medium-voltage switchgear secondary distribution ... · • secondary distribution switch-gear...
TRANSCRIPT
Secondary Distribution SwitchgearType 8DJ10 up to 24 kV,Gas-Insulated
Medium-VoltageSwitchgear
Catalog HA 45.112005
2 Siemens HA 45.11 · 2005
Features
Application, RequirementsContents
© Siemens AG 2005
8DJ10 secondary distributionswitchgear is a factory-assem-bled, type-tested, metal-enclosedswitchgear for indoor installation.
Typical uses
8DJ10 secondary distributionswitchgear is used for power dis-tribution in substations – evenunder severe environmental con-ditions, such as:
• Industrial environments
• Damp, sandy or dusty areas
• Simple outdoor substations
Main uses
• Compact substations
• Compact transformer substations,e.g. for wind power stations
• Garage and vault substations
• Underground and underfloorsubstations
• Substations by pavements,e.g. in systems with extremelysmall construction widths, inparticular the basic versions ofschemes 10 and 71 in conurba-tions
• Substations with control aisle
Technical features
• Secondary distribution switch-gear design with up to 6 feeders
• Maintenance-free
• Climate-independent
• Three-pole primary enclosure,metal-enclosed
• Insulating gas SF6
• Gas-tight, welded switchgearvessel made of stainless steel,with welded-in bushings forelectrical connections andmechanical components
• Three-position switch-discon-nector with load-break andmake-proof earthing function
• Cable connection forbushings with outside cone
• Connection with cable plugs– In ring-main feeders with bolted
contact (M16)– In transformer feeders with
plug-in contact
• Option: Connection withconventional sealing ends
– For thermoplastic-insulatedcables via elbow adapterAKE 20/630 (make Siemens)
– For paper-insulated mass-im-pregnated cables via commer-cially available adapter systems
• Easy installation
Personal safety
• Safe-to-touch and hermeticallysealed primary enclosure
• HV HRC fuses and cable sealingends are only accessible whenfeeders are earthed
• Operation is only possiblewhen the enclosure is closed
• Logical mechanical interlocking
• Capacitive voltage detectionsystem for verification of safeisolation from supply
• Feeder earthing by means ofmake-proof earthing switches
Operating safety
• Hermetically sealed primary en-closure independent of environ-mental effects (dirt, moisture &small animals) – sealed for life:
– Welded switchgear vessel– Welded-in bushings and
operating mechanism
• Maintenance-free operatingmechanism parts (IEC 60 694/VDE 0670-1000)
• Switch operating mechanismsaccessible outside the switch-gear vessel
• Switchgear interlocking withlogical mechanical interlocking
Cost-efficiency
Extremely low “life-cycle costs”throughout the entire productservice life as a result of:
• Maintenance-free concept
• Climatic independence
• Minimum space requirement
• Maximum availability
Standards *
Page
* Standards see also Catalog HA 40.1
Technical Data, Shipping
Electrical data, temperature, filling pressure 4Switchgear installation, shipping data 4
Application, Requirements
Features 2Designs, typical use 3
Product Range
Product range overview, schemes 5Equipment features 5
Design
Panel design 6
Dimensions
Switchgear,floor openings, fixing points 10Cable connection fittings 11
Notes
11
Further Information
See Catalog HA 40.1
Components
Three-position switch-disconnector 7Operating mechanisms 7HV HRC fuse assembly 8Secondary equipment 8Cable connection 9
