metal-enclosed interrupter switchgear type simosec, up to 27.6 kv

44
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Medium-Voltage Switchgear Catalog HA 41.31 · 2008 Answers for energy.

Upload: vanliem

Post on 05-Jan-2017

226 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear

Type SIMOSEC, up to 27.6 kV, ANSI,

Air-Insulated, Extendable

Medium-Voltage Switchgear

Catalog HA 41.31 · 2008

Answers for energy.

Page 2: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 20082

Application, Requirements Page

Typical uses, features 2 to 4

Technical Data

Electrical data, pressure values,temperature 5

Switchgear installation 6

Shipping data 7

Product Range

Product range overview, equipmentfeatures 8 and 9

Panels 10 to 18

Design

Panel design 19

Components

Two/three-position switch-disconnector 20

Two/three-position switch 21

Busbars, HV CL (current-limiting)fuse assembly 22 and 23

Operating mechanisms 24

Indicating and measuring equipment 25

Transformers 26 and 27

Cable connection 28 and 29

Dimensions (in mm/inch)

Panels 30 to 38

Floor openings, fixing points 39

Standards

Standards, specifications, guidelines 40 and 41

Notes

42

Invalid: Catalog HA 41.31 · 2007

SIMOSEC ANSI switchgear

R-HA

41-0

86ep

s

© 2008 Siemens Power Transmission & Distribution, Inc.SIEMENS is a registered trademark of Siemens AG.

Contents Application

Page 3: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

3Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

R-HA

41-1

09ep

s

R-HA

41-1

12ep

s

R-HA41-110 eps

R-HA41-111 eps

R-HA

41-0

85ep

s

Application

Typical uses

Page 4: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 20084

Reliability

• Type (design) tested withthird-party witness

• Standardized and manu-factured using numericallycontrolled machines

• Quality management systemaccording to ISO 9001

• More than 500,000 switchgearpanels in operation worldwidefor many years

• No cross-insulation betweenphases

Personal safety

• All switching operations canbe performed with closedpanel front

• Metal-enclosed switchgear

• HV CL fuses and cable termi-nations are only accessiblewhen the outgoing feedersare grounded

• Logical mechanical inter-locking

• Capacitive voltage detectionsystem for verification of safeisolation from supply

• Grounding of outgoing feedersby means of make-proofgrounding switches

Security of operation

• Components, e.g., operatingmechanisms, three-positionswitches proven for years

• Metal-enclosed panels plusmetal compartmentalizationbetween busbar and switchingdevice and between switchingdevice and cable connectioncompartment

• Three-position switch metal-enclosed with gas-insulatedswitching functions

– Welded sealed-for-lifeswitchgear vessel

– No cross-insulation betweenphases

– With welded-in bushings forcable connection, busbar andoperating mechanism

• Switch operating mechanismsoutside switchgear vessel

• Maintenance-free operatingmechanism parts

SIMOSEC ANSI switchgearis a factory-assembled, type-tested, three-phase, metal-enclosed, indoor switchgearaccording to ANSI/IEEEC37.20.3 * for single busbars.

Typical uses

SIMOSEC ANSI switchgear isused for power distribution indistribution systems withfeeder currents up to 1200 A.

Modular space-saving designallows use in

• Substations, customer trans-fer substations, distributionsubstations and switchingsubstations of power supplyand public utilities

• Public buildings, such ashigh-rise buildings, railwaystations, hospitals

• Industrial plants

Typical examples

• Office parks

• Airports

• Underground railway stations

• Sewage treatment plants

• Schools

• Shopping centers

• Petroleum industry

• Chemical industry

• Industrial plants

• Textile, paper andfood industry

Modular design

• Individual panels, for freecombination and extension

Technical features

• Air-insulated indoorswitchgear

• Gas-insulated, maintenance-free switching functions forthe two/three-position switch

• Three-pole primary enclosure

• Phases arranged one behindthe other

• No cross-insulation betweenphases

• Busbar system at the top orbottom, as required by appli-cation

• Air-insulated busbar and cableconnection system

• Two/three-position switch,metal-enclosed, with air-insulated primary terminalsand gas-insulated switchingfunctions

• Hermetically-sealed (welded)stainless-steel switchgearvessel,

– For switching devices– With welded-in bushings

(for electrical connectionsand mechanical components)

– With insulating gas SF6

• Metal-enclosed design

• Pressure relief– To the rear and upwards– Separately for each

compartment

• Air-insulated cable connectionsystem for conventional cablelugs

• Three-phase current trans-former, factory-assembled onthe feeder bushings

• Integrated low-voltage niche(standard) for installationof low-voltage devices

– E.g. terminals, pushbuttons– MCBs

• Option: Space heaters forsevere ambient conditions,e.g. condensation

• Mechanical switch positionindications integrated inmimic diagram

• Switchgear interlockingsystem with logicalmechanical interlocks

Life-cycle cost-efficiency

Extremely low life-cycle costsand extremely high availabilitythroughout the entire productservice life cycle as a result of:

• Two/three-position switchwith gas-insulated quenchingprinciple

• Minimum space requirement

• Easy switchgear extension

Electrical features

• Rated voltages up to 27.6 kV

• Rated short-circuit current(fused) up to 63 kA at 15 kVand below, and 20 kA at27.6 kV

• Rated short-time withstandcurrent up to 20 kA, 2 secondor 25 kA, 2 seconds

• Rated normal current offeeders

– Up to 600 A (feeders)– Up to 1200 A

(panel without switch)

• Rated normal current ofbusbar up to 1200 A

* Standards see page 40

Features

Application, Requirements

Page 5: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

5Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

1) The rated continuous currents apply to ambient temperatures of 40 °C/104 °F.

2) Pressure values for SF6-insulated vessels.

3) The fuse assembly is designed for a reference dimension “e” = 537 mm/21.1 inch.With reference dimension “e” = 442 mm/17.4 inch, an extension tube(95 mm/3.7 inch long) is required.

4) Depending on the HV CL fuse links.

5) Fused

6) Without fuses

Complete switchgearRated insulation level Rated voltage Ur kV 4.76 15 27.6

Rated short-duration (one minute) power-frequencywithstand voltage Ud, rms

kV 19 36 60

Rated lightning impulse withstand voltage Up, peak kV 60 95 125Rated frequency fr Hz 50/60Rated continuous current Ir

1)

of busbarOn request A 600Standard A 1200

Rated short-circuit current for switchgear with all feeders fused (panel type FS) kA (sym) 63 63 20kA (asym) 101 101 32kA (peak) 164 164 52

Rated short-time withstand current Ik6) for switchgear with tk = 2 s rated duration up to kA 20 25 20 25 20

Rated peak withstand current Ip6) up to kA 52 65 52 65 52

Rated filling pressure pre2) PSI (kPa)

at 20 °C/68 °F(absolute)

21.8 (150)Minimum operating pressure pme

2) 18.9 (130)

Ambient temperature T for panels without secondary equipment °C/°F -30 to +40 / -22 to +104

Cable switch panel type CS, cable connection panel type CC, cable grounding panel type CG

Rated voltage Ur kV 4.76 15 27.6

Rated continuous current Ir1) for panel type CS, CG A 600

only for panel type CC A 600, 1200Rated fault closing current Ima

6) only for panel type CS kA (asym) 32 40 32 40 32kA (peak) 52 65 52 65 52

Fuse panel types FS, FU

Rated voltage Ur kV 4.76 15 27.6

Rated continuous current Ir1) 4) for feeder A 200, 600

Rated peak withstand current Ip5) up to kA 164 164 52

Rated fault closing current Ima5) only for panel type FS kA (asym) 101 101 32

kA (peak) 164 164 52Reference dimension “e“ 3) for HV CL (current limiting) fuses mm/inch 537/21.1Maximum fuse rating for panel FS-1 A 450E 200E 65E

for panel FS-2 A two 350E two 200E two 65Efor panel FS-3 A three 200E three 200E three 65E

Busbar grounding panel type BG

Rated voltage Ur kV 4.76 15 27.6

Rated fault closing current Ima6) kA (asym) 32 40 32 40 32

kA (peak) 52 65 52 65 52

Busbar voltage metering switch panel types MS2, MS3

Rated voltage Ur kV 4.76 15 27.6

Rated peak withstand current Ip5) up to kA 52 65 52 65 52

Rated fault closing current Ima5) kA (asym) 32 40 32 40 32

kA (peak) 52 65 52 65 52

Metering panel types MT3, MC3, bus riser panel BR

Rated voltage Ur kV 4.76 15 27.6

Rated continuous current Ir1) A 600, 1200

Technical Data

Electrical data of panels, pressure values, temperature

Page 6: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 20086

���������� �

��������

���������

��������

����

����

����

�������� �����������

�������

���������

���������

��������

����

����

����

��

��

����

����

����������� �

��������

���������

��������

��������

�������

���������

���������

��������

�����������

��

Room planning

Switchgear installation

Wall-standing or free-standingarrangement– Single row– Double row (for face-to-face

arrangement)

Room dimensions

See opposite dimensiondrawings

Door dimensions

The door dimensionsdepend on the– Number of panels in a

transport unit– Height of the panel

Switchgear fastening

• For floor openings andfixing points of the switch-gear, see page 39

• Foundations:– Steel structure– Steel-reinforced concrete

Panel dimensions

See pages 30 to 38

Weight

The weight of a panel dependson the extent to which it isequipped (e.g. with motoroperating mechanism, voltagetransformer). For details,please refer to page 7.

