micro800 programmable controllersdocshare01.docshare.tips/files/25786/257868482.pdfrockwell...
TRANSCRIPT
-
Release Notes
Micro800 Programmable ControllersCatalog Numbers Bulletin 2080
About This PublicationThese release notes supplement the existing documentation supplied with your product.
Read this document before using Micro800™ controllers.
Firmware Revision History
Topic Page
About This Publication 1
Firmware Revision History 1
Features 4
Anomalies 10
Additional Resources 21
Firmware Revision History for Micro810™ Controllers
Revision Description
1.011 First revision release
1.012 Minor revision release
1.013 Minor revision release
2.011 Major revision release
2.012 Minor revision release
-
2 Micro800 Programmable Controllers
Firmware Backward CompatibilityMicro800 firmware is always backward compatible with previous revisions. It is not necessary to flash upgrade a controller to a previous revision to match an
Firmware Revision History for Micro820™ Controllers
Revision Description
6.011 First major revision release
Firmware Revision History for Micro830™ Controllers
Revision Description
1.011 First revision release
1.012 Minor revision release
1.013 Minor revision release
2.011 Major revision release
4.011 Major revision release
4.012 Minor revision release
4.013 Minor revision release
6.011 Major revision release
Firmware Revision History for Micro850™ Controllers
Revision Description
2.011 First revision release
4.011 Major revision release
4.012 Minor revision release
4.013 Minor revision release
6.011 Major revision release
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
Micro800 Programmable Controllers 3
earlier project revision. For example, a Connected Components Workbench™ project configured with a controller revision of 2.x can be downloaded into a controller with firmware revision 2.x or higher. It is, however, recommended that you always upgrade to the latest software, as older software revisions cannot recognize newer firmware revision controllers when discovering, uploading, and downloading.
Availability of Enhancements and Anomaly FixesEnhancements are available in the controller only if the controller is at the required firmware revision or higher, and the Connected Components Workbench project contains a controller configured with the required firmware revision or higher. If the project contains a controller revision that is lower than the required revision for an enhancement, then the project is still valid but the enhancement will not be available until the project is upgraded to the minimum supported revision.
Fixes for firmware anomalies will be available as long as the controller firmware revision is at the minimum revision or higher. The configured controller revision in the project does not matter.
The following tables provide a list of enhancements, known anomalies, and corrected anomalies for the Micro800 firmware revisions.
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
4 Micro800 Programmable Controllers
Features
Features for Micro820 Controllers
Feature(1) Description FirmwareRevision
2080-DNET20 DeviceNet scanner plug-in support(2)
The DeviceNet plug-in serves as scanner and client for explicit messaging to remote devices. The module can scan devices such as CompactBlock™ LDX, PowerFlex® drives, E1Plus overloads, and stacklights.User-defined function blocks (UDFB)(3) are required to configure the plug-in and scan the network.
6.011
2080-MOT-HSC High-speed Counter plug-in support(2)
The high-speed counter plug-in provides enhanced high speed counter capabilities to the Micro800 controller. It supports up to 250 KHz differential line driver for improved noise immunity.User-defined function blocks (UDFB)(3) are required to configure and use the high-speed counter plug-in.
6.011
2080-REMLCD Remote LCD module support
The Remote LCD module serves as a simple operator interface supporting ASCII text. It is an accessory to the Micro820 controller. It allows easier configuration of such controller settings as IP address.
6.011
microSD™ card slot Industrial grade(4) microSD cards are supported through an embedded microSD card slot on Micro820 controllers. The microSD card enables project backup and restore, as well as datalogging and recipe, on Micro820 controllers.
6.011
Datalogging and Recipe
Datalogging and recipe is supported through the DLG and RCP function blocks, respectively.The datalogging feature allows the capture of global and local variables with timestamp from the Micro800 controller into the microSD card. The recipe feature allows storage and loading of a list of data to and/or from a recipe data file on the microSD card.
6.011
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
Micro800 Programmable Controllers 5
Backup and restore through the microSD card
Project backup and restore are supported on Micro820 controllers through the microSD card.
6.011
Powerup settings through ConfigMeFirst.txt file
Controller settings on powerup can be set through the optional ConfigMeFirst.txt file in the microSD card. This configuration file contains such parameters as IP address, subnet mask, gateway, and directories for backup, restore, datalog and recipe.For detailed information about ConfigMeFirst.txt file and powerup settings on the Micro820 controller, see the Micro820 Programmable Controllers User Manual, publication 2080-UM005.