IEC Standard VDE Standard
IEC 60 694 VDE 0670-1000
IEC 62 271-200 VDE 0671-200
IEC 62 271-100 VDE 0671-100
IEC 62 271-102 VDE 0671-102
IEC 62 265-1 VDE 0670-301
IEC 62 271-105 VDE 0671-105
IEC 61 243-5 VDE 0682-415
IEC 60 282-1 VDE 0670-4
IEC 60 529 VDE 0470-1
IEC 60 071 VDE 0111
IEC 60 044-1 VDE 0414-1
IEC 60 044-2 VDE 0414-2
Secondary Distribution Switchgear Type 8DJ10 up to 24 kV, Gas-Insulated
Siemens HA 45.11 · 2005 3
Secondary Distribution Switchgear Type 8DJ10 up to 24 kV, Gas-Insulated
Application
Our product range comprisesswitchgear consisting of
• Ring-main feeders
• Transformer feeders withHV HRC fuse assemblies
The switchgear is available intwo overall heights:
• 1360 mm(with low subframe)
• 1650 mm(with high subframe)
These overall heights cover allareas of application, from com-pact substations to switchgearrooms with control aisle
Basic design
• Transformer cable connectionabove
• With logical mechanical inter-locks
• With ready-for-service indicator
• With a capacitive voltagedetection system at thering-main feeders
Options
• Capacitive voltage detectionsystem at the transformerfeeders
• Motor operating mechanismsfor the three-position switch-disconnectors of the ring-main and transformer feeders
• Auxiliary switch for three-position switch-disconnectorand make-proof earthing switch
• Short-circuit indicator withbuilt-in housing for ring-mainfeeders
• Surge arresters for ring-mainfeeders
• Shunt releases for trans-former feeders
• Secondary equipment forremote operation or remoteindication, e.g. with local-remote switch in the case ofmotor operating mechanismsor ”trip signal” in the case oftransformer feeders
• Locking devices
• Closing lock-out
• Mounted cable clamps at thering-main feeders
• Further options on request
Designs, typical use
R-HA
45-1
22ce
ps
8DJ10 switchgearwith walk-in access
3 ring-main feeders1 transformer feeder
Scheme 71
2 ring-main feeders1 transformer feeder
Scheme 10
4 ring-main feeders2 transformer feeders
Scheme 62
Ring-main/transformer blocks
R-HA
45-1
19b
eps
R-HA
45-1
21b
eps
R-HA
45-1
20b
eps
4 Siemens HA 45.11 · 2005
Secondary Distribution Switchgear Type 8DJ10 up to 24 kV, Gas-Insulated
Technical Data, Shipping
Electrical data,temperature, filling pressure
SchemeNo.
Version(abbrevi-ations)
Switch-gearheight
mm
Transport dimensions
Width Height Depth
m m m
Vol-ume
m3
Grossweight2)
approx.kg
Transport within Europe by rail, truck, container
Packing with protective PE foil and timber floor
10 2RK+1T 1360 1.10 1.56 1.10 1.89 300
1650 1.10 1.85 1.10 2.24 330
71 3RK+1T 1360 1.45 1.56 1.10 2.49 380
1650 1.45 1.85 1.10 2.95 430
62 4RK+2T 1360 1.80 1.56 1.10 3.09 580
1650 1.80 1.85 1.10 3.66 660
Transport overseas by seafreight
Packing with protective PE foil and seaworthy crate
10 2RK+1T 1360 1.10 2.0 1.15 2.53 350
1650 1.10 2.0 1.15 2.53 380
71 3RK+1T 1360 1.45 2.0 1.15 3.34 460
1650 1.45 2.0 1.15 3.34 510
62 4RK+2T 1360 1.80 2.0 1.15 4.14 680
1650 1.80 2.0 1.15 4.14 760
Abbreviations:
RK = Ring-main feederT = Transformer feeder
Switchgear installation,shipping data
Electrical data
Rated voltage Ur kV 7.2 12 15 17.5 24
Rated insulation level:Rated short-duration power kVfrequency withstand volt. Ud
20 28 1) 36 38 50
Rated lightning impulse kVwithstand voltage Up
60 75 1) 95 95 125
Rated frequency fr 50/60 Hz
Rated normal current Irfor ring-main feeders 400 A or 630 Afor transformer feedersdepending on theHV HRC fuse link
