metasys® system ul® 864 uukl ninth edition smoke
TRANSCRIPT
1Metasys® System UL® 864 UUKL Ninth Edition Smoke Control SystemTechnical Bulletin
Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SCT Tool and the LCT Standard Applications Library . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Smoke Control Software and Firmware Version Numbering. . . . . . . . . . . . . . . . . . . . . 12
Smoke Control Labeling - Factory and Production Date Codes . . . . . . . . . . . . . . . . . . 12
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Smoke Control Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Eighth Edition and Ninth Edition Coexistence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
FSCS (Fire Fighters Smoke Control Station) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
FSCS Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
FSCS Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
NAE Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Metasys® System Smoke Control System Overview. . . . . . . . . . . . . . . . . . . . . . . . 19Smoke Control Application Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Overview of HVAC Smoke Control System Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Central Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Dedicated Smoke Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Non-Dedicated Smoke Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Individual Floor Fan Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Coil Units/Water Source Heat Pumps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Induction Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Variable Air Volume (VAV) Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Smoke Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Smoke Movement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Smoke Control Strategies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control SystemTechnical Bulletin Code No. LIT-12011252
Issued August 7, 2008Supersedes May 2, 2007
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin2
Initiating Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Manual Initiation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Automatic Initiation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
End-to-End Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Fan Relay Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Response Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
UL 864 UUKL Ninth Edition Communication Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Automatic Fan Command Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Manual Fan Command Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Weekly Dedicated Fan Test Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Automatic Damper Command Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Manual Damper Command Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Weekly Dedicated Damper Test Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Network Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Fire Alarm Annunciation Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36IFC2-640 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
IFC2-3030 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
IFC-320 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Surge Protection Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Ethernet Transient Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
APC PNET1GB Ethernet Transient Protector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Power Surge Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Tripp Lite 8 Ultra Surge Suppressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Tripp Lite ISOBAR 12 Ultra Surge Suppressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Network Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Copper Cable Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 3
Fiber-Optic Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
ST Style Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
MTRJ Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
NU-RJ45SW1-0U 24 Port Ethernet Switch with RJ45 Connectors . . . . . . . . . . . . . . . . 48
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5 Port Ethernet Copper Switch with RJ45 Connectors . . . . . . . . . . . . . . . . . . . . . . . . . 50
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Media Convertors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
NU-MC101-0U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
NU-MC102-0U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Smoke Control Network Automation Engines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Standard NAE Features and Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Serial Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
USB Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Smoke Control NAEs MS-NAE5510-1U and MS-NAE5520-1U . . . . . . . . . . . . . . . . . . . . 62
Device Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Powering On the NAE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Disconnecting Power from the NAE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Smoke Control NAEs MS-NAE4510-2U and MS-NAE4520-2U . . . . . . . . . . . . . . . . . . . . 70
Device Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin4
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Smoke Control NAEs MS-NAE3510-2U and MS-NAE3520-2U . . . . . . . . . . . . . . . . . . . . 75
Device Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Wiring Considerations and Guidelines for Network Integrations . . . . . . . . . . . . . . . . . . 78
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
MS/TP Field Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
MS/TP Bus Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
FC Bus Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
SA Bus Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Baud Rates on the MS/TP Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Device Addresses on the MS/TP Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Setting a Device Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
SMK-MOVKIT-MSTP Transient Protection Kit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
SMK-MOVKIT-MSTP Wiring for MS/TP FC Bus Communication Terminations . . . . . . . . . 90
SMK-MOVKIT-MSTP Wiring for SA Bus Communication Terminations . . . . . . . . . . . . . . . 92
MOV Requirements for MS/TP I/O Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
End-of-Line Termination on the MS/TP Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
End-of-Line Termination Switch Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
FC and SA Bus Device EOL Switch Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
EOL Termination on the FC Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
EOL Termination on the SA Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
SA Buses with Multiple Network Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Terminating FC Devices that do not have Integral EOL Termination Capability . . . . . . . . 101
FC Bus Rules when using TEC26xx Series Thermostats and Third-Party MS/TP Devices106
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 5
FC Bus Rules and Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
SA Bus Rules and Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
MS/TP Bus Cable Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Wiring the MS/TP Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
General MS/TP Bus Wiring Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
FC Bus Wiring Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
FC Bus and SA Bus Screw Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Grounding the Cable Shield on MS/TP Bus Segments . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
SA Bus 6-Pin RJ-Style Modular Jack and Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Commissioning Devices on the MS/TP Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
NU-RPT101-0U RS-485-to-RS-485 Repeater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Setting EOL for the Repeater. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
SMOKE-TRNKIT-1U Tranzorbs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
MS/TP Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124FEU16x0 and FEU26x0 Field Equipment Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Common FEC Configuration Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Setup and Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
IOMx710 Field Equipment Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Common IOM Configuration Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin6
Wiring the IOM1710. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Wiring the IOM2710 and IOM3710 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Wiring the IOM4710. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
IOMx710-0U Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
VMA16x0 Field Equipment Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Common VMA Configuration Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
MS/TP SA Bus Network Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Selection Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
LONWORKS® Field Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169Network Topologies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Bus Topology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Devices per Segment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
LONWORKS Network Bus Topology Termination NXM-TERM-FTT-U . . . . . . . . . . . . . . . . 170
SMK-MOVKIT-LON Transient Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
SMK-MOVKIT-LON Requirements for LON Communication Bus Transient Protection . . 173
SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
LN Series Programmable VAV Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Selecting Differential Pressure Scales. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 7
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
NXP-FSC-01U Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
NXP-CPU-01U CPU Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Connecting 24 VAC Power to the NXP-CPU-01U CPU Board . . . . . . . . . . . . . . . . . . . . . 189
Connecting I/O Boards to the NXP-CPU-386-01U CPU Board . . . . . . . . . . . . . . . . . . . . . 190
NXP-CPU-386-01U CPU Board to I/O Board Ribbon Cable Pinouts . . . . . . . . . . . . . . . . 191
I/O Board Addressing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
NXP-FSC-01U I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
NXP-8UI-01U (8 UI Board) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
NXP-8DO-01U (8 DO Board) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
NXP-4DO4AO-01U (4 DO/4 AO Board) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
i.LON 600 LONWORKS/IP Server Router (72603-U) . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin8
NXE-RPT-FTT-U LON Repeater. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
NXE-FTT-FTT-U Router . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Smoke Control System Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235SCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
LONWORKS Network Configuration Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
System Programming Guidelines for Smoke Control . . . . . . . . . . . . . . . . . . . . . . . . . 235
Enclosures and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236PAN-PWRSP-U Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Wiring the PAN-PWRSP-U Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
PAN-PWRSP-U Power Supply Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
PAN-96VAXFR-U Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Power Distribution Panel and Enclosure (PA0P00010FC0-U) . . . . . . . . . . . . . . . . . . . 244
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
UL Label Placement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
Smoke Control Listed Accessories in a Smoke Control Panel . . . . . . . . . . . . . . . . . . 247
Non-Smoke Control Listed Accessories in a Smoke Control Panel . . . . . . . . . . . . . . 247
Ordering Smoke Control Enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Enclosures Requiring a Union Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Ordering and Revision Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250General Smoke Control Ordering Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Selection Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 9
Smoke Control UL 864 UUKL Ninth Edition Compliance Checklist . . . . . . . . . . . 257Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
UL 864 UUKL Ninth Edition Smoke Control Compliance Survey . . . . . . . . . . . . . 258General UUKL Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
FSCS UUKL Ninth Edition Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
Smoke Control Wiring UUKL Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin10
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 11
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control SystemTechnical Bulletin
Document IntroductionThis document provides sales representatives, project engineers, application engineers, system representatives, and system installers with the information necessary to sell, engineer, and install a Metasys® system smoke control system that complies with the Underwriters Laboratories, Inc.® (UL) requirements for the UL 864 UUKL Ninth Edition Smoke Control Listing. To comply with the Listing, you must follow the requirements and restrictions placed on the Metasys system components as detailed in this and other Metasys system documentation applying to the UL 864 UUKL Ninth Edition Listing. The restrictions apply to both used and assembled Metasys system components.
Note: The Intelligent Fire Controller (IFC) fire system or third party fire system is the primary fire annunciation station. The Johnson Controls® Metasys system smoke control system is utilized as a secondary fire annunciation station.
This document specifically addresses the Johnson Controls® Metasys system smoke control system. This document provides information on the Ethernet-based systems, communication equipment, and MS/TP Bus and LON® Bus controllers necessary to create a Metasys system smoke control application. Do not confuse this document with the Metasys System Extended Architecture Smoke Control UL 864 UUKL Eighth Edition system.
Related DocumentationThe Metasys System UL 864 UUKL Ninth Edition smoke control Application Notes are listed in Table 1. Table 1: Related DocumentationFor Information On Refer To LIT No./Part No.Single-Story Shopping Mall Smoke Control
Metasys System UL® 864 UUKL Ninth Edition - Standard Smoke Control Applications Application Guide
LIT-12011308
Multi-Story Building Smoke ControlWarehouse Smoke Control
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin12
SCT Tool and the LCT Standard Applications Library The Site Configuration Tool (SCT) is used in all phases of engineering, installation, and commissioning of NAEs, FC bus devices, and LON devices that make up the Metasys smoke control system. The SCT is used offline to create archive databases that are downloaded to a smoke control NAE. The Logic Connector Tool (LCT), contained in the SCT, was used to create the standard smoke control applications included on the Branch Purchase Package (BPP) CD.
The standard smoke control applications can be installed and executed on any smoke control NAE. Use the standard smoke control applications as written, any sequence modification to the LCT program must be pre-approved by the Authority Having Jurisdiction (AHJ). The SCT tool must not be accessible to anyone other than designated qualified technicians who are responsible for installing, commissioning, and maintaining the smoke control site configuration. Password restriction in conjunction with SCT accessibility will prevent unauthorized editing of the smoke control sequences.
Smoke Control Software and Firmware Version NumberingMetasys smoke control system software uses the following numbering scheme:
X.x.y
Where:
• X is the major revision
• x is the minor revision
• y is a patch
Example: 3.0.1
Smoke Control Labeling - Factory and Production Date CodesJohnson Control’s Ninth Edition smoke control products all have a coded label that designates the factory where the product was produced and its production year and week (LLLYYWW).
Where LLL is the 1 to 3 character factory location code
Where YY is the last 2 digits of the Gregorian Calendar year
Where WW is a 2 digit number corresponding to the week of the current calendar year (01 thru 52)
For example, a part manufactured at the Reynosa factory in the 12th week of 2007 would have a label code of M0712.
Figure 1: Example Label With Date Code
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 13
Factory Location List
ReferencesWhen designing your smoke control system, you must read and become familiar with the following documents, codes, and standards, as applicable:
• National Fire Protection Association (NFPA) 92A Recommended Practice for Smoke Control Systems
• American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) publication entitled Design of Smoke Control Systems for Buildings
• NFPA 70 National Electrical Code
• NFPA 72 National Fire Alarm Code
• NFPA 101 Life Safety Code
• NFPA 90A Standard for the Installation of Air-Conditioning and Ventilating Systems
• NFPA 92B Guide for Smoke Management Systems in Malls, Atria, and Large Areas
• International Code Council (ICC) which includes:
- Building Officials and Code Administrators International (BOCA) model code
- International Conference of Building Officials (ICBO) model code
- Southern Building Code Congress International (SBCCI) regulations
• UL 864 Ninth Edition Standard for Control Units and Accessories for Fire Alarm Systems
Table 2: Factory Location Code TableFactory Code Factory LocationRY1 Plant 1, Reynosa, Mexico
RY2 Plant 2, Reynosa, Mexico
LKY Louisville, Kentucky
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin14
Smoke Control Requirements
Eighth Edition and Ninth Edition CoexistenceThe intended combined smoke control system must be approved in writing by the local Authority Having Jurisdiction (AHJ) prior to the installation of any Ninth Edition equipment.
To maintain the UL smoke control Listing, the following rules for a smoke control system where Eighth Edition and Ninth Edition smoke control equipment coexist must be followed:
1. The isolation of the Eighth and Ninth Edition smoke control equipment must occur at the ethernet switch.
2. The Eighth Edition smoke control system is installed and operating as detailed in the Johnson Controls Metasys System Extended Architecture Smoke Control UL 864 UUKL Eighth Edition literature.
3. The Ninth Edition smoke control system must be installed and operate as detailed in the Johnson Controls Ninth Edition smoke control literature.
4. Do not replace an Eighth Edition supervisory controller with a Ninth Edition supervisory controller in order to expand the Eighth Edition smoke control system. Eighth Edition smoke control systems must remain N2 field bus only and Ninth Edition smoke control systems must only be MS/TP and/or LON field bus.
5. If an Eighth Edition supervisory controller requires replacement, it must only be replaced with an Eighth Edition smoke control replacement part (Ninth Edition supervisory controllers are not allowed as Eight Edition replacement parts).
6. The operation of the smoke control applications must have continuity between the two systems - floor above/floor below / etc. smoke control applications must be programmed to allow smoke control between all floors as if a single system were controlling the building.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 15
Figure 2 shows coexisting Eighth Edition and Ninth Edition Smoke Control Systems with devices that are supported by each Edition.
Figure 2: Coexisting Eighth Edition and Ninth Edition Smoke Control System Details
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin16
FSCS (Fire Fighters Smoke Control Station)
FSCS GuidelinesFollow these guidelines:
• Use a UL 864 UUKL Listed FSCS to provide manual control of smoke control systems. You must use the UL Listed annunciator panel made by Automation Displays, Inc. See the FSCS Requirements on page 18 for ADI contact information.
• Provide positive indication of operation on the FSCS for all smoke control equipment, for example, the damper reaches its intended position.
• Configure each Binary Output (BO) object used for pressurization and exhaust control outputs with positive feedback. Positive feedback monitors the associated controlled equipment status. Typically, smoke control dampers provide a pair of feedback binary inputs for the two damper end switches, full open and full closed. For smoke control fans, provide positive indication of air flow with either a flow switch or pressure differential sensor to determine the intended operating status of the fan.
• Display the status of all smoke control systems on the FSCS.
• Indicate, both visibly and audibly, on the FSCS any trouble conditions, when smoke control equipment does not respond to automatic or manual commands. The FSCS controls the Sonalert logic for all smoke control systems, no other application is necessary.
• Prevent the duct smoke detectors from stopping any smoke control fans once the smoke control system has been activated, if the smoke control strategy is such that the return duct exhausts the smoke from the building during the smoke control system operation. Duct smoke detectors are often located in the return duct of a Heating, Ventilating, and Air Conditioning (HVAC) fan and connected to stop the fan when smoke is detected, which is in compliance with NFPA 90A.
• Use the Weekly Dedicated Test section, located in each of the three Application Notes, on all dedicated smoke control systems to verify proper operation of Dampers and Pressurization Fans. Refer to the Single-Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System UL 864 UUKL Ninth Edition Application Note (LIT-12011067), Multi-Story Building Smoke Control with FSCS Override- Metasys System UL 864 UUKL Ninth Edition Application Note (LIT-12011068), Warehouse Smoke Control with FSCS Override - Metasys System UL 864 UUKL Ninth Edition Application Note (LIT-12011069) for more information.
• Automatic activation of any smoke control sequence of operation must have priority over any automatic environmental control strategy and over any non-smoke control manual commands. When an automatic smoke control sequence is initiated, the system design must bypass the following operational overrides:
- High and Low Temperature Protection Devices (specifically, A-11 and A-25 series Temperature Protection Devices)
- Return and Exhaust Air Duct Smoke Detectors
• Make the indication of a trouble condition from any air duct smoke detector available to FSCS operators so that they are able to make informed decisions concerning their override actions if smoke is detected elsewhere, especially in the supply air. This can be in the form of annunciation on the fire alarm system control panel or a remote annunciator controlled by the fire alarm system.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 17
• Give the highest priority to the FSCS to manually activate or deactivate any predefined smoke control strategy. Give automatic smoke control a higher priority than any manual or automatic HVAC application.
• After a smoke alarm is received and acted upon automatically by the smoke control system, additional smoke alarms must not cause the smoke control system to take automatic secondary actions. However, the system must execute any manual commands from the FSCS.
• Ensure that all communication links between buildings are fiber-optic cable or copper cable buried in a conduit that is separate from power wiring.
• Ensure that response time for individual smoke control components to reach their intended position from the point of command does not exceed the following time periods: 60 seconds for fan operation at the desired state plus 10 seconds to annunciate; 75 seconds for completion of damper travel plus 10 seconds to annunciate. In the case of fan start after damper close add these times. If the damper must be closed before the fan starts, the total response time could be up to 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate is added to this time. (Control system response is the time from automatic detection of a smoke condition to the issuing of the first smoke control command to the equipment.)
• Automatic activation of any smoke control sequence of operation has priority over any non-smoke control manual commands and any automatic environmental control strategy, when an auto smoke control sequence is initiated. High and low temperature protection devices and return and exhaust air-duct smoke detectors are bypassed.
• Use the UL Listed Smoke Control NAE to interface all input and output smoke control points.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin18
FSCS RequirementsRequirements of an FSCS include the following. The FSCS must have:
• full monitoring and manual control capability over all smoke control systems and equipment
• the capability to override (partially or in full) any operation in progress, including programmed actions, non-smoke control manual overrides, and non-smoke control bypasses
• the highest priority over all smoke control systems and equipment
• a building diagram clearly indicating the type and location of all smoke control equipment
• indication of the actual status (not the command status) of systems and equipment used for smoke control. This includes both the full open status and the full closed status of each damper, the status of each fan used for smoke control, and the air flow status of every fan.
• the ability to activate an audible signal if the operation proof sensor (binary feedback point) failed to provide positive feedback that its command was executed within the allowed response time
• hardware supervision alarms, such as binary feedback trouble on fans and dampers, as well as the system trouble points, that will turn on the FSCS alarm horn
• sole control (Use only one FSCS on a Metasys system network used for smoke control applications, unless multiple FSCSs are approved by the AHJ.)
Note: You must use the approved UL Listed display panel as your FSCS. This panel is available from:
Automation Displays, Inc. (ADI)3533 N. White AvenueEau Claire, WI 54703(715) 834-9595
The FSCS can be connected to any UL 864 UUKL Listed NAE (MS-NAE5510-1U, MS-5520-1U, MS-NAE-4510-2U, MS-4520-2U, MS3510-2U, or MS-3520-2U) in the network.
NAE Requirements
Alarm Repository
The smoke control NAE must not overwrite the initial smoke event that initiated the smoke control sequence. This a required setting for all UL 864 UUKL Ninth Edition smoke control NAEs.
Refer to the Required Smoke Control Site Object and Smoke Control NAE Settings section in the Metasys System UL 864 UUKL Ninth Edition Standard Smoke Control Applications Application Note (LIT-12011308) for details on these settings.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 19
Metasys® System Smoke Control System Overview
Smoke Control Application ExamplesTo help design a smoke control system, Figure 3 - Figure 5 show examples that comply with UL 864 UUKL Ninth Edition listings, incorporating smoke control and non-smoke control systems. These are examples - the number and arrangement of components in your system may differ. Ensure that your system complies with all UL 864 UUKL Ninth Edition device and communication requirements and restrictions.
See Figure 4 for MS/TP connection details and Figure 5 for LON Bus connection details.
Figure 3: Metasys System Smoke Control System Main Connection Details
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin20
Figure 4: Metasys System Smoke Control System FC Bus Connection Details
FC A FC BFC A
MS-NAE5510-1USmoke Control NAE
MS-NAE4510-2Uor
MS-3510-2USmoke Control NAE
NOTE: NAE MS-5510-1U (FC Bus A and FC Bus B ports) and MS-NAE4510-2U or MS-3510-2U (FC Bus A ports) can be configured as:
1. Smoke Control bus only. 2. Smoke Control bus with a Repeater isolated Non-Smoke Control bus. 3. Non-Smoke FC bus or non-smoke N2 bus.
SA Bus
Smoke Control 55/45/35 NAE
FC Bus
IOM
FEC
NetworkSensor
NU-RPT101-0 Repeater
SA Bus
VMA SA BusIOM
IOM
IOM IOMNetworkSensor
NetworkSensor
. . .
. . .
. . .
FC Bus
A - Near Side
B - Far Side
To either the
Non-Smoke Control equipment.
Extended Smoke Control FC Busor
NOTE: Repeater is utilized to:
1. Extend the physical length of a Smoke Control FC bus.
2. Isolate the Smoke Control bus from Non-Smoke Control equipment and/or Third-Party equipment on the same FC bus. Once isolated from the smoke control bus, no smoke control devices can be added to the Far Side bus.
1
SMO
KE
_WIR
E_F
C_D
ETA
ILS
FC Bus
FSCS Panelwith FEC1610
SA Bus
FC Bus Details
NOTE: 3rd Party Fire System Points may be connected as Dry Contacts to a digital input on an FEC or IOM.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 21
Figure 5: Metasys System Smoke Control System LON Bus Connection Details
LON Bus
MS-NAE5520-1USmoke Control NAE
LON Bus
MS-NAE4520-2Uor
MS-3520-2USmoke Control NAE
NOTE: Repeater may be utilized to:
1. Extend the physical length of a Smoke Control LON Bus. 2. Isolate the Smoke Control bus from Non-Smoke Control equipment or Third-Party equipment.
2
Smoke Control 55/45/35 NAE
LON Bus
NXE-RPT-FTT LON Repeater
A - Near Side
B - Far Side
ToNon-Smoke Control
and Third-Partyor
Extended Smoke Control Bus
FSC
VAV
Smoke Control 55/45/35 NAE
LON Bus
NXE-RPT-FTT LON Repeater
A - Near Side
B - Far Side
ToNon-Smoke Control
and Third-Partyor
Extended Smoke Control Bus
FSC
VAV
LON Bus
A - Near Side
B - Far Side
ToNon-Smoke Control
and Third-Partyor
Extended Smoke Control Bus
FSC
VAV
Smoke Control NAE
NXE-RPT-FTTLON Repeater
ToNon-Smoke Control
and Third-Partyor
Extended Smoke Control Bus
LON Bus
NXE-RPT-FTTLON Repeater
A - Near Side
B - Far Side
ToNon-Smoke Control
and Third-Partyor
Extended Smoke Control Bus
FSC
VAV
Smoke Control NAE
ToNon-Smoke Control
and Third-Partyor
Extended Smoke Control Bus
. . .
iLON 600 IP Router
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin22
Figure 6 shows a third-party Fire Alarm Control Panel used in a smoke control system. You can use any UL 864 UOJZ Listed FACP manufactured by a third party.
Figure 7 shows a application using fiber-optic cable and media converters. The following guidelines apply in this system:
• Install all fiber-optic lines and copper cables in conduit.
• Verify that all fiber-optic lines with ST connectors have a maximum length of 2000 meters (6560 feet).
• Verify that connections between a media converter and a Smoke Control supervisory controller have a maximum length of 6 meters (20 feet) and that all cables are in the same room as the media converters.
• Verify that all copper cables with RJ45 connectors are Category 5 twisted pair.
Figure 6: Fire Alarm Control Panel Inputs
IOM
Smoke Control NAE 5510-1USmoke Control NAE 4510-2USmoke Control NAE 3510-2U
FEC
Fire AlarmControl Panel(Third Party)
Fire AlarmControl Panel(Third Party)
LON
Fire AlarmControl Panel(Third Party)
LON
Fire AlarmControl Panel(Third Party)
LON
Fire AlarmControl Panel(Third Party)
FC FC
MS/TPSmoke Control NAE 5520-1USmoke Control NAE 4520-2USmoke Control NAE 3520-2U
LON
Dry ContactsMaximum
20 Foot Length(Must be in conduit)
NXP-FSC-01UNXP-FSC-01UNXP-FSC-01U NXP-FSC-01U
LON
Fire AlarmControl Panel(Third Party) 3r
d_Pa
rty_W
ire
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 23
Figure 7: Smoke Control System - Fiber-Optic and Ethernet Communications
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin24
Overview of HVAC Smoke Control System Types
Central SystemsCentral HVAC systems are frequently employed in smoke control designs. The designer should ensure that the system’s capacity is sufficient to supply the quantity of outdoor air necessary to pressurize the areas adjacent to any fire area. The designer should also make sure that the fan systems can handle situations where a fire may expand to other areas, requiring more areas to be positively pressurized. In addition, the installer must install smoke dampers at the duct risers of each floor’s supply and return takeoffs as required by NFPA 92A. Pressure controls should also be employed in order to avoid rupturing or collapsing the ductwork.
Dedicated Smoke Control Systems
Dedicated smoke control systems are fan, damper, and duct systems designed for the sole purpose of controlling smoke within a building. An example of a dedicated system is a stairwell or elevator shaft pressurization system that is operational only during a smoke control event. The dedicated smoke control systems form a system of air movement that is separate and distinct from the building’s HVAC system, and they only operate to control the flow of smoke. With their function being dedicated to the performance of smoke control, dedicated smoke control systems are more immune to faults in the building’s HVAC system.
Note: To assure full performance and maintain UL compliance, apply automatic weekly testing to all dedicated systems, including dedicated elevator shaft fans, dampers used exclusively for smoke control. Refer to the Single-Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System UL 864 UUKL Ninth Edition Application Note (LIT-12011067), Multi-Story Building Smoke Control with FSCS Override- Metasys System UL 864 UUKL Ninth Edition Application Note (LIT-12011068), Warehouse Smoke Control with FSCS Override - Metasys System UL 864 UUKL Ninth Edition Application Note (LIT-12011069) for details on how to perform the necessary tests. Any failure to properly respond in the allotted time must send a trouble signal to the FSCS.
Non-Dedicated Smoke Control Systems
Non-dedicated smoke control systems share components with other air moving equipment normally used for building environmental control. When the smoke control mode is activated, the operating mode of the building’s HVAC equipment changes in order to accomplish the objectives of the smoke control design. Non-dedicated systems tend to be less costly and occupy less space. However, from an operational standpoint, the control strategy becomes more elaborate. This may expand the number of control and monitoring points connected to a Building Automation System (BAS) and increases the complexity of the sequence of operation of the air moving equipment.
Individual Floor Fan UnitsIf sufficient outdoor air is available and the system has the capability to exhaust an area, individual or floor-by-floor fan units can be used in smoke control applications.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 25
Fan Coil Units/Water Source Heat PumpsThese types of units are generally located on the perimeters of buildings and draw only enough outdoor air to fulfill the fresh air requirements of the spaces they serve. The units are used in conjunction with central systems, which deliver fresh air and exhaust recirculated air in larger quantities. When the fan coil unit is not located in the smoke zone, it is acceptable to exclude it from the smoke control sequence. When the unit serves the smoke zone in a design that calls for the area to be negatively pressurized, its outdoor air damper should be closed, and the unit should be de-energized.
Induction Units
During a smoke control mode, induction units that serve the smoke zone should be shut down, or their primary air source should be closed off.
Variable Air Volume (VAV) SystemsThe Variable Air Volume (VAV) system, when employed as part of a smoke control strategy, is a subset of the general central system category described above. Employ control strategies that ensure adequate quantities of air pass through the terminal units to permit floor pressurization in the areas adjacent to the smoke zone. This may include overriding the air volume control to provide maximum deliverable air to the areas adjacent to the fire area. If fan-powered terminal units are used and installed in the smoke zone, shut off their fans. If bypass dampers fulfill the volume control, close the damper during smoke control mode.
Smoke Dampers
All dampers used as barriers in smoke partitions or as safety dampers in a smoke control system must be UL Listed and Classified for use in that application. (Refer to UL 555S Standard for Leakage Rated Dampers for Use in Smoke Control Systems.)
Design ConsiderationsThis section outlines the design criteria you should consider when implementing a smoke control strategy.
Smoke MovementIn general, the movement of smoke will follow the same pattern as the overall air movement within a building. The major influences on smoke movement includes stack effect, air/smoke buoyancy, air/smoke expansion, wind, pressure, and the operating HVAC system. In a fire situation, a combination of these influences usually causes smoke movement.
An accepted way of containing smoke within a compartment or an area is to create pressure differences across partitions that separate the affected area from the surrounding areas. You can accomplish this by creating higher pressure in the adjacent space than the pressure which is in the smoke zone. The pressure differential should be sufficient to overcome the effects of wind pressure, stack effect, buoyancy of hot gases, and other influences, yet permit doors leading to emergency exit routes to be opened.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin26
In addition, air flow can minimize the movement of smoke through openings such as doors. For example, you can pressurize a stairwell, thereby minimizing the migration of smoke into the stairwell. Should one of the stairwell doors open, the flow of fresh air from the stairwell reduces the movement of smoke into the affected area.
Note: Treat elevator shafts like stairwells and positively pressurize them to prevent vertical migration of smoke through the building. You may close inter-floor and inter-area duct work not being used for active smoke control at the appropriate locations, as detailed. See Table 1 Related Documentation on page 11 of this document.
Smoke Control StrategiesThe smoke alarm initiation of an automatic smoke detection device, such as an area-type smoke detector located in one of the facility’s smoke zones, generally activates the smoke control system. This activation may initiate a control strategy for the air moving equipment to create higher pressures in the areas surrounding the smoke zone than are present in the smoke zone. This may include positively pressurizing areas adjacent to the smoke zone and/or negatively pressurizing the smoke zone and exhausting air from the smoke zone. Subsequent smoke alarm conditions in other zones must be prevented from automatically changing the initial smoke control sequence. Keep in mind the guidelines provided in this section when planning your smoke control strategy.
Note: Do not use duct type smoke detectors exclusively to activate smoke control, for the following reasons:
• The dilution of air in the duct system likely results in a slow response time.
• The supply air duct detector, when exposed to outdoor air in the HVAC supply air duct, may report a false alarm condition.
• The duct system may move smoke from the smoke zone, and this causes the duct detector in the return/exhaust duct of the non-dedicated fan system to register an alarm condition.
Note: It may be acceptable to use a duct smoke detector if it is not exposed to outdoor air, the duct detector’s coverage area is equal to the area covered by a spot type area smoke detector (typically 900 square feet or less), and/or the AHJ has approved the application.
Initiating DevicesThe following section describes initiating devices for manual and automatic initiation.
Manual InitiationDo not use manual pull stations to initiate a smoke control sequence, since there is no certainty that manual devices will be activated in the area of involvement. However, you can use manual pull stations to initiate global operations, such as energizing stairwell and elevator shaft pressurization fans.
Manual implementation of the smoke control strategy takes place at the FSCS. The FSCS must be capable of overriding, either partially or in full, any automatic activation that may be in progress. It must also be capable of manually controlling each control point (damper, HVAC fan, and so forth) that is used for smoke control in the facility. Refer to the application notes in Related Documentation on page 11 for details on how to integrate an FSCS into a Metasys system.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 27
Interface devices (those that interface field points to the controller) have the following restrictions. They must:
• be listed for use in the Johnson Controls Smoke Control Listing
• be used and installed according to Johnson Controls literature
• result in fan operation at the desired state within 60 seconds (plus 10 seconds to annunciate) when commanded
• result in completion of damper travel within 75 seconds (plus 10 seconds to annunciate) when commanded
For more information, see the Smoke Control Applications in Table 1 on page 11.
Automatic InitiationYou can initiate an automatic operation of a smoke control sequence using a Multi-State or Life-Safety BACnet Gateway connected to an IFC2-640, IFC2-3030, or IFC-320 Intelligent Fire Controller panel. In addition, a third-party Fire Alarm Control Panel can initiate automatic operation of a smoke control sequence using a set of dry contacts.
Third party devices must be connected to a repeater (NU-RPT101-1U).
End-to-End VerificationEnd-to-end verification is required to ensure that the smoke control sequence of operation has been implemented. Verification must be accomplished by using damper position indicators and air flow switches or differential pressure sensors. Failures resulting in equipment failing to respond (or responding inappropriately) to commands from the Metasys smoke control system, must generate an audible and visual trouble signal at the FSCS. For HVAC dampers, used in smoke control sequences, the FSCS must display a positive indication of the damper’s fully opened position and its fully closed position and must report a trouble condition if the damper position does not agree with the commanded position. For a permanent record of trouble conditions, including situations where the commanded smoke control sequence does not equal condition, use the audit trail function to record the last commands and events during a Smoke Control Sequence.
Fan Relay SupervisionIf the project must meet Life Safety Code NFPA 101 requirements (where the fire system utilizes the HVAC system to sequence control or shutdown an HVAC fan), then fan relay supervision is required. The auxiliary relay used to control the motor starter on the HVAC system fan must be located within three feet of the motor starter. The wiring between the fan shutdown controller and the shutdown relay must be monitored for integrity (supervised). This can be accomplished by using electronic supervision or continuously powered shutdown relays that turn the fan off if power is lost to the relay circuit. In addition, proof of fan operation such as an air flow switch is required.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin28
Response TimesResponse times for individual components to achieve their intended state from the point of command should not exceed the following time periods: 60 seconds for fan operation at the intended state plus 10 seconds to annunciate; 75 seconds for completion of damper travel plus 10 seconds to annunciate. See Figure 8 through Figure 14 for examples of response times and timing order.
UL 864 UUKL Ninth Edition Communication Timing
Figure 8: UL 864 UUKL Ninth Edition Communication Timing
IFC Fire Panel NAE FSCS
On Loss of the communication to the NAE you
have 200 seconds to
annunciate the trouble at the
FSCS
Field Controller
Fan Controls
On Loss of the communication to a Fire Panel you have 200
seconds to annunciate the trouble at the
FSCS
NOTE: If the trouble is locked in for 24 hrs, the FSCS must resound the trouble by flashing the LED for the equipment and sounding the audible alarm on the FSCS again.
On Loss of the communication
to the FSCS you have 200
seconds to annunciate the Trouble/Alarm
at the NAE
On Loss of the communication
to the Field Controller you
have 10 seconds to
annunciate the trouble at the
FSCS
On a trouble for the output / feedback
circuits on the Field Controller
you have 10 seconds to
annunciate the trouble at the
FSCS
Com
mun
icat
ion
Loss
Tim
ing
Seq
uenc
e.vs
d
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 29
Automatic Fan Command Timing
Figu
re 9
: Aut
omat
ic F
an C
omm
and
Tim
ing
IFC
Fire
Pa
nel
NA
EFS
CS
Ann
unci
atio
n of
a F
ire a
larm
fro
m th
e IF
C
Fire
Pan
el
The
NAE
m
ust p
roce
ss
the
Ala
rm a
nd
send
a
Com
man
d to
th
e FS
CS
The
FSC
S m
ust i
ndic
ate
a Fi
re A
larm
w
ith a
sol
id
Zone
LE
D
In P
aral
lel,
the
NAE
mus
t tri
gger
the
Sm
oke
Con
trol
Stra
tegy
Fiel
d C
ontro
ller
Fan
Con
trols
BTh
e ov
eral
l tim
e fo
r the
fir
st S
mok
e co
ntro
l co
mm
and
is
10 s
econ
ds
from
the
annu
ncia
tion
of th
e Fi
re
alar
m a
t the
FS
CS
+ 10
Se
cond
s =
20
Seco
nds
from
th
e fir
e al
arm
at
the
IFC
Fire
P
anel
CTh
e Fa
n ha
s 60
sec
onds
to
chan
ge to
the
inte
nded
po
sitio
n
DTh
e Fa
n ha
s 60
sec
onds
to
chan
ge to
the
inte
nded
po
sitio
n, if
it
does
not
you
ha
ve 1
0 se
c to
ann
unci
ate
a Tr
oubl
e at
th
e FS
CS
ATh
e ov
eral
l tim
e fo
r an
nunc
iatio
n is
10
seco
nds,
re
gard
less
of
how
man
y co
ntro
llers
are
in
the
proc
ess
In Parallel
NO
TE: I
f the
equ
ipm
ent f
ails
to re
ach
its in
tend
ed p
ositi
on fo
r the
test
, a T
roub
le is
ann
unci
ated
on
the
FSC
S.
An
Aut
o C
omm
and
Ret
ry th
en o
ccur
s ev
ery
min
ute
until
eith
er th
e eq
uipm
ent h
as
reac
hed
the
inte
nded
pos
ition
or t
he fi
re c
ondi
tion
requ
iring
sm
oke
cont
rol o
n th
e eq
uipm
ent i
s cl
eare
d. If
the
Trou
ble
is lo
cked
in fo
r 24
hrs,
the
FSC
S m
ust f
lash
its
Trou
ble
LED
for t
he
equi
pmen
t and
reso
und
the
FSC
S au
dibl
e al
arm
.
UL
864
UU
KL
Nin
th E
ditio
n A
utom
atic
Fan
Com
man
d Ti
min
g
10 S
econ
ds
A10
Sec
onds
B1st
Com
man
d60
Sec
onds
C
10 S
econ
ds
DFi
eld
Con
trol
0 S
econ
ds
IFC
Det
ects
A
larm
and
A
nnun
ciat
es
at th
e IF
C
Fire
Pan
elTr
oubl
e An
nunc
iatio
n
Sm
oke
Alar
m A
nnun
ciat
ion
– 10
Sec
onds
V9_Automatic_Fan_Cmd
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin30
Manual Fan Command Timing
Figu
re 1
0: M
anua
l Fan
Com
man
d Ti
min
g
V9_Manual_Fan_Cmd
NA
EFS
CS
Usi
ng th
e FS
CS
sw
itche
s,
issu
e a
man
ual F
an
com
man
d
The
NA
E
mus
t pro
cess
th
e co
mm
and
from
the
FSC
S
Fiel
d C
ontro
ller
Fan
Con
trols
ATh
e ov
eral
l tim
e fo
r the
S
mok
e co
ntro
l co
mm
and
is
10 s
econ
ds
for t
he
com
man
d is
sued
at t
he
FSC
S
BTh
e Fa
n ha
s 60
sec
onds
to
chan
ge to
the
inte
nded
po
sitio
n
CTh
e Fa
n ha
d 60
sec
onds
to
chan
ge to
the
inte
nded
po
sitio
n, if
it
did
not y
ou
have
10
sec
to a
nnun
ciat
e a
Trou
ble
at
the
FSC
S
NO
TE: I
f the
equ
ipm
ent f
ails
to re
ach
its in
tend
ed p
ositi
on fo
r the
test
, a T
roub
le is
ann
unci
ated
on
the
FSC
S.
An A
uto
Com
man
d R
etry
then
occ
urs
ever
y m
inut
e un
til e
ither
the
equi
pmen
t has
re
ache
d th
e in
tend
ed p
ositi
on o
r the
fire
con
ditio
n re
quiri
ng s
mok
e co
ntro
l on
the
equi
pmen
t is
clea
red.
If th
e Tr
oubl
e is
lock
ed in
for 2
4 hr
s, th
e FS
CS
mus
t fla
sh it
s Tr
oubl
e LE
D fo
r the
eq
uipm
ent a
nd re
soun
d th
e FS
CS
audi
ble
alar
m.
UL
864
UU
KL
Nin
th E
ditio
n M
anua
l Fan
Com
man
d Ti
min
g
10 S
econ
ds
A
60 S
econ
ds
BM
anu a
l Com
ma n
d
10 S
econ
ds
C
Fiel
d C
ontro
l
0 Se
cond
s
NA
E pr
oces
ses
the
man
ual
com
man
d
Fan
Fails
to R
each
Inte
nded
Pos
ition
- Tr
oubl
e A
nnun
ciat
ion
Fan
Posi
tion
Atte
mpt
– 6
0 S
econ
ds
10 Seconds
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 31
Weekly Dedicated Fan Test Timing
Figu
re 1
1: W
eekl
y D
edic
ated
Fan
Tes
t Tim
ing
NA
EFS
CS
Fiel
d C
ontro
ller
Fan
Con
trols
ATh
e ov
eral
l tim
e fo
r the
fir
st
Equi
pmen
t Te
st
com
man
d is
10
sec
onds
fro
m th
e st
art
of th
e W
eekl
y D
edic
ated
Te
st.
BTh
e Fa
n ha
s 60
sec
onds
to
chan
ge to
the
inte
nded
po
sitio
n
CTh
e Fa
n ha
d 60
sec
onds
to
chan
ge to
the
inte
nded
po
sitio
n, if
it
did
not y
ou
have
10
sec
to a
nnun
ciat
e a
Trou
ble
at
the
FSC
S
UL
864
UU
KL
Nin
th E
ditio
n W
eekl
y D
edic
ated
Fan
Tes
t Tim
ing
10 S
econ
ds
A
60 S
econ
ds
BN
AE C
omm
and
10 S
econ
ds
C
Fiel
d C
ontro
l
0 S
econ
ds
NA
E co
mm
ands
th
e W
eekl
y Te
st to
beg
in
Dam
per F
ails
to R
each
Inte
nded
Pos
ition
- Tr
oubl
e An
nunc
iatio
n
Fan
Pos
ition
Atte
mpt
– 6
0 S
econ
ds
NO
TE: I
f the
equ
ipm
ent f
ails
to re
ach
the
inte
nded
pos
ition
for t
he te
st, a
Tro
uble
is a
nnun
ciat
ed
on th
e FS
CS.
An
Aut
o C
omm
and
Ret
ry th
en o
ccur
s ev
ery
10 m
inut
es u
ntil
the
test
is c
ompl
eted
sa
tisfa
ctor
ily. T
he te
st is
term
inat
ed a
t the
firs
t Tro
uble
indi
cate
d if
eith
er a
fire
ala
rm o
ccur
s th
at
incl
udes
this
equ
ipm
ent,
an F
SC
S Z
one
Sw
itch
is m
oved
from
the
Aut
o po
sitio
n th
at in
clud
es th
is
equi
pmen
t, or
the
indi
vidu
al e
quip
men
t FSC
S sw
itch
is m
oved
from
the
Aut
o po
sitio
n. I
f the
Tr
oubl
e is
lock
ed in
for 2
4 hr
s, th
e FS
CS
mus
t fla
sh th
e LE
D fo
r the
equ
ipm
ent a
nd re
soun
d th
e au
dibl
e al
arm
on
the
FSC
S.
