micom p721 & p723 - rza.by · pdf filemicom p721 & p723 numerical high impedance...
TRANSCRIPT
MiCOM P721 & P723
High Impedance Differential Protection
P72x/EN TDS/B21
Technical Data Sheet This document does not replace the Technical Manual
Note: The technical manual for this device gives instructions for its installation, commissioning, and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate Schneider Electric technical sales office and request the necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric including settlements of warranties, result solely from the applicable purchase contract, which is not affected by the contents of the technical manual.
This device MUST NOT be modified. If any modification is made without the express permission of Schneider Electric, it will invalidate the warranty, and may render the product unsafe.
The Schneider Electric logo and any alternative version thereof are trademarks and service marks of Schneider Electric.
MiCOM is a registered trademark of Schneider Electric. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners.
This manual is provided for informational use only and is subject to change without notice.
© 2012, Schneider Electric. All rights reserved.
01Protection Relays
MiCOM P721 & P723Numerical High Impedance Differential Relay
The new P72x high impedance differential protection series provides an independent and simple high impedance differential protection solution for generator, reactor, motor and busbar applications where fast clearance of faults is required.
Combined with the P79x, a standalone metrosil and resistor unit, it provides simplified scheme engineering for single or three-phase differential applications.
As well as offering the same application benefits as traditional high impedance electromechanical protection schemes, it combines the added benefits of numerical technology to provide advanced communications, event records, fault records, disturbance records and ancillary protection features.
Customer Benefits
•Simple scheme engineering
•Reliable algorithm
•Supervision functions included in the
same protection box
02Protection Relays MiCOM P72x
APPLICATION
When circulating current protection schemes aresubjected to through faults, the sudden and oftenasymmetrical growth in the system current can cause the line current transformers to reach saturation. Under these conditions the variation in current transformer magnetising characteristics can cause large ratio errors with a consequent circuit imbalance and maloperation of the protective relays. To ensure stability, it is common practice to employ high impedance relays set to operate at a slightly higher voltage than that developed in the worst theoretical case of this condition for a given through fault current. On a balanced earth fault system for example, this is when one current transformer of a group is saturated whilst the others remain unaffected. The saturated transformer presents a low impedance path in parallel with the relay and limits the voltage applied. For internal faults this limitation does not exist and voltages of twice the setting are easily reached resulting in fast operation of the differential relay. The P72x relay together with the P79x unit, is designed for applications where sensitive settings with stability on heavy through faults are required. It offers a reliable protection for busbars, transformers windings, generators, reactors and motors.
OVERVIEW
Two models are available:MiCOM P721 is a single-phase high impedancedifferential protection. It is suitable for restricted earth fault or balanced earth fault applications.
MiCOM P723 can be configured either as highimpedance differential three-phase protection (87) or as high impedance differential earth protection (87N). The connection setting determines whether 87 or 87N is being used.
MAIN fuNCTIONS
Phase segregated high impedance differential protection (87A, 87B, 87C)
The application of P723 numerical relay as differential protection for machines and busbar installations is based on the high impedance differential principle. This principle requires stabilising resistors in each phase and a metrosil is generally required across the relay circuit. These are included in the P79x accessoryas shown in Figure 1.
Stability for any type of fault occurring outside theprotected zone and satisfactory operation for faults within the zone are achieved.
Figure 1 shows the typical application diagram where P723 is configured as a phase segregated high impedance differential protection.
fuNCTIONAL OVERVIEW
87P
P79x
RST
ProtectedPlant
P72x
Metrosil
I diff
BinaryInput / Output
LEDs
87N
95P
95N
50BF
Disturbance
Measurements
Self Monitoring
Fault RecordsLocalCommunication
RemoteComm. Port Record
P72x and P79x together offer a simple and reliable high impedance differential protection
03Protection Relays MiCOM P72x
PROTECTION fuNCTIONS OVERVIEW
ANSI features P721 P72387P Phase segregated high impedance current differential protection •95P Phase bus-wire supervision •87N Restricted earth fault protection • •95N Earth bus-wire supervision • •87CZ Check zone input •50BF Breaker failure detection • •
GENERAL fEATuRES
features P721 P723Number of opto-isolated inputs 2 5Number of relay output contacts 4 8Event recording 250 250Fault recording 25 25Disturbance recording 5 5Instantaneous records 5 5Setting groups 2 2Auxiliary timers 4 4Communication protocols Modbus RTU (rear port) • •
DNP3 (rear port) • •IEC 60870-5-103 (rear port) • •Modbus RTU (front port) • •
Setting software MiCOM S1 Studio • •
Logic equations AND, OR and NOT gates 8 Boolean equations • •
Measurements Neutral supervision/differential currents (INdiff) • •Phase supervision/differential currents (IAdiff, IBdiff and ICdiff) •Maximum differential currents (ImaxAdiff, ImaxBdiff and ImaxCdiff) •
Maximum differential neutral currents (ImaxNdiff) • •
Figure 1: P723 configured as phase segregated high impedance differential busbar protection
04Protection Relays MiCOM P72x
High impedance differential earth fault protection (87N)
The P721 has a single differential element and may only function as an 87N protection. The P723 can be configured as 87N when only one analogue current input is required.Restricted earth fault protection is included to cover a larger percentage of the transformer windings than might be possible with the main biased differential transformer protection. 87N is commonly referred as restricted earth fault (REF) protection for star windings and balanced earth fault (BEF) protection for delta windings. Figures 2 and 3 show the P72x configured for these applications.
