micropack 24/240 wor - · pdf file see last page for specifications micropack 24/240 wor...
TRANSCRIPT
www.eltekvalere.com See last page for specifications
Micropack 24/240 WOR24VDC & 30VDC Rectifier Module
GREAT SMALL POWER
Convection cooled rectifier for system installation in harsh and noise sensitive environments. The module operates with DC as well as AC input, making it even more flexible.
Product Description With an output voltage range of 21.5-36VDC, the Micropack 24/240 WOR covers both traditional 24 and 30VDC systems as well as 24V system with NiCad batteries which requires high boost charging voltage. Wide ranges of both input voltage and operating temperature give the system superior availability. High current ability for selective fuse tripping, keeps the other load running when there is a short circuit in a load branch. Micropack rectifiers arealso designed to have the highest possible immunity level and fulfill the IEC61000-6-5 (immunity, power station and substation) which is unique in the Industry. The Micropack 24V/240W is a power supply for small power systems. Suitable for load ranges typically between 240W and 960W. Perfect for control cabinets, safety systems and building automation applications. Whether you are in need of a simple standalone power supply or a complete power system with battery backup, distribution, remote control and monitoring, the Micropack family is the perfect choice. Its modularity with DIN rail mountable building blocks allows for high flexibility, on site configuration and assembly. Micropack rectifiers are CE marked and UL recognized. Accompanied by a small DIN railed mounted filter the rectifiers can also be used in marine and offshore applications.
www.eltekvalere.com
2(4)
AC/DC application examples
DC/DC application examples
www.eltekvalere.com
3(4) 241120.200.DS3 – v4
Selective load fuse tripping – to avoid all loads going down when one branch is short circuited
SBF The Micropack 24/240 WOR has a selective quick tripping feature; it is able to deliver 55A for 35ms to help tripping the fuse of the short circuited load before the short circuit pulls down the DC supply voltage for the other loads. The number of rectifiers, type and size of the load breaker which needs to be tripped sets the maximum length of the load cables. This is specified in the table below.
Calculated Maximum loop length (m)
Wire size (mm2)
breaker type 0,8 1 1,5 2,5 4 6 10
system size 10A
C2 13 17 26 43 69 104
C4 8 11 15 28 44 67 112
B6 8 11 17 29 46 70 116
system size 20A
C2 21 28 42 71 114 171
C4 8 11 16 28 44 67 112
C6 2 3 4 8 13 19 33
B6 17 22 34 57 91 137 228
B10 9 13 23 36 55 92
B13 5 9 15 23 38
system size 30A
C2 24 32 49 81 130
C4 11 15 23 38 61 92
C6 5 7 11 18 29 44 74
B6 20 26 40 67 107 161 269
B10 13 19 33 53 79 133
B13 11 19 31 47 79
B16 11 18 27 46
system size 40A
C2 26 34 52 87 139
C4 13 17 26 43 69 104
C6 7 9 14 23 38 57 95
C10 5 8 13 20 34
B6 21 29 43 72 116 174 291
B10 15 23 38 61 92 154
B13 15 25 40 60 100
B16 16 26 40 67
B20 15 22 37
DC/DC applications The Micropack 24/240 WOR running on a battery backup DC supply (85-300VDC)
DC/DC System with controller ü Active current sharing ü Accurate control of output
voltage ü Module monitoring ü N+1 redundancy for converter ü Secondary side load fuse
monitoring ü Secondary side current
monitoring ü Monitoring and alarms through
Ethernet and/or relay signal
Multiple DC/DC stand alone ü N+1 redundancy for converter
and supply breaker ü Passive load sharing ü Serial DC ok signal ü DC output voltage set by
pot.meter
Single DC/DC standalone ü DC ok signal from converter ü DC output voltage set by
pot.meter
AC/DC applications The Micropack 24/240 WOR on mains
DC/DC System with controller ü Bulk feed or -24V 2-30A breakers ü Battery backup on output ü Active current sharing ü Accurate control of output
voltage ü Module monitoring ü N+1 redundancy for rectifier ü Secondary side load fuse
monitoring ü Secondary side current
monitoring ü Monitoring and alarms through
Ethernet and/or relay signal
AC/DC stand alone ü Paralleling for redundancy and
passive load sharing option ü DC ok signal ü DC output voltage set by
pot.meter
www.eltekvalere.com Eltek Valere Gråterudv. 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Fax: +47 32 20 32 10
Applicable Standards Electrical safety IEC 60950-1
UL 60950-1 CSA 22.2
EMC ETSI EN 300 386 V.1.3.2 EN 61000-6-1 (immunity, light
industry) EN 61000-6-2 (immunity, industry) EN 61000-6-3 (emission, light industry) EN 61000-6-4 (emission, industry) EN 61000-6-5 (immunity, power
station and substation)
Mains Harmonics EN 61000-3-2
Environment ETSI EN 300 019-2-1 Class 1.2 ETSI EN 300 019-2-2 Class 2.3 ETSI EN 300 019-2-3 Class 3.2 ETSI EN 300 132-2 RoHS compliant
Marine compliant (w/ additional filer
module)
DnV Rules for Classification of Ships, High Speed & Light Craft and DnV Offshore Standards
Specifications are subject to change without notice (1) from SW revision 1.2.
