means of egress

Upload: abemar-gegantoni

Post on 16-Oct-2015

24 views

Category:

Documents


0 download

DESCRIPTION

firesafety

TRANSCRIPT

  • Means of Egress

    March 2010

    By: Felipe Agustin

    USGBC-LEEDTM AP

  • EMERGENCY LIGHTING

    PRIMARY OBJECTIVES:

    1. Indicate the escape route clearly

    2. Illuminate open areas used as escape route so that obstructions can be avoided.

    3. Ensure fire alarm call points and fire equipment can be readily located.

    4. Provide illumination for high risk areas to allow safety shutdown.

    GENERAL REQUIREMENTS:

    1. Provide lesser level of light than normal through the use of emergency and directional exit lights to create calm in an emergency situation.

    2. Highlight fire equipment to permit safety operations.

  • MANDATORY POINTS OF EMPHASIS

    EMERGENCY LIGHTING

    At each corridor Intersection Outside each final exit At each Exit Door

    At fire alarm call points At each floor level change At fire fighting equipment

  • MANDATORY POINTS OF EMPHASIS

    Exit and safety signs locationsOn each Staircase

    EMERGENCY LIGHTING

  • OTHER LOCATIONS

    Escalators

    Elevators

    Plant Rooms

    Covered carparks

    High risk task area

    EMERGENCY LIGHTING

  • Escape Route

    MINIMUM ILLUMINATION LEVELS

    EMERGENCY LIGHTING

    NFPA 101 Section 7.9.2 states that emergency lighting facilities shall be arranged to provide illumination that is not less than an average of 1 ft-candle (10.8 lux) and, at any point, not less than 0.1ft-candle (1.1 lux), measured along the path of egress at floor level. Illumination levels shall be permitted to decline to not less than an average of 0.6 ft-candle (6.5 lux) and, at any point, not less than 0.06 ft-candle (0.65 lux) at the end of of the 1 hours. A minimum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded.

    BS 5266: Part 1 calls for a minimum of 0.5 lux at floor level on the centerline of permanently unobstructed escape routes. Points of emphasis shall be illuminated to a minimum of 1.0 lux except for fire alarm call points and fire fighting equipment where 5.0 lux is the minimum requirement.

    Fire Code of the Philippines Section 10.2.5.11 ( C ) does not mention specific requirement.

  • EXIT MARKING

    Exit Sign Self-luminous Exit Sign

    Pictograms Exit Signage

    EUROPEAN FORMAT

    AMERICAN STANDARD FORMAT

    EMERGENCY LIGHTING

  • MOUNTING HEIGHT

    EMERGENCY LIGHTING

  • VIEWING DISTANCE

    BS 5266: Part 7 Requirements

    EMERGENCY LIGHTING

    NFPA 101 Section 7.10.1.5.2:

    States that new sign placement shall be such that no point in an exit access corridor is in excess of the

    rated viewing distance or 100 ft (30 m), whichever is less, from the nearest sign.

  • DURATION OF EMERGENCY LIGHTING SYSTEM

    REFERENCE STANDARDS PERIOD OF OPERATION

    Fire Code of the Philippines of 2008 Section 10.2.5.11 9 (C)(2)

    1 hours

    Philippine Electrical Code (PEC) Part 1 Article 7.0

    1 hours

    BS 5266: Part 1 1 hour

    NFPA 101 Section 7.9.2.1 1 hours

    EMERGENCY LIGHTING

  • CATEGORIES OF EMERGENCY LIGHTING

    EMERGENCY LIGHTING

  • SOURCES OF EMERGENCY LIGHTING SYSTEM

    1. EMERGENCY GENERATOR. In the event of failure of the normal supply, emergency power shall be available within 10 seconds.

    2. UNIT EQUIPMENT AND BATTERY SYSTEMS. No interruption in power.

    TYPES OF EMERGENCY LIGHTING SYSTEM

    1. SELF-CONTAINED Each luminaire an internal battery which operate during normal power failure. Wiring to a self-contained luminaire does not need to be fire-resistant.

    2. SLAVE Luminaire is powered from a central system. The power source is remote from the luminaire thus requiring wiring to be of fire-resistant cable.

    3. CONVERSIONS By using conversion kit, any mains luminaire can be converted for emergency use. Usual application is for luminaire having more than one lamp wherein just one lamp is for emergency use.

    EMERGENCY LIGHTING

  • TYPES OF CENTRAL POWER SUPPLY SYSTEMS

    EMERGENCY LIGHTING

    1. DC Central Power Supplies

    This system directly uses a battery to supply power to emergency lighting loads. The battery can be 2, 48/50 or 110 V.

    2. INVERTERS AC SYSTEM

    With the use of an inverter, the battery voltage is transformed from dc to ac (mains voltage).

    Central Power Supply units provide power to a substantial number of emergency slave luminaires. A dedicated room housing the battery and the control unit is normally required for central power supply unit.

  • TESTING OF EMERGENCY LIGHTING EQUIPMENT

    EMERGENCY LIGHTING

    Description NFPA 101 BS 5266 Part 1

    Daily Daily visual inspection

    Monthly Functional testing at 30-day intervals for not less than 30 seconds.

    Simulate a mains failure or a time sufficient only to verify emergency operation.

    Note: For safety reasons the simulated mains failure should not discharge the battery by more than of its capacity.

    Six Monthly Testing as monthly but for 1/3 of the rated duration.

    Annually For battery powered emergency lighting system, conduct annual functional testing for not less than 1 hours.

    Testing as monthly but for the full duration.

    For all tests Emergency lighting system shall be fully operational for the duration of tests.

    Emergency lighting system shall be fully operational for the duration of tests.

    Written records of visual inspections and test shall be made available as required by local authority.

    Written records of test date, results, repairs and completion.

  • TESTING OF EMERGENCY LIGHTING EQUIPMENT

    TYPICAL WIRING ARRANGEMENT OF NETWORKED TESTING PANELS CONNECTED TO CENTRAL BATTERY SYSTEMS

    CENTRAL

    BATTERY

    SYSTEM

    ADDRESSABLE TESTING

    PANEL

    EMERGENCY LIGHTING