Power Meter EME

System Rated Current Type Article No. Units per Designation package 1N 32 A EME1P32 167397 11N 32 A, MID cert. EME1P32MID 167398 13N 80 A EME3P80 167413 13N 80 A, MID cert. EME3P80MID 167414 13N 5 A, CT EME3PCT 167417 13N 125 A, MID cert. EME3P125MID 167416 1

SG10007

Accessories Current Transformer• Z-MG/WAK: maximum cable diameter 21 mm• Z-MG/WAS: maximum busbar cross section 30 x 10 mm, 40 x 10 mm or 50 x 12 mm, maximum cable diameter 23 mm / 30 mm - accord-

ing to type, see dimension diagramms

Communication modules

Description Type Article No. Units per Designation package Communication module MBUS EMECMBUS 167420 1Communication module with MODBUS EMECMODB 167421 1

wa_sg00312

EMECMODB

Basic Devices

System Rated Current Type Article No. Units per Designation package 3N 63 A, MODBUS EME3P63BMODBUS 167409 1wa_sg05711

Page 3: Measuring Instruments Measuring Instruments

198 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Specifi cations | Power Meters single-phase 32-40 A, EME

Description

Technical Data

• Digital active energy meter with measurement I - U - Hz - PF measurement of active instantaneous power, by IR side set up communication - 1 tariff - 1 S0

• Active energy-meters for single-phase alternating current with a, 7 digits counter. These meters have 1 S0 output generating pulses for remote pro-cessing of the active energy measurements for 1 tariff.

• Display LCD• For direct connection 32 A and 40 A• 7 digits for energy values indication• Accuracy class 1 for active energy according to EN 50470-3 (B)• Most attractive operating range current (Ist ... Imax) - for direct connection 32

A and 40 A = 0.020 ... 32 A or 40 A

• The standard versions are designed to be combined with the communica-tion module

• Active energy register zero setting (not for MID types)• Active energy register in T1 import/export• Instantaneous power active import/export display• Current RMS• Voltage RMS• Power factor• Frequency• FW release• FW checksum• 1 DIN modules wide (18 mm)

EME1P32 EME1P32MID direct connection 32 AData in compliance with EN 50470-1, EN 50470-3 and EN 62053-31General characteristics Housing DIN 43880 DIN 1 modules Mounting EN 60715 35 mm DIN rail Depth mm 70Reference standard active energy - EN 50470-1-3, EN 62053-31Operating features Connectivity to single-phase network n° wires 2 Storage of energy values and confi guration FRAM memory - yesSupply Rated control supply voltage Un VAC 230 Operating range voltage V 184 ... 276 Rated frequency fn Hz 50 Rated power dissipation (max.) Pv VA (W) 8 (0.6)Overload capability Voltage Un continuous V 276 momentary (1 s) V 300 Current Imax continuous A 32 momentary (10 ms) A 960Display (readouts) Display type LCD n° digits 7 (2 decimals) digit dimensions mm x mm 6.00 x 3 Active energy: 1 display, 7-digit kWh 0.00 ... 999999.9 Instantaneous tariff measurement - 1 1 display, 1-digit - T1 Display period refresh s 1Measuring accuracy at 23 ±1°C, referred to nominal values Active energy and power acc.to EN 50470-3 % ±1 (B)Measuring input Type of connection phase/N - direct Operating range voltage phase/N V 184 ... 276 Current Iref A 5 Current Imin A 0.25 Operating range current (Ist ... Imax) direct connection A 0.02 ... 32 Frequency Hz 50 Input waveform - alternating Starting current for energy measurement (Ist) mA 20Pulse output S0 acc.to EN 62053-31 Pulse output for active energy - yes Pulse quantity Imp/kWh 1000 Pulse duration ms 90 Required voltage min. (max.) VAC (DC) 5 ... 230 ±5% (5 ... 300) Permissible current pulse ON (max. 230 V AC/DC) mA 90 Permissible current impuls OFF (leakage currrent max. 230 V AC/DC) µA 1Optical interfaces Front side (accuracy control) LED Imp/kWh 5000

Page 4: Measuring Instruments Measuring Instruments

199 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Dimensions (mm) Connection diagram

A Miniature Circuit Breaker of 32A or 40A is recommended.

EME1P32 EME1P32MID direct connection 32 ASafety acc. to EN 50470-1 Indoor meter - yes Degree of pollution - 2 Operational voltage V 300 AC voltage test (EN 50470-3, 7.2) kV 4 Impulse voltage test 1.2/50 µs-kV 6 Protection class (EN 50470) class II Housing material fl ame resistance UL 94 class V0 Safety-sealing between upper and lower housing part - no yesAdaptor for Communication Plug-and-play technology - • LAN Interface (TCP/IP) Ethernet 802.3 EMECLAN 10/100 Mbps Modbus RTU, Ascii RS-485 3 wires EMECMODB up to 19.200 bps M-Bus RS-485 2 wires EMECMBUS up to 9.600 bpsConnection terminals Type cage main current paths screw head Z +/- POZIDRIV PZ1 Type cage pulse output blade for slotted screw mm PZ0 Terminal capacity main current paths solid wire min. (max.) mm2 16 stranded wire with sleeve min. (max.) mm2 16 Terminal capacity pulse outlet solid wire min. (max.) mm2 0.15 (2.5) stranded wire with sleeve min. (max.) mm2 0.15 (4)Environmental conditions Mechanical environment - M1 Electromagnetic environment - E2 Operating temperature °C -10 ... +55 Limit temperature of transportation and storage °C -25 ... +70 Relative humidity (not condensation) % 80 Vibrations 50 Hz sinusoidal vibration amplitude mm ±0.075 Degree protectionhousing when mounted in front (terminal) - IP51*)/IP20

*) For the installation in a cabinet at least with IP51 protection

Page 5: Measuring Instruments Measuring Instruments

200 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Specifi cations | Power Meters three-phase, transformer 5 A, direct 80 A, EME

Description

Technical Data

• Digital active and reactive energy-meter with measurement of active and reactive instantaneous power, by IR side set up communication - 2 tariffs - 2 S0 (MID types: displays only active power).

