Micro MotionSeries 1000 and 2000 Transmitterswith MVD Technology!

Product Data SheetPS-00400June 2002

www.micromotion.com

Page 2: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

2 Series 1000 and 2000 Transmitters

Micro Motion® Series 1000 and 2000 Transmitterswith MVD™ Technology

The new approach tosensor electronics

Only Micro Motion® combines new MVD™

Technology with a modular architecture thatredefines sensor electronics. That meansmultivariable digital processing that’s scalable forany flow application. MVD Technology gets yourmost basic – or most complex – application upand running quicker, easier and more costeffectively than ever before.

MVD Technology

MVD Technology makes your Micro Motionflowmeter work smarter. Front-end digitalprocessing dramatically reduces signal noise andgives you faster response time compared toanalog devices. Innovative MVD Technology alsoenables multiple variable measurement anddiagnostics never before possible. And this is justthe beginning.

Only MVD Technology allows you to:

• Measure multiple variables

• Choose integral or remote mounting with astandard twisted, shielded 4-wire signalcable

• Identify and resolve problems easily withbuilt-in smart diagnostics

• Choose transmitter capabilities based onyour application’s needs

• Upgrade transmitter functionalityas needed

What’s the bottom line of MVD Technology?

Reducing costs in your bottom line throughimproved process consistency andmaximized uptime.

Scalable architecture

You asked for it and Micro Motion has delivered.Series 1000 and 2000 transmitters allow you tochoose the functionality you want. Series 1000transmitters are perfect for applications thatrequire single variable measurement. For moredemanding applications, Series 2000 transmittersmeasure multiple variables simultaneously, haveadditional output and digital communicationoptions, and can be used in custody transferapplications.

What happens when you put Micro Motion’sMVD Technology together with the Series 1000and 2000 transmitters?

Only four wires

Approved forhazardous areas

Page 3: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

Series 1000 and 2000 Transmitters 3

Clean, noise-freedigital signals thatimprovemeasurementperformance

Delivering a suite of power-packedstandard features

All Series 1000 and 2000 transmitters offer:

• Class I, Division 1/Zone 1 local operatorinterface to:

• View process variables

• View meter status at a glance

• View and acknowledge alarms

• Start, stop, and reset transmitter totalizers

• Zero flowmeter

• Perform output simulation tests

• Change measurement units

• Assign variables to outputs

• Scale outputs

• Set RS-485 communication options

• Interface functions can be customized andpassword protected

• Compact, integral mounting to sensor with360 degrees of rotation

• Cost-effective, hassle-free, 4-wire remotemounting to sensor

• Simple start-up with virtually no specialprogramming requirements

• Digital communications

• Easy-to-access diagnostics: meter status,process issues, and more

Series 1000 flow measurement transmitter

For applications requiring only mass flow orvolume flow measurement

Series 1000 transmitters are ideal for flowapplications where only a single variable isneeded at any given time. Series 1000transmitters feature a milliamp and afrequency/pulse output, and HART® or Modbus®

digital communications.

Series 1000 transmitters can output one of thefollowing variables:

• Mass flow rate

• Volume flow rate

Series 2000 Multivariable Transmitter

For applications requiring simultaneousmonitoring of multiple flow variables

Series 2000 transmitters are designed specificallyfor applications where multiple variables areneeded simultaneously. Series 2000 transmittersfeature a milliamp and a frequency/pulse output,plus HART, Modbus, FOUNDATION™ Fieldbus, andProfibus-PA digital communications.

Series 2000 transmitters can simultaneouslyoutput multiple variables, including:

• Mass flow rate

• Volume flow rate

• Density

• Temperature

• Drive gain

Page 4: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

4 Series 1000 and 2000 Transmitters

Series 1000 and Series 2000 Transmitters

Offering options tailored to meet yourapplication needs

Discrete batch control

Simple discrete batch control is easy using theModel 2700 transmitter. The frequency output canbe configured as a discrete output, using batchtargets entered from a host control system or fromthe local display. If additional inputs or outputs arerequired, the Series 3000 transmitter/controllershould also be considered.