1 Relief opening

2 Direction of pressure relief

3 Pressure relief of switchgear

4 Room height

5 Individual panel depth

6 Control aisle

7 Option: Floor cover

8 Cable

9 Foundation

10 Height of cable basement corresponding tocable bending radius

11 Wall distance

12 Side wall distance

13 Panel width

14 End wall

15 Depth of pressure relief duct

Room planning (dimensions in mm/inch)

Plan view Plan view

Wall-standing arrangement (side view) Free-standing arrangement (side view)

Cable basement Cable basement

Switchgearroom

Switchgearroom

* Switchgear height 2250 mm /88.5" or 2550 mm / 100.5"

** Depending on bending radius ofcable

*** 950/37.5 distance shown is thespace required by the equipment.The actual space must alsoreflect requirements of applicablecodes (e.g. NEC) or standardsand regulations.

Switchgear installation

Technical Data

Page 7: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

7Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

����������� �

�� ��

���

���

����������� �

��

��

��

��

����

��

Transport unitsfor shipping (plan view)

With individual panel

With combinations of differentindividual panels

1 T1 = Depth of individual panel

2 Individual paneldimension B1 x T1

3 Transport unit,dimension B2 x T2

4 B3 = Overall width ofcombination of differentindividual panels

5 B2 = Width of thetransport unit

Transport of individual panels

Panel type Weightkg/lb

Width B1mm / inch

Height H1mm / inch

Depth T1mm / inch

Cable switch panel CS1

CS2

180/397

205/452

375 / 14.8

500 / 19.7

2250 / 88.6

2250 / 88.6

1230 / 48.4

1230 / 48.4

Fuse switch panel FS1

FS2

FS3

205/452

230/507

250/551

375 / 14.8

500 / 19.7

750 / 29.5

2250 / 88.6

2250 / 88.6

2250 / 88.6

1230 / 48.4

1230 / 48.4

1230 / 48.4

Fuse panel FU1

FU2

FU3

160/353

185/408

210/463

375 / 14.8

500 / 19.7

750 / 29.5

2250 / 88.6

2250 / 88.6

2250 / 88.6

1230 / 48.4

1230 / 48.4

1230 / 48.4

Cable connection panel CC1

CC2

145/320

170/375

375 / 14.8

500 / 19.7

2250 / 88.6

2250 / 88.6

1230 / 48.4

1230 / 48.4

Cable grounding panel CG1

CG2

180/397

205/452

375 / 14.8

500 / 19.7

2250 / 88.6

2250 / 88.6

1230 / 48.4

1230 / 48.4

Metering panel MT3 420/926 750 / 29.5 2250 / 88.6 1230 / 48.4

Metering cable panel MC3 420/926 750 / 29.5 2250 / 88.6 1230 / 48.4

Metering switch panel MS2

MS3

350/772

420/926

500 / 19.7

750 / 29.5

2250 / 88.6

2250 / 88.6

1230 / 48.4

1230 / 48.4

Bus riser panel BR1

BR2

145/320

170/375

375 / 14.8

500 / 19.7

2250 / 88.6

2250 / 88.6

1230 / 48.4

1230 / 48.4

Busbar grounding panel BG1 180/397 375 / 14.8 2250 / 88.6 1230 / 48.4

Transport of combinations of different individual panels

Transport unit Overall width B3

mm / inch

Weight *

kg/lb

Width B2

mm / inch

Height H2 **

mm / inch

Depth T2

mm / inch

VolumeB2 x H2 x T2

m3 / yd3

Transport unit w 750 / 29.5 70/155 1100 / 43.3 2450 / 96.5 1400 / 56.1 3.8 / 5.0

Transport unit w 1750 / 58.9 120/265 2200 / 86.6 2450 / 96.5 1400 / 56.1 7.6 / 10.0

Top case necessary for cable top entry, delivered in accessory bag

Packing, transport (examples)

Packing Version For supply Transport

Panels mounted on wooden floorand covered with protection sheeting

For container Overseas Ship + truck

* Additional packing weight in kg/lb (without weight of panels)

** Transport unit for air freight, height H2 2610 mm/102.8 inchand width B2 1700 mm/66.9 inch

Technical Data

Shipping data

Page 8: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 20088

Paneltype

Panelwidth

CS1 375 mm / 14.8"

CS2 500 mm / 19.7"

FS1 375 mm / 14.8"

FS2 500 mm / 19.7"

FS3 750 mm / 29.5"

FU1 375 mm / 14.8"

FU2 500 mm / 19.7"

FU3 750 mm / 29.5"

CC1 375 mm / 14.8"

CC2 500 mm / 19.7"

CG1 375 mm / 14.8"

CG2 500 mm / 19.7"

MT3 750 mm / 29.5"

MC3 750 mm / 29.5"

MS2 500 mm / 19.7"

MS3 750 mm / 29.5"

BR1 375 mm / 14.8"

BR2 500 mm / 19.7"

BG1 375 mm / 14.8"

Panel designation

Cable switch panel

Fuse switch panel

Fuse panel

Cable connection panel

Cable grounding panel(= cable connection panelwith grounding switch)

Metering panel

Metering cable panel

Metering switch panel

Bus riser panel

Busbar grounding panel

Standard panels

Cable switch paneltype CS

Fuse switch paneltype FS

Cable connection paneltype CC

R-HA

41-0

87ep

sR-

HA41

-088

eps

R-HA

41-0

89ep

s

Column No.

Product range overview

Product Range

Page 9: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

9Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

7)

7)

• ° – • ° ° – – ° – ° ° ° ° ° – ° – ° ° ° ° ° °CS1

• ° – • ° ° – – ° – ° ° ° ° ° – ° – ° ° ° ° ° °CS2

• ° – • ° ° ° ° ° ° ° ° ° ° ° ° – ° ° ° ° ° ° °FS1

• ° – • ° ° ° – ° ° ° ° ° ° ° ° – ° ° ° ° ° ° °FS2

• ° – • ° ° ° ° ° ° ° ° ° ° ° ° – ° ° ° ° ° ° °FS3

– – – – – – – – – ° – – – ° ° – – – ° ° ° ° ° °FU1

– – – – – – – – – ° – – – ° ° – – – ° ° ° ° ° °FU2

– – – – – – – – – ° – – – ° ° – – – ° ° ° ° ° °FU3

– – – – – – – – – – – – – ° ° – – – ° ° ° ° ° °CC1

– – – – – – – – – – – – – ° ° – – – ° ° ° ° ° °CC2

– – • • – – – – ° – ° – – ° ° – – – ° ° ° ° ° °CG1

– – • • – – – – ° – ° – – ° ° – – – ° ° ° ° ° °CG2

– – – – – – – – – – – – – – – – – – – – – ° ° °MT3

– – – – – – – – – – – – – ° ° – – – ° ° ° ° ° °MC3

– • – – • – – – ° – ° ° ° – – – – – – – ° ° ° °MS2

– • – – • – – – ° – ° ° ° – – – – – – – ° ° ° °MS3

– – – – – – – – – – – – – – – – – – – – – ° ° °BR1

– – – – – – – – – – – – – – – – – – – – – ° ° °BR2

– – • • – – – – ° – ° – – – – – – – – – – ° ° °BG1

Two-p

osition sw

itch-d

isconnec

tor (C

LOSE

D-OPE

N)

Thre

e-posit

ion switc

h-disc

onnecto

r (CLO

SED-O

PEN-G

ROUNDED

)