6.011
Error codes specific to Micro820
The following error codes have been added for the Micro820 controllers. These codes indicate that power down information in persistent memory may not be written properly due to a noisy environment or an internal hardware failure.• OxF030• OxF031• OxF032• OxF033If the system variable __SYSVA_USER_DATA_LOST has been be set, the controller will be able to recover the user program but the user data will be cleared. If not, the Micro800 controller program will be cleared.
6.011
(1) For more information, see the following User Manuals:- Micro820 Programmable Controllers User Manual, publication 2080-UM005- Micro800 Plug-ins User Manual, publication 2080-UM004.
(2) Micro820 controllers support all Micro800 plug-in modules, except for the 2080-MEMBAK-RTC plug-in. This plug-in module is newly introduced with firmware revision 6.011 and is supported on most Micro800 controllers.
(3) UDFBs and sample Micro800 programs for Connected Components Workbench can be downloaded from the Sample Code Library: http://www.rockwellautomation.com/go/scmicro800.
(4) The slot supports Class 6 and 10 SDSC and SDHC microSD cards, with FAT32/16 formats, 32 GB maximum size. Micro820 controllers do not support Class 4 microSD cards.
Features for Micro820 Controllers
Feature(1) Description FirmwareRevision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
http://literature.rockwellautomation.com/idc/groups/literature/documents/um/2080-um005_-en-e.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/um/2080-um004_-en-e.pdfhttp://www.rockwellautomation.com/go/scmicro800http://literature.rockwellautomation.com/idc/groups/literature/documents/um/2080-um005_-en-e.pdf
-
6 Micro800 Programmable Controllers
Enhancements for Micro830 and Micro850 Controllers
Enhancement Description FirmwareRevision
2080-DNET20 DeviceNet scanner plug-in support
The DeviceNet plug-in serves as scanner and client for explicit messaging to remote devices. The module can scan devices such as CompactBlock™ LDX, PowerFlex® drives, E1Plus overloads, and stacklights.User-defined function blocks (UDFB)(1) are required to configure the plug-in and scan the network.
6.011
2080-MOT-HSC high-speed counter plug-in support
The high-speed counter plug-in provides enhanced high speed counter capabilities to the Micro800 controller. It supports up to 250 KHz differential line driver for improved noise immunity.User-defined function blocks (UDFB)(2) are required to configure and use the high-speed counter plug-in
6.011
RS-485 serial port for ASCII communication
The RS-485 serial port supports ASCII communications on Micro800 controllers from firmware revision 6.011.
6.011
PWM function PWM function is added via PTO motion parameter 1005. The duty cycle of the PTO can now be set using MC_WriteParameter. The value ranges from 0...100, indicating 0…100%.
6.011
PTO motion parameters 1006 and 1007
PTO motion parameters 1006 and 1007 are added to read Pulses per Revolution and Unit per Revolution configuration in user program.
6.011
Additional error code: OxF019
This error code pertains to unexpected software error due to memory or other controller resource issue.
6.011
Additional error codes: 0xF017 and 0xF018
The following error codes have been added:• 0xF017 for unexpected hardware interrupt• 0xF018 for SPI communication failureIf the system variable __SYSVA_USER_DATA_LOST has been set, the controller will be able to recover the user program but the user data will be cleared. If not, the Micro800 controller program will be cleared.
6.011
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
Micro800 Programmable Controllers 7
CIP Generic and CIP Symbolic client messaging
CIP Generic and CIP Symbolic client messaging support is made available through the addition of two function blocks to the instruction set: MSG_CIPGENERIC and MSG_CIPSYMBOLIC. CIP Messaging is available on all serial (including embedded, plug-in) and Ethernet communication ports.
4.011
Modbus TCP client function on Micro850 controllers
On Micro850 controllers, support for Modbus TCP client function is available through the addition of the MSG_MODBUS2 function block.This feature is not available for Micro830 controllers.
4.011
Memory Copy function
The addition of the COP function block enables support for memory copy across data types. This function block is typically used in conjunction with the client messaging instructions. Source and destination must be a complete array with an optional offset.
