millennium tm gas-engine-drive chillers 1,435 7,939 1.5 - 5 1,500 g3606 1,765 7,685 43 - 47 1,000...

32
FORM 160.60-EG1 (1295) MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS Design Level "A" 400 Through 2100 Tons Utilizing HFC-134a

Upload: hadiep

Post on 19-May-2018

219 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

FORM 160.60-EG1 (1295)

MILLENNIUM TM

GAS-ENGINE-DRIVE CHILLERSDesign Level "A"

400 Through 2100 TonsUtilizing HFC-134a

Page 2: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

TABLE OF CONTENTS

NOMENCLATURE

The model number denotes the following characteristics of the unit:

YG RE RC J1 ---- G508 A

Model

Cooler Code Design Level

Condenser Code Engine Size

Compressor Code Power Supply - for 60 Hz

Engine, Compressor and Shell Combinations

SHELLS G4 H0 H1 H2 J1 J2 J3 J4LBLBLBLCLCLBLCLC

G3408G3408G3408G3408

MBMBMBMCMCMBMCMC

G3408G3408G3408G3408

G3408G3408G3408G3408

NBNBNBNCNCNBNCNC

G3408G3408G3408G3408

G3408G3408G3408G3408

G3412G3412G3412G3412

G3412G3412G3412G3412

PBPBPBPCPCPBPCPC

G3408G3408G3408G3408

G3408G3408G3408G3408

G3408/3412G3408/3412G3408/3412G3408/3412

G3412/3508G3412/3508G3412/3508G3412/3508

QBQBQBQCQCQBQCQC

G3408/3412G3408/3412G3408/3412G3408/3412

G3412/3508G3412/3508G3412/3508G3412/3508

QDQBQDQCQEQBQEQC

G3508/3512G3508/3512G3508/3512G3508/3512

G3512/3516G3512/3516G3512/3516G3512/3516

RBRBRBRCRCRBRCRC

G3508G3508G3508G3508

RDRBRDRCRERBRERC

G3508/3512G3508/3512G3508/3512G3508/3512

G3512/3516G3512/3516G3512/3516G3512/3516

G3516/3606G3516/3606G3516/3606G3516/3606

G3516/3606G3516/3606G3516/3606G3516/3606

SDSBSDSCSESBSESC

G3512/3516G3512/3516G3512/3516G3512/3516

G3516/3606G3516/3606G3516/3606G3516/3606

G3516/3606G3516/3606G3516/3606G3516/3606

Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Millennium Control Center . . . . . . . . . . . . . . . . . . . . 5

Mechanical Specifications . . . . . . . . . . . . . . . . . . . . 7

Accessories and Modifications. . . . . . . . . . . . . . . . . 12

Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Guide Specifications. . . . . . . . . . . . . . . . . . . . . . . . . 27

2 YORK INTERNATIONAL

Page 3: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Introduction

YORK® MILLENNIUM TM Gas-Engine-Drive (GED) Chiller 400 to 2100 Tons

The YORK Gas-Engine-Drive (GED) Chiller is the mostefficient gas-cooling technology available today. TheGED Chiller is the only natural-gas-engine chiller to bejointly designed, manufactured and tested by two world-class manufacturers; YORK and Caterpillar. The resultis an environmentally friendly, high efficiency chiller withunprecedented product service and support.

HIGH EFFICIENCY RESULTS IN MAXIMUM OPERATIONAL COST SAVINGS

YORK has integrated Caterpillar’s proven gas-enginedesign with its renowned Millennium centrifugal-chillertechnology, resulting in a chiller with full load COPs ashigh as 2.0. Also, by using YORK’s patented variable-speed technology, the GED is a true variable speedchiller capable of part load COPs as high as 2.5. Thehigh efficiency natural gas driven GED chiller maxi-

mizes operational savings by avoiding the demandcharges, ratchet rates and time-of-day charges associ-ated with electrical use. And, because the engine’swaste heat can be reclaimed to produce hot water forheating, many applications will not require a boiler -saving even more money.