Grounding sw

itch (G

ROUNDED

-OPE

N)

Man

ualoper

ating m

echan

ism

Man

ualoper

ating m

echan

ismwith

store

d-ener

gy mec

hanism

Store

d-ener

gy mec

hanism

operat

edby sh

unt relea

se

Store

d-ener

gy mec

hanism

– electr

ical tr

ipping by time dela

y relay

Store

d-ener

gy mec

hanism

– mec

hanica

l tripping by a dev

ice

Signal

switc

h (1NO) fo

r rem

oteele

ctrica

l read

y-for-s

ervic

e indicatio

n

Signal

switc

h fuse

blown

Auxiliar

y switc

h (CLO

SED-O

PEN-G

ROUNDED

)

Moto

r operat

ing mec

hanism

(CLO

SED-O

PEN)

Loca

l rem

otesw

itch

Cable

com

partm

ent co

ver with

inspec

tion window

Cable

com

partm

ent co

ver with

infrare

d window

Interlo

cking – de-g

rounding if th

e door isopen

Interlo

cking – clo

sing not possi

bleif th

e door isopen

Interlo

cking – clo

sing th

e disconnec

tor sw

itch is

onlypossi

bleif th

e fuse

isinsta

lled an

d intact

C-rail t

o fixca

ble

C-rail w

ithbra

cket

s tofix

cable

Floor co

ver

Heatin

g

Heatin

g withth

erm

ostat

Heatin

g withhum

idistat

Panel

type

• Basic equipment

° Additional (optional) equipment

– Not available

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

°

Product Range

Equipment features

Page 10: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200810

����������� �

������������

������������

Type CS

Cable switch panelas feeder panel

Type CS

����������� �

������������

Cable switch panelas transfer panel

Note: For detailed design, pleasecontact your local Siemens partner.

Cable-typecurrent transformer

2nd cable(not included inthe scope of supply)

Surge arrester

Three-positionswitch-disconnector

*

HA41

-260

8.ep

s

Cable (not includedin the scope of supply)

Capacitve voltagedetection system

������������ �

������������

Type CS

����������� �

������������

������������

Type CSType CS

����������� �

������������

����������� �

������������

Type CS

* Switch-disconnectoras:– two-position

switch-discon-nector

– three-positionswitch-discon-nector

Three-positionswitch-disconnector

*

Cable switch panel

Product Range

Page 11: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

11Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

���������� �

��

������������

������������

������������

Type FS

Fuse switch panelas feeder panel

Type FS

����������� �

��

������������

������������

Fuse switch panelas transfer panel

Note: For detailed design, pleasecontact your local Siemens partner.

2nd HV CL fuse

HV CL fuse

Surge arrester

Discharge switch

Capacitve voltagedetection system

����������� �

��

������������

������������

Type FS

����������� �

��

������������

������������

������������

Type FSType FS

����������� �

��

������������

������������

����������� �

��

������������

������������

Type FS

2nd and 3rd HV CL fuse

2nd cable(not included inthe scope of supply)

Cable (not includedin the scope of supply)

2nd and 3rd cable(not included inthe scope of supply)

Cable-typecurrent transformer

HA41

-260

8.ep

s

* Switch-disconnectoras:– two-position

switch-discon-nector

– three-positionswitch-discon-nector

Three-positionswitch-disconnector

*

Three-positionswitch-disconnector

*

Product Range

Fuse switch panel

Page 12: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200812

����������� �

������������

���������

������

Type FU

Fuse panelas feeder panel

Type FU

����������� �

������������

Fuse panelas transfer panel

Note: For detailed design, pleasecontact your local Siemens partner.

2nd HV CL fuse

HV CL fuse

Surge arrester

Grounding stud

Capacitve voltagedetection system

����������� �

������������

Type FU

����������� �

���������

������

������������

Type FUType FU

���������� �

������������

����������� �

������������

Type FU

2nd and 3rd HV CL fuse

2nd cable(not included inthe scope of supply)

Cable (not includedin the scope of supply)

2nd and 3rd cable(not included inthe scope of supply)

Cable-typecurrent transformer

HA41

-260

8.ep

s

Fuse panel

Product Range

Page 13: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

13Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

����������� �

������������

Cable connection panelas feeder panel

Type CC

Note: For detailed design, pleasecontact your local Siemens partner.

Surge arrester

Grounding stud

Capacitve voltagedetection system

����������� �

������������

Type CC

2nd cable(not included inthe scope of supply)

Cable (not includedin the scope of supply)

Cable-typecurrent transformer

HA41

-260

8.ep

s

Product Range

Cable connection panel

Page 14: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200814

����������� �

������������

Type CG

Cable grounding panel(= cable connection panelwith grounding switch)

Type CG

����������� �

Cable grounding panel/busbar grounding panel(with grounding switch)

Note: For detailed design, pleasecontact your local Siemens partner.

Surge arrester

Grounding switch

Capacitve voltagedetection system

����������� �

Type CG

����������� �

������������

Type CG

2nd cable(not included inthe scope of supply)

Cable (not includedin the scope of supply)

Cable-typecurrent transformer

HA41

-260

8.ep

s

Type CG

���������� �

����������� �

Type CG

Cable grounding panel, busbar grounding panel

Product Range

Page 15: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

15Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

����������� �

���������

������

Type MT3

Metering panel

Type MT3

����������� �

���������

������

Note: For detailed design, pleasecontact your local Siemens partner.

Grounding stud

Capacitve voltagedetection system

����������� �

���������

������

Type MT3 Type MT3

����������� �

���������

������

Block-typecurrent-transformer4MA and voltagetransformer 4MR(both cast-resininsulated)

Block-typecurrent-transformer4MA and voltagetransformer 4MR(both cast-resininsulated)

Block-typecurrent-transformer4MA and voltagetransformer 4MR(both cast-resininsulated)

Block-typecurrent-transformer4MA and voltagetransformer 4MR(both cast-resininsulated)

Block-typecurrent-transformer4MA and voltagetransformer 4MR(both cast-resininsulated)

HA41

-260

8.ep

s

Product Range

Metering panel

Page 16: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200816

����������� �

������������

������������

Type MC

Metering panel with cable

Type MC

����������� �

������������

������������

Note: For detailed design, pleasecontact your local Siemens partner.

Capacitve voltagedetection system

����������� �

������������

������������

������������

Type MC Type MC

����������� �

������������

������������

������������

���������� �

������������

������������

Type MC Type MC

����������� �

������������

������������

Grounding stud

Block-typecurrent-transformer4MA and voltagetransformer 4MR(both cast-resininsulated)

Block-typecurrent-transformer4MA and voltagetransformer 4MR(both cast-resininsulated)

Surge arrester

2nd cable(not included inthe scope of supply)

Cable (not includedin the scope of supply)

HA41

-260

8.ep

s

Metering panel with cable

Product Range

Page 17: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

17Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

����������� �

������������

������������

������������

Type MC

Metering panel with cable

Type MC

����������� �

������������

������������

������������

Capacitve voltagedetection system

Grounding stud

Block-typecurrent-transformer4MA and voltagetransformer 4MR(both cast-resininsulated)

Block-typecurrent-transformer4MA and voltagetransformer 4MR(both cast-resininsulated)

Surge arrester

HV CL fuse ***

Voltage transformer 4MR(cast-resin insulated)

Control power trans-former (CPT) make ITI

2nd cable(not included inthe scope of supply)

Cable (not includedin the scope of supply)

HA41

-260

8.ep

s

Metering switch panel

����������� �

�� !�

������������

" ���#���

Type MS Type MS

����������� �

�� !�

������������

" ���#���

Type MS

����������� �

�� !�

������������

" ���#���

Note: For detailed design, pleasecontact your local Siemens partner.

* Switch-disconnector as:– two-position switch-disconnector– three-position switch-disconnector

** Only in combination with VT or CPT

*** Fuses: Potential transformer fuses type CAV

Three-positionswitch-disconnector

*

Three-positionswitch-disconnector

*

Product Range

Metering panel with cable (continued), metering switch panel

Page 18: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200818

����������� �

Bus riser panel

Type BR

����������� �

Capacitve voltagedetection system

Grounding stud

Type BR

Busbar grounding panel

����������� �

Type BG Type BG

���������� �

Type BG

����������� �

����������� �

Type BG Type BG

����������� �

Type BG

����������� �

Grounding switch

HA41

-260

8.ep

s

Note: For detaileddesign, pleasecontact your localSiemens partner.