V9_Weekly_Fan_Test
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin32
Automatic Damper Command Timing
Figu
re 1
2: A
utom
atic
Dam
per C
omm
and
Tim
ing
IFC
Fire
Pa
nel
NA
EFS
CS
Ann
unci
atio
n of
a F
ire a
larm
fro
m th
e IF
C
Fire
Pan
el
The
NAE
m
ust p
roce
ss
the
Ala
rm a
nd
send
a
Com
man
d to
th
e FS
CS
The
FSC
S
mus
t ind
icat
e a
Fire
Ala
rm
with
a s
olid
Zo
ne L
ED
In P
aral
lel,
the
NA
E m
ust
trigg
er th
e Sm
oke
Con
trol
Stra
tegy
Fiel
d C
ontro
ller
Dam
per
Con
trols
BTh
e ov
eral
l tim
e fo
r the
fir
st S
mok
e co
ntro
l co
mm
and
is
10 s
econ
ds
from
the
annu
ncia
tion
of th
e Fi
re
alar
m a
t the
FS
CS
+ 1
0 Se
cond
s =
20
Seco
nds
from
th
e fir
e al
arm
at
the
IFC
Fire
P
anel
CTh
e D
ampe
r ha
s 75
se
cond
s to
ch
ange
to th
e in
tend
ed
posi
tion
DTh
e D
ampe
r ha
s 75
se
cond
s to
ch
ange
to th
e in
tend
ed
posi
tion,
if it
do
es n
ot y
ou
have
10
sec
to a
nnun
ciat
e a
Trou
ble
at
the
FSC
S
ATh
e ov
eral
l tim
e fo
r an
nunc
iatio
n is
10
seco
nds,
re
gard
less
of
how
man
y co
ntro
llers
are
in
the
proc
ess
NO
TE: I
f the
equ
ipm
ent f
ails
to re
ach
its in
tend
ed p
ositi
on fo
r the
test
, a T
roub
le is
ann
unci
ated
on
the
FSC
S.
An A
uto
Com
man
d R
etry
then
occ
urs
ever
y m
inut
e un
til e
ither
the
equi
pmen
t has
re
ache
d th
e in
tend
ed p
ositi
on o
r the
fire
con
ditio
n re
quiri
ng s
mok
e co
ntro
l on
the
equi
pmen
t is
clea
red.
If th
e Tr
oubl
e is
lock
ed in
for 2
4 hr
s, th
e FS
CS
mus
t fla
sh it
s Tr
oubl
e LE
D fo
r the
eq
uipm
ent a
nd re
soun
d th
e FS
CS
aud
ible
ala
rm.
UL
864
UU
KL
Nin
th E
ditio
n A
utom
atic
Dam
per C
omm
and
Tim
ing
10 S
econ
ds
A10
Sec
onds
B1st
Com
man
d75
Sec
onds
C
10 S
econ
ds
DFi
eld
Con
trol
0 Se
cond
s
IFC
Det
ects
A
larm
and
A
nnun
ciat
es
at th
e IF
C
Fire
Pan
elTr
oubl
e An
nunc
iatio
n
Sm
oke
Ala
rm A
nnun
ciat
ion
– 10
Sec
onds
V9_Automatic_Damper_Cmd
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 33
Manual Damper Command Timing
NAE
FSC
S
Usi
ng th
e FS
CS
switc
hes,
is
sue
a m
anua
l D
ampe
r co
mm
and
The
NA
E
mus
t pro
cess
th
e co
mm
and
from
the
FSC
S
Fiel
d C
ontro
ller
Dam
per
Con
trols
ATh
e ov
eral
l tim
e fo
r the
S
mok
e co
ntro
l co
mm
and
is
10 s
econ
ds
for t
he
com
man
d is
sued
at t
he
FSC
S
BTh
e D
ampe
r ha
s 75
se
cond
s to
ch
ange
to th
e in
tend
ed
posi
tion
CTh
e D
ampe
r ha
d 75
se
cond
s to
ch
ange
to th
e in
tend
ed
posi
tion,
if it
di
d no
t you
ha
ve 1
0 se
c to
ann
unci
ate
a Tr
oubl
e at
th
e FS
CS
NO
TE: I
f the
equ
ipm
ent f
ails
to re
ach
its in
tend
ed p
ositi
on fo
r the
test
, a T
roub
le is
ann
unci
ated
on
the
FSC
S.
An
Auto
Com
man
d R
etry
then
occ
urs
ever
y m
inut
e un
til e
ither
the
equi
pmen
t has
re
ache
d th
e in
tend
ed p
ositi
on o
r the
fire
con
ditio
n re
quiri
ng s
mok
e co
ntro
l on
the
equi
pmen
t is
clea
red.
If th
e Tr
oubl
e is
lock
ed in
for 2
4 hr
s, th
e FS
CS
mus
t fla
sh it
s Tr
oubl
e LE
D fo
r the
eq
uipm
ent a
nd re
soun
d th
e FS
CS
audi
ble
alar
m.
UL
864
UU
KL
Nin
th E
ditio
n M
anua
l Dam
per C
omm
and
Tim
ing
10 S
econ
ds
A
75 S
econ
ds
BM
anu a
l Com
ma n
d
10 S
econ
ds
C
Fiel
d C
ontro
l
0 S
econ
ds
NAE
pr
oces
ses
the
man
ual
com
man
d
Dam
per F
ails
to R
each
Inte
nded
Pos
ition
- Tr
oubl
e A
nnun
ciat
ion
Dam
per P
ositi
on A
ttem
pt –
75
Seco
nds
10 Seconds
V9_Manual_Damper_Cmd
Figu
re 1
3: M
anua
l Dam
per C
omm
and
Tim
ing
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin34
Weekly Dedicated Damper Test Timing
Figu
re 1
4: W
eekl
y D
edic
ated
Dam
per T
est T
imin
g
V9_Weekly_Damper_Test
NAE
FSC
S
Fiel
d C
ontro
ller
Dam
per
Con
trols
ATh
e ov
eral
l tim
e fo
r the
fir
st
Equ
ipm
ent
Test
co
mm
and
is
10 s
econ
ds
from
the
star
t of
the
Wee
kly
Ded
icat
ed
Test
.
BTh
e D
ampe
r ha
s 75
se
cond
s to
ch
ange
to th
e in
tend
ed
posi
tion
CTh
e D
ampe
r ha
d 75
se
cond
s to
ch
ange
to th
e in
tend
ed
posi
tion,
if it
di
d no
t you
ha
ve 1
0 se
c to
ann
unci
ate
a Tr
oubl
e at
th
e FS
CS
UL
864
UU
KL
Nin
th E
ditio
n W
eekl
y D
edic
ated
Dam
per T
est T
imin
g
10 S
econ
ds
A
75 S
econ
ds
BN
AE C
omm
and
10 S
econ
ds
C
Fiel
d C
ontro
l
0 S
econ
ds
NAE
co
mm
ands
th
e W
eekl
y Te
st to
beg
in
Dam
per F
ails
to R
each
Inte
nded
Pos
ition
- Tr
oubl
e An
nunc
iatio
n
Dam
per P
ositi
on A
ttem
pt –
75
Seco
nds
NO
TE: I
f the
equ
ipm
ent f
ails
to re
ach
the
inte
nded
pos
ition
for t
he te
st, a
Tro
uble
is a
nnun
ciat
ed
on th
e FS
CS
. A
n A
uto
Com
man
d R
etry
then
occ
urs
ever
y 10
min
utes
unt
il th
e te
st is
com
plet
ed
satis
fact
orily
. The
test
is te
rmin
ated
at t
he fi
rst T
roub
le in
dica
ted
if ei
ther
a fi
re a
larm
occ
urs
that
in
clud
es th
is e
quip
men
t, an
FS
CS
Zon
e Sw
itch
is m
oved
from
the
Auto
pos
ition
that
incl
udes
this
eq
uipm
ent,
or th
e in
divi
dual
equ
ipm
ent F
SCS
sw
itch
is m
oved
from
the
Aut
o po
sitio
n. I
f the
Tr
oubl
e is
lock
ed in
for 2
4 hr
s, th
e FS
CS
mus
t fla
sh th
e LE
D fo
r the
equ
ipm
ent a
nd re
soun
d th
e au
dibl
e al
arm
on
the
FSC
S.
V9_Weekly_Damper_Test
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 35
Network CommunicationsSee Table 3 for ethernet network rules. Follow the Important information listed below. Table 3: Ethernet Network RulesCategory Rules/Maximum AllowedGeneral Star topology with network hubs, switches, and routers
Number of Devices Maximum of 100 devices can be connected to one site in the Metasys system extended architecture.
Line Length and Type Solid unshielded twisted pair (Category 5 cable): 100 m (330 ft)Stranded unshielded twisted pair (patch cable): 10 m (33 ft)RG58A/U coax cable (for 10Base2 systems): 185 m (607 ft)Plastic/glass fiber optic with external adapter: 2000 m (6600 ft)
Terminations For 10/100 BaseT, no line terminators allowed.
Surge Protection All ethernet connections must have a PNET1GB surge suppressor at each end of its ethernet cable. The ground lead of the PNET1GB must be connected to earth ground. See APC PNET1GB Ethernet Transient Protector on page 38 for additional information and wiring details.
IMPORTANT: Do not apply power to the Metasys network before finishing communication wiring and checking all wiring connections. Short-circuited or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations. Do not exceed the electrical ratings for the devices on the Metasys network.
IMPORTANT: Do not run network communication cables in the same conduit, raceway, or panel with any high voltage (>30 VAC) wiring. Isolate all network devices from high-voltage wiring and equipment. Failure to isolate network wiring and network devices from high-voltage wiring and equipment can result in damage to network devices or poor network performance.
IMPORTANT: Prevent any static electric discharge to the network wiring and network devices. Static electric discharge can damage the network devices and void any warranties.
IMPORTANT: Always consult with the customer’s Network IT department before installing Metasys Ethernet components. Other online systems may be affected, so close coordination with the IT department is very important.
IMPORTANT: Do not deform, bend, stretch, or staple Ethernet cables. Also, do not run Ethernet cables parallel to power cables or near noise inducing components.
!WARNING: Risk of Electric Shock and Property Damage. Disconnect or isolate all power supplies before making electrical connections. More than one disconnect or isolation may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin36
Fire Alarm Annunciation Panels
IFC2-640The IFC2-640 Intelligent Addressable Fire Alarm Control Panel is part of the Fire Alarm Controls. As a standalone small-to-large system or as a large network, the products meet virtually every application requirement. Designed with modularity and for ease of system planning, the IFC2-640 can be configured with just a few devices for small building applications or for a large campus or high-rise application. Simply add additional peripheral equipment to suit the application.
IFC2-3030The IFC2-3030 is an intelligent Fire Alarm Control Panel designed for medium- to large-scale facilities. Fire emergency detection and evacuation are extremely critical to life safety, and the IFC2-3030 is ideally suited for these applications.
Figure 15: IFC2-640 Intelligent Addressable Fire Alarm Control Panel
Figure 16: IFC2-3030 Fire Alarm Annunciation Panel
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 37
IFC-320The IFC-320 is designed to bring sophistication and superior performance to smaller applications. Auto-programming features allow fire protection to be established in seconds. Additional programming is quick and easy and patented technology makes the IFC-320 exceed worldwide code requirements for response time.
Figure 17: IFC-320 Fire Alarm Annunciation Panel
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin38
Surge Protection Devices
Ethernet Transient Protection
APC PNET1GB Ethernet Transient ProtectorThe PNET1GB provides standalone data-line surge suppression for ethernet networks, telecommunication and PC system protection.
APC's Surge Protectors are fail safe, which means that once the circuit of an APC Surge Protector has been compromised the unit disconnects equipment from the power supply ensuring that no damaging surges reach your equipment.
See the Wiring section of each ethernet device for proper wiring connections.
Safety Precautions
• Use only for ethernet and token ring interface cards, hubs, switches, and other LAN equipment.
• Turn off power to all equipment to be protected prior to installing the PNET1GB.
• The PNET1GB must be connected to earth ground.
• To prevent electric shock when installing the ground wire to the electrical power outlet ground, turn off electricity to the outlet.
From the electrical panel, switch off the appropriate circuit breaker or remove the fuse for that circuit/outlet.
Figure 18: APC Pnet1Gb Ethernet Transient Protector
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 39
Installation
1. Verify all hardware installation and software configuration prior to installing the PNET1GB. Verify that the system functions correctly with the existing network line.
2. Switch off power to the equipment to be protected.
3. Disconnect the existing network line from the equipment to be protected.
4. Connect this network line to the input jack o on the PNET1GB.
5. Connect one end of the supplied 6-inch patch cable to the output jack on the PNET1GB. This jack is labeled on the PNET1GB with a circle and arrow.
6. Connect the other end of the patch cable to the input jack on the network equipment j to be protected.
7. Connect the green/yellow ground wire to ground.
Note: To fully protect your system, all surge protectors must be properly grounded. If your electrical system is a two-wire non-grounded system, the PNET1GB may be left ungrounded. However, if the PNET1GB ground wire is unconnected to earth ground, the longitudinal (line to ground) surge protection will be rendered ineffective.
Note: An APC PNET1GB is required at both ethernet cable ends of all ethernet connections. It must be connected as closely as possible to the device. It must be mounted as shown in Figure 19.
Figure 19: APC PNET1GB Ethernet Transient Protector Mounting Details
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin40
Specifications
UL Label Placement
UL Listing labels must be positioned as shown in Figure 20.
Table 4: APC PNET1GB SpecificationsCategory SpecificationsPeak Current Normal Mode 6.50 kAmps
Peak Surge Current 250A Max with 8 x 20µs waveform
Peak Voltage ±6,000V with 1.2 x 50µs waveform
Breakover Voltage 60 VDC
NM Surge Response Time 1 ns
Dataline protection RJ45 10/100/1000 Base-T Ethernet protection
Data Lines Protected 1
Let Through Voltage Rating < 60
Nominal Operating Temperature 32 to 120º F (0 to 49º C)
Relative Humidity 10 to 93%, Non-Condensing
Lines Protected Pin #1-8 (on Pin 8 Modular Jack)
Standard Compliance Compliant with IEEE 802.3, 802.5, 802.12 Ethernet standard, Category 5, 6
Compliance UL 497BUL 1449 TVSS Rating 330 V
Dimensions (H x W x D) 4.10 x 1.87 x 1.10 in (10.4 x 4.7 x 2.8 cm)
Net Weight 0.11 lbs. (0.05 kg)
Figure 20: PNET1GB-0U UL Label Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 41
Power Surge ProtectionThe Tripp Lite Isobar Ultra 8 and Ultra 12 premium surge and noise suppression devices prevent equipment damage and performance problems resulting from damaging transient surges and line noise. Their active filter network maintains noise-free output with zero reaction / response time. Rugged all-metal, mountable housing fitted with high quality duplex-style output receptacles. 8 outlets, 2350 joules AC protection level, less than 35V let through voltage, 3 diagnostic LEDs.
Tripp Lite 8 Ultra Surge Suppressor
Robust surge suppression circuits with sine-wave tracking offer extreme levels of protection against the heaviest surge conditions exceeding IEEE 587 category A & B specifications and reducing 6,000V test surges to harmless levels under 35 volts. Isobar's unique protection system combines large torroidal chokes, ferrite rod-core inductors, High Frequency/Very High Frequency (HF/VHF) capacitors and multiple layers of metal oxide varistors into exclusive isolated filter banks that remove Electromagnetic Interference/Radio Frequency Interference (EMI/RFI), even noise generated by other pieces of connected equipment. ISOBAR8ULTRA offers 8 outlets arranged in four filter banks to prevent system crashes, reboots and performance problems common as noisy system peripherals are powered off and on.
Surge suppression rated at 2350 joules / 97,000 amps offers network-grade protection. Widely spaced NEMA 5-15 outlets accommodate up to 4 large transformer plugs without blocking outlets. Diagnostic LEDs confirm power availability, line fault and protection status. Includes 12 foot AC line cord with space-saving angled input plug, and keyhole mounting tabs.
Figure 21: Tripp Lite Isobar 8 Ultra Surge Suppressor
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin42
Specifications
UL Label PlacementUL Listing labels are not required for this product.
Table 5: Tripp Lite ISOBAR 8 Ultra Surge Suppressor SpecificationsCategory SpecificationVoltage compatibilityFrequency compatibility
120 VAC60 Hz
Output volt amp capacity 12 Amps
Output watt capacity 1440 watts
Outlet quantity / type 8 NEMA 5-15R output receptacles, high quality duplex style
Transformer accommodation Supports up to 4 large transformer plug accessories without covering remaining outlets
Input connection type NEMA 5-15P input plug
Input cord length 12 ft (3.7 m)
Recommended electrical service 120V 15A
Diagnostic LEDs PROTECTION PRESENT (green)LINE FAULT (red)LINE OK (green)
Switches Two position red illuminated on/off power switch
Protection modes Includes full normal mode (H-N) and common mode (N-G / H-G) line surge suppression
AC suppression joule rating 2350 joules
Clamping voltage (RMS) 140V
AC suppression response time NM = 0 ns, CM = <1 ns
AC suppression surge current rating 97,000 amps (36,000 NM / 61,000 CM)
AC suppression components used Metal oxide varistors, toroidal balanced chokes, ferrite rod-core inductors and VHF capacitors.
Safe thermal fusing Prevents unsafe conditions during extreme extended overvoltages and catastrophic occurrences
UL1499 let through rating 330V - UL Verified
IEEE587 Cat. A ringwave let through Less than 35 volts
EMI / RFI filtering 40-80 dB
Unit Weight 4.6 lbs (2.1 kg)
Dimensions (Height x Width x Depth) 2.5 x 9 x 3.5 in (6.4 x 22.9 x 8.9 cm)
ComplianceUL 1449 1998 Rev. (AC Suppression) UL1449 (UR status)
UL 1283 (EMI Filter) UL 1283
UL 1363 (EMI Filter) UL 1363
cUL / CSA (Canada) cUL
Approvals Exceeds IEEE 587 category A&B specifications
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 43
Tripp Lite ISOBAR 12 Ultra Surge SuppressorTripp Lite's ISOBAR12ULTRA offers network-grade surge and noise suppression in a versatile all-metal multi-mount cabinet. Detachable mounting flanges are configurable for rackmount, wallmount and under-counter installation. Uses only 1 rack space (1U) when installed in any 19 inch EIA standard rack. Features the highest level of AC surge and EMI/RFI noise suppression of all Tripp Lite rackmount surge suppressors. Outlets are arranged in exclusive isolated filter banks to limit noise interaction among connected items. Includes 12 outlets (2 front / 10 rear), 15 ft AC power cord and guarded power switch to reduce the risk of accidental shutoff. Diagnostic LEDs indicate AC present, line fault and protection status.
Figure 22: Tripp Lite Isobar 12 Ultra Surge Suppressor
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin44
Specifications
UL Label Placement
UL Listing labels are not required for this product.
Table 6: Tripp Lite Isobar 12 Ultra Surge Suppressor SpecificationsCategory SpecificationVoltage compatibilityFrequency compatibility
120 VAC60 Hz
Output volt amp capacity 15 Amps
Output watt capacity 1800 watts
Outlet quantity / type 12 NEMA 5-15R output duplex style receptacles, 2 front / 10 rear
Transformer accommodation Supports up to 4 large transformer plug accessories without covering remaining outlets
Input connection type NEMA 5-15P input plug
Input cord length 15 ft (4.6 m)
Recommended electrical service 120V 15A
Diagnostic LEDs PROTECTION PRESENT (green)LINE FAULT (red)LINE OK (green)
Switches Two-position red illuminated on/off power switch to all outlets
Protection modes Includes full normal mode (H-N) and common mode (N-G / H-G) line surge suppression
AC suppression joule rating 1280 joules
Clamping voltage (RMS) 140V
AC suppression response time NM = 0 ns, CM = <1 ns
AC suppression surge current rating 96,000 amps
AC suppression components used Metal oxide varistors, toroidal balanced chokes, and VHF capacitors.
Safe thermal fusing Prevents unsafe conditions during extreme extended overvoltages and catastrophic occurrences
UL1499 let through rating 330V - UL Verified
EMI / RFI filtering 40-80 dB
Unit Weight 4.6 lbs (2.1 kg)
Dimensions (Height x Width x Depth) 2.5 x 9 x 3.5 in (6.4 x 22.9 x 8.9 cm)
ComplianceUL 1449 1998 Rev. (AC Suppression)
UL1449 (UR status)
UL 1283 (EMI Filter) UL 1283
cUL / CSA (Canada) cUL
Approvals Exceeds IEEE 587 category A&B specifications
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 45
Network Communications
Copper Cable ConnectionsUse copper cables (10BaseT, Twisted Pair) with 4-pair RJ45 connectors for connections between RJ45 ports on switches, media converters, and Ethernet Network Interface Cards (NICs). Use cables less than 100 meters (328 feet) in length. Straight-through cables are used for all ethernet connections but one.
Use copper cable that has the following characteristics:
• 10BaseT, Unshielded Twisted Pair
• 2.5 meters (8.2 feet) minimum distance between nodes
• 100 meters (330 feet) maximum length
• RJ45 connectors
Verify that copper cable connected to media converters does not leave the room in which the media converter is installed. Use an American Power Conversion (APC) ProtectNet (Model PNET1GB) surge protector on each cable segment to prevent electrical surges.
Note: See Figure 19 on page 39 for ethernet surge protection details using the PNET1GB.
Step 1. Align plug on cable with port on device.
Step 2. Insert plug into port.
Step 3. Push forward slightly to lock into place.
R 45 Female Port on DeviceJ
Figure 23: Using RJ45 Style Connectors on Copper Cables
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin46
Fiber-Optic Cable ConnectionsUse fiber-optic cable that has the following characteristics:
• 10BaseFL
• plastic optical fibers
• multimode
• 6560 feet (2000 meters) maximum length
• ST-style connectors (820nm wavelength) or MTRJ-style connectors (1300 nm wavelength)
Figure 24: Ethernet Straight-Thru Cable RJ45 Connector Pinouts
Figure 25: Ethernet Cross-Over Cable RJ45 Connector Pinouts
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 47
ST Style Connectors
MTRJ Connectors
Step 1: Line up the peg on the cable with the slot on the connector.
.
Step 3: Push forward and twist to lock in place.
Push
Twist
Collar
Peg
Twist
Step 2: Twist the collar on the cable to line up with the peg on the connector.
Figure 26: Using ST-Style Connectors on Fiber-Optic Lines
MTRJ-style Connector for Multimode Fiber-Optic Lines
Step 1. Align plug on cable with port on device.
Step 2. Insert plug into port.
Step 3. Push forward slightly to lock into place.
MTRJ-Style Porton Device for
Multimode Fiber-Optic Lines
Figure 27: Using MTRJ-Style Connectors on Fiber-Optic
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin48
NU-RJ45SW1-0U 24 Port Ethernet Switch with RJ45 ConnectorsThe 24 ports on the NU-RJ45SW1-0U Copper Switch with RJ45 Connectors are 10/100 Mbps and automatically detect which communication speed is used, allowing any of the ports to be used for 100 Mbps uplink. It also automatically detects whether the communication is half-duplex or full-duplex.
Figure 28: NU-RJ45SW1-0U Copper Switch
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 49
Specifications
UL Label PlacementUL Listing labels must be positioned as shown in Figure 29.
Table 7: 24 Port Ethernet Copper Switch SpecificationsCategory SpecificationsFast Ethernet 24 x 10/100BaseTX Fast Ethernet ports with Auto-Uplink: RJ-45 shielded
connectors
Configuration IEEE Auto Negotiation (sets 10/100 Mbps speed and half/full duplex)
Status Indicators System: PowerPer Port: 2 LEDs. Link (solid)/activity (blink). 100 Mbps (on)/10 Mbps (off)
Efficiency Non-blocking, Fast Ethernet switching
Switch Architecture Triple-chip design with on-board frame buffers
Error Detection Frames with errors (malformed PHY, runt < 64 bytes, CRC error, long > 1536) are discarded
Forwarding MAC Table 4K addresses
On-Chip Buffer 768 KB (total)
Dimensions (H x W x D) 1.7 x 17.5 x 4.7 in (4.5 x 44.5 x 12.0 cm)
Weight 4.0 lbs (1.8 Kg)
Power 120 VAC, 60 Hz, 0.33A Max.
Operating Temperature 32 to 120º F (0º to 49º C)
Relative Humidity 10 to 93%, non-condensing
Standards Compliance IEEE 802.3u Fast Ethernet over 2 pairs of UTP Category 5 (100BaseTX) IEEE 802.3 Ethernet over 2 pairs of UTP Category 3 (10BaseT)
Emissions Compliance FCC Class A
Compliance UL, cUL, CE Safety
Figure 29: UL Label Placement for the Asante Ethernet Switch
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin50
5 Port Ethernet Copper Switch with RJ45 ConnectorsThe 5 ports on the FS105 Copper Switch with RJ45 Connectors are 10/100 Mbps and automatically detect which communication speed is used, allowing any of the ports to be used for 100 Mbps uplink. It also automatically detects whether the communication is half-duplex or full duplex.
Wiring
Copper Cables
See Copper Cable Connections on page 45 for details on ethernet copper connections.
Figure 30: 5 Port Copper Switch
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 51
Specifications
UL Label PlacementUL Listing labels are not required for this product.
Table 8: 5 Port Ethernet Copper Switch Electrical SpecificationsCategory SpecificationsNetwork Ports Five auto speed-sensing UTP ports
Fast Ethernet 24 x 10/100BaseTX Fast Ethernet ports with Auto-Uplink: RJ-45 shielded connectors
Configuration IEEE Auto Negotiation (sets 10/100 Mbps speed and half/full duplex)
Status LEDs Link, speed, and activity indicators built into each RJ-45 port
Efficiency Non-blocking, Fast Ethernet switching
Switch Architecture Triple-chip design with on-board frame buffers
Error Detection Frames with errors (malformed PHY, runt < 64 bytes, CRC error, long > 1536) are discarded
Forwarding Modes Store-and-forward
Buffer Memory 64 KB
Bandwidth 1Gbps
Network Latency Less than 20 µs for 64-byte frames in store-and-forward mode for 100 Mbps to 100 Mbps transmission
Address Database Size 1,000
Addressing 48-bit MAC address
Dimensions (H x W x D) 3.7 x 4.1 x 1.1 in (9.4 x 10.3 x 2.7 cm)
Weight 0.62 lbs (0.28 Kg)
AC Power 7.5W (7.5 VDC, 1A)
Operating Temperature 32 to 120º F (0 to 49º C)
Relative Humidity 10 to 93%RH, non-condensing
Standards Compliance IEEE 802.3 10BASE-T EthernetIEEE 802.3u 100BASE-TX Fast EthernetIEEE 802.3x Full-duplex Flow Control
Electromagnetic Emissions Compliance
CE mark, commercialFCC part 15 Class AEN55 022 (CISPR22), Class AVCCI Class AC-Tick
Safety Agency Compliance
UL listed (UL 1950)/cULIEC950/EN60950
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin52
Media ConvertorsFollow these additional guidelines when installing the media converters:
• Keep copper cables in the same room as media converters. Use Category 5 copper cables with RJ45 connectors. Cables must be 6 meters (20 feet) or less in length.
• Use an AC to DC power adapter to provide power to the media converters. Secure the power adaptors in a locked enclosure with a UL Listed terminal strip.
NU-MC101-0U
Wiring
Ethernet Surge Protection
See Figure 19 on page 39 for information on the PNET1GB ethernet surge suppression.
Copper Cables
See Copper Cable Connections on page 45 for details on Copper connections.
Fiber-Optic Connections
See Fiber-Optic Cable Connections on page 46 for more information on fiber-optic connections.
Figure 31: 10 Mbps Media Converter Connectors
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 53
SpecificationsTable 9: NU-MC101-0U SpecificationsCategory SpecificationsExternal Power Supply 120 VAC, 60Hz
Input Supply Voltage 12VDC
Max Current .5A
Power Consumption 6W
Status Indicators Power (PWR) - Indicates power is applied to the converterLink (LNK) (2) - Indicates a valid receive link existsReceive (REC) (2) - Indicates converter is receiving valid dataNormal (NML) Indicates product is working in normal modeOn Line Indicates - BNC port is connected to an active 10Base2 segment (MC15 only)Collision (COL) - Indicates BNC port is sensing a collision signal (MC15 only)
Packet Transmission Characteristics Round Trip Delay - 0.4µ MaximumBit Error Rate (BER) <10 -12
Operating Temperature 32 to 120°F (0 to 49°C)
Relative Humidity 10% to 93% RH, non-condensing
Operating Altitude 0 to 10,000 ft (0 to 3,048 m)
Dimensions(Width x Depth x Height)
4.12 x 3.75 x 1.0 in(10.5 x 9.5 x 2.5cm)
Weight 0.65 lb (0.29 Kg)
EMC Compliance FCC Class A
Safety Compliance UL-Cul, CSA/CSA, NRTL, TUV,CE compliant
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin54
UL Label PlacementUL Listing labels must be positioned as shown in the picture below.
Figure 32: UL Label Placement for the NU-MC101-0U Ethernet Media Converter
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 55
NU-MC102-0U
Wiring
Ethernet Surge Protection
See Figure 19 on page 39 for information on the PNET1GB ethernet surge suppression.
Copper Cables
See for Copper Cable Connections on page 45 details on Copper connections.
Fiber-Optic Connections
See Fiber-Optic Cable Connections on page 46 for more information on fiber-optic connections.
Figure 33: 100 Mbps Media Converter Connectors
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin56
SpecificationsTable 10: NU-MC102-0U SpecificationsCategory SpecificationsStandards IEEE 802.3 1998 Edition 10BASE-T; 10BASE-FL
Unit Power LED Lit for normal operation
Port Link LEDs Lit LED indicates unit is receiving link pulses from a compliant device
Port Receive LEDs Flashing or lit LED indicates packets are being received
Power Supplied by chassis
Connectors 1 RJ-45 (10BASE-T: 100 meters); 1 duplex fiber optic
Dimensions(Width x Depth x Height)
1.0 x 4.7 x 3.0 in (25 x 119 x 76mm)
Shipping Weight 1 lb (0.45 kg)
Compliance UL Listed; C-UL Listed (Canada);CISPR/EN55022 Class A; FCC Class A; CE Mark
Environment 32 to 120° F (0 to 49° C); 10 to 93% humidity, noncondensing
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 57
UL Label PlacementUL Listing labels must be positioned as shown in the picture below.
Note: Figure 34 shows the NU-MC102-0U media converter mounted inside the NU-CH101-0U chassis.
See the manufacturer’s information packaged with each device for more device-specific information.
Figure 34: UL Label Placement for the NU-MC102-0 Media Converter
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin58
Table 11: NU-MC102-0U Fiber Optic Connector SpecificationsConnector Type
Fiber Type
Wave length
Typical Distance
Min TX PWR
Max TX PWR
Sensitivity(dBm)
Max In PWR
Link Budget
ST Multimode 850nm LED
2 km -16.0 dBm -10.0 dBm -29.5 dBm -7.2 dBm 13.5 dB
Table 12: Electrical Specifications for Ethernet-to-Fiber Media ConvertorsProduct Code Number
Product Electrical Specifications
NU-MC101-0U 10 Mpbs Media Converter External power (AC/DC Adapter) 120 VAC, 60 HzPower Draw of Converter: 12 VDC, 0.5 A, 6 Watts
NU-MC102-0U(requires NU-CH101-0U)
100 Mbps Media Converter Power supplied from NU-CH101-0UPower Draw: 12 VDC, 3.4 Watts
NU-CH101-0U Single Slot Chassis for NU-MC102-0U and NU-MC103-0U
External Power (AC/DC Adapter) 120 VAC, 60 HzAdapter Output to Chassis: 12 VDC, 0.8A, 9.6 Watts
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 59
Smoke Control Network Automation Engines
Standard NAE Features and ConnectionsThe Smoke Control NAE55, NAE45, and NAE35 models have several common features and wiring connections.
Power Supply
MS-NAE5510-1U and MS-NAE5520-1U Power Supply
The MS-NAE5510-1U and MS-NAE5520-1U NAEs must be powered from either a PAN-PWRSP-U or a PAN-96VAXFR-U power supply transformer.
MS-NAE4510-2U, MS-NAE4520-2U, MS-NAE3510-2U, and MS-NAE3520-2U Power Supply
The MS-NAE4510-2U, MS-NAE4520-2U, MS-NAE3510-2U, and MS-NAE3520-2 NAEs must be powered from either a PAN-PWRSP-U or a PAN-96VAXFR-U power supply transformer.
Wiring
Power Wiring
Connect the 24 VAC supply power wires from the transformer to the removable 3-terminal plug as shown in Figure 35. The middle terminal is not used.
The 24 VAC power should be connected to all network devices so transformer phasing is uniform across the devices. Powering devices with uniform 24 VAC supply power phasing reduces noise, interference, and ground loop problems. The NAE does not require an earth ground connection.
Disconnecting Power from the NAE
When 24 VAC supply power to an NAE is disconnected or lost, the NAE is non-operational, but the POWER LED (Figure 55) remains On and the data protection battery continues to power the NAE for several (1 to 5) minutes while volatile data is backed up in nonvolatile memory. The RUN LED goes Off when data backup and shutdown are complete.
Figure 35: 24 VAC Supply Power
NAE35/NAE45/NAE55Power Terminal Block
NAE PowerTerminal Block
Plug
Wires from Johnson Controls24 VAC Class 2
Power Transformer
Brown Wire(COM)
Orange Wire(24 VAC) N
AE_
ALL
_PO
WE
R_P
OR
T24V~
CO
M
HO
T
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin60
FC Bus Wiring (MS-NAE5510-1U, MS-NAE4510-2U, and MS-NAE-3510-2U Models Only)
Connect the three FC Bus wires to the removable 4-terminal plug as shown in Figure 36 (labeled FC Bus).
If the NAE is connected to an FC Bus, you must set the End-of-Line (EOL) switch to the proper position. See the Setting the MS-NAE3510-2U’s End-of-Line Switch section in this document.
LON Wiring (MS-NAE5520-1U, MS-NAE4520-2U, and MS-NAE-3520-2U Models Only)
For LONWORKS compatible networks, connect the wires from the LON network trunk to the removable 3-terminal plug as shown in Figure 37. See SMK-MOVKIT-LON Requirements for LON Communication Bus Transient Protection on page 173 SMOKE-MOVKIT-0 transient protection wiring details.
Figure 36: FC Bus Wiring
FC BusTerminal
Block
FC BusTerminal Block
Plug
NAE
_FC
_BU
S
SH
LD
CO
M
- +
FC+FC-REF
Figure 37: LONWORKS Network Terminal Block and Wiring Connections
Wires from LON Network
Trunk
LON NetworkTerminal Block
LON NetworkTerminal Block
Plug
LON Network wires are not polarity sensitive.
NA
E_L
ON
PO
RT
BASHD
LON
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 61
Serial PortsUse the RS232C A and RS232C B serial ports for direct connections using a standard 9-pin female to 9-pin female Data Terminal Equipment (DTE) to DTE null modem cable.
Use the RS232C A serial port to direct connect to a computer serial port to browse to the NAE or to connect to a VT100 or a computer with a VT100 emulator and perform diagnostic procedures.
USB Port
The USB port is not to be used for any purpose.
Ethernet Port
The Ethernet connection (10 or 100 Mb/s) is an 8-pin RJ-45 network port. Use the Ethernet port to connect to Internet Protocol (IP) networks.
Note: Transient protection using a PNET1GB transient protector is required at each end of every ethernet connection. See APC PNET1GB Ethernet Transient Protector on page 38 for more information.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin62
Smoke Control NAEs MS-NAE5510-1U and MS-NAE5520-1UUse the Smoke Control NAE, MS-NAE5510-1U (MS/TP) or MS-NAE5520-1U (LON), to interface all input and output smoke control points. The internal modem is not available for smoke control NAEs. Place the Smoke Control NAE in a locked enclosure..
Figure 38: Smoke Control NAE MS-NAE5510-1U
Figure 39: Smoke Control NAE MS-NAE5520-1U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 63
Device Layout
Figure 40: Smoke Control NAE MS-NAE5510-1U
LON
24 VACPower Terminal
FC BusTerminals
RS-232-CSerial PortsUSB
Ports
RJ-45 8-PinEthernet
Jack
DataProtection
BatteryCompartment
SystemRe-BootSwitch
Wall MountFeet
System StatusLight-Emitting Diodes
(LEDs)
End-of-Line(EOL) Switches
96.5 mm3.8 in.
226 mm(8.9 in.)
NAE
55_M
STP_
FRO
NT
Figure 41: Smoke Control MS-NAE5520-1U
LON
LON B
LON A
SHIELD
24 VACPower Terminal
FC Bus(N2 Trunk,FC Bus)
TerminalsL WTerminalON ORKS RRS-232-C
Serial PortsUSBPorts
RJ-45 8-PinEthernet
Jack
DataProtection
BatteryCompartment
SystemRe-BootSwitch
Wall MountFeet
System StatusLight-Emitting Diodes
(LEDs)
End-of-Line(EOL) Switches
96.5 mm3.8 in.
226 mm(8.9 in.)
NAE
55_L
ON
_FR
ON
T
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin64
Powering On the NAEAfter applying 24 VAC power, the NAE requires up to 5 minutes to start up and become operational. See the LED Test Sequence at Startup section.
Startup is complete and the NAE is operational when the (green) RUN LED is On steady and the (red) GEN FAULT LED is Off. See Figure 42 for LED locations.
Disconnecting Power from the NAE
The 24 VAC supply power is disconnected from the NAE by removing the terminal block plug from the power terminal port on the NAE (Figure 35).
When the 24 VAC supply power to the NAE is disconnected or lost, the NAE is nonoperational. The POWER LED (Figure 42) remains On, and the data protection battery continues to power the NAE for several (1 to 8) minutes so that the volatile data can be backed up in nonvolatile memory. The POWER LED goes Off when the data backup is completed.
Troubleshooting
LED Status Indicators
The NAE55 has 11 LEDs to indicate power and communication status. Figure 42 shows the LEDs and Table 13 describes their meaning.
LED Test Sequence at Startup
During startup, the NAE automatically initiates an LED test to verify the operational status of the LEDs. Immediately after connecting supply power, the following LED lighting sequence occurs:
1. The PEER COM, RUN, FC A, FC B, and GENL FAULT LEDs turn on, indicating that the Operating System (OS) is booting up.
2. The PEER COM, RUN, GENL FAULT LEDs, and the FC A and FC B LEDs shut off. The RUN LED flashes to indicate that the NAE software is loading.
IMPORTANT: The data protection battery must be installed and charged before disconnecting the 24 VAC supply power.
Figure 42: Front of NAE55 with LED Designations
POWERETHERNET10/LINK100/LINK
FC AFC BPEER COMRUN
24 VACBATT FAULTGENL FAULT
N2-B
N2-A
POW
ER+-REF
S N2
+-REF
S N2
+NC
-
PO
WER
ETH
ERN
ET
10/LINK
100/LIN
K
N2A
N2B
PE
ER
CO
MR
UN
24 VAC
BAT
T FAU
LTG
ENL FA
ULT
SE
RIA
L B
SE
RIA
L A
US
B A
US
B B
ETHERNET MODEM
SY
STEM
RE
-BOO
T
NAERET SY
NAE
_LE
D_S
TATU
S
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 65
3. The LEDs display the operational status of the NAE. When the RUN LED goes On Steady, the operating system and Metasys application are running and the NAE is ready.
The total time to start up the NAE depends on the size of the database and can take several minutes.
System Re-Boot Switch
The System Re-Boot switch (Figure 40 and Figure 41) forces a manual restart of the NAE processor. All data changes made to the system since the last time the NAE saved data are lost on restart, including alarm, trend, and audit trail data. Press the System Re-Boot switch only if the NAE fails to respond and cannot be accessed by any user device. Do not press the System Re-Boot switch unless you have tried other reasonable means to fix the problem.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin66
Table 13: NAE LEDs Designation, Normal Status, Description, and Other ConditionsLED Normal Descriptions/Other ConditionsPOWER (Green) On Steady On Steady = Unit is getting power from either the battery or 24 VAC power.
Also see the 24 VAC LED. Off Steady = Unit is shut down.
ETHERNET (Green) Flicker Flicker = Data is transferring on the Ethernet connection. Ethernet traffic is general traffic (may not be for the NAE).Off Steady = No Ethernet traffic, probably indicates a dead Ethernet network or bad Ethernet connection.
10/LINK (Green) On Steady On Steady = Ethernet connection is established at 10 Mb/s.
100/LINK (Green) On Steady On Steady = Ethernet connection is established at 100 Mb/s.
FC A (NAE55 only) (Green)
Flicker On Steady = Controllers are defined to FC A (FC Bus 1 or N2 Trunk 1) in the NAE, but none are communicating. (NAE transmitting only)Flicker = Normal communications; FC A port is transmitting and receiving data. Flickers are generally in sync with data transmission but should not be used to indicate specific transmission times.Off Steady = No field controllers are defined to FC A (FC Bus 1 or N2 Trunk 1) in the NAE.
FC B (NAE55 only) (Green)
Flicker On Steady = Controllers are defined to FC B (FC Bus 2 or N2 Trunk 2) in the NAE, but none are communicating. (NAE transmitting only)Flicker = Normal communications; FC B port is transmitting and receiving data. Flickers are generally in sync with data transmission but should not be used to indicate specific transmission times.Off Steady = No field controllers are defined to FC B (FC Bus 2 or N2 Trunk 2) in the NAE.
PEER COMM (Green) Varies (see next column)
Flicker = Data traffic between NAE devices. For an NAE that is not a Site Director, this LED indicates regular heartbeat communications with the Site Director. For a Site Director NAE, flashes are more frequent and indicate heartbeat communications from all other NAE devices on the site. For a single NAE on a network without an Application and Data Server (ADS), there is no flicker.