4.011
Digital I/O plug-in module support
This firmware revision supports the configuration and upload of digital I/O plug-ins through Connected Components Workbench. I/O global variables are automatically generated for the inputs and outputs.Previous method of using RA_2080_IQ4x and RA_2080_O4x user-defined function blocks to configure the digital I/O modules (supported on earlier firmware revision 2), can still work with firmware revision 4, but will not work in conjunction with the digital I/O configuration feature in firmware revision 4. This means that on firmware revision 4, users are only allowed to either use the previous method of configuration (through user-defined function blocks) or the new method (through Connected Components Workbench configuration interface), but not both at the same time.An error will be reported by the function block should conflict occur.
4.011
1 GAIN renamed to MOV
1 GAIN instruction for setting one variable equal to another variable of the same data type is renamed to MOV for easier reference. 1 GAIN is no longer available from revision 4 projects onwards.
4.011
Enhancements for Micro830 and Micro850 Controllers
Enhancement Description FirmwareRevision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
8 Micro800 Programmable Controllers
Motion control Firmware revision 2 supports motion control configuration on certain Micro830 and Micro850 controllers.This feature is supported through embedded Pulse Train Outputs (PTO) on Micro830 and Micro850 controllers with catalog numbers that end in QVB and QBB.
2.011
Expansion I/O support
Micro850 controllers with firmware revision 2 can support up to four expansion I/O configuration.
2.011
Communication connections
The following communication protocols are supported with firmware revision 2:• Modbus/TCP Server (Micro850 controllers only
through Ethernet channel)• CIP Serial Server (RS-232 only)• EtherNet/IP Server (Micro850 controllers)These communication protocols are supported through the RS-232 and RS-485 communication channels and the RJ-45 Ethernet port.
2.011
Controller security Controller password can be enforced to restrict access to the programming software connection to the controller.
2.011
Digital output variables
All digital output variables driven by the IO scan gets cleared on powerup or during transition to RUN mode.
2.011
0xF000 and 0xF002 Fault Handling on Powerup
Controller attempts to recover user program and clear user variables upon powerup.
2.011
(1) UDFBs and sample Micro800 programs for Connected Components Workbench can be downloaded from the Sample Code Library: http://www.rockwellautomation.com/go/scmicro800.
Enhancements for Micro830 and Micro850 Controllers
Enhancement Description FirmwareRevision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
http://www.rockwellautomation.com/go/scmicro800
-
Micro800 Programmable Controllers 9
Enhancement for Micro810 Controllers
Enhancement(1)
(1) See Micro810 User Manual, publication 2080-UM001 for more information.
Description FirmwareRevision
Controller security Controller password can be enforced to restrict access to the programming software connection to the controller.
2
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
http://literature.rockwellautomation.com/idc/groups/literature/documents/um/2080-um001_-en-e.pdf
-
10 Micro800 Programmable Controllers
Anomalies
Known Anomalies for Micro820 Controllers
Anomaly Description Affected Firmware Revisions
Corrected Firmware Revision
SD LED indicator may remain off on card insertion
It may be observed, in very rare instances, that the SD LED indicator may remain off when a good microSD card is inserted, instead of lighting On. Users are advised to eject and re-insert the card if this issue is ever encountered.
APBC00017196
6.011
SD LED continues to blink after card is ejected
SD LED indicator continues to blink for a couple of seconds after card is ejected while datalog, recipe, backup, and restore activities are in progress. This continuous blinking is due to SD card read/write retries.
APBC00017743
6.011
Hard fault on controller when card is removed during backup and restore
The controller goes into a hard fault when the microSD card is removed while backup and restore is in progress. (The hard fault is indicated by a solid red Fault LED indication.)Users are advised to power cycle the controller and clear the fault to recover the controller.
APBC00017633
6.011
Communication breaks if project backup or restore fails
Ethernet and/or serial ports communication may not work when project back up or restore fails. Users are advised to power cycle the controller to recover the connection.
APBC00018270
6.011
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
Micro800 Programmable Controllers 11
Error message “Memory card is not present” takes approximately 30 seconds to be displayed after card is ejected
"Memory Card is not present" message in Connected Components Workbench takes some time (approximately 30 seconds) to display after card has been ejected. The delay is only observed when ongoing upload or search of datalog or recipe files activities is interrupted by card ejection. The delay is attributed to card read/write retries.