Petroleum measurement

The Model 2700 with the petroleum measurementsoftware option software option can calculate:

• Base density

• CTL (the effect of temperature on a liquid)

• Gross volume at standard temperature

• Flow weighted average temperature

• Flow weighted average density (observedgravity)

One instrument can now be used to measurecorrected volume flow and corrected density,eliminating the need for a densitometer, reducingmaintenance, and lowering your capitalinvestment. No calibration or recalibration fordifferent density fluids is required. The softwareuses API MPMS Chapter 11.1 for GeneralizedPetroleum, Generalized Crude Oil, Lubricants,and other fluids with a known thermal coefficientof expansion to calculate base density from theflowing density and flowing temperature.

Custody transfer

Series 2000 transmitters feature physical securityfor custody transfer applications such as bottlefilling, CNG dispensing, and vehicle loading andunloading. Micro Motion Coriolis meters providelegal trade accuracies for a wide range of fluidswithout the need for upstream and downstreamstraight runs and without the need for externalcompensation. Custody transfer based on massflow eliminates many of the problems associatedwith volumetric technologies: Coriolis meters haveno moving parts, are not affected by seasonalvariations in quantities delivered due totemperature changes, and can eliminate re-workand waste by providing the correct amount ofproduct every time.

Fast response time

Series 1000 and 2000 transmitters offer as astandard feature a selectable response time forthe analog output and frequency output. Thenormal response mode uses the maximumamount of digital signal processing (DSP) and a20 Hz update rate for the selected processvariable. The special response mode uses a100 Hz update rate with slightly reduced noiserejection. Micro Motion Coriolis sensors withSeries 1000 and 2000 transmitters are an idealchoice for applications that require fast, accuratemeasurements. MVD DSP provides excellentrepeatability with batch times as low as 1 secondin duration, and eliminates process variations dueto density and temperature changes.

Page 5: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

Series 1000 and 2000 Transmitters 5

Series 1000 and 2000 functional specifications

Electrical connectionsInput and output connections

Three pairs of wiring terminals for transmitter outputs.

Screw terminals accept one or two solid conductors, 14 to12 AWG (2.5 to 4 mm2); or one or two stranded conductors,22 to 14 AWG (0.34 to 2.5 mm2).

Power connectionOne pair of wiring terminals accepts either AC or DCpower.

One internal ground lug for power-supply ground wiring.

Screw terminals accept one or two solid conductors, 14 to12 AWG (2.5 to 4 mm2); or one or two stranded conductors,22 to 14 AWG (0.34 to 2.5 mm2).

Service port connectionTwo clips for temporary connection to the service port

Input/output signalsAll transmitters

One 4-wire sensor signal input connection with ground,intrinsically safe

Non-intrinsically safe output HART/Modbus transmitters(output option code A, see page 9 for output option codedescriptions)

One active 4–20 mA outputNot intrinsically safeIsolated to ±50 VDC from all other outputs and earth

groundMaximum load limit, 600 ohmsSeries 1000 can report mass flow or volume flow; Series

2000 can report mass flow, volume flow, density,temperature, or drive gain

Output is linear with process from 3.8 to 20.5 mA, perNAMUR NE43 (June 1994)

One active or passive frequency/pulse outputNot intrinsically safeCan report mass flow or volume flow, which can be used

to indicate flow rate or totalFor Series 1000, if mA output is not assigned to flow

rate, the frequency output acts as a discrete outputFor Series 2000, frequency output is independent of

mA outputScalable to 10,000 HzMaximum output of 30 VDC max., 24 VDC typicalInternal 2.2 kohm pull-up, sinking up to 500 mA at 30

VDC maximumOutput is linear with flow rate to 12,500 Hz

Non-intrinsically safe configurable output transmittersfor Series 2000 transmitters (output options codes Band C, see page 9 for output option code descriptions)

