cubicles and 1 bussection)

375 375 375 375 375 375 375 375500 500900 900 900 900

200

804

Transitioncubicle

3 feeders cubicle Motorpact

Incomer cubicle AD3

3 feeders cubicle Motorpact

Bussection cubicles CL3/GL3

Incomer cubicle AD3

Transitioncubicle

Page 70: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

68

E72

901R Switchgear resistance to ageing in a substation depends on

3 key factorsThe need for correctly made connections

New cold connecting technologies offer easy installation and favour durability in time. Their design means they can be used in polluted environments with harsh atmospheres.

The impact of relative humidityThe installing of a heating element is essential in climates with high relative humidities and signifi cant temperature differentials.

Ventilation controlThe dimensions of air vents must be appropriate for the dissipated energy in the substation. They must only sweep across the transformer environment.Cold connected terminalsSchneider Electric’s experience has led it to favour this technology wherever possible for optimum durability. The maximum acceptable cable cross-section for standard assemblies are:

630 mm2 for incomer or feeder cubicles with single-pole cables,400 mm2 for incomer or feeder cubicles with three-pole cables,95 mm2 for transformer protection cubicles with fuses.

Access to the compartment is only possible when the earthing switch is closed.Tightening torques for cables will be attained using a dynamo wrench set to 50 mN.

Dry, single pole cableShort end piece, cold connectable Performance 3 to 17.5 kV - 400 A - 2500 - 3150 A - 4000 ACross section mm2 50 to 630 mm2

Supplier All suppliers of cold connectable terminals: Silec, 3M, Pirelli, Raychem...

Number of cables 1 to 8 per phaseComments For greater cross-section and number of cables, please consult us

Dry, three-pole cableShort end piece, cold connectable Performance 3 to 17.5 kV - 400 A - 2500 - 3150 A - 4000 A (2)

Cross section mm2 50 to 240 mm2

Supplier All suppliers of cold connectable terminals: Silec, 3M, Pirelli, Raychem...

Number of cables 1 to 4 per phaseComments For greater cross-section and number of cables, please consult us

Connection possibilities using dry cables Number of cables AD1 AD1

contactorAD2 AD3 DI2

1 single per phase b (1) b (1) b (1) b

2 single per phase b (1) b (1) b (1) b

3 single per phase b b b b

4 single per phase b

1 three per cubicle b b b

2 three per cubicle b b b b

3 three per cubicle b b b b

4 three per cubicle b

(1) Possibility of installing LV toroid transformers.(2) please consult us.

b

b

b

bbb

Installation Connections

Page 71: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

69

DE

5677

1

P

H

Figure 1

Bottom cable connectionCable connection height

Type of cubicle Confi guration H (mm)AD1 - AD2 630 A LV toroid CT 650 (1)

1 set of 3 CT’s 5002 sets of 3 CT’s 465

1250 A LV toroid CT 650 (1)

1 set of 3 CT’s 4802 sets of 3 CT’s 465

AD3 2500 A 1 set of 3 CT’s 4352 sets of 3 CT’s 435

DI2 450

(1) When installing with a LV core balance CT, use a LV core balance CT of type ARC3 when connecting with 2 cables (see page 31).

The cubicles and cables requiring the maximum depth should be taken into consideration when determining the depth P of a switchboard cable duct (fi gure 1).

When using cables of length greater than 460 mm, install an additional compartment as marked (A) under the cubicle (fi gure 2).

b

b

Top cable connection (optional, fi gure 3)

2 depths are available, function of the number of cables and the internal arc withstand of the cubicle: 2000 mm and 2275 mm.

Top busbar connection (optional, fi gure 4)

The cubicle depth is equal to 2000 mm, it can be equipped with 1 or 2 CT’s.

DE

5677

2D

E56

773

DE

5748

9

Figure 2

Figure 3

Figure 4

Installation Connections (cont.)

Page 72: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

70

Appendices Cubicle equipment

Equipment Type of cubicleAD1 AD1

cont.AD2 AD3 CL1 CL2 CL3 GL1 GL2 GL3 TT1 TT2 DI2

SwitchgearCircuit-breaker b b b b b b

Contactor b

Fuse switch b

Disconnector truck v v v v v v

Earthing truck v v v v v v v

Fixed busbars b b b

Racking position indication contact for the withdrawable part

3 NO + 3 NC b b b b b b b

6 NO + 6 NC v v v v v v

Padlocking of isolating shutters for withdrawable parts v v v v v v v

Locking of withdrawable part/cable compartment v v v v v v v

Disabling of circuit-breaker operating mechanism v v v v v v

Voltage present indicator b b b b v v v b (1) b (1) b

Locking of mechanical racking of the withdrawable part (padlock) b b b b b b b

Locking of mechanical racking of the withdrawable part (keylock) v v v v v v v

Locking of the electromagnetic racking of the withdrawable part v v v v v v v

Earthing switch (SMALT)Earthing switch v v v v v v v v v b

Earthing switch position indication contacts 3 NO + 3 NC v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (4)

Earthing switch position key locking (2) v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (1) v

Electromagnetic earthing switch position locking v v v v v v v v v

TransformersVoltage transformers(1 per phase)