APBC00017502
6.011
REMLCD backlight briefly turns on before startup message
When backlight is configured using LCD_BKLT_REM for the REMLCD module, the backlight briefly turns on in blue color before it displays the startup message.
APBC00017400
6.011
Long Real data values used on DLG that are either too big or too small affect scan time performance
Scan time is significantly longer when the program includes execution of one DLG function block that is configured with multiple Long Real data values which are either extremely huge (that is, >> ±1.0E+50), or extremely small (that is, -1.0E-50 value > 0).
APBC00018658
6.011
Incorrect conversion of REAL/LREAL variables using Any_To_String
Any_To_String instruction converts REAL/LREAL variables erroneously. The conversion result has no proper data truncation and is incorrect for certain patterns, such as 0.0123456.
APBC00018944
6.011
Analog input calibration offset must be positive
Analog input calibration only accepts positive values (or zero) when set from Connected Components Workbench or in the 2080-REMLCD. Negative values should also be supported.
APBC00019113
6.011
Known Anomalies for Micro820 Controllers
Anomaly Description Affected Firmware Revisions
Corrected Firmware Revision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
12 Micro800 Programmable Controllers
Known and Corrected Anomalies for Micro830 and Micro850 Controllers
Anomaly Description Affected Firmware Revisions
Corrected Firmware Revision
Incorrect conversion of REAL/LREAL variables using Any_To_String
Any_To_String instruction converts REAL/LREAL variables erroneously. The conversion result has no proper data truncation and is incorrect for certain patterns, such as 0.0123456.
APBC00018944
6.011
Controller faults when restoring an older project from memory module to a controller containing a project created with Connected Components Workbench revision 6
Project restore (from a memory module that contains a project created by a pre-revision 6 Connected Components Workbench) will fail on a Micro810/Micro830/Micro850 controller with firmware revision 1 or 2 that has a project created by Connected Components Workbench revision 6 or later. A fault will be reported by the controller. Users are advised to clear the fault and power cycle the controller and then repeat the restore action.
APBC00017367
2.0xx1.0xx
4.0xx
Embedded serial port may shut down on powerup
It has been observed that the embedded serial port shuts down if the controller encounters power supply disruption at a certain time after powerup.
APBC000016906
4.0124.0112.011
4.013
CIP Serial communication on embedded serial port may be temporarily disrupted
CIP Serial server and client messaging via Micro830 and Micro850 controller embedded serial port is disrupted for 15...16 seconds before resuming normal operation.This may happen when CIP Serial communication is operating continuously for more than 17 days.
APBC000015297
4.0112.011
4.012
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
Micro800 Programmable Controllers 13
CIP symbolic pass-through not supported
CIP Symbolic pass-through fails with Micro800 as an intermediate bridge using unconnected messages. For example, with Micro850 controller, it is not possible to send an unconnected CIP symbolic message from device A to B with the Micro850 controller as a bridge in the middle. Connected messaging is supported.
APBC000014849
4.011 6.011
DN and Error bits do not go false on certain ASCII instructions
For some ASCII communications instructions, the DN and error output status bits do not go false when the instruction enable IN goes false. Done and Error status should immediately go false if IN is false. ACL status will never go false once true. ARD, ARL, AWA, AWT will go false only if IN goes false and then true.
APBC00015308
4.0112.0xx1.0xx
6.011
CIP Symbolic and CIP Generic messages not supported on Logix serial port
MSG_CIPSYMBOLIC and MSG_CIPGENERIC are not supported on connected client messaging via serial communication when connected to a CompactLogix™ or ControlLogix® embedded serial port.A Micro800 controller as server and a Logix controller as client is supported.
APBC000014851
4.011 6.011
CIP messaging communication may be affected by cable break
For CIP messaging client function, if there is one or more devices with a cable break, the messaging client connection with other devices may become slower, with possible timeouts.This may happen if multiple messages are pending due to the cable break.
APBC000015030
4.011 –
Known and Corrected Anomalies for Micro830 and Micro850 Controllers
Anomaly Description Affected Firmware Revisions
Corrected Firmware Revision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
14 Micro800 Programmable Controllers
Possible data packet loss with Ethernet communication(1)
A heavily loaded Ethernet communication, with the client sending multiple message requests simultaneously, may result in data packet loss on a Micro850 controller. Connection timeouts may consequently occur. Other connections with other devices are not affected. This issue can happen to both client and server function. Client should only have one pending message to avoid this issue.