• Active energy-meters for three-phase alternating current with either 2, 8 digits digital counters. These meters have 2 S0 output generating pulses for remote processing of the instantaneous energy active and reactive measurements for 2 tariffs.

• Green backlighted LCD• For direct connection 80 A, or for transformer .../5 A• For transformer primary current of 5 A to 10.000/5 A. Input is in 5 A incre-

ments• 8 digits - 8 display for energy values indication• Detection of connection errors (phase transposition)

• Accuracy class 1 for active energy and power according to EN 50470-3 (B)• Accuracy class 2 for reactive energy and power according to EN 62053-23• Most attractive operating range current (Ist ... Imax), for direct connection 80

A = 0.015 ... 80 A, for connection by CT .../5 A = 0.003 ... 5 A• The standard versions are designed to be combined with the communica-

tion module• Energy register zero setting (not for MID types)• Energy register for import and export• Instantaneous power active and reactive display (MID types: only active

power)• Sealable terminal covers• 4 DIN modules wide (72 mm)

EME3P80 EME3P80MID EME3PCT direct connection 80 A CT connection till 10.000/5 AData in compliance with EN 50470-1, EN 50470-3, EN 62053-23 and EN 62053-31General characteristics Housing DIN 43880 DIN 4 modules 4 modules Mounting EN 60715 35 mm DIN rail DIN rail Depth mm 70 70Reference standard active energy - EN 50470-1-3 EN 50470-1-3 pulse output EN 62053-31 EN 62053-31Operating features Connectivity to single/three-phase network n° wires 2-4 4 Storage of energy values and confi guration digital display (EEPROM) - yes yes Display tariffs identifi er for active and reactive energy n° 2 T1 and T2 T1 and T2Supply Rated control supply voltage Un VAC 230 230 Operating range voltage V 184 ... 276 184 ... 276 Rated frequency fn Hz 50 50 Rated power dissipation (max. for phase) Pv VA (W) 8 (0.6) 8 (0.6) Overload capability Voltage Un continuous; phase/phase V 480 480 1 second: phase/phase V 800 800 continuous; phase/N V 276 276 1 second: phase/N V 460 460 Current Imax continuous A 80 6 momentary (0,5 s) A - 120 momentary (10 ms) A 2400 -Display (readouts) Connection errors and phase out discernible from phase-sequence indication - PHASE Err PHASE Err Display type LCD n° digits 8 (2 decimal) 8 (2 decimal) digit dimensions mm x mm 6.00 x 3 6.00 x 3 Active energy: 1 display, 8 digit tariffs 2 Wh 0.01 0.01 + display import or export (arrow) overfl ow MWh 999999.99 999999.99 Reactive energy: 1 display, 8-digit tariffs 2 varh 0.01 0.01 + display import or export (arrow) overfl ow Mvarh 999999.99 999999.99 Instantaneous active power: 1 display, 3-digit W, kW or MW 000 ... 999 000 ... 999 Instantaneous reactive power: 1 display, 3-digit var, kvar or Mvar 000 ... 999 000 ... 999 Instantaneous tariff measurement 1 display, 1-digit - T1 or T2 T1 or T2 Transformer primary current A - 5 ... 10.000 Display period refresh s 1 1Measuring accuracy Active energy and power acc.to EN 50470-3 class 1 B B Reactive energy and power acc.to EN 62053-23 class 2 2 2

Page 6: Measuring Instruments Measuring Instruments

201 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

EME3P80 EME3P80MID EME3PCT direct connection 80 A CT connection till 10.000/5 AMeasuring input Type of connection direct transformer .../5 A Voltage Un phase/phase V 400 400 phase/N V 230 230 Operating range voltage phase/phase V 319 ... 480 319 ... 480 phase/N V 184 ... 276 184 ... 276 Current Iref A 5 - Current In A - 5 Current Imin A 0.25 0.05 Operating range current (Ist ... Imax) direct connection A 0.015 ... 80 - transformer connection (CT) A - 0.003 ... 6 Transformer current primary current of the transformer A - 5 ...10.000 smallest input step adjustment - in 5 A steps A - 5 Frequency Hz 50 50 Input waveform - sinusoidal sinusoidal Starting current for energy measurement (Ist) mA 15 3Pulse output SO acc.to EN 62053-31 Pulse output for act. and react. energy T1 and T2 yes yes Quantity pulse output for direct connection 80 A Imp/kWh 500 - depending on the transf. factor. Imp/kWh - 100-10-1 Pulse duration ms 30 ±2 30 ±2 Required voltage min. (max.) VAC (DC) 5 ... 230 ±5% (5 ... 300) 5 ... 230 ±5% (5 ... 300) Permissible current pulse ON (max. 230 V AC/DC) mA 90 90 Permissible current pulse OFF (leakage current max. 230 V AC/DC) µA 1 1Optical interfaces Front side (accuracy control) LED Imp/kWh 1000 10.000Safety acc. to EN 50470-1 Indoor meter - yes yes Degree of pollution - 2 2 Operational voltage V 300 300 AC voltage test (EN 50470-3, 7.2) kV 4 4 Impulse voltage test 1.2/50 µs-kV 6 6 Protection class (EN 50470) class II II Housing material fl ame resistance UL 94 class V0 V0 Safety-sealing between upper and lower housing part - yes no noAdaptor for Communication Plug-and-play technology - • • LAN (TCP/IP) interface Ethernet 802.3 EMECLAN 10/100 Mbps 10/100 Mbps Modbus RTU, Ascii interface RS-485 - 3 wires EMECMODB up to 19.200 bps up to 19.200 bps M-Bus interface RS-485 - 2 wires EMECMBUS up to 9.600 bps up to 9.600 bpsConnection terminals Type cage main current paths screw head Z +/- POZIDRIV PZ2 PZ1 Type cage pulse output blade for slotted screw mm 0.8 x 3.5 0.8 x 3.5 Terminal capacity main current paths solid wire min. (max.) mm2 1.5 (35) 1 (4) stranded wire with sleeve min. (max.) mm2 1.5 (35) 1 (4) Terminal capacity pulse outlet solid wire min. (max.) mm2 1 (4) 1 (4) stranded wire with sleeve min. (max.) mm2 1 (2.5) 1 (4)