200 A
Rated short-time kAwithstand current Ik, 1 s kA
kA
–2025
–2025
–2025
162025
1620–
Rated short-time kAwithstand current Ik, 3 s (option)
20 20 20 20 20
Rated peak withstand kAcurrent Ip kA
kA
–5063
–5063
–5063
405063
4050–
Rated short-circuit makingcurrent Ima
for transformer feeders kA 25 25 25 25 25for ring-main feeders kA
kAkA
–5063
–5063
–5063
405063
405063
Ambient temperature T – 40 to +70 °C
Pressure values at 20 °Cfor the insulation:
Ratedfilling pressure pre
1500 hPa (absolute)
Minimumoperating pressure pme
1300 hPA (absolute)
Temperature, filling pressure Shipping data
Switchgear installation
����
����
��
�������������� ����� �� �
�
�
�
�
�
1 Switchgear
2 Floor openinginto cable duct
3 Cooling sheets madeof expanded metal
4 Direction of pressure relief
5 Cable
6 Sheet-metalpartition (not includedin the scope of supply)
DownwardsTo the rear (on request)
Wall-standing arrangement
DownwardsOverall height 1360 mm
Direction ofpressure relief
Overall height 1650 mm
2) Weight depending on the relevant equipment,e.g. motor operating mechanism
1) 42 kV/95 kV according to some national requirements
Secondary Distribution Switchgear Type 8DJ10 up to 24 kV, Gas-Insulated
Siemens HA 45.11 · 2005 5
Product Range
Equipment features of panelsProduct range overview, schemes
Scheme Overall dimensions Netweight1)
approx.kg
Width
mm
Depth
mm
Height
mm
Block types,consisting of ring-main and transformer feeders
Scheme 10
2 ring-main feeders and1 transformer feeder
(Abbreviations 2RK+1T)
710 775 13601650
270300
Scheme 71
3 ring-main feeders and1 transformer feeder
(Abbreviations 3RK+1T)
1060 775 13601650
340390
Scheme 62
4 ring-main feeders and2 transformer feeders
(Abbreviations 4RK+2T)
1410 775 13601650
500580
����
����
����
�� ��
�
��
����
����
����
�� �� ��
�
��
����
����
����
�� �� �� ��
� �
�� ��
1) Weight depending on the relevant equipment,e.g. motor operating mechanism
5) Cable routing optionally:– To the rear (standard)– Upwards (option)– To the right (option)
6) Cable routing optionally:– To the rear (standard)– Upwards (option)
Abbreviations:
RK = Ring-main feederT = Transformer feeder
Equipment
Ring-mainfeederspanels RK
Transformerfeederspanels T
Manual operating mechanism forthree-position switch-disconnector:
– As spring-operated mechanism– As spring-operat./stored-energy mech.
•–
–•
Motor operating mechanism forthree-position switch-disconnector ° °Interlock of cable compartmentcover for ring-main feeders • x
Interlock of HV HRC fuse compartmentand transformer cable connectioncompartment
x •
Cable bracket 2) in ring-main feeders,cable routing downwards • x
Cable connection in transformer feeder(cable fixing by customer, suppliedwithout cable bracket) for cable routing
– To the rear (standard)for cable elbow plugs or
– Upwardsfor straight cable plugs or
– To the rightfor cable elbow plugs
x
x
x
•
or °or ° 3)
Low-voltage terminals in theoperating mechanism(option for secondary equipment)
• •
Shunt release – °Auxiliary switch for– Switch-disconnector CLOSED/OPEN:
1 NO + 1 NC– EARTHING CLOSED/OPEN:
1 NO + 1 NC°°
°°
Locking device forthree-position switch-disconnector ° °Short-circuit or earth-fault indicator– Wiring at the indicator (standard)– Wiring on the terminal (option) °
°––
Closing lock-out forthree-position switch-disconnector ° –
Double cable connection for
– Overall switchgear height 1360 mm– Overall switchgear height 1650 mm °
°xx
Surge arrester for