Bus riser panel, busbar grounding panel

Product Range

Page 19: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

19Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

����������� �

�����

� ��

��

��

���

��

����

���

��

��

��

��

��

��

��

��

��

��

��

��

��

Cable switch panel type CS Fuse switch panel type FS

Metering panel type MT

Legend

1 Indicator “Fuse intact/fuseblown”

2 Switch position indicator

3 View port for switch bladeposition

4 Sockets for capacitivevoltage detection system

5 Information label for viewport

6 Mimic diagram

7 Warning label

8 Gas-insulated vessel forswitching device

9 Manual operation for themechanism of the load-break-disconnecting function

10 “Ready-for-service” indicatorfor switching device

11 Manual operation for themechanism of the groundingfunction

12 Interlocking lever of cablecompartment cover (option)

13 Option: Locking device forthree-position switch

14 Pressure relief device forswitching device

15 Metal compartmentalizationof cable connectioncompartment

16 Rating and type plate

17 Option: Local-remote switchand momentary-contactrotary control switch“CLOSED-OPEN” for the motoroperating mechanism

18 Feeder designation label

19 Pressure relief duct

20 Cable termination(not incl. in scope of supply)

21 Cable bracket with clamps

22 Cable connectioncompartment

23 Busbar

24 Insulating cap on busbar(for > 15 kV)

25 Bushing-type insulator forbusbar

26 Metal compartmentalizationof busbar compartment

27 Spring-operated mechanismfor three-position switch

28 Three-position switch

29 Grounding busbar

30 Bushing-type insulator forfeeder

31 Cable connection

32 Cable compartment:As cover or door(latched or screwed-on)

33 Grounding connection

34 Grounding switch todischarge capacitance ofconnected transformers

35 Post insulator

36 HV CL (current limiting) fuse

37 4MA7 block-type currenttransformer

38 Fuse holder for VT fuse

39 4MR voltage transformer

����������� �

������

� ��

��

��

���

��

����

���

��

����

����

��

��

��

��

��

��

��

��

��

��

��

��

����������� �

� ��

��

��

��

��

��

��

��

��

��

��

��

��

Type CS1 Type FS2

Type MT3

Section Section

Section

Design

Panel design (examples)

Page 20: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200820

����������� �

Characteristics

• Switch positions:– CLOSED-OPEN

or– CLOSED-OPEN-GROUNDED

• Designed as a multi-chamberswitch incorporating thefollowing functions

– Switch-disconnector and– Make-proof grounding switch

• Operation via gas-tightwelded bushing at the frontof the switchgear vessel

• Switching functions asgeneral purpose switch-disconnector according toANSI/IEEE C37.20.3 *

Mode of operation

The switch shaft with themoving contacts rotates insidethe chamber containing thefixed contacts.

Compression vanes, whichrotate in conjunction with theswitch shaft, divide the arcingchamber into two subchamberseach of which changes in con-junction with the rotation.

During the switching move-ment, the compression vanesgenerate a pressure differencebetween the subchambers.The SF6 gas flows through anozzle, causes a directionalblow-out of the breaking arcand quenches it rapidly.

Interlocking is not necessaryas the CLOSED and GROUNDEDfunctions cannot be imple-mented simultaneously.

* Standards see page 40

Switching functions

CLOSED OPEN GROUNDED

Switch positions:

Three-positionswitch-disconnector

– CLOSED

– OPEN

– GROUNDED

Control board withswitch positionindicators fordetachable levermechanism

$���

������ �

$���

������� �

$���

������� �

Switch positionsof three-positionswitch-disconnector

Switch positionsof two-positionswitch-disconnector

CLOSED OPEN

Legend

1 Moving contact

2 Fixed contact for GROUNDED

3 Fixed contact for CLOSED

Two/three-position switch-disconnector

Components

Fixed contact

Arcing chamber

Moving contact, complete

Compression vane (with nozzle)

Exploded view

Switch shaft

R-HA

35-0

47ep

sThree-positionswitch-disconnector

Page 21: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

21Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

����������� �

Common features

• Metal-enclosed

• Located in agas-insulatedswitchgear vessel

• Switch positions:– CLOSED-OPEN

or– CLOSED-OPEN-

GROUNDED

• No cross insulationbetween phases

• Two/three-positionswitch with air-insula-ted primary connec-tions for busbar andfeeder

• Operation via agas-tight welded-inmetal bellows in thefront of the switchgearvessel

View port

The visual inspection ofthe actual position of thetwo/three-position switchis possible via a viewport.(Fig. shown on the right)

1 Bushing-type insulator for busbar

2 Switchgear vessel for gas insulation

3 Three-position switch-disconnector

4 Bushing-type insulator for feeder

5 Spring-operated mechanism with detachable lever

6 View port

Detachable lever mechanismwith three-position switch-disconnector

$���

������� �

7 Operating lever, inserted

Two/three-positionswitch-disconnector 600 A

• Up to 600 A

• With gas-insulated,maintenance-free quench-ing principle

Operating mechanism

• Spring-operated mechanismwith detachable lever

• Manual operation with theaid of a detachable lever

• Options:– Mechanical ready-for-

service indication– Auxiliary switch– Motor operating mechanism

for switch-disconnector– Locking device

• Spring-operated/stored-energy mechanism fortransformer panel type FS

Interlocks

• Opening of panel cover orcable compartment coveronly in “GROUNDED“position

Operating cycles

• Capable of 100 operatingcycles at rated continuouscurrent 600 A

• Mechanical endurance of1000 operating cycles

Switch positions ofthree-position switch:

CLOSED

OPEN

GROUNDED

Switching functions of the three-position switch-disconnector 600 A

• Switching and disconnecting under load

• General-purpose switching function

• Make-proof grounding function

��������%�� �

View port

Legend for view port

1 Moving contact

2 Fixed contact for CLOSED

3 Fixed contact for GROUNDED

Components

Two/three-position switch as two/three-position switch-disconnector

Three-positionswitch-disconnector600 A (side removed for photo)

Page 22: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200822

$���

������� �

Busbar compartment extending over 2 panels, example (side view)

Busbars

• Metal-enclosed busbarcompartment

• Three-pole design,bolted from panel topanel

• Easy switchgearextension

• Made of copper:Round-edge copper forup to 1200 A

Option:Shrink-on sleeve

HV CL fuse assembly

• For fuse panel type FS

• For busbar voltage meter-ing panel type MS

• HV CL fuse linksacc. to ANSI/IEEEC37.41/C37.46 *

– As short-circuit protec-tion before transformers

– With selectivity (depend-ing on correct selection)to upstream and down-stream connected equip-ment

• Requirements fulfilled asHV alternating currentswitch fuse combination

• Selection of HV CLfuses for transformers

• Fuse replacement possi-ble only when feeder isgrounded

• Option: Shunt release onoperating mechanism oftwo/three-position switch-disconnector

• Option: “Tripped indica-tion” of two/three-positionswitch-disconnector intransformer feeder (trans-former switch) for remoteelectrical indication withone normally-open con-tact (1NO)

“HV CL fuse tripped”

Following the tripping of anHV CL fuse link, the mecha-nism for charging the springmust be set to the “OPEN”position

Subsequently, groundingcan be implemented bymeans of the two/three-position switch-disconnec-tor and e.g., the fuse can bereplaced.