Page 7: Measuring Instruments Measuring Instruments

202 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

EME3P80 EME3P80MID EME3PCT direct connection 80 A CT connection till 10.000/5 AEnvironmental conditions Mechanical environment - M1 M1 Electromagnetic environment - E2 E2 Operating temperature °C -10 ... +55 -10 ... +55 Limit temperature of transportation and storage °C -25 ... +70 -25 ... +70 Relative humidity (not condensation) % 80 80 Vibrations 50 Hz sinusoidal vibration amplitude mm ±0.075 ±0.075 Degree protectionhousing when mounted in front (terminal) - IP51*)/IP20 IP51*)/IP20

*) For the installation in a cabinet at least with IP51 protection

Dimensions (mm) Connection diagrams

A Miniature Circuit Breaker of 80A is recommended.

Wire N needs to be connected to the meter.

Direct connection 80 A

Page 8: Measuring Instruments Measuring Instruments

203 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Dimensions (mm) Connection diagrams

Wire N needs to be connected to the meter.

Instructions for the connection of transformer countersA Miniature Circuit Breaker of 6A is recommended. Current transformers must not be operated with open terminals since dangerous high voltages might occur which may result in per-sonal injuriesand property damage. In addition to this, the transformers are exposed to thermal overload.

Connection through CT .../5 A till 10.000/5 A

Page 9: Measuring Instruments Measuring Instruments

204 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Specifi cations | Power Meter three-phase 125 A, EME

Description

Technical Data

• Digital active and reactive energy-meter with measurement of active and reactive instantaneous power, by IR side set up communication - 2 tariffs - 2 S0 (MID types: displays only active power).

• Active energy-meters for three-phase alternating current with either 2, 8 digits digital counters. These meters have 2 S0 output generating pulses for remote processing of the instantaneous energy active and reactive measurements for 2 tariffs.

• Green backlighted LCD• For direct connection 125 A• 8 digits - 8 display for energy values indication• Detection of connection errors (phase transposition)• Accuracy class 1 for active energy and power according to EN 50470-3 (B)

• Accuracy class 2 for reactive energy and power according to EN 62053-23• Most attractive operating range current (Ist ... Imax) for direct connection

125 A = 0.020 ... 125 A• The standard versions are designed to be combined with the communica-

tion module• Energy register zero setting (not for MID types)• Energy register for import and export• Instantaneous power active and reactive display (MID types: only active

power)• Sealable terminal covers• 6 DIN modules wide (108 mm)

EME3P125MID direct connection 125 AData in compliance with EN 50470-1, EN 50470-3, EN 62053-23 and EN 62053-31General characteristics Housing DIN 43880 DIN 6 modules Mounting EN 60715 35 mm DIN rail Depth mm 70Reference standard active energy - EN 50470-1-3 reactive energy - pulse output EN 62053-23-31Operating features Connectivity to single/three-phase network n° wires 2-4 Storage of energy values and confi guration digital display (EEPROM) - yes Display tariffs identifi er for active and reactive energy n° 2 T1 and T2Supply Rated control supply voltage Un VAC 230 Operating range voltage V 184 ... 276 Rated frequency fn Hz 50 Rated power dissipation (max.) Pv VA (W) 8 (0.6) Overload capability Voltage Un continuous; phase/phase V 480 1 second: phase/phase V 800 continuous; phase/N V 276 1 second: phase/N V 300 Current Imax continuous A 125 momentary (10 ms) A 3750Display (readouts) Connection errors and phase out discernible from phase-sequence indication - PHASE Err Display type LCD n° digits 8 (2 decimal) digit dimensions mm x mm 6.00 x 3 Active energy: 1 display, 8 digit tariffs 2 Wh 0.01 + display import or export (arrow) overfl ow MWh 999999.99 Reactive energy: 1 display, 8 digit tariffs 2 varh 0.01 + display import or export (arrow) overfl ow Mvarh 999999.99 Instantaneous active power: 1 display, 3-digit W, kW or MW 000 ... 999 Instantaneous reactive power: 1 display, 3-digit var, kvar or Mvar 000 ... 999 Instantaneous tariff measurement - 1 1 display, 1-digit - T1 or T2 Display period refresh s 1Measuring accuracy Active energy and power acc.to EN 50470-3 % B Reactive energy and power acc.to EN 62053-23 % 2Measuring input Type of connection direct Voltage Un phase/phase V 400 phase/N V 230Operating range voltage phase/phase V 319 ... 480 phase/N V 184 ... 276