241120.200.DS3 – v4
Micropack 24/240 WOR Additional Technical Specifications
Part no. Description 241120.200 Micropack 24/240 WOR 241120.900 Stand alone DIN rail fixing 241120.930 Marine Filter CTOU0x02.xxxx CTO configured Micropack system
AC Input Voltage 85-300 VAC (Nominal 185 – 275 VAC)
Linear output derating below 185VAC
Frequency 0 to 66Hz(1)
Maximum Current 1.2 Arms maximum at 230VAC at full load 1.3 Arms maximum at 85VAC and 100W
load
Maximum earth leakage
2.0 mA at 250VAC/50Hz
Power Factor 0.99 at 75% load or more
THD < 5% at nominal input and 50-100% load
Input Protection Varistor for transient protection Mains fuse in both lines (2x 2.5A) Shut down above 300 VAC
DC Output Voltage Pb batteries (24V or30V) NiCd batteries (48V) No of cells configurable in controller
Default: 27.2 VDC Float/Boost: 24.0-36.0VDC Standby test range: 21.5 – 24.0VDC Stand alone: adj. range: 21.5-30.0 VDC Float/Boost charge: 2.0 – 2.4 VDC/cell Standby/Test: 1.8 – 2.0 VDC/cell Float charge: 1,40 – 1.45 VDC/cell Boost charge: 1.45 – 1.65 VDC/cell Standby/Test: 1.05 – 1.2 VDC/cell Pb: 12 (24V) or 15 (30V) NiCd: 20 – 22 (24V)
Output Power 240 W at nominal input 100W at 85VAC
Maximum Current 10 A at 24 VDC and nominal input 15 A for 1min at 21.5V → Capacitive load start-up 55 A for 35ms < 5V → Selective fuse tripping
Current Sharing ±5% of maximum current from 10 to 100% load
U/I Characteristics Constant Power: 21.5 - 36VDC Constant Current: 21.5 - 5VDC Selective fuse tripping < 5VDC
Static voltage regulation
±0.5% from 10% to 100% load
Dynamic voltage regulation
±5.0% for 10-90% or 90-10% load variation, regulation time < 10ms
Hold up time > 20ms; output voltage > 21.5 VDC at 240W load
Ripple and Noise < 200 mV peak to peak, 30 MHz bandwidth
< 5 mV rms psophometric
Output Protection Overvoltage shutdown Hot plug-in - Inrush current limiting Short circuit proof High temperature protection Fuse
Other Specifications Efficiency >92% at 50-90% load
Isolation 3.0 KVAC – input and output 1.5 KVAC – input earth 0.5 KVDC – output earth
Alarms: Low mains shutdown High temperature shutdown Rectifier Failure Overvoltage shutdown on output Low voltage alarm at 21.7V CAN bus failure
Warnings: Low temperature shutdown Rectifier in power derate mode Remote battery current limit activated Input voltage out of range, flashing at
overvoltage Loss of CAN communication with control
unit, stand alone mode
Visual indications
Green LED: ON, no faults Red LED: rectifier failure Yellow LED : rectifier warning
Alarm output (isolated)
NO (+positive terminal) COM (-negative terminal) 60V / 100mA max
Operating temp
-40 to +60°C (-40 to +142°F), derating linear above +45°C to 80W at +60°C
Storage temp -40 to +85°C (-40 to +185°F)
Cooling Convection
MTBF > 480, 000 hours Telcordia SR-332 Issue I, method III (a) (Tambient : 25°C)
Humidity Operating: 5% to 95% RH non-condensing Storage: 0% to 99% RH non-condensing
Dimensions 39.0 x 88.5 x 149mm (wxhxd) (1.54 x 3.48 x 5.87”)
Weight 0.5 kg (1.1lbs)