Replacement of HV CL fuselinks

• Isolating and groundingof the transformer feeder

• Subsequent manualreplacement of theHV CL fuse links

1 Busbar

2 Bushing-typeinsulator for busbar

$���

������� �

Busbars

HV HRC fuse assembly

3 HV CL fuse

4 Lower fuse holder

5 Grounding stud

6 Cable termination(not included in thescope of supply)

HV CL fuses in fuse panel type FS (side view, 2 sets of fuses shown)

$���

������� �

Control board of a fuse panel

Fuse intact

* Standards see page 40

Fuse blown

Displays

Busbars, HV CL (current-limiting) fuse assembly

Components

Page 23: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

23Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

The table opposite shows therecommended fuse links (elec-trical data valid for ambienttemperatures of up to 40 oC/104 °F) for the fuse protectionof transformers

Recommendation

The two/three-position switch-disconnector in the trans-former feeder (transformerswitch) is combined withBussmann fuse links. Dimen-sions according to DIN stan-dards (especially manufacturedfor Siemens)

Standards

HV CL fuse links according toANSI/IEEE C37.41/C37.46 *

* Standards see page 40

** FS1/FU1: Single fuseFS2/FU2: Two fuses in parallelFS3/FU3: Three fuses in parallel

Bussmann fuses

Ratedvoltage

kV

Length

mm / inch

Diameter

mm / inch

Ratedcurrent I1

A

Powerloss

W

Panel type ** Code/referenceNo. for SIMOSECANSI

FS1/FU1 FS2/FU2 FS3/FU3Permissible continuous current

A A A

5.5

5.5

5.5

442 / 17.4

442 / 17.4

442 / 17.4

51 / 2.0

51 / 2.0

51 / 2.0

10

15

20

8

11

11

10

15

20

18

27

36

24

36

48

55GDMSJ10ES

55GDMSJ15ES

55GDMSJ20ES

5.5

5.5

5.5

442 / 17.4

442 / 17.4

442 / 17.4

51 / 2.051 / 2.0

51 / 2.0

25

30

40

15

17

27

25

30

40

45

54

72

60

72

96

55GDMSJ25ES

55GDMSJ30ES

55GDMSJ40ES

5.5

5.5

5.5

442 / 17.4

442 / 17.4

442 / 17.4

51 / 2.051 / 2.0

51 / 2.0

50

65

80

36

44

53

50

65

80

90

117

144

120

156

192

55GDMSJ50ES

55GDMSJ65ES

55GDMSJ80ES

5.5

5.5

442 / 17.4

442 / 17.4

51 / 2.051 / 2.0

100

125

69

94

100

120

180

220

240

300

55GDMSJ100ES

55GDMSJ125ES

5.5

5.5

5.5

442 / 17.4

442 / 17.4

442 / 17.4

76 / 3.0

76 / 3.0

76 / 3.0

150

175

200

103

121

126

150

164

183

270

292

327

360

416

466

55GDMSJ150ES

55GDMSJ175ES

55GDMSJ200ES

5.5

5.5

5.5

442 / 17.4

442 / 17.4

442 / 17.4

76 / 3.0

76 / 3.0

76 / 3.0

250

300

350

139

147

161

220

241

269

390

429

478

555

598

600

55GDMSJ250ES

55GDMSJ300ES

55GDMSJ350ES

5.5

5.5

442 / 17.4

442 / 17.4

76 / 3.0

76 / 3.0

400

450

167

183

302

325

536

575

600

600

55GDMSJ400ES

55GDMSJ450ES

15.5

15.5

537 / 21.14

537 / 21.14

88 / 3.5

88 / 3.5

175

200

177

238

167

165

310

305

420

430

175GXQSJ175ES

175GXQSJ200ES

17.5

17.5

17.5

442 / 17.4

442 / 17.4

442 / 17.4

51 / 2.0

51 / 2.0

51 / 2.0

10

15

20

22

30

32

10

15

20

18

27

36

24

36

48

175GDMSJ10ES

175GDMSJ15ES

175GDMSJ20ES

17.5

17.5

442 / 17.4

442 / 17.4

51 / 2.0

51 / 2.0

25

30

41

47

25

30

4554

60

72

175GDMSJ25ES

175GDMSJ30ES

17.5

17.5

17.5

442 / 17.4

442 / 17.4

442 / 17.4

76 / 3.0

76 / 3.0

76 / 3.0

40

50

65

79

95

130

40

50

59

72

90

104

69

120

149

175GFMSJ40ES

175GFMSJ50ES

175GFMSJ65ES

17.5

17.5

442 / 17.4

442 / 17.4

76 / 3.0

88 / 3.5

80

100

126

169

73

85

131

155

186

225

175GXMSJ80ES

175GXMSJ100ES

17.5

17.5

537 / 21.14

537 / 21.14

88 / 3.5

88 / 3.5

125

150

203

221

112

123

207

238

292

336

175GXQSJ125ES

175GXQSJ150ES

25.8

25.8

25.8

537 / 21.14

537 / 21.14

537 / 21.14

51 / 2.0

51 / 2.0

51 / 2.0

10

15

20

27

41

44

10

15

20

18

27

36

24

36

48

258GDQSJ10ES

258GDQSJ15ES

252GDQSJ20ES

25.8

25.8

537 / 21.14

537 / 21.14

51 / 2.0

51 / 2.0

25

30

50

67

25

30

45

54

60

72

252GDQSJ25ES

252GDQSJ30ES

25.8

25.8

25.8

537 / 21.14

537 / 21.14

537 / 21.14

88 / 3.5

88 / 3.5

88 / 3.5

40

50

65

87

103

140

40

50

65

72

90

117

96

120

156

252GDQSJ40ES

252GDQSJ50ES

252GDQSJ65ES

Components

Allocation of HV CL fuses and transformers

Page 24: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200824

Manual operatingmechanism

• Standard:As detachable levermechanism

• Spring-operated mecha-nism

– For cable-switch paneltype CS

– For all two/three-positionswitches (except in paneltype FS)

• Spring-operated/stored-energy mechanismFor fuse panel type FS aswell as for busbar voltagemetering switch paneltype MS

The two/three-positionswitch is operated via arocker with metal bellowswhich is gas-tight andwelded at the switchgearvessel.

Motor operatingmechanism (option)

The manual operating mech-anisms can be equipped withmotor operating mechanismsfor the two/three-positionswitch-disconnector.

Operating voltages for motoroperating mechanisms:– 24, 48, 60, 125 V DC– 50/60 Hz 120 and 240 V AC

Electrical operation:

• Standard: Remote opera-tion (applied to terminal)

• Option: Local operationby momentary-contactrotary control switch

Shunt release (option)

Spring-operated/stored-energy mechanisms can beequipped with a shunt re-lease. Remote electricaltripping of the two/three-position switch-disconnectoris possible via the magneticcoil of the shunt release,e.g., transformer overtem-perature tripping.

To avoid thermal overloadingof the shunt release in theevent of a continuous signalthat may be applied, theshunt release is switched offvia an auxiliary switch whichis mechanically coupled withthe three-position switch-disconnector.

Auxiliary switch (option)

Each operating mechanismof the two/three-positionswitch-disconnector can beoptionally equipped with anauxiliary switch for theswitch position indication:– Function switch-discon-

nector or disconnector:CLOSED and OPEN:2NO + 2NC

– Function groundingswitch at the two/three-position switch:CLOSED and OPEN:2NO + 2NC

Operating mechanisms

Detachable lever mechanismas spring-operated/stored-energy mechanism

1 Ready-for-serviceindicator

2 Auxiliary switch

3 Switch positionindicator for thethree-positionswitch-disconnector

4 Locking device(standard for motoroperating mechanism)

5 Operating mechanismfor the three-positionswitch-disconnectorcoupled with the motoroperating mechanism

6 Low-voltage niche

7 Terminal strip locatedin the low-voltageniche

8 M.c.b. (option)in the low-voltageniche

9 Local-remote switch(option)

10 Actuation for themotor operatingmechanism of thethree-positionswitch-disconnector

$���

������� �

Operating mechanism parts inpanel types FS… (transformer feeders)

Abbreviations:

NO = normally-open contactNC = normally-closed contact

Technical data of the auxiliary switchBreaking capacity

AC operation at50 Hz to 60 Hz

Operating Normalvoltage current

V A

DC operation

Operating Normal currentvoltage resistive inductive:

T=20 msV A A

up to 240 10 24 10 10

48 10 9

60 9 7

110 5 4

125 5 4

240 2.5 2

Rated insulationvoltage 250 V AC/DC

Insulation groupC to VDE 0110

Continuous current10 A

Making capacity50 A

Rated switching capacity

R-HA

41-0

97ep

s

R-HA

41-0

98ep

s

Detachable lever mechanismas spring-operated mechanism

Operating mechanisms for two/three-position switches

Components

Page 25: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

25Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

Ready-for-service indicator(option for three-positionswitch)

• Self-monitoring; easy toread

• Independent of tempera-ture and pressure variations

• Independent of site altitude

• Only responds to changesin gas density

• Option: Alarm switch“1NO contact”

Mode of operation

For the ready-for-service indi-cator, a gas-tight measuringbox is installed on the insideof the switchgear vessel.

A coupling magnet, whichis fitted to the bottom endof the measuring box, trans-mits its position to an outsidearmature through the stain-less steel switchgear vessel.This armature moves theready-for-service indicator ofthe switchgear.