– Overall switchgear height 1360 mm– Overall switchgear height 1650 mm ° 4)
°xx
Mounted cable clamps ° x
Abbreviations:
RK = Ring-main feederT = Transformer feeder
3) For scheme 62 only possiblefor the right-hand feeder
4) Only possible for– 105 mm deeper
cable compartment coverand
– 300 mm deepercable compartment cover
2) For overall switchgearheight 1360 mm:Cable bracket below the feeder
• Basic equipment
° Additional equipment (option),further additional equipmenton request
x Not applicable
– Not available
Secondary Distribution Switchgear Type 8DJ10 up to 24 kV, Gas-Insulated
6 Siemens HA 45.11 · 2005
����
����
����
��
��
��
��
��
�
��
��
��
��
��
Panel design (example)
Design
11 HV HRC fuse assembly, cover removed
12 Interlock for HV HRC fuse assembly
13 Mimic diagram for transformer feeder
14 Rating and type plate
15 Mimic diagram for ring-main feeder
16 Arrangement of cable connections
17 Cable elbow plug with plug-in contact
18 Bushing as interface type “A“for cable plugs with plug-in contact
19 Connecting bar to cable connection
20 Three-position switch-disconnector
21 Switchgear vessel, filled with gas
22 Cable connection compartment
23 Straight cable plug with plug-in contact
24 Cover of the HV HRC fuse compartmentand of the transformer cable connectioncompartment
25 Spring-operated/stored-energy mechanism
26 Cable connection compartment cover
27 M12 earthing connection
28 Pressure relief device
29 Cable bracket in ring-main feeder
30 Spring-operated mechanism
31 Bushing as interface type “C“ for cableplugs with bolted contact (M16)
32 Elbow adapter AKE 20/630for conventional cable sealing end(bolted contact M16)
33 Cover in transformer feederfor cable routing to the right
Ring-main/transformer block Transformer feeder
Section A-A
Cable connection with bolted contact (M16)optionally for:– Cable T-plugs or cable elbow plugs– Elbow adapter AKE 20/630 (make Siemens)
for conventional cable sealing ends
Ring-main feeder
Section B-B
Personal safety
All feeder-related covers can only beopened if the associated three-positionswitch-disconnector has been switchedto the “EARTHED” position.
Design options for the transformercable connection, see table on page 9(cable fixing always by customer)
����
����
����
������
�
�
�
�
�
�
�
�
��
��
��
��
��
��
��
�
�
��
��
�
1 Feederdesignation label
2 Sockets forvoltage detectionsystem
3 Ready-for-serviceindicator
4 Switch positionindication forearthing function“OPEN – EARTHED“
5 Switch position indicationfor load-break function“CLOSED – OPEN”
6 Locking device(option for three-position switch-disconnector)
7 Manual operationfor the mechanismof the earthingfunction
8 Manual operationfor the mechanismof the load-breakfunction
9 Short-circuit/earth-faultindicator (option)
10 Interlock of thecable compartment cover
Scheme 10
����
����
����
�
�
��
��
��
��
��
��
�
��
�
�
��
�
OptionCable connection for straightcable plugs with plug-in contact,cable routing upwards
StandardCable connection for cableelbow plugs with plug-in contact,cable routing to the rear
Option (only for schemes 10 and 71)Cable connection for cableelbow plugs with plug-in contact,cable routing to the right
Secondary Distribution Switchgear Type 8DJ10 up to 24 kV, Gas-Insulated
Siemens HA 45.11 · 2005 7
Three-position switch-disconnector, operating mechanisms
Components
Three-positionswitch-disconnector
The proven three-positionswitch-disconnector is used asswitching device.