Run (Green) On Steady On Steady = NAE software is running.On 1 second, Off 1 second = NAE software is in startup mode.On 0.5 seconds, Off 0.5 seconds = NAE software is shutting down.Off Steady = Operating system is shutting down or software is not running.
24 VAC (Green) On Steady On Steady = 24 VAC power is present.Off Steady = Loss of 24 VAC power. In the Off Steady condition, the NAE can be running on battery power. Also see the POWER LED.
BATT FAULT (Red) Off Steady On Steady = Battery fault. Replace the battery. Battery not connected or cannot be charged. The BATT FAULT LED may remain On for up to 24 hours after initially powering-on the NAE. If the BATT FAULT LED remains on longer than 48 hours after initially powering-on the NAE, check the battery connection or replace the battery.
GENL FAULT (Red) Off Steady On Steady = General Fault. Fault conditions are user configurable in software. Preconfigured fault conditions include excessive Central Processing Unit (CPU), flash or memory use, excessive CPU or Printed Wire Board (PWB) temperature, or Battery Fault. In normal operation, the GENL FAULT LED stays on steady for the first half of the startup sequence.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 67
SpecificationsTable 14: Smoke Control NAE55x0-1U Technical Specifications Category SpecificationsPower Requirement Dedicated nominal 24 VAC
Power Consumption 50 VA maximum
Installation Environment Indoor, Dry
Ambient Operating Conditions
32 to 120° F (0 to 49° C)10 to 93% RH, non-condensing
Data Protection Battery Supports data protection on power failure. Rechargeable NiMH battery: 12V, 1.2 Ah, with a typical life of 3 to 5 years at 70° F (21° C); Product Code Number: MS-BAT1010-0
Clock Battery Maintains real-time clock through a power failure. On board cell; typical life 10 years at 70°F (21°C)
Processor 300 MHz Pentium® class Geode® GX1 MMX enhanced processor
Memory 256 MB Flash nonvolatile memory for operating system, configuration data, and operations data storage and backup.256 MB Synchronous Dynamic Random Access Memory (DRAM) for operations data dynamic memory for all models
Operating System Microsoft Windows XP embedded
Network and Serial Interfaces
Two optically isolated RS-485 BACnet MS/TP ports; (9,600, 19.2K, 38.4K, or 76.8K baud); pluggable and keyed 4-position terminal blocksTwo RS-232-C serial ports with standard 9-pin sub-D connectors that support all standard baud ratesTwo USB serial ports, standard USB connectorsOne LONWORKS port; FTT10 78 Kbps; pluggable, keyed 3-position terminal block (LONWORKS port available on NAE5520-1U models only).
Maximum Object Count 5,000 objects
Alarm Repository Size 1,000 alarms
Housing Plastic housingPlastic material: ABS + polycarbonate UL94-5VBProtection: IP20 (IEC 60529) Mounting On flat surface with screws on three mounting feet or single DIN rail
Mounting On flat surface with screws on three mounting screws or single DIN rail
Compliance United States
UL Listed, File S4977, CCN PAZX, UL 916, Energy Management EquipmentFCC Compliant to CFR47, Part 15, Subpart B, Class AUL Listed, File S4977, CCN UUKL, UL 864, Control Units and Accessories for Fire Alarm Systems
Canada UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal EquipmentIndustry Canada Compliant, ICES-003
Europe CE Mark, EMC Directive 89/336/EEC, in accordance with EN 61000-6-3 (2001) Generic Emission Standard for Residential and Light Industry and EN 61000-6-2 (2001) Generic Immunity Standard for Heavy Industrial Environment
Australia and New Zeland
C-Tick Mark, Australia/NZ Emissions Compliant
Dimensions(Height x Width x Depth)
226 x 332 x 96.5 mm. (8.9 x 13.1 x 3.8 in.)Minimum space for mounting 303 x 408 x 148 mm. (12.0 x 16.1 x 5.8 in.)
Shipping Weight 2.9 kg (6.4 lb.)
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin68
UL Label PlacementUL Listing labels must be positioned as shown in Figure 43 and Figure 44.
Figure 43: UL Label Placement for the MS-NAE5510-1U (Front and Bottom View)
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 69
Figure 44: UL Label Placement for the MS-NAE5520-1U (Front and Bottom View)
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin70
Smoke Control NAEs MS-NAE4510-2U and MS-NAE4520-2UUse the Smoke Control NAEs, MS-NAE4510-2U (MS/TP) or MS-NAE4520-2U (LON), to interface all input and output smoke control points. The internal modem is not available on the smoke control NAE. Place the Smoke Control NAE in a locked enclosure.
Figure 45: Smoke Control MS-NAE4510-2U
Figure 46: Smoke Control MS-NAE4520-2U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 71
Device LayoutSee Figure 47 (MS/TP) and Figure 48 (LON) for the location of the power supply terminal, network terminals, Universal Serial Bus (USB) port, and Ethernet port on the NAE.
Field Controller (FC) Bus Jack and Service Port (NAE4510 Models Only)
The NAE is designed to control one field controller MS/TP FC Bus trunk. The RJ-11, 6-Pin jack labeled FC BUS (Figure 47) is an FC bus service port.
Figure 47: Smoke Control MS-NAE4510-2U
RET SY
24 VACPower Terminal
RJ-45 8-PinEthernet
Port
USBPortRJ-11 6-Pin
ModemPort RS-232
Serial Port
MountingClip
End-of-LineSwitch
FC Bus(N2 Bus or
FC BusTerminal)
Data Protection BatteryCompartment
MountingClip
RJ-11 6-PinField Controller
Service Port
1315.2
622.5
27010.6
System StatusLight-Emitting Diodes
(LEDs) NA
E45
_FR
ON
T_D
IMS
MountingClip
35013.8
2108.3
1104.3
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin72
LONWORKS® Network Port (NAE4520-2U Model Only)
The LONWORKS network port on the NAE3520-2U is a 3-position removable, keyed terminal block labeled LON (Figure 48). Use the LONWORKS port to integrate LON device networks into a Metasys® network. The Shield connection (SHLD) on the LONWORKS port is an open terminal and is not connected in the NAE.
SpecificationsTable 15: Smoke Control NAE45x0-2U Technical SpecificationsCategory SpecificationsPower Requirement Dedicated nominal 24 VAC, Class 2 power supply
Power Consumption 25 VA maximum
Ambient Operating Conditions
32 to 120° F (0 to 49° C)10 to 93% RH, non-condensing
Data Protection Battery Supports data protection on power failure. Rechargeable NiMH battery: 3.6 V, 500 mAh, with a typical life of 10 years at 70° F (21° C); Product Code Number: MS-BAT1020-0
Clock Battery Maintains real-time clock through a power failure. On board cell; typical life 10 years at 70° F (21° C)
Processor 192 MHz Renesas™ SH4 7760 RISC processor
Memory 128 MB Flash nonvolatile memory for operating system, configuration data, and operations data storage and backup128 MB Synchronous Dynamic Random Access Memory (DRAM) for operations data dynamic memory
Operating System Microsoft® Windows® CE embedded
Figure 48: Smoke Control MS-NAE4520-2U
RET SY
24 VACPower Terminal
RJ-45 8-PinEthernet
Port
USBPortRJ-11 6-Pin
ModemPort RS-232
Serial Port
MountingClip LON Bus
Terminal
Data Protection BatteryCompartment
MountingClip
1315.2
622.5
27010.6
System StatusLight-Emitting Diodes
(LEDs) LON
_SM
OKE
_NA
E35_
FRO
NT_
DIM
S
MountingClip
35013.8
2108.3
1104.3
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 73
Network and Serial Interfaces
One Ethernet port; 10/100 Mb; 8-pin RJ-45 connectorOne optically isolated RS-485 port; 9600 baud; with a pluggable and keyed 4-position terminal blockTwo RS-232-C serial ports, with standard 9-pin sub-D connectors, that support all standard baud ratesOne USB serial port with standard USB connector
Housing Plastic housingPlastic material: ABS + polycarbonate UL94-5VBProtection: IP20 (IEC 60529) Mounting On flat surface with screws on three mounting feet or single DIN rail
Mounting On flat surface with screws on three mounting screws or single DIN rail
Compliance United States
UL Listed, File S4977, CCN PAZX, UL 916, Energy Management EquipmentFCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal EquipmentIndustry Canada Compliant, ICES-003
Europe CE Mark, EMC Directive 89/336/EEC, in accordance with EN 61000-6-3 (2001) Generic Emission Standard for Residentialand Light Industry and EN 61000-6-2 (2001) Generic Immunity Standard for Heavy Industrial Environment
Australia and New Zeland
C-Tick Mark, Australia/NZ Emissions Compliant
Dimensions(Height x Width x Depth)
152 x 270 x 62 mm (6.0 x 10.7 x 2.5 in.)Minimum space for mounting NAE45: 190 x 280 x 85 mm (7.5 x 11.5 x 3.5 in.)
Shipping Weight 1.2 kg (2.7 lb.)
Table 15: Smoke Control NAE45x0-2U Technical SpecificationsCategory Specifications
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin74
UL Label PlacementUL Listing labels must be positioned as shown in Figure 49.
Figure 49: UL Label Placement for the MS-NAE4510-2U and MS-NAE4520-2U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 75
Smoke Control NAEs MS-NAE3510-2U and MS-NAE3520-2UThe Network Automation Engine (NAE) is a Web-enabled, Ethernet-based, supervisory device that monitors and controls networks of field-level building automation devices, HVAC equipment, lighting, and smoke control. Figure 50 shows a smoke control NAE3510-2U (MS/TP) and Figure 51 shows a smoke control NAE3520-2U (LON) model.
Use the Smoke Control NAE MS-NAE35x0-2U to interface all input and output smoke control points. Place the Smoke Control NAE in a locked enclosure.
Figure 50: Smoke Control MS-NAE3510-2U
Figure 51: Smoke Control MS-NAE3520-2U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin76
Device Layout
MS-NAE3510-2U
The MS-NAE3510-2U is designed to control one field controller MS/TP FC Bus trunk. The RJ-11, 6-Pin jack labeled FC BUS (Figure 52) is an FC bus service port. See Figure 52 for the location of the power supply terminal, network terminals, Universal Serial Bus (USB) port, and Ethernet port on the MS/TP NAE.
Figure 52: Smoke Control MS-NAE3510-2U
RET SY
24 VACPower Terminal
RJ-45 8-PinEthernet
Port
USBPortRJ-11 6-Pin
ModemPort RS-232
Serial Port
MountingClip
End-of-LineSwitch
FC BusTerminal
Data Protection BatteryCompartment
MountingClip
RJ-11 6-PinField Controller
Service Port
1315.2
622.5
27010.6
System StatusLight-Emitting Diodes
(LEDs) NA
E45
_FR
ON
T_D
IMS
MountingClip
35013.8
2108.3
1104.3
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 77
MS-NAE3520-2U
The MS-NAE3520-2U is designed with a LONWORKS network port. The LONWORKS network port is a 3-position removable, keyed terminal block labeled LON (Figure 53). Use the LON port to integrate LON device networks into a Metasys® network. The Shield connection (SHLD) on the LONWORKS port is an open terminal and is not connected in the NAE.
See Figure 53 for the location of the power supply terminal, network terminals, Universal Serial Bus (USB) port, and Ethernet port on the MS-NAE3520-2U.
Figure 53: Smoke Control MS-NAE3520-2U
RET SY
24 VACPower Terminal
RJ-45 8-PinEthernet
Port
USBPortRJ-11 6-Pin
ModemPort RS-232
Serial Port
MountingClip LON Bus
Terminal
Data Protection BatteryCompartment
MountingClip
1315.2
622.5
27010.6
System StatusLight-Emitting Diodes
(LEDs) LON
_NAE
35_F
RO
NT_
DIM
S
MountingClip
35013.8
2108.3
1104.3
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin78
Wiring Considerations and Guidelines for Network Integrations Table 16: Guidelines for MS/TP (FC Bus) Network TopologyCategory Rules/Maximums AllowedGeneral One FC Bus per NAE35 and NAE45
Only daisy-chained devices
Number of FC Devices Supported NAE45 models support up to 1001 devices on the FC Bus trunk with no more than two repeaters between an NAE and any device and a maximum of 50 devices between repeaters.
1. If TEC Thermostat Controllers or third-party devices are used on the FC Bus, the maximum total number of devices is 32 and the maximum length is 1,219 m (4,000 ft).
NAE35 models support up to 501 devices on the FC Bus trunk with no more than two repeaters between an NAE and any device and a maximum of 50 devices between repeaters.
Cable Length and Type 1,500 m (5,000 ft) twisted pair cable without a repeater
4,500 m (15,000 ft) twisted pair cable from an NAE and the farthest FC device (three segments of 1,500 m [5,000 ft] each, separated by repeaters)
2,000 m (6,600 ft) between two fiber media convertors
Cable Wire Type and Size Solid or stranded 22 AWG recommended (24 AWG twisted pair or larger is acceptable)
Terminations Two FC Bus devices with EOL switches in the ON position, one at each end of each FC Bus segment
Table 17: NAE Ethernet Network Rules Category Rules/Maximums Allowed1
General Point-to-point star topology with network hubs/switches
Number of Devices Maximum of 100 supervisory devices may be connected to one site in the Metasys system extended architecture.
Line Length and Type 2000 m (6600 ft) for plastic/glass fiber optic with external adapter
100 m (330 ft) CAT5 cable
Terminations For 10/100BaseT, no line terminators allowed
Transient Protection A PNET1GB transient protector is required at each end of every ethernet connection
1. See Surge Protection Devices and Network Communications for more information.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 79
Powering On the NAE
After applying 24 VAC power, the NAE requires up to 3 minutes to start up and become operational. See the LED Test Sequence at Startup section.
Startup is complete and the NAE is operational when the (green) RUN LED is On steady and the (red) FAULT LED is Off (Figure 55).
Disconnecting Power from the NAE
When 24 VAC supply power to an NAE is disconnected or lost, the NAE is non-operational, but the POWER LED (Figure 55) remains On and the data protection battery continues to power the NAE for several (1 to 5) minutes while volatile data is backed up in nonvolatile memory. The RUN LED goes Off when data backup and shutdown are complete.
Setting the MS-NAE3510-2U’s End-of-Line Switch
MS/TP network devices at either end of an FC Bus must be set as network terminated devices. The MS-NAE3510-2U has an End-of-Line (EOL) switch that allows you to set the NAE as a network terminated device. The MS-NAE3510-2U is shipped with the EOL switch in the factory default, ON (up) position (Figure 54).
The MS-NAE3510-2U follows the same rules as other MS/TP terminated devices. See NU-RPT101-0U RS-485-to-RS-485 Repeater on page 118 for details.
Troubleshooting
LED Status Indicators
The Smoke Control NAE35 and NAE45 models have 9 LEDs to indicate power and network communication status. Figure 55 shows the LEDs and Table 18 describes the LED indications.
IMPORTANT: The data protection battery must be installed and charged before disconnecting the 24 VAC supply power.
Figure 54: FC Bus EOL Switch in the Factory Default ON (Up) Position
NAE
45_E
OL
1
Figure 55: Smoke Control NAE 35/45 FC Bus (left) and LON Bus (right) LED Designations
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin80
LED Test Sequence at Startup
During startup, the NAE automatically initiates an LED test to verify the operational status of the LEDs. Immediately after connecting supply power, the following LED lighting sequence occurs:
1. The POWER, BAT FAULT, 10 LINK, FAULT, RUN, and PEER COM LEDs turn On, indicating that the Operating System (OS) is booting up. (After 2 seconds, the LEDs may change states depending on site-specific network activity.)
2. The BAT FAULT, PEER COM, and FAULT LEDs shut Off. The RUN LED flashes to indicate that the NAE software is loading.
3. The LEDs display the operational status of the NAE. When the RUN LED goes On Steady, startup is complete, and the NAE is operational.
Note: The total time to start up the NAE depends on the size of the database and can take several minutes.
Table 18: NAE LED Designations, Normal Status and DescriptionsLED Designation Normal
StatusDescriptions/Other Conditions
POWER (Green) On Steady On Steady = Unit is getting power from either the battery or 24 VAC power. Off Steady = Unit is shut down.
ETHERNET (Green) Flicker Flicker = Data is transferring on the Ethernet connection. Ethernet traffic is general traffic (may not be for the NAE).Off Steady = No Ethernet traffic, probably indicates a dead Ethernet network or bad Ethernet connection.
10/LINK (Green) On Steady On Steady = Ethernet connection is established at 10 Mbps.
100/LINK (Green) On Steady On Steady = Ethernet connection is established at 100 Mbps.
FC BUS (Green) NAE3510-2U and NAE4510-2U models only
Flicker Flicker = Normal communications; the FC Bus is transmitting and receiving data. Flickers are generally in sync with data transmission, but should not be used to indicate specific transmission times.Off Steady = No field controllers are defined to FC Bus in the NAE.
LON (Green)NAE3520-2U and NAE4520-2U models only
Flash Indicates regular LON heartbeat commnications.
PEER COM (Green) Varies (see next column)
Flicker = Data traffic between NAE devices. For an NAE that is not a Site Director, this LED indicates regular heartbeat communications with the Site Director. For a Site Director NAE, flashes are more frequent and indicate heartbeat communications from all other NAE devices on the site. For a single NAE on a network without an Application and Data Server (ADS), there is no flicker.
RUN (Green) On Steady On Steady = NAE software is running.On 1 second, Off 1 second = NAE software is in startup mode.On 0.5 seconds, Off 0.5 seconds = NAE software is shutting down.Off Steady = Operating system is shutting down or software is not running.
BAT FAULT (Red) Off Steady On Steady = Battery defective. Flicker = Data Protection Battery is not installed. Connect or install battery.
FAULT (Red) Off Steady On Steady = General Fault. Fault conditions are user configurable in software. Preconfigured fault conditions include excessive Central Processing Unit (CPU) flash or memory use, excessive Printed Wire Board (PWB) temperature.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 81
SpecificationsTable 19: Smoke Control NAE35x0-2U Technical SpecificationsCategory SpecificationsPower Requirement Dedicated nominal 24 VAC
Power Consumption 25 VA maximum
Ambient Operating Temperature
32 to 120° F (0 to 49° C)
Ambient Operating Conditions
10 to 93% RH, non-condensing
Data Protection Battery Supports data protection on power failure. Rechargeable NiMH battery: 3.6 V, 500 mAh, with a typical life of 10 years at 70° F (21° C); Product Code Number: MS-BAT1020-0
Clock Battery Maintains real-time clock through a power failure. On board cell; typical life 10 years at 70° F (21° C)
Processor 192 MHz Renesas™ SH4 7760 RISC processor
Memory 128 MB Flash nonvolatile memory for operating system, configuration data, and operations data storage and backup128 MB Synchronous Dynamic Random Access Memory (DRAM) for operations data dynamic memory
Operating System Microsoft® Windows® CE embedded
Network and Serial Interfaces
One Ethernet port; 10/100 Mb; 8-pin RJ-45 connectorOne optically isolated RS-485 port; 9600 baud; with a pluggable and keyed 4-position terminal blockOne RS-232-C serial ports, with standard 9-pin sub-D connectors, that support all standard baud rates(Only the models without an optional internal modem have a second serial port that supports an optional, user-supplied external modem)One USB serial port with standard USB connectorOptions: One Telephone port for internal modem; up to 56 Kbps; 6-pin RJ-11 connector (Models with an optional internal modem have one RS-232-C serial port only.)
Dimensions (Height x Width x Depth)
152 x 270 x 62 mm (6.0 x 10.7 x 2.5 in.)Minimum space for mounting NAE45: 190 x 280 x 85 mm (7.5 x 11.5 x 3.5 in.)
Housing Plastic housingPlastic material: ABS + polycarbonate UL94-5VBProtection: IP20 (IEC 60529) Mounting On flat surface with screws on three mounting feet or single DIN rail
Mounting On flat surface with screws on three mounting screws or single DIN rail
Compliance United States UL Listed, File E107041, CCN PAZX, UL 916, Energy Management EquipmentFCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal EquipmentIndustry Canada Compliant, ICES-003
Europe CE Mark, EMC Directive 89/336/EEC, in accordance with EN 61000-6-3 (2001) Generic Emission Standard for Residentialand Light Industry and EN 61000-6-2 (2001) Generic Immunity Standard for Heavy Industrial Environment
Australia and New Zeland
C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight 1.2 kg (2.7 lb.)
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin82
UL Label PlacementUL Listing labels must be positioned as shown in Figure 56.
Figure 56: UL Label Placement for the MS-NAE3510-2U and MS-3520-2U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 83
MS/TP Field Bus
IntroductionThe BACnet® protocol MS/TP Communications Bus is a local network that connects supervisory controllers and field controllers to field point interfaces.
This section describes the specifications, device limits, and rules of the MS/TP Communications Bus. It describes how to wire and terminate devices and troubleshoot the communications of devices on the MS/TP Bus.
This section helps you understand the rules, specifications, and MS/TP configuration and installation.
MS/TP Bus OverviewThe BACnet® protocol MS/TP Communications Bus is high-baud RS-485 protocol network bus that connects Metasys NAEs to Metasys BACnet MS/TP field controllers and control point interfaces (IOMs). The MS/TP Communications Bus (Figure 57) supports two bus types/levels of buses:
• a Field Controller Bus (FC) - connects NAEs to MS/TP field controllers and IOMs
• a Sensor-Actuator Bus (SA) - connects the MS/TP controllers to IOMs, thermostats, sensors and other slave level network devices
The FC Bus and the SA Bus are networks of daisy-chained devices. Each bus has only one bus supervisor. The bus supervisor communicates with devices on the supervised bus and with the next (higher level) bus on the network. The bus supervisor typically starts the communication on the FC bus and SA Bus. If an SA Bus or FC Bus does not have a bus supervisor, the device with the lowest device address value on the bus starts the communication.
Figure 57: Example MS/TP Network
VMA
FC BusSupervisor
SA BusSupervisor
SA BusSupervisor
FIG
_MS-
TPRET SY
NAE
NetworkSensor
FEC
RET
SY
ON S
AB
US
FAU
LT
PO
WE
R
ON
NetworkSensor
RE
TSY
ON
SA
BUS
FAU
LT
PO
WER
ON
IOM
Ethernet Network
P OW ER
FA U LT
S A BU S
FC BU S
MS-VMA1 620 -0P WR I N: 2 4VA C 2 .5 A, CL AS S 2O UT PU T S: 24VA C 0 .5 A, CL AS S 2, P IL O T DU TY
MA NU A LO VE R RI D E
OP EN E NERG YMA NAG EMEN TEQ UIPMENT
CLE AR =LO W RE D=H IG H 35 IN -LB (4 Nm) 60 SE CO ND SAL L F IE LD TER MIN ALS A RE PO WER LI MIT ED
O UT 1
O CO M 1
O UT 2
O CO M 2
O UT 3
O CO M 3
BINA
RY
O UT 4
O CO M 4
O UT 5
O CO M 5
HO T
CO M
CON
FIGUR
AB
LE24
ADD
RES
S 0=OFF
UNIVE
RSA
L
+15
I N
I CO M
SENS
OR
SA BU
SF
C B
US
SAPWR
CO M
–
+
SHLD
CO M
–
+
FCEO L
15U0
NetworkSensor
FC Bus
SA Bus
SA Bus
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin84
FC Bus OverviewThe FC Bus connects Field Equipment Controllers (FECs), Variable Air Volume Modular Assemblies (VMAs), Input/Output Modules (IOMs), and TEC26xx Series network thermostats to a Metasys system Network Automation Engine (NAE).
On an FC Bus, the NAE is the bus supervisor and has a fixed device address of 0 on the bus. See Device Addresses on the MS/TP Bus on page 86.
An FC Bus can be divided into (up to three) bus segments using network repeaters (Figure 58). See FC Bus Rules and Specifications on page 107.
SA Bus OverviewThe SA Bus connects FECs and VMAs to point devices such as IOMs, network thermostats, and network sensors to controllers on the FC Bus.
On an SA bus, an FEC or VMA is the bus supervisor and always has a fixed device address of 0. See Device Addresses on the MS/TP Bus on page 86.
The SA Bus does not support bus segments (Figure 59). See SA Bus Rules and Specifications on page 109 for more information.
Figure 58: FC Bus with Three Bus Segments
RE T S Y
EOL SwitchON
NAE
TR R
Bus Segment1520 m (5,000 ft) Maximum
50 Metasys Device Connections
= EOL Termination switch ONT
R = Repeater
FIG
_FC
_SEG
S
T T TT
T
Note: When TEC26xx Series thermostats and/or third-party BACnet MS/TP devices are connected to the FC Bus, a bus segment supportsonly up to 32 devices and an FC Bus supports only up to 64 devices.
Bus Segment1520 m (5,000 ft) Maximum
50 Metasys Device Connections
(maximum)
FC Bus4570 m (15,000 ft) Maximum
100 Total Metasys Devices
Bus Segment1520 m (5,000 ft) Maximum
50 Metasys Device Connections
Figure 59: SA Bus
SA_S
egm
entEOL ON
(Fixed)
FEC/VMA1600
1200 ft (maximum)10 Nodes (maximum)
RET S Y
ON
S A BU S
FA U LT
P OWE R
ON
T = EOL fixed ON
T
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 85
Baud Rates on the MS/TP BusAn MS/TP bus can be configured to communicate at one of four different baud rates. All devices on the MS/TP bus must communicate at the same baud rate.
The baud rate setting determines the rate at which devices communicate data over the bus. The baud rate settings available on Metasys MS/TP devices are 9600, 19,200, 38,400, 76,800, and Auto.
We recommend setting all MS/TP bus supervisors to 38,400.
In the Auto setting, the Metasys devices listen for the bus supervisor to communicate first, the devices then automatically set their baud rate to the bus supervisor’s baud rate. We recommend setting all field controllers on the FC Bus (FECs, VMAs, and IOMs) to Auto.
TEC26xx Series thermostats automatically set their baud rate to the bus supervisor’s baud rate. The baud rate setting on bus repeaters and third-party MS/TP devices typically is configured manually at the device and the baud rate setting must match the setting of the bus supervisor. Refer to the manufacturer’s product documentation for information on setting the device’s baud rate.
Note: Some third-party devices do not support all four baud rates. The NAE55xx-0 models do not support 76,800 baud.
The two device attributes related to the baud rate are Baud Rate Selection and Active Baud Rate. The Baud Rate Selection attribute allows you to use the SCT (for NAEs) or the CCT (for FECs, VMAs, and IOMs) to set the baud rate for the device. The Active Baud Rate attribute allows you to view the baud rate at which the device is communicating on the active bus when Auto baud is selected. For more information on Metasys system attributes, refer to the Metasys system Help.
Higher baud rates require a limited range of wire gauge. There is a direct relationship among the baud rate, wire gauge, and wire length that determines the number of devices allowed on the bus. Higher baud rates support more devices, but require small gauge wire (which provides lower capacitance). A lower baud rate may be required in order to use existing, larger gauge wire (which has higher capacitance), but may support fewer devices. We recommend 38,400 baud using 22 AWG stranded wire. This provides the best balance between performance and installation sensitivity.
For more details on baud rate, wire gauge, wire length, and the number of devices see MS/TP Bus Cable Recommendations on page 111.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin86
Device Addresses on the MS/TP BusEach device connection on an MS/TP Bus requires a device address to coordinate communication on the bus. Each bus has a set of device addresses which is separate and independent from the device addresses on all other buses. Devices connected to both an FC Bus and SA Bus have two different device addresses, one for each device connection.
In the MS/TP bus hierarchy, device connections on separate buses can have the same device address. Every bus supervisor connection on an MS/TP bus, for example, has a device address of 0 (zero), and the device address for the first network sensor on many SA Buses is 199. Figure 60 shows an example of an MS/TP bus and the device addresses for connections on the FC Bus and the SA Buses.
The NAE is the bus supervisor on an FC Bus. The FEC or VMA is the bus supervisor on an SA Bus. Bus supervisors have a fixed device address of 0 (zero) that cannot be changed (Figure 60). Depending on the model, a network sensor has either a fixed address of 199 or can be assigned a switch-selectable address between 200 and 203. Table 20 on page 87 provides a list of the MS/TP device address values and address value ranges for devices connected to an MS/TP bus.
Token-passing messages are sent from address to address in consecutive order, therefore any gaps in the device address range reduce bus performance while the message negotiates the gap to find the next device address on the bus. Start with the lowest device address value and use consecutive address values for optimal bus performance. Table 20 lists the address ranges.
Note: The devices on the bus do not need to be physically wired in sequential order as long as there are no gaps in the address value range.
Figure 60: Example MS/TP Bus Showing FC Bus and SA Bus Addresses
VMA(on FC Bus)
FC BusSupervisor
199
SA BusSupervisor
SA Bus and
Addresses
FC Bus and Addresses
8
765
4SA Bus
Supervisor
FIG
_NET
_AD
DR
SS
RE T S Y
NAE
NetworkSensor
FEC(on FC Bus)
RE
TSY
ON
SA
BUS
FAU
LT
PO
WE
R
ON
NetworkSensor
RET
SY
ON
SABU
S
FAUL
T
POW
ER
ON
IOM
Ethernet Network
P OW ER
FA U LT
S A BU S
FC BU S
MS-VMA1 620 -0P WR I N: 2 4VA C 2 .5 A, CL AS S 2O UT PU T S: 24VA C 0 .5 A, CL AS S 2, P IL O T DU T Y
MA NU A LO VE R RI D E
OP EN E NERG YMA NAG EMEN TEQ UIPMENT
CLE AR =LO W RE D=H IG H 35 IN - LB (4 Nm) 60 SE CO ND SAL L F IE LD TER MIN ALS A RE PO WER L IMIT ED
O UT 1
O CO M 1
O UT 2
O CO M 2
O UT 3
O CO M 3
BIN
ARY
O UT 4
O CO M 4
O UT 5
O CO M 5
HO T
CO M
CON
FIGUR
ABL
E24
ADD
RESS
0=OFF
UN
IVER
SAL
+15
I N
I CO M
SEN
SOR
SA B
US
FC B
US
SAPWR
CO M
–
+
SHLD
CO M
–
+
FCEO L
15U0
0
0
4
0
NetworkSensor
SA Bus and
Addresses
199
200
NetworkSensor
200
FC BusDevice
FC BusDevice
FC BusDevice
NetworkSensor
201
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 87
Setting a Device Address
For most (non-supervisory) devices on an FC Bus or SA Bus, the device address is set using the DIP switches on the device’s ADDRESS DIP switch block. The DIP switches are binary switch blocks and each switch represents a binary numerical value when the switch is in the ON position.
The device address set on the ADDRESS DIP switch block applies to only the bus where the device is not the bus supervisor. For example, the DIP switches on an FEC set the FC Bus address. If the FEC also supervises an SA Bus, the FEC’s SA Bus address is 0 by default (Figure 60). The switches on the IOM set the address of the FC Bus or SA Bus depending on the bus on which the IOM is located.
As you set the device address, the best-practice is to set the highest switch value first, then the next highest switch value, and so on, until the total of the switch values equal the intended device address. For example, to set a device address for a device on an SA Bus to 227, position switch 128 to ON first, then 64, 32, 2, and 1. Positioning switches 16, 4, and 1 to ON (as shown in Figure 61) sets the device address to 21 for a device on the FC Bus.
Table 20: Valid MS/TP Bus Address and Value RangesAddress Value/Address Range
Class Examples
0 Bus Supervisor NAE on the FC BusFEC and VMA on the SA Bus
1 Reserved Wireless Commissioning Converter
2 - 3 Reserved Reserved for future use.
4 - 127 Master Range FEC, VMA, IOM, TEC26xx on the FC BusIOM on the SA Bus
128 - 254 Slave Range Slave devices and network sensors on the SA Bus
198 Reserved VAV Balancing Sensor (handheld)
199 Reserved Most NS Series Network Sensor models or VAV Balancing Sensor (wall-mounted)
200 - 203 Reserved NS Series Network Sensors (specified models)
255 Broadcast Do not apply address 255 to any device.
128 64 32 16 8 4
2 1
O
N
Figure 61: Setting the Device Address on the ADDRESS DIP Switch Block
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin88
Note: Devices may go offline momentarily when a device address is changed on an active bus, but the bus devices and bus supervisor do not need to be reset after changing a device address.
Some devices, such as the TEC26xx Series thermostats and third-party MS/TP devices, use their own configuration settings to establish the device address on the bus. Refer to the device manufacturer’s product documentation for instructions on setting the device address. The device address values for TEC26xx thermostats and all third-party devices must comply with the rules and ranges described above.
SMK-MOVKIT-MSTP Transient Protection KitThe MS/TP FC bus and SA bus communication lines must have an SMK-MOVKIT-MSTP MOV kit installed when the conduit run between enclosures does not remain in the same room.
Installation Requirements
Care must be taken when installing transient protectors (MOV kits) in close proximiy to other protectors. Use the information below to install the MOV kit.
• Before installing the MOV kit to the MS/TP terminal block, twist it together with the field lead and insert it in the terminal block as one wire.
• Twist the wire tightly around the transient protection device a minimum of two turns before inserting it into the terminal block.
• When more that two wires are to be placed under a single terminal screw, the wires must be soldered together with a single 6 inch length of 18 AWG wire having a minimum insulation thickness of 1/64 inch. The exposed solder connection must be covered with a UL recgonized component heat shrink. The single wire end that will be inserted into the terminal must be stripped and then tinned or crimped with a suitable lug that fits securely under the terminal screw. The single wire end that will be attached to earth ground must be stripped and crimped with a suitable lug that will fit securely under the grounding screw.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 89
Figure 62 shows wire runs to MS/TP equipment in cabinets in various rooms and the correct use of the SMK-MOVKIT-MSTP to protect the MS/TP devices from transients.
Figure 62: SMK-MOVKIT-MSTP Communication Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin90
SMK-MOVKIT-MSTP Wiring for MS/TP FC Bus Communication TerminationsFigure 63 shows a SMK-MOVKIT-MSTP and its wiring when the wiring terminates at the MS/TP FC Bus communication terminal block.
Figure 63: SMK-MOVKIT-MSTP MS/TP FC Bus Communication Wiring Terminations
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 91
Figure 64 shows the SMK-MOVKIT-MSTP wiring for an FC Bus when the FC Bus communication wiring does not terminate at the MS/TP FC Bus terminal block.
Figure 64: SMK-MOVKIT-MSTP FC Bus Wiring Terminations - Multiple MSTP Wires
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin92
SMK-MOVKIT-MSTP Wiring for SA Bus Communication TerminationsFigure 65 shows a SMK-MOVKIT-MSTP and its wiring when the SA Bus communication wiring terminates at the MS/TP SA Bus terminal block.
Figure 65: SMK-MOVKIT-MSTP MS/TP SA Bus Communication Wiring Terminations
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 93
Figure 66 shows the SMK-MOVKIT-MSTP wiring for an SA Bus when the SA Bus communication wiring does not terminate at the MS/TP SA Bus terminal block.
Figure 66: SMK-MOVKIT-MSTP SA Bus Wiring Terminations - Multiple MSTP Wires
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin94
MOV Requirements for MS/TP I/O TerminalsAll MS/TP controller input terminals and output terminals must have an MOV from a SMOKE-MOVKIT-0 placed between earth ground and each Power terminal, I/O Common terminal, and I/O terminal.
The MS/TP field device’s I/O lines must have a SMOKE-MOVKIT-0 MOV kit installed when the conduit run between the enclosures and an MS/TP I/O field device does not remain in the same room.
Note: The SMOKE-MOVKIT-0 kit contains 10 MOVs.
Installation RequirementsCare must be taken when installing transient protectors (MOV kits) in close proximiy to other protectors. Use the information below to install the MOV kit.
• Before installing the MOV kit to the MS/TP I/O terminal block, twist it together with the field lead and insert it in the terminal block as one wire.
• Twist the wire tightly around the transient protection device a minimum of two turns before inserting it into the terminal block.
When more that two wires are to be placed under a single terminal screw, the wires must be soldered together with a single 6 inch length of 18 AWG wire having a minimum insulation thickness of 1/64 inch. The exposed solder connection must be covered with a UL recgonized component heat shrink. The single wire end that will be inserted into the terminal must be stripped and then tinned or crimped with a suitable lug that fits securely under the terminal screw. The single wire end that will be attached to earth ground must be stripped and crimped with a suitable lug that will fit securely under the grounding screw.
Note: The SMOKE-MOVKIT-0 contains 10 individual MOVs.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 95
Figure 67 shows the MSTP controller I/O terminal block SMOKE-MOVKIT-0 connections using 3 MOVs from the SMOKE-MOVKIT-0 kit..
End-of-Line Termination on the MS/TP BusDaisy-chained RS485-protocol networks typically require some type of End-of-Line (EOL) termination to reduce interference caused by signal reflection that occurs when data transmissions reach the end of a bus segment and bounce back on the segment. The high baud rates on MS/TP bus applications require robust EOL termination and strict adherence to the EOL termination rules. Figure 68 shows an example of the EOL termination settings on an MS/TP bus application.
The EOL termination requirements for FC Buses are different from the SA Bus requirements. See SA Bus Rules and Specifications on page 109 and EOL Termination on the SA Bus on page 100 for more information on terminating the MS/TP bus.
Figure 67: SMOKE-MOVKIT-0 MSTP I/O Wiring Terminations
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin96
End-of-Line Termination Switch LocationsEOL termination on the FC Bus is enabled with a switch on the MS/TP device (Figure 69) and (Figure 70). EOL termination on the SA Bus is fixed On on the MS/TP device.
Figure 68: EOL Termination on an MS/TP Bus
Net
wor
k_ex
ampl
e
VMA1620FC Bus EOL OFF SA Bus EOL ON
(Fixed)
RE T S Y
EOL SwitchON (Up)
NAE45
TFC Bus
= EOL switch set to ONT
T
NetworkSensor
FEC1610FC Bus EOL ONSA Bus EOL ON
(Fixed)
RET S
Y
ON
SAB
US
FAULT
POW
ER
ON
NetworkSensor
SA Bus
SA Bus
RET
SY
ON SA
BU
S
FAU
LT
PO
WE
R
ON
IOM3710SA Bus EOL ON - Recommended
(EOL OFF - Acceptable)
Ethernet Network
T = EOL fixed ON
T
T
T
P OW ER
FA U LT
S A BU S
FC BU S
MS-VMA1 620 -0P WR I N: 2 4VA C 2 .5 A, CL AS S 2O UT PU T S: 24VA C 0 .5 A, CL AS S 2, P IL O T DU TY
MA NU A LO VE R RI D E
OP EN E NERG YMA NAG EMEN TEQ UIPMENT
CLE AR =LO W RE D=H IG H 35 IN - LB (4 Nm) 60 SE CO ND SAL L F IE LD TER MIN ALS A RE PO WER LI MIT ED
O UT 1
O CO M 1
O UT 2
O CO M 2
O UT 3
O CO M 3
BIN
ARY
O UT 4
O CO M 4
O UT 5
O CO M 5
HO T
CO M
CON
FIGUR
ABL
E24
ADD
RESS
0=OFF
UN
IVE
RSAL
+15
I N
I CO M
SEN
SOR
SA B
US
FC B
US
SAPWR
CO M
–
+
SHLD
CO M
–
+
FCEO L
15U0
FC BusDevice
FC BusDevice
FC BusDevice
EOL OFF
Figure 69: MS/TP Controllers Set as EOL Termination Devices
RET SYFAULT
MS-VMA1620-0PWR IN: 24VAC 2.5A, CLASS 2OUTPU TS: 24VAC 0.5A, CLASS 2, PILOT DUTY
CLEAR=LOW RED=HIGH 35 IN-LB (4Nm) 60 SECONDSALL FIELD TERMINALS ARE POWER LIMITED
OUT 1
OCOM 1
OUT 2
OCOM 2
OUT 3
OCOM 3
BINARY
OUT 4
OCOM 4
OUT 5
OCOM 5
CONFIG
URABLE
24
ADDRESS 0=O
FF
UNIVERSA
L
+15
IN
ICOM
SENSOR
SA BUS
FC BUS
SAPW R
COM
–
+
SHLD
COM
–
+
FCEO L
RET SYFAULT
RET SYFAULT
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 97
FC and SA Bus Device EOL Switch Details
MS/TP NAEs connect only to FC Buses. FECs and VMAs can connect to an FC Bus and an SA Bus simultaneously. The EOL switches on NAEs, FECs, and VMAs enable EOL termination on the FC Bus only.
Smoke Control NAE5510-1U models have two FC Bus ports and EOL switches, and each EOL switch is double-pole.
Smoke Control NAE3510-2U and 4510-2U models have one FC Bus port and one double-pole EOL switch.
Note: The FECs or VMAs do not have EOL switches for the SA Bus and these controllers are always (fixed ON) SA Bus EOL termination devices.
IOMs connect to either an FC Bus or SA Bus. IOMs can not simultaneously connect to the FC Bus and SA Bus. The EOL switch on IOMs enables an IOM as an EOL termination device on either an FC Bus or an SA Bus.
IMPORTANT: The TEC Series Thermostat Controllers cannot be used as End-of-Line (EOL) devices. You can use the MS-BACEOL-0 RS-485 EOL Terminator to provide EOL termination on Metasys® RS-485 protocol FC segments when the terminating field device does not have integral EOL termination capability.
Figure 70: MS/TP NAE5510-1U Controller Set as EOL Termination DevicesLON
LON
BLO
NA
SHIELD
End-of-Line(EOL) Switchesin On Position
NAE
55_L
ON
_EO
L
1ON
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin98
EOL Termination on the FC BusA MS/TP FC Bus may consist of up to three bus segments. Each bus segment on an FC Bus requires two EOL termination devices, one at each end of the bus segment. All other devices on the FC Bus should have their EOL termination disabled (EOL switches OFF). See Figure 71.