While changes in the gasdensity during the loss ofgas, which are decisive forthe insulating capacity, aredisplayed, temperature-dependent changes in thegas pressure are not. The gasin the measuring box has thesame temperature as that inthe switchgear.

The temperature effect iscompensated via the samepressure change in both gasvolumes.

Voltage detection systems

For voltage detectionaccording to IEC 61 243-5 /VDE 0682-415

Plug-in voltagedetection systems

• Standard: HR system

Features of theHR system

• Voltage indicatorHR system (standard)

• Verification of safe isolationfrom supply phase byphase through insertion ineach socket pair

• Voltage indicator flashesif high voltage is present

• For continuous operation

• Safe-to-touch

• Measuring system andvoltage indicator can betested

• Fixed-mounted capacitivevoltage divider in bushings

• Without auxiliary power

Mounting of voltagedetection systems

See “Product range”pages 10 to 18

Verification of correctterminal-phase connections

• Possible by means of aphase comparison test unit(optional)

• Safe-to-touch handling ofthe phase comparison testunit by inserting it into thecapacitive taps (socketpairs) of the switchgear

����������� �

��

Voltage indicator,HR system (standard)

R-HA

40-0

88ep

s

3 Measuring box

4 Magnetic coupling

5 Red indication:not ready for service

6 Green indication:ready for service

Principle of operation of gas monitoringwith ready-for-service indicator

Stainless-steel vesselfilled with SF6 gas,gauge pressure50 kPa (7.25 psi) at 20 °C

Ready-for-serviceindicator

$���

������ �

Indicating and measuring equipment(examples)

Control board of a ring-main panel(example)

Mounting locations in the controlboard for

1 Ready-for-service indicator(option)

2 Voltage indicator, HR system,plugged-in (standard)

Components

Indicating and measuring equipment

Page 26: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200826

4MC70 33 cable-type current transformerson the cable at the panel connection **

Application

• For cable paneltypes CS, CC, CG

• For fuse paneltypes FS, FU

Features

• According toANSI / IEEE C57.13

• Designed as a single-polering-core current transformer

• Only for shielded cables

• Climate-independent

• Free of dielectricallystressed cast-resin parts(due to design)

• Inductive type

• Secondary connection bymeans of a terminal stripinside the panel

Installation

• Arranged on the cable atthe panel connection

• Transformers mounted ona supporting plate at thefactory; final assembly onthe cables at site

* Depending on the core data

** Assembly normally under thepanel floor

*** Accuracy class varies accordingto CT data

Other values available on request

R-HA

41-1

02ep

s

R-HA

41-0

24ep

s

H

4MC70 33 cable-typecurrent transformer,4 different overall heights

Technical data

MC70 33 cable-type current transformer

Primary data

Max. equipment operating voltage Um 0.60 kV

Rated current IN 30 A to 600 A

Rated short-duration power-frequencywithstand voltage (winding test)

3 kV

Rated thermal short-time withstand current Ith 25 kA

Rated continuous thermal current ID 1.0 x INoption: 1.2 x IN

Rated peak withstand current Idyn unlimited

Secondary data

Rated current 5 A

Measuring core Class *** 0.3 0.6 1.2

Burden 0.2 VA to 1.8 VA

Protection core Class *** C10 ... C200

Dimensions

Overall height H mm 50* 100* 170* 285*Outside diameter Ø 145 mm / 5.7 inch

Inside diameter Ø 55 mm / 2.2 inch

For cable diameter Ø 36 ... 50 mm / 1.4 ... 2.0 inch

4MC70 33 cable-type current transformers

Components

Page 27: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

27Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

Other values available on request

Application

• For metering paneltypes MT, MS, MC

Features

• 4MA7 current transformer

• According toANSI / IEEE C57.13

• Dimensions according toDIN 42600-8

• Designed as a single-poleindoor block-type currenttransformer

• Cast-resin insulated

• Secondary connection bymeans of screw-typeterminals

4MR voltage transformer

• According toANSI / IEEE C57.13

• Dimensions according toDIN 42600-9 (small model)

• Designed as an indoorvoltage transformer:

– Type 4MR, single-pole– Option: Type 4MR, two-pole

• Cast-resin insulated

• Secondary connection bymeans of screw-typeterminals

Other values available on request

R-HA

41-1

01ep

s

4MA7 block-type currenttransformer,single-pole

4MR14 voltagetransformer,single-pole

4MR voltage transformer and4MA7 block-type current transformer installed in metering panel

R-HA

41-0

29a

eps

R-HA

41-0

30a

eps

Technical data4MA7 single-pole block-type current transf.

Primary data

Max. equipmentoperating voltage Um

15.5 kV 27.6 kV

Rated short-durationpower-frequencywithstand voltage

34 kV 1) 40 kV 1)

36 kV 2) 60 kV 2)

Rated lightning impulsewithstand voltage Up

95 kV 125 kV

Rated current IN 50 A to 600 A> 600 A: onrequest

Rated thermal short-timewithstand current Ith

up to 25 kA

Rated continuous thermalcurrent ID

up to 1.0 x INoption: 1.2 x IN

R. peak withst. current Idyn max. 2.5 x Ith

Secondary data

Rated current 5 A

Measuring core Class 3) 0.3 0.6 1.2

Burden 0.2 to 1.8 VA

Protection core Class 3) C10 ... C200

4MR single-pole voltage transformer

Max. equipmentoperating voltageUm

5.6 kV 9.52 kV 15.5 kV 25.5 kVB

Rated short-duration power-frequency with-stand voltage

16 kV 1)

20 kV 2)

26 kV 1)

28 kV 2)

34 kV 1)

36 kV 2)

40 kV 1)

60 kV 2)

Rated lightningimpulse withstandvoltage Up

60 kV 75 kV 95 kV 125 kV

Rated voltage 100/ 3 V110/ 3 V120/ 3 V

Rated voltage forauxiliary winding

100/3 V110/3 V120/3 V

Burden 25 ... 200 VA

Class 0.3 0.5 1.2

B On request: operating voltageUm > 25.5 kV, e.g. 27.6 kV

1) Acc. to ANSI/IEEE C57.13(standard)

2) Option: on request

3) Accuracy class varies accordingto CT data

Components

4MA7 block-type current transformers and 4MR voltage transformers

Page 28: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200828

General features

• Cable termination points arearranged one behind the other

• Uniform cable connectionheight per panel (see dimensiondrawings)

• With cable bracket or cableclamps and grounding pointsfor cable shields

• Access to the cable connectioncompartment only whenfeeder has been grounded

Features for cable terminals

• For thermoplastic-insulatedcables

• For paper-insulated mass-impregnated cables

• For connection cross-sections (cable size) * up to300 mm2 (600 kcmil)

• Cable bottom entry frombelow (standard)

• Cable top entry from above(optional)

$���

������� �

������

$���

������� �

������

$���

������� �

$���

������� �

Cable connection (examples)

Cable connection compartmentwith cable termination

Cable switch panel type CSCable connection compartment as delivered

Cable connection compartmentwith cable termination

Fuse panel type FSCable connection compartment as delivered

Legend

1 As delivered condition forcable termination

2 As delivered condition,prepared for cable termination

3 Cold shrink brand 3M

4 Cable termination brand 3M orTyco Electronics Raychem

5 Cable termination brand 3M orTyco Electronics Raychem(with cold shrink brand 3M)

* Larger connection cross-sectionson request.