Two active 4–20 mA outputsNot intrinsically safeIsolated to ±50 VDC from all other outputs and earth

groundMaximum load limit: mA1 — 820 ohms;

mA2 — 420 ohmsSeries 2000 can report mass flow, volume flow, density,

temperature, or drive gainOutput is linear with process from 3.8 to 20.5 mA, per

NAMUR NE43 (June 1994)

Two active or passive frequency/pulse outputsNot intrinsically safeCan report mass flow or volume flow, which can be used

to indicate flow rate or totalOutputs are electrically isolated but not independent

(see custody transfer note below)Scalable to 10,000 HzInternally powered to +15 VDC ±3%Externally powered 3–30 VDC max., internal 2.2 kohm

pull-up, sinking up to 500 mA at 30 VDC maximumOutput is linear with flow rate to 12,500 Hz

Two discrete outputsNot intrinsically safeCan report event 1, event 2, event 1 and 2, flow switch,

forward/reverse flow, calibration in progress, or faultMaximum sink capability is 500 mA

One discrete inputCan report none, start mechanical zero, reset mass

total, reset volume total, reset corrected volume total,or reset totals

Custody transfer using double pulse frequency outputThe transmitter can be configured for two frequencyoutputs on channels B and C. The frequency outputs arenot independent – they are identical in frequency. Theoutput on channel C can be phase-shifted 0, 90, or 180degrees from the output on channel B. The direction of flowcan be inferred from the direction of phase shift, and theamount of flow can be determined by reading channel B. Inaddition, channel C can output zero to indicate a faultcondition.

Page 6: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

6 Series 1000 and 2000 Transmitters

Series 1000 and 2000 functional specifications continued

Intrinsically safe transmitters (output option code D, seepage 9 for output option code descriptions)

One intrinsically safe passive 4–20mA output (two withSeries 2000)

Maximum input voltage, 30 VDC, 1 watt maximumMaximum current 300 mAMaximum load limits, see chart belowSeries 1000 can report mass flow or volume flow; Series

2000 can report mass flow, volume flow, density,temperature, or drive gain

Output is linear with process from 3.8 to 20.5 mA, perNAMUR NE43 (June 1994)

One intrinsically safe passive output, configurable asfrequency, pulse, or discrete output

Maximum input voltage, 30 VDC, 0.75 watt maximumMaximum current 100 mAMaximum load limit, see chart belowCan report mass flow or volume flow, which can be used

to indicate flow rate or totalFor Series 1000, output is dependent on mA output; for

Series 2000, output is independentScalable to 10,000 HzOutput is linear with flow rate to 12,500 Hz

Fieldbus and PROFIBUS-PA transmittersOne FOUNDATION fieldbus H1 or PROFIBUS-PA output

FOUNDATION fieldbus and PROFIBUS-PA wiring isintrinsically safe with an intrinsically safe powersupply

Manchester-encoded digital signal conforms to IEC1158-2.

0

100

200

300

400

500

600

700

800

900

1000

12 14 16 18 20 22 24 26 28 30

mA Output Load Resistance ValueRmax = (Vsupply - 12)/0.0023*

*If communicating with HART a minimum of 250 ohms and 17.75V supply is needed

Supply voltage (volts)

Ext

erna

lres

isto

r(o

hms)

OperatingRegion

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

5 7 9 11 13 15 17 19 21 23 25 27 29

Frequency Output Load Resistance ValueRmax = (Vsupply - 4)/0.003

*Rmin = (Vsupply - 25)/0.006*Absolute minimum = 100 ohms for Vsupply < 25.6 volts

Supply voltage (volts)

Ext

erna

lres

isto

r(o

hms)

OperatingRegion

Page 7: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

Series 1000 and 2000 Transmitters 7

Series 1000 and 2000 functional specifications continued

Digital communicationsAll transmitters

One service port can be used for temporary connectiononly.

Uses RS-485 Modbus signal, baud rate of 38.4 kilobaud,one stop bit, no parity

HART or intrinsically safe HART output (output optioncodes A, B, C, or D)

HART Bell 202 signal is superimposed on the primarymilliamp output, and is available for host system interface.