Functions
• Load-break function
• Earthing function with short-circuit making capacity
• Switch positionsCLOSED – OPEN – EARTHED
Operating mechanisms
The three-position switch-disconnector is operated fromthe switchgear front via
Detachable lever mechanism
• Spring-operated mechanism– With “spring-operated
CLOSED” and“spring-operated OPEN”for use in ring-main feeders
• Spring-operated/stored-energy mechanism
– With “spring-operatedCLOSED”and“spring-operated OPEN”for use in transformer feeders
– With an additional energystore device for the function“stored-energy OPEN”after being tripped by theHV HRC fuse (striker pintripping) or by the shuntrelease
Options
• Motor operating mechanismfor switch-disconnector
• Locking devices
• Auxiliary switch for three-position switch-disconnectorand make-proof earthingswitch
• Shunt release for transformerfeeders
• Closing lock-out for ring-mainfeeders
• Different operating levers 1)
for the operating mechanismsof the switch-disconnectorand the make-proof earthingswitch
Three-position switch-disconnector
R-HA
45-1
23ep
sR-
HA45
-103
aep
s
3
1
2
Three-position switch-disconnector
Rear view of the switchgear vessel of aring-main/transformer block, scheme 10
1 Three-position switch-disconnectorin the transformer feeder
2 Three-position switch-disconnectorin the ring-main feeders
3 Pressure relief device
Operating mechanisms
Control boardfor detachable lever mechanisms(standard)
ExampleRing-main/transformer block,scheme 10
4 Locking device (option)for the detachable lever mechanism
5 Detachable lever mechanismfor the earthing function
6 Detachable lever mechanismfor the load-break function
7 Detachable lever mechanismfor the ring-main feeder
8 Detachable lever mechanismfor the transformer feeder
R-HA
45-1
24a
eps
R-HA
45-1
05ep
s
R-HA
45-1
04ep
s
5
4
6
7
8
On request:Control boardfor rotary operating mechanisms
ExampleRing-main feeder
9 Symbols for the actuating directionof the rotary operating mechanism
10 Locking device for therotary operating mechanism
11 Rotary operating mechanism
R-HA
45-1
06a
eps
R-HA
45-1
07ep
s
119
10
1) According to VDN */ VDEW **recommendation
* Association of German NetworkOperators VDN e.V. at the VDEWin Germany (as of 2003)
** Association of German PowerStations VDEW e.V.
Secondary Distribution Switchgear Type 8DJ10 up to 24 kV, Gas-Insulated
8 Siemens HA 45.11 · 2005
HV HRC fuse assembly, secondary equipment
HV HRC fuse assembly
The HV HRC fuse boxes areprovided with single-phaseinsulation and are locatedabove the transformer feederoutside the switchgear vessel.
Standards
HV HRC fuse links with strikerpin in “medium” versionaccording to
• IEC 60 282-1 *
• VDE 0670 Parts 4 and 402
• DIN 43 625main dimensions
Features
• Access to the HV HRC fusecompartment and replace-ment of HV HRC fuses isonly possible if the transfor-mer feeder has been iso-lated and earthed
• Requirements fulfilled as HValternating current switchfuse combination *
• Selection of HV HRC fusesfor transformers
• Thermostatic protectionsystem protects the switch-gear against the effects ofan incorrectly inserted fuselink
• Thermal striker trippingwhen using an appropriateHV HRC fuse link, e.g. makeSiemens, type 3GD1
• HV HRC fuses are easy toreplace
Secondary equipment(option)
Examples:
• Auxiliary contacts
• Motor operating mechanisms
• Shunt releases
Wiring
Auxiliary contacts, motoroperating mechanisms or shuntreleases are wired to a terminalstrip, itself located next to theoperating mechanism assemblyof the relevant feeder.
Wiring is led in by the custo-mer from the side or rear andconnected to the terminal stripallotted to the operating mecha-nism assembly.