Page 10: Measuring Instruments Measuring Instruments

205 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

EME3P125MID direct connection 125 AMeasuring input Current Iref A 5 Current Imin A 0.25 Operating range current (Ist ... Imax) direct connection A 0.020 ... 125 Frequency Hz 50 ±2% Input waveform - sinusoidal Starting current for energy measurement (Ist) mA 20Pulse output S0 acc.to EN 62053-31 Pulse output for active and reactive energy T1 and T2 yes Quantity pulse output Imp/kWh 500 Pulse duration ms 30 ±2 ms Required voltage min. (max.) VAC (DC) 5 ... 230 ±5% (5 ... 300) Permissible current pulse ON (max. 230 V AC/DC) mA 90 Permissible current impuls OFF (leakage currrent max. 230 V AC/DC) µA 1Optical interfaces Front side (accuracy control) LED Imp/kWh 1000Safety acc. to EN 50470-1 Indoor meter - yes Degree of pollution - 2 Operational voltage V 300 AC voltage test (EN 50470-3, 7.2) kV 4 Impulse voltage test 1.2/50 µs-kV 6 Protection class (EN 50470) class II Housing material fl ame resistance UL 94 class V0 Safety-sealing between upper and lower housing part - yesAdaptor for Communication Plug-and-play technology - • LAN (TCP/IP) interface Ethernet 802.3 EMECLAN 10/100 Mbps Modbus RTU, Ascii interface RS-485 - 3 wires EMECMODB up to 19.200 bps M-Bus interface RS-485 - 2 wires ENECMBUS up to 9.600 bpsConnection terminals Type cage main current paths screw head Z +/- POZIDRIV PZ2 Type cage pulse output blade for slotted screw mm 0.8 x 3.5 Terminal capacity main current paths solid wire min. (max.) mm2 1.5 (50) stranded wire with sleeve min. (max.) mm2 1.5 (50) Terminal capacity pulse outlet solid wire min. (max.) mm2 1 (4) stranded wire with sleeve min. (max.) mm2 1 (2.5)Environmental conditions Mechanical environment - M1 Electromagnetic environment - E2 Operating temperature °C -10 ... +55 Limit temperature of transportation and storage °C -25 ... +70 Relative humidity (not condensation) % 80 Vibrations 50 Hz sinusoidal vibration amplitude mm ±0.075 Degree protectionhousing when mounted in front (terminal) - IP51*)/IP20

*) For the installation in a cabinet at least with IP51 protection

Page 11: Measuring Instruments Measuring Instruments

206 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Dimensions (mm) Connection diagram

A Miniature Circuit Breaker of 125A is recommended.

Wire N needs to be connected to the meter.

Page 12: Measuring Instruments Measuring Instruments

207 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Specifi cations | M-Bus interface EMECMBUS

Description

Technical Data

Dimensions (mm)

• Additional communication modules for Energy-meter, Network analyzer and Power-meters

• Additional module for M-Bus connection for energy, power, V, I, cos, fre-quency

• M-Bus according to EN1434• Suitable for both single-phase and three-phase energy meters• 1 DIN module wide (18 mm)

EMECMBUSData in compliance with EN 13757-1-2-3, IEC 60950, EN 61000-6-2, EN 61000-6-3 and EN 61000-4-2General characteristics Housing DIN 43880 DIN 1 module Mounting EN 60715 35 mm DIN rail Depth mm 70Power supply Power supply - through bus connectionOperating features Suitable for both single-phase and three-phase energy meters yesM-bus interface HW interface - 2 screw clamps SW protocol - M-Bus according to EN1434 Baudrate Baud 300-9600Interface to measuring instrument HW interface optical IR n° 2 (Tx, Rx) SW protocol - proprietarySafety acc. to IEC 60950 Degree pollution - 2 Overvoltage category - II Working voltage V 24 ... 36 Clearance in equipment mm 1.5 on PCB (not coated) mm 1.5 Creepage distance mm 2.1 Test voltage impulse (1,2/50 µs) peak value kV 2.5 50 Hz 1 min kV 1.35 Housing material fl ame resistance UL 94 class V0Connection terminals Type cage main current paths screw head Z +/- POZIDRIV PZ0 Terminal capacity solid wire min. (max.) mm2 0.15 (2.5) stranded wire with sleeve min. (max.) mm2 0.15 (4)Environmental conditions Operating temperature °C 0 ... +55 Limit temperature of transportation and storage °C -25 ... +70 Relative humidity % 80 Vibrations 50 Hz sinusoidal vibration amplitude mm ±0.25 Protection class acc.to IEC 60950 - II Degree of protection housing when mounted in front IP20

Page 13: Measuring Instruments Measuring Instruments

Measuring Instruments

Specifi cations | Modbus interface RTU and Ascii EMECMODB

Description

Technical Data

Dimensions (mm)

• Additional communication modules for Energy-meter, Network analyzer and Power-meters

• Additional module for Modbus RTU and Ascii connection for energy, power, V, I, cos, frequency

• Protocols Modbus Ascii - Modbus RTU• Suitable for both single-phase and three-phase energy meters• 1 DIN module wide (18 mm)