Frequency 1.2 and 2.2 kHzAmplitude 0.8 V peak-to-peak1200 baudRequires 250 to 600 ohms load resistance

HART/Modbus transmitter (output option Code A)One RS-485 output can be used for direct connection to aHART or Modbus host system. Accepts baud ratesbetween 1200 baud and 38.4 kilobaud.

Fieldbus transmittersTransmitters are registered with the Fieldbus Foundation,and conform to the Foundation fieldbus H1 protocolspecification.

Input frequency from sensorMass flow 20 HzVolume flow 20 HzDensity 20 HzTemperature 1 Hz

Analog Input Function BlocksCycle time host dependentUpdate rate 50 millisecondsRefresh ratehost dependent

PROFIBUS-PA transmittersTransmitters are registered with the PROFIBUSOrganization, and fulfill the requirements of thePROFIBUS-PA Profile for Process Control Devices.

Input frequency from sensorMass flow 20 HzVolume flow 20 HzDensity 20 HzTemperature 1 Hz

Analog Input Function BlocksCycle time host dependentUpdate rate 50 millisecondsRefresh ratehost dependent

Power supplySelf-switching AC/DC input, automatically recognizessupply voltage.

Complies with low voltage directive 73/23/EEC per IEC1010-1 with amendment 2

Installation (Overvoltage) Category II, Pollution Degree 2

The transmitter fieldbus circuit is passive, and draws itspower from the fieldbus segment. Current draw from thefieldbus segment is 11.5 mA.

AC power85 to 265 VAC, 50/60 Hz, 5 watts typical, 8 watts maximum

DC power18 to 100 VDC, 5 watts typical, 8 watts maximumAt startup, transmitter power source must provide aminimum of 1.5 amperes of short-term current at aminimum of 18 volts at the transmitter’s power inputterminalsMinimum 22 VDC with 1000 feet of 18 AWG (300 meters of0.8 mm2) power-supply cable

FuseIEC 127-1.25 fuse, slowblow

Page 8: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

8 Series 1000 and 2000 Transmitters

Series 1000 and 2000 functional specifications continued

Environmental limitsAmbient temperature limits

Operating –40 to 140°F (–40 to 60°C)Storage –40 to 140°F (–40 to 60°C)

Note: Display responsiveness decreases, and display maybecome difficult to read, below –4°F (–20°C). Above 131°F(55°C), some darkening of display might occur.

ATEX and UL approvals require limiting ambienttemperature to below 131 °F (55 °C).

Humidity limits5 to 95% relative humidity, non-condensing at 140°F (60°C)

Vibration limitsMeets IEC 68.2.6, endurance sweep, 5 to 2000 Hz, 50 sweepcycles at 1.0 g.

Environmental effectsEMI effects

Series 1000 and 2000 transmitters conform to NAMURNE21 (August 1998 German and May 1999 English).

Series 1000 and 2000 transmitters meet EMC directive 89/336/EEC per EN 50081-2 (August 1993) and EN 50082-2(March 1995), and EN 61326 Industrial.

Ambient temperature effectOn analog outputs ±0.005% of span per °C

Hazardous area classificationUL and CSAAmbient temperature is limited to below 131 °F (55 °C) for ULcompliance.

TransmitterClass I, Div. 1, Groups C and D. Class II, Div. 1, Groups E,F, and G explosion proof (when installed with approvedconduit seals). Otherwise, Class I, Div. 2, Groups A, B, C,and D.

OutputsProvides nonincendive sensor outputs for use in Class I,Div. 2, Groups A, B, C, and D; or intrinsically safe sensoroutputs for use in Class I, Div. 1, Groups C and D or ClassII, Div. 1, Groups E, F, and G.

ATEXAmbient temperature is limited to below 131 °F (55 °C) forATEX compliance.