HV HRC fuse compartment
* Standards see Catalog HA 40.1
Secondary equipment (option)
HV HRC fuse compartment withcable compartment cover removed
Phase L1:HV HRC fuse box withHV HRC fuse slide removed
Phase L2:HV HRC fuse box closed
Phase L3:Replacement of HV HRC fuses
Auxiliary contacts, motor operatingmechanism and shunt release
Operating mechanism components at thespring-operated/stored-energymechanism of a transformer feeder:
1 Motor operating mechanism
2 Auxiliary contacts
3 Terminal strip
4 Shunt release
L1 L2 L3
1
2
3
4
R-HA
45-1
12ep
sR-
HA45
-129
aep
s
Components
Secondary Distribution Switchgear Type 8DJ10 up to 24 kV, Gas-Insulated
Siemens HA 45.11 · 2005 9
Cable connection
• Bushings according toEN 50 181/DIN EN 50 181 1)
with outside cone
• Access to the cable con-nection compartment only ifthe feeder has been isolatedand earthed
Ring-main connection
• With bolted contact (M16) asinterface type “C“ accordingto EN 50 181/DIN EN 50 181
• Cable connection at one level
• For thermoplastic-insulatedcables
• For paper-insulated mass-impregnated cables withadapter systems
• For conventional cable sealingends via elbow adaptersAKE 20/630 (make Siemens)
• For cable T-plugs or cableelbow plugs with boltedcontact
• For connection cross-sectionsup to 300 mm2 (standard)
• Cable routing downwards,cable connection at front
• For rated normal currentsof 400 A or 630 A
Options
• Suitable for the connectionof surge arresters
• Short-circuit/earth-faultindicator
• Mounted cable clamps
• Double cable connection withcorresponding cable plugs
Transformer cable connection
• With plug-in contact as inter-face type “A” according toEN 50 181/DIN EN 50 181
• For thermoplastic-insulatedcables
• For cable elbow plugs (stand-ard) or straight cable plugswith plug-in contact
• For connection cross-sectionsup to 120 mm2
• For rated normal currentsof 200 A
Option
• Cable routing upwards or tothe right
R-HA
45-1
30ep
sR-
HA45
-111
eps
1) Standard EN 50 181/DIN EN 50 181:“Plug-in bushings above1 kV up to 36 kV and from 250 A to1.25 kA for equipment other thanliquid-filled transformers.”
Cable plugs, cable sealing ends andcable clamps are not included in thescope of supply.
Cable connection (examples)
Cable connection compart-ment, as delivered(front view)
Cable plugs withbolted contact (M16)
R-HA
45-1
28ep
s
Cable connectionsin ring-main feeder
1 Prepared for cable plugswith bolted contact (M16)
2 Phase L1:Make: Euromold,type K400 LBas cable elbow plug
3 Phase L2:Make: Euromold,type K400 TBas cable T-plug
4 Phase L3:Make: Euromold,type AGT 20/630as cable T-plug
Option:Mounted cable clamps
Cable connection,as delivered(side view)
Cable elbow plug withcable routing to the rear
R-HA
45-1
31ep
s
1
6
2
3
4
Cable connectionsin transformer feeder
5 Prepared for cable plugswith plug-in contact
6 Phase L1:Make: Euromold,type K158 LR
7 Phase L2:Make: nkt cables,type EASW 20/250
8 Phase L3:Make: Cooper,type DE 250-R-C
Cable routing to the rear,cable fixing by customer
5
L1 L2 L3 L3L2L1
L3 L2 L1 L1L2L3
7
8
Transformer cable connection for cable plugswith plug-in contact as interface type “A“Arrangement ofconnections
Cable routing Cable plugversion
Above, besidethe HV HRCfuse assembly
To the rear (standard) Cable elbow plug with plug-in contactfor all schemes
To the right (option) Cable elbow plug with plug-in contact– For schemes 10 and 71– For scheme 62: only possible for the
right transformer feeder
Upwards (option) Straight cable plug with plug-in contactfor all schemes
Components
Secondary Distribution Switchgear Type 8DJ10 up to 24 kV, Gas-Insulated
10 Siemens HA 45.11 · 2005
Switchgear, floor openings (dimensions in red) and fixing points
Dimensions
Block types, consisting of ring-main feeders and transformer feeders · optionally in 2 overall heights�������������
��
���
��
��
��
���
����
���
�
� �
����
��
���
��
���
���
��������
�
�
�
�
�
������������
���
�����
��
��
����
����
����
����
����
���
�� ��
��� ���
�
�
�
����
����
����
����
����
����
�
�� �� ��
��� ��� ���
�
�
�������������� � �
����
����
���
����
����
����
�
�� �� �� ��
��� ��� ��� ���
� �
�
������������� �
�
�� ����
For missing dimensionssee scheme 10
Floor openings and fixing points
Scheme 71
For missing dimensionssee scheme 10
Floor openings and fixing points
Scheme 62
Floor openings and fixing points
Scheme 10
Sections
Section A-A Section B-B
Ring-main feeder RK Transformer feeder T The cables and cable plugs shown hereare not included in the scope of supply.