EMECMODBData in compliance with IEC 60950, EN 61000-6-2, EN 61000-6-3 and EN 61000-4-2General characteristics Housing DIN 43880 DIN 1 module Mounting EN 60715 35 mm DIN rail Depth mm 70Power supply Auxiliary voltage rating Un VAC 230 Auxiliary power rating W 10 Auxiliary voltage range VAC 0.80 ... 1.20 x Un Frequency rating Hz 50/60 Frequency range Hz 45 ... 65 Operating features Protocol selectable by software - Modbus RTU or Ascii Suitable for both single-phase and three-phase energy meters yesModbus interface HW interface RS-485 terminals n° 3 (+/-, cable shield) Input resistance UL (k) 1 (12) Termination resistance 80 SW protocol SW selectable - Modbus Ascii - Modbus RTU Data transfer speed SW selectable baud 38.400 - default 19200 Parity - none/even - default: none Addressing - 1 to 247Interface to measuring instrument HW interface optical IR n° 2 (Tx, Rx) SW protocol - proprietarySafety acc. to IEC 60950 Degree pollution - 2 Overvoltage category - II Working voltage V 300 Clearance mm 4 Creepage distance mm 4 Test voltage impulse (1,2/50 µs) peak value on AC power supply kV 2.5 on telecommunication network kV 1.5 50 Hz 1 min kV 2.5 Housing material fl ame resistance UL 94 class V0Connection terminals Type cage main current paths screw head Z +/- POZIDRIV PZ0 Terminal capacity solid wire min. (max.) mm2 0.15 (2.5) stranded wire with sleeve min. (max.) mm2 0.15 (4)Environmental conditions Operating temperature °C 0 ... +55 Limit temperature of transportation and storage °C -25 ... +70 Relative humidity % 80 Vibrations 50 Hz sinusoidal vibration amplitude mm ±0.25 Protection class acc.to IEC 60950 - II Degree of protection housing when mounted in front IP20

208 EATON CORPORATION xxxxx+xxxx-xxxxEN

Page 14: Measuring Instruments Measuring Instruments

209 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Specifi cations | BASIC Power Meters three-phase, 63 A, EME

Description

Technical Data

• Digital active energy meter with partial active energy counter resettable and inbuilt communication Modbus RTU- 2 tariffs

• Three-phase digital active energy-meter with direct connection 0.25-5 (63) A, and inbuilt communication Modbus RTU - 2 tariffs

• For direct connection 63 A• 9 digits for 8 energy indication values• Detection of connection errors (phase transposition and phase missing)• Accuracy class 1 for active energy and power according to EN 50470-3 (B)

• Most attractive operating range current (Ist ... Imax), for direct connection 63 A = 0.015 ... 63 A

• Energy register zero setting (not for MID types)• Energy register “Partial” zero setting also for MID types• Sealable terminal covers• Energy register for delivery and supply• 4 DIN modules wide (72 mm)

EME3P63BMODBUS direct connection 63 AData in compliance with EN 50470-1, EN 50470-3 and EN 62053-31General characteristics Housing DIN 43880 DIN 4 modules Mounting EN 60715 35 mm DIN rail Depth mm 70Reference standard active energy - EN 50470-1-3 pulse output EN 62053-31Operating features Connectivity to three-phase network n° wires 4 Storage of energy values and confi guration digital display (EEPROM) - yes Display tariffs identifi er for active energy n° 2 T1 and T2Supply Rated control supply voltage Un VAC 230 Operating range voltage V 184 ... 276 Rated frequency fn Hz 50 Rated power dissipation (max. for phase) Pv VA (W) 8 (0.6)Overload capability Voltage Un continuous; phase/phase V 480 1 second: phase/phase V 800 continuous; phase/N V 276 1 second: phase/N V 300 Current Imax continuous A 80 momentary (0,5 s) A - momentary (10 ms) A 2400Display (readouts) Connection errors and phase out discernible from phase-sequence indication - PHASE Err Display type LCD n° digits 9 (2 decimal) digit dimensions mm x mm 6.00 x 3 Active energy: 1 display, 9 digit - 2 tariffs min. measuring energy kWh 0.01 + display import or export (arrow) max. measuring overfl ow kWh 9999999.99 Instantaneous tariff measurement 1 display, 1-digit - T1 or T2 Transformer primary current A - Display period refresh s 1Measuring accuracy Active energy acc.to EN 50470-3 class 1 BMeasuring input Type of connection direct Voltage Un phase/phase V 400 phase/N V 230 Operating range voltage phase/phase V 319 ... 480 phase/N V 184 ... 276 Current Iref A 5 Current In A - Current Imin A 0.25 Operating range current (Ist ... Imax) direct connection A 0.015 ... 63 transformer connection (CT) A - Transformer current primary current of the transformer A - smallest input step adjustment - A - Frequency Hz 50 Input waveform - sinusoidal Starting current for energy measurement (Ist) mA 15

Page 15: Measuring Instruments Measuring Instruments

210 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

EME3P63BMODBUS direct connection 63 AOptical interfaces Front side (accuracy control) LED Imp/kWh 1000Safety acc. to EN 50470-1 Indoor meter - yes Degree of pollution - 2 Operational voltage V 300 AC voltage test (EN 50470-3, 7.2) kV 4 Impulse voltage test 1.2/50 µs-kV 6 Protection class (EN 50470) class II Housing material fl ame resistance UL 94 class V0 Safety-sealing between upper and lower housing part - yesEmbedded communication Modbus RTU RS-485 - 3 wires - up to 19.200 bpsConnection terminals Type cage main current paths screw head Z +/- POZIDRIV PZ2 Type cage pulse output blade for slotted screw mm 0.8 x 3.5 Terminal capacity main current paths solid wire min. (max.) mm2 1.5 (35) stranded wire with sleeve min. (max.) mm2 1.5 (35) Terminal capacity pulse outlet solid wire min. (max.) mm2 1 (4) stranded wire with sleeve min. (max.) mm2 1 (2.5)Environmental conditions Mechanical environment - M1 Electromagnetic environment - E2 Operating temperature °C -10 ... +55 Limit temperature of transportation and storage °C -25 ... +70 Relative humidity (not condensation) % 80 Vibrations 50 Hz sinusoidal vibration amplitude mm ±0.075 Degree protectionhousing when mounted in front (terminal) - IP51*)/IP20

*) For the installation in a cabinet at least with IP51 protection

Dimensions (mm) Connection diagrams

Wire N needs to be connected to the meter.