ENVIRONMENTALLY FRIENDLY DESIGN

The YORK GED chiller is also an environmentally re-sponsible choice for your cooling needs. GED chillersoperate exclusively with HFC-134a, a CFC-free refrig-erant with zero ozone-depletion potential. Using clean-burning natural gas, SOx emissions are negligible whiletotal CO2 emissions are less per ton-hour than anelectric chiller. Plus, GED chillers are equipped with thefinest NOx reduction technology available to address themost stringent air-quality control standards.

YORK INTERNATIONAL 3

Page 4: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Ratings

CHILLER

MODELCAPACITY (Tons)CONSUMPTION (Btu/Ton Hr)UNIT COP (PER HHV)REFRIGERANT

YGPBPBH1550

6,4721.85

R 134a

YGPCPCH2800

6,4991.85

R 134a

YGQEQCJ1925

6,0821.97

R 134a

YGRERCJ21,3506,2191.93

R 134a

YGSDSBJ31,7506,4821.85

R 134a

YGSESCJ42,0756,2701.91

R 134a

ENGINE

CATERPILLAR ENGINE MODELMAX. ENGINE POWER (BHp)F.L. PERFORMANCE (Btu/BHp Hr)INLET GAS PRESSURE (Psi)RPM

G3408451

8,2411.5 - 51,800

G3412675

7,9681.5 - 51,800

G3508717

7,8741.5 - 51,500

G35121,0777,8691.5 - 51,500

G35161,4357,9391.5 - 51,500

G36061,7657,685

43 - 471,000

EVAPORATOR

GPM (Gal/Min)ENTERING TEMPERATURE (°F)LEAVING TEMPERATURE (°F)PRESSURE DROP (Ft H20)

1,3205444

14.7

1,9205444

20.9

2,2205444

15.7

3,2405444

17.9

4,2005444

21.2

4,9805444

21.7

CONDENSER

GPM (Gal/Min)ENTERING TEMPERATURE (°F)LEAVING TEMPERATURE (°F)PRESSURE DROP (Ft H20)

1,650859517

2,400859517

2,775859517

4,050859517

5,250859517

6,225859517

DRIVELINE HX

GPM (Gal/Min)ENTERING TEMPERATURE (°F)LEAVING TEMPERATURE (°F)PRESSURE DROP (Ft H20)

16585

104.116.2

21585

104.416.2

39585

104.916.2

43085

104.816.2

40085

104.916.2

4158510416.2

TOWERREQUIREMENTS

GPM (Gal/Min)ENTERING TEMPERATURE (°F)LEAVING TEMPERATURE (°F)

1,81595.885

2,61595.885

3,17096.285

4,48095.985

5,65095.785

6,64095.685

HEATRECOVERY

JACKET WATER (Btu/Hr)EXHAUST TO 350°F (Btu/Hr)

1,231,623503,503

1,720,869585,576

1,553,298792,973

2,081,5701,333,523

2,924,9191,862,646

1,143,5222,686,223

PHYSICALDATA

MECHANICAL SOUND @ 3 Ft (dBA)DIMENSIONS (L x W x H)OPERATING WEIGHT

97234 x 191 x 91

47,855

99234 x 191 x 91

52,390

98234 x 243 x 112

75,090

98253 x 262 x 112

94,140

99272 x 268 x 112

110,675

102366 x 264 x 162

176,105

COMPUTERIZED PERFORMANCE RATINGS

Each chiller is custom-matched to meet the individualbuilding load and energy requirements. A large numberof standard heat exchangers and pass arrangementsare available to provide the best possible match.

It is not practical to provide tabulated performance foreach combination, as the energy requirements at bothfull and part-load vary significally with each heat ex-changer and pass arrangement. Computerized ratingsare available through each YORK sales office. Theseratings can be tailored to specific job requirements.

PART-LOAD PERFORMANCE

A chiller should be chosen not only to meet the full-loaddesign, but also for its ability to perform efficiently at lowerloads and lower tower water temperatures. It is notuncommon for chillers with the same full-load BTU/TONto have an operating cost difference of over 10% due topart-load operation.

Part-load information can be easily and accurately gen-erated by use of the computer. And because it is soimportant to an owner’s operating budget, this informa-tion has now been standardized in the form of an Inte-grated Part-Load Value (IPLV), and ApplicationPart-Load Value (APLV).