GENERAL SCHEME LOGIC
The schemes in figures 4 and 5 describe the logic of the three-phase high impedance differential protection and high impedance differential earth fault protection relays. External blocking inputs are available to allow the user to configure an input to enable or disable the differential element. A selectable logic input is also available as a check zone input from another P72x or differential relay.
CONTROL AND INDICATION
Control
Two blocking logics are available where for example opto inputs can be independently configured to block the differential element or any of the auxiliary timer functions.
Logic equations
The MiCOM P72X relays integrate complete logicequations to allow customization of the product based on customer application. Up to 8 independent Boolean equations can be used. Each equation offers the possibility to use AND, OR & NOT logical gates. Up to 16 parameters can be used for each equation. Every result of equation can be time delayed and assigned to any output relays, trip, triplatching and/or HMI LEDs.
Figure 2: BEF protection for the delta winding of a power transformer with supply system earthed
Figure 3: REF protection of a 3 phase, 4 wire system applicable to star connected generators or power transformer windings with neutral earthed at generator/transformer star point
Figure 4: General scheme of the three-phase high impedance differential protection
[87] DIFF
&
[87CZ] Check Zone
Blocking Logic 1 / 2 DT
Start [87] DIFF
Temporized [87] tDIFF
[95] SUPStart [95] SUP
Temporized [95] tSUP
DT
&
Figure 5: General scheme of high impedance differential earth fault protection
[87N] DIFF
&Blocking Logic 1 / 2
DT
Start [87N] DIFF
Temporized [87N] tDIFF
[95N] SUP Start [95N] SUP
Temporized [95N] tSUP
DT
05Protection Relays MiCOM P72x
SuPERVISORY fuNCTIONS
Open circuit failures of the CTs or bus-wires will cause a spill current to flow through the differential element and operation will occur if this current is greater than the setting. Two methods are used to prevent nuisance tripping due to open circuit conditions:
1. Bus-wire supervision elements are provided tomonitor for a continuous low level of spill current.After a time delay, this relay would usually shortcircuit the AC bus-wires to ensure stability and also give an alarm. The disadvantage of this scheme is that the differential elements must be set higher than the bus-wire supervision elements (and usually above maximum load conditions) if nuisance tripping is to be avoided. This may create sensitivity issues.
2. Duplicate differential elements (main and checkzones) fed from separate CTs using segregated(phase by phase) bus-wires. Tripping is only permitted when both differential elements operate.The advantage of this scheme is that the differential settings can remain very sensitive (below full load current values), but this will require a total duplication of the scheme. The selectable logic input from another P72x deployed as a check zone is available for this function.
The above two methods are usually used inconjunction with each other, although to reduce costs either scheme could be used independently.
Optos
Protectionelements
AutomaticControl
Timers
Gate Logic
LED's
Relaycontacts
Figure 6 CBF detection logic
Trip [87] tDIFF
Idiff<
&
CB Fail time tBF
CB Fail
Pick up timer
LEDs
Four programmable LEDs are available.
Alarms
Protection and control functions generate alarms on the screen and LEDs as configured. Certain alarms can be inhibited or automatically reset by preliminary parameter setting. Alarms can be stored in non-volatile memory.
Phase segregated outputs are available from the buswire supervision such that each phase can be“stabilised” by short circuiting the bus-wires asrequired. The differential elements are internallyblocked due to bus-wire supervision (although this will not negate the requirement for external shorting of bus-wires).
Bus-wire Shorting
To limit the power dissipated in the resistance, after the differential trip protection [87] or bus-wiresupervision [95] are activated, the bus-wires must be short-circuited. This function is latched in the internal logic. The bus-wire shorting signal can be connected as shown in figures 1, 2 and 3.
CB Failure function
The CB failure output from the P72x is an input to the breaker failure scheme. The general scheme for the breaker failure detection function is shown in figure 6.
OPERATION AND CONfIGuRATION
Setting groupsExternal conditions may request the need for different settings. MiCOM P72x provide two independent setting groups. The active setting group can be switched to the other from the local HMI or from external conditions (opto input change of state or DCS control).
Multi-language user interface (HMI)
All functions, including protection, automation,communication, LEDs, inputs and outputs, can beprogrammed and modified using the front panel user interface (Human Machine Interface, HMI).The backlit LCD informs the user about settings,measurements & faults thanks to the pull-downstructure menu allowing easy and quick access to any data. Moreover, even if the relay is delivered with the language specified at the order, the user can change the language used within the relay from the HMI.
06Protection Relays MiCOM P72x
MEASuREMENTS AND RECORDING
Measurements
The following measurements are available for display and remote measurements:• The P723 measures Phase supervision/
differential currents (IAdiff, IBdiff and ICdiff).
Figure 7: Disturbance Record
• The P721 and P723 measure the neutral supervision/differential currents (INdiff).
• The P723 measures the maximum differential currents (ImaxAdiff, ImaxBdiff and ImaxCdiff).
• The P721 and P723 measure the maximum differential neutral currents (ImaxNdiff).
Fault records
25 time-tagged fault records that indicate the faulted phase, protection operation, active setting group, pre-fault and differential fault currents magnitudes are available.
Disturbance records
A disturbance record is generated for every trip. Inaddition, the disturbance recorder can be triggered by an opto-isolated input, or a remote control signal.
Up to five records of 3 seconds each one can bestored.The disturbance records are 32 samples per cycle.
Event records
250 time-tagged event records can be stored.Events include operation and reset of inputs/outputs, alarms, internal signals, and contacts.All events are time stamped to 1ms, and can beaccessed either locally or remotely.
