metal clad mv switchgear - e-i-eng.com

5
METAL CLAD MV SWITCHGEAR P4S PRODUCT RANGE

Upload: others

Post on 02-Oct-2021

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: METAL CLAD MV SWITCHGEAR - e-i-eng.com

METAL CLAD MV SWITCHGEARP4S PRODUCT RANGE

Page 2: METAL CLAD MV SWITCHGEAR - e-i-eng.com

E+I Engineering’s Metal Clad MV switchgear range is an indoor air

insulated switchgear for medium voltage power distribution

P4 Series (P4S) is an indoor air insulated switchgear for medium

voltage power distribution. This new series of switchgear is based

around the ethos of safety and reliability and is a result of E+I

Engineering group’s quest for continuous innovation and long-term

R&D commitment.

The modular construction of the range allows E+I Engineering’s

team of expert engineers to customise each medium voltage power

solution based on individual project specification.

Key features:

– Circuit breaker is withdrawable for maintenance

– Integration of internal arc prevention technologies

– Vacuum Technology for safe, compact and reliable performance

– Compact and modular designfor increased project flexibility.

– Comprehensive mechanical and electrical interlocks for safety and

prevention of maloperation

Standards

The P4S range is type

tested and certified by an

NRTL. It is manufactured in a

certified management system

environment where Quality ISO

9001, Safety OHSAS 18001and

Environmental ISO 14001

standards are applied to all

aspects of the manufacturing

and installation processes. It is

manufactured in accordance

with ANSI C37.20.2

Type Tests

– Dielectric tests

– Power frequency withstand test

– Lightning impulse withstand test

– Measurement of the resistance

of the main circuits

– Temperature-rise tests

– Short-time withstand current

and peak withstand current tests

– Verification of the IP coding

– Additional tests on auxiliary and

control circuits

– Verification of making and

breaking capacities

– Mechanical operation tests

– Verify the protection of persons

against dangerous electrical

effects

– Internal arc test

ETL Certified

E+I Engineering have

undergone an extensive

testing program independently

witnessed and certified by

ETL to ensure the P4S range

meets the requirements of

ANSI C37.20.2 Metal Clad

Switchgear

STANDARDS

OHSAS 18001:2007 OHS 533652

ISO 9001:2015 FM 12680

ISO 14001:2015 No: EMS 566536

All certificates available on request

2 www.e-i-eng.comwww.e-i-eng.com 1

MV SWITCHGEARMETAL CLAD P4S PRODUCT RANGE

Page 3: METAL CLAD MV SWITCHGEAR - e-i-eng.com

SWITCHGEAR STRUCTURE

The panel is divided into 6 independent compartments which are

1. Cable Compartment

The cable compartment is accessible from the rear door. This door has

an interlock with the earth switch ensuring that the door will only open

when the earth switch is closed.

2. Potential transformer compartment

The potential transformer (PT) compartment allows for a withdrawable

PT to be connected and racked in. An interlock on the PT truck

ensures that the door must be closed before the PT is racked in.

3. Vacuum circuit breaker compartmentThe vacuum circuit breaker (VCB) compartment houses the

withdrawable VCB. An interlock on the VCB truck ensures that door

must be closed before the VCB can be racked in to the service

position.

4. Main busbar compartment

The main busbar compartment houses the main horizontal inter-

connecting bus. It is accessed via a removable panel at the rear of the

switchgear.

5. Plenum Assembly

If required the plenum assembly is bolted to the top of the enclosure,

the plenum assembly can be extended past the Switchgear to an

external wall.

6. Low voltage control compartment

The low voltage control compartment houses all the main control

and protection relays required. There is a direct connection from this

compartment to the wiring plug connected to the VCB.

SWITCHGEAR STRUCTURE

EnclosuresThe enclosure and partition are made from high quality cold rolled mild steel or galvanized sheet steel, the

processing of these materials is carried out by CNC punch and multiple edge folding technology. The panels

used within the structure are secured by means of riveting or high tensile nut and bolt.

– Side sheets are made from durable 11 gauge sheet steel incorporating advanced double bend technology

to ensure additional structural strength

– Gland plates made from 10 gauge stainless steel

– Exterior paint in RAL 7035 light grey

– Doors with integral strength enhancing struts

– Viewing window for visual confirmation of VCB status

Product Dimensions

24” (30”) 60”

91”

A

B

C

Rating (A) width A (in) height B (in) depth C (in) Weight (lb)

15kV

1200 24 92 60 1,760 – 2,640

2000 30

1200 with side cover 26

2000 with side cover 32

4 www.e-i-eng.comwww.e-i-eng.com 3

MV SWITCHGEARMETAL CLAD P4S PRODUCT RANGE

Page 4: METAL CLAD MV SWITCHGEAR - e-i-eng.com

TECHNICAL DATA

P4S Switchgear Technical Data

item 15kV

Rated Frequency Hz 50/60

Rated power frequency (60s) kV 36

Rated Lightning impulse withstand voltage (peak) kV 95

Rated current A 630, 1200, 2000

Rated short-time withstand current (3s) kA 31.5

Rated Peak withstand current kA 82

Degree of protection IP IP4X, Nema1 indoor construction

ESW Earthing Switch Technical data

Rated withstand voltage at power frequency (60s) kV 36

Rated lightning impulse withstand voltage (peak) kV 95

Rated short-time withstand current (3s) kA 31.5

Rated Peak withstand current kA +82

Phase space in 5.9, 8.3

Normal Service Conditions

Ambient air temperature °C

Maximum +40

Maximum 24h average +35

Minimum 24h average -5

Minimum recommended +5

Altitude above sea level Meters (m)

Maximum 1000

Conditions of humidity %

Average value of relative humidity (24h) ≤ 95

Average value of relative humidity (1 month) ≤ 90

Pollution The ambient air must not be significantly polluted by dust,

smoke, corrosive and/or flammable gases, vapours or salt.

SWITCHGEAR OPTIONS

The modular construction of the range allows customers to tailor each medium voltage power

solution based on individual project specification.

– Choice of protective relays, Transfer Controllers, Generator Controllers or Paralleling Controls for

increased performance flexibility.

– CB Control Switches, Lock out Relays, Annunciator lights, etc. can be adde

– Optional Integrated Grounding Switch or grounding truck available

Protection Relays

Choice of protection relays from all major manufacturers including SEL, ABB Relion series, Micom and GE Multilin

Vacuum Circuit Breakers

ABB VD4 circuit breakers

6 www.e-i-eng.comwww.e-i-eng.com 5

MV SWITCHGEARMETAL CLAD P4S PRODUCT RANGE

Page 5: METAL CLAD MV SWITCHGEAR - e-i-eng.com

WWW.E-I-ENG.COM

Email:[email protected]

E+I Engineering USA CorpUSA Manufacturing Location

400 Supreme Industrial DriveAnderson South Carolina29621

Tel: +1 864 375 1757

E+I Engineering Ltd. European Manufacturing Location

BallyderowenBurnfoot Co.DonegalIreland

Tel:(UK) +44 (0)28 71353030(ROI) +353 (0)74 9368719

Powerbar Gulf LLCMiddle East Manufacturing Location

N16/N17Al Ghail Industrial ParkRas Al KhaimahPO Box 13229UAE

Tel: +971 (0) 7221 6100

E+I Engineering Ltd. UK Central Office

Campsie Industrial EstateDerryNorthern IrelandBT47 3XY