Cable connection

Components

Page 29: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

29Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

Principle of cable connection (dimensions in mm/inch)(e.g. for panel type CS)

����������� �

�������

&'()���������

������

�����

����������� �

&'()���������

�������

�����

����������� �

&'()���������

Panel type CS1 + 2 FS1 + 2 + 3 FU1 + 2 + 3 CC1 + 2 CG1 + 2 MC3

Cabletermi-nationheight inmm/inch

Panelheight

inmm/inch

Cabletermi-nationheight inmm/inch

Panelheight

inmm/inch

Cabletermi-nationheight inmm/inch

Panelheight

inmm/inch

Cabletermi-nationheight inmm/inch

Panelheight

inmm/inch

Cabletermi-nationheight inmm/inch

Panelheight

inmm/inch

Cabletermi-nationheight inmm/inch

Panelheight

inmm/inch

Top cable entry

Main switch or vertical copperbar in upper position(fuse assembly in lower position)

490/19.3

2550/100.4

490/19.3

2550/100.4

490/19.3

2550/100.4

490/19.3

2550/100.4

490/19.3

2550/100.4

530/20.8

2250/88.6

Main switch or vertical copperbar in lower position(fuse assembly in upper position)

notavailable

notavailable

notavailable

notavailable

490/19.3

2550/100.4

notavailable

notavailable

notavailable

notavailable

notavailable

notavailable

Middle cable connection

to top 940/37

2250/88.6

notavailable

notavailable

940/37

2250/88.6

940/37

2250/88.6

940/37

2250/88.6

notavailable

notavailable

to bottom 1240/48.8

2250/88.6

notavailable

notavailable

1240/48.8

2250/88.6

1240/48.8

2250/88.6

1240/48.8

2250/88.6

notavailable

notavailable

Bottom cable entry

Main switch or vertical copperbar in upper position(fuse assembly in upper position)

notavailable

notavailable

notavailable

notavailable

490/19.3

2250/88.6

notavailable

notavailable

notavailable

notavailable

notavailable

notavailable

Main switch or vertical copperbar in upper position(fuse assembly in lower position)

490/19.3

2250/88.6

490/19.3

2250/88.6

notavailable

notavailable

490/19.3

2250/88.6

490/19.3

2250/88.6

490/19.3

2250/88.6

Components

Selection data for various cable terminations

Page 30: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200830

����������� �

������

���������

��������

��������

��������

�����

�����

�����

��������������

��������

���

�����

��������

������

��������

��������

����������� �

������

��������

��������

��������

��������

�����

�����

�����

��������������

�����

���

�����

��������

������

��������

��������

Type CS1 Type CS2

Type CS1 Type CS2

Legend

1 Available mounting depthin the LV niche

Cable switch panel types CS… (dimensions in mm/inch)

Dimensions

Page 31: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

31Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

����������� �

������

��������

��������

��������

�����

�����

�����

��������������

�������

���

�����

��������

������

��������

�������

''��������

��������

��������

��������

Type FS1 Type FS2 Type FS3

����������� �

��������

��������

��������

��������

������

�����

�����

�����

��������������

���

����� ��

�����

��������

��������

��������

�������

��������

'' ��������

�������

���������

Type FS1 Type FS2

���������%�� �

������

��������

�������

��������

��������

�����

�����

�����

��������������

�������

���

�����

�������

������

��������

��������

�������

�������

��������

' '

��������

��������

Type FS1 Type FS2 Type FS3

Type FS3

Legend

1 Available mounting depthin the LV niche

2 Screwed-on door(fuse compartment)

3 Top case for cable top entry

Dimensions

Fuse switch panel types FS… (dimensions in mm/inch)

Page 32: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

���������� �

������

������

��������

��������

��������

�����

�����

�����

��������������

�������

���

�����

��������

������

��������

��������

��������

�������

��������

' ' ��������

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200832

���������%�� �

������

������

�������

��������

��������

�����

�����

�����

��������������

�������

���

�����

�������

������

��������

��������

�������

�������

' '��������

��������

��������

��

Type FU1 Type FU2

����������� �

������

������

��������

��������

�����

�����

�����

��������������

���

�����

��������

������

��������

�������

Type FU1 Type FU2 Type FU3

Type FU3

Fuse panel types FU… (dimensions in mm/inch)

Dimensions

Legend

1 Available mounting depthin the LV niche

2 Screwed-on door(fuse compartment)

3 Top case for cable top entry

Type FU1 Type FU2 Type FU3

Page 33: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

33Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

���������%�� �

������

������

��������

��������

��������

�����

�����

�����

��������������

���

�����

��������

������

��������

��������

��������Type CC1 Type CC2

���������%�� �

������

������

��������

��������

��������

�����

�����

�����

������

�����

���

�����

��������

������

��������

��������

��������Type CC1 Type CC2

Legend

1 Available mounting depthin the LV niche

2 Screwed-on cover

Dimensions

Cable connection panel types CC… (dimensions in mm/inch)

Page 34: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200834

���������%�� �

������

���������

��������

��������

��������

�����

�����

�����

��������������

���

�����

��������

������

��������

��������

��������

���������%�� �

������

��������

��������

��������

��������

�����

�����

�����

������

�����

���

�����

��������

������

��������

��������

��������Type CG1 Type CG2

Type CG1 Type CG2

Legend

1 Available mounting depthin the LV niche

2 Screwed-on cover

Cable grounding panel types CG… (dimensions in mm/inch)

Dimensions

Page 35: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

35Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

���������%�� �

������

������

�����

�����

���������

�����

��������

�������

������

��������

���������%�� �

������

������

�����

�����

���������

�����

��������

�������

������

��������Type MT3

���������%�� �

�������

�����

���������

��������

�������

�����

�����

������

�����

�����

�����

��������

������

Type MS2 (with voltage transformer 4MR)

Type MT3

���������%�� �

������

������

�����

�����

���������

�����

��������

�������

������

��������Type MT3

��������%�� �

�������

�����

���������

��������

�������

�����

�����

�����

��������

������

Type MS3 (with control power transformer make ITI)

Legend

1 Available mounting depth in the LV niche

2 Screwed-on cover

Dimensions

Metering panel type MT3, metering switch panel types MS (dimensions in mm/inch)

Page 36: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200836

���������%�� �

������

������

�����

�����

���������

�����

��������

�������

������ ��

����

���������

��������

���������%�� �

�����

���������

��������

�������

������

������

�����

�����

������ ��

�����

��������

���������

��������Type MC3

���������%�� �

������

������

�����

�����

���������

�����

��������

�������

������ ��

����

��������

���������

��������Type MC3

Type MC3

Legend

1 Available mounting depth in the LV niche

2 Screwed-on cover

Metering cable panel type MC3 (dimensions in mm/inch)

Dimensions

Page 37: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

37Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

���������%�� �

������

������

�����

���������

��������

��������

��������

������

��������

���������%�� �

������

������

�����

���������

��������

��������

��������

������

��������Type BR1

���������%�� �

������

������

�����

���������

��������

��������

��������

������

��������Type BR1

Type BR1 Type BR2

Type BR2

Type BR2

Legend

1 Available mounting depth in the LV niche

2 Screwed-on cover

Dimensions

Bus riser panel types BR… (dimensions in mm/inch)

Page 38: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200838

���������%�� �

������

��������

��������

�������� �����

���������

��������

���������%�� �

������

��������

��������

�������� �����

���������

��������Type BG1

�������%�� �

������

���������

��������

�������� �����

���������

��������Type BG1

Type BG1

Legend

1 Available mounting depth in the LV niche

2 Screwed-on cover

Busbar grounding panel type BG1 (dimensions in mm/inch)

Dimensions

Page 39: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

39Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

��������������

����������������

������

������

������

���������

��������

����� �����

���������� �

���)�������)����

���)��������)���

�������

�����

� ��

� ���������

������

���

��������

��

��������������

��������

��������

������

������

������

���������

��������

����� �����

���������� �

���)�������)����

���)��������)���

�������

�����

� ��

� ���������

������

���

��������

������������

������

��������

������

������

������

������

��������

����� �����

���������� �

���)�������)����

���)��������)���

�������

�����

� ��

� ���������

������

���

��������

��

������������

������

��������

������

������

������

������

��������

����� �����

���������� �

���)�������)����

���)��������)���

�������

�����

� ��

� ���������

������

���

��������

��������������

�������

��������

������

������

������

���������

��������

����� �������

���������� �

���)�������)����

���)��������)���

�������

�����

� ��

� ���������

������

���

��������

��������

��������

��

��������������

�������

��������

������

������

������

���������

��������

����� �������

���������� �

���)�������)����

���)��������)���

�������

�����

� ��

� ���������

������

���

��������

��������

��������

1 Wall distance

2 Fixing frame (base)of an individual panel or panel block

3 Floor opening for high-voltage cables and,where applicable, control cables

4 Position of the cables for the feeder

5 Fixing points

6 Floor opening if required for panelswithout cable connection

Paneltype

CS1FS1FU1CC1CG1

Paneltype

BG1BR1

Paneltype

CS2FS2FU2CC2CG2

Paneltype

BR2MS2

Paneltype

FS3FU3

Paneltype

MT3MS3

Paneltype

MC3

��������������

�������

��������

������

������

������

���������

��������

����� �������

���������� �

���)�������)����

���)��������)���

�������

�����

� ��

� ���������

������

���

��������

��������

��������

��

Forp

anel

wid

th37

5m

m/1

4.8"

Forp

anel

wid

th50

0m

m/1

9.7"

Forp

anel

wid

th75

0m

m/2

9.5"

Dimensions

Floor openings (dimensions in mm/inch in red) and fixing points

Page 40: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200840

Altitude correction factor Ka

For site altitudesabove 1000 m/3281 ft, the alti-tude correctionfactor Ka is recom-mended, depend-ing on the actualsite altitude abovesea level.