A Miniature Circuit Breaker of 63A is recommended.

Page 16: Measuring Instruments Measuring Instruments

211 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Multimeter EME3PMMCT5

Communication link Type Article No. Units per Designation package S0 EME3PMMCT5 171631 1SG14413

Specifi cations | Multimeter, EME3PMMCT5

Description• The Eaton Multimeter offer an extremely compact multifunction solution

for switchgear and incoming or outgoing feeders in industrial plants and buildings like offi ces, hospitals, universities and so on

• Can be connected to three phase networks via current transformers (.../5A till 10.000/5A)

• Three phase 38 readouts, imported and exported power• Clear readable LED display that reports all measurements through a user-

friendly interface controlled directly from the front panel• Analysis of the different loads on each phase to identify displacements,

asymmetrical or unbalanced conditions

• Offers a range of different options to combine and assess measured values• Provided with 2 S0 outputs report active and reactive energy• Two different tariffs settled by an external energy counter (Wh and VArh)• With a side IrDA interface for external communication• External communication allows for the transmission of measured values to

a remote energy management system• 6 modules housing for DIN rail mounting• User can display continuously fi ve indicated values

Page 17: Measuring Instruments Measuring Instruments

212 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Technical Data

EME3PMMCT5Communication link S0Connection .../5 AHousing DIN modules (wide) 6Measuring voltage range V AC 50 ... 276 / 87 ... 480Frequency range Hz 49 ... 51Starting current (Ist) mA 3Reference current (Iref) A 5Main supply V AC Auxiliary 184 ... 276System connectivity (n° wires) 2 - 3 - 4Display (n° digit) LEDDisplay green backlighted YESMain terminal (wire mm2) 4Operating temperature °C -10 to +55Pulse output SO (n°) 2Measuring accurancy EN 50470-1-3 active energy class 1 B (1%) EN 62053-23 reactive energy class 2 2%Voltage L1, L2, L3 L1-2, L2-3, L3-1 Current L1, L2, L3 N Power factor L1, L2, L3 L Frequency Active power L1, L2, L3 L Reactive power L1, L2, L3 L Apparent power L1, L2, L3 L Import active energy L1, L2, L3, L Tariff 1 and 2 Export active energy L1, L2, L3, L Tariff 1 and 2 Import reactive energy L1, L2, L3, L Tariff 1 and 2 Export reactive energy L1, L2, L3, L Tariff 1 and 2 Communication ()IR - side: M-Bus, Modbus RTU, KNX, LAN-TCP/IP, SD-Card YES

= Measured parameters displayed, = Measured parameters through IR side modules

Page 18: Measuring Instruments Measuring Instruments

LAN Server Modbus/TCP EMELSMODBUS

Description Type Article No. Units per Designation package Data Concentrator with Modbus/TCP EMELSMODBUS 170509 1SG14313

213 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Specifi cations | LAN Server Modbus/TCP, EMELSMODBUS

DescriptionOverview:The LAN Servers are Plug-and-Play data concentrators for Energy Meter, Network Analyzer and Power Meter products. The LAN Server allows an easy and reliable connection of several instruments to a data communication network. It is an innovative product designed to implement fast data com-munication between a supervisory PC and a set of measurement instruments connected through LAN, WAN or Internet. Instruments may be of different kinds and are automatically recognized through a unique coding.

LAN Server Modbus/TCP:This Plug-and-Play product collects the measurement data from different devices connected via a Modbus serial bus. Data are made available on LAN, WAN or Intranet through an HTTP interface and are accessible using simulta-neously a standard browser or a Modbus/TCP Application.The LAN Server Modbus/TCP requires an auxiliary at 230 V AC power supply.

Common features• Worldwide communication with measuring devices• Hardware connection through RJ45• TCP/IP data protocol• HTTP for web server• FTP for fi le transfer• NTP for time synchronization• Static or DHCP based addressing• DDNS to maintain a host name, accessible on the internet, without the

need for a static IP• Plug-and-play technology• Internet browser user interface, three languages• Password-protected site access• Internal memory: 2 Gigabytes available for long period storage• 4 DIN modules wide (72 mm)

Page 19: Measuring Instruments Measuring Instruments

214 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Technical Data

EMELSMODBUSType LAN Server Modbus/TCPDescription Data Concentrator with Modbus/TCPAccording to norm general EN 61000-6-2-3, EN 61000-4-2 YESAccording to norm general EN 60950Number of modules 4

Power supplyVoltage range V AC 230 ±20 %Aux. power rating VA 10Frequency range Hz 45 ... 65

Operation featureMemory storage Internal 2 GigabyteLAN - HW interface RJ 45LAN - SW protocol TCP/IPLAN - Bandrate 10/100 Mbit/sApplication level protocols HTTP - FTP - modbus/TCPInterface to instruments RS485HW interface 3 screw clampsSW protocol Modbus RTU and ASCIIDirectly connected instruments 31S0 impulse input –

Safety acc. to IEC 60950Degree pollution 2Overvoltage category IIWorking voltage V AC ... 300Test voltage impulse (1,2/50 µs) peak value kV 4 50 Hz 1 min kV 4

Environmental conditionsOperating temperature °C -10 to 55 Limit temperature of storage °C -25 to 70 Relative humidity (non condensing) 80%Vibrations amplitude at 50 Hz mm ±0.25 Protection class IIDegree of protection IP20

Page 20: Measuring Instruments Measuring Instruments

215 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Digital Ammeter and Voltmeter EM