IPLV or APLV is a single BTU/TON value that describespart-load performance of a chiller. It was originally de-vised to satisfy the needs of the new ANSI/ASHRAE

Standard 90.1 (Standard For Energy Efficient Design ofNew Nonresidential And High-Rise Residential Build-ings). It is based on a schedule of "typical" operatinghours spent at each load point. This allows direct com-parison of each manufacturer’s part-load performanceon an equal basis. An example of the IPLV/APLV calcu-lation is shown below. 1 IPLV or APLV =

0.17 + 0.39 + 0.33 + 0.11 A B C D

WHERE: A = BTU/TON HR AT 100% CAPACITY B = BTU/TON HR AT 75% CAPACITY C = BTU/TON HR AT 50% CAPACITY D = BTU/TON HR AT 25% CAPACITY

%LOAD

ECWT TONS HPBTU/HP

HRBTU/TON

COP WEIGHT

100 85.00 1325 1046 7,831 6,182 1.94 0.1775 78.75 994 726 7,495 5,476 2.19 0.3950 72.50 663 501 8,048 6,086 1.97 0.3325 66.25 331 330 10,024 9,986 1.20 0.11

BTU/TON HR APLV FUEL INPUT 6,293IPLV COP 1.91

While IPLV/APLV provides a quick method of comparingpart-load capabilities, this should not be construed asbeing "typical" for every, or even the majority of jobs. Theonly valid information must take into account actualbuilding load profiles, and local weather data. Part-loadperformance data should be obtained for each job usingits own design criteria.

4 YORK INTERNATIONAL

Page 5: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

MILLENNIUM Control Center

The GED Control Center, furnished as standard on eachGas-Engine-Driven Chiller, provides the ultimate in effi-ciency and chiller protection. State-of-the-art microelec-tronics assure precise, reliable chiller control logic andsafety annunciations. The control center allows directinterfacing with the YORK Integrated Systems Network(ISN) building automation system, allowing complete in-tegration of chiller, airside, and building automation con-trols. This feature makes the YORK chiller the mostversatile in the market place.

Information Display

Vital chiller operating information can be shown on the40-character alphanumeric display. All information is inthe English language with numeric data provided in Eng-lish or metric units.

Information provided on all units as standard includes:• Chilled liquid temperatures - entering and leaving• Condenser liquid temperatures - entering and leaving• Refrigerant pressures - evaporator and condenser• Differential oil pressure• % Engine load• Operating hours• Number of compressor starts• Saturation temperatures - evaporator and condenser• Discharge temperature• Compressor thrust bearing oil temperature• Engine RPM• Engine manifold pressure

• Engine oil pressure• Engine jacket water temperature

In addition, all operating and setpoint information can betransmitted to an optional remote printer through theRS-232 port to obtain data logs:• At any time by pressing PRINT button• At set time intervals by programming the panel• Record of time and cause of safety and cycling shutdowns

with all operating information just prior to shutdown• History printout of last four shutdowns

Leaving Chilled Water Temperature Control

• Digital keypad entry of setpoint to 0.1°F.• Verify actual vs. setpoint temperature via alphanumeric

display.• Remote reset capability standard with YORK ISN Building

Automation System, optional for other analog or discreetremote signals.

• Adjustable remote reset range (up to 20°F) provides flex-ible, efficient use of remote signal depending on resetneeds.

System Cycling Controls

• Programmable seven-day time clock for automaticstart/stop of chiller, cooler and condenser water pumps,and cooling tower.

• Separate schedule input strictly for holidays.• Remote cycling contacts available for other field-supplied

signals.

YORK INTERNATIONAL 5

Page 6: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

MILLENNIUM Control Center (Continued)

System Shutdown Controls

The following safeties responsible for system shutdownare shown in English on the alphanumeric display. Eachannunciation details the day, time, reason for shutdownand type of re-start required. All shutdowns are se-quenced by the micro board except as noted.

Cycling - those controls which automatically reset andpermit auto re-start of the system • Time clock• Low water temperature as sensed through the LWT sensor.

If a drop in water temperature occurs, the unit is stopped at4°F below the chilled liquid temperature setpoint. On a risein water temperature, the unit re-starts automatically.