1 Wall distance
2 Fixing points
3 Position of the incoming cablesin the ring-main feeder
4 Position of the incoming cablesto the rear in the transformer feeder (standard)
5 Floor opening for high-voltage cables
6 Fixing frame (base) of the switchgear
* Depending on the type of cable plug
** Dimensions depending on the overallswitchgear heights 1360 and 1650 mm
*** Dimensions depending on the overallswitchgear heights 1360 and 1650 mm,slight deviations are possible due to thevarious makes of cable elbow plugs
B Dimension for bushing as interface type “C“with bolted contact (M16)
��������������������� ����
� ��
�
����� ��
�
���
��
�
����
��
�������������������������
����
����
���
�
��
Plan view
Secondary Distribution Switchgear Type 8DJ10 up to 24 kV, Gas-Insulated
Siemens HA 45.11 · 2005 11
Notes
If not stated otherwise onthe individual pages of thiscatalog, we reserve the rightto include modifications, espe-cially regarding the stated val-ues, dimensions and weights.
Drawings are not binding.
All product designations usedare trademarks or productnames of Siemens AG or othersuppliers.
If not stated otherwise, alldimensions in this catalog aregiven in mm.
The information in this docu-ment contains general de-scriptions of the technicaloptions available, which donot always have to be presentin individual cases.The required features shouldtherefore be specified in eachindividual case at the time ofclosing the contract.
KGK 12.05 0.0 VO/- 12 En101720 6101/C6059
Cable connection fittings in ring-main feedersExamples for an overall height of 1650 mm
Standard cable compartment cover
������������������������� ���
����
��
�
�������
����� � ��
�
���������
�
� �
� �
Single cable connection
1 Elbow adapter, make: Siemens, type AKE 20/630with conventional cable sealing end,make: Corning Cables, type IAE 20
2 Cable T-plug, make: Euromold, type (K) 400 TB/TBS
Footnotes for alldimension drawings
* Max. mounting spacefor cable and/orsurge arrester
** Depth of floor opening
B Dimension for bushingwith bolted contact(M16)
1) Make:Tyco Electronics Raychem
Dimension a
– 610 mm up to type RDA21– 635 mm for type RDA24
Standard cable compartment cover
� �
��
�
������������ �
�������������� ��� �
�
����
��
�
�����
�
�
� �
��
���
�������������
����
����
����
Standardcable compartment cover
Standardcable compartment cover
150 mm deepercable compartment cover���������������������������� ���
� �
����
��
�
����������
������
�
��������
���
���
� �
����
��
105 mm deeper cable compartment coverStandard cable compartment cover
Cable connection with surge arresters
3 Cable plug, make: Tyco Electronics Raychem, type RICS 5139
4 Surge arrester 1), types up to RDA21 or RDA24
5 Cable plug, make: nkt cables, type CB 24-630
6 Surge arrester, make: nkt cables, type CSA 24-5
7 Cable plug, make: Euromold, type (K) 400 TB/TBS
8 Surge arrester, e.g. make: Euromold, type 400 Pbor similar types
Double cable connection
9 Cable T-plug, make: nkt cables, type CB 24-630 and CC 24-630
10 Cable T-plug, make: Südkabel (ABB), 2 x type SET (12/24)with coupling insert KU 23.2
Dimensions
Responsible for
Technical contents:Christoph MaulSiemens AG, Dept. PTD M 2 PPMErlangen
General editing:Gabriele PollokSiemens AG, Dept. PTD CC MErlangen
www.siemens.com/medium-voltage-switchgear
If you have any questions aboutPower Transmission and Distribution,our Customer Support Centeris available around the clock
Tel: +49 180 / 524 70 00Fax: +49 180 / 524 24 71
E-Mail: [email protected]/energy-support
(Subject to charges,e.g.: 12 ct/min.)
Published by
Siemens AG
Power Transmission and DistributionMedium Voltage DivisionPostfach 32 40
91050 ErlangenGermany
Order No.: E50001-K1445-A111-A8-7600