Read Keyclear Key
trip led
Alarm led
Device fail.
Power supply
battery is not used anymore
cursor Keys
Rs 232
freely Programmable leds
07Protection Relays MiCOM P72x
COMMuNICATION & SYNCHRONIZATION
The MiCOM P72x offers a wide range ofcommunication protocols, allowing its utilisation in most of the network control and data acquisitionsystems (via Modbus, IEC 60870-5-103, and DNP3.0). It has been designed for permanent multi-drop connection through the rear RS485 communication port.
The MiCOM P72x incorporates an internal clock used for the time tagging of alarms, events, fault and disturbance record. The relay’s internal clock is synchronise to the timing information to an accuracy of 1ms.To avoid any drifting of the time tagging clock, it’s necessary to periodically synchronize the relays. To do this P72x offers two solutions:
1. Synchronization from the substation control system via the rear communication port2. Synchronization from an external GPS clock via a dedicated digital input
STABILISING RESISTOR AND VARISTOR ACCESSORY
The P79x accessory contains a number of fixedresistors that provide stability during external faults. In addition to the stabilising resistors, a varistor is included for each phase.
Figure 8: MiCOM P721/P791 diagram connection
373533+
_34
36WDWatch dog
RL1 to RL4 areprogrammableoutputs
L1 to 2 areprogrammableinputs
Auxiliarysupply
ABC
P791
Link terminals 30 and 32if the relay is connectedat the end of the RS485bus
RS485communicationport
+
_
642RL1
1210
8RL2
1614RL32018RL4
551A
56
47
MiCOMP721
5A48
2224
+
_
*31
30
29
32
L1+
_
2628 L2
P791
Simple and reliable high impedance differential scheme protection
Two models are available: the P791 used in singlephase applications and the P793 used in three phase applications.
Stabilising resistor
Three options of internal stabilising resistors areoffered. In each option is possible to get 4combinations of serial and parallel connections to give various values of resistance as required by the application.
Varistor
Varistors are used to limit the peak voltage developed by the current transformers under internal fault conditions to a value below the insulation level of the current transformers, relay and interconnecting wiring, which are typically able to withstand approximately 3000V peak.
Two options of varistors are available. The half power option may withstand up to 10kJ of transient energy and the full power up to 20kJ.
Figures 8 and 9 show P721/P791 and P723/P793connection diagram. See P79x brochure for more information.
08
EnergyAutomation-DS-P72x-2200-EN 10-2010
Protection Relays MiCOM P72x
© 2
010
Sch
neid
er E
lect
ric -
All
right
s re
serv
ed
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
Publishing: Schneider ElectricDesign: Schneider ElectricPrinting:
This document has been printed on ecological paper
Schneider Electric35, rue Joseph Monier CS 30323 92506 Rueil-Malmaison Cedex, France Tel: +33 (0) 1 41 29 70 00
RCS Nanterre 954 503 439 Capital social 896 313 776 €www.schneider-electric.com
Figure 9: MiCOM P723/P793 diagram connection
33+
_34
Auxiliarysupply
Three-Phase High Impedance Differential
373536WD
Watch dog
RL1 to RL8 areprogrammableoutputs
642RL1
12108RL2
1614RL32018RL4
31RL575RL69
11RL71315RL8
RS485communicationport
+
_
*31
30
29
32
L1 to 5 areprogrammableinputs
_
2224 L1+
_
2628 L2
(*) Link terminals 30 and 32 if the relay is connected at the end of the RS485 bus
MiCOMP723
491A
5051
1A5253
1A5455
1A5641
5A4243
5A4445
5A4647
5A48
P793
PROTECTED ZONE
TC1
CT1
P793
TC2
CT2
TCN
CTN
CBA
_
1719 L3+
_
2123 L4
+
_
2527 L5
Device Track Record -High Impedance Differential Protection
• MiCOM P12x series relays used in high-impedance applications since 1998
• MiCOM P14X series relays used in high-impedance applications since 1999
P721 – P723 Technical DataSheet 9 P72x/EN TDS/B21
RATINGS
Power Supply
Nominal auxiliary voltage Vx
48 -250 Vdc/ 48-240 Vac 24-250 Vdc/ 48-240Vac
Operating range DC: ± 20% of Vx AC: – 20%, +10% of Vx
Residual ripple Up to 12%
Stored energy time
50 ms for interruption of Vx
Burden Stand by: <3W DC or <8VA ACMax: <6W DC or <14VA AC
Frequency
Frequency protection functions
Nominal frequency 5Hz
Nominal frequency 50/60 Hz
Current inputs
Phase current inputs
1 and 5 A by connection
Earth current inputs
1 and 5 A by connection
Operating range Selected at order (Cortec)
Burden Phase Current
< 0.025 VA (1 A) < 0.3 VA (5 A)
Burden Earth Current
< 0.08 VA (1 A) < 0.42 VA (5 A)
Thermal withstand
1 s @ 100 x rated current 2 s @ 40 x rated current continuous @ 4 x rated current