Figure 71: Example of Proper EOL Termination on an FC Bus
RE T S Y
EOL SwitchON
NAE(FC Bus
Supervisor)
TR R
Bus Segment1520 m (5,000 ft) Maximum
50 Metasys Device Connections
= EOL Termination switch ONT
R = Repeater
FIG
_FC
_SEG
S
T T TT
T
Note: When TEC26xx Series thermostats and/or third-party BACnet MS/TP devices are connected to the FC Bus, a bus segment supportsonly up to 32 devices and an FC Bus supports only up to 64 devices.
Bus Segment1520 m (5,000 ft) Maximum
50 Metasys Device Connections
(maximum)
FC Bus4570 m (15,000 ft) Maximum
100 Total Metasys Devices
Bus Segment1520 m (5,000 ft) Maximum
50 Metasys Device Connections
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 99
FC Bus EOL Termination Scenarios
The FC Bus requires EOL terminations on the devices at the end of each bus segment on the FC Bus. Figure 72 shows examples of FC Bus EOL termination in four different FC Bus scenarios.
Note: Set the EOL termination switch on a repeater to ON only when the repeater terminates a bus segment at the repeater. See Scenario 4 in Figure 72.
Figure 72: FC Bus Termination Scenarios
RET SY
NAE
EOL SwitchON (Up)
RET SY
NAE
EOL SwitchOFF (Down)
TT
TT
5,000 ft (maximum)
FC_E
OL= EOL switch set to ONT
R = Repeater
RET SY
EOL SwitchON (Up)
NAE
T
T
T
R
T
FC Bus Segment 15,000 ft (max )imum
FC Bus Segment 25,000 ft (max )imum
= FC Bus Device
RET SY
EOL SwitchON (Up)
NAE
TT T
R
T
FC Bus Segment 15,000 ft (max )imum
FC Bus Segment 25,000 ft (max )imum
Scenario 1FC Bus with an NAE at the endof the line
Scenario 2
not FC Bus with anNAE at the end of the line
SCenario 3FC Bus in twosegments with the repeater at the end of both segments
Scenario 4
not
FC Bus in two segments with the repeater at the end of both segments
5,000 ft (max )imum
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin100
EOL Termination on the SA BusAn SA Bus is a single-segment bus only. NAEs, FECs, or VMAs are always (fixed ON) EOL termination devices on an SA Bus. An IOMs EOL termination is enabled by positioning the IOM EOL switch to ON.
Since an SA Bus is always connected to a supervisory/master controller (FEC and VMA) or an IOM, an SA Bus always meets the acceptable EOL termination requirements. For enhanced bus performance, it is preferable to have EOL termination enabled on the devices at each end of the SA Bus. Figure 73 shows SA Bus EOL termination scenarios.
Note: The MS-BACEOL-0 RS-485 End-of-Line Terminator module is not designed for use on the SA bus.
Figure 73: SA Bus Termination Scenarios
FEC/VMA1600
EOL ON(Fixed)
SA Bus Devices
FEC/VMA1600
EOL ON(Fixed)
RET S Y
ON
S A BU S
FA U LT
P OWE R
ON
RET S Y
ON
S A BU S
FA U LT
P OWE R
ON
SA_E
OL
EOL ON(Fixed)
FEC/VMA1600
RET S Y
ON
S A BU S
FA U LT
P OWE R
ON
IOMEOL = ON
Best
Acceptable
Acceptable
T
= EOL switch set to ONT
T = EOL fixed ON
T
T
T
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 101
SA Buses with Multiple Network SensorsThe SA Bus supports up to four network sensors. Figure 74 shows an example of two SA Buses, each with four network sensors. To place multiple network sensors on the bus, three of the four network sensors must be switch addressable model NS-ATN7003-0 or NS-BTN7003-0.
Terminating FC Devices that do not have Integral EOL Termination Capability
MS-BACEOL-0 EOL Terminator Module
The non-smoke control listed MS-BACOL-0 RS-485 EOL terminator provides EOL termination on FC Bus segments when the terminating device does not have integral EOL termination capability.
The EOL terminator module is a compact, lightweight, module wrapped in a protective cover that can be quickly installed in the field in a variety of ways. The EOL connects directly to the terminating device on a bus segment with the attached wire leads. The EOL requires 24 VAC, Class 2 power supplied by the field device or other 24 VAC source.
An EOL is required in all Metasys MS/TP applications wherever a terminating a third-party device that does not have integral EOL termination (for example, TEC26xx Series thermostats) on an isolated non-smoke FC Bus segment.
The EOL is designed for Metasys RS-485 buses.
IMPORTANT: When you use a third-party device, place a repeater before it. Third-party devices require an EOL terminator module at the beginning of the bus. You also must set the EOL switch on the A and B side of the repeater to EOL. Ensure the last third-party device on the bus has a terminator module. In addition, a SMOKE-TRNKIT-1 tranzorb must be installed on the repeater’s TB1 and TB2 terminals.
Figure 74: SA Bus Example Showing Multiple Networks Sensors
NAE55
VMA1620
FEC1610
NS-x
TN70
03-0
Addr
esse
d to
200
SA Bus with 4 Daisy-Chained Network SensorsUsing Terminal Blocks
FIG
: ns_
exam
ple
FC BusSA Bus with 3 Daisy-Chained Network Sensors
Using Terminal Blocks Plus1 Network Sensor with a Modular Jack
NS-x
TN70
03-0
Addr
esse
d to
201
NS-x
TN70
03-0
Addr
esse
d to
202
NS-x
TN70
03-0
Addr
esse
d to
200
NS-x
TN70
03-0
Addr
esse
d to
201
NS-x
TN70
03-0
Addr
esse
d to
202
NS-x
xx70
0-0
Addr
ess
= 19
92
NS-x
xx70
0-0
Addr
ess
= 19
91
Ethernet Network
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin102
Note: Disable the integral EOL termination on the 3rd party device if the EOL terminator is connected to a third-party device that has integral EOL termination.
Figure 75: MS-BACEOL-0 FC Bus EOL Terminator
Figure 77: EOL Terminator Connected to a TEC2600 Series Thermostat
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 103
Wiring the MS-BACEOL-0 EOL Terminator Module
Observe the following guidelines when wiring the EOL terminator:
• The EOL terminator is designed for MS/TP trunks on Metasys RS-485 Buses. Connect the EOL terminator to only MS/TP trunks on Metasys RS-485 FC Buses.
• Connect the EOL terminator to MS/TP devices that terminate Metasys bus segments and do not have integral EOL termination capability.
• When a third-party device terminates a Metasys FC Bus segment, it is recommended that any EOL termination on the third-party be disabled and an EOL terminator be installed to provide EOL termination on the bus segment.
• When the third-party (terminating) device has only the + and - terminals (no REF or COM), isolate and insulate the blue REF lead on the EOL (Figure 79).
Connect the EOL FC Bus leads to the appropriate FC Bus terminals on the bus terminating device (Figure 79).
Connect the EOL 24 VAC power supply leads to a dedicated or surged protected 24 VAC, Class 2 power supply (Figure 79).
!CAUTION: Risk of Electric ShockDisconnect power supply before making electrical connections to avoid electric shock.
IMPORTANT: Do not connect 24 VAC supply power to the EOL Terminator before wiring is complete.
IMPORTANT: Use copper conductors only. Ensure all wiring is in accordance with local, national, and regional regulations.
IMPORTANT: The EOL Terminator is a low-voltage (<30 VAC) device. Do not exceed the EOL Terminator electrical ratings.
IMPORTANT: Prevent any static electric discharge to the EOL Terminator. Static electric discharge can damage the EOL Terminator and void any warranties.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin104
Mounting the MS-BACEOL-0U EOL Terminator Module in Plenum Applications
Troubleshooting the MS-BACEOL-0 EOL Terminator Module
An improperly wired or malfunctioning EOL terminator may result in loss of network communication or poor performance on the RS-485 bus.
To troubleshoot the EOL terminator:
1. Check the supply voltage to the EOL to ensure that the voltage is between 18 and 30 VAC:
• If the supply voltage is between 18 and 30 VAC, proceed to Step 2.
• If the voltage is <18 or >30 VAC, troubleshoot the supply power source and bring the supply voltage into the required range, then proceed to Step 2.
2. With the EOL connected to 24 VAC power and the FC Bus leads disconnected, check the voltage drop between the REF and FC+ leads and between the REF and FC- leads:
• REF to FC+ should be 2.7 to 3.2 VDC
• REF to FC- should be 2.3 to 2.7 VDC
IMPORTANT: Before installing the MS-BACEOL-0 RS-485 EOL Terminator in plenum applications, verify acceptance of exposed plastic materials in plenum areas with the local building authority. Building codes for plenum requirements vary by location. Some local building authorities accept compliance to UL 1995, Heating and Cooling Equipment. Check with the local building authority for local building codes.
Figure 79: Wiring the MS-BACEOL-0 EOL Terminator to a Bus-Terminating Device
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 105
If the EOL voltages are within these ranges, the EOL is operating properly and is not a source of communication or performance problems on the bus.
If the EOL voltages are out of either of these ranges, replace the EOL terminator.
3. Reconnect a properly operating EOL terminator to the 24 VAC, Class 2 (network) power source.
If network communication or performance problems persist, continue troubleshooting the RS-485 bus.
SpecificationsTable 21: MS-BACEOL-0 SpecificationsCategory SpecificationsProduct Code MS-BACEOL-0 RS-485 End-of-Line Terminator
Power Requirements 24 VAC, 1.2 VA Maximum
Wiring Terminations and Network Interfaces
Power: Two 200 mm (8 in.) 22 AWG wire leads for 24 VAC supply power connectionsNetwork: Three 200 mm (8 in.) 22 AWG wire leads for RS-485 Bus connections
Ambient Operating Temperature
32 to 120° F (0 to 49° C)
Ambient Operating Humidity
10 to 93% RH, non-condensing
Dimensions 70 x 38 x 10 mm (2-3/4 x 1-1/2 x 3/8 in.) with five 20 cm (8 in.) 20 AWG wire leads
Shipping Weight 40.0 g (1.4 oz)
Compliance United States: UL Listed, File S4977, CCN PAZX, UL 916, Energy Management EquipmentFCC Compliant to CFR47, Part 15, Subpart B, Class AUL Listed, File S4977, CCN UUKL, UL 864, Control Units and Accessories for Fire Alarm Systems
Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, SignalEquipment. Industry Canada Compliant, ICES-003
Europe: CE Mark, EMC Directive 89/336/EEC, in accordance with EN 50081-1, Class B, Generic emission standard for residential, commercial and light industry, and EN 50082-2/EN 61000-6-2, Generic immunity standard for heavy industrial environment
Australia and New Zealand: C-Tick Mark, Australia/New Zealand Emissions Compliant
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin106
FC Bus Rules when using TEC26xx Series Thermostats and Third-Party MS/TP DevicesIf TEC26xx Series thermostats and/or third-party BACnet MS/TP devices are connected on an FC Bus, then they must be isolated from the MS/TP bus using a NU-RPT101-1U repeater.
When a TEC26xx Series thermostat terminates an isolated FC Bus bus-segment, an EOL Terminator module (MS-BACEOL-0) must be wired to the FC Bus terminals on the TEC26xx thermostat. See Terminating FC Devices that do not have Integral EOL Termination Capability on page 101 for more information.
If one or more TEC26xx Series thermostats and/or third-party BACnet MS/TP devices are connected on an isolated FC Bus, the supported maximum device counts, bus segments, and bus length are:
• 64 devices total per FC Bus (maximum)
• 3 bus segments per FC Bus (maximum)
• 32 devices per bus segment (maximum, not to exceed 64 devices total on FC Bus)
• 1,220 m (4,000 ft) maximum per bus segment (using 22 AWG stranded, 3-wire twisted, shielded cable)
• 3660 m (12,000 ft) maximum per FC Bus (using 22 AWG stranded, 3-wire twisted, shielded cable)
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 107
FC Bus Rules and SpecificationsThe FC Bus connects field controllers to an NAE. Table 22 and Table 23 provide FC Bus rules and specifications. Table 22: FC Bus RulesCategory Rules/LimitsGeneral NAE55 Series models support up to two FC Buses.
NAE35 and NAE45 Series models support one FC Bus.Only daisy-chained connections (no T or Star topology configurations)
Number of Devices An FC Bus supports up to 100 Metasys devices and up to three bus segments. Note: When TEC26xx Series thermostats and/or third-party MS/TP controllers are connected on the FC Bus, the FC Bus supports only up to 64 devices.A bus segment on an FC Bus supports up to 50 Metasys devices (but the total number of Metasys devices on the FC Bus cannot exceed 100).Note: When TEC26xx Series thermostats and/or third-party MS/TP controllers are connected on the bus segment, the bus segment supports only up to 32 devices per bus segment and the FC Bus supports a maximum of 64 devices.
Up to two cascaded repeaters may be applied to an FC Bus.
Cable Length and Type 1,520 m (5,000 ft.)2 maximum separation between any devices on a bus segment. Repeaters are used to connect bus segments.
4,570 m (15,000 ft.)2 between any devices on a bus (up to three segments of 1,520 m [5,000 ft.] each using cascaded repeaters). See Figure 58 on page 84.Note: When TEC26xx Series thermostats and/or third-party MS/TP controllers
are connected on the FC Bus:1. Each bus segment may be up to 1,220 m (4,000 ft) in length (using 22 AWG
3-wire twisted, shielded cable).2. The FC Bus may be up to 3,660 m (12,000 ft)in length (using 22 AWG 3-wire
twisted, shielded cable).
RecommendedCable Type1
1. The recommended cable type provides the best bus performance. See MS/TP Bus Cable Recommendations on page 111 for more information on alternative cable types.
2. If third-party devices are connected to the bus, the cable lengths should be reduced if necessary to match the third-party vendor recommendations.
22 AWG Stranded, 3-Wire Twisted, Shielded Cable
EOL Termination The EOL switch must be set to On (or an EOL terminator installed) on the two devices located at either end of each bus segment on an FC Bus.The EOL switches must be set to Off (or EOL termination disabled) for all other devices on the FC Bus segment. See SA Bus Rules and Specifications on page 109 for more information.
EOL Termination Method Integral EOL Termination switch or add-on EOL Terminator module (See SA Bus Rules and Specifications on page 109 and Terminating FC Devices that do not have Integral EOL Termination Capability on page 101 for more information.)
FC Bus Communication Wiring Transient Protection
Requires a SMK-MOVKIT-MSTP for all FC Bus communication terminal wiring. See SMK-MOVKIT-MSTP Wiring for MS/TP FC Bus Communication Terminations on page 90 for details.
FC Bus I/O Terminals Transient Protection
Requires SMOKE-MOVKIT-0 between all FC Bus I/O terminals (Power terminals, I/O Common terminals, I/O terminals, and earth ground).See MOV Requirements for MS/TP I/O Terminals on page 94 for details.
Connecting TEC26xx Series thermostats and/or third-party MS/TP controllers
When TEC26xx Series thermostats and/or third-party MS/TP controllers are connected on the FC bus segment, an NU-RPT101-0 repeater is required to isolate the FC Bus. See NU-RPT101-0U RS-485-to-RS-485 Repeater on page 118 for more information.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin108
Table 23: FC Bus SpecificationsCategory SpecificationError Checking Message Headers checked using 8 bit CRC test. Message data check using
16-bit CRC test.
Device Addressing 0 - 255 (See Device Addresses on the MS/TP Bus on page 86 for more information.)
Data Transmission Standard RS485
Signaling Method BACnet MS/TP
Signaling Rate 9,600, 19,200, 38,400, or 76,800 baud as selected by bus supervisor
Transient Immunity Meets ENG1000-4 Requirements for heavy industrial applications. Protected against misapplication of 24 VAC.
EOL Termination Method Integral EOL Termination switch or add-on EOL Terminator module (See SA Bus Rules and Specifications on page 109 and Terminating FC Devices that do not have Integral EOL Termination Capability on page 101 for more information.)
Shield Grounding One (only) hard ground connection per bus segment with shielded cable.
Physical Configuration Daisy-chained
Optional Vendor Components Repeaters• NU-RPT101-0U (Acromag 4683-TTM-1F (115 VAC)) Note: A repeater is required to support more than 50 devices per trunk
segment and/ or trunk cable segments longer than 1,524 m (5,000 ft.).MS-BACEOL-0 RS485 End-of-Line Terminator • provides EOL termination on Metasys® RS485 protocol Field Controller
(FC) Bus segments when the terminating field device does not have integral EOL termination capability.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 109
SA Bus Rules and SpecificationsThe SA Bus connects input/output point controllers and network sensors to field controllers.
Table 24 and Table 25 provide SA Bus rules and specifications. Table 24: SA Bus Rules
Category Rules/LimitsGeneral Each bus supervisor supports one SA Bus and each SA Bus supports one segment.
Number of Devices Supported on the Bus
An SA Bus supports up to 10 devices.Note: An SA Bus supports only up to four Network Sensors (due to bus address and power limits).
SA Buses do not support repeaters.
Cable Length 366 m (1,200 ft.) maximum separation between any devices on the bus
152 m (500 ft.) maximum distance between network sensor and the controller supplying power (FEC, VMA) using screw terminal blocks
30 m (100 ft.) maximum length for network sensors using the modular jack
366 m (1,200 ft.) maximum Bus Length
Recommended Cable Type1
1. The recommended cable types provide the best bus performance. See MS/TP Bus Cable Recommendations on page 111 for information on alternative cable types.
Screw Terminal Connections: 22 AWG Stranded 4-wire, 2-Twisted Pairs, Shielded Cable for screw terminalsModular Jack Connections: 6-Pin RJ-Style Modular Connectors with 24 or 26 AWG Stranded 6-Wire, 3-Twisted Pairs
EOL Termination Each SA Bus supervisor has integral EOL termination, which typically provides sufficient EOL termination on an SA Bus. Long SA Bus runs or persistent communication problems on an SA Bus may require EOL termination at the last device on the SA Bus (in addition to the integral EOL termination at the SA Bus supervisor).
EOL Termination Method
Integral EOL Termination switch or add-on EOL Terminator module (See SA Bus Rules and Specifications on page 109 and Terminating FC Devices that do not have Integral EOL Termination Capability on page 101 for more information.)
SA Bus Communication Wiring Transient Protection
Requires SMK-MOVKIT-MSTP for all FC Bus communication terminal wiring. See SMK-MOVKIT-MSTP Wiring for SA Bus Communication Terminations on page 92 for details.
SA Bus I/O Terminals Transient Protection
Requires SMOKE-MOVKIT-0 between all SA Bus I/O terminals(Power terminals, I/O Common terminals, I/O terminals, and earth ground).See MOV Requirements for MS/TP I/O Terminals on page 94 for details.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin110
Table 25: SA Bus SpecificationsCategory SpecificationError Checking Message Headers checked using 8 bit CRC test.
Message data check using 16-bit CRC test.
Device Addressing 0 - 255 (See Device Addresses on the MS/TP Bus on page 86 for more information.)
Data Transmission Standard
RS-485
Signaling Method BACnet MS/TP
Signaling Rate 9,600, 19,200, 38,400 (default), or 76,800 baud as selected by the bus supervisor
Transient Immunity Meets ENG1000-4 Requirements for heavy industrial applications. Protected against misapplication of 24 VAC.
Shield Grounding One hard ground per bus when using shielded cable
Physical Configuration Daisy-chained (screw terminal only).
Optional Vendor Components
Transient Eliminator:• Advanced Protection Technologies Transient Eliminator TE/JC04C12
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 111
MS/TP Bus Cable RecommendationsTable 26 provides cable recommendations for MS/TP applications. The recommended FC Bus and SA Bus cables are available from Belden CDT® Inc. and Anixter Inc.
Note: For the best performance on MS/TP bus applications, 22 AWG stranded wire in a shielded cable with proper cable shield grounding is recommended. Other wire gauges and non-shielded cable may provide acceptable bus performance in many applications, especially applications that have short cable runs and low ambient inductive noise levels. See Table 26 and Table 27 for more information.
MS/TP buses cannot support the same number of devices at every baud rate and wire gauge. See Table 27. We recommend operating the MS/TP bus at 38,400 baud.
Table 26: Recommended Cable for FC Buses and SA BusesBus and Cable Type Non-Plenum Applications Plenum Applications
Part Number O.D. Part Number O.D.FC Bus: 22 AWG Stranded, 3-Wire Twisted Shielded Cable1
1. A 3-wire (for FC Bus) and 4-wire, 2 twisted-pair (for SA Bus), 22 AWG stranded, shielded cable is strongly recommended. 22 gauge cable offers the best performance for various baud rates, cable distances and number of trunk devices primarily due to lower conductor-to-conductor capacitance. Shielded cable offers better overall electrical noise immunity than non-shielded cable. Observe the shield grounding requirements.
Anixter: CBL-22/3-FC-PVC Belden: B5501FE
0.138 in. Anixter: CBL-22/3-FC-PVC Belden: B6501FE
0.140 in.
SA Bus (Terminal Block):22 AWG Stranded, 4-Wire, 2 Twisted-Pair Shielded Cable1
Anixter: CBL-22/2P-SA-PVCBelden: B5541FE
0.209 in. Anixter: CBL-22/2P-SA-PLN Belden: B6541FE
0.206 in.
SA Bus (Modular Jack)2:26 AWG Stranded 6-Wire, 3 Twisted-Pair Cable
2. 26 AWG stranded, 6-wire, (3 twisted pairs) cable is recommended as the best fit for fabricating modular cables with the modular jack housing assembly. Be sure the cable you use fits the modular jack housing. The preassembled cables that are available from Anixter (Part No. CBL-NETWORKxxx) use 24 gauge wire.
— — Anixter Inc. preassembled: CBL-NETWORK25CBL-NETWORK50CBL-NETWORK75CBL-NETWORK100
0.15 in.
FC Bus: 22 AWG Stranded, 3-Wire Twisted Non-Shielded Cable
Belden: B5501UE 0.135 in. Belden: B6501UE 0.131 in.
SA Bus (Terminal Block):22 AWG Stranded, 4-Wire, 2 Twisted-Pair Non-Shielded Cable
Belden: B5541UE 0.206 in. Belden: B6541UE 0.199 in.
Recommended Acceptable
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin112
Wiring the MS/TP Bus
Table 27: FC Bus Wire Gauge vs. FC Bus Baud RateAWG Wire Gauge
Maximum Cable Length and Node Connections Limit
Baud Rate
96001 19,2001 38,4002 76,800
18 Maximum Cable Length per Bus Segment [m (ft)]
1,524 (5,000) 1,524 (5,000) 1,524 (5,000)
1,219 (4,000)
1,524 (5,000)
305 (1000)
Maximum Number of Nodes [per Segment / per FC Bus]
25/25 50/50 40/100 50/100 10/30 50/100
20 Maximum Cable Length per Bus Segment [m (ft)]
1,524 (5,000) 1,524 (5,000) 1,524 (5,000) 1,524 (5,000)
1,219 (4,000)
Maximum Number of Nodes [per Segment / per FC Bus]
25/25 50/50 50/100 40/100 50/100
22 Maximum Cable Length per Bus Segment [m (ft)]
1,524 (5,000) 1,524 (5,000) 1,524 (5,000) 1,524 (5,000)
Maximum Number of Nodes [per Segment / per FC Bus]
25/25 50/50 50/100 50/100
24 Maximum Cable Length per Bus Segment [m (ft)]
1,524 (5,000) 1,524 (5,000) 1,524 (5,000) 1,524 (5,000)
Maximum Number of Nodes [per Segment / per FC Bus]
25/25 50/50 50/100 50/100
26 Maximum Cable Length per Bus Segment [m (ft)]
1,524 (5,000) 1,524 (5,000) 1,524 (5,000) 1,524 (5,000)
Maximum Number of Nodes [per Segment / per FC Bus]
25/25 50/50 50/100 50/100
Best Acceptable Acceptable with Possible Restrictions Not Recommended
1. The maximum number of devices is reduced at lower baud rates due to increased token loop times. 2. 3 conductor (FC Bus), 22 AWG stranded, shielded cable is recommended. 22 gauge cable offers the best
performance for various baud rates, cable distances, and number of trunk devices primarily due to lower conductor-to-conductor capacitance. Shielded cable offers better overall electrical noise immunity than non-shielded cable.
IMPORTANT: Do not apply power to the Metasys network before finishing communication wiring and checking all wiring connections. Short-circuited or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations. Do not exceed the electrical ratings for the devices on the Metasys network.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 113
General MS/TP Bus Wiring GuidelinesObserve the following when installing and wiring the MS/TP Communications Bus:
• Do not run cables near moving parts. Avoid sharp bends, abrasion, and the potential for severing or crushing the cable.
• Route cables neatly to promote good ventilation, visibility, testing, and ease of service.
• Provide some slack in the wires and cables to allow for access and servicing.
• Protect, coil, and secure any excess cable.
• Ensure proper grounding for bus cable shielding.
• Ensure proper EOL termination on buses and bus segments.
• Use dedicated transformers for 24 VAC supply power to the network devices or provide surge protection on the primary side of the 24 VAC supply power transformers to isolate the network devices from inductive surges or spikes.
FC Bus Wiring Guidelines
The FC Bus is a 22 AWG stranded, 3-wire, twisted shielded cable. Figure 4 shows a wiring detail for the FC Bus terminal blocks.
See Table 27 on page 112 for bus cable length limits.
Follow these guidelines for wiring the FC Bus:
• Wire the bus devices in a daisy-chain network configuration. Maintain polarity (FC+ to FC+, FC- to FC-, COM to COM, and SHLD to SHLD) along entire bus daisy-chain (Figure 81).
• Twist the FC Bus lead pairs together before inserting into the termination and ensure that the termination is tight at each terminal block on the daisy-chain.
• Each FC Bus segment must have only one hard ground connection to the cable shield.
• The hard ground connection to the cable shield should be made at the NAE when the NAE terminates the bus segment. Cable shield ground connection should be made within the first inch after entering the NAE enclosure.
• All other cable shield connections along the bus segment must be isolated from ground unless network communication problems persist.
IMPORTANT: Do not run network communication cables in the same conduit, raceway, or panel with any highvoltage (>30 VAC) wiring. Isolate all network devices from high-voltage wiring and equipment. Failure to isolate network wiring and network devices from high-voltage wiring and equipment can result in damage to network devices or poor network performance.
IMPORTANT: Properly install, terminate, and ground the cable shield on the FC Bus to minimize inductive noise, which can result in unreliable communication on the bus.
IMPORTANT: Prevent any static electric discharge to the network wiring and network devices. Static electric discharge can damage the network devices and void any warranties.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin114
FC Bus and SA Bus Screw TerminationsBoth the FC Bus and SA Bus terminations have pluggable screw terminal blocks that allow you to connect the bus devices in a daisy-chain configuration (Figure 81).
For optimum bus performance, connect the FC Bus cable shield to a metal, earth grounded enclosure at only one connection on each bus segment. On bus segments connected to an NAE, this connection should be made within 1 or 2 in. of the NAE. Connect the remaining devices on each bus segment on the FC Bus as shown in Figure 81.
Note: The SHLD terminal on the FC Bus terminal block is electrically isolated from ground and is provided as a convenient terminal for connecting the cable shield in a daisy-chain on the bus segment.
Grounding the Cable Shield on MS/TP Bus Segments
Inductive interference and Radio Frequency (RF) interference can adversely affect MS/TP applications, causing poor bus performance and frequent device offline occurrences. Experience has shown that installing properly grounded shielded cable in MS/TP applications greatly reduces the impact of ambient inductive noise and RF interference. Applications installed without shielded cable are much less tolerant to ambient interference.
We recommended installing MS/TP bus applications using shielded cable. In applications using shielded cable, it is very important to ensure you ground the cable shield properly. Improper shield grounding can also result in poor bus performance and frequent device offline occurrences.
Figure 81: FC Bus and SA Bus Terminal Block Wiring Details
22 AWG Stranded, 4-Wire (2 Twisted Pair) Shielded Cable(One is and . The second pair is COM and SA PWR.) + -
To Next Deviceon the SA Bus
To Next Deviceon the SA Bus
+ CO
MSA
PW
R
FIG
_FC&
SA_T
ERM
SA BusTerminal
Block
+ _ CO
MSH
LD
22 AWG Stranded, 3-Wire Twisted, Shield Cable
Isolated ShieldConnection
Terminal
To Next Deviceon the FC Bus
To Next Deviceon the FC Bus
FC BusTerminal
Block
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 115
To properly ground the cable shield on an MS/TP application, the cable shields on each bus segment must be connected in a daisy-chain as shown in (Figure 81). Each daisy-chained segment must be connected at only one point to a hard ground connection. We recommend making the hard ground connection within the first 2 inches of the cable terminations at the bus supervisor (the NAE on an FC Bus, and the FEC or VMA on the SA Bus). SA Bus Wiring
Guidelines
The SA Bus can connected using either a 4-wire (2-twisted pair) cable to the SA Bus (screw) terminal block or 6-wire cables with RJ-style modular jacks.
SA Bus Screw Terminations
The SA bus is a (2 twisted pair) shielded cable. The + and - leads makeup one twisted pair and the SA PWR and COM leads makeup the second twisted pair.
• Wire the SA Bus devices in a daisy-chain network configuration. Maintain polarity (SA+ to SA+, SA- to SA-, COM to COM, and SA PWR to SA PWR) along entire bus daisy-chain.
• Twist the SA bus leads together before inserting into the termination and ensure that the termination is tight at each terminal block on the daisy-chain.
• Each SA Bus must have only one hard ground connection to the cable shield.
• The single hard ground connection should be made at the bus supervisor where the SA Bus originates and should be made within one inch of entering an enclosure.
• All shield connections on the SA Bus must be isolated from ground and connected in continuous segment along the SA Bus.
Note: The SA Bus terminal blocks do not provide an isolated terminal for making cable shield connections. Use a small wirenut or other suitable connector to daisy-chain and isolate the cable shield on the SA Bus (Figure 82).
• Isolate the cable shield at the end of the bus segment (opposite the controller).
IMPORTANT: Ensure that the cable shield is connected to hard ground at only one point on the bus segment and is completely isolated from hard ground at all other points on the bus segment. Multiple hard ground connections on a bus segment can create transient currents in the cable shield, which can result in poor bus performance and frequent device offline occurrences.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin116
SA Bus 6-Pin RJ-Style Modular Jack and CablesThe 6-pin modular jack SA Bus connection is a straight-through (not a crossover) connection and that uses a 6-wire connector cable (with 6-pin RJ-style modular jacks) to connect SA devices to network sensors and the VMA Balancing Sensor. On the 6-wire cable, two wires are used for network communication, two wires for network sensor power, and two wires supply 15 VDC (200 mA maximum) power to the devices connected to the sensor.
The Wireless Commissioning Converter is also connected (temporarily) to the SA Bus modular jack to commission the controller.
The cable connected to the SA Bus 6-pin modular jack can not exceed 30 m (100 ft). The SA Bus 6-pin modular jack supports only one device and no other SA device may be daisy-chained to the port.
Every MS/TP device (except the NAE55) has at least one 6-pin modular jack. Modular jacks on the network sensors allow you to connect a Wireless Commissioning Converter or VMA Balancing Sensor. Figure 83 shows the SA Bus modular jack pinouts.
IMPORTANT: Failure to adhere to the wiring details may cause your network sensor to function incorrectly. You will not be able to connect to the system using the Wireless Commissioning Converter, the Handheld VAV Balancing Sensor, nor will you be able to expand the system with future offerings.
Figure 82: SA Bus Terminal Block Wiring Details
+ CO
MSA
PW
R22 AWG Stranded, 4-Wire (2 Twisted Pair) Shielded Cable(One is and . The second pair is COM and SA PWR.) + -
To Next Deviceon the SA Bus
To Next Deviceon the SA Bus
FIG
_SA
_TER
M
SA BusTerminalBlock
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 117
Figure 83: SA Bus 6-Pin Modular Jack Pinout Details
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin118
Commissioning Devices on the MS/TP BusCommission the devices on the MS/TP Bus using the Controller Configuration Tool (CCT) software.
Applications and device configurations are downloaded to the hardware from the CCT computer using the Wireless Commissioning Converter or through the NAE from the User Interface (UI).
Hardware points can be auto discovered from the online UI of the NAE, the Application and Data Server (ADS), or the Extended Application and Data Server (ADX).
NU-RPT101-0U RS-485-to-RS-485 RepeaterInstall the repeater inside a UL Listed enclosure (see Enclosures and Accessories). The repeater provides isolation on the FC Bus end of a smoke control system. Input and output wiring is supervised and power-limited. The repeater has non-power-limited wiring for the input power source.
The NU-RPT101-0U repeater serves two purposes:
1. Isolate Smoke Control equipment from Non-Smoke Control equipment.
2. Extend the physical length of the FC Bus on a single Smoke Control FC Bus.
Figure 84: NU-RPT101-1U RS-485-to-RS-485 Repeater
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 119
Setting EOL for the RepeaterFigure 85 show the EOL jumper locations for the NU-RPT101-1U repeater. Table 28 shows the EOL jumper settings.
Table 28: EOL Setting for RepeaterSide Jumper If Repeater:
Side A J1 and J2 At end-of-line, install both jumpers over Pins 1 and 2 (EOL In).
Not at end-of-line, install both jumpers over Pins 2 and 3 (EOL Out).
Side B J3 and J4 At end-of-line, install both jumpers over Pins 1 and 2 (EOL In).
Not at end-of-line, install both jumpers over Pins 2 and 3 (EOL Out).
Figure 85: NU-RPT101-1U RS-485-to-RS-485 Repeater EOL Termination
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin120
Wiring
Transient Protection
Install tranzorbs on the NU-RPT101-1U on both terminal blocks TB1 and TB2. The tranzorbs must be from tranzorb kit SMOKE-TRNKIT-1, which must be ordered separately. See SMOKE-TRNKIT-1U Tranzorbs on page 123 for more information.
Note: Two SMOKE-TRNKIT-1 tranzorbs are required (one for TB1 and one for TB2) to protect the NU-RPT101-1U repeater.
Install the SMOKE-TRNKIT-1 tranzorbs to terminal blocks TB1 and TB2 using the following procedure(Figure 86):
1. Starting with TB1 (Far Side), strip the FC bus wiring to 0.5 inches.
2. Twist the single wire side of the first tranzorb to the FC COM Far Side wire.
3. Attach the twisted FC COM wires to the TB1 COM terminal.
4. Twist the FC+ Far Side bus wire together with one wire from 2-wire end of the first tranzorb.
5. Attach the twisted wires to the TB1 D+ terminal.
6. Twist the FC- Far Side bus wire together with the remaining 2-wire wire from the first tranzorb.
7. Attach the twisted wires to the TB1 D- terminal.
8. Repeat the process for TB2 (Near Side).
Note: The SMOKE-TRNKIT-1 tranzorb has no polarity. FC Bus wire colors may vary from this example.
Figure 86: NU-RPT101-1U FC Field and SMOKE-TRNKIT-1U Tranzorb
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 121
Specifications
Table 29: Physical SpecificationsCategory SpecificationsOperating Temp. Range 0 to 49° C (32 to 120° F)
Relative Humidity (RH) 10 to 93% RH, Noncondensing
Power 120VAC, 60 Hz, 0.2A
Power Line Fuse 0.5A, 250V, 3AG type
Power Wire AWG 2 to 18 AWG (without terminal lugs); 14 to 18 AWG (with terminal lugs)
Power Wire Length Less than 32 feet (10 meters) length
Isolation The network repeater provides galvanic and opto-coupler isolation between RS-485(A), RS-485(B), AC power, and chassis ground. Common mode voltages are permitted up to 250V rms or 354V DC (withstands a 1500V AC dielectric strength test for 1 min. without breakdown) on a continuous basis. Complies with test requirements outlined in ANSI C39.5-1974 for voltage ratings specified.
RFI Resistance Withstands an RFI field strength of 10V per meter at 27 Mhz, 151 Mhz, and 467 Mhz with no digital effect, per SAMA PMC 33.1 test procedures.
Line Noise Effects Field and power line terminals withstand ANSI/IEEE C37.90-1978 Surge Withstanding Capability (SWC) Test with no component failures.Unit is tested to a standardized test waveform that is representative of surges (high-freq. transient electrical interference), observed in actual installations.
Communications Connections
Network repeater - both RS-485 conn. use modular terminal blocks with screw clamps. Wire range 14 to 26 AWG, CSA approval.
Power Wire Connections
Network repeater term. block.
Approvals UL Listed, CSA Certified file LR25710.
Dimensions (L x W x D) 7 x 4.3 x 2.1 in (17.8 x 10.3 x 5.3 cm)
Weight 3.0 pounds (1.4 kg) packed per unit.
Table 30: Communication SpecificationsCategory SpecificationsBaud Rates Switch settings on unit for 600, 1200, 2400, 4800, 9600, 19.2K, 38.4K, and 76.8K baud
rates. Switch must be in the proper baud rate position for proper operation.
RS-485 Bus Loading One unit load equivalent.
RS-485 Bus Drive Complete RS-485 compliance for up to 32 unit loads (31 unit loads if a repeater is used).
End-of-Line Termination Network
The EOLN termination network is enabled for the A side or B side when the associated pair of jumpers are positioned over pins 1 and 2. Conversely, the EOLN is disabled (out of the circuit) when the pair jumpers are positioned over pins 2 and 3.The EOLN termination network is individually selected on both the A and B sides by a pair of shorting clips. The A-side is controlled by jumper pair J1, J2 and the B-side is controlled by jumper pair J3 and J4
Duplex Half-duplex only
Data Format Ten bits typical (1 start bit, 8 data bits, and 1 stop bit). Other formats are supported.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin122
UL Label PlacementUL Listing labels must be positioned as shown in Figure 87.
Figure 87: Acromag Repeater UL Label Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 123
SMOKE-TRNKIT-1U Tranzorbs The SMOKE-TRNKIT-1U is a kit containing 1 transient suppressor (Figure 88). The SMOKE-TRNKIT-1U is UL Listed for Smoke Control and Energy Management equipment. The NU-RPT101-1U Repeater requires these tranzorbs on TB1 and TB2.
Table 31: SMOKE-TRNKIT-1U SpecificationsCategory Specifications
Breakdown Voltage (V(BR) AT IT)1 7.22 V Minimum7.98 V Maximum
Test Current (IT) 10 mA
Standoff Voltage (VWM) 6.5 V
Maximum Reverse Leakage (AT VWM ID) 400 µA
Maximum Peak Pulse Current (IPPM) 44.7 A
Maximum Clamping Voltage (AT IPPM VC) 11.2 V
Maximum Temperature Coefficient (OF V(BR)) 5.0 mV/°C
1. Pulse Test: tp 50 ms
Figure 88: SMOKE-TRNKIT-1U and a Single Tranzorb
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin124
MS/TP Controllers
FEU16x0 and FEU26x0 Field Equipment ControllersThe FEU16x0 and FEU26x0 controllers are members of the Metasys® system Field Equipment Controller (FEC) family. They are designed to run a variety of pre-engineered Heating, Ventilation, and Air Conditioning (HVAC) applications and provide the inputs/outputs required for these applications.
The MS-FEU2610-0U controller consists of two parts which are the mounting base (MS-FEB2610-0) and the controller cover (MS-FEC2610-0).
The MS-FEU2620-0U controller consists of two parts which are the mounting base (MS-FEB2620-0) and the controller cover (MS-FEC2620-0).)
IMPORTANT: Any FEU1620 or FEU2620 controller used for smoke control must be locked in an enclosure to prevent unauthorized access.
IMPORTANT: Do not use the buttons on the face of the FEU1620 or FEU2620 controller to override smoke control points.
Figure 89: FEU1610 FEU2610
Figure 90: FEU1620 FEU2620
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 125
MountingThe mounting base may be mounted without the controller cover. If you mount the mounting base without the controller cover, ensure that there is sufficient clearance to allow later mounting of the controller cover.
Follow these guidelines when mounting all FEC controller models listed above:
• Ensure that the mounting surface can support the FEC controller and any user-supplied enclosure.
• Mount the FEC controller in the proper orientation. See Figure 91.
• Mount the FEC controller on an even surface whenever possible.
• Use shims or washers to mount the unit securely on the mounting surface.
• Mount the FEC controller in areas free of corrosive vapors and observe the environmental limitations listed in the Technical Specifications section.
• Do not mount the FEC controller on surfaces that are prone to vibration, such as duct work, or in areas where electromagnetic emissions from other devices or wiring can interfere with FEC controller communication.
• Allow sufficient space for cable and wire connections (minimum of 50 mm [2 inches] in each direction).
• On panel or enclosure mount applications, observe the following guidelines:
• Do not install the FEC controller in an airtight enclosure.
• Mount the FEC controller so that the enclosure wall or the transformer does not obstruct ventilation of or radiate heat into the FEC controller housing.
Mounting Orientation
Common FEC Configuration DetailsUse the following information links to configure all Smoke Control FEC models.
Determining the FC Bus Address
See Device Addresses on the MS/TP Bus on page 86 for detailed information.
Setting the FC Bus Address
See Setting a Device Address on page 87 for detailed information.