HART/Modbus and configurable input/output transmitters(output option codes A, B, or C)

All models are CE 0575 II 2G

Flameproof when installed with approved cable glands:with display EEx d [ib] IIB+H2 T5without display EEx d [ib] IIC T5

Increased safety when installed with approved cableglands:

with display EEx de [ib] IIB+H2 T5without display EEx de [ib] IIC T5

Fieldbus, PROFIBUS-PA, and IS output transmitters (outputoption codes D, E, and G)

All models are CE 0575 II 2(1)G

Flameproof when installed with approved cable glands:with display EEx d [ia/ib] IIB+H2 T5without display EEx d [ia/ib] IIC T5

Increased safety when installed with approved cableglands:

with display EEx de [ia/ib] IIB+H2 T5without display EEx de [ia/ib] IIC T5

������������������������������������������

����������������������������

Page 9: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

Series 1000 and 2000 Transmitters 9

Series 2000 Transmitters with Configurable Inputs and Outputs

Series 2000 transmitters with configurable IOfunctionalityThe Series 2000 transmitter with configurable inputs andoutputs is designed to increase transmitter flexibility andreduce the number of transmitter variations required ininventory. The table below shows the various configurationoptions that can be produced with the configurable IO outputoption.

Channel assignments for Series 2000transmitters with configurable IO (outputoption codes B and C)• When output code B is selected, the transmitter ships with

channels assigned to default values.

• When output code C is selected, the transmitter is customconfigured prior to shipment.

Channel Terminals Configuration options Default variable assignment Power

A 1 and 2 mAO with Bell 202/HART (only) mass flow internal

B 3 and 4 • mAO (default) • mAO — density internal

• FO • FO — mass flow internal or external(1)

• DO • DO — fwd/rev flow internal or external

C 5 and 6 • FO (default)(2) • FO — mass flow internal or external

• DO • DO — flow switch internal or external

• DI • DI — none internal or external

(1)The user must supply power when a channel is set to external power.(2)When configured for two frequency outputs (dual pulse), both outputs are generated from the same signal. The outputs are

electrically isolated but not independent.

Page 10: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

10 Series 1000 and 2000 Transmitters

Series 2000 with FOUNDATION™ fieldbus

Series 2000 fieldbus software functionalitySeries 2000 Foundation fieldbus software is designed topermit remote testing and configuration of the transmitterusing the DeltaV™ Fieldbus Configuration Tool, or otherFoundation fieldbus compliant hosts. The illustration belowshows how the Coriolis sensor signal is channelled throughthe flowmeter to the control room and the Foundation fieldbusconfiguration device.

Transducer blockThe transducer block holds the data from the Coriolis sensor.It includes information about the sensor type, sensorconfiguration, engineering units, calibration, damping, anddiagnostics.

Resource blockThe resource block contains physical device information,including available memory, manufacturer identification, typeof device, and features.

Function blocksThe Analog Input (AI) function block processes themeasurement from the Coriolis sensor and makes it availableto other function blocks. It also allows filtering, alarmhandling, and engineering unit change. Each of the fourSeries 2000 AI blocks can be assigned to one variable fromthe five available: mass flow, volume flow, density,temperature, and drive gain.

Integrator blockThe integrator block provides functionality for the transmittertotalizers. The flow variable (mass or volume) can be selectedand reset.

Diagnostics and serviceSeries 2000 transmitters automatically perform continuousself diagnostics. Using the transducer block, the user canperform on-line testing of the transmitter and sensor.Diagnostics are event driven and do not require polling foraccess.

FOUNDATION fieldbus compliantcommunications stack

Resource blockPhysical device

information

Function blocksAI1, AI2, AI3, AI4

Integrator blockFlow totalizers

Transducer blockCoriolis sensor signal processing

(equations, diagnostics)

Block diagram for Series 2000 transmitters with FOUNDATION fieldbus

Page 11: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

Series 1000 and 2000 Transmitters 11

Series 1000/2000 performance specifications

Sensor Process Variable Accuracy Repeatability

ELITE flow(1)

liquids and slurriesgas(2)

(1)Flow accuracy includes the combined effects of repeatability, linearity, and hysteresis. All specifications for liquids are based onreference conditions of 68 to 77°F (20 to 25°C) and 15 to 30 psig. Specifications for gas are based on air at 60°F (15.5°C) and1000 psig (70 bar), unless otherwise noted.