APBC000015191
4.011 6.011
CIP Serial client messaging to a PC running RSLinx software is not supported
CIP Serial client messaging (CIP Symbolic or CIP Generic) to a PC running RSLinx software is not supported. The controller may stop all communication functions with other communication ports when such unsupported messages are sent continuously.
APBC000015243
4.011 4.012
Micro800 serial ports do not support control lines
ASCII: Micro800 serial ports do not support control lines RTS and CTS, even though configuration is available for ASCII and Modbus RTU in the software.
APBC000014284
4.0112.0111.0xx
6.011
Axis Decelerating flag turns on for non-zero jerk moves while axis is accelerating
For a move from ConstantVelocity or Standstill state, if the jerk is not equal to 0, the Deceleration status is set for one Motion Engine interval before the axis starts to accelerate. The Deceleration and Acceleration flag do not turn on at the same time.This anomaly only occurs when program scan time is less than the Motion Engine interval.
APBC00011729
4.0112.011
6.011
ASCII connection only works with RS-232 interface
The ASCII protocol for Micro800 controllers only supports RS-232 media. The RS-485 interface is not supported.
APBC00011336
4.0112.0111.0xx
6.011
Known and Corrected Anomalies for Micro830 and Micro850 Controllers
Anomaly Description Affected Firmware Revisions
Corrected Firmware Revision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
Micro800 Programmable Controllers 15
ASCII communication buffer is not cleared
A new program download should automatically clear the buffer for ASCII serial communication messages but the buffer does not get cleared.
APBC00009305
2.0111.0xx
4.011
Incomplete home URL string in EDS file
The EDS file includes an incomplete home URL text string.
APBC000009490
2.0111.0xx
4.011
Password mismatch status is not correct
Password mismatch status is not correct after power cycle if Load on Error is set.
APBC00011949
2.011 4.011
ErrorMode parameter does not handle errors
ErrorMode input of IPIDCONTROLLER instruction does not handle errors as expected and does not recognize any input values.
APBC00006755
1.011 2.011
ControlFlash firmware update results in a red flashing fault
Even when a ControlFlash update is successful, the Micro800 controller shows a fault code of 0xF004 (Memory Module transfer error), and the status indicator flashes red. This occurs when the firmware update is performed on a controller with a physical Memory module inserted, and with a user program in that memory module which has the “Load Always” or “Load Always on Memory Error”set.Clear the fault and use the controller normally.
APBC00005287
1.011 2.011
Modbus configured target address returns illegal address error
A Modbus client read to a valid Modbus boundary address of 65535 in the controller results to an illegal address error in the client.
APBC00007660
1.011 2.011
Known and Corrected Anomalies for Micro830 and Micro850 Controllers
Anomaly Description Affected Firmware Revisions
Corrected Firmware Revision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
16 Micro800 Programmable Controllers
Fault translation error
Error code is not handled properly as soft fault EP_WDT_EXPIRED (0xD011) in a user interrupt POU is translated as hard fault EP_WDT_HARDFAULT (0xF002).
APBC00007864
1.011 2.011
STI configuration reloaded when UID and UIE are used
STI is erroneously disabled and then reloaded whenever UID and UIE are used so STI program may not execute at the configured periodic rate.Both UID and UIE functions are normally used to mask and unmask user interrupts in the user program to prevent conflict with simultaneous references to the same variables.
APBC00007923
1.011 2.011
CRC errors and timeouts in Modbus packet communications
When using the MSG_MODBUS instruction to communicate with any other Modbus Slave devices that require turnaround delay, setting TriggerType in LocalCfg to 1 may cause increased failure rates in modbus packets received/transmitted. Introduce a turnaround delay, such as 5 ms, at a user program level.
APBC00005317 / APBC00005339
1.011 1.013
Known and Corrected Anomalies for Micro830 and Micro850 Controllers
Anomaly Description Affected Firmware Revisions
Corrected Firmware Revision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
Micro800 Programmable Controllers 17
High Speed Counter (HSC) instruction configuration causes controller Hard Reset
The following conditions may cause a controller Hard Reset.