Phase and earth current transformers consumption
P72x phase CT consumption
phase transformer 5A
RM
S v
olta
ge (
V)
Current (A)
phase transformer 1A
phase transformer 5A
RM
S v
olta
ge (
V)
Current (A)
phase transformer 1A
P72x earth CT consumption
earth transformer 5A
RM
S v
olta
ge (
V)
Current (A)
earth transformer 1A
earth transformer 5A
RM
S v
olta
ge (
V)
Current (A)
earth transformer 1A
Logic inputs
Logic input type Independent optically insulated
Logic input burden < 10 mA per input
Logic input recognition time (DC inputs)
< 5 ms in a 50 Hz system < 4 ms in a 60 Hz system
Logic input recognition time (AC inputs)
<7 ms in a 50 Hz system < 6 ms in a 60 Hz system
Logic input recognition time (ENA inputs)
<15 ms in a 50 Hz system < 12 ms in a 60 Hz system
P721 – P723 Technical DataSheet 10 P72x/EN TDS/B21
Supply
Relay auxiliary power supply Logic Inputs
Ord
erin
g C
ode
Nominal voltage range
Vx
Operating voltage range
Nominal Voltage range
Minimal polarisation
voltage
Maximum polarisation
current
Holding current
after 2ms
Maximum continuou
s withstand
A* 24–60Vdc 19,2–76Vdc
F* 48–250Vdc 48–240Vac
38.4–300Vdc 38.4–264Vac
24–250Vdc 24–240Vac
19.2Vdc 19.2Vac
35mA
2.3mA
300Vdc264Vac
T 48–250Vdc 48–240Vac Special EA
38.4–300Vdc 38.4–264Vac
24–250Vdc 24–240Vac
19.2Vdc 19.2Vac
35mA
2.3mA
300Vdc264Vac
H 48–250Vdc 48–240Vac
38.4–300Vdc 38.4–264Vac
129Vdc
105Vdc
3.0 mA @ 129Vdc
145Vdc
V 48–250Vdc 48–240Vac
38.4–300Vdc 38.4–264Vac
110Vdc
77Vdc
7.3 mA @ 110Vdc
132Vdc
W 48–250Vdc 48–240Vac
38.4–300Vdc 38.4–264Vac
220Vdc
154Vdc
3.4 mA @ 220Vdc
262Vdc
Z 24–250Vdc 48–250Vac
19,2–300Vdc 38,2–264Vac
24–250Vdc 24–240Vac
19.2Vdc 19.2Vac
35mA
2.3mA
300Vdc264Vac
(*) Ordering code (Cortec) options A and F are not available for sale
(**) Logic input recognition time for EA approval. Dedicated filtering on 24 samples (15ms at 50Hz).
Output Relay Characteristic
Contact rating
Contact relay Dry contact Ag Ni
Make current Max. 30 A and carry for 3s
Carry capacity 5 A continuous
Rated Voltage 250 Vac
Breaking characteristic
Breaking capacity AC 1500 VA resistive 1500 VA inductive (P.F. = 0.5) 220 Vac, 5 A (cos = 0.6)
Breaking capacity DC 135 Vdc, 0.3 A (L/R = 30 ms)250 Vdc, 50W resistive or 25 W inductive (L/R=40 ms)
Operation time <7 ms
Durability
Loaded contact 10000 operation minimum
Unloaded contact 100000 operation minimum
TYPICAL OPERATING TIMES
The typical operating times for Restricted earth fault and balanced earth fault (REF/BEF) applications are shown in Figure 1. To determine the typical operating times the current levels considered were 1In, 5In, 10In and 20In and the point on wave was varied from 0 to 150 in 30
steps. The tests were performed considering [87N] Threshold I Diff set to 0.5In and 0.1In and [87N] Measurement Filter set to Fourier, Sample and Fast Sample.
0.000
0.010
0.020
0.030
0.040
0.050
0.060
0.070
0.080
0.090
0 10 20 30 40 50 60 70 80 90 100
multiple of setting (xIsetting)
tim
e (s
)
fourier fast sample
Figure 1 Typical operating times – REF/BEF applications
P721 – P723 Technical DataSheet 11 P72x/EN TDS/B21
The typical operating times for busbar applications are shown in Figure 2, Figure 3 and Figure 4. To determine the typical operating times the current levels considered were 5In, 10In, 25In and 50In and the point on wave was varied from 0 to 150 in 30 steps. The tests were
performed considering [87] Threshold I Diff set to 0.5In and 0.1In and [87] Measurement Filter set to Fourier, Sample and Fast Sample.
Single Phase Fault
0.020
0.025
0.030
0.035
0.040
0.045
0.050
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
multiple of setting (xIsetting)
typ
ical
op
erat
ing
tim
e (s
)
Fourier Fast Sample Sample
Figure 2 Typical operating times – Single phase faults – Busbar applications
P721 – P723 Technical DataSheet 12 P72x/EN TDS/B21
Phase to Phase Faults
0.0200
0.0250
0.0300
0.0350
0.0400
0.0450
10 20 30 40 50 60 70 80 90 100
multiples of setting (xIsetting)
typ
ical
op
era
tin
g t
ime
(s)
Fourier Fast Sample Sample
Figure 3 Typical operating times – Phase to phase faults – Busbar applications
Three Phase Faults
0.0100
0.0150
0.0200
0.0250
0.0300
0.0350
0.0400
10 20 30 40 50 60 70 80 90 100
multiples of setting (xIsetting)
typ
ical
op
era
tin
g t
ime
(s)
Fourier Fast sample Sample
Figure 4 Typical operating times – Three phase faults – Busbar applications
P721 – P723 Technical DataSheet 13 P72x/EN TDS/B21
INSULATION
Dielectric withstand IEC 60255-5 : 2000 2 kV common mode 1 kV differential mode
ANSI/IEEE C37.90-1989 (reaffirmed 1994) 1.5 kV rms AC for 1 minute, across normally open contacts.