(2)CMF400 sensors are not rated for gas.

±0.10% of rate(3)

±0.35% of rate(3)

(3)When flow rate is less than [zero stability/(base accuracy percentage/100)], accuracy equals ±[(zero stability/flow rate) x 100]%of rate.

±0.05% of rate(4)

±0.20% of rate(4)

(4)When flow rate is less than [zero stability/(base accuracy percentage/100)], repeatability equals ±[½(zero stability/flow rate) x100]% of rate.

densityCMF010Pothers

±0.002 g/cc (±2.0 kg/m3)±0.0005 g/cc (±0.5 kg/m3)

±0.001 g/cc (±1.0 kg/m3)±0.0002 g/cc (±2.0 kg/m3)

temperature ±1°C ± 0.5% of reading in °C ±0.2°C

T-Series flow (liquid only)(1) ±0.15% of rate(3) ±0.05% of rate(4)

density (liquid) ±0.002 g/cc (±2.0 kg/m3) ±0.001 g/cc (±1.0 kg/m3)

temperature ±1°C ± 0.5% of reading in °C ±0.2°C

F-Series flow(1)

liquids and slurriesgas

±0.20% of rate(3)

±0.70% of rate(3)

±0.10% of rate(4)

±0.35% of rate(4)

density (liquid) ±0.002 g/cc (±2.0 kg/m3) ±0.001 g/cc (±1.0 kg/m3)

temperature ±1°C ± 0.5% of reading in °C ±0.2°C

R-Series flow(1)

liquidgas(5)

(5)R200 sensors are not rated for gas.

±0.5% of rate(3)

±0.75% of rate(3)

±0.25% of rate(4)

±0.50% of rate(4)

density not rated for density

temperature ±1°C ± 0.5% of reading in °C ±0.2°C

Page 12: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

12 Series 1000 and 2000 Transmitters

Model 1700 and 2700 physical specifications

Field-mount housingNEMA 4X (IP67) epoxy painted cast aluminum housing.

Terminal compartment contains output terminals, powerterminals and service-port terminals. The output terminalsare physically separated from the power- and service-portterminals.

The electronics compartment contains all electronicsand the standard display.

The sensor compartment contains the wiring terminalsfor connection to the core processor on the sensor.

Screw-terminal on housing for chassis ground.

Cable gland entrances are either 1/2”-14 NPT or M20 x 1.5female conduit ports.

MountingModel 1700 and 2700 field-mount transmitters areavailable integrally mounted to Micro Motion T-Series,R-Series, and F-Series sensors. They may also beremotely mounted to any Micro Motion sensor. See thesensor Product Data Sheet for details and restrictions.

Remote-mount transmitters include a mounting bracket,and require standard 4-wire twisted, shielded signalcable, up to 1000 feet (300 meters) in length, betweenthe sensor and the transmitter. Hardware for installingthe transmitter on the mounting bracket is included.

Remote-mount transmitters with a 9-wire signal cablebetween the sensor and the transmitter have amaximum cable length of 60 feet (20 meters). Hardwarefor installing the transmitter on the supplied mountingbracket is supplied.

The transmitter can be rotated on the sensor or themounting bracket, 360 degrees, in 90-degreeincrements.

Interface/displaySegmented 2-line display with LCD screen with opticalcontrols and flowmeter-status LED is standard. Suitable forhazardous area installation.

To facilitate various mounting orientations, the display canrotate on transmitter, 360 degrees, in 90-degreeincrements.

LCD line 1 lists the process variable, line 2 listsengineering unit of measure. Non-glare tempered glasslens.

Display controls feature optical switches that areoperated through the glass with a red LED for visualfeedback to confirm when a "button" is pressed.

Display functionsOperational

View process variables; start, stop, and reset totalizers;view and acknowledge alarms.