Figure 91: Orientation for Wall Mount (left) and DIN Rail (right) Installations
RET SY
ON
ADDRESS
ADDRESS Ø = ALL OFF
SA BUS
FAULT
POWER
CO
M
HOT
COM
+ – SHLD
SA BUS
SENSOR COM
+ – SA PWR
OUT
4
OCO
M 4
OUT
5
OCO
M 5
OUT
6
OCO
M 6
OUT
7
OCO
M 7
OUT
2
OCO
M 2
OUT
1
OC
OM
1
OUT
3
OCO
M 3
BINARY
IN3
ICO
M3
UNIVERSAL
+15V
IN1
ICO
M1
IN2
ICO
M2
FC
EOL
ON
RET
SY
ON
ADD
RESS
ADDRES
SØ
=ALL
OFF
SA BUS
FAULT
POW
ER
COM
HOT
COM
+
–
SHLD
SABU
S
SENSO
R
COM
+–
SAPWR
OUT 4
OCOM 4
OUT 5
OCOM 5
OUT 6
OCOM 6
OUT 7
OCOM 7
OUT 2
OCOM 2
OUT 1
OCOM 1
OUT 3
OCOM 3BINAR
Y
IN3
ICOM3
UNIVE
RSAL
+15V
IN1
ICOM1
IN2ICOM
2
FC
EOL
ON
Wal
l Mou
nt.c
dr
RET SY
ON
ADDRESS
ADDRESS Ø = ALL OFF
SA BUS
FAULT
POWER
CO
M
HO
T
CO
M
+ – SHLD
SA BUS
SENSOR CO
M
+ – SA PWR
OU
T 4
OCO
M 4
OU
T 5
OC
OM
5
OU
T 6
OCO
M 6
OU
T 7
OC
OM
7
OU
T 2
OC
OM
2
OU
T 1
OC
OM
1
OU
T 3
OCO
M 3
BINARY
IN3
ICO
M3
UNIVERSAL
+15V
IN1
ICO
M1
IN2
ICO
M2
FC
EOL
ON
DIN
Rai
l.cdr
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin126
FC Bus End-of-Line Switch
See End-of-Line Termination on the MS/TP Bus on page 95 for detailed information.
WiringTo wire all FEC controller models:
1. Terminate wiring per engineering drawings.
2. Wire Network Sensors and other devices to the SA Bus or RJ-45 modular jack for sensors. See Figure 92 (FEC1610/FEC1620) and Figure 94 (FEC2610/2620).
3. Wire the FC Bus in a daisy chain to other devices on the FC Bus and the supervisory controller.
4. Wire the SA Bus in a daisy chain.
Note: The FEC controller should be at one end of the SA Bus daisy chain. If multiple Input/Output Modules (IOMs) are used, set the End-of-Line (EOL) switch on the last IOM.
5. Ensure the device address DIP switches are set to the appropriate address (in the range of 4-127).
6. Add SMOKE-MOVKIT-MSTP transient protector kits to all FC and SA Bus communication terminal block connections. See MS/TP SA Bus Network Sensors on page 167 for details.
7. Add SMOKE-MOVKIT-0 transient protectors to all MS/TP I/O terminal connections. See MOV Requirements for MS/TP I/O Terminals on page 94 for details.
8. Connect power to the FEC controller.
9. Download and commission the FEU1610/2610 controller. See the Commissioning section.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 127
Figure 92: FEU1610/1620 Wiring Interface
RET SY
ON
ADDRESS
ADDRESS Ø = ALL OFF
SA BUS
FAULT
POWER
CO
M
HO
T
CO
M
+ – SH
LD
SA BUS
SENSOR CO
M
+ – SA
PW
R
OU
T 4
OC
OM
4
OU
T 5
OC
OM
5
OU
T 6
OC
OM
6
OU
T 7
OC
OM
7
OU
T 2
OC
OM
2
OU
T 1
OC
OM
1
OU
T 3
OC
OM
3
BINARY
IN3
ICO
M3
UNIVERSAL
+15V
IN1
ICO
M1
IN2
ICO
M2
FC
EOL
ON
Status LEDs
FC BusAddress
DIPSwitches
EOLSwitch
UniversalInputs
BinaryInputs
SA Bus FC Bus
BinaryOutputs
ConfigurableOutputs
24 VACPower Terminal
FEC
1610
_cvr
.cdr
RJ-45 Modular Jack for Sensor
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin128
Terminal Type Terminal ConnectionRequired MOV ProtectionUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Input IN3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Input ICOM3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 93: MS-FEU-1610-0U and MS-FEU-2610-0U I/O MOV Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 129
Figure 94: FEU2610/2620 Wiring Interface
RET SY
SA BUS
FAULT
POWER
ON ADDRESS
ADDRESS Ø = ALL OFF
CO
M
HO
T
CO
M
+ – SHLD
OU
T 4
OC
OM
4
OU
T 5
OC
OM
5
OU
T 6
OC
OM
6
OU
T 7
OC
OM
7
OU
T 2
OC
OM
2
OU
T 1
OC
OM
1
OU
T 3
OC
OM
3
SA BUS
STAT CO
M
+ – 15V
OU
T 8
OC
OM
8
OU
T 9
OC
OM
9
UNIVERSAL
+15V
IN1
ICO
M1
IN2
ICO
M2
+15V
IN3
ICO
M3
IN4
ICO
M4
+15V
IN5
ICO
M5
IN6
ICO
M6
IN7
ICO
M7
IN8
ICO
M8
BINARY
EOL
ON
StatusLEDs
DeviceAddress
DIPSwitches
EOLSwitch
BinaryOutputs
ConfigurableOutputs
AnalogOutputs
24 VACPower Terminal
UniversalInputs Binary
Inputs FC BusTerminals
FC BusPort
SA BusTerminals FE
C26
10_c
vr.c
dr
RJ-45 Modular Jack
for Sensor
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin130
Terminal Type Terminal ConnectionRequired MOV ProtectionUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Input IN7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Input ICOM7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Input IN7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Input ICOM7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output OUT8 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output OCOM8 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output OUT9 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output OCOM9 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 95: MS-FEU-1620-0U and MS-FEU-2620-0U I/O MOV Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 131
Table 32: FEUx610 and FEUx620 Field Controller Platform Wiring List (Part 1 of 2)Terminal Block Terminal
LabelsFunction and Electrical Ratings/Requirements
Wiring Requirements(See Table 33 on page 133)
Universal IN +15V Sources 15 VDC power for active devices35 mA total current
Same as IN, 5
IN n Analog Input, Voltage ModeAccepts a 0-10 VDC input signal10 VDC Maximum Input VoltageInternal 75k ohm Pulldown
A3, 5
Analog Input, Current ModeAccepts a 4-20 mA input signalInternal 100 ohm load Impedance
B3, 5
Analog Input, Resistive ModeAccepts 0-600k ohm input signalInternal 12 V, 15k ohm PullupRTD (1k Nickel [Johnson Controls], 1k Platinum, A99BSilicon Temperature Sensor)Negative Temperature Coefficient (NTC) Sensor (10k Type L, 2.252k Type 2)
A3, 5
Binary Input, Dry Contact Maintained Mode1 s minimum pulse width (0.5 Hz at 50% duty cycle)Internal 12 V, 15k ohm Pullup
A3, 5
ICOM n The input signal common for Universal IN terminals; isolated from all other terminal commons
Same as IN
Binary IN IN n Binary Input, Dry Contact Maintained Mode0.01 second minimum pulse width (50 Hz at 50% duty cycle)Internal 12 V, 15k ohm Pullup
A3, 5
Binary Input, Pulse Counter Mode0.01 second minimum pulse width (50 Hz at 50% duty cycle)Internal 12 V, 15k ohm Pullup
ICOM n The signal common for all Binary IN terminals; isolated from all other terminal commons
Analog OUTNote: (FEC2610 and
FEC2620 only)
OUT n Analog Output, Voltage ModeSources 0-10 VDC output voltageExternal 1k ohm minimum load required10 VDC maximum output voltage10 mA maximum output current
A3, 5
Analog Output, Current ModeSources 4-20 mA output currentExternal 300 ohm maximum load required
B3, 5
OCOM n The output signal common for Analog OUT terminals; isolated from all other terminal commons
Same as OUT, 5
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin132
Binary OUT(Jumper set to External)
OUT n Binary Output, 24 VAC TriacConnects OUT to OCOM when activated30 VAC maximum output voltage0.5 A maximum output current40 mA minimum load current
C3, 5
OCOM n The output signal common for Binary OUT terminals; isolated from all other terminal commons, including BO terminal commons
Binary OUT(Jumper set to Internal)
OUT n Sources 24 VAC Power (Hot) C3, 5
OCOM n Binary Output, 24 VAC TriacConnects OCOM to 24 VAC Power (Com) when activated (low side switching)30 VAC maximum output voltage0.5 A maximum output current40 mA minimum load current
Configurable OUT OUT n Analog Output, Voltage ModeSources 0-10 VDCExternal 1k ohm minimum load required10 VDC maximum output voltage10 mA maximum output current
A3, 5
Binary Output, 24 VAC Triac modeConnects OUT to OCOM when activated30 VAC maximum output voltage0.5 A maximum output current40 mA minimum load current
C3, 5
OCOM n The output signal common; isolated from all other terminal commons
Same as OUT, 5
Sensor1,2 Sensor Provides SA Bus communication networkRJ-12 6-position modular connector
30.5 m (100 ft) max.length phone cord
SA Bus2,4 +-COM
Provides SA Bus communication network Daisy-chained366 m (1,200 ft) max. length0.6 mm to 1.5 mm2 (18 to 24 AWG)[22 AWG Recommended]
SA PWR Sources 15 VDC power for devices on the SA Bus
FC Bus2,4 +-COM
Provides FC Bus communication network Daisy-chained1,524 m (5,000 ft) max. length0.6 mm to 1.5 mm2 (18 to 24 AWG)[22 AWG Recommended]
SHLD Provides an optional shield connection
24~ Power Hot AC Supply Input - Nominal 24 VAC 16 AWG
COM The 24~ Power common; isolated from all other terminal commons
1. The SA Bus and the Sensor Port are daisy-chained internally.2. The SA Bus and FC Bus specifications in this table are for MS/TP bus communications at 38.4k. For more information,
refer to the MS/TP Field Bus on page 83 section in this document.3. See MS/TP Bus Cable Recommendations on page 111 for wire length specifications.4. Requires a SMK-MOVKIT-MSTP transient protector kit for all MS/TP communication terminal connections. See
SMK-MOVKIT-MSTP Wiring for MS/TP FC Bus Communication Terminations on page 90 and SMK-MOVKIT-MSTP Wiring for SA Bus Communication Terminations on page 92 for wiring details.
5. Requires SMOKE-MOVKIT-0 transient protectors for all MS/TP I/O terminal connections. See MOV Requirements for MS/TP I/O Terminals on page 94 for wiring details.
Table 32: FEUx610 and FEUx620 Field Controller Platform Wiring List (Part 2 of 2)Terminal Block Terminal
LabelsFunction and Electrical Ratings/Requirements
Wiring Requirements(See Table 33 on page 133)
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 133
Use Table 33 for all FEC wiring. Table 33: FEC Wire Gauge and Length GuidelinesGuideline Cable
Size (AWG)
Maximum Length (Ft)
Assumptions
A 18 1500 100 mV maximum voltage drop at maximum current
20 975
22 600
24 350
B 18 750 100 mV maximum voltage drop at maximum current
20 450
22 300
24 200
C 40 mA Load
18 400
20 250
22 150
24 100
500 mA Load
18 75
20 50
22 30
24 20
18 AWG (1.5 mm )2
20 AWG (0.8 mm )2
22 AWG (0.6 mm )2
24 AWG (N/A)
450 500400350300250200150100500
Load Current (mA)
0 ft (0 m)
50 ft (15.2 m)
100 ft (30.5 m)
150 ft (45.7 m)
200 ft (61 m)
250 ft (76.2 m)
300 ft (91.4 m)
350 ft (106.7 m)
400 ft (121.9 m)
450 ft (137.2 m)
Length
Load Current vs Wire Length
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin134
Setup and Adjustments
Setting the Binary Output INT/EXT Jumpers
The Binary Output jumpers (OUT1 through OUT3) are located on the circuit board in the mounting base near the binary outputs. These jumpers select whether the output provides internal power to the load (INT) or requires external power (EXT). See Figure 96.
When set to the INT position, the FEC controller is the power source for the Binary Output and both sides of the load can be wired directly to the OUTx and COMx terminals.
Setting the jumper to the EXT position isolates the Binary Outputs and power must come from one or more external sources. Do not wire the load directly to the OUTx and COMx terminals. Wire one side of the load to the source and the other side of the load to the OUTx terminal. Wire the other side of the external power source to the COMx terminal.
Setting the Analog Input Load Resistor Enable/Disable
The Analog Input Resistor Enable/Disable jumpers (J10 through J15) are located on the circuit board in the controller cover. These jumpers can permanently connect the internal 4-20 mA, 100 ohm load resistor to the input terminals. There is one jumper for each of the Universal Inputs. See Figure 97.
Software configuration of the Universal Input normally selects the enabling or disabling of the analog input load resistor. In cases when the analog input load resistor must be left connected even when power is OFF to the controller, set this jumper to the ENABLE position.
This jumper must be in the DISABLE position for all Universal Input modes other than 4-20 mA.
Figure 96: Binary Output Jumper Positions
Jumper
Pins
Jumper positioned on top two pins
Jumper positioned on bottom two pins
INT
EXT (Default)
Bina
ry O
UT_
Jum
pers
.cdr
Figure 97: Analog Input Resistor Jumper Positions
Jumper
Pins
Jumper positioned on top two pins
Jumper positioned on bottom two pins
ENABLE
DISABLE (Default)
Anal
og In
put_
Jum
pers
.cdr
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 135
CommissioningCommission the FEUx610 or FEUx620 controller through the NAE passthrough and FC communication bus and the Controller Configuration Tool (CCT) software.
Troubleshooting
Use Table 34 to troubleshoot the FEC controllers.Table 34: Status Light-Emitting Diodes (LEDs)Name Color Normal DescriptionsPower Green On Steady Off Steady = No Power
On Steady = Power is supplied by Primary Voltage.
Fault Red Off Steady Blink - 2 Hz = Download or Startup in progress, not ready for normal operationOff Steady = No FaultsOn Steady = Device Fault or no application loaded
FC Bus Green Blink - 2 Hz Blink - 2 Hz = Data Transmission (normal communication)Off Steady = No Data Transmission (auto baud in progress)On Steady = Communication lost, waiting to join communication ring
SA Bus Green Blink - 2 Hz Blink - 2 Hz = Data Transmission (normal communication)Off Steady = No Data Transmission (N/A - auto baud not supported)On Steady = Communication lost, waiting to join communication ring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin136
SpecificationsTable 35: FEUx6x0-0U Technical SpecificationsCategory SpecificationProduct Code Number MS-FEU1610-0U Cooling Only
MS-FEU2610-0 U Cooling with Reheat
MS-FEU1620-0U Cooling Only with Display
MS-FEU2620-0U Cooling with Reheat with Display
Supply Voltage 24 VAC, 60 Hz
Power Consumption 10 VA maximum plus all BO and Configurable Output loads
Ambient Operating Conditions
0 to 49°C (32 to 120°F) 10 to 93% RH non-condensing
Terminations 6.3 mm (1/4 in.) spade lugs except communications and 24 VAC power, which are screw terminals
Controller Addressing DIP switch set (4-127). Addresses 0 - 3, 128-255 are reserved.
Communications Bus BACnet MS/TP; 3-wire Field Controller Bus (FC Bus) between the Network Automation Engine (NAE) and other devices. 4-wireSensor-Actuator Bus (SA Bus) between network sensors and other devices.1
Mounting Mounts to damper shaft using single set screw and to duct with single mounting screw.
Actuator Rating 4 N·m (35 lb·in) minimum shaft length = 44 mm (1-3/4 in.)
Compliance UL Listed and CSA CertifiedUL 916 Energy Management Listing, CSA C22.2 No. 205, CFR47FCC Part 15 Class ACE Mark and C-Tick DirectiveCE Directive 89/336/EEC (EN50081-1 Class B, EN50082-2)
Dimensions Width: 182 mm (7-3/16 in.)Length: 182 mm (7-3/16 in.)Height: 64 mm (2-1/2 in.)Center of Output Hub to Center of Anti-rotation Slot: 160 mm (6-5/16 in.)
Housing Plastic housingPlastic material: ABS _ polycarbonate UL94-5VBProtection: IP20 (IEC 60529)
Weight 0.5 kg (1.1 lb) 0.68 kg (1.5 lb)
1.For more information, refer to the MS/TP Field Bus section in this document.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 137
UL Label PlacementUL Listing labels must be positioned as shown in Figure 98.
Figure 98: UL Label Placement for the MS-FEU1610-0U and MS-FEU2610-0U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin138
UL Listing labels must be positioned as shown in Figure 99.
Figure 99: UL Label Placement for the MS-FEU1620-0U and MS-FEU2620-0U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 139
IOMx710 Field Equipment ControllersThe Input Output Modules (IOMs) IOM1710, IOM2710, IOM3710, and IOM4710 are members of the Metasys® system Field Equipment Controller family. The IOM provides increased capacity to larger Field Equipment Controller (FEC) applications when used on the Sensor Actuator (SA) bus. The IOM can also be used on the Field Controller (FC) bus to connect additional physical points to the system.
Mounting
Follow the guidelines below when mounting an IOM controller:
• Ensure that the mounting surface can support the IOM controller and any user-supplied enclosure.
• Mount the IOM controller in the proper orientation. See Figure 102.
• Mount the IOM controller on an even surface whenever possible.
• Use shims or washers to mount the unit securely on the mounting surface.
• Mount the IOM controller in areas free of corrosive vapors and observe the environmental limitations listed in the Technical Specifications section.
Figure 100: IOM1710 IOM2710
Figure 101: IOM3710 IOM4710
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin140
• Do not mount the IOM controller on surfaces that are prone to vibration, such as duct work, or in areas where electromagnetic emissions from other devices or wiring can interfere with IOM controller communication.
• Allow sufficient space for cable and wire connections (minimum of 2 inches in each direction).
On panel or enclosure mount applications, observe the guidelines below:
• Do not install the IOM controller in an airtight enclosure.
Mount the IOM controller so that the enclosure wall or the transformer does not obstruct ventilation of or radiate heat into the IOM controller housing.
Wall Mount Applications
Use the holes in the two mounting clips for wall mount applications.
To mount the IOM on a wall or other vertical surface:
1. Ensure the two mounting clips are pulled outward and snapped firmly into the extended position.
2. Mark the location of the two wall mount holes using the supplied dimensions or hold the IOM up to the wall as a template and mark the locations.
Note: Mount the IOM horizontally for proper air flow (Figure 102).
3. Drill holes in the wall at the locations marked in Step 2 and insert wall anchors (if necessary).
4. Position the IOM and insert the screws through the holes in the mounting clips, and carefully tighten all the screws.
Common IOM Configuration DetailsUse the following information links to configure all IOM models.
Determining the FC Bus Address
See Device Addresses on the MS/TP Bus on page 86 for detailed information.
Setting the FC Bus Address
See Setting a Device Address on page 87 for detailed information.
FC Bus End-of-Line Switch
See End-of-Line Termination on the MS/TP Bus on page 95 for detailed information.
Figure 102: Required Orientation for Wall Mount Applications
RET SY
FAULT
POWER
ADDRESSON
IN 1
ICO
M 1
IN 2
ICO
M 2
IN 3
ICO
M 3
IN 4
ICO
M 4
BINARY INPUTS
CO
M+ – SH
LD
+ – CO
M
PW
R
CO
M
HO
T
ADDRESS Ø = ALL OFF EOLON
RET SY
FAULT
POWER
ADDRESSON
+15V
+5V
IN 1
ICO
M 1
IN 2
ICO
M 2
+15V
+5V
IN 3
ICO
M 3
IN 4
ICO
M 4
UNIVERSAL
CO
M
+ –
+ – CO
MSA PW
R
CO
M
HO
T
OU
T 7
OC
OM
7O
UT
8O
CO
M 8
OU
T 5
OC
OM
5O
UT
6O
CO
M 6
OU
T 4
NO
OC
OM
4O
UT
4 N
C
OU
T 3
NO
OC
OM
3O
UT
3 N
C
OU
T 2
NO
OC
OM
2O
UT
2 N
C
OU
T 1
NO
OC
OM
1O
UT
1 N
C
ADDRESS Ø = ALL OFFEOL
ON
RET SY
ON
ADDRESS
ADDRESS Ø = ALL OFF
SA BUS
FAULT
POWER
CO
M
HO
T
CO
M
+ – SH
LD
SA BUS
SENSOR CO
M
+ – SA
PW
R
OU
T 4
OC
OM
4
OU
T 5
OC
OM
5
OU
T 6
OC
OM
6
OU
T 7
OC
OM
7
OU
T 2
OC
OM
2
OU
T 1
OC
OM
1
OU
T 3
OC
OM
3
BINARY
IN3
ICO
M3
UNIVERSAL
+15V
IN1
ICO
M1
IN2
ICO
M2
FC
EOL
ON
RET
SY
ON
AD
DR
ES
S
ADD
RES
SØ
=A
LLO
FF
SA
BU
S
FAU
LT
PO
WER
COM
HOT
COM
+
–
SHLD
SAB
US
SEN
SOR
COM
+
–
SAPWR
OUT 4
OCOM 4
OUT 5
OCOM 5
OUT 6
OCOM 6
OUT 7
OCOM 7
OUT 2
OCOM 2
OUT 1
OCOM 1
OUT 3
OCOM 3BIN
ARY
IN3
ICOM3
UN
IVE
RSA
L
+15V
IN1
ICOM1
IN2ICOM
2
FC
EOL
ON
Wal
l Mou
nt.c
dr
IOM1710 IOM2710 and IOM3710 IOM4710
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 141
Commissioning the IOM
Commission all Smoke Control IOM models through the NAE passthrough and FC communication bus and the Controller Configuration Tool (CCT) software.
Wiring
General Wiring Precautions
IMPORTANT: Do not connect 24 VAC supply power to the Network Automation Engine (NAE) before finishing wiring and checking all wiring connections. Short circuits or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: User copper conductors only. Make all wiring in accordance with local, national, and regional regulations. The IOM is a low-voltage (<30 VAC) device. Do not exceed the IOM electrical ratings.
IMPORTANT: Prevent any static electric discharge to the IOM. Static electric discharge can damage the IOM and void any warranties.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin142
IOM Wire Gauge and Length Guidelines
Use Table 36 for all IOM wiring.
Wiring the IOM1710To wire the IOM1710:
1. Terminate wiring per engineering drawings.
2. Wire Network Sensors and other devices to the SA Bus or Sensor socket.
3. Ensure the device address DIP switches are set to the appropriate hardware address (in the range of 4-127).
4. Add SMK-MOVKIT-MSTP transient protector kits to all FC and SA Bus communication terminal block connections. See MS/TP SA Bus Network Sensors on page 167 for details.
5. Add SMOKE-MOVKIT-0 transient protectors to all MS/TP I/O terminal connections. See MOV Requirements for MS/TP I/O Terminals on page 94 for details.
6. Connect power to the IOM.
7. Download and commission the IOM.
Table 36: IOM Wire Gauge and Length GuidelinesGuideline Cable Size (AWG) Maximum
Length (Ft)Assumptions
A 18 1500 100 mV maximum voltage drop at maximum current
20 975
22 600
24 350
B 18 750 100 mV maximum voltage drop at maximum current
20 450
22 300
24 200
C 40 mA Load
18 400
20 250
22 150
24 100
500 mA Load
18 75
20 50
22 30
24 20
18 AWG (1.5 mm )2
20 AWG (0.8 mm )2
22 AWG (0.6 mm )2
24 AWG (N/A)
450 500400350300250200150100500
Load Current (mA)
0 ft (0 m)
50 ft (15.2 m)
100 ft (30.5 m)
150 ft (45.7 m)
200 ft (61 m)
250 ft (76.2 m)
300 ft (91.4 m)
350 ft (106.7 m)
400 ft (121.9 m)
450 ft (137.2 m)
Length
Wiri
ng le
ngth
.cdr
Load Current vs Wire Length
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 143
Figure 103: IOM1710 Wiring Interface Showing Dimensions (mm/in.), and Physical Features
108.0(4.25)
HO
T
CO
M
RET SY
FAULT
POWER
ADDRESSON
IN 1
ICO
M 1
IN 2
ICO
M 2
IN 3
ICO
M 3
IN 4
ICO
M 4
BINARY INPUTSC
OM+ – S
HLD
+ – CO
M
PWR
CO
M
HO
T
ADDRESS Ø = ALL OFF EOLON
BinaryInputs
MountingClip
EOLSwitch
Device AddressDIP Switches
SA BUSFC BUS
24 VACPower TerminalMounting
Clip
StatusLEDs
SA/FC BusPort
Terminal Type Terminal ConnectionRequired MOV ProtectionUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input +5V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 1 NO 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OCOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 1 NC 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 2 NO 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OCOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 2 NC 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OUT3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OCOM3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OUT4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OCOM4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 104: MS-IOM1710-0U I/O MOV Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin144
IOM1710 Field Controller Platform Wiring List
Troubleshooting
Use Table 38 to troubleshoot the IOM1710 module.
Table 37: IOM1710 Field Controller Platform Wiring ListTerminal Block
Terminal Labels
Function and Electrical Ratings/Requirements Wiring Requirements(see Table 36 on page 142)
Binary IN IN n Dry Contact Maintained Mode0.01 s minimum pulse width (50 Hz at 50% duty cycle)Internal 12 V, 15k ohm Pull-up
A4
Pulse Counter Mode0.01 s minimum pulse width (50 Hz at 50% duty cycle)Internal 12 V, 15k ohm Pull-up
ICOM n The signal common for all Binary IN terminals; isolated from all other terminal commons
SA Bus1, 3
1. The SA Bus and FC Bus specifications in this table are for MS/TP bus communications at 38.4K. For more information, see MS/TP Bus Cable Recommendations on page 111.
2. Requires a SMK-MOVKIT-MSTP transient protector kit for all MS/TP communication terminal connections. See SMK-MOVKIT-MSTP Wiring for MS/TP FC Bus Communication Terminations on page 90 for wiring details.
3. Requires a SMK-MOVKIT-MSTP transient protector kit for all MS/TP communication terminal connections. See SMK-MOVKIT-MSTP Wiring for SA Bus Communication Terminations on page 92 for details.
4. Requires SMOKE-MOVKIT-0 transient protectors for all MS/TP I/O terminal connections. See MOV Requirements for MS/TP I/O Terminals on page 94 for wiring details.
+-COM
Provides SA Bus communication network. Daisy-chained366 m (1,200 ft) maximum length0.6 mm to 1.5 mm2 (18 to 24 AWG)(22 AWG Recommended)
SA PWR Sources 15 VDC power for devices on the SA Bus.
FC Bus1, 2 +-COM
Provides FC Bus communication network. Daisy-chained1,524 m (5,000 ft) maximum length0.6 mm to 1.5 mm2 (18 to 24 AWG)[22 AWG Recommended]
SHLD Provides an optional shield connection.
24~ Power Hot AC Supply Input, Nominal 24 VAC 16 AWG
COM The 24~ Power common; isolated from all other terminal commons
Table 38: IOM1710 LED IndicatorsName Color Normal DescriptionsPower Green On Steady On Steady = Power is Supplied by Primary Voltage.
Off = No Power
Fault Red Off Off Steady = No FaultsOn Steady = Device FaultFlicker = Download or startup in progress and not ready for normal operation
SA Bus/FC Bus Green Flicker Flicker = Normal CommunicationOff Steady = Auto baud in progress (Not applicable for SA Bus)On Steady = Communication lost
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 145
Wiring the IOM2710 and IOM3710To wire the IOM2710 or IOM3710:
1. Terminate wiring per engineering drawings.
2. Wire Network Sensors and other devices to the SA Bus or Sensor socket.
3. Ensure the device address DIP switches are set to the appropriate hardware address (in the range of 4-127).
4. Connect power to the IOM.
5. Download and commission the IOM.
Figure 105: IOM2710 Wiring Interface Showing Dimensions (mm/in.), and Physical Features
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin146
Terminal Type Terminal ConnectionRequired MOV ProtectionUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input +5V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 1 NO 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OCOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 1 NC 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 2 NO 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OCOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 2 NC 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OUT3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OCOM3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OUT4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OCOM4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 106: MS-IOM2710-0U I/O MOV Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 147
Figure 107: IOM3710 Wiring Interface Showing Dimensions (mm/in.), and Physical Features
58.02.28
127.55.02
180.07.09
RET SYFAULT
POWER
ADDRESSON
+15V
+5V
IN 1
ICO
M 1
IN 2
ICO
M 2
+15V
+5V
IN 3
ICO
M 3
IN 4
ICO
M 4
UNIVERSAL
CO
M
+ –+ – CO
MS
AP
WR
CO
M
HO
T
OU
T 7
OC
OM
7O
UT
8O
CO
M 8
OU
T 5
OC
OM
5O
UT
6O
CO
M 6
OU
T 4
NO
OC
OM
4O
UT
4 N
C
OU
T 3
NO
OC
OM
3O
UT
3 N
C
OU
T 2
NO
OC
OM
2O
UT
2 N
C
OU
T 1
NO
OC
OM
1O
UT
1 N
C
ADDRESS Ø = ALL OFF
CO
M
HO
T
O7
OC
7
O8
OC
8
O5
OC
5
O6
OC
6
NO
4
OC
4
NC
4
NO
3
OC
3
NC
3
NO
2
OC
2
NC
2
NO
1
OC
1
NC
1
EOLON
SA/FC BusTerminals
Mounting Clip
481.92
97.53.77
903.5
47.91.88
47.91.88
Status LEDs
58.02.28
127.55.02
180.07.09
RET SYFAULT
POWER
ADDRESSON
+15V
+5V
IN 1
ICO
M 1
IN 2
ICO
M 2
+15V
+5V
IN 3
ICO
M 3
IN 4
ICO
M 4
UNIVERSAL
CO
M
+ –+ – CO
MS
AP
WR
CO
M
HO
T
OU
T 7
OC
OM
7O
UT
8O
CO
M 8
OU
T 5
OC
OM
5O
UT
6O
CO
M 6
OU
T 4
NO
OC
OM
4O
UT
4 N
C
OU
T 3
NO
OC
OM
3O
UT
3 N
C
OU
T 2
NO
OC
OM
2O
UT
2 N
C
OU
T 1
NO
OC
OM
1O
UT
1 N
C
ADDRESS Ø = ALL OFF
CO
M
HO
T
O7
OC
7
O8
OC
8
O5
OC
5
O6
OC
6
NO
4
OC
4
NC
4
NO
3
OC
3
NC
3
NO
2
OC
2
NC
2
NO
1
OC
1
NC
1
EOLON
SA/FC BusPort
EOL Switch
Universal Inputs
Universal Outputs
24 VACPower Terminal
Device AddressDIP Switches
481.92
97.53.77
903.5
47.91.88
47.91.88
Relay Outputs
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin148
Terminal Type Terminal ConnectionRequired MOV ProtectionUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input +5V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input +5V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 1 NO 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OCOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 1 NC 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 2 NO 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OCOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 2 NC 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 3 NO 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OCOM3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 3 NC 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 4 NO 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OCOM4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundRelay Output OUT 4 NC 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OUT5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OCOM5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OUT6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OCOM6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OUT7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OCOM7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OUT8 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Output OCOM8 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 108: MS-3710-0U I/O MOV Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 149
IOM2710 and IOM3710 Field Controller Platform Wiring ListTable 39: IOM2710 and IOM3710 Field Controller Platform Wiring List (Part 1 of 2)Terminal Block1
Terminal Labels
Function and Electrical Ratings/Requirements Wiring Requirements (see Table 36 on page 142)
Universal IN +5V Sources 5 VDC power for active devices60 mA total current
Same as IN 4
+15V Sources 15 VDC power for active devices35 mA total current
Same as IN 4
IN n Analog Input, Voltage ModeAccepts a 0-10 VDC input signal10 VDC Maximum Input VoltageInternal 75k ohm Pull-down
A 4
Analog Input, Current ModeAccepts a 4-20 mA input signalInternal 100 ohm load Impedance
B 4
Analog Input, Resistive ModeAccepts 0-600K Ohm input signalInternal 12 V, 15k ohm Pull-up
A 4
Binary Input, Dry Contact Maintained Mode1 sec minimum pulse width (0.5 Hz at 50% duty cycle)Internal 12 V, 15k ohm Pull-up
A 4
Binary Input, Dry Contact Pulse Counter Mode1 sec minimum pulse width (0.5 Hz at 50% duty cycle)Internal 12 V, 15k ohm Pull-up
A 4
ICOM n The input signal common for Universal IN terminals; isolated from all other terminal commons
Same as IN 4
Universal OUT
OUT n Analog Output, Voltage ModeSources 0-10 VDC output voltage1K Ohm minimum load10 VDC maximum output voltage10 mA maximum output current
A 4
Binary Output Mode24 V AC/DC FETConnects OUT to OCOM when activated30 V AC/DC maximum output voltage0.5 A maximum output current40 mA minimum load current (hold current)
B 4
Analog Output, Current ModeSources 4-20 mA output currentExternal 300 Ohm maximum load required
B 4
OCOM n The output signal common; isolated from all other terminal commons, including UO terminal commons
Same as OUT 4
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin150
Troubleshooting
Use Table 40 to troubleshoot the IOM2710 and IOM3710 modules.
Relay Output Control
OUT NO n Normally Open ContactConnects OCOM to OUT NO when activated240 VAC maximum voltage1/3 Hp 125 VAC, 1/2 hp 250 VAC
OCOM n The relay signal common; isolated from other terminal commons, including Relay Output terminal commons
OUT NC n Normally Closed ContactConnects OCOM to OUT NC when activated240 VAC maximum voltage1/3 hp 125 VAC, 1/2 hp 250 VAC
SA Bus2,3 +-COM
Provides SA Bus communication network Daisy-chained366 m (1,200 ft) maximum length0.6 mm to 1.5 mm2 (18 to 24 AWG)[22 AWG Recommended]
FC Bus,3 +-COM
Provides FC Bus communication network Daisy-chained1,524 m (5,000 ft) maximum length0.6 mm to 1.5 mm2 (18 to 24 AWG)[22 AWG Recommended]
SHLD Provides an optional shield connection
24~ Power Hot AC Supply Input - Nominal 24 VAC 16 AWG
COM The 24~ Power common; isolated from all other terminal commons
1. The terminal block column displays all the points for the IOM3710 model.2. The SA Bus and FC Bus specifications in this table are for MS/TP bus communications at 38.4K. For more information,
see MS/TP Bus Cable Recommendations on page 111.3. Requires a SMK-MOVKIT-MSTP transient protector kit for all MS/TP communication terminal connections. See
SMK-MOVKIT-MSTP Wiring for MS/TP FC Bus Communication Terminations on page 90 and SMK-MOVKIT-MSTP Wiring for SA Bus Communication Terminations on page 92 for wiring details.
4. Requires SMOKE-MOVKIT-0 transient protectors for all MS/TP I/O terminal connections. See MOV Requirements for MS/TP I/O Terminals on page 94 for wiring details.
Table 40: IOM2710 and IOM3710 LED Status IndicatorsName Color Normal DescriptionsPower Green On Steady On Steady = Power is Supplied by Primary Voltage
Off = No Power
Fault Red Off Off Steady = No FaultsOn Steady = Device FaultFlicker = Download or startup in progress and not ready for normal operation
SA Bus/FC Bus Green Flicker Flicker = Normal CommunicationOff Steady = Auto baud in progress (Not applicable for SA Bus)On Steady = Communication lost
Table 39: IOM2710 and IOM3710 Field Controller Platform Wiring List (Part 2 of 2)Terminal Block1
Terminal Labels
Function and Electrical Ratings/Requirements Wiring Requirements (see Table 36 on page 142)
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 151
Wiring the IOM47101. Terminate wiring per engineering drawings.
2. Wire Network Sensors and other devices to the SA Bus or Sensor socket.
3. Wire the FC Bus in a daisy chain.
4. Wire the SA Bus in a daisy chain.
5. The IOM4710 module should be at one end of the SA Bus daisy chain. If multiple Input/Output Modules (IOMs) are used, set the End-of-Line (EOL) switch on the last IOM.
6. Ensure the device address DIP switches are set to the appropriate hardware address (in the range of 4-127). See Device Addresses on the MS/TP Bus on page 86.
7. Connect power to the IOM4710 module.
8. Download and commission the IOM4710 module.
Figure 109: IOM4710 Module Wiring Interface
RET SY
FAULT
POWER
ON ADDRESS
ADDRESS Ø = ALL OFF
CO
M
HO
T
OU
T 4
OC
OM
4
OU
T 5
OC
OM
5
OU
T 6
OC
OM
6
OU
T 7
OC
OM
7
OU
T 2
OC
OM
2
OU
T 1
OC
OM
1
OU
T 3
OC
OM
3
OU
T 8
OC
OM
8
OU
T 9
OC
OM
9
UNIVERSAL
+15V
IN1
ICO
M1
IN2
ICO
M2
+15V
IN3
ICO
M3
IN4
ICO
M4
+15V
IN5
ICO
M5
IN6
ICO
M6
IN7
ICO
M7
IN8
ICO
M8
BINARY
EOL
ON
StatusLEDs
DeviceAddress
DIPSwitches
EOLSwitch
IOM
4710
-cvr
.cdr
+ - CO
M
+ - CO
M
15V
SA
PW
R
FC
SA
BinaryOutputs
ConfigurableOutputs
AnalogOutputs 24 VAC
Power Terminal
UniversalInputs
BinaryInputs
SA/FC BusTeerminals
SA/FC BusPort
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin152
Terminal Type Terminal Connection Required MOV ProtectionUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Input IN7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Input ICOM7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Input IN7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Input ICOM7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output OUT8 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output OCOM8 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output OUT9 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output OCOM9 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 110: MS-IOU4710-0U I/O MOV Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 153
IOM4710 Field Controller Platform Wiring ListTable 41: IOM4710 Field Controller Platform Wiring List (Part 1 of 2)Terminal Block
Terminal Labels
Function and Electrical Ratings/Requirements Wiring Requirements(see Table 36 on page 142)
Universal IN +15V Sources 15 VDC power for active devices100 mA total current
Same as IN 4
IN n Analog Input, Voltage ModeAccepts a 0-10 VDC input signal10 VDC Maximum Input VoltageInternal 75k ohm Pulldown
A 4
Analog Input, Current ModeAccepts a 4-20 mA input signalInternal 100 ohm load Impedance
B 4
Analog Input, Resistive ModeAccepts 0-600k ohm input signalInternal 12 V, 15k ohm PullupRTD (1k Nickel [Johnson Controls], 1k Platinum, A99B Silicon Temperature Sensor)Negative Temperature Coefficient (NTC) Sensor (10k Type L, 2.252k Type 2)
A 4
Binary Input, Dry Contact Maintained Mode1 s minimum pulse width (0.5 Hz at 50% duty cycle)Internal 12 V, 15k ohm Pullup
A 4
ICOM n The input signal common for Universal IN terminals; isolated from all other terminal commons
Same as IN 4
Binary IN IN n Binary Input, Dry Contact Maintained Mode0.01 s minimum pulse width (50 Hz at 50% duty cycle)Internal 12 V, 15k ohm Pullup
A 4
Binary Input, Pulse Counter Mode0.01 s minimum pulse width (50 Hz at 50% duty cycle)Internal 12 V, 15k ohm Pullup
ICOM n The signal common for all Binary IN terminals; isolated from all other terminal commons
Analog OUT OUT n Analog Output, Voltage ModeSources 0-10 VDC output voltageExternal 1k ohm minimum load required10 VDC maximum output voltage10 mA maximum output current
A 4
Analog Output, Current ModeSources 4-20 mA output currentExternal 300 ohm maximum load required
B 4
OCOM n The output signal common for Analog OUT terminals; isolated from all other terminal commons
Same as OUT 4
Binary OUT(Jumper set to External)
OUT n Binary Output, 24 VAC TriacConnects OUT to OCOM when activated30 VAC maximum output voltage0.5 A maximum output current40 mA minimum load current
C 4
OCOM n The output signal common for Binary OUT terminals; isolated from all other terminal commons, including BO terminal commons
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin154
Binary OUT(Jumper set to Internal)
OUT n Sources 24~ Power (Hot) C 4
OCOM n Binary Output, 24 VAC TriacConnects OCOM to 24~ Power (Com) when activated30 VAC maximum output voltage0.5 A maximum output current40 mA minimum load current
Configurable OUT
OUT n Analog Output, Voltage ModeSources 0-10 VDCExternal 1k ohm minimum load required10 VDC maximum output voltage10 mA maximum output current
A 4
Binary Output, 24 VAC Triac ModeConnects OUT to OCOM when activated30 VAC maximum output voltage0.5 A maximum output current40 mA minimum load current
C 4
OCOM n The output signal common; isolated from all other terminal commons
Same as OUT
Sensor1, Sensor Provides SA Bus communication networkRJ-12 6-position modular connector
30.5 m (100 ft) maximum length phone cord
SA Bus,2,3 +-COM
Provides SA Bus communication network Daisy-chained366 m (1,200 ft) maximum length0.6 mm to 1.5 mm2 (18 to 24 AWG)[22 AWG Recommended]
SA PWR Sources 15 VDC power for devices on the SA Bus
FC Bus2, 3 +-COM
Provides FC Bus communication network Daisy-chained1,524 m (5,000 ft) maximum length0.6 mm to 1.5 mm2 (18 to 24 AWG)[22 AWG Recommended]
SHLD Provides an optional shield connection
24~ Power Hot AC Supply Input - Nominal 24 VAC 16 AWG
COM The 24~ Power common; isolated from all other terminal commons
1. The SA Bus and the Sensor Port are daisy-chained internally.2. The SA Bus and FC Bus specifications in this table are for MS/TP bus communications at 38.4k.3. Requires a SMK-MOVKIT-MSTP transient protector kit for all MS/TP communication terminal connections. See
SMK-MOVKIT-MSTP Wiring for MS/TP FC Bus Communication Terminations on page 90 and SMK-MOVKIT-MSTP Wiring for SA Bus Communication Terminations on page 92 for wiring details.
4. Requires SMOKE-MOVKIT-0 transient protectors for all MS/TP I/O terminal connections. See MOV Requirements for MS/TP I/O Terminals on page 94 for wiring details.
Table 41: IOM4710 Field Controller Platform Wiring List (Part 2 of 2)Terminal Block
Terminal Labels
Function and Electrical Ratings/Requirements Wiring Requirements(see Table 36 on page 142)
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 155
Troubleshooting Use Table 42 to troubleshoot the IOM4710 module.