• Remote/local cycling devices (field supplied).• Automatic re-start after power failure

(a jumper plug is furnished if automatic re-start is desired).• Multi-unit sequencing.• Power fault relay.• Low compressor oil temperature• Aftercooler high inlet water temperature

(Manual restart required)• DC undervoltage• Vanes open• Low differential compressor oil temperature

Safety - those controls which (when employed) requirea manual operation to depress the STOP-RESET switchand then COMPRESSOR START to re-start the system.

• Chilled water pump interlock or flow switch. Flow must beinterrupted for a minimum of two seconds before shutdownwill occur.

• High Compressor Discharge Temperature- fixed cutout provided by thermistor sensor.

• Compressor Thrust Bearing Position and Oil Temperature - combination proximity probe and oil temperature module

shuts down compressor if either threshold limit isreached.

• High Compresssor Oil Reservoir Temperature- fixed cutout provided by thermistor sensor.

Manual re-start after Power Failure(jumper plug furnished if automatic re-start is desired).

• High or Low Compressor Oil Pressure- fixed cutout provided by differential between separate

transducer readings from the compressor sump andbearing feed line.

• Low Evaporator Pressure or High Condenser Pressure- to avoid nuisance cycling, the compressor capacity is

held at cutout threshold for a safe period of time; ifcondition persists, a fixed cutout is provided by dedi-cated transducers.

• Remote stop (field-supplied signal).• Differential between Leaving Chilled Water and Evaporator

Saturation Temperatures- fixed cutout when value falls outside specified range to

detect faulty sensors.

• Auxiliary shutdown• Faulty discharge temperature sensor• Compressor rotation fault• Engine overload• High engine water temperature• Low engine oil pressure• Evaporator transducer or probe error• Clutch failure• Manual engine shutdown• Faulty compressor oil pressure transducer• Faulty proximity probe• Open thermocouple probe• Engine cranking, overspeed, fault• Engine panel shutdown• Engine PLC failure• Surge shutdown• 24 V DC fault• Faulty condenser pressure transducer

Control Mode Selection

There are three keys for the selection of the controlcenter modes:

• ACCESS CODE permits access to the microcomputerPROGRAM and MODE buttons.

• PROGRAM permits the operator to program the setpoints.• MODE permits the operator to select the following control

modes:

• LOCAL allows manual compressor start from the com-pressor switch located on the control center.

• REMOTE allows remote start and stop of the compres-sor and remote reset of the chilled water temperatureand load limit.

• SERVICE allows manual operation of the compressorprerotation vanes and engine speed through the OPEN,CLOSE, HOLD and AUTO keys. Manual operation ofthe oil pump is also included.

Field Interlocks - Chiller Status

• Remote mode ready to start - contact closure indicates thatthe panel is in REMOTE mode and that the unit will start(all safeties and cycling devices satisfied) when a remotestart signal is received.

• Cycling shutdown - contact closure indicates that a cyclingshutdown has occurred and that the unit will re-start whenthe cycling control re-closes.

• Safety shutdown - contact closure indicates that a safetyshutdown has occurred and that a manual reset is requiredto re-start.

• Run contact - closure indicates that the panel is providinga run signal to the engine.

• Remote engine load limit - PWM signal used to limit en-gine’s demand for natural gas.

6 YORK INTERNATIONAL

Page 7: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Mechanical Specifications

GENERAL

The YORK Gas Engine Drive Centrifugal Chiller consistsof, and ships as two packages; a shell package and adriveline package. The shell package includes an evapo-rator and condenser with internal subcooler. The drivelinepackage includes a compressor, compressor lubricationsystem, natural gas engine, clutch, speed increaser, tor-sional vibration reducing coupling, power panel, enginePLC panel and chiller control panel. Interconnecting pipingis shipped separately for field connection. The chiller ispainted with durable alkyd-modified, vinyl enamel machin-ery paint prior to shipment.

The initial charge of oil and refrigerant (HFC-134a) issupplied, shipped in containers and cylinders for fieldinstallation by YORK.