Impulse voltage IEC 60255-5 : 2000 5 kV common mode 1 kV differential mode
Insulation resistance IEC 60255-5 : 2000 > 1000 M
EMC TESTS
High Frequency Disturbance IEC 60255-22-1:1988 2.5 kV common mode, Class III 1 kV differential mode, Class III
Electrostatic Discharge EN 61000-4-2: 1995 and IEC 60255-22-2: 1996 8 kV contact discharge, Class 4 15 kV air discharge, Class 4
Fast Transient IEC 60255-22-4:2002, Class A 2 kV 5 kHz, terminal block comms. 4 kV 2.5 kHz, all circuits excluding comms.
EN 61000-4-4:1995, Level 4 4 kV 5 kHz, power supply 2 kV 5 kHz, all circuits excluding power supply
Surge EN 61000-4-5:1995 and IEC 60255-22-5:2002 4 kV common mode, Level 4 2 kV differential mode, Level 4
Conducted Emissions
EN 55022: 1998 0.15 - 0.5 MHz, 79 dBµV (quasi peak) 66 dBµV (average)
0.5 – 30 MHz, 73 dBµV (quasi peak) 60 dBµV (average).
Radiated Emissions
EN 55022: 1998 30 – 230 MHz, 40 dBµV/m at 10 m measurement distance
230 – 1 GHz, 47 dBµV/m at 10 m measurement distance.
Conducted Immunity
EN 61000-4-6:1996 Level 3, 10 V rms @ 1 kHz 80% am, 150 kHz to 80 MHz
Radiated Immunity
EN 61000-4-3:2002 ANSI/IEEE C37.90.2:2004
Level 3, 10 V/m 80 MHz to 1 GHz @ 1 kHz 80% am
35 V/m 80 MHz to 1 GHz @ 1 kHz 80% am
35 V/m 80 MHz to 1 GHz @ 100% pulse modulated front face only.
Radiated immunity from digital telephones
EN 61000-4-3:2002 Level 4, 30 V/m 800 MHz to 960 MHz and 1.4 GHz to 2 GHz @ 1 kHz 80% am
ANSI Surge Withstand Capability
IEEE/ANSI C37.90.1: 2002 4 kV fast transient and 2.5 kV oscillatory applied common mode and differential mode
Magnetic Field Immunity
IEC 61000-4-8: 1994 IEC 61000-4-9: 1993 IEC 61000-4-10: 1993
Level 5, 100 A/m applied continuously, 1000 A/m for 3 s. Level 5, 1000 A/m. Level 5, 100 A/m at 100 kHz and 1 MHz.
ENVIRONMENT
Temperature IEC 60068-2-1 : 1993 Storage –25 °C to +70 °C IEC 60068-2-2: 1993 Operation: –25 °C to + 55 °C –25 °C to 70 °C (*) (*) The upper limit is permissible for a single 6 hour duration within any 24 hour period.
Humidity damp heat IEC 60068-2-78:2001 56 days at 93% RH and 40 °C
Enclosure protection IEC 60-529: 2001 Dust IP50 (whole case), Front IP 52, Back IP 10
Sinusoidal Vibrations IEC 60255-21-1:1998 Response and endurance, class 2
Shocks IEC 60255-21-2:1998 Response and withstand, class 2
Shock withstand & Bump IEC 60255-21-2:1998 Response and withstand, class 1
Seismic IEC 60255-21-3:1993 Class 2
Corrosive Environments : Per IEC 60068-2-60: 1995, Part 2, Test Ke, Method (class) 3 Industrial corrosive environment/poor environmental control, mixed gas flow test. 21 days at 75% relative humidity and +30°C Exposure to elevated concentrations of H²S, NO², Cl² and SO².
EU DIRECTIVE
EMC compliance
89/336/EEC
93/31/EEC
Compliance with European Commission EMC Directive.
Generic standards were used to establish conformity: EN50081-2: 1994 EN60952-2: 1995
Product safety
2006/95/EC
(replacing 73/23/EEC from 01/2007)
Compliance with European Commission Low Voltage Directive. Compliance is demonstrated by reference to generic safety standards: EN61010-1: 1993/A2: 1995 EN60950: 1992/A11: 1997
DEVIATION OF PROTECTION ELEMENTS
P721 – P723 Technical DataSheet 14 P72x/EN TDS/B21
Element Range Deviation Fault timer Reset timer
Earth differential protection I diff (V diff)
0.01In to 1In (0.5 to 200 V)
2% 0 s – 2 s 0 to 600 s
Phase differential protection I diff (V diff)
0.02 to 2In (1 to 400 V)
2% 0 s – 2 s 0 to 600 s
Earth bus-wire supervision
0.01 to 1 In (0.5 to 200 V)
2% 0.5 s – 3 s 0 to 600 s
Phase bus-wire supervision I Sup (V Sup)
0.02 to 2In (1 to 400 V)
2% 0.5 s – 3 s 0 to 600 s
DEVIATION OF AUTOMATION FUNCTIONS TIMERS CB fail & CB monitoring timers 2% 0-10 s
Auxiliary timers tAUX1, tAUX2, tAUX3, tAUX4
2% 0-200 s
DEVIATION OF MEASUREMENTS Measurement Range Deviation
Phase current 0.02In to 10In Typical 0.5% at In
Earth current 0.004In to 2In Typical 0.5% at In
PROTECTIONS FUNCTIONS
Settings
[87N] Earth differential protection
[87N] Earth differential protection Yes / No [87N] Threshold I diff 0.01In to 1In [87N] Threshold V diff 0.5 V to 200 V [87N] Filter timer t Diff 0 s to 2 s [87N] Reset timer tReset 0 to 600 s Measurement Filter Sample mode Fast sample mode Fourier mode