Description Type Article No. Units per Designation package Ammeter EMA20 167423 1Voltmeter EMV600 167422 1

wa_sg00212

Function Ratio/Measuring Range Type Article No. Units per Designation package

Accessories Current Transformer

• Z-MG/WAK: maximum cable diameter 21 mm• Z-MG/WAS: maximum busbar cross section 30 x 10 mm, 40 x 10 mm or 50 x 12 mm, maximum cable diameter 23 mm / 30 mm - accord-

ing to type, see dimension diagramms

Current transf. for cable 40/5 Z-MG/WAK-40 101619 1Current transf. for cable 50/5 Z-MG/WAK-50 101620 1Current transf. for cable 60/5 Z-MG/WAK-60 101621 1Current transf. for cable 80/5 Z-MG/WAK-80 101622 1Current transf. for busbar 100/5 Z-MG/WAS-100 101623 1Current transf. for busbar 150/5 Z-MG/WAS-150 101625 1Current transf. for busbar 200/5 Z-MG/WAS-200 101626 1Current transf. for busbar 250/5 Z-MG/WAS-250 101627 1Current transf. for busbar 300/5 Z-MG/WAS-300 101628 1Current transf. for busbar 400/5 Z-MG/WAS-400 101629 1Current transf. for busbar 500/5 Z-MG/WAS-500 101630 1Current transf. for busbar 600/5 Z-MG/WAS-600 101631 1Current transf. for busbar 800/5 Z-MG/WAS-800 101632 1Current transf. for busbar 1000/5 Z-MG/WAS-1000 101624 1

SG8797

Specifi cations | Ammeter EMA20 - Voltmeter EMV600

Description• Digital measuring instruments offer greater readout immediacy for the

value displayed. They also offer the advantage of having no moving parts which are subject to wear over the long term, an issue which can affect the precision and reliability of the instrument.

• Voltmeter AC• Ammeter AC• 2 DIN modules wide (36 mm)

Page 21: Measuring Instruments Measuring Instruments

216 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Technical Data

Voltmeter Ammeter EMV600 EMA20Data in compliance with EN 61010-1, EN 61000-6-2, EN 61000-6-3General characteristics Housing DIN 43880 DIN 2 modules 2 modules Mounting EN 60715 35 mm DIN rail DIN rail Depth mm 70 70 Reference standard - DIN 43751-1-2 DIN 43751-1-2Power supply Voltage VAC 230 230 Operating range voltage VAC 0.90 ... 1.15 0.90 ... 1.15 Frequency rating Hz 50/60 50/60 Operating range frequency Hz 45 ... 65 45 ... 65 Power rating VA 2 2Overload capability Voltage Un continuous V 1.2 x voltage rating - momentary (1 s) V 1.3 x voltage rating - Current Ib/In continuous A - 1.1 x current rating momentary (1 s) A - 10 x current ratingDisplay (readouts) Voltage 3 digits h = 10 mm V 12 ... 600 - voltages >600 V - HHH - voltages <12 V - --- - Current 3 digits h = 10 mm A - 0.4 ... 20 (a) 0.1 ... 5 (b) (CT operat.) currents >10 A - 20 A/5 A (connection CT) A - HHH currents <0.1 A - 0.2 A - 0.4 A (connection CT) A - --- Readout refresh rate readout/s 4 4Measuring accuracy at 23 ±1°C referred to nominal values Voltage % ±1 ±1 digit - Current % - ± 0.5 ±1 digit Temperature (deviating) % for °C ±0.03 ±0.03Measuring input Connectivity - direct direct (a)(b < 5 A) with CT .../5 A (b) Voltage Un V 600 - Measurement range voltage V 12 ... 600 - Current Ib/In A - 20 (a) 5 (b) Measurement range current A - 0.4 ... 20 (a) 0.2 ... 10 (b) (0.1 ... 5) x transformer ratio (b) Frequency rating Hz 50 50 Measurement range frequency Hz 45 ... 65 45 ... 65 Input waveform - synus. symmetric synus. symmetricSafety acc. to EN 61010-1 Degree pollution - 2 2 Overvoltage category - II II Working voltage V 300 600 Material group - II II Clearance mm 3.0 1.5 Creepage distance inside the equipment mm 4.3 2.1 on printed wiring boards (not coated) mm 3.0 1.5 Test voltage impulse (1,2/50 µs) peak value kV 4.0 2.5 50 Hz 1 min kV 2.2 1.35 Housing material fl ame resistance UL 94 class V0 V0

Page 22: Measuring Instruments Measuring Instruments

217 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Voltmeter Ammeter EMV600 EMA20Connection terminals Type cage screw head Z +/- POZIDRIV PZ1 PZ1 Terminal capacity solid wire min. (max.) mm2 1 (6) 1 (6) stranded wire with sleeve min. (max.) mm2 1 (6) 1 (6)Environmental conditions Operating temperature °C -10 ... +55 -10 ... +55 Limit temperature of transportation and storage °C -40 ... +70 -40 ... +70 Relative humidity % 80 80 Vibrations (sinusoidal) 50 Hz sinusoidal vibration amplitude mm ±0.25 ±0.25 Protection class acc.to EN 61010-1 - II II Degree of protection (terminals) IP40 (IP20) IP40 (IP20)

Dimensions (mm) Connection diagrams

Page 23: Measuring Instruments Measuring Instruments

218 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Measuring Instruments Accessories

Current Transformer for Cable Z-MG/WAK, Current Transformer for Busbar Z-MG/WAS

• Transform high currents to standard measuring currents• Current transformers help to cut costs when installing and connecting bus-

bar system• Recommended from 40 A upward• Accuracy classes

Class 0.5: for accurate measurement and calibrated kWh-metersClass 1: for general measurement and non-calibrated kWh-metersClass 3: for coarse measurement, relays and for protection

• When winding several turns of the primary cable around the current trans-former, you will receive half the primary current per turn while power and class remain unchanged.