• Value of HSCAppData underflow setting (UFSetting) and low preset setting (LPSetting) more than or equal to 0.
• Value of HSCAppData overflow setting (OFSetting) and high preset setting (HPSetting) less than or equal to 0.
• Setting the HSC user interrupt parameter for underflow (Mask for IN) to True, when counting up with HSC Mode 0 or 1.
APBC00005342
1.011 1.013
High Speed Counter (HSC) user interrupt does not work for 10/16-point controllers
HSC ID HSC1 does not work for 2080-LC30-10QVB/QWB, and 2080-LC30-16QVB/QWB.
APBC00005198
1.011 1.013
Universal Plug-In Module (UPM) interrupt configuration causes controller Hard Reset
Adding UPM interrupts in the Interrupt Properties page may cause a controller Hard Reset
APBC00005332 / APBC00005357
1.012 1.013
Known and Corrected Anomalies for Micro830 and Micro850 Controllers
Anomaly Description Affected Firmware Revisions
Corrected Firmware Revision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
18 Micro800 Programmable Controllers
Generic plug-in module’s controller status byte may report inaccurate information
The Controller Status Byte may inaccurately report an Operation Error during normal RUN mode or on “Power Failure Triggered”.Internally developed UPM modules do not use the Controller Status Byte. Such modules are not affected by this anomaly. Third party UPM modules that are based on the Generic Plug-in module specifications and that use the result of the Controller Status Byte to perform certain actions, however, may be affected.
APBC00007064
1.0121.011
1.013
The controller may report a fault (error code 0xD011) when continuously powered on for more than 49.71 days
Under certain conditions, when the controller is continuously powered on for more than 49.71 days, the controller may report a recoverable fault (error code 0xD011), and the outputs will be disabled. Certain time based instructions may not operate correctly within the 3 ms window immediately after 49.71 days.On Micro810 controllers, the power LED goes off. The LCD display changes from RUN mode to FAULT mode. On Micro830 controllers, the fault LED flashes red.
APBC00006019 / KnowledgeBase ID 450489
1.011 1.012
(1) This anomaly does not apply to Micro830 controllers.
Known and Corrected Anomalies for Micro810 Controllers
Anomaly Description Affected Firmware Revision
Corrected Firmware Revision
Incorrect conversion of REAL/LREAL variables using Any_To_String
Any_To_String instruction converts REAL/LREAL variables erroneously. The conversion result has no proper data truncation and is incorrect for certain patterns, such as 0.0123456.
APBC00018944
6.011
Known and Corrected Anomalies for Micro830 and Micro850 Controllers
Anomaly Description Affected Firmware Revisions
Corrected Firmware Revision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
Micro800 Programmable Controllers 19
Controller faults when restoring an older project from memory module to a controller containing a project created with Connected Components Workbench revision 6
Project restore (from a memory module that contains a project created by a pre-revision 6 Connected Components Workbench) will fail on a Micro810/Micro830/Micro850 controller with firmware revision 1 or 2 that has a project created by Connected Components Workbench revision 6 or later. A fault will be reported by the controller. Users are advised to clear the fault and power cycle the controller and then repeat the restore action.
APBC00017367
2.0xx1.0xx
4.0xx
Analog input calibration offset must be positive
Analog input calibration only accepts positive values (or zero) when set from Connected Components Workbench or in the 2080-LCD. Negative values should also be supported.
APBC00019113
2.0xx1.0xx
No I/O force indication
There is no I/O force indication on the LCD display I/O status screen.
2.0111.0xx
2.012
Password mismatch status is not correct
Password mismatch status is not correct after power cycle if Load on Error is set.
APBC00011949
2.011 2.012
Wrong language on localized LCD options
Certain menu strings still display in English on localized (French, Italian, Spanish) LCD menu display.
APBC00013978
2.0111.0xx
2.012
Incomplete home URL string in EDS file
The EDS file includes incomplete home URL string.
APBC00009490
2.0111.0xx
2.012
Known and Corrected Anomalies for Micro810 Controllers
Anomaly Description Affected Firmware Revision
Corrected Firmware Revision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
20 Micro800 Programmable Controllers
LCD instruction causes controller fault
When the LCD instruction switches between user defined and default I/O status screens (for example, Enable input parameter goes from FALSE to TRUE or from TRUE to FALSE), there is a possibility that the controller faults and is no longer in run mode.