Off-line (specific functions where applicable, depending onoption board)

Zero flowmeter, simulate outputs, change measurementunits, configure outputs, and set RS-485 communicationsoptions.

Status lightThree-color LED status light on display panel indicatesflowmeter condition at a glance. Green, yellow, or red,either continuously on or blinking, status light immediatelyindicates flowmeter status.

Weight4-wire remote mount transmitter 8 lb (3.6 kg)9-wire remote transmitter 13 lb (5.9 kg)

For weight of integrally mounted transmitter and sensor,refer to sensor specifications.

Page 13: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

Series 1000 and 2000 Transmitters 13

Model 1700 and 2700 physical specifications continued

Dimensions in inches(mm)

2 7/16(62)

ø4 7/8(124)

2 3/8(60)

(to 1/2 NPTor M20)

4 3/4(120)

4 13/16(122)

4 1/2(114)

6 7/8(174)

3 15/16(99)

2 11/16(69)

1 7/8(48)

1 3/4(45)

8 7/16(214)

wall mount

9 5/8(244)

to centerline of 2” pipepipe mount

4 5/16(110)

2 1/4(58)

1(26)

3x 1/2-14 NPTor M20 x 1.5

4-wire remote mountSeries 1000/2000transmitter

6 7/8(174)

3 15/16(99)

3x 1/2-14 NPTor M20 x 1.5

2 11/16(69)

9 5/8(244)

to centerline of 2” pipepipe mount

8 7/16(214)

wall mount

4 5/16(110)

4 3/8(111)

2 9/16(65)

13/16(21)

3 1/16(78)

7/8(22)

8 3/16(207)

3 11/16(93)2 13/16

(71)

4x ø3/8(10)

2 13/16(71)

9-wire remote Series1000/2000 transmitter

For dimensions of integrally mounted transmitter and sensor, refer to sensor specifications.

Page 14: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

14 Series 1000 and 2000 Transmitters

Model 1700 and 2700 physical specifications continued

Dimensions in inches(mm)

9-wire remotely mountedcore processor

4 5/16(110)

wall mount

4(102)

pole mount

ø3 5/8(92)

2X 2 1/4(58)

2 1/8(54)

4 1/16(104)

2 9/16(65)

4 1/2(114)

3 1/4(83)

7/8(22)

2X 1/2”–14 NPTor

M20 X 1.5

7/8(22)

2 13/16(71)

4X ø3/8(10)

4 1/2(114)

2 13/16(71)

Page 15: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

Series 1000 and 2000 Transmitters 15

Series 1000 model number matrixModel Product Description

1700 Micro Motion Coriolis MVD™ single variable flow transmitter

Code Mounting

R 4-wire remote mount transmitter

I Integral mount transmitter

B 4-wire remote mount transmitter with 9-wire remote core processor

C 9-wire remote transmitter (requires J-box sensor)

Code Power

1 18 to 30 VDC and 85 to 265 VAC; self switching

Code Display

1 Dual line display for process variables and totalizer reset (standard)

3 No display

Code Output

A One mA; one frequency; RS485

D Intrinsically safe outputs: one mA, one frequency

Code Conduit Connections

B 1/2-inch NPT — no gland

C 1/2-inch NPT with brass nickel cable gland

D 1/2-inch NPT with stainless steel cable gland

E M20 — no gland

F M20 with brass nickel cable gland

G M20 with stainless steel cable gland

Code Approvals

M Micro Motion Standard (no approval)

U UL

C CSA (Canada only)

A CSA (US and Canada)

Z ATEX — Equipment Category II 2 G (Zone 1, gas — increased safety)

F ATEX — Equipment Category II 2 G (Zone 1, gas — flameproof)