Without fuse Phase-phase v v v v v v v

Phase-earth v v v v v v v v v v v

With plug-in fuses Phase-phase v v v v v v v

Phase-earth v v v v v v v v v v v

Fuse melting indication contact 1 NO v v v v v v v v v v v

Current transformer Single set 3 CT’s v v v v v v v v v v

Double set 6 CT’s v v v v

LV toroid transformer CT (3) v v v

LPCT v v v v v v v

ConnectionsConnection with cable terminal height > 460 mm v v v v v

Connection from top bar v v v v

Connection by cable from the top v v v v

Connection by cable from the bottom b b b b b

CubicleProtection index (7) Enclosure IP3X b b b b b b b b b b b b b

IP4X b b b v b b v b b v b b b

IPX1 v v v v v v v v v v v v v

Compartments (5) IP2XC b b b b b b b b b b b b b

Anti-arcing protection (2) 25 kA - 1 s v v v v v v v v v v v v v

31.5 kA - 1 s v v v v v v v v v v v v v

40 kA - 1 s v v v v v v v v

50 kA - 1 s v v v v v v v v

Lightning arrester v v v v v v v v v

Busbars1250 A / 2500 A / 3150 A / 4000 A (6) Exposed b b b b b b b b b b b b b

Insulated v v v v v v v v v v v v v

LV control cabinet key locking v v v v v v v v v v v v v

LV control cabinet lighting v v v v v v v v v v v v v

Anti-condensation heating element v v v v v v v v v v

Key:b: basic equipmentv: option(1) Basic equipment with earthing switch option.(2) According to the room in which the MCset switchboard is installed, you can choose option 3 or 4 sides, and possibly an exhaust tunnel for hot gases (see page 12).(3) Connection 1 or 2 cables per phase.(4) 1 NO + 1 NC available.(5) Compartment protection.(6) For 4000 A/95 kV impulse: insulated busbar compulsory.(7) IPX2: consult us.

Page 73: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

71

Preferred current transformers: 7.2 to 17.5 kV secondary 1 A or 5 A

Type of cubicle Accuracy classand ratio

AD1 AD1 fuse- contactor

AD2 AD2 AD3CL3

CL1 CL2

Isc kA 1 s 31.5 NA (1) 40 50 50 31.5 50Ratio number 1Accuracy classand ratio

40-80/1 or 52.5-5 VA - 5P20

v 10/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v

50-100/1-52.5-5 VA - 5P20

v 20/1-12.5 VA - 5P2015 VA - cl 0.5

v v

75-150/1 or 52.5-5 VA - 5P20

v 30/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v

100-200/1-1 or 5-52.5-5 VA - 5P20

v 40/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v

150-300/1-1 or 5-52.5-5 VA - 5P2010-20 VA - cl 0.5

v 50/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v

200-400/1-1 or 5-55-10 VA - 5P207.5-15 VA - cl 0.5

v 75/1-1 or 5/52.5 VA - 5P2015 VA - cl 0.5

v v

250-500/1-1 or 5-55-10 VA - 5P2010-20 VA - cl 0.5

v 100/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v

600/1-1 or 5-57.5 VA - 5P2020 VA - cl 0.5

v 150/1-1 or 5-57.5 VA - 5P1015 VA - cl 0.5

v v v v v

750/1-1 or 5-57.5 VA - 5P2020 VA - cl 0.5

v 200/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v v v v

1000/1-1 or 5-510 VA - 5P2030 VA - cl 0.5

v 250/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v v v v

1250/1-1 or 5-510 VA - 5P2030 VA - cl 0.5

v 300/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v v v v

1500/1-1 or 5-515 VA - 5P2030 VA - cl 0.5

400/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v

2000/1-1 or 5-515 VA - 5P2030 VA - cl 0.5

v

2500/1-1 or 5-515 VA - 5P20 30 VA - cl 0.5

v

(1) Short-circuit current withstand is co-ordinated with the current limited through the fuses.Other characteristics are available, including the possibility of having 3 secondary windings. Please consult us detailing the type of protection or measuring required as well as the impedance of the outside loads and the cabling.

Appendices Current transformersSelection guide

Page 74: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

72

A few references MCset, a product for all your electrical distribution applications

EnergyEPM, ColombiaLing-Ao power nuclear station, ChinaSunshine Electricity Biomass Cogeneration, Australia

Oil, GasTOTAL (FPSO), NigeriaSHELL, BruneiTECHNIP, VietnamIOOC (Iran Offshore Oil Company), IranOXY company, OmanDalia Oil Field Production Platform (Offshore platform), AngolaQatar Petroleum (onshore extraction), QatarADCO (Abu Dhabi Company for Onshore oil operation), United Arab EmiratesGASPROM, Russia

MetallurgySIDMAR, BelgiumSMS DEMAG, ChileARCELOR, FranceSIDERAR, ArgentinaALUAR, Argentina

MarineDAEWOO shipbuilding (container ship), South KoreaDAEWOO shipbuilding (LNG carrier), South KoreaNavy, France

Industry, InfrastructureHeathrow Airport, United KingdomGAZIANTEP DSI water treatment, TurkeyDesalination plant, Perth, AustraliaUnited Paper Mills (paper mills), FranceLAFARGE, South Africa

bbb

bbbbbbbbb

bbbbb

bbb

bbbbb

PE

5658

6

PE

5657

5P

E56

574

PE

5657

3P

E56

584

PE

5658

5

Page 75: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

DEAI02EN_COUV.indd 3DEAI02EN_COUV.indd 3 26/09/07 13:31:5826/09/07 13:31:58

Page 76: MCset 17.5 kV Air insulated switchboard - FGC · MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations

DEAI02EN 10-2007

AR

T.96

0195

© S

chne

ider

Ele

ctric

Indu

strie

s S

AS

- To

us d

roits

rése

rvés

As standards, specifi cations and designs change from time to time, please ask for confi rmation of the information given in this publication.