APBC00013978
2.0111.0xx
2.012
User application cannot back up and restore
A project configured with a revision 1.x controller cannot be backed up or restored successfully using the LCD module with a firmware revision 2.011 controller.
APBC00014192
2.011 2.012
ErrorMode parameter does not handle errors
ErrorMode input of IPIDCONTROLLER instruction does not handle errors as expected and does not recognize any input values.
APBC00006755
1.011 2.011
RHC instruction in Micro810 controllers is not accurate
The RHC function block uses a time base of 49.86 µs and returns counter times 5, instead of a 40 µs timer with a return counter times 4.
APBC00005186
1.012 1.013
The controller may report a fault (error code 0xD011) when continuously powered on for more than 49.71 days
Under certain conditions, when the controller is continuously powered on for more than 49.71 days, the controller may report a recoverable fault (error code 0xD011), and the outputs are disabled. Certain time based instructions may not operate correctly within the 3 ms window immediately following 49.71 days.On Micro810 controllers, the power LED goes off. The LCD display changes from RUN mode to FAULT mode. On Micro830 controllers, the fault LED flashes red.
APBC00006019 / KnowledgeBase ID 450489
1.012 1.012
Known and Corrected Anomalies for Micro810 Controllers
Anomaly Description Affected Firmware Revision
Corrected Firmware Revision
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
Micro800 Programmable Controllers 21
Firmware UpdateInstructions on how to flash update your controller with the latest firmware is provided in the User Manual for your Micro800 controller. See Additional Resources for the link to your online user manual.
To get the latest firmware for your Controller, go to the following links:
• Firmware for Micro810 • Firmware for Micro820• Firmware for Micro830 • Firmware for Micro850
Look for the Resources tab, then click Firmware to download the latest firmware.
Additional ResourcesThese documents contain additional information concerning related Rockwell Automation products.
Resource Description
Micro810 Programmable Controllers User Manual, publication 2080-UM001 xxxxx
Detailed description of features and how to install and use the Micro810, Micro820, Micro830, and Micro850 programmable controllers.
Micro820 Programmable Controllers User Manual, publication 2080-UM005
Micro830 and Micro850 Programmable Controllers User Manual, publication 2080-UM002 xxxxxxx
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.rockwellautomation.com/products/certification/
Provides declarations of conformity, certificates, and other certification details.
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
http://literature.rockwellautomation.com/idc/groups/literature/documents/um/2080-um001_-en-e.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/um/2080-um002_-en-e.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://www.rockwellautomation.com/products/certification/http://ab.rockwellautomation.com/Programmable-Controllers/Micro810http://ab.rockwellautomation.com/Programmable-Controllers/Micro830http://ab.rockwellautomation.com/Programmable-Controllers/Micro850http://literature.rockwellautomation.com/idc/groups/literature/documents/um/2080-um005_-en-e.pdfhttp://ab.rockwellautomation.com/Programmable-Controllers/Micro820
-
22 Micro800 Programmable Controllers
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
http://www.rockwellautomation.com/literature/
-
Micro800 Programmable Controllers 23
Notes:
Rockwell Automation Publication 2080-RN001I-EN-P - December 2013
-
Rockwell Automation Support
Publication 2080-RN001I-EN-P- December 2013
Allen-Bradley, Rockwell Automation, Micro800, Micro810, Micro820, Micro830, Micro850, CompactLogix, ControlLogix, CompactBlock, PowerFlex, Connected Components Workbench, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.
Installation AssistanceIf you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
New Product Satisfaction ReturnRockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
United States or Canada 1.440.646.3434
Outside United States or Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.
United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Supersedes Publication 2080-RN001H-EN-P - October 2013 Copyright © 2013 Rockwell Automation, Inc. All rights reserved.
http://www.rockwellautomation.com/locations/http://www.rockwellautomation.com/support/americas/phone_en.htmlhttp://www.rockwellautomation.com/support/http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/literature/
2080-RN001I-EN-P Micro800 Programmable Controllers Release NotesAbout This PublicationFirmware Revision HistoryFirmware Backward CompatibilityAvailability of Enhancements and Anomaly Fixes
FeaturesAnomaliesFirmware UpdateAdditional Resources
Back Cover