DRIVELINE

The driveline is a skid mounted, factory packaged as-sembly consisting of a heavy duty, industrial grade,turbocharged-aftercooled gas engine; clutch; speed in-creaser; torsional vibration reducing coupling; compres-sor; and compressor oil reservoir with submersiblepump.

MOUNTING BASE - THREE POINT SUSPENSION

The engine, speed increaser, clutch, and compressorare mounted on a common base. The driveline base isdesigned and built by the engine manufacturer to resistdeflection, maintain alignment, and to minimize linearvibration.

The driveline base will be of heavy duty I-beam construc-tion reinforced to maintain equipment alignment duringchiller operation. The base will be 21" for 3400 seriesengines, 24" for 3500 series engines and 36" for 3600series engines. It will accommodate an accessory mod-ule which includes an expansion tank, heat exchanger,and all control panels.

The base will support the full driveline weight on steelspring isolators. The isolators will be bolted to the basein a 3-point mounting arrangement to help maintain shaftalignment. The isolators are installed between thedriveline base and mounting surface and have a waffleor ribbed pad on their bottom surface.

ENGINE

The industrial gas engine is manufactured by CaterpillarInc. The engine is a stationary, liquid-cooled, four-stroke

design, vertical in-line or V-type configuration. The en-gine will be equipped with air filters, pressure gauges,lubricating oil cooler and filter, water pump and pressuregauge, service hour-meter, flywheel and flywheel hous-ing.

Structure and Metallurgy - The design of the basicengine provides for maximum structural integrity to ex-tend service life. Materials used in the engine incorpo-rate the highest level of proven metallurgical andmanufacturing technology.

The block is a one-piece design and cast of high tensilestrength iron in the engine manufacturer’s own foundry.Cylinder wear surfaces are induction hardened overtheir entire length. Pistons are a lightweight aluminumalloy which is elliptically ground across the skirt andtapered from crown to skirt. Compression rings in alu-minum bodies have integral cast iron ring bands. Oil jetssupply piston cooling and lubricating oil. Valves arehard-faced with replaceable inserts.

The crankshaft is a one-piece design. Connecting rods arefabricated of high strength steel with tapered pin bore.

Starting System - The engine starting system can befurnished as either electric or air start.

An electric starting system includes 24 volt DC startingmotor(s), starter relay, and automatic reset circuitbreaker to protect against butt engagement. Batteriesare maintenance free, lead acid type mounted on acorrosion resistant rack near the starting motor.

An air start system includes air starting motor(s), si-lencer, start valve, and pressure regulator. The systemrequires an air supply at an operating pressure of 100psig. (by others)

Both systems are capable of starting a properlyequipped engine within 10 seconds at ambient tempera-tures greater than 70°F.

Engine Lubrication System - The lubrication oil pumpis a positive displacement type that is integral with theengine and gear driven from the engine gear train. Thesystem incorporates a full flow filtration with bypass valveto continue lubrication in the event of filter clogging.

The bypass valve is integral with the engine filter baseor receptacle. Pistons are oil cooled by continuous jetspray to the underside or inside of the crown and pistonring.

YORK INTERNATIONAL 7

Page 8: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Mechanical Specifications (Continued)

Gaseous Fuel System - The gaseous fuel systemconsists of gas pressure regulators and carburetors. Abalance line between the regulator and engine inlet airmanifold is provided to compensate for air cleaner re-striction and turbocharger boost. Carburetors are of thediaphragm type with throttle body and a load screw forair-fuel ratio adjustment.

Ignition System - Units are equipped with an electronicignition system, including detonation sensitive timing.

An accelerometer and electronic buffer unit are mountedon each side of the cylinder block to detect detonationlevel (if any). If detonation is detected, the electronictiming control will adjust ignition timing to eliminatedetonation, or will shut down the unit if required.

Governor - The engine governor is a Woodward Elec-tronic Governor with EG Electro-Hydraulic Actuator.Speed is sensed by a magnetic pickup off the engineflywheel ring gear. A provision for remote speed adjust-ment is included to allow the chiller control panel toadjust engine speed based on load.