IOMx710-0U Specifications
Table 42: IOM4710 Status LEDsName Color Normal DescriptionsPower Green On Steady Off Steady = No Power
On Steady = Power is Supplied by Primary Voltage.
Fault Red Off Steady Blink - 2 Hz = Download or startup in progress, not ready for normal operationOff Steady = No FaultsOn Steady = Device Fault
SA/FC Bus Green Blink - 2 Hz Blink - 2 Hz = Data Transmission (normal communication)Off Steady = No Data Transmission (auto baud in progress, N/A for SA bus)On Steady = Communication lost, waiting to join communication ring
Table 43: IOMx710-0U Technical SpecificationsCategory SpecificationProduct Code Number MS-IOM1710-0U MS-IOM2710-0U MS-IOM3710-0U MS-IOU4710-0U
IOM - Cover and Triac Mounting Base
Supply Voltage 24 VAC Nominal at 60 Hz
Power Consumption 0.6 A Max, 10 VA maximum plus all BO and Configurable Output loads
Ambient Operating Conditions
0 to 49°C (32 to 120°F); 10 to 93% RH noncondensing
Terminations Screw terminals, 3-Position Screw Terminal Pluggable Blocks, 4-Position Screw Terminal Pluggable Blocks
Controller Addressing DIP switch set (4-127). Addresses 0 - 3, 128-255 are reserved.
Communications Bus • BACnet MS/TP; 3-wire Field Controller Bus (FC Bus) between the Network Automation Engine (NAE) and other devices.
• 4-wire Sensor-Actuator Bus (SA Bus) between network sensors and other devices.1
Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail
Standards Compliance UL Listed and CSA CertifiedUL 916 Energy Management Listing, CSA C22.2 No. 205, CFR47FCC Part 15 Class ACE Mark and C-Tick DirectiveCE Directive 89/336/EEC (EN50081-1, EN50082-2)
Dimensions(Height x Width x Depth)
108 x 127 x 58 mm(4-1/4 x 5 x 2-1/4 in.)
180 x 127 x 58 mm(7-1/16 x 5 x 2-1/4 in.)
180 x 127 x 58 mm(7-1/16 x 5 x 2-1/4 in.)
180 x 127 x 58 mm(7-1/16 x 5 x 2-1/4 in.)
Housing Plastic housingPlastic material: ABS _ polycarbonate UL94 5VBProtection: IP20 (IEC529)
Weight 0.31 kg (0.7 lb) 0.48 kg (1.1 lb) 0.55 kg (1.2 lb) 0.68 kg (1.5 lb)
1. For more information, refer to the MS/TP Field Bus section in this document.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin156
UL Label PlacementUL Listing labels must be positioned as shown in Figure 111 and Figure 112.
Figure 111: UL Label Placement for the MS-IOM1710-0U and MS-IOM2710-0U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 157
Figure 112: UL Label Placement for the MS-IOM3710-0U and MS-IOM4710-0U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin158
VMA16x0 Field Equipment ControllersThe Variable Air Volume (VAV) Modular Assembly (VMA) 1600 Series consists of configurable digital controllers that use the BACnet® Master-Slave/Token-Passing (MS/TP) communications protocol. Both the VMA1610 and VMA1620 have a pressure sensor and actuator in a prewired unit.
MountingTo mount the VMA1610/VMA1620:
1. Place the VMA in the proper mounting position on the damper shaft so that the wiring connections are easily accessible. Make sure the VMA base is parallel to the VAV box (perpendicular to the damper shaft). If needed, use a spacer to offset tipping of the VMA caused by the shaft bushings.
2. Secure the self-piercing No. 10 screw through the VMA mounting slot with a power screwdriver and 100 mm (4 inch) extension socket. Otherwise, use a punch to mark the position of the shoulder washer, and then drill a hole into the VAV box using a 3.5 mm (9/64 in.) drill bit. Insert the mounting screw, and tighten against the washer.
3. Locate the damper position using the typical marking on the end of the damper shaft (Figure 114).
IMPORTANT: When the air supply to the VAV box is below 10°C (50°F), make sure that any condensation on the VAV box, particularly on the damper shaft, does not enter the electronics. Mount the VMA vertically above the damper shaft to allow any shaft condensation to fall away from the VMA controller. Additional measures may be required in some installations.
IMPORTANT: Do not overtighten the screws, or the threads may strip. If mounting to the VAV box, make sure the screws do not interfere with damper blade movement.
Figure 113: VMA1610 VMA1620
d_sh
aft
Figure 114: Typical Damper End Shaft
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 159
4. Note the direction, Clockwise (CW) or Counterclockwise (CCW), required to close the damper. Grasp the damper shaft firmly with pliers and either manually close the damper for 90° boxes or manually open for 45° or 60° boxes.
5. Push down and hold the Manual Override button (see Figure 115), and turn the VMA coupler until it contacts the mechanical end-stop at either the fully closed (90° boxes) or fully open (45° and 60° boxes) position.
6. If the damper for a 90° box closes CCW, rotate the coupler to the CCW mechanical limit. If the damper for a 90° box closes CW, rotate the coupler to the CW mechanical limit. The open end-stop is automatically set for 90° boxes.
7. For 45° and 60° boxes, hard stops must be provided at both fully closed and fully open damper positions. By installing the VMA at the fully open position, the VMA provides the open stop for 45° and 60° boxes. The closed damper seal provides the fully closed stop.
8. Tighten the square coupler bolt to the shaft using an 8 mm (5/16 in.) wrench or 10 mm (3/8 in.) 12-point socket. Tighten to 17 to 21 N·m (150 to 180 lb·in [14 lb·ft]).
9. Loop the pneumatic tubing to include a trap for condensation. Attach the tubing from the VMA to the VAV box pickup. The HIGH (red) tubing is connected to the inlet or high-pressure side and the clear tubing to the low side (see Figure 115).
10. Push the manual release button, and turn the actuator coupling manually to ensure that the actuator can rotate from full closed to full open positions without binding.
11. Complete the mounting by rotating the damper to the full open position.
Common VMA Configuration Details
Use the following information links to configure all Smoke Control VMA models.
Determining the FC Bus Address
See Device Addresses on the MS/TP Bus on page 86 for detailed information.
Setting the FC Bus Address
See Setting a Device Address on page 87 for detailed information.
FC Bus End-of-Line Switch
See End-of-Line Termination on the MS/TP Bus on page 95 for detailed information.
Commissioning the VMA
Commission all Smoke Control VMA models through the NAE passthrough and FC communication bus and the Controller Configuration Tool (CCT) software.
!CAUTION: Risk of Property Damage.Rotate the damper to full open position before starting the air handler. Failure to rotate the damper to the full-open position may result in damage to the Variable Air Volume (VAV) box or ductwork when the air handler is started.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin160
WiringFor more information on the rules of the MS/TP Communications Bus, refer to the MS/TP Field Bus section in this document.
To wire the VMA:
1. Terminate wiring per engineering drawings.
2. Wire network sensors and other devices to the SA Bus or Sensor socket.
3. Wire the FC Bus in a daisy chain.
4. Ensure the device address DIP switches are set to the appropriate hardware address (4-127).
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 161
5. Connect power to the VMA.
Figure 115: VMA1610/1620 Wiring
TAG
DE
SCR
IPTI
ON
CA
BLE
TY
PE
TAG
DE
SCR
IPTI
ON
CA
BLE
TYP
EBO
DA
-TD
ISC
HAR
GE
AIR
TE
MP
ERAT
UR
E2/
22H
TG-O
HEA
TIN
G O
UTP
UT
3/22
SF-
CSU
PPL
Y F
AN
CO
MM
AN
D2/
22
SA
BU
S D
EVI
CE
1
ZN-T
ZON
E TE
MP
ER
ATU
RE
4/22
OU
T 1
BOO
UT
2
CO
OU
T 4
CO
OU
T 5
BO
OU
T 3
UI
IN 1
FAN
-C
C24V
NC C NO
1
OLs
2
CINHTG
-O
24V
GR
OU
ND
XFR
277
VAC
12
DA
-TPneu
mat
ic T
ubin
g
RTD
NI C
OM -
PW
R
+
MS/
TP
FRO
M L
AST
DEV
ICE
TO N
EXT
DEV
ICE
MS
/TP
ZN-T
WC
-AD
J
Dis
char
ge A
ir Fr
omA
ir H
andl
ing
Uni
t
Ret
urn
Air
from
Roo
m
N C
DA
-VP
VMA
ZN-T
WC
-AD
JD
A-T
HC
HTG
-OR
ETU
RN
SUPP
LY
FAN
-C
CLE
AR=L
OW
RED
=HIG
H
35 IN
-LB
(4N
m) 6
0 SE
CON
DSA
LL F
IELD
TER
MIN
ALS
ARE
PO
WER
LIM
ITED
OUT
1
OC
OM
1
OUT
2
OC
OM
2
OUT
3
OC
OM
3
BINARY
OU
T 4
OCO
M 4
OU
T 5
OCO
M 5
CONFIGURABLE 24
ADDRESS 0=OFF
UNIVERSAL
+15
IN ICO
M SENSOR SA BUS FC BUS
SA PWR
COM – + SHLD
COM – +FC EO
L
vma1620_wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin162
Table 44: VMA Wiring List (Part 1 of 2)Terminal Block
Terminal Labels
Function and Electrical Ratings/Requirements Wiring Requirements
Universal IN +15V Sources 15 VDC power for active devices35 mA total current
A3,5
IN n Analog Input, Voltage ModeAccepts a 0-10 VDC input signal10 VDC Maximum Input VoltageInternal 75k ohm Pulldown
Analog Input, Resistive ModeAccepts 0-600k ohm input signalInternal 12 V, 15k ohm PullupRTD (1k Nickel [Johnson Controls], 1k Platinum, A99BSilicon Temperature Sensor)Negative Temperature Coefficient (NTC) Sensor (10k Type L, 2.252k Type 2)
Binary Input, Dry Contact Maintained Mode1 s minimum pulse width (0.5 Hz at 50% duty cycle)Internal 12 V, 15k Ohm Pullup
ICOM n The input signal common for Universal IN terminals; isolated from all other terminal commons
Terminal Type Terminal Connection Required MOV ProtectionUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 116: MS-VMA1610-0U I/O MOV Placement
Terminal Type Terminal Connection Required MOV ProtectionUniversal Input +15V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input ICOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OUT3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundBinary Output OCOM3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OUT5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundConfigurable Output OCOM5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 117: MS-VMA1620-0U I/O MOV Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 163
Binary OUT OUT n Sources 24~ Power (Hot) C3,5
OCOM n Binary Output, 24 VAC TriacConnects OCOM to 24~ Power (Com) when activated30 VAC maximum output voltage0.5 A maximum output current40 mA minimum load current
Configurable OUT
OUT n Analog Output, Voltage ModeSources 0-10 VDCExternal 1k ohm minimum load required10 VDC maximum output voltage10 mA maximum output current
A3,5
Binary Output, 24 VAC Triac ModeConnects OUT to OCOM when activated30 VAC maximum output voltage0.5 A maximum output current40 mA minimum load current
C3,5
OCOM n The output signal common; isolated from all other terminal commons
Same as OUT5
Sensor1,2 Sensor Provides SA Bus communication networkRJ-12 6-position modular connector
30.5 m (100 ft) maximum length phone cord
SA Bus1,2,4 +-COM
Provides SA Bus communication network Daisy-chained366 m (1,200 ft) maximum length0.6 mm to 1.5 mm2 (18 to 24 AWG)[22 AWG Recommended]
SA PWR Sources 15 VDC power for devices on the SA Bus
FC Bus2,4 +-COM
Provides FC Bus communication network Daisy-chained1,524 m (5,000 ft) maximum length0.6 mm to 1.5 mm2 (18 to 24 AWG)[22 AWG Recommended]
SHLD Provides an optional shield connection
24~ Power Hot AC Supply Input - Nominal 24 VAC 16 AWG
COM The 24~ Power common; isolated from all other terminal commons
1. The SA Bus and the Sensor Port are daisy-chained internally.2. The SA Bus and FC Bus specifications in this table are for MS/TP bus communications at 38.4k. For more information,
refer to the MS/TP Field Bus section in this document.3. See MS/TP Bus Cable Recommendations on page 111 for wire length specifications.4. Requires a SMK-MOVKIT-MSTP transient protector kit for all MS/TP communication terminal connections. See
SMK-MOVKIT-MSTP Wiring for MS/TP FC Bus Communication Terminations on page 90 and SMK-MOVKIT-MSTP Wiring for SA Bus Communication Terminations on page 92 for wiring details.
5. Requires SMOKE-MOVKIT-0 transient protectors for all MS/TP I/O terminal connections.
See MOV Requirements for MS/TP I/O Terminals on page 94 for wiring details.
Table 44: VMA Wiring List (Part 2 of 2)Terminal Block
Terminal Labels
Function and Electrical Ratings/Requirements Wiring Requirements
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin164
VMA Wire Gauge and Length Guidelines
Use Table 45 for all VMA wiring.
Troubleshooting
Use Table 46 to troubleshoot the VMA controllers.
Table 45: VMA Wire Gauge and Length GuidelinesGuideline Cable
Size (AWG)
Maximum Length (Ft)
Assumptions
A 18 1500 100 mV maximum voltage drop at maximum current
20 975
22 600
24 350
B 18 750 100 mV maximum voltage drop at maximum current
20 450
22 300
24 200
C 40 mA Load
18 400
20 250
22 150
24 100
500 mA Load
18 75
20 50
22 30
24 20
Table 46: Status Light-Emitting Diodes (LEDs)Name Color Normal DescriptionsPower Green On Steady Off Steady = No Power
On Steady = Power is supplied by Primary Voltage.
Fault Red Off Steady Blink - 2 Hz = Download or Startup in progress, not ready for normal operationOff Steady = No FaultsOn Steady = Device Fault or no application loaded
FC Bus Green Blink - 2 Hz Blink - 2 Hz = Data Transmission (normal communication)Off Steady = No Data Transmission (auto baud in progress)On Steady = Communication lost, waiting to join communication ring
SA Bus Green Blink - 2 Hz Blink - 2 Hz = Data Transmission (normal communication)Off Steady = No Data Transmission (N/A - auto baud not supported)On Steady = Communication lost, waiting to join communication ring
18 AWG (1.5 mm )2
20 AWG (0.8 mm )2
22 AWG (0.6 mm )2
24 AWG (N/A)
450 500400350300250200150100500
Load Current (mA)
0 ft (0 m)
50 ft (15.2 m)
100 ft (30.5 m)
150 ft (45.7 m)
200 ft (61 m)
250 ft (76.2 m)
300 ft (91.4 m)
350 ft (106.7 m)
400 ft (121.9 m)
450 ft (137.2 m)
Length
Load Current vs Wire Length
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 165
SpecificationsTable 47: VMA16x0-0U Technical SpecificationsCategory SpecificationProduct Code Number MS-VMA1610-0U Cooling Only
MS-VMA1620-0U Cooling with Reheat
Supply Voltage 24 VAC @ 60 Hz
Power Consumption 10 VA maximum; Power delivered to devices connected to the binary outputs (for example, valves, relays, and so on) is not included in this rating.
Ambient Operating Conditions
0 to 49°C (32 to 120°F) 10 to 93% RH noncondensing
Terminations 6.3 mm (1/4 in.) spade lugs except communications and 24 VAC power, which are screw terminals
Controller Addressing DIP switch set (4-127). Addresses 0 - 3, 128 - 255 are reserved.
Communications Bus • BACnet MS/TP; 3-wire Field Controller Bus (FC Bus) between the Network Automation Engine (NAE) and other devices.
• 4-wire Sensor-Actuator Bus (SA Bus) between network sensors and other devices.
Mounting Mounts to damper shaft using single set screw and to duct with single mounting screw.
Actuator Rating 4 N·m (35 lb·in) minimum shaft length = 44 mm (1-3/4 in.)
Standards Compliance UL Listed and CSA CertifiedUL 916 Energy Management Listing, CSA C22.2 No. 205, CFR47FCC Part 15 Class ACE Mark and C-Tick DirectiveCE Directive 89/336/EEC (EN50081-1 Class B, EN50082-2)
Dimensions Width: 182 mm (7-3/16 in.)Length: 182 mm (7-3/16 in.)Height: 64 mm (2-1/2 in.)Center of Output Hub to Center of Anti-rotation Slot: 160 mm (6-5/16 in.)
Weight 0.86 kg (1.9 lb) 0.86 kg (1.9 lb)
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin166
UL Label PlacementUL Listing labels must be positioned as shown Figure 118.
Figure 118: UL Label Placement for the MS-VMA1610-0U and MS-VMA1620-0U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 167
MS/TP SA Bus Network SensorsThe MS/TP NS Series Network Sensors are SA Bus electronic zone sensors designed to function directly with Metasys® system BACnet® protocol FECs, IOMs, and the VMA 1600. They are available in either temperature only or temperature and humidity models.
Selection Charts Network Sensor Ordering Information — Temperature and Humidity ModelsProduct Code Number
Size (mm), Height x Width
Vertical Wallbox-Mounted (WB), or Surface-Mounted (SM)
LCD Display
Humidity Temperature Adjustment: Setpoint (Set), or Warmer/Cooler Dial (W/C)
Occupancy Override
F/C Scale Toggle
Screw Terminals (ST), or Modular Jack (MJ)
NS-APA7001-0 80 x 80 SM Yes 2% Set Yes MJNS-APA7002-0 80 x 80 SM Yes 2% Set Yes STNS-APB7001-0 80 x 80 SM Yes 2% Set Yes Yes MJNS-APB7002-0 80 x 80 SM Yes 2% Set Yes Yes STNS-BPB7001-0 120 x 80 WB, SM Yes 2% Set Yes Yes MJNS-BPB7002-0 120 x 80 WB, SM Yes 2% Set Yes Yes STNS-AHA7001-0 80 x 80 SM Yes 3% Set Yes MJNS-AHA7002-0 80 x 80 SM Yes 3% Set Yes STNS-AHB7001-0 80 x 80 SM Yes 3% Set Yes Yes MJNS-AHB7002-0 80 x 80 SM Yes 3% Set Yes Yes STNS-BHB7001-0 120 x 80 WB, SM Yes 3% Set Yes Yes MJNS-BHB7002-0 120 x 80 WB, SM Yes 3% Set Yes Yes ST
Network Sensor Ordering Information — Temperature Only ModelsProduct Code Number
Size (mm), Height x Width
Vertical Wallbox-Mounted (WB), or Surface-Mounted (SM)
LCD Display
Temperature Adjustment: Setpoint (Set), or Warmer/Cooler Dial (W/C)
Occupancy Override
F/C Scale Toggle
Fan Control
Screw Terminals (ST), or Modular Jack (MJ)
Address Switches
VAV Balancing Feature
NS-ATA7001-0 80 x 80 SM Yes Set Yes MJNS-ATA7002-0 80 x 80 SM Yes Set Yes STNS-ATB7001-0 80 x 80 SM Yes Set Yes Yes MJNS-ATB7002-0 80 x 80 SM Yes Set Yes Yes STNS-ATC7001-0 80 x 80 SM Yes Set Yes Yes MJNS-ATC7002-0 80 x 80 SM Yes Set Yes Yes STNS-ATD7001-0 80 x 80 SM Yes Set Yes Yes Yes MJNS-ATD7002-0 80 x 80 SM Yes Set Yes Yes Yes STNS-ATN7001-0 80 x 80 SM MJNS-ATN7003-0 80 x 80 SM ST YesNS-ATP7001-0 80 x 80 SM W/C Yes MJNS-ATP7002-0 80 x 80 SM W/C Yes STNS-ATV7001-0 80 x 80 SM Yes Set Yes Yes No1 MJ YesNS-ATV7002-0 80 x 80 SM Yes Set Yes Yes No1
1. In the VAV Balancing models, the Fan Control button is replaced by a light bulb button used in the VAV Balancing Process.
ST YesNS-BTB7001-0 120 x 80 WB, SM Yes Set Yes Yes MJNS-BTB7002-0 120 x 80 WB, SM Yes Set Yes Yes STNS-BTN7001-0 120 x 80 WB, SM MJNS-BTN7003-0 120 x 80 WB, SM ST YesNS-BTP7001-0 120 x 80 WB, SM W/C Yes MJNS-BTP7002-0 120 x 80 WB, SM W/C Yes STNS-BTV7001-0 120 x 80 WB, SM Yes Set Yes Yes No1 MJ YesNS-BTV7002-0 120 x 80 WB, SM Yes Set Yes Yes No1 ST Yes
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin168
Specifications NS Series Network Sensor
Sensor Type With Setpoint Adjustment Without Setpoint AdjustmentSupply Voltage 9.8 to 16.5 VDC; 15 VDC NominalCurrent Consumption 25 mA Maximum (Non-Transmitting) 13 mA Maximum (Non-Transmitting)Terminations Modular Jack or Screw Terminal BlockSensor Addressing on the SA Bus
NS-xTN7003-0 Model
NA DIP Switch Set (200 to 203)
All Other Models Fixed Address of 199 Fixed Address of 199Wire Size Modular Jack
Models26 AWG (0.4 mm Diameter) Recommended; Three Twisted Pair (6 conductors)
Screw Terminal Block Models
18 to 22 AWG (1.0 to 0.6 mm Diameter); 22 AWG (0.6 mm Diameter) Recommended
Communication Rate Auto-Detect: 9600, 19.2k, 38.4k, or 76.8k bpsMounting Surface-Mounted (80 x 80)
Surface-Mounted or Vertical Wallbox-Mounted (120 x 80)Temperature Measurement Range 0.0°C/ 32.0°F to 40.0°C/104.0°FSensor Type Local Platinum Resistance Temperature Detector (RTD)Resolution ±0.5C°/±0.5F° NASensor Accuracy ±0.6C°/±1.0F°Time Constant 10 Minutes Nominal at 10 fpm AirflowDefault Setpoint Adjustment Range 10.0°C/50.0°F to 30.0°C/86.0°F in 0.5° Increments ±3.0C°/±5.0F°Ambient Conditions Operating 0 to 40°C (32 to 104°F); 10 to 95% RH, Noncondensing; 29°C (85°F) Maximum Dew Point
Storage -20 to 60°C (-4 to 140°F); 5 to 95% RH, Noncondensing -40 to 70°C (-40 to 158°F); 5 to 95% RH, NoncondensingCompliance United States UL Listed, File E107041, CCN PAZX, Under UL 916, Energy Management Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class ACanada UL Listed, File E107041, CCN PAZX7, Under CSA C22.2 No. 205, Signal Equipment
Industry Canada, ICES-003European Union CE Mark, EMC Directive 89/336/EEC
EN61000-6-3 (2001) Generic Emission Standard for Residential and Light IndustryEN61000-6-2 (2001) Generic Immunity Standard for Heavy Industrial Environment
Australia and New Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight 0.09 kg (0.20 lb) for NS-Axx7xxx-00.11 kg (0.25 lb) for NS-Bxx7xxx-0
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 169
LONWORKS® Field Bus
Network TopologiesThe physical routing of the communication channel defines the network topology. The channel and transceiver types define the requirements and limitations of each wiring topology.
Some network segments such as the TP/FT-10 and TP/XF-1250 require termination for proper data transmission performance. Free topology and bus network topology differ in their termination requirements. The following sections describe the Bus topology, its terminator type, and termination procedures.
Bus TopologyA bus topology is a physical routing of the communication channel that includes a distinct beginning and end, each requiring termination. This type is also known as a daisy-chain topology. Figure 119 shows examples of various Bus topology configurations for Smoke Control systems.
Figure 119: Bus Topology
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin170
Devices per Segment
LONWORKS Network Bus Topology Termination NXM-TERM-FTT-U
Table 48: Maximum Number of Devices per LONWORKS Network Segment Device Type Maximum AllowedFTT-10 Nodes Only 64 (if repeaters are not used)
FTT-10 Nodes Only 128 (if repeaters are used)
Mixed FTT-10 and LPT-10 Nodes1
1. Each LPT10 channel segment (between repeaters) requires its own power supply. Other factors such as power consumption of individual LPT10 devices may limit a segment to fewer devices.
([FTT10 x 2] + LPT10) < 128
Terminators:Bus Topology 2 bus type EOL terminators required (NXM-TERM-FTT)
Physical Layer Repeaters Maximum of 1 per segment
Table 49: LONWORKS Network TerminationTermination Requirements Johnson Controls Part No.
R1 = 105 Ohm, 1%, 1/8WC1 = 100µF, = 50VC2 = 100µF, = 50V
NXM-TERM-FTT-U (FTT10 Bus topology)
Table 50: Guidelines for LONWORKS Network Bus TopologyCable Type Maximum Segment Length with
FTT10 Devices Only1
1. For the bus topology, the maximum length stub cable is 3 m (10 ft), and the stub lengths must be calculated into the overall segment length.
Maximum Segment Length with FTT10 and/or LPT10 Devices1
Belden® 85102 2700 m (8,850 ft) 2200 m (7,200 ft)
Belden 8471 2700 m (8,850 ft) 2200 m (7,200 ft)
Level IV 22 AWG 1400 m (4,600 ft) 1150 m (3,770 ft)
JY (St.) Y 2 x 2 x 0.8 900 m (2,950 ft) 750 m (2,460 ft)
Figure 120: NXM-TERM-FTT-U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 171
SMK-MOVKIT-LON Transient ProtectionThe LON Communication line must have a SMK-MOVKIT-LON MOV kit installed when the conduit run between the enclosures does not remain in the same room.
Installation RequirementsWhen installing the transient protectors (MOV kits) care must be taken when installing a protector close to other protectors. Use the information below to install the MOV kit:
• Before installing the protective device in the terminal block, twist it together with the field lead and insert it into the terminal block as one wire.
• Twist the wire tightly around the transient protection device a minimum of two turns before inserting it into the terminal block.
• When more than two wires are to be placed under a single terminal screw, the wires must be soldered together with a single #18 AWG wire 6 inches in length having a minimum insulation thickness of 1/64 inch. The exposed terminal must be stripped and then tinned or crimped with a suitable lug that will fit securely under the terminal screw.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin172
Figure 121 shows wire runs to LON equipment in cabinets in various rooms and the correct use of the SMK-MOVKIT-LON to protect the LON devices from transients.
Figure 121: SMK-MOVKIT-LON Communication Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 173
SMK-MOVKIT-LON Requirements for LON Communication Bus Transient ProtectionFigure 122 shows a SMK-MOVKIT-LON and its wiring when the communication wiring leaves the same room and the LON Bus communication wiring terminates at the LON communication terminal block.
Figure 122: SMK-MOVKIT-LON LON Communication Wiring Terminations
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin174
Figure 123 shows the SMK-MOVKIT-LON wiring when the communication wiring leaves the same room and the LON Bus communication wires do not terminate at the LON terminal block.
Figure 123: SMK-MOVKIT-LON Wiring Terminations - Multiple LON Wires
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 175
SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals
With the exception of the LN-VAVC-0 and LN-VAVCF-0 LON controllers, all other LON controller input terminals and output terminals must have an MOV from a SMOKE-MOVKIT-0 placed between earth ground and each Power terminal, I/O Common terminal, and I/O terminal (Figure 124).
The LON field device’s I/O lines must have a SMOKE-MOVKIT-0 MOV kit installed when the conduit run between the enclosures and a LON I/O field device does not remain in the same room.
Note: The SMOKE-MOVKIT-0 kit contains 10 MOVs.
SMK-MOVKIT-LON Transient Protection for LN-VAVC-0 and LN-VAVCF-0 LON Controllers
All LN-VAVC-0 and LN-VAVCF-0 controllers requires a combination of SMOKE-MOVKIT-0 and a SMK-MOVKIT-MSTP transient protectors to protect all input and output terminals as shown in Figure 124.
Installation Requirements
Care must be taken when installing transient protectors (MOV kits) in close proximiy to other protectors. Use the information below to install the MOV kit.
• Before installing the MOV kit to the LON I/O terminal block, twist it together with the field lead and insert it in the terminal block as one wire.
• Twist the wire tightly around the transient protection device a minimum of two turns before inserting it into the terminal block.
When more that two wires are to be placed under a single terminal screw, the wires must be soldered together with a single 6 inch length of 18 AWG wire having a minimum insulation thickness of 1/64 inch. The exposed solder connection must be covered with a UL recgonized component heat shrink. The single wire end that will be inserted into the terminal must be stripped and then tinned or crimped with a suitable lug that fits securely under the terminal screw. The single wire end that will be attached to earth ground must be stripped and crimped with a suitable lug that will fit securely under the grounding screw.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin176
The left and upper right diagrams in Figure 124 show the LON controller I/O terminal block SMOKE-MOVKIT-0 connections. In the bottom right diagram in Figure 124, notice that the LN-VAVC-0U and LN-VAVCF-0U both require a SMK-MOVKIT-MSTP. Even though this is a LON device, it requires the SMK-MOVKIT-MSTP.
Figure 124: SMOKE-MOVKIT-0 LON I/O Wiring and MOV Terminations
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 177
LN Series Programmable VAV ControllersThe VAV Application Free Programmable Controller operates as a stand-alone unit or as part of a network system. It features 4 configurable universal inputs, 1 pressure differential input, 3 triac outputs (digital or PWM), 1 analog output (0-10 Volt PWM or digital 0-12 Volt), 1 floating motor control output, a flow sensor, 3 different flow sensor calibration settings (automatic with duct area or K factor, nominal flow, two-point calibration) and an actuator.
Connectors for the inputs, outputs, power, and network wires are found on the right side of the unit. The connectors are labeled and easily accessible.
IMPORTANT: The standard 3-terminal LON communication connector is replaced by a special UL Listed terminal block which allows for two-wires to be placed under a single terminal. Do not use any other terminal block to connect the LON communication trunk or you will void the UL Listing.
Figure 125: LN-VAVC-0
Figure 126: LN-VAVCF-0
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin178
Selecting Differential Pressure ScalesThree differential pressure scales are available and are selected using the pressure scale jumpers. See Figure 127 for the jumper location and Figure 128 for the correct setting.
Figure 127: Component Layout
0 1
Mechanical Stops
Connectors
Connectors
Low PressureSensor Input
Hole for Damper Shaft
MountingKit
Distech Controls
Pressure ScaleSelection Jumper
High PressureSensor Input
Figure 128: Differential Pressure Scale Settings
Range A Range B Range C
0 - 0.5H2O
0 - 125Pa
0 - 1H2O
0 - 250Pa
0 - 2H2O
0 - 500Pa
Terminal Type Terminal Connection Required MOV ProtectionUniversal Input I4+ 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input C 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input 13+ 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input I2+ 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input C 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input I1+ 1 lead (+) of a SMOKE-MOVKIT-MSTP installed between Terminal and Common Earth GroundAnalog Output C 1 lead (-) of a SMOKE-MOVKIT-MSTP installed between Terminal and Common Earth GroundAnalog Output A01 1 lead (Ref) of a SMOKE-MOVKIT-MSTP installed between Terminal and Common Earth GroundDigital Triac Output C 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundDigital Triac Output DO3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundDigital Triac Output DO2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundDigital Triac Output C 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundDigital Triac Output DO1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 129: LN-VAVC-0U I/O MOV Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 179
Wiring
Power Wiring
Figure 130: LN-VAVCF-0U I/O MOV Placement
Terminal Type Terminal Connection Required MOV ProtectionUniversal Input MOTOR FEEDBACK 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input C 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input 13+ 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input I2+ 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input C 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input I1+ 1 lead (+) of a SMOKE-MOVKIT-MSTP installed between Terminal and Common Earth GroundAnalog Output C 1 lead (-) of a SMOKE-MOVKIT-MSTP installed between Terminal and Common Earth GroundAnalog Output A01 1 lead (Ref) of a SMOKE-MOVKIT-MSTP installed between Terminal and Common Earth GroundDigital Triac Output C 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundDigital Triac Output DO3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundDigital Triac Output DO2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundDigital Triac Output C 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundDigital Triac Output DO1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 131: Power Connection
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin180
Wiring the Inputs (I1, I2, I3)
By default, the VAV controllers are shipped with every input configured as a 10 k Ohm thermistor, or digital, input.To change the input type, remove the cover and move the jumpers as shown from Figure 132 to Figure 137. Figure 137 shows an internally sourced 4 to 20 mA input. The power supply is internal to the sensor and is not on the board.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Figure 132: Selecting Analog 10 k Ohm or Digital Inputs
Figure 133: Potentiometer Input
Figure 134: 10 k Ohm or Digital Inputs
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 181
Figure 135: 0 to 5 VDC Analog Inputs
Figure 136: Externally Sourced 4 to 20 mA Inputs
Figure 137: Internally Sourced 4 to 20 mA Input
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin182
Wiring Powered Digital Outputs (DO1, DO2, DO3)
At time of shipping, all digital outputs are configured as unpowered output types.
The digital outputs can be configured as one of the two types described below:
The unpowered output type does not have any voltage on the output terminals when the output is active.
Voltage and current are supplied from outside the board.
The powered output type has 24 VAC on the output terminals when the output is active. Voltage and current are supplied from the board.
Maximum current for all digital outputs whether powered or unpowered is 1 Ampere.
DO1 and DO2 are controlled by a single jumper and so, must be set identically. The DO3 output has its own jumper and can be set independently of the other two outputs.
All digital outputs are controlled by triacs. As a result, measurements across outputs with a digital voltmeter may be misleading.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections
Wiring Powered Digital Outputs
Powered digital outputs switch 24 VAC from the supply transformer.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Set the output type selection jumpers as shown in Figure 138.
Wire the powered output terminal as shown in Figure 139.
Figure 138: Jumper Position for Powered Output Types
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 183
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Wiring Unpowered Outputs
Set the output type selection jumpers as shown in Figure 140.
Wire the unpowered digital output terminal as shown in Figure 141. See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Figure 139: Powered Outputs
Figure 140: Unpowered Outputs
Figure 141: Unpowered Digital Outputs
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin184
Wiring Analog Outputs
When configured as digital type, the analog outputs can provide 60 mA of current for relay, or solid state relay, operation. Table 51 describes the Analog Output characteristics.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections
Table 51: Analog Output CharacteristicsAnalog Output CharacteristicVoltage 0 to 10 VDC when configured as an analog output
0 to 12 VDC when configured as a digital output
Maximum Current 60 mA @ 12 VDC when configured as digital (200 Ohm load)50 mA @ 10 VDC when configured as analog
Figure 142: Analog Output
Figure 143: Analog to Digital Output Using a Relay
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 185
SpecificationsTable 52: LN-VAVC-0U and LN-VAVCF-0U Technical SpecificationsCategory SpecificationProduct(s) LN-VAVC-0U
LN-VAVCF-0U
Power Requirements Voltage: 24 VAC, 60 Hz, 3.2 Amp Maximum
Environmental Operating Temperature: 0°C to 49°C, 32°F to 120°FRelative Humidity: 0 to 93% Noncondensing
General Processor: Neuron® 3150®; 8 bits, 10 MHzMemory: Non-volatile Flash 64 K (APB application and configuration properties)Communication: LonTalk® ProtocolMedia Channel: TP/FT-10; 78 kbpsTransceiver: Echelon® Free Topology Transceiver (FTT-10)Battery (for clock only): Real-time Clock ChipEnclosure: Material: PVC, flammable class VO Dimension: 4.88 x 8.9 x 2.48 inches (124 x 226 x 63 mm) Weight: 1.84 lbs (0.835 kg)Safety: CSA and UL Listed
Damper Motor Motor: LM24-MusTorque: 35 in·lb, 4N·mAngle of Rotation: 95° adjustableFits shaft diameter: 8.5 mm to 18.2 mm; 5/16’’ to 3/4‘’Power Supply from Controller
Inputs Number: 4 UniversalDigital: Dry ContactVoltage: 0-10 VC, Accuracy ±0.5%Current: 4-20 mA with 500 K Ohms external resistor, Accuracy: ±0.5%Resistor: Thermistor Type 2 10 K ohms Accuracy: ±0.5°C; ±0.9°F\ Resolution: 0.1°C; 0.18°F Range: -40°C to 150°C; -40°F to 302°F Potentiometer 10 K ohms Linear 2-point setpoint adjustment Min/Max linear configuration Configurable on several pointsInput Resolution: 12 bits analog/digital converter1 Differential pressure: Range 125-250-500 Pa (0.5-1-2’’ H20), Accuracy ±3% full scale
Outputs Number: 43 Digital: Triac 24 VAC ±15%, 50/60 Hz, maximum charge 1.0 A, internal or external supply1 Tri-mode Analog: 0-10 VDC (linear), PWM or digital 0-12 VDC 60 mA maximum @ 12 VDC (60°C ; 140°F) Maximum load 200 ohms Auto reset fuse: 60 mA @ 60°C; 140°F, 100 mA @ 20°C ; 68°F Analog Output Resolution: 8 bits digital/analog converter
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin186
UL Label PlacementUL Listing labels must be positioned as shown in Figure 144.
Figure 144: UL Label Placement for the LN-VAVC-0U and LN-VAVCF-0U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 187
NXP-FSC-01U ControllerThe NXP-FSC-01U is a LONWORKS network Flexible System Controller. The NXP-FSC-01U, with its NXP-CPU-01U 386 CPU board, works in conjunction with all LNS-based LONWORKS network devices on an FTT-10 LONWORKS network.The NXP-FSC-01U supports 32 hardwired I/O points via any combination of three different I/O boards. These I/O boards are discussed in the following sections.
The NXP-CPU-01U CPU board is a computer and is the decision making component of the NXP-FSC-01U. The NXP-CPU-01U CPU does not have the ability to gather information, therefore I/O modules are used to gather information from the field. In turn, decisions the NXP-FSC-01U makes are communicated to the I/O modules through the communication interface bus on the NXP-CPU-01U CPU board.
On the NXP-CPU-01U CPU board, the decisions are made by the 386EX microcontroller and are passed on to the Neuron. The Neuron contains the MIP (Microprocessor Interface Program) that allows the information from the microcontroller to be passed on to other devices via the network. This transfer of information is done through the LONWORKS Network.
Figure 145: NXP-FSC-01U Controller
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin188
NXP-CPU-01U CPU Board
See Figure 147 for the 24 VAC power connection to the NXP-CPU-01U CPU board.
Figure 146: NXP-CPU-01U CPU Board
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 189
Connecting 24 VAC Power to the NXP-CPU-01U CPU BoardTo connect power to the NXP-CPU-01U CPU board (Figure 147):
1. Wire 24 VAC Hot to the Hot terminal of the NXP-CPU-01U CPU board.
2. Connect 24 VAC Neutral to the Neutral terminal of the NXP-CPU-01U CPU board.
Figure 147: 24 VAC to NXP-CPU-01U CPU Board Connections
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin190
Connecting I/O Boards to the NXP-CPU-386-01U CPU BoardThe I/O modules are connected to the NXP-CPU-01U board through a polarized ribbon cable. The NXP-CPU-01U board supports a total of 4 I/O modules. Four I/O modules can be connected through the EXPANSION A port on the NXP-CPU-01U board.
Note: Do not connect any I/O modules to EXPANSION B.
The I/O modules can be placed in any order. The first I/O module is connected directly to the NXP-CPU-01U through a 6 ft. or 3 ft. polarized ribbon cable. The remaining I/O modules are connected via a short polarized ribbon cable. The last I/O board on EXPANSION A (4 maximum) contains no ribbon cable connection on the connector labeled EXPANSION.
To connect the NXP-CPU-01U to any of the NXP-FSC-01U’s I/O modules:
1. Connect one end of the polarized ribbon cable to the connector labeled EXPANSION A on the NXP-CPU-01U board.
2. Connect the other end of the polarized ribbon cable to the connector labeled CONTROLLER on the first I/O module.
If there are more I/O modules to connect:
3. Connect one end of the short polarized ribbon cable to the connector labeled EXPANSION on theI/O module.
4. Connect the other end of the short polarized ribbon cable to the connector labeled CONTROLLER on the next I/O module.
Note: The last I/O module contains no ribbon cable on the connector labeled EXPANSION.
If I/O modules are snap-track mounted you must ground each I/O board to chassis ground using spade lug J1 or J2, depending on the I/O module.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 191
NXP-CPU-386-01U CPU Board to I/O Board Ribbon Cable PinoutsFigure 148 shows the pinouts for the straight-through 20-pin ribbon cable that connects the NXP-CPU-386-01U’s Expansion A port (J1) to the first FSC I/O board’s Controller port (JP3). These pinouts are also the same for the short straight-through ribbon cable, included with each I/O board, that connects each I/O board’s Expansion port (JP1) to the next I/O board’s Controller port (JP3).
Even though the physical ribbon cable is a straight-through cable, the module select lines are internally shifted to determine the physical order of each installed I/O board.
Figure 148: I/O Board Ribbon Cable Pinouts and Logic
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin192
Figure 149: I/O Board to NXP-CPU-01U Board Connections
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 193
I/O Board AddressingFor addressing purposes, the first board connected to the NXP-FSC-01U’s NXP-CPU-01U CPU board’s EXPANSION A port is board 1. The first point on each I/O board is point 1.
Note: Do not connect any I/O boards to the EXPANSION B port.
For example, in Figure 150, the 8 DO module is the first board connected to EXPANSION A so it is Board 1. The first point on that board is Point 1. Board 3 is also an 8 DO module and its last two digital output points are shown. Their addresses are Board 3, Point 7 and Board 3, Point 8.
Figure 150: I/O Board Addressing
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin194
TroubleshootingTable 53: FSC-01U TroubleshootingSymptom Possible Cause SolutionNo LEDs No AC Power Check LED 1 on NXP-CPU-01U CPU board. If
LED 1 is ON, use a volt meter across P1 to check for 24 VAC coming from the transformer.
Loss of Communications or Panel Down
1. LON disconnected
2. Unterminated network
1. Check LON connection on J3.2. Check for terminating resistors on the LON
connection (location of the resistors depends on the topology being used.