[95N] Earth bus-wire supervision
[95N] Earth bus-wire supervision Yes / No [95N] Threshold I sup 0.01In to 1In [95N] Threshold V sup 0.5 V to 200 V [95N] Filter timer t sup 0.5 s to 3 s [95N] Reset timer tReset 0 to 600 s Measurement Filter Sample mode Fast sample mode Fourier mode
[87] Phase differential protection (P723 only)
[87] Phase differential protection Yes / No [87] Threshold I diff 0.02In to 2In [87] Threshold V diff 1 V to 400 V [87] Filter timer t Diff 0 s to 2 s [87] Check zone Yes / No [87] Reset timer tReset 0 to 600 s Measurement Filter Sample mode Fast sample mode Fourier mode
[95] Phase bus-wire supervision (P723 only)
[95] Phase bus-wire supervision Yes / No [95] Threshold I sup 0.02In to 2In [95] Threshold V sup 0.5 V to 400 V [95] Filter timer t sup 0.5 s to 3 s [95] Check zone Yes / No [95] Reset timer tReset 0 to 600 s Measurement Filter Sample mode Fast sample mode Fourier mode
P721 – P723 Technical DataSheet 15 P72x/EN TDS/B21
Automation and accessory functions
Trip command
Assignation of the following thresholds to trip output relay: – all models: [87N] tDiff, t Aux 1, t Aux 2, Control Trip,
tEqu.A, tEqu.B, tEqu.C, tEqu.D, tEqu.E, tEqu.F, tEqu.G, tEqu.H,
– P723 additional functions: [87] tDiff, t Aux 3 and t Aux 4
Latch functions
Trip output relay programmable with one or many thresholds: – all models: [87N] tDiff, t Aux 1, t Aux 2, Control Trip,
tEqu.A, tEqu.B, tEqu.C, tEqu.D, tEqu.E, tEqu.F, tEqu.G, tEqu.H.
– P723 additional functions: [87] tDiff, t Aux 3, t Aux 4.
Blocking logic
Possibility to block the following delayed thresholds: – all models: [87N] tDiff, t Aux 1, t Aux 2, – P723 additional functions: [87] tDiff, t Aux 3 and
t Aux 4.
Output relays
Alarm and trip threshold assignation to a logic output: 3 relays (P721) and 7 relays (P723). Assignable functions: – all models: [87N] Diff, [87N] tDiff, [95N] Sup, [95N]
tSup, Buswire Short, CB Fail, t Aux 1, t Aux 2, Active group, Control trip, Input1, Input2, tEqu. A , tEqu. B, tEqu. C, tEqu D, tEqu E, tEqu. F , tEqu. G, tEqu. H.
– P723 additional functions: [87] Diff, [87] tDiff, [87CZ] ChkZone, [95] Sup, [95] tSup, [95A] tSup A, [95B] tSup B, [95C] tSup C, t Aux 3, t Aux 4, Input3, Input4, Input5
Latch of the auxiliary output relays
Possibility to latch output relays: – P721: Output 2 to 4 – P723: Output 2 to 8
Inputs
Inputs assignation Single function or multiple automation functions assignable to 4 logic inputs: – all models: Unlatch, Aux 1, Aux 2, Blocking Logic 1,
Blocking Logic 2, Start Disturb, Change setting, Reset LEDs, Maint. Mode, Local Mode, Synchro
– P723 additional functions: Aux 3, Aux 4, [87CZ] Chk Zone
Auxiliary timers: – Aux1 time tAux1 0 to 200s – Aux2 time tAux2 0 to 200s – Aux3 time tAux3 0 to 200s – Aux4 time tAux4 0 to 200s
Circuit Breaker Failure
CB Fail Setting Ranges: – CB Fail ? Yes / No I Diff < 0.01 In to 1 In V Diff < 0.5 v to 200 V CB Fail Time tBF 0 to 10s
Logic Equations
The MiCOM P721 and P723 relays integrate complete logic equations to allow customization of the product based on customer application. Up to 8 independent Boolean equations can be used (from A to H). Every result of equation can be time delayed and assigned to any output relays, trip, trip latching and/or HMI LEDs. Up to 16 operands can be used (from 00 to 15). Within operands, there are two parts: – (1/2) : logical gates (NOT, OR, AND, NOT AND, NOT
OR) – (2/2) : signals ([87N] Diff, [95N] tSup, tAux, input…etc) Timer Setting Ranges – EQU. A to H Toperat 0 to 600 s – EQU. A to H Treset 0 to 600 s Available logical gates:
Logical gates
Availability (1/2)
NOT A00, B00, C00, D00, E00, F00, G00, H00
OR (by default) AND AND NOT OR NOT
A01 to A15, B01 to B15, C01 to C15, D01 to D15, E01 to E15, F01 to F15 G01 to G15, H01 to H15
Available signals:
Text Signals (2/2)
P721 and P723:
Null Condition is Null Not Null Condition is not Null [87N] Diff Earth differential protection threshold [87N] tDiff Time delayed earth differential protection threshold [95N] tSup Time delayed earth high impedance differential