Cooling System - All waterside heat rejection from thedriveline is accomplished through a manifolded assem-bly of heat exchangers such that only a single point towerwater supply and return connection is required. Theengine jacket water cooling system is a closed circuitdesign with provision for filling, expansion, and deaera-tion. The engine water pump is driven by the engine. Theengine jacket coolant loop is in turn cooled with a clean-able plate type heat exchanger operating with coolingtower water. Aftercooler and engine oil coolers are plateand frame type heat exchangers. The maximum designcooling tower water supply temperature is 85°F. Coolantpumps, required for heat exchangers or separate circuitaftercooling are engine driven. Coolant temperature isregulated to by-pass external cooling systems until oper-ating temperature is achieved.

Inlet Air System - The engine air cleaner is enginemounted with dry element. If external ducting is required,maximum restriction to the combustion air inlet is limitedto 27 in. H2O.

Turbocharging - The turbocharger consists of an axialflow turbine driven by engine exhaust gases and direct-connected to the compressor supplying engine combus-tion air.

Aftercooling - The aftercooler reduces the temperatureof the air/fuel mixture after compression. Aftercooler

core air surfaces will be coated with a corrosion inhibitorto minimize oxidation.

Speed Increaser - The system driveline is equippedwith a factory aligned gear-set that increases the rotatingspeed from full load engine RPM to 3600 RPM for inputto the compressor. The speed increaser is supplied withface hardened, double helical gears and sleeve bear-ings.

Torsional Coupling - A torsional coupling is selectedto assure that excissive torsional vibration levels are nottransmitted to the gearbox and compressor at all oper-ating speeds.

Air Actuated Clutch - The unit is equipped with a drivedisconnect. The drum type clutch is air actuated andspecifically designed and manufactured for heavyequipment applications. The clutch allows the engine towarm up before engaging and loading the compressor.The clutch also allows the engine to complete a cooldown sequence, as recommended by the engine manu-facturer, without the compressor being engaged.

COMPRESSOR

The compressor is a single stage centrifugal type. Thehousing is fully accessible with vertical circular joints.The complete operating assembly is removable from thecompressor and scroll housing. The rotor assemblyconsists of a heat treated alloy steel drive shaft andimpeller shaft with a cast aluminum, fully shroudedimpeller. The compressor shaft is laser aligned to thespeed increaser in the factory. The impeller is designedfor balanced thrust, and is dynamically balanced, andoverspeed tested for smooth, vibration free operation.Insert type journal bearings are fabricated of aluminumalloy, precision bored and axially grooved.

Internal single helical gears with crowned teeth aredesigned so that more than one tooth is in contact at alltimes to provide even distribution of the compressorload. Each gear is individually mounted in its own journaland thrust bearings to isolate it from impeller and driveforces.

The open drive compressor shaft seal consists of aspring loaded, precision carbon ring, high temperatureelastometer "O" ring static seal, and stress relieved,precision lapped collars. The seal features a small facearea and low rubbing speed. It provides an efficient sealunder high pressure conditions. The seal is oil floodedat all times and is pressure-lubricated during compres-sor operation.

8 YORK INTERNATIONAL

Page 9: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Capacity control is achieved by use of impeller speedvariation and prerotation vanes. Engine speed and pre-rotation vane position are automatically controlled by thecontrol panel to maintain leaving chilled liquid tempera-ture at the desired setpoint without overloading theengine. Engine speed is set to optimize energy effi-ciency. The unit is capable of operating with lower watertemperature cooling tower water during part load opera-tion. At operating conditions requiring less than fullimpeller speed, engine speed is reduced to improvesystem efficiency.

COMPRESSOR LUBRICATION SYSTEM

Lubrication oil is force-fed to all bearings, gears, androtating surfaces by an oil pump which operates prior tostart-up and continuously during operation and coast-down. An oil reservoir, separate from the compressor,contains a submersible oil pump and two immersion-typeoil heaters, thermostatically controlled to remove refrig-erant from the oil. Oil is filtered by an externally mountedreplaceable cartridge oil filter equipped with servicevalves, and cooled by a water cooled oil cooler beforeentering the compressor. Oil piping on the driveline iscompletely factory installed.