3. If LED 7 is flashing, the CPU is running. If LED 7 in not flashing, see below.
No Statuses from I/O Modules
1. Ribbon cable from NXP-CPU-01U to I/O modules is not connected properly.
2. I/O board are not connected in the order in which they were setup in the LON configuration tool.
1. Check the silk screen on the 8UI module to ensure that the jumper setting matches the field device.
2. See NXP-8UI-01U (8 UI Board) on page 197 to ensure the correct wiring for the field device.
Erratic Communications Multiple Nodes with the Same Address
Verify node assignment for each panel in the network.
Service Pin Not Detected at LON Configuration Tool
1. LON Disconnected2. Unterminated
1. Check LON connection on JP9.2. Check for terminating resistors on the LON
connection (location of the resistors depends on the topology being used)
LED 5 On Local Trouble - The LED is On when an I/O module is in Trouble. It will flash, if an I/O point is in Trouble.
Check the ribbon cable connection from the 386 CPU to the I/O modules.
LED 6 On Remote Trouble - The LED is ON when a remote module is in Trouble. It will flash, if a remote point is in Trouble.
Check all remote panels.
LED 7 Not Flashing Panel is locked up. Press the reset button and make sure the panel comes up. If the panel does not come up, then insert JP5 and press the Reset button. This will delete the panels’s data. When the panel comes up remove JP5. Reconfigure the node and update the CPL to the panel from the LON Configuration Tool.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 195
SpecificationsTable 54: NXP-FSC-01U Technical SpecificationsCategory SpecificationPower Requirements Voltage: 24 VAC, 60 Hz
Typical Consumption: 5 VAMaximum Consumption: 10 VA Protection: 5 Ampere removable fuse
Environmental Operating Temperature: 32° to 120°F (0° to 49°C) Relative Humidity: 0 to 93% Non condensing
General Processor: Neuron® 3150®; 8 bits, 10 MHzMemory: Non-volatile Flash 64 K (APB application and configuration properties)Communication: LonTalk® ProtocolMedia Channel: TP/FT-10; 78 kbpsTransceiver: Echelon® Free Topology Transceiver (FTT-10)Battery (for clock only): Real-time Clock ChipEnclosure: Material: PVC, flammable class VO Dimension: 4.88 x 8.9 x 2.48 inches (124 x 226 x 63 mm) Weight: 1.84 lbs (0.835 kg)Safety: CSA and UL Listed
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin196
UL Label PlacementUL Listing labels must be positioned as shown in Figure 165.
Figure 151: UL Label Placement for the NXP-FSC-01U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 197
NXP-FSC-01U I/O ModulesNXP-FSC-01U I/O modules communicate with the NXP-FSC-01U’s 386 CPU board regarding field information. A total of 4 I/O modules can be connected to the NXP-FSC-01U. A ribbon cable connects the 386 CPU board to the first I/O module to and to other I/O modules. The NXP-FSC-01U currently supports the use of 8 UI (Universal Input) modules, 4 DO (Digital Output) /4 AO (Analog Output) modules, and 8 DO (Digital Output) modules.
NXP-8UI-01U (8 UI Board)The 8 UI I/O module is a 4” x 6” circuit board that provides 8 universal inputs individually configurable for thermistors, dry contacts, pulsed inputs 4-20 mA transducers, 0-10V transmitters, or 0-5V transmitters. It is an optional I/O module for the NXP-FSC-01U.
Wiring
Power
Power (+24 VDC) is supplied to the 8 DO module through the 386 CPU. This is provided through a ribbon cable and is located at the I/O module connector JP2.
Spade Lug Connection
The 8 UI module has one spade lug (J2) that is used to ground the module to chassis ground.
If the 8 UI module is snap-track mounted it must be grounded to chassis ground by using the spade lug on J2. Use a short length of heavy gauge wire to attach to a suitable chassis ground. Backplane mounted 8 UI modules do not require this connection.
Figure 152: 8 UI Board
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin198
Universal Input Configuration
The 8 UI module allows a user to connect 8 various types of transducers and transmitters with varying voltages to the I/O module. The Universal Inputs are jumper selectable to allow for the following inputs: thermistors, dry contacts, pulsed inputs, 4-20mA transducers, 0-10V transmitters, or 0-5V transmitters. Figure 154 shows the Universal Input configuration.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Terminal Type Terminal Connection Required MOV ProtectionUniversal Input +24V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN1 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input GND 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN2 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN3 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input GND 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN4 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN5 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input GND 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN6 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN7 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input GND 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input IN8 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundUniversal Input +24V 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 153: NXP-8UI-01U I/O MOV Placement
Figure 154: Universal Input Configuration
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 199
Universal Input Labeling
The Universal Inputs are labeled IN1 to IN8.
The Universal Inputs are labeled IN1-IN8 and are located on terminal blocks JP14 and JP15 on the 8 UI module. The jumpers for the Universal Inputs are labeled JP6-JP13. Table 55 lists the Universal Input number with its corresponding jumper block number:
Universal Input Jumper Blocks
The Universal Inputs are jumper selectable to allow for thermistors, dry contacts, pulsed inputs (the dry contact jumper is used) 4-20mA transducers, 0-10V transmitters, or 0-5V transmitters. Figure 155 is an example of one of the jumper blocks for the Universal Inputs.
Table 55: 8 UI Universal Inputs and Corresponding Jumper NumbersJumper Block Number Universal Input NumberJP6 IN8
JP7 IN7
JP8 IN6
JP9 IN5
JP10 IN4
JP11 IN3
JP12 IN2
JP13 IN1
Figure 155: 8 UI Jumpers for Input Selection
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin200
Thermistor Wiring
To wire a thermistor to the 8 UI module:
1. Select the correct jumper setting for a thermistor (TH).
2. Connect one lead of the thermistor to an input terminal (IN1-IN8 on terminal block JP14 or JP15).
3. Connect the other lead to one of the GND terminals.
4. Ground the shield to chassis ground at ONE point. (It is recommended to ground at the controller.)
Note: Only a 10K Type II (CP Curve) thermistor may be used.
Since jumper block JP9 is used, you must use Universal Input 5. See Table 55.
Figure 156: 8 UI Thermistor Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 201
Dry Contact or Pulsed Input Wiring
To wire a thermistor to the 8 UI module:
1. Select the correct jumper setting for a thermistor (TH).
2. Connect one lead of the thermistor to an input terminal (IN1-IN8 on terminal block JP14 or JP15).
3. Connect the other lead to one of the GND terminals.
4. Ground the shield to chassis ground at ONE point. (It is recommended to ground at the controller.)
Note: Only a 10K Type II (CP Curve) thermistor may be used.
Note: Since jumper block JP9 is used, you must use Universal Input 5. See Table 55.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Figure 157: 8 UI Wiring for Dry Contacts
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin202
4-20 Milliamp Transducer Wiring
There are 3 scenarios for wiring 4-20mA transducers to the 8 UI module. These wiring connections are shown in the next three wiring examples.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Internal Loop Powered, 2-Wire 4-20mA Transducer
To wire an internal loop powered, 2-wire 4-20mA transducer to the 8 UI module:
1. Select the correct jumper setting for a 4-20mA transducer.
2. Connect the Signal Out lead from the 4-20mA transducer to an input terminal (IN1-IN8 on terminal block JP14 or JP15).
3. Connect the positive lead of the 4-20 milliampere transducer to the 24VDC terminal (+24V on terminal block JP14 or JP15).
Note: Since jumper block JP6 is used, you must use Universal Input 8. SeeTable 55
Figure 158: 8 UI 4-20 Milliamp Transducer Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 203
External Loop Powered, 2-Wire 4-20mA Transducer
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
To wire an external loop powered, 2-wire 4-20 mA transducer to the 8 UI module:
1. Select the correct jumper setting for a 4-20mA transducer.
2. Connect the Signal Out lead from the 4-20mA transducer to an input terminal (IN1-IN8 on terminal block JP14 or JP15).
3. Connect the positive lead of the 4-20mA transducer to the positive terminal on the UL® Listed External Power Supply.
4. Connect the negative terminal of the UL® Listed External Power supply to one of the GND terminals on terminal block JP14 or JP15.
Note: Since jumper block JP6 is used, you must use Universal Input 8. See Table 55.
IMPORTANT: If the power supply does not have floating ground, an isolation transducer module must be used between the transducer and the controller input to prevent the possibility of ground loops!
Figure 159: 8 UI External Loop Powered, 2-Wire 4-20mA Transducer
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin204
External Loop Powered 4-20mA Transducer
To wire an externally powered 4-20 mA transducer to the 8 UI module:
1. Select the correct jumper setting for a 4-20mA transducer.
2. Connect the Signal Out lead from the 4-20mA transducer to an input terminal (IN1-IN8 on terminal block JP14 or JP15).
3. Connect the negative lead of the 4-20mA transducer to one of the GND terminals on terminal block JP14 or JP15.
4. Connect the positive supply voltage lead of the 4-20mA transducer to the positive terminal on the UL® Listed External Power Supply.
5. Connect the negative supply voltage lead of the 4-20mA transducer to the negative terminal on the UL® Listed External Power Supply.
Note: Since jumper block JP6 is used, you must use Universal Input 8. See Table 55.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
IMPORTANT: If the power supply does not have floating ground, an isolation transducer module must be used between the transducer and the controller input to prevent the possibility of ground loops!
Figure 160: 8 UI External Loop Powered 4-20mA Transducer
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 205
0-10V Transmitter Wiring
There are 2 scenarios for wiring 0-10V transmitters to the 8 UI module. These wiring connections are shown in the next two wiring examples.
Internally Powered 0-10 Volt Transmitter
To wire an internally powered 0-10 volt transmitter to the 8 UI module:
1. Select the correct jumper setting for a 0-10V transmitter.
2. Connect the Signal Out lead from the 0-10V transmitter to an input terminal (IN1-IN8 on terminal block JP14 or JP15).
3. Connect the negative lead of the transmitter to one of the GND terminals on terminal block JP14 or JP15.
4. Connect the positive lead of the 0-10V transmitter to the +24VDC terminal (+24V on terminal block JP14 or JP15).
Note: Since jumper block JP6 is used, you must use Universal Input 8. See Table 55.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Figure 161: 8 UI 0-10V Transmitter Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin206
Externally Powered 0-10V Transmitter
To wire an externally powered 0-10 volt transmitter to the 8 UI module:
1. Select the correct jumper setting for a 0-10V transmitter.
2. Connect the Signal Out lead from the 0-10V transmitter to an input terminal (IN1-IN8 on terminal block JP14 or JP15).
3. Connect the negative lead of the transmitter to one of the GND terminals on terminal block JP14 or JP15.
4. Connect the positive supply voltage lead of the 0-10V transmitter to the positive terminal on the UL® Listed External Power Supply.
5. Connect the negative supply voltage lead of the 0-10V transmitter to the negative terminal on the UL® Listed External Power Supply.
Note: Since jumper block JP6 is used, you must use Universal Input 8. See Table 55.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
IMPORTANT: If the power supply does not have floating ground, an isolation transducer module must be used between the transducer and the controller input to prevent the possibility of ground loops!
Figure 162: 8 UI Externally Powered 0-10V Transmitter
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 207
0-5V Transmitter Wiring
There are 2 scenarios for wiring 0-5V transmitters to the 8 UI module. These wiring connections are shown in the next two wiring examples.
Internally Powered 0-5V Transmitter
To wire an internally powered 0-5 volt transmitter to the 8 UI module:
1. Select the correct jumper setting for a 0-5V transmitter.
2. Connect the Signal Out lead from the 0-10V transmitter to an input terminal (IN1-IN8 on terminal block JP14 or JP15).
3. Connect the negative lead of the transmitter to one of the GND terminals on terminal block JP14 or JP15.
4. Connect the positive lead of the 0-10V transmitter to the +24VDC terminal (+24V on terminal block JP14 or JP15).
Note: Since jumper block JP6 is used, you must use Universal Input 8. See Table 55.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Figure 163: 8 UI 0-5V Transmitter
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin208
Externally Powered 0-5V Transmitter
To wire an externally powered 0-5 volt transmitter to the 8 UI module:
1. Select the correct jumper setting for a 0-5V transmitter.
2. Connect the Signal Out lead from the 0-5V transmitter to an input terminal (IN1-IN8 on terminal block JP14 or JP15).
3. Connect the negative lead of the transmitter to one of the GND terminals on terminal block JP14 or JP15.
4. Connect the positive supply voltage lead of the 0-5V transmitter to the positive terminal on the UL® Listed External Power Supply.
5. Connect the negative supply voltage lead of the 0-5V transmitter to the negative terminal on the UL® Listed External Power Supply.
Note: Since jumper block JP6 is used, you must use Universal Input 8. See Table 55.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
IMPORTANT: If the power supply does not have a floating ground, an isolation transducer module must be used between the transducer and the controller input to prevent the possibility of ground loops!
Figure 164: 8 UI Externally Powered 0-5V Transmitter
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 209
TroubleshootingTable 56: 8 UI Module TroubleshootingSymptom Possible Cause SolutionNo LEDs No DC Power Check ribbon cable connections. If
the 8UI module is the only I/O module, one end of the polarized ribbon cable is connected to EXPANSION A or B on the 386 CPU board and the other end of the ribbon cable is connected to the JP3 (labeled CONTROLLER) on the 8UI module. If there is more than one I/O module on the controller, one end of the polarized ribbon cable is connected to the expansion connector labeled EXPANSION on the I/O module, and the other end of the ribbon cable is connected to the expansion connector labeled CONTROLLER on the I/O module.
Loss of Communications or No Statuses from Board
1. Improper Board Orientation
2. Microcontroller Locked Up
1. Check board orientation. All I/O modules are placed in the tub with the CONTROLLER expansion connector towards the top of the tub and the EXPANSION expansion connector towards the bottom of the tub.
2. Cycle power by disabling power on the Controller expansion connector (JP3). Leave the ribbon cable disconnected for a minimum of 5 seconds.
See Specifications on page 210 for the LED table and more information.
Invalid or Incorrect Statuses on the Inputs
1. Improper Jumper Setting
2. Improper Terminal Connections
1. Check the silk screen on the 8UI module to ensure that the jumper setting matches the field device.
2. See NXP-8UI-01U (8 UI Board) on page 197 to ensure the correct wiring for the field device.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin210
Specifications
UL Label PlacementUL Listing labels must be positioned as shown in Figure 165.
Table 57: 8 UI Board SpecificationsCategory SpecificationsPower input +24VDC @ 300mA from 386 CPU board
+5VDC @ 10mA from 386 CPU board
Power Consumption <11.5W
Processor Microchip Technologies PIC16C62
Inputs (8) jumper selectable: JP6 thru JP13• 0-5 VDC• 0-10 VDC• 4-20mA• 10K Thermistor• Dry Contacts: Wetted with 5mA Totalizer pulses @ 8 samples/second
Power to inputs 24VDC is available for powering input devices at 20mA per device maximum or 160mA total maximum
Status LEDs • LED 1 = Heart Beat (Green): Indicates that the microcontroller is functioning correctly. The LED flashes ON a half second and OFF a half second.
• LED 2 = Status (Red): Indicates that the CPU board is communicating with the 8 UI module. The LED flashes ON every time a communication occurs.
• LED 4 = Power (Green): Indicates that power is being supplied through the ribbon cable and converted to +5VDC on the board.
Dimensions 4 x 6 in (101.6 x 152.4 mm)
Figure 165: UL Label Placement for the NXP-8UI-01U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 211
NXP-8DO-01U (8 DO Board) The 8 DO I/O module is a 4” x 6” circuit board that provides 8 independently controllable relay outputs. It is an optional I/O module for the NXP-FSC-01.
Wiring
Power
Power (+24 VDC) is supplied to the 8 DO module through the 386 CPU. This is provided through a ribbon cable and is located at the I/O module connector JP2.
HOA Switch Settings
The 8 relay outputs have fully monitored HOA (HAND/OFF/AUTO) switches to allow you to:
• activate the relay (HAND)
• allow the CPU board to control the relay (AUTO)
• deactivate the relay (OFF).
Note: With power being supplied, the HOA switches function even if the microcontroller fails. There are 8 HOA switches used for wiring the digital outputs. Table 58 shows the HOA switch settings.
Figure 166: 8 DO Board
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin212
Spade Lug Connection
The 8 DO module has one spade lug (J1) that is used to ground the module to chassis ground.
If the 8 DO module is snap-track mounted it must be grounded to chassis ground by using the spade lug on J1. Use a short length of heavy gauge wire to attach to a suitable chassis ground. Backplane mounted 8 DO modules do not require this connection.
Table 58: 8 DO Module HOA Switch SettingsDigital Output Number
Terminal Block Number
HOA Switch Number
DO1 JP10 S8DO2 JP9 S7DO3 JP8 S6DO4 JP7 S5DO5 JP6 S4DO6 JP5 S3DO7 JP4 S2DO8 JP3 S1
Terminal Type Terminal Connection Required MOV ProtectionRelay Output NC None RequiredRelay Output C None RequiredRelay Output 1 NO None RequiredRelay Output NC None RequiredRelay Output C None RequiredRelay Output 2 NO None RequiredRelay Output NC None RequiredRelay Output C None RequiredRelay Output 3 NO None RequiredRelay Output NC None RequiredRelay Output C None RequiredRelay Output 4 NO None RequiredRelay Output NC None RequiredRelay Output C None RequiredRelay Output 5 NO None RequiredRelay Output NC None RequiredRelay Output C None RequiredRelay Output 6 NO None RequiredRelay Output NC None RequiredRelay Output C None RequiredRelay Output 7 NO None RequiredRelay Output NC None RequiredRelay Output C None RequiredRelay Output 8 NO None RequiredNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 167: NXP-8DO-01U I/O MOV Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 213
Digital Output Wiring
Maintained relays, momentary relays and floating devices (floating actuators) are 3 types of digital outputs that can be wired to the 8 DO module. These wiring connections are shown in the three wiring examples below.
Maintained Relay Wiring
Note: The rating for this output is 24VAC at 1.0 amps.
To wire a Maintained relay to the 8 DO module:
1. Determine if the device is normally open (NO) or normally closed (NC).
2. Connect one lead from the device to the desired NO or NC terminal (on terminal blocks JP7-JP10).
3. Connect the other lead from the device to the Neutral lead of the UL® Listed External Power Supply.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
4. Connect the Hot lead of the UL® Listed External Power Supply to the Common terminal (C on terminal blocks JP7-JP10).
Figure 168: 8 DO Maintained Relay Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin214
Momentary Relay Wiring
Note: The rating for this output is 24VAC at 0.5 amps.
This example uses a GE® RR-7 Lighting Relay as the momentary relay.
To wire a Momentary relay to the 8 DO module:
1. Determine if the device is normally open (NO) or normally closed (NC).
2. Connect the Black wire (OFF) from the device to the desired NO or NC terminal (on terminal blocks JP7-JP10).
3. Connect the Red wire (ON) from the device to the desired NO or NC terminal (on terminal blocks JP7-JP10).
4. Connect the Blue wire (24VAC) from the device to the Neutral lead of the UL® Listed External Power Supply.
5. Connect the Hot lead of the UL® Listed External Power Supply to the Common terminals (C on terminal blocks JP7-JP10).
Note: The recommended pulse time is 1 second (minimum 1 second).
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Figure 169: 8 DO Momentary Relay Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 215
Floating Device Wiring
Note: The rating for this output is 24VAC at 1.0 amps.
To wire a Floating Actuator to the 8 DO module:
1. Determine if the device is normally open (NO) or normally closed (NC).
2. Connect the Increment lead from the device to the desired NO or NC terminal (on terminal blocks JP7-JP10).
3. Connect the Decrement lead from the device to the desired NO or NC terminal (on terminal blocks JP7-JP10).
4. Connect the Ground lead from the device to the Neutral lead of the UL® Listed External Power Supply.
5. Connect the Hot lead of the UL® Listed External Power Supply to the Common terminals (C on terminal blocks JP7-JP10).
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Figure 170: 8 DO Floating Devices Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin216
TroubleshootingTable 59: 8 DO Module TroubleshootingSymptom Possible Cause SolutionNo LEDs No DC Power Check ribbon cable connections. If the 8 DO
module is the only I/O module, one end of the polarized ribbon cable is connected to EXPANSION A or B on the 386 CPU board and the other end of the ribbon cable is connected to the JP3 (labeled CONTROLLER) on the 8 DO module. If there is more than one I/O module on the controller, one end of the polarized ribbon cable is connected to the expansion connector labeled EXPANSION on the I/O module, and the other end of the ribbon cable is connected to the expansion connector labeled CONTROLLER on the I/O module.
Loss of Communications or No Statuses from Board
1. Improper Board Orientation
2. Microcontroller Locked Up
1. Check board orientation. All I/O modules are placed in the tub with the CONTROLLER expansion connector towards the top of the tub and the EXPANSION expansion connector towards the bottom of the tub.
2. Cycle power by disabling power on the Controller expansion connector (JP3). Leave the ribbon cable disconnected for a minimum of 5 seconds.
See Specifications on page 217 for the LED table and more information.
Point Commands Do Not Work HOA Switch in Wrong Position Check the HOA switch position. The HOA switch must be in AUTO to be commanded from the Network tool.
Output Not Functioning in HAND mode.
Bad 8 DO Module Send 8 DO module back or use spare output point if available
Digital outputs operating backwards from field.
Wrong connection of Normal Open or Normally Closed for Field Device.
1. Check the silk screen on the 8 DO module to ensure that the jumper setting matches the field device.
2. See NXP-8DO-01U (8 DO Board) on page 211 to ensure the correct wiring for the field device.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 217
SpecificationsTable 60: 8 DO Module SpecificationsCategory SpecificationsPower input +24VDC @ 300mA from 386 CPU board
+5VDC @ 10mA from 386 CPU board
Power Consumption <11.5W
Processor Microchip Technologies PIC16C62
Outputs (8) relay outputs: Form C, 24VAC@ 1.0A, UL Listed, HOA operation and LED indicatorRelay ON time programmable with 100 mS resolution (+/- 10%) and 1,000 seconds maximum.
Relay Output HOA Switches
S1 thru S8: Fully monitored Hand/Off/Auto (HOA) switchesHand: User controlOff: Deactivate relay outputAuto: FSC CPU board control
Status LEDs • LED 1 = Heart Beat (Green): Indicates that the microcontroller is functioning correctly. The LED flashes ON a half second and OFF a half second.
• LED 2 = Status (Red): Indicates that the CPU board is communicating with the 8 UI module. The LED flashes ON every time a communication occurs.
• LED 3 = HOA (Yellow): Indicates that one or more of the outputs is in a mode other than AUTO.
• LED 4 = ON (Red): Indicates that Digital Output 8 is ON1 • LED 5 = ON (Red): Indicates that Digital Output 7 is ON1 • LED 6 = ON (Red): Indicates that Digital Output 6 is ON1 • LED 7 = ON (Red): Indicates that Digital Output 5 is ON1 • LED 8 = ON (Red): Indicates that Digital Output4 is ON1 • LED 9 = ON (Red): Indicates that Digital Output 3 is ON1 • LED 10 = ON (Red): Indicates that Digital Output 2 is ON1 • LED 11 = ON (Red): Indicates that Digital Output 1 is ON1 • LED 12 = Power (Green): Indicates that power is being supplied through the ribbon
cable and converted to +5VDC on the board.
DO Settings DO LocationNumber
DO Number (Setting)
JP3 DO 8 (Normally Open or Normally Closed)
JP4 DO7 (Normally Open or Normally Closed)
JP5 DO6 (Normally Open or Normally Closed)
JP6 DO5 (Normally Open or Normally Closed)
JP7 DO4 (Normally Open or Normally Closed)
JP8 DO3 (Normally Open or Normally Closed)
JP9 DO2 (Normally Open or Normally Closed)
JP10 DO1 (Normally Open or Normally Closed)
Ambient Operating Conditions
32 to-120 °F (0 to 49 C°) at 10% to 93% non-condensing
Dimensions 4 x 6 in (102 x 152 mm)(4) corner mounting holes 0.156 in (4.0 mm)
1. Either commanded thru the LONWORKS network configuration tool or switched to HAND mode.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin218
UL Label PlacementUL Listing labels must be positioned as shown in Figure 171.
Figure 171: UL Label Placement for the NXP-8DO-01U
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 219
NXP-4DO4AO-01U (4 DO/4 AO Board) The 4 DO/4 AO I/O module is a 4” x 6” circuit board that is optional I/O module for the NXP-FSC-01.
The 4 DO/4 AO module provides 4 independently controllable relay outputs and 4 analog outputs. The relay outputs have fully monitored HOA (HAND/OFF/AUTO) switches to allow the user the ability to activate the relay (HAND), allow the CPU board to control the relay (AUTO), or deactivate the relay (OFF). The analog outputs have HA (HAND/AUTO) switches to allow the user the ability to adjust the voltage of the output from 0 to 10 volts (HAND), or allow the CPU board to control the voltage of the output (AUTO).
Wiring
Power
Power (+24 VDC) is supplied to the 8 DO module through the 386 CPU. This is provided through a ribbon cable and is located at the I/O module connector JP2.
HOA Switch Settings
The 4 relay outputs have fully monitored HOA (HAND/OFF/AUTO) switches to allow you to:
• activate the relay (HAND)
• allow the CPU board to control the relay (AUTO)
• deactivate the relay (OFF).
The analog outputs are labeled AO1(+)(-) - AO4(+)(-) on terminal blocks JP3-JP6. The digital outputs are labeled 1 NO C NC - 4 NO C NC on terminal blocks JP7-JP10.
Figure 172: 4 DO/4 AO Board
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin220
The analog outputs have corresponding HA switches. Table 61 shows the analog output, their corresponding terminal block number and HA switch number.
The digital outputs have corresponding HOA switches. Table 62 shows the digital inputs with their corresponding terminal block number and HOA switch number.
Spade Lug Connection
The 4 DO/4 AO module has one spade lug (J1) that is used to ground the module to chassis ground.
Note: If the 4 DO/4 AO module is snap-track mounted it must be grounded to chassis ground by using the spade lug on J1. Use a short length of heavy gauge wire to attach to a suitable chassis ground. Backplane mounted 4 DO/4 AO modules do not require this connection.
Table 61: 4 DO/4 AO Board HA Switch SettingsAnalog Output Number
Terminal Block Number
HA Switch Number
1 JP6 S82 JP5 S73 JP4 S64 JP3 S5
Table 62: 4 DO/4 AO Board Digital Output HOA Switch SettingsDigital Output Number
Terminal Block Number
HOA Switch Number
1 JP10 S42 JP9 S33 JP8 S24 JP7 S1
Terminal Type Terminal Connection Required MOV ProtectionRelay Output NC None RequiredRelay Output C None RequiredRelay Output 1 NO None RequiredRelay Output NC None RequiredRelay Output C None RequiredRelay Output 2 NO None RequiredRelay Output NC None RequiredRelay Output C None RequiredRelay Output 3 NO None RequiredRelay Output NC None RequiredRelay Output C None RequiredRelay Output 4 NO None RequiredAnalog Output AO1- 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output AO1+ 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output AO2- 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output AO2+ 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output AO3- 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output AO3+ 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output AO4- 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundAnalog Output AO4+ 1 piece of a SMOKE-MOVKIT-0 installed between Terminal and Earth GroundNote: the SMOKE-MOVKIT-0 contains 10 individual MOVs.
Figure 173: NXP-4DO4AO-01U I/O MOV Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 221
Digital Output Wiring
Maintained relays, momentary relays and floating devices (floating actuators) are 3 types of digital outputs that can be wired to the 4 DO/4 AO module. The wiring connections are shown in the following examples:
Maintained Relay Wiring
Note: The rating for this output is 24VAC at 1.0 amps.
To wire a Maintained relay to the 4 DO/4 AO module:
1. Determine if the device is normally open (NO) or normally closed (NC).
2. Connect one lead from the device to the desired NO or NC terminal (on terminal blocks JP7-JP10).
3. Connect the other lead from the device to the Neutral lead of the UL® Listed External Power Supply.
4. Connect the Hot lead of the UL® Listed External Power Supply to the Common terminal (C on terminal blocks JP7-JP10). See Figure 174.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Figure 174: 4 DO/4 AO Maintained Relay Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin222
Momentary Relay Wiring
Note: The rating for this output is 24VAC at 0.5 amps. This example uses a GE RR-7 Lighting Relay as the momentary relay.
To wire a Momentary relay to the 4 DO/4 AO module:
1. Determine if the device is normally open (NO) or normally closed (NC).
2. Connect the Black wire (OFF) from the device to the desired NO or NC terminal (on terminal blocks JP7-JP10).
3. Connect the Red wire (ON) from the device to the desired NO or NC terminal (on terminal blocks JP7-JP10).
4. Connect the Blue wire (24VAC) from the device to the Neutral lead of the UL® Listed External Power Supply.
5. Connect the Hot lead of the UL® Listed External Power Supply to the Common terminals (C on terminal blocks JP7-JP10). See Figure 175.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Figure 175: 4 DO/4 AO Momentary Relay Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 223
Floating Actuator Wiring
Note: The rating for this output is 24VAC at 1.0 amps.
To wire a Floating actuator to the 4 DO/4 AO module:
1. Determine if the device is normally open (NO) or normally closed (NC).
2. Connect the Increment lead from the device to the desired NO or NC terminal (on terminal blocks JP7-JP10).
3. Connect the Decrement lead from the device to the desired NO or NC terminal (on terminal blocks JP7-JP10).
4. Connect the Ground lead from the device to the Neutral lead of the UL® Listed External Power Supply.
5. Connect the Hot lead of the UL® Listed External Power Supply to the Common terminals (C on terminal blocks JP7-JP10). See Figure 176.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Figure 176: 4 DO/4 AO Floating Actuator Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin224
Analog Output Wiring
To wire an analog output to the 4 DO/4 AO module:
1. Connect the positive lead from the analog device to the desired + AO terminal (AO1-AO4 on terminal blocks JP3-JP6).
2. Connect the negative lead from the analog device to the - AO terminal (AO1-AO4 on terminal blocks JP3-JP6). See Figure 177.
Note: See SMOKE-MOVKIT-0 and SMK-MOVKIT-MSTP Transient Protection Requirements for LON I/O Terminals on page 175 for details on required SMOKE-MOVKIT-0 connections.
Figure 177: 4 DO/4 AO Analog Output Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 225
TroubleshootingTable 63: 4 DO/4 AO Module TroubleshootingSymptom Possible Cause SolutionNo LEDs No DC Power Check ribbon cable connections. If the
4 DO/4 AO module is the only I/O module, one end of the polarized ribbon cable is connected to EXPANSION A or B on the 386 CPU board and the other end of the ribbon cable is connected to the JP3 (labeled CONTROLLER) on the 4 DO/4 AO module. If there is more than one I/O module on the controller, one end of the polarized ribbon cable is connected to the expansion connector labeled EXPANSION on the I/O module, and the other end of the ribbon cable is connected to the expansion connector labeled CONTROLLER on the I/O module.
Loss of Communications or No Statuses from Board
1. Improper Board Orientation
2. Microcontroller Locked Up
1. Check board orientation. All I/O modules are placed in the tub with the CONTROLLER expansion connector towards the top of the tub and the EXPANSION expansion connector towards the bottom of the tub.
2. Cycle power by disabling power on the Controller expansion connector (JP3). Leave the ribbon cable disconnected for a minimum of 5 seconds.
See Specifications on page 226 for the LED table and more information.
Point Commands Do Not Work HOA Switch in Wrong Position Check the HOA switch position. The HOA switch must be in AUTO to be commanded from the Network tool.
Output Not Functioning in HAND mode.
Bad 4DO/4AO Module Send 4DO/4AO module back or use spare output point if available
Digital outputs operating backwards from field.
1. Wrong connection of Normal Open or Normally Closed for Field Device.
1. Check the silk screen on the 4 DO/4 AOI module to ensure that the jumper setting matches the field device.
2. See NXP-4DO4AO-01U (4 DO/4 AO Board) on page 219 to ensure the correct wiring for the field device.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin226
SpecificationsTable 64: 4 DO/4 AO Module SpecificationsCategory SpecificationsPower input +24VDC @ 300mA from NXP-CPU-01U board
+5VDC @ 10mA from NXP-CPU-01U board
Power Consumption <11.5W
Processor Microchip Technologies PIC16C62
Digital Outputs (4) relay outputs: Form C, 24VAC@ 1.0A, UL Listed, HOA operation and LED indicatorRelay ON time programmable with 100 mS resolution (+/- 10%) and 1,000 seconds maximum.
Relay Output HOA Switches
S1 thru S4: Fully monitored Hand/Off/Auto (HOA) switchesHand: User controlOff: Deactivate relay outputAuto: FSC CPU board control
Digital Output Jumpers (4) Digital Output jumpers:JP7 = Digital Output 4 (N.O. or N.C)JP8 = Digital Output 3 (N.O. or N.C)JP9 = Digital Output 2 (N.O. or N.C)JP10 = Digital Output 1 (N.O. or N.C)
Analog Outputs (4) Analog Outputs: Resolution: 0-10 VDC@5mA 8 bit resolutionResponse Time: 2 seconds (change form 10% to 90% of full scale)H/A Operation: Uses on-board potentiometers - single-turn, thumbnail adjustment
Analog Output Jumpers (4) Analog Output jumpers:JP3 = Analog Output 4 (+ or -)JP4 = Analog Output 3 (+ or -)JP5 = Analog Output 2 (+ or -)JP6 = Analog Output 1 (+ or -)
Analog Output Hand/Auto (HA) Switches
S5 thru S8: Fully monitored Hand/Auto switchesHand: User controlAuto: FSC CPU board control
Status LEDs • LED 1 = Heart Beat (Green): Indicates that the microcontroller is functioning correctly. The LED flashes ON a half second and OFF a half second. Normally Flashing
• LED 2 = Status (Red): Indicates that the CPU board is communicating with the 8 UI module. The LED flashes ON every time a communication occurs. Normally Flashing.
• LED 4 = HOA (Yellow): Indicates that one or more of the outputs is in a mode other than AUTO. Normally Off (When no HOA switches are set to Hand or Auto).
• LED 5 = ON (Red): Indicates that Digital Output 4 is ON1.• LED 6 = ON (Red): Indicates that Digital Output 3 is ON1.
• LED 7 = ON (Red): Indicates that Digital Output 2 is ON1
• LED 8 = ON (Red): Indicates that Digital Output1 is ON1 • LED 9 = Power (Green): Indicates that power is being supplied through the ribbon
cable and converted to +5VDC on the board. Normally On.
Dimensions 4 x 6 in (10.16 x 15.24 cm)
1. Either commanded thru the LONWORKS network configuration tool or switched to HAND mode. Normally On when the DO is On.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 227
UL Label PlacementUL Listing labels must be positioned as shown in Figure 178.
i.LON 600 LONWORKS/IP Server Router (72603-U)The i.LON 600 LONWORKS/IP Server (Figure 179) is an EIA-852 compliant device that allows LonTalk-to-IP communication and provides reliable and secure access to devices.
Figure 178: UL Label Placement for the NXP-4DO4AO-01U
Figure 179: iLON 600 LonTalk-to-IP Router
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin228
Figure 180 shows an example iLON 600 LonTalk-to-Router Connection Layout
Figure 180: Example iLON 600 LonTalk-to-Router Connection Layout
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 229
Specifications
UL Label PlacementUL Listing labels must be positioned as shown in Figure 181.
Table 65: iLON600 LonTalk Router SpecificationsCategory SpecificationsProcessor AMD Au1000 32-bit RISC
Channel Type TP/FT10
LonWorks Twisted Pair Connector
Screw Terminals
Ethernet Port 10/100 BaseT, auto-selecting, auto polarity
Ethernet Connector RJ-45
Console Interface EIA-232, 9600 baud (8 data bits, no parity, 1 stop bit)
Console Connector DB-9
Operating Input Voltage +24V AC or DC, <15 Watts (Model 72603R)
Power Connector Screw Terminals
Controls (Switches) Reset and Service switches
Indicators (LEDs) Power On, Ethernet Link, Activity, 10/100 Mbps, LonWorks Tx/Rx, Connect
Neuron Chip Service Pin Function
Service pin message controlled by console application or hardware service switch
Operating Temperature 32 to 120°F (0 to 49°C)
Operating Humidity 10 to 93% RH, Non-condensing
Enclosure 8TE DIN
Dimensions (H x W x D) 3.51 x 5.47 x 2.60 in (8.9 x 13.8 x 6.6 cm)
EMC FCC Part 15 Class B and EN55022 Class B, EN55024, CISPER 22 Class B, VCCI Class B
Agency Listings UL 60950, cUL, C22.2 No. 60950-00, TÜV EN60950, CE, C-Tick
Figure 181: 72603-iLON 600 Router
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin230
NXE-RPT-FTT-U LON RepeaterThe NXE-RPT-FTT-U LON repeater serves two purposes:
1. Isolate Smoke Control LON equipment from Non-Smoke Control LON equipment.
2. Extend the physical length of a single LON bus.
Wiring
Figure 182: NXW-REP-FTT-U Repeater
Figure 183: NXE-REP-FTT-U Repeater Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 231
Specifications
UL Label PlacementUL Listing labels must be positioned as shown in Figure 184.
Table 66: NXE-REP-FTT-U SpecificationsCategory SpecificationsPower 24 VAC
Network LONWORKS FTT10
Network Topology Bus or Free (jumper selectable)
Dimensions (H x W x D) 5.50 x 3.29 x 1.25 in (13.97 x 8.36 x 3.18 cm)
Figure 184: NXE-REP-FTT-U UL Label Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin232
NXE-FTT-FTT-U RouterThe Johnson Controls NXE-FTT-FTT-U (Router- FT-10 to FT-10) (Echelon’s LPR10 model number 72603R) is a two-channel LONWORKS (ANSI/EIA709.1) router that interfaces between TP/FT10 and TP/FT10 twisted-pair channels. It is used to manage network traffic, increase the total number of LONWORKS devices, and increase the cabling length in a system. Figure 185 shows the NXE-FTT-FTT-U router.
Wiring
Figure 186 shows the NXE-FTT-FTT-U faceplate.
Figure 185: NXE-FTT-FTT-U LonTalk TP/FT10-to-TP/FT10 Router
Figure 186: NXE-FTT-FTT Faceplate View
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 233
Network Communications
Figure 187 shows the NEX-FTT-FTT-U network wiring connections.
Figure 187: NXE-FTT-FTT-U Wiring Connections (cover removed)
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin234
Specifications
UL Label PlacementUL Listing labels must be positioned as shown in Figure 188.
Table 67: NXE-FTT-FTT-U SpecificationsCategory SpecificationsProcessor Two Neuron 3150 Chips, 10Mhz
Service Function Recessed service switch (wink) LED.
Transceiver Type TP/FT10 to TP/FT10
Input Power 24 VAC or DC @ 2VA, internally isolated power supply
Mounting Type 2 or 2D DIN base plate
Temperature 32 to 120°F (0 to 49°C), operating and non-operating
Humidity 10 to 93% RH
EMI FCCA, CE Mark
Safety Agency UL 916
Dimensions 3.9 x 3.9 1.0 in (10 x 10 x 2.5 cm)
Figure 188: NXE-FTT-FTT-U UL Label Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 235
Smoke Control System Software
SCTThe SCT is used in all phases of engineering, installation, and commissioning of NAEs, FC bus devices, and LON devices that make up the Metasys smoke control system. The SCT is used offline to create archive databases that are downloaded to a smoke control NAE. The Logic Connector Tool (LCT), contained in the SCT, was used to create the standard smoke control applications included on the Branch Purchase Package (BPP) CD.
The standard smoke control applications can be installed and executed on any smoke control NAE. Use the standard smoke control applications as written, any sequence modification to the LCT program must be pre-approved by the Authority Having Jurisdiction (AHJ). The SCT tool must not be accessible to anyone other than designated qualified technicians who are responsible for installing, commissioning, and maintaining the smoke control site configuration. Password restriction in conjunction with SCT accessibility will prevent unauthorized editing of the smoke control sequences.
LONWORKS Network Configuration ToolUse a LONWORKS network configuration tool such as LonBuilder, MCL Tool, or LonMaker to commission the LONWORKS network smoke control devices.
System Programming Guidelines for Smoke ControlWhen programming the system for smoke control applications, the system must conform to the guidelines outlined below.
Follow these guidelines when defining systems and objects:
• Name all systems used for smoke control in a manner that makes identification obvious. For example, the air handling unit serving the west wing on the third floor might be called AHU3_W and the stairwell pressurization system might be called STR_PRES.
• Name all objects within a system used for smoke control in a manner that makes identification obvious. For example, the outdoor air damper might be called "OSA_DMPR" and the mixed air damper might be called "MXA_DMPR."
• Use engineering units that are appropriate to easily determine the current status of a device.
• Use the 24-character expanded ID attribute in an object definition window to provide information that is pertinent to an object’s type and location and is easily understood in an emergency situation.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin236
Enclosures and AccessoriesAll enclosures must be of correct metal thickness for its size, mounted, and wired in accordance with the UL 864 Control Units and Accessories for Fire Alarm Systems, Ninth Edition specification.