Technical Data

Connection diagram

Dimensions (mm)

Z-MG/WAK Z-MG/WAS

Electrical Max. service voltage 720 V 720 VSecondary current 5 A 5 ARated frequency 50-60 Hz 50-60 HzCable diameter 21 mm 23 mm, 30 mmBusbar cross section – 30 x 10 mm, 40 x 10 mm, 50 x 12 mm Class P [VA] Class P [VA] Primary nominal current IpN 40 A 3 1.3 50 A 3 1.5 60 A 3 1.5 80 A 3 2 100 A 1 1.5 150 A 1 3 200 A 1 3 250 A 0.5 2 300 A 0.5 2 400 A 0.5 3 500 A 0.5 10 600 A 0.5 10 800 A 0.5 10 1000 A 0.5 10Connections P1 (K) primary input, P2 (L) primary output, s1 (k) secondary input, s2 (l) secondary outputNominal thermic short-time current Ith 60 x IpN for 1 s 60 x IpN for 1 sNominal dynamic short circuit current Idyn 2.5 x Ith for 1 s 2.5 x Ith for 1 sPermanent overload 1.2 x IpN 1.2 x IpNInsulation class (IEC 85) E ETest voltage 50Hz/1min. 6 kV 6 kV

Mechanical Mounting quick fastening on DIN rail IEC/EN 60715, wall mounting, directly onto the cable or onto busbarDegree of protection IP30 IP30Secondary connection plug-in terminals 6.3 mm plug-in terminals 6.3 mmPermitted relative humidity 80% 80%Perm. ambient temperature range -20 to +50°C -20 to +50°CMax. temperature of busbars – 70°C

Page 24: Measuring Instruments Measuring Instruments

219 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Operating Hours Counter ASOHC230

Readout Rated Voltage Type Article No. Units per Designation package 5+2 digit 230V 50Hz ASOHC230 167424 1wa_sg04411

Specifi cations | Operating Hours Counter ASOHC230

Description

Connection diagram

Technical Data

Dimensions (mm)

• The operating hours counter registers the operating hours to an accuracy of two decimals (hundredths of a second).• Power supply for terminals 1 and 3 of the electronic counter is required to enable the device to continuously display the measured values. If terminal 3 is

supplied with voltage (at DC “+“), the counting process will get started. • In case of a power failure, the counting result will be saved for an indefi nite period of time (EEPROM). Once power is back again, counting will be continued

from the value that has been saved before.• Time counters are used for a reliable collection of production and service hours, which allows an accurate planning and monitoring of production processes,

maintenance cycles and warranty periods.

ASOHC230Standards DIN VDE 0435-110, DIN EN 60255-6, UL 863Approvals UL 863, UL File No. E300537, CSA C22.2 No. 6 and 55Rated control supply voltage Uc VAC 230Working range at 50/60 Hz x Uc 0,9 ... 1,1Rated frequency Hz 50Rated power loss Pv VA <1Type of operation counting of - hoursDisplay Cyclometer register h 00000,00Terminals ±Screws (Philips) - 1Terminal capacity rigid mm2 1,5 fl exible with wire end sleeve, min. mm2 0,75Allowed range of ambient temperature °C -10 ... +70Degree of protection acc. to DIN EN 60529 - IP20, with conductors connectedProtection class acc. to DIN EN 61140 / VDE 0140 IIAllowed range of air humidity % <80

Page 25: Measuring Instruments Measuring Instruments

220 EATON CORPORATION xxxxx+xxxx-xxxxEN

Measuring Instruments

Pulse Counter ASPC230

Readout Rated Voltage Type Article No. Units per Designation package 7 diigt 230V 50Hz ASPC230 167425 1wa_sg05011

Specifi cations | Pulse Counter ASPC230

Description

Connection diagram

Technical Data

Dimensions (mm)

• The pulse counter sums up the number of pulses, e.g. how many times a device is switched on.• Power supply for terminals 1 and 3 of the electronic counter is required to enable the device to continuously display the measured values. If terminal 3 is

supplied with voltage (at DC “+“), the counting process will get started.• In case of a power failure, the counting result will be saved for an indefi nite period of time (EEPROM). Once power is back again, counting will be continued

from the value that has been saved before.• Pulse counters are used for a reliable collection of production and service hours, which allows an accurate planning and monitoring of production processes,

maintenance cycles and warranty periods.• Pulse counting is used for general quantity counting, registration of the switch-on frequency, and for the collection of switch-on cycles or production quanti-

ties in systems and machines.

ASPC230Standards DIN VDE 0435-110, DIN EN 60255-6, UL 863Approvals UL 863, UL File No. E300537, CSA C22.2 No. 6 and 55Rated control supply voltage Uc VAC 230Working range at 50/60 Hz x Uc 0,9 ... 1,1Rated frequency Hz 50/60Rated power loss Pv VA <1Type of operation counting of - pulsesDisplay Cyclometer register 0000000 LCD Display h -- --Frequency of counting Hz 10Pulse duration ms 50Resetting electrical -- mechanical --Terminals ±Screws (Philips) - 1Terminal capacity rigid mm2 1,5 fl exible with wire end sleeve, min. mm2 0,75Allowed range of ambient temperature °C -10 ... +70Degree of protection acc. to DIN EN 60529 - IP20, with conductors connectedProtection class acc. to DIN EN 61140 / VDE 0140 IIAllowed range of air humidity % <80