threshold (buswire supervision) tAux 1 Copy of the status of the Logic Input tAux 1 tAux 2 Copy of the status of the Logic Input tAux 2 Input 1 Instantaneous digital input 1 Input 2 Instantaneous digital input 2 Group 2 Group 2 is active (setting) CB Fail Circuit Breaker does not operate
P723 only:
[87] Diff Phase differential protection threshold [87] tDiff Time delayed phase differential protection threshold [87CZ] Check zone Check Zone status [95] Sup Phase high impedance differential threshold
(buswire supervision) [95N] Sup Earth high impedance differential threshold (buswire
supervision) [95] tSup Time delayed phase high impedance differential
threshold (buswire supervision) [95A] tSupA Time delayed phase A (or L1, or R) high impedance
differential threshold (buswire supervision) [95B] tSupB As above for phase B (or L2 or S) [95C] tSupC As above for phase C (or L3 or T) Buswire Short Buswires short-circuited tAux 3 Copy of the status of the Logic Input tAux 3 tAux 4 Copy of the status of the Logic Input tAux 4 Input 3 Instantaneous digital input 3 Input 4 Instantaneous digital input 4 Input 5 Instantaneous digital input 5
P721 – P723 Technical DataSheet 16 P72x/EN TDS/B21
RECORDING FUNCTIONS Fault Record
Capacity 25 faults
Time-tag 1 millisecond
Triggers Any selected protection alarm and threshold
Data Fault date, Active setting Group, Faulted phase, Threshold, Fault magnitude, [87] tDIFF fault (tripping) [87N] tDIFF fault (tripping) tAux 1 fault (tripping) tAux 2 fault (tripping) tAux 3 fault (tripping) tAux 4 fault (tripping) tEquation A, B, C, D, E, F, G and H fault (tripping) Control trip
Instantaneous recorder
Capacity 5 starting items of information (instantaneous)
Time-tag 1 millisecond
Triggers Any selected protection alarm and threshold
Data date, hour origin (any protection alarm) length (duration of the instantaneous trip yes or no
Disturbance Records Triggers; Data; Setting Ranges
Triggers Any selected protection alarm and threshold, logic input, remote command
Data AC input channels digital input and output states frequency value
Default value Setting range
P72x Min Max Step
Pre-Time 1.0 s 0.1 s 3 s 0.1 s
Post-Time 2.0 s 0.1 s 3 s 0.1 s
Disturb rec Trig
ON INST ON TRIP or ON INST.
Trigger Any selected protection alarm and threshold Logic input Remote command
Communications
Type Port
Relay position Physical Link Connectors Data Rate Protocol
RS485 Rear port Screened twister pair
Screws or snap-on
300 to 38400 baud (programmable)
ModBus RTU, Courier, IEC60870-5-103, DNP3.0
RS232 Front port Screened twister pair
Sub–D 9 pin female connector
300 to 38400 baud (programmable)
ModBus RTU
P721 – P723 Technical DataSheet 17 P72x/EN TDS/B21
DIMENSIONS
P721 and P723:
External size: Height case 152 mm front panel 177 mm Width case 97 mm front panel 103 mm Depth case 226 mm front panel + case 252 mm
P0078ENb
Figure Dimensional drawings
P721 – P723 Technical DataSheet 18 P72x/EN TDS/B21
WIRING CONNECTIONS Typical application diagram P721
CB
29
RS
485
Nota
:(1
)
(c)
(a)
(b)
30
32
*
31- +
34
P721
MiC
OM
26
28
24
22
L2
L1
RL4
RL2
RL3
RL1
20
1810 8 16
141224
33
+ -6
(d)
+ - + -
47
55
53
49
51
37 45
43
41
39
35
33
29
31
48
56
54
52
5038
46
44
4240
36
34
32
30
24
23
27
25
28
262
1 21
19
15
17
13
22
20
16
18
14
7 9 1153
8 12
1064
A
48
4756
55
WD
36
35
37
Phase
rota
tion
Auxili
ary
voltage
Pro
gra
mm
able
input
Pro
gra
mm
able
input
Case
eart
h
Module
term
inalblo
cks
vie
wed
from
pre
ar
(with
inte
gra
lcase
eart
hlin
k)
Watc
hdog
(4)
Pro
gra
mm
able
trip
pin
goutp
ut
Pro
gra
mm
able
outp
ut
Pro
gra
mm
able
outp
ut
Case
eart
hconnection
Port
com
munic
ation
(:Lin
kte
rmin
als
30
and
32
ifth
ere
lay
isconnecte
datth
eend
ofth
eR
S485
bus
)
CT
short
ing
links
make
befo
re(b
)
Short
term
inals
bre
ak
befo
re(c
)
Long
term
inals
Pin
ste
rmin
als
(pcb
type)
(2)
CT
connection
are
typic
alonly
(3)
Eart
hte
rmin
als
are
typic
alonly
(4)
The
MIC
OM
P120/P
121
rela
ys
are
show
nw
ith
supply
off.
*
CA B
5A
48
4756
1A
55
Altern
ative
:R
estr
icte
dE
art
hF
ault
Pro
tection
(Delta
connection)
CA B
P791
sta
bili
sin
gre
sis
tors
Altern
ative
:R
estr
icte
dE
art
hF
ault
Pro
tection
(S
tar
connection)
P791
(-V
)A
uxili
ary
voltage
Ctr
lshort
ing
rela
y
and
(c)
dis
connect
5A
1A
P791
(-V
)A
uxili
ary
voltage
Ctr
lshort
ing
rela
y
Auxili
ary
voltage
(+V
)
RS
t.R
St.