Rated short-duration power-frequency withstand voltage to be selected

W Rated short-duration power-frequency withstand voltage · Ka

Rated lightning impulse withstand voltage to be selected

W Rated lightning impulse withstand voltage · Ka

Example:

3000 m/9842 ft site altitude above sea level15 kV switchgear rated voltage95.0 kV rated lightning impulse withstand voltage

Rated lightning impulse withstand voltageto be selected 95 kV · 1.28 = 122 kV

Overview of standards

SIMOSEC ANSI switchgear com-plies with the following rele-vant standards and specifica-tions as applicable:

• ANSI/IEEE Std. C37.20.3-2001

• ANSI/IEEE Std. C37.20.4-2001

• ANSI/IEEE Std. C37.57-2003

• ANSI/IEEE Std. C37.58-2003

• ANSI/IEEE Std. 1247-2005

• ANSI/IEEE Std. C37.22-1997

• CSA C22.2 No. 193-M 1983

• CSA C22.2 No. 31-04

• EEMAC G11-1(measurement of Corona)

• IEC 62 271-105

Third-party listing

SIMOSEC ANSI is available formost configurations with ULor C-UL listing.

Type of service location

SIMOSEC ANSI switchgear canbe used as an indoor installa-tion in accordance with NEC(NFPA70)

• Outside lockable electricalservice locations at placeswhich are not accessible tothe public. Enclosures ofswitchgear can only beremoved with tools.

• Inside lockable electricalservice locations. A lockableelectrical service location isa place outdoors or indoorsthat is reserved exclusivelyfor housing electrical equip-ment and which is kept un-der lock and key. Access is re-stricted to authorized person-nel and persons who havebeen properly instructed inelectrical engineering.Untrained or unskilled per-sons may only enter underthe supervision of authorizedpersonnel or properly in-structed persons.

Terms

• “Make-proof groundingswitches” are groundingswitches with short-circuitmaking capacity according toIEC 62 271-102

• Switch-disconnector corre-sponds to interrupter switch

• HV CL are high-voltagecurrent limiting fuse links

���������

���������

�������

���������

����

���

����

����

�����������

���������

���������

����

�����

��

� �

����

���������

Alti

tude

corr

ectio

nfa

ctor

Site altitude in m/ft above sea level

Insulating capacity

• The insulating capacity is veri-fied by testing the switchgearwith rated values of short-duration power-frequencywithstand voltage and light-ning impulse withstand volt-age according to IEC 60 694/VDE 0670-1000 andANSI/IEEE C37.20.3.

• The rated values are referredto sea level and to normalatmospheric conditions14.7 PSI, 68 °F, 0.00068 lb/ft3

humidity in accordance withIEC 60 071/VDE 0111 andANSI/IEEE.

• The insulating capacitydecreases with increasingaltitude.For site altitudes above1000 m/3281 ft (above sealevel) the standards do notprovide any guidelines for theinsulation rating. Instead,special regulations apply tothese altitudes.

Site altitude

• As the altitude increases, theinsulating capacity of insula-tion in air decreases due tothe decreasing air density.

• For site altitudes above1000 m/3281 ft a higherinsulation level must beselected. This results fromthe multiplication of therated insulation level for0 mm/0 ft to 1000 m/3281 ft(above sea level) with alti-tude correction factor Ka.

Result:

According to the abovetable, a switchgear for arated voltage of 27.6 kV isto be selected.

Table – Insulating capacity

Rated voltage (rms value) kV 8.25 15 27.6

Rated short-duration (1 minute) power-frequency withstand voltage (rms value)

– Across isolating distances kV 39.6 39.6 66

– Between phases and to ground kV 36 36 60

Rated lightning impulse withstand voltage (peak value)

– Across isolating distances kV 105 105 138

– Between phases and to ground kV 95 95 125

Standards, specifications, guidelines

Standards

Page 41: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

41Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008

• For cable testing– the installation and

operating instructions ofthe switchgear

– the information on manu-facturer-dependent cable

sealing ends– the cable version

(e.g. paper-insulated mass-impregnated cables, PVCcables or XLPE cables)must be observed.

Cable testing

• For switch-disconnectorfeeders

• DC voltage test

before the test:

Remove or disconnect anyvoltage transformers at thecable connection in SIMOSECANSI switchgear.

SIMOSEC ANSI switchgearfor rated voltages up to27.6 kV can be subjected tocable tests at a max. DC testvoltage of 70 kV. The voltageat the busbar may be 27.6 kVin this case.

Rated voltageof switchgear

kV

DC test voltage,maximum value

kV

VLF* test voltagecosine-rectangularwaveform rms(peak) voltage

kV

VLF* test voltagesinusoidalwaveform rms(peak) voltage

kV

15 55 22 (22) 16 (22)

27.6 72 33 (33) 23 (33)

Climate and ambientconditions

SIMOSEC ANSI switchgear maybe used, subject to possible ad-ditional measures – e.g. panelheaters or floor covers –under the following ambientconditions and operatingtemperatures:

• Ambient conditions– Natural foreign materials– Chemically active pollutants– Small animals

• Operating temperaturesThe operating temperaturesare classified according toANSI/IEEE C37.20.3

SIMOSEC ANSI switchgear islargely insensitive to climateand ambient conditions byvirtue of the following features:

• No cross insulation forisolating distances betweenphases

* VLF = Very Low Frequency.Refer to IEEE Standard 400.2-2004“IEEE Guide for Field Testing ofShielded Power Cable SystemsUsing Very Low Frequency (VLF)”.For cosine-rectangular waveform,the rms value is taken as equal tothe peak value. For sinusoidalwaveform, the rms value is 0.707times the peak value, if distortion isless than 5 %.

• Metal enclosure of switchingdevices (e.g. three-positionswitch) in gas-filled stainless-steel switchgear vessel

• Dry-type bearings inoperating mechanism

• Essential parts of the operat-ing mechanism made ofcorrosion-proof materials

• Use of climate-independentcable-type current trans-formers

• All contacts (switch discon-nector and make-proofgrounding switch) are main-tenance-free

• Joints of the energizedcopper bars are silver plated

• Under indoor operatingconditions, SIMOSEC ANSIrequires low maintenance

Protection against solidforeign bodies, electric shockand ingress of water

SIMOSEC ANSI switchgearfulfills acc. to the standardsANSI/IEEE C37.20.3 thefollowing type of protection:All openings in the enclosureprevent the entrance of a rodwith a diameter of 3.2 mm/0.13 inch.

Test voltages:

Aseismic capacity (optional)

SIMOSEC ANSI switchgear canbe upgraded for regions at riskfrom earthquake.

For upgrading, earthquakequalification testing has beencarried out in accordance withthe following standards asapplicable:

– IEC 60 068-3-3, 1993– IEC 60 068-2-6, 1195– IABG TA13-TM-002/98

(guide)– NFPA 5000 and IBC Level

Seismic Simulation

Within the range of the pre-vailing earthquake frequenciesfrom 1 to 35 Hz, the requiredresponse spectrum to IBC200 % and 300 % covers thefollowing response spectra:

– Uniform Building Code zone 4– Seismic Requirements

Spec. 9067; Department ofWater & Power, Los Angeles

– GTS-1.1013 ENDES, Chile– VDE 0670-111– IABG TA13-TM-002/98

category 2

Standards

Standards, specifications, guidelines

Switchgear color

Light grey No. 61according to ASTM D1535 97(Munsell notation8.3 G6.10/0.54)

Page 42: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 200842

Responsible for

Technical contents:Siemens AG, Dept. PTD M 2 PPMErlangen, Germany

General editing:Siemens AG, Dept. E CC MCC RErlangen, Germany

Page 43: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV
Page 44: Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

www.usa.siemens.com/energy

All statements, technical information and recommendationscontained herein are based on information and tests webelieve to be reliable. The accuracy hereof is not guaranteed.Since conditions of use are outside our control, the user shoulddetermine the suitability of the product for its intended use andassumes all risk and liability whatsoever in connection herewith.

Siemens Power Transmission & Distribution, Inc.7000 Siemens RoadWendell, NC 27591Phone: 1-800-347-6659