Code Language

A Danish/English

D Dutch/English

E English/English

F French/French

G German/German

H Finnish/English

I Italian/English

J Japanese/English

M Chinese/English

N Norwegian/English

O Polish/English

P Portuguese/English

S Spanish/Spanish

W Swedish/English

Code Software Options

ZZ Reserved for future use

Code Factory OptionsZ Standard product

X CEQ hardware

Typical Model Number: 1700 I 1 1 A D M E ZZ Z

Page 16: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

16 Series 1000 and 2000 Transmitters

Series 2000 model number matrixModel Product Description2700 Micro Motion Coriolis MVD™ multivariable flow and density transmitterCode MountingR 4-wire remote mount transmitterI Integral mount transmitterB 4-wire remote mount transmitter with 9-wire remote core processorC 9-wire remote transmitter (requires J-box sensor)Code Power1 18 to 30 VDC and 85 to 265 VAC; self switchingCode Display1 Dual line display for process variables and totalizer reset (standard)3 No displayCode OutputA One mA; one frequency; RS485B One mA; two configurable IO channels — default configurationC One mA; two configurable IO channels — custom configurationD Intrinsically safe outputs: two mA, one frequencyE FOUNDATION fieldbus H1G PROFIBUS-PACode Conduit ConnectionsB 1/2-inch NPT — no glandC 1/2-inch NPT with brass nickel cable glandD 1/2-inch NPT with stainless steel cable glandE M20 — no glandF M20 with brass nickel cable glandG M20 with stainless steel cable glandCode ApprovalsM Micro Motion Standard (no approval)U ULC CSA (Canada only)A CSA (US and Canada)Z ATEX — Equipment Category 2 (Zone 1 — increased safety)F ATEX — Equipment Category 2 (Zone 1 — flameproof)Code Language (quick reference installation guide/instruction manual)A Danish/EnglishD Dutch/EnglishE English/EnglishF French/FrenchG German/GermanH Finnish/EnglishI Italian/EnglishJ Japanese/EnglishM Chinese/EnglishN Norwegian/EnglishO Polish/EnglishP Portuguese/EnglishS Spanish/SpanishW Swedish/EnglishCode Software Options 1Z Flow & density variables (standard)A Petroleum measurement softwareX CEQ software option 1Code Software Options 2Z No software options 2

W(1)

(1)Available with output option codes B and C only.

Weights and measures custody transfer

A Standard fieldbus function blocksX CEQ software option 2Code Factory OptionsZ Standard productX CEQ hardwareTypical Model Number: 2700 I 1 1 A D M E Z Z Z

Page 17: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

Series 1000 and 2000 Transmitters 17

Page 18: Micro Motion Series 1000 and 2000 Transmitters - hkfdi.com · Micro Motion Series 1000 and 2000 Transmitters ... . 2 Series 1000 and 2000 Transmitters Micro Motion ... The Model …

Due to Micro Motion’s commitment to continuous improvement of our products, all specifications are subject to change without notice. MicroMotion is a registered trademark and MVD and EXPERT2 are trademarks of Micro Motion, Inc., Boulder, Colorado. PlantWeb is a registeredtrademark of Fisher-Rosemount, Clayton, Missouri. HART is a registered trademark of the HART Communication Foundation, Austin, Texas.FOUNDATION is a trademark of the Fieldbus Foundation, Austin, Texas.

© 2002, Micro Motion, Inc. All rights reserved.PS-00400 (6/02)

Micro Motion Inc. USAWorldwide Headquarters7070 Winchester CircleBoulder, Colorado 80301Tel (303) 530-8400

(800) 522-6277Fax (303) 530-8459

Micro Motion EuropeEmerson Process ManagementWiltonstraat 303905 KW VeenendaalThe NetherlandsTel +31 (0) 318 549 549Fax +31 (0) 318 549 559

Micro Motion AsiaEmerson Process Management1 Pandan CrescentSingapore 128461Republic of SingaporeTel (65) 777-8211Fax (65) 770-8003

For the latest Micro Motion product specifications, view thePRODUCTS section of our Web site at www.micromotion.com

Micro Motion JapanEmerson Process ManagementShinagawa NF Bldg. 5F1-2-5, Higashi ShinagawaShinagawa-kuTokyo 140-0002 JapanTel (81) 3 5769-6803Fax (81) 3 5769-6843