P3955ENa
{{ {
{{{{
P721 – P723 Technical DataSheet 19 P72x/EN TDS/B21
Typical application diagram P723
29
RS
48
5
Nota
:(1
)
(c)
(a)
(b)
30
32
*
31- +
34
P7
23
MiC
OM
33
+ -
Te
rre
bo
îtie
r
(d)
47
55
53
49
51
37 45
43
41
39
35
33
29
31
48
56
54
52
5038
46
44
4240
36
34
32
30
24
23
27
25
28
262
1 21
19
15
17
13
22
20
16
18
14
7 9 1153
8 12
1064
5A
5A
5A
5A
1A
1A
48
4746
45
44
43
4241
56
55
54
52 53
1A
1A
50
51
49
Altern
ative
:R
estr
icte
dE
art
hF
ault
Pro
tection
(S
tar
connection)
Au
xili
ary
vo
lta
ge
Thre
e-P
hase
Hig
hIm
pedance
Diffe
rential
Ca
se
ea
rth
Mo
du
lete
rmin
alb
locks
vie
we
dfr
om
pre
ar
(with
inte
gra
lca
se
ea
rth
link)
Ca
se
ea
rth
co
nn
ectio
n
Po
rtco
mm
un
ica
tio
n
(:
Lin
kte
rmin
als
30
an
d3
2if
the
rela
yis
co
nn
ecte
da
tth
ee
nd
of
the
RS
48
5b
us
)
CT
sh
ort
ing
links
ma
ke
be
fore
(b)
an
d(c
)d
isco
nn
ect
Sh
ort
term
ina
lsb
rea
kb
efo
re(c
)
Lo
ng
term
ina
ls
Pin
ste
rmin
als
(pcb
typ
e)
(2)
CT
co
nn
ectio
na
rety
pic
alo
nly
(3)
Ea
rth
term
ina
lsa
rety
pic
alo
nly
(4)
Th
eM
ICO
Mre
lays
are
sh
ow
nw
ith
su
pp
lyo
ff.
*
Altern
ative
:R
estr
icte
dE
art
hF
ault
Pro
tection
(Delta
connection)
L3
23
27
25
{{{{{{
21
19
L5
L4
26
17
28
24
22
L2
L1
+ - + - + - + - + -
Pro
gra
mm
ab
lein
pu
t
Pro
gra
mm
ab
lein
pu
t
Pro
gra
mm
ab
lein
pu
tinp
ut
Pro
gra
mm
ab
le
Pro
gra
mm
ab
lein
pu
t
RL
7
RL
8
13
15
11
{{{{{{{{
RL
6
RL
5
RL
4
RL
2
RL
3
RL
1
5 971320
1810 8 16
1412246
WD
36
35
37
Wa
tch
Do
g(4
)
Pro
gra
mm
ab
letr
ipp
ing
ou
tpu
t
Pro
gra
mm
ab
leo
utp
ut
Pro
gra
mm
ab
leo
utp
ut
Pro
gra
mm
ab
leo
utp
ut
Pro
gra
mm
ab
leo
utp
ut
Pro
gra
mm
ab
leo
utp
ut
Pro
gra
mm
ab
leo
utp
ut
CB
A
Ph
ase
rota
tio
n
P793
P7
91
an
dP
79
3sta
bili
sin
gre
sis
tors
(-V
)A
uxili
ary
vo
lta
ge
Ctr
lsh
ort
ing
rela
y
Au
xili
ary
vo
lta
ge
(+V
)
CA B
5A
48
5A
47
4645
44
5A
5A
43
42
41
56
1A
1A
55
54
53
52
1A
51
1A
50
49
P791
(-V
)A
uxili
ary
vo
lta
ge
Ctr
lsh
ort
ing
rela
y
CA B
5A
48
5A
47
4645
44
5A
5A
43
42
41
56
1A
1A
55
54
53
52
1A
51
1A
50
49
P791
(-V
)A
uxili
ary
vo
lta
ge
Ctr
lsh
ort
ing
rela
y
RS
t.
CT1
CT2
CTn
RS
t.
RS
t.
RS
t.
RS
t.
P3954ENa
P721 – P723 Technical DataSheet 20 P72x/EN TDS/B21
ORDERING OPTIONS
Information Required with Order
Relay Type (differential protection) P72 0 0 0
Variant Simple phase high impedance differential protection
Simple phase or three phase high impedance protection with binary I/O extension
1
3
Auxiliary and digital input voltage
Auxiliary voltage digital input voltage
48-250 Vdc / 48-240 Vac48-250 Vdc / 48-240 Vac48-250 Vdc / 48-240 Vac48-250 Vdc / 48-240 Vac24-250Vdc / 48-240Vac
105-145 Vdc (1) 48-250 Vdc (ENA UK) 110 Vdc –30% / +20% (1) 220 Vdc –30% / +20% (1) 24-250 Vdc / 24 / 240 Vdc
H T V W Z
Rear port communication interface
Modbus K-Bus/Courier IEC 60870-5-103 DNP 3.0
1 2 3 4
Default HMI language
French English / American Spanish German Italian Portuguese
0 1 2 3 4 7
Platform
phase 2 with standard software 2
Software
Unless specified the latest version will be delivered
Mounting option
None (default) (2) Pre-fixed HMI (no withdrawability) Sealed cover (2) Pre-fixed HMI + Sealed cover
0123
(1) : special application (2) : : not available
Schneider Electric
35 rue Joseph Monier 92506 Rueil-Malmaison FRANCE
Phone: +33 (0) 1 41 29 70 00 Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P72x/EN TDS/B21 03/2012
2
012
Sch
neid
er E
lect
ric. A
ll rig
hts
rese
rved
.