Mount NAE55 controllers, switches, routers and all other equipment in the smoke control network in a UL Listed enclosure. See the installation information packaged with each product. See Table 72 on page 251 for enclosure and accessory part numbers and specifications.Table 68: PAN-PWRSP-U Device LimitationsDevice(s) Allowed to Use a Single PAN-PWRSP-U Power SupplyFEU2610FEU2620FEU1610FEU1620IOU4710IOM3710IOM2710IOM1710FEU2610 and 1 IOM1710FEU2620 and 1 IOM1710IOU4710 and 1 IOM1710IOM3710 and 1 IOM1710IOM2710 and 1 IOM1710Two IOM1710sFEU2610 and Smoke Control Accesories (Total power not to exceed the PAN-PWRSP-U 96VA limit.)FEU2620 and Smoke Control Accesories (Total power not to exceed the PAN-PWRSP-U 96VA limit.)IOU4710 and Smoke Control Accesories (Total power not to exceed the PAN-PWRSP-U 96VA limit.)IOM3710 and Smoke Control Accesories (Total power not to exceed the PAN-PWRSP-U 96VA limit.)IOM2710 and Smoke Control Accesories (Total power not to exceed the PAN-PWRSP-U 96VA limit.)IOM1710 and Smoke Control Accesories (Total power not to exceed the PAN-PWRSP-U 96VA limit.)Note: Any other combination requires the use of a PAN-PWRSP-U and at least one PAN-96VAXFR-U.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 237
PAN-PWRSP-U Power Supply The PAN-PWRSP-U Power Supply is a UL® Listed and CSA Certified Class 2 120/24 VAC power supply with a duplex outlet, and power switch. An overcurrent circuit breaker is provided for each of the two 120 VAC outlets.
Figure 189: PAN-PWRSP-U Power Supply
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin238
Wiring the PAN-PWRSP-U Power Supply
PAN-PWRSP-U Power Supply Connections
Main Power Terminal Connections
120 VAC supply power connects to a three-terminal terminal block mounted on top of the power supply.
To wire the PAN-PWRSP-U Main Power terminal, connect the 120 VAC supply wires to the respective Hot (H), Neutral (N) and Ground (G) terminals of the Main Power Input block (Figure 190).
On/Off Switch
An On/Off rocker switch on the right side of the power supply controls 120 VAC at the secondary power terminal block and 24 VAC out from the power supply. The two utility outlets are unswitched and always remain Hot.
Figure 190: PAN-PWRSP-U Power Supply
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 239
Switched 120 VAC Secondary Output
A switched 120 VAC source is available from the PAN-PWRSP’s Secondary Output terminal block. This is used to power a PAN-96VAXFR-U power supply that is mounted in the same enclosure as the PAN-PWRSP-U. A rocker switch on the right side of the PAN-PWRSP-U controls the 120 VAC output.
To connect to the Switched Output:
1. Connect the Hot side of the PAN-96VAXFR-U to the Hot terminal of the PAN-PWRSP-U’s Secondary Power terminal block.
2. Connect the Neutral wire of the PAN-96VAXFR-U to the Neutral terminal of the PAN-PWRSP-U’s Secondary Power terminal block.
Note: See Figure 193 on page 242 for wiring details.
Switched 24 VAC to Field - Wiring Connections
1. Connect the PAN-PWRSP-U’s Orange wire to the field device’s 24 VAC Hot terminal connection.
2. Connect the PAN-PWRSP-U’s Brown wire to the field device’s 24 VAC COM (Neutral) terminal connection.
Utility Plugs
Two factory-wired, unswitched 120 VAC utility plugs are part of the PAN-PWRSP-U power supply. One plug is located on the front of the power supply and the other is located on the right side. Connecting 120 VAC to the Main Power input terminal automatically powers the utility plugs.
Specifications
IMPORTANT: Be sure the Ground lug for the PAN-PWRSP-U and PAN-96VAXFR-U are both securely mounted to the backplane.
Table 69: PAN-PWRSP-U Power Supply SpecificationsCategory DescriptionPower 96 VA 120/24 VAC power assembly
Receptacle Two receptacles 120 VAC, 5A manual resettable thermal protection circuit breaker
Primary Voltage 120 VRMS
Secondary Voltage 24 VAC, 3.5A Max.
Transformer Insulation Class 130
Transformer Class Class 2
Operating Temperature 0 to 49° C (32 to 120° F)
Agency Listings UL® 1585CSA C22.2 No. 66-1988
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin240
UL Label PlacementUL Listing labels must be positioned as shown in Figure 191.
Figure 191: PAN-PWRSP-U UL Label Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 241
PAN-96VAXFR-U Power Supply The PAN-96VAXFR-U Power Supply is a UL® Listed and CSA Certified Class 2 120/24 VAC power supply. It is used in conjunction with a PAN-PWRSP-U power supply when loads exceed the PAN-PWRSP-U’s 96 VA limit.
Specifications Table 70: PAN-96VAXFR-U Power Supply SpecificationsCategory DescriptionPower 96 VA 120/24 VAC power assembly
Receptacle 4A secondary, manual resettable thermal protection circuit breaker
Primary Voltage 120 VRMS
Secondary Voltage 24 VAC, 3.5A Max.
Transformer Insulation Class 130
Transformer Class Class 2
Operating Temperature 0 to 49° C (32 to 120° F)
Agency Listings UL® 1585CSA C22.2 No. 66-1988
Figure 192: PAN-96VAXFR-U Power Supply
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin242
The secondary output terminal of the PAN-PWRSP-U provides a switched 120 VAC to the PAN-96VAXFR-U.
Figure 193: PAN-PWRSP-U to PAN-96VAXFR-U Wiring
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 243
UL Label PlacementUL Listing labels must be positioned as shown in Figure 194.
Figure 194: PAN-PWRSP-U and PAN-96VAXFR-U UL Label Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin244
Power Distribution Panel and Enclosure (PA0P00010FC0-U)The PA0P00010FC0-U is a prewired, preassembled Standard Control Panel and enclosure that contains four 96 VA 120/24 VAC class 2 transformers, each with 4 Amp manual reset secondary protection for powering Variable Air Volume (VAV) box controllers. This predesigned solution saves both time and money by not requiring individual transformers in every VAV box.
The PA0P00010FC0-U Control Panel is shipped complete, mounted in a 16 in. W x 20 in. H steel enclosure. In addition to the four 96VA transformers, the assembly also contains low voltage terminal blocks and a 10 Amp circuit breaker that provides primary protection for all four transformers.
The PA0P00010FC0-U contains terminals that are prewired and prelabeled to match each transformer, making installation, commissioning, and servicing quicker and easier.
Figure 195: PA0P00010FC0-U Assembly 24 VAC Power Distribution Control Panel
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 245
Maximum devices per each 96 VA low voltage power distribution trunk are as follows:
1. A single VMA1610 draws a maximum of 14 VA, which means you can have a maximum of 6 VMA1610s per 96 VA transformer.
2. A single VMA1620 draws a maximum of 14 VA. Adding relays, actuators, etc. adds another 6 VA which means you can have a maximum of 5 VMA1620s per 96 VA transformer.
3. A single LN-VAVC or LN-VAVCF draws a maximum of 10 VA, which means you can have a maximum of 10 LN-VAVs per trunk.
The above recommendations are based on a system where every controller is not fully loaded at all times.
SpecificationsTable 71: PA0P00010FC0-U SpecificationsCategory DescriptionTerminal Blocks Terminal Blocks: 1/4 in. (6 mm) Wire Slots
Wiring All Components are Prewired to Terminal Blocks
Wire Size Ground Wire: 14 AWG; Transformer Wires: 18 AWG
Enclosure Rating Type 1
Ambient Operating Condition 32 to 120°F (0 to 49°C)10 to 93% RH
Transformers Four PAN-96VAXFR-U Transformers, Power, Panel Mount, 120 V Primary, 24 V Secondary, 96 VA, Split Bobbin, 4 Amp Secondary Circuit Breaker, 10 Amp Primary Circuit Breaker that provides primary protection for all four transformers.
Enclosure Type 1 with keyed lock, 16 in. W x 20 in. H x 6.62 in. D (406 mm W x 508 mm H x 168 mm D)
Agency Compliance Control Panel: UL 508A Rated (cULus); Enclosure: UL 50 Rated, CSA Approved
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin246
UL Label PlacementUL Listing labels must be positioned as shown in Figure 196 and Figure 197.
Figure 196: PA0P00010FC0-U UL Device Label Placement
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 247
Smoke Control Listed Accessories in a Smoke Control PanelControl accessories that are smoke control listed, such as the Acromag NU-RPT101-0U repeater, NXE-FTT-FTT-U router, NXE-RPT-FTT-U LON repeater, iLON600 72603-U router, NU-MC101-0U and NU-MC102-0U media converters, etc. can be mounted in a smoke control enclosure provided:
1. There is enough space to mount the devices.
2. The total power required by the smoke control devices and the control accessories does not exceed the enclosure’s power supply transformer rating. A second transformer may be required to satisfy total power requirements.
3. Addition of the control accessories does not cause the ambient temperature inside the enclosure to exceed 120° F (49° C).
Non-Smoke Control Listed Accessories in a Smoke Control PanelControl accessories that are non-smoke control listed, such as relays, pneumatics, etc. can NOT be mounted in a smoke control enclosure. A separate enclosure must be mounted to install all non-smoke control accessories in.
Figure 197: PA0P00010FC0-U UL Label Placement - Enclosure Door
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin248
Ordering Smoke Control EnclosuresAll UL 864 UUKL Ninth Edition smoke control enclosures are ordered as custom enclosures. There are three possible ways to order Smoke Control Enclosures:
1. Custom enclosures using UL 864 UUKL Ninth Edition listed NAE55x0-1U, NAE45x0-1U, NAE35x0-1U, FECx6x0-0U, IOMx710-0U, LN-PRGxA-0U, controllers are ordered through the Johnson Controls, Control Panels website, Custom Panels section. Order form # 1634-a is used to place a custom panel order.
• Be sure to check the Smoke Control checkbox in the Special Conditions section of this form.
• If the local authority requires that a Union label be affixed to the panel, then check the Union Label Required checkbox.
2. Custom enclosures using the UL 864 UUKL Ninth Edition listed NXP-FSC-01U are ordered from Louisville Kentucky. Contact Tony Cozzens at the Louisville Kentucky branch at (502) 671-7351 to place an order.
3. Custom enclosures using the UL 864 UUKL Ninth Edition listed VMA-16x0-0U, LN-VAVC-0U, or LN-VAVCF-0U controllers are ordered from Environmental Technologies, Inc. using the ETI Selection Program. The ETI Selection Program and ordering instructions are available at the Johnson Controls, Mechanical Systems website. See Figure 198 for ETI enclosure details.
• Be sure to select the Smoke Control Electronics Enclosure option when ordering a new VAV box unit from ETI.
• For systems having a VAV box unit that was not manufactured by ETI, order only the Smoke Control Electronics Enclosure from ETI. Install the enclosure on the non-ETI manufactured VAV box unit to house the controller.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 249
Figure 198: ETI VAV Smoke Control Electronics Enclosure
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin250
Enclosures Requiring a Union LabelCertain jurisdictions require that smoke control panels display a union label. Johnson Controls must contract with an external union electrical shop to meet Union requirements. The process to meet these requirements is:
1. The Johnson Controls Branch orders a Smoke Control Listed panel requiring a Union label.
2. Johnson Controls provides all Smoke Control Listed parts.
3. Every part of the smoke control panel, including the enclosure with manufacturer’s UL label, is inspected and labeled in accordance with Johnson Control’s Smoke Control Listing.
4. All parts are factory mounted in an enclosure by Johnson Controls in accordance with the UL 864 Control Units and Accessories for Fire Alarm Systems, Ninth Edition specification.
5. Johnson Controls sends the preassembled panel to the union electrical shop.
6. The union electrical shop wires the panel in accordance with UL 864 Control Units and Accessories for Fire Alarm Systems, Ninth Edition specification, applies the union label, and sends the completed panel to the specified smoke control site.
Ordering and Revision InformationTable 72 shows ordering information and revision numbers (when applicable) for all UL 864 UUKL Ninth Edition Smoke Control Parts.
General Smoke Control Ordering Requirements All Smoke Control sites must abide by the following requirements:
1. You can not purchase a similar third-party device and install it in a UL Listed smoke control system. Doing so voids the UL Smoke Control Listing. Third-party devices must be provided and labeled by the “factory” as described in the UL Smoke Control Listing.
2. A minimum of one Asante Ethernet switch is required for each smoke control site.
3. A PNET1GB Ethernet transient protector is required at each end of all Ethernet communication cables. The PNET1GB must have the strain-relief tie-wrap installed.
4. All 120VAC rackmount communication devices must be connected to a TrippLite Isobar 12 Ultra rackmount surge suppressor.
5. All devices that have a 120 VAC power converter and are not mounted in an enclosure, must have the power converter connected to a TrippLite Isobar 8 Ultra surge suppressor or a TrippLite Isobar 12 Ultra rackmount surge suppressor.
6. All devices mounted in enclosures, having a 120 VAC power converter must have the power converter connected to a TrippLite Isobar 8 Ultra surge suppressor mounted in the same enclosure.
7. Acromag repeaters must be mounted in an enclosure and must have its 120 VAC power connected to a TrippLite Isobar 8 Ultra surge suppressor mounted in the same enclosure.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 251
Note: All parts below are UL 864 UUKL listed for Ninth Edition smoke control applications.
Note: Previously listed UL 864 UUKL Eighth Edition part numbers are noted with an asterisk (*) followed by their UL 864 UUKL Eighth Edition part number in parenthesis.
IMPORTANT: Only Johnson Controls products listed in Table 72 have been tested and Listed by UL for use in a Metasys System UL 864 UUKL Ninth Edition Smoke Control System. The original manufacturer’s part number is only listed below as a reference for installation instructions. Products ordered directly from the manufacturer have not been UL Listed and labeled for smoke control applications.Installation of a product that is not UL-Listed and labeled for this application prevents the entire system from being UL Listed for smoke control!
Table 72: UL 864 UUKL Ninth Edition Smoke Control Part Ordering / Revision InformationPart Number Description Revision
Johnson Controls Supervisory EquipmentMS-NAE5510-1U*(MS-NAE5510-0U)
NAE55 with MSTP, Supports two BACnet MS/TP (RS-485 port) trunks.UL 864 UUKL listed for Ninth Edition smoke control applications.
3.0.0
MS-NAE4510-2U NAE45 with MSTP, Supports one BACnet MS/TP (RS-485 port) trunk.UL 864 UUKL listed for Ninth Edition smoke control applications.
3.0.0
MS-NAE3510-2U NAE35 with MSTP, Supports one BACnet MS/TP (RS-485 port) trunk.UL 864 UUKL listed for Ninth Edition smoke control applications.
3.0.0
MS-NAE5520-1U NAE55 with LON, Supports one LONWORKS trunk and two FC trunks.UL 864 UUKL listed for Ninth Edition smoke control applications.
3.0.0
MS-NAE4520-2U NAE45 with LON, Supports one LONWORKS trunk and one FC trunk.UL 864 UUKL listed for Ninth Edition smoke control applications.
3.0.0
MS-NAE3520-2U NAE35 with LON, Supports one LONWORKS trunk and one FC trunk.UL 864 UUKL listed for Ninth Edition smoke control applications.
3.0.0
Johnson Controls FC ControllersMS-FEU1610-0U 10-Point Field Equipment Controller with 2 UI, 1 BI, 3 BO, and 4 CO, 24
VAC, and SA Bus, with Mounting Base, Single Pack3.0.0
MS-FEU1620-0U 10-Point Field Equipment Controller with Display, 2 UI, 1 BI, 3 BO, and 4 CO, 24 VAC, and SA Bus, with Mounting Base, Single Pack
3.0.0
MS-FEU2610-0U 17-Point Field Equipment Controller with 6 UI, 2 BI, 3 BO, 2 AO and 4 CO, 24 VAC, and SA Bus with Mounting Base, Single Pack
3.0.0
MS-FEU2620-0U 17-Point Field Equipment Controller with Display, 6 UI, 2 BI, 3 BO, 2 AO and 4 CO, 24 VAC, and SA Bus with Mounting Base, Single Pack
3.0.0
MS-IOU4710-0U 17-Point IOM with 6 UI, 2 BI, 3 BO, 2 AO, 4 CO, 24 VAC, FC Bus and SA Bus with Mounting Base, Single Pack
3.0.0
MS-IOM3710-0U 12-Point IOM with 4 UI, 4 UO, 4 BO, FC Bus and SA Bus Support 3.0.0
MS-IOM2710-0U 6-Point IOM with 2 UI, 2 UO, 2 BO, FC Bus and SA Bus Support 3.0.0
MS-IOM1710-0U 4-Point IOM with 4 BI, FC Bus and SA Bus Support 3.0.0
MS-VMA1610-0U Integrated VAV Controller/Actuator/Pressure Sensor (Cooling Only), FC Bus and SA Bus, Single Pack
3.0.0
MS-VMA1620-0U Integrated VAV Controller/Actuator/Pressure Sensor (with Reheat and Fan Control), FC Bus and SA Bus, Single Pack
3.0.0
UL Listed MSTP AccessoriesNU-RPT101-1U Acromag MSTP Repeater N/A
SMOKE-TRNKIT-1U*(SMOKE-TRNKIT-1)
Acromag MSTP Repeater Kit - tranzorb transient suppressor for smoke control applications
N/A
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin252
SMK-MOVKIT-MSTP MOV transient protection kit for MSTP equipmentNote: Updated original part number only (previously
SMOKE-MOVKIT-MSTP); no component changes.
N/A
Non-UL Listed MSTP AccessoriesNS-APA7001 SA Bus network sensor -SA Bus network sensor - 80x80 mm, surface
mount, LCD, 2% RH, setpoint adjustment, override, modular jackN/A
NS-APA7002 SA Bus network sensor - 80x80 mm, surface mount, LCD, 2% RH, setpoint adjustment, override, screw terminal
N/A
NS-APB7001 SA Bus network sensor - 80x80 mm, surface mount, LCD, 2% RH, setpoint adjustment, override, F/C toggle, modular jack
N/A
NS-APB7002 SA Bus network sensor - 80x80 mm, surface mount, LCD, 2% RH, setpoint adjustment, override, F/C toggle, screw terminal
N/A
NS-BPB7001 SA Bus network sensor - 120x80 mm, wall or surface mount, LCD, 2% RH, setpoint adjustment, override, F/C toggle, modular jack
N/A
NS-BPB7002 SA Bus network sensor - 120x80 mm, wall or surface mount, LCD, 2% RH, setpoint adjustment, override, F/C toggle, screw terminal
N/A
NS-AHA7001 SA Bus network sensor - 80x80 mm, surface mount, LCD, 3% RH, setpoint adjustment, override, modular jack
N/A
NS-AHA7002 SA Bus network sensor - 80x80 mm, surface mount, LCD, 3% RH, setpoint adjustment, override, screw terminal
N/A
NS-AHB7001 SA Bus network sensor - 80x80 mm, surface mount, LCD, 3% RH, setpoint adjustment, override, F/C toggle, modular jack
N/A
NS-AHB7002 SA Bus network sensor - 80x80 mm, surface mount, LCD, 3% RH, setpoint adjustment, override, F/C toggle, screw terminal
N/A
NS-BHB7001 SA Bus network sensor - 120x80 mm, wall or surface mount, LCD, 3% RH, setpoint adjustment, override, F/C toggle, modular jack
N/A
NS-BHB7002 SA Bus network sensor - 120x80 mm, wall or surface mount, LCD, 3% RH, setpoint adjustment, override, F/C toggle, screw terminal
N/A
NS-ATA7001 SA Bus network sensor - 80x80 mm, surface mount, LCD, setpoint adjustment, override, modular jack
N/A
NS-ATA7002 SA Bus network sensor - 80x80 mm, surface mount, LCD, setpoint adjustment, override, screw terminal
N/A
NS-ATB7001 SA Bus network sensor - 80x80 mm, surface mount, LCD, setpoint adjustment, F/C toggle, override, modular jack
N/A
NS-ATB7002 SA Bus network sensor - 80x80 mm, surface mount, LCD, setpoint adjustment, F/C toggle, override, screw terminal
N/A
NS-ATC7001 SA Bus network sensor - 80x80 mm, surface mount, LCD, setpoint adjustment, fan control, override, modular jack
N/A
NS-ATC7002 SA Bus network sensor - 80x80 mm, surface mount, LCD, setpoint adjustment, fan control, override, screw terminal
N/A
NS-ATD7001 SA Bus network sensor - 80x80 mm, surface mount, LCD, setpoint adjustment, F/C toggle, fan control, override, modular jack
N/A
NS-ATD7002 SA Bus network sensor - 80x80 mm, surface mount, LCD, setpoint adjustment, F/C toggle, fan control, override, screw terminal
N/A
NS-ATN7001 SA Bus network sensor - 80x80 mm, surface mount, modular jack N/A
NS-ATN7003 SA Bus network sensor - 80x80 mm, surface mount, screw terminal, address switches
N/A
NS-ATP7001 SA Bus network sensor - 80x80 mm, surface mount, warmer/cooler dial adjustment, override, modular jack
N/A
Table 72: UL 864 UUKL Ninth Edition Smoke Control Part Ordering / Revision InformationPart Number Description Revision
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 253
NS-ATP7002 SA Bus network sensor - 80x80 mm, surface mount, warmer/cooler dial adjustment, override, screw terminal
N/A
NS-ATV7001 SA Bus network sensor - 80x80 mm, surface mount, LCD, setpoint adjustment, F/C toggle, override, modular jack, VAV balancing featureNote: Fan control button is replaced by a light bulb button used in the
balancing process.
N/A
NS-ATV7002 SA Bus network sensor - 80x80 mm, surface mount, LCD, setpoint adjustment, F/C toggle, override, screw terminal, VAV balancing featureNote: Fan control button is replaced by a light bulb button used in the
balancing process.
N/A
NS-BTB7001 SA Bus network sensor - 120x80 mm, wall or surface mount, LCD, setpoint adjustment, override, F/C toggle, fan control, modular jack
N/A
NS-BTB7002 SA Bus network sensor - 120x80 mm, wall or surface mount, LCD, setpoint adjustment, F/C toggle, fan control, override, screw terminal
N/A
NS-BTN7001 SA Bus network sensor - 120x80 mm, wall or surface mount, modular jack N/A
NS-BTN7003 SA Bus network sensor - 120x80 mm, wall or surface mount, screw terminal, address switches
N/A
NS-BTP7001 SA Bus network sensor - 120x80 mm, wall or surface mount, warmer/cooler dial adjustment, override, modular jack
N/A
NS-BTP7002 SA Bus network sensor - 120x80 mm, wall or surface mount, warmer/cooler dial adjustment, override, screw terminal
N/A
NS-BTV7001 SA Bus network sensor - 120x80 mm, wall or surface mount, LCD, setpoint adjustment, F/C toggle, override, modular jack, VAV balancing featureNote: Fan control button is replaced by a light bulb button used in the
balancing process.
N/A
NS-BTV7002 SA Bus network sensor - 120x80 mm, wall or surface mount, LCD, setpoint adjustment, F/C toggle, override, screw terminal, VAV balancing featureNote: Fan control button is replaced by a light bulb button used in the
balancing process.
N/A
Johnson Controls LON EquipmentLN-VAVC-0U LN-Series Programmable VAVC enclosure with LM-24M actuator,
pressure sensor, and 8 I/O (4 UI, 3 triac DO, 1 AO), with Logging and LNS Plug-in
2.34
LN-VAVCF-0U LN-Series Programmable VAVC enclosure with LM-24M10 feed-back actuator, pressure sensor, and 7 I/O (3 UI, 3 triac DO, 1 AO), with Logging and LNS Plug-in
2.34
NXP-FSC-01U NXP-EN-RMH0013U Back Plane - includes NXP-CPU-01U, PAN-PWRSP Power Supply, NXM-CABLE-MGS04U 2' I/O Cable, NXP-8UI-01U 8UI for FSC CPU, NXP-4DO4AO-01U 4DO/4AO for FSC CPUNote: See individual components for revision level.
See Note
NXP-CPU-01U FSC CPU only SSM 4292-A03
NXP-8UI-01U 8UI I/O Board for NXP-FSC-01U SSM 4284-B01
NXP-4DO4AO-01U 4DO/4AO I/O Board for NXP-FSC-01U SSM 4286-B00
NXP-8DO-01U 8DO I/O Board for NXP-FSC-01U SSM 4287-B00
NXM-CABLE-MGS22U 6 ft. I/O Cable N/A
Table 72: UL 864 UUKL Ninth Edition Smoke Control Part Ordering / Revision InformationPart Number Description Revision
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin254
NXP-FSC-EXP1U FSC-01U Expansion Panel - includes NXP-EN-RMH0013U Backplane and NXM-CABLE-MGS22U 6 ft. I/O Cable
N/A
NXE-REP-FFT-U LON Repeater N/A
NXE-FTT-FTT-U Echelon - LPR10 - JCI Router N/A
NXP-EN28185-01U FSC Enclosure - 28 in. x 18.5 in. N/A
NXP-EN-RMH0013-U Full Backplane for NXP-EN28185-01U FSC Enclosure N/A
NXM-TERM-FTT-U LonWorks FTT10 Bus Terminator N/A
72603-U Echelon® - iLON 600 LON IP Router N/A
SMK-MOVKIT-LON MOV transient protection kit for LON equipmentNote: Updated original part number only (previously
SMOKE-MOVKIT-LON); no component changes.
N/A
Johnson Controls Communication EquipmentNU-RJ45SW1-0U*(NU-RJ45SW1-0)
10/100 Asante Ethernet Switch N/A
NU-MC101-0U*(NU-MC101-0)
10mps Ethernet / Fiber Media Converter - Complete N/A
NU-MC102-0U*(NU-MC102-0)
100mps Ethernet / Fiber Media Converter - Requires Chassis N/A
NU-CH101-0U*(NU-CH101-0)
Ethernet / Fiber Media Converter - Chassis N/A
464163 NetGear - FS105 5-Port Ethernet SwitchNote: Order through Johnson Controls ITAS
N/A
Johnson Controls Enclosures // TransformersStandard Hoffman Enclosures
PAN-ENH1620WDP 6.62 x 16 x 20 Encl w/door, latch, sub-panel N/A
PAN-ENH1620WD 6.62 x 16 x 20 Encl w/door, latch N/A
PAN-ENH2024WDP 6.62 x 20 x 24 Encl w/door, latch, sub-panel N/A
PAN-ENH2024WD 6.62 x 20 x 24 Encl w/door, latch N/A
PAN-ENH2424WDP 6.62 x 24 x 24 Encl w/door, lock, sub-panel N/A
PAN-ENH2424WD 6.62 x 24 x 24 Encl w/door, lock N/A
PAN-ENH2436WDP 6.62 x 24 x 36 Encl w/door, lock, sub-panel N/A
PAN-ENH2436WD 6.62 x 24 x 36 Encl w/door, lock N/A
Custom Hoffman Enclosures with Lift-Off Doors, Louvers, and Locks
PAN-ENC1620WDP1 6.62 x 16 x 20 Encl w/door, lock, sub-panel N/A
PAN-ENC1620WD1 6.62 x 16 x 20 Encl w/door, lock N/A
PAN-ENC2024WDP1 9.25 x 20 x 24 Encl w/door, lock, sub-panel N/A
PAN-ENC2024WD1 9.25 x 20 x 24 Encl w/door, lock N/A
PAN-ENC2424WDP1 9.25 x 24 x 24 Encl w/door, lock, sub-panel N/A
PAN-ENC2424WDF1 9.25 x 24 x 24 Encl w/cut-out door, lock N/A
PAN-ENC2424WD1 9.25 x 24 x 24 Encl w/door, lock N/A
PAN-ENC2436WDP1 9.25 x 24 x 36 Encl w/door, lock, sub-panel N/A
PAN-ENC2436WDF1 9.25 x 24 x 36 Encl w/cut-out door, lock N/A
PAN-ENC2436WD1 9.25 x 24 x 36 Encl w/door, lock N/A
Table 72: UL 864 UUKL Ninth Edition Smoke Control Part Ordering / Revision InformationPart Number Description Revision
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 255
PAN-ENC3042WDP1 9.25 x 30 x 42 Encl w/door, lock, sub-panel N/A
PAN-ENC3042WD1 9.25 x 30 x 42 Encl w/door, lock N/A
PAN-ENC3648WDP1 9.25 x 36 x 48 Encl w/door, lock, sub-panel N/A
PAN-ENC3648WD1 9.25 x 36 x 48 Encl w/door, lock N/A
PAN-PWRSP-U 96 VA 120/24 VAC power assembly (transformer, receptacle, 5 Amp overcurrent circuit breaker)
N/A
PAN-96VAXFR-U Transformer, Power, Panel Mount, 120 V Primary, 24 V Secondary, 96 VA, Split Bobbin, 4 Amp Secondary Circuit Breaker,
N/A
PA0P00010FC0-U Power Distribution Panel and Enclosure - Contains four PAN-96VAXFR-U transformers, 120V,10 Amp Primary Circuit Breaker. For powering multiple VAV/VMAs.
N/A
NXP-EN28185-01 5.00 x 28.5 x 18 Encl w/door, lock (FSC Enclosure only -no backplane) N/A
NXP-EN-RMH0013 13.50 x 27.25 Backplane for NXP-EN28185-01 Enclosure N/A
00-00051-0100-00052-01
ETI VAV Electonic Enclosure - 16” Enclosure, Electronic Control, 18GAETI VAV Electronic Enclosure - 16” Cover, Electronic Control, 18GA
N/A
3rd Party Equipment*(ISOBAR8Ultra)www.cdw.com
CDW - 025070 - Tripp Lite® ISOBAR8Ultra Surge Suppressor N/A
*(ISOBAR12Ultra)www.cdw.com
CDW - 154600 - Tripp Lite® ISOBAR12Ultra Rackmount Surge Suppressor
N/A
PNET1GB*(PNET1)www.apc.com
American Power Conversion (APC®) - PNET1GB Ethernet Surge Suppressor
N/A
www.adipanel.com ADI MSTP FSCS - Note: Custom product from Automation Displays, Inc. (ADI®)
N/A
www.echelon.com Echelon® - 72603 - iLON 600 LON IP Router N/A
1. All Hoffman custom enclosures have a factory installed grounding strap, supplied by Hoffman, connecting the enclosure to the enclosure door.
Table 72: UL 864 UUKL Ninth Edition Smoke Control Part Ordering / Revision InformationPart Number Description Revision
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin256
Selection Charts Table 73: Network Sensor Ordering Information — Temperature and Humidity ModelsProduct Code Number
Size (mm), Height x Width
Vertical Wallbox-Mounted (WB), or Surface-Mounted (SM)
LCD Display
Humidity Temperature Adjustment: Setpoint (Set) orWarmer/Cooler Dial (W/C)
Occupancy Override
F/C Scale Toggle
Screw Terminals (ST), or Modular Jack (MJ)
NS-APA7001-0 80 x 80 SM Yes 2% Set Yes MJNS-APA7002-0 80 x 80 SM Yes 2% Set Yes STNS-APB7001-0 80 x 80 SM Yes 2% Set Yes Yes MJNS-APB7002-0 80 x 80 SM Yes 2% Set Yes Yes STNS-BPB7001-0 120 x 80 WB, SM Yes 2% Set Yes Yes MJNS-BPB7002-0 120 x 80 WB, SM Yes 2% Set Yes Yes STNS-AHA7001-0 80 x 80 SM Yes 3% Set Yes MJNS-AHA7002-0 80 x 80 SM Yes 3% Set Yes STNS-AHB7001-0 80 x 80 SM Yes 3% Set Yes Yes MJNS-AHB7002-0 80 x 80 SM Yes 3% Set Yes Yes STNS-BHB7001-0 120 x 80 WB, SM Yes 3% Set Yes Yes MJNS-BHB7002-0 120 x 80 WB, SM Yes 3% Set Yes Yes ST
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 257
Table 74: Network Sensor Ordering Information — Temperature Only ModelsProduct Code Number
Size (mm), Height x Width
Vertical Wallbox-Mounted (WB), or Surface-Mounted (SM)
LCD Display
Temperature Adjustment: Setpoint (Set), or Warmer/Cooler Dial (W/C)
Occupancy Override
F/C Scale Toggle
Fan Control
Screw Terminal (ST), or Modular Jack (MJ)
Address Switches
VAV Balancing Feature
NS-ATA7001-0
80 x 80 SM Yes Set Yes MJ N/A
NS-ATA7002-0
80 x 80 SM Yes Set Yes ST N/A
NS-ATB7001-0
80 x 80 SM Yes Set Yes Yes MJ N/A
NS-ATB7002-0
80 x 80 SM Yes Set Yes Yes ST N/A
NS-ATC7001-0
80 x 80 SM Yes Set Yes Yes MJ N/A
NS-ATC7002-0
80 x 80 SM Yes Set Yes Yes ST N/A
NS-ATD7001-0
80 x 80 SM Yes Set Yes Yes Yes MJ N/A
NS-ATD7002-0
80 x 80 SM Yes Set Yes Yes Yes ST N/A
NS-ATN7001-0
80 x 80 SM MJ N/A
NS-ATN7003-0
80 x 80 SM ST Yes N/A
NS-ATP7001-0
80 x 80 SM W/C Yes MJ N/A
NS-ATP7002-0
80 x 80 SM W/C Yes ST N/A
NS-ATV7001-0
80 x 80 SM Yes Set Yes Yes No1 MJ Yes
NS-ATV7002-0
80 x 80 SM Yes Set Yes Yes No1 ST Yes
NS-BTB7001-0
120 x 80 WB, SM Yes Set Yes Yes MJ N/A
NS-BTB7002-0
120 x 80 WB, SM Yes Set Yes Yes ST N/A
NS-BTN7001-0
120 x 80 WB, SM MJ N/A
NS-BTN7003-0
120 x 80 WB, SM ST Yes N/A
NS-BTP7001-0
120 x 80 WB, SM W/C Yes MJ N/A
NS-BTP7002-0
120 x 80 WB, SM W/C Yes ST N/A
NS-BTV7001-0
120 x 80 WB, SM Yes Set Yes Yes No1 MJ Yes
NS-BTV7002-0
120 x 80 WB, SM Yes Set Yes Yes No1 ST Yes
1. In the VAV Balancing models, the Fan Control button is replaced by a light bulb button used in the VAV Balancing Process.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin258
Smoke Control UL 864 UUKL Ninth Edition Compliance Checklist
OverviewThis section summarizes the most common requirements to configure the Metasys system extended architecture to comply with Underwriters Laboratories®, Inc. (UL), UL UUKL 864 Ninth Edition Smoke Control Listing. A UL 864 UUKL Smoke Control Compliance Survey form is followed by tables listing the requirements for UL 864 UUKL Listing compliance.
The purpose of the UL 864 UUKL Ninth Edition Smoke Control Compliance Survey is to provide a record of those elements of National Fire Protection Association (NFPA) 92A and UUKL that Johnson Controls, Inc. does or does not provide.
UUKL is an identifier created by UL to identify those products Listed under UL 864 as part of a Smoke Control system. Products covered by this listing are intended to be installed in conjunction with Heating, Ventilating, and Air Conditioning (HVAC) equipment to form a system for controlling the flow of smoke in a building during a fire condition in accordance with NFPA Recommended Practice 92A.
It is important that we document the system elements that are being provided. The UL 864 UUKL Ninth Edition Smoke Control Compliance Survey can be used to provide that documentation.
In the case where a project specification dictates compliance with the UUKL Listing, but contains elements of the system design that conflict with the Listing or are omitted, the completed UL 864 UUKL Ninth Edition Smoke Control Compliance Survey can be given to the designer and/or the AHJ to obtain recognition and agreement on the extent of Listing compliance. This should occur prior to bid and/or proposal.
Once agreement is reached with the AHJ, designer, and customer, the signed or initialed Smoke Control Compliance Checklist must become a permanent part of the project file.
Related DocumentationIf you are bidding, engineering, installing, or commissioning a Metasys system extended architecture requiring UUKL 864 Ninth Edition Smoke Control Listing compliance, follow the guidelines, requirements, and procedures listed in this document and in Table 1 Related Documentation.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 259
UL 864 UUKL Ninth Edition Smoke Control Compliance Survey
Date of SurveyConducted ByProjectLocationBranch OfficeProject Manager
Applicable Building Codes and Standards
Local (Branch) Person Providing and Verifying InformationInitials Name
Specifications
Building Codes
Contract
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin260
General UUKL RequirementsTable 75 lists general requirements for UL 864 UUKL Listing compliance. Mark Yes/No for compliance and initial each item that was verified.Table 75: General UUKL RequirementsRequirement Y/N
NAPerson Verifying
Communication links between buildings are fiber-optic cable or copper cable buried in a conduit separate from power wiring.Each binary output object used for pressurization and exhaust control is configured with positive feedback. The feedback input monitors the associated controlled equipment status (for example, both open and closed, on and off). For smoke control dampers, there may be a pair of feedback binary inputs for two damper end switches. Any mismatch of a command and status of the binary output occurring longer than the allowed response time must create a trouble light indication at the FSCS.For fans there is positive indication of airflow.Non UL-Listed control equipment must be isolated from the UL-Listed network.The Weekly Testing of Dedicated Stairwell Pressurization Fans application is used on all dedicated smoke control systems.Automatic smoke control sequences take precedence over HVAC automatic and manual commands. Manual FSCS takes precedence over all else.Automatic activation of any smoke control sequence of operation has priority over any non-smoke control manual commands and any automatic environmental control strategy, when an auto smoke control sequence is initiated. High and low temperature protection devices and return and exhaust air-duct smoke detectors are bypassed.Response time for individual smoke control fans to reach commanded state is no more than 60 seconds.Response time for individual smoke control dampers to reach commanded state is no more than 75 seconds.Fire alarm system manual pull stations do not initiate automatic smoke control sequences.Smoke detectors are used to initiate a smoke control strategy only as detailed in this document, Metasys System UL 864 UUKL Smoke Control System Technical Bulletin (LIT-12011252).All Application Specific Controls (ASCs) that monitor or control smoke control equipment are UUKL Listed.Electrical disconnects, overloads, duct static pressure limits, and supply air duct smoke detectors are not overridden by manual or automatic smoke control strategies.
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 261
FSCS UUKL Ninth Edition RequirementsTable 76 lists general requirements for UL 864 UUKL Listing compliance for FSCSs where required. Mark Yes/No for compliance and initial each item that was verified.Table 76: FSCS UUKL Requirements Requirement Y/N
NAPerson Verifying
FSCS is UUKL Listed and provides manual control of the smoke control system, a UUKL Listed annunciator panel is used as FSCS.Custom annunciator FSCS is connected to a UUKL Listed Smoke Control NAE55.FSCS provides positive indication of the operation of all smoke control equipment (for example, both open and closed, on and off).FSCS provides audible and visible trouble indication when any smoke control equipment does not respond to automatic or manual commands.FSCS simultaneously displays the status of all smoke control systems dampers, fansFSCS has manual control over all smoke control systems.FSCS can override (partially or in full) any operation in progress, including programmed actions, non-smoke control manual overrides.FSCS has highest priority over all smoke control systems.A building diagram or equivalent at FSCS clearly indicates the type and location of all smoke control equipment.FSCS indicates the actual status (not the command status) of systems and equipment used for smoke control. This includes the current position of each damper used in an active smoke control sequence and the status of airflow status of every fan.FSCS activates an audible signal if the operation proof sensor (binary feedback point) failed to provide positive feedback that fan or damper reached its intended position.Only one FSCS on Metasys system is used for smoke control applications unless approved by the AHJ.The FSCS manual activation or deactivation of any smoke control device has priority over any automatic smoke or environmental sequence of operation.Any return air duct smoke detectors in duct work of each HVAC fan system used for smoke control exhaust or purge only reports an alarm condition to the FSCS or fire alarm annunciator located at the FSCS and does not stop the fan.All hardware supervision alarms, such as binary feedback alarms on fans and dampers, as well as system alarm points turn on FSCS alarm horn.Annunciation on the FSCS of change of state of smoke control equipment is no more than 10 seconds after reaching commanded state.
Metasys® is a registered trademark of Johnson Controls, Inc.All other marks herein are the marks of their respective owners.
© 2008 Johnson Controls, Inc.
Controls Group507 E. Michigan StreetMilwaukee, WI 53202
Published in U.S.A. www.johnsoncontrols.com
Metasys® System UL® 864 UUKL Ninth Edition Smoke Control System Technical Bulletin262
Smoke Control Wiring UUKL Requirements
Table 77 lists requirements for UL 864 UUKL Ninth Edition Listing compliance for Smoke Control Wiring. Mark Yes/No for compliance and initial each item verified.Table 77: Smoke Control Wiring Ninth Edition UUKL RequirementsRequirement Y/N
NAPerson Verifying
Communication links between buildings are fiber-optic cable or copper cable buried in a conduit separate from power wiring.If FC Bus or LON Bus signal circuits leave the room, transient protection is applied as detailed in the Metasys System UL 864 UUKL Ninth Edition Smoke Control Technical Bulletin (LIT-12011252).Verify that a Tripp Lite® ISOBAR8ULTRA surge protector or a Tripp Lite ISOBAR12ULTRA surge protector protects all 120 VAC power sources.If fiber-optic cable is used, verify that it meets the requirements listed in the Metasys System UL 864 UUKL Ninth Edition Smoke Control System Technical Bulletin (LIT-12011252).If copper cable is used, verify that it meets the requirements listed in the Metasys System UL 864 UUKL Ninth Edition Smoke Control System Technical Bulletin (LIT-12011252).Verify that copper cable connected to media converters does not leave the room in which the media converter is installed.Verify that all RJ45 ethernet cables are protected from electrical surges through the use of the American Power Conversion (APC) Protect Net (Model PNET1GB) surge protector at each end of the RJ45 ethernet cable.Verify that only the Smoke Control NAE model MS-NAE5510-1U, MS-NAE5520-1U, MS-NAE4510-2U, NAE4520-2U, NAE3510-2U, NAE3520-2U are used for smoke control in a UL 864 UUKL Ninth Edition smoke control system.If an RS-485-to-RS-485 repeater is used to isolate UUKL from non-UUKL devices on an FC Bus, verify that it is installed in a UL-Listed enclosure. Refer to the Metasys System UL 864 UUKL Ninth Edition Smoke Control System Technical Bulletin (LIT-12011252.). The transzorb must be a Johnson Controls Code No. SMOKE-TRNKIT-1.