EVAPORATOR

The evaporator is of the shell-and-tube, flooded type,designed for 180 psig working pressure on the refrigerantside, and tested at 270 psig. The shell is fabricated fromrolled carbon steel plate with fusion welded seams; hascarbon steel tube sheets, drilled and reamed to accom-modate the tubes; and intermediate tube supportsspaced no more than three feet apart. The refrigerantside is designed, tested and stamped in accordance withAMSE Boiler and Pressure Vessel Code, Section VIII-Di-vision 1.

Tubes are high efficiency, externally and internally en-hanced type. Each tube is roller expanded into tubesheets providing a leak-tight seal. Tubes are 3/4" O.D.,23 BWG, copper alloy and individually replaceable.

Two liquid level sight glasses are located on the side ofthe shell to aid in determining proper refrigerant charge.The evaporator has a refrigerant relief device sized tomeet the requirements of ASHRAE 15 Safety Code forMechanical Refrigeration.

Water boxes are removable to permit tube cleaning andreplacement. Stubout water box connections with 150 lb.ANSI raised face flange are provided. Water boxes aredesigned for 150 psig design working pressure andtested at 225 psig. Plugged 3/4" vent and drain connec-tions are provided in each water box.

CONDENSER

The condenser is of the shell-and-tube type, designedfor 180 psig working pressure on the refrigerant side,and tested at 270 psig. The shell is fabricated from rolledcarbon steel plate with fusion welded seams; has carbonsteel tube sheets, drilled and reamed to accommodatethe tubes; and intermediate tube supports spaced nomore than four feet apart. An internal refrigerant sub-cooler is provided for improved cycle efficiency. Therefrigerant side is designed, tested and stamped inaccordance with ASME Boiler and Pressure VesselCode, Section VIII-Division 1.

Tubes are high efficiency, externally and internally en-hanced type. Each tube is roller expanded into tubesheets providing a leak-tight seal. Tubes are 3/4" O.D.,23 BWG, copper alloy and individually replaceable.

Water boxes are removable to permit tube cleaning andreplacement. Stubout water box connections with 150lb. ANSI raised face flange are provided. Water boxesare designed for 150 psig design working pressure andtested at 225 psig. Plugged 3/4" vent and drain connec-tions are be provided in each water box.

REFRIGERANT FLOW CONTROL

Refrigerant flow to the evaporator is controlled by avariable orifice. The variable orifice automatically adjuststo maintain proper refrigerant level in the condenser andevaporator. This will optimize unit performance at varyingload and temperature conditions.

MICROCOMPUTER CONTROL CENTER

Each unit will be furnished complete with a micro-com-puter control center in a locked enclosure. The controlcenter includes a 40 character alpha-numeric displayshowing all system parameters in the English languagewith numeric data in English or metric units.

Digital programming of setpoints through a color coded,non-tactile keypad includes: leaving chilled liquid tem-perature, percent engine load limit, seven day time clockfor starting and stopping chiller and pumps (completewith holiday schedule), remote reset temperature range,and data logger.

Security access is provided to prevent unauthorizedchange of setpoints, to allow local or remote control ofthe chiller, and to allow manual operation of the prerota-tion vanes, engine speed, and compressor oil pump.

All safety and cycle shutdowns are annunciatedthrough an alpha-numeric display and consist of day,time, cause of shutdown, and type of restart required.

YORK INTERNATIONAL 9

Page 10: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Mechanical Specifications (Continued)

Safety shutdowns include: low evaporator pressure,high condenser pressure, auxiliary safety, high dis-charge temperature, faulty discharge temperature sen-sor, high compressor oil temperature, power failure(manual restart), compressor rotation fault, engineoverload, loss of chilled water flow, high engine watertemperature, low engine oil pressure, low compressoroil pressure, high compressor oil pressure, evaporatortransducer or probe error, clutch failure, manual engineshutdown, faulty compressor oil pressure transducer,proximity sensor fault, high speed thrust bearing oildrain temperature, faulty proximity probe, open thermo-couple probe, engine cranking, engine fault, engineoverspeed, compressor overspeed, engine PLC fault,engine panel shutdown, 24V DC fault, faulty condenser,pressure transducer and remote stop (field suppliedsignal). Cycling shutdowns include: low compressor oiltemperature, power failure (auto restart), low chilledwater temperature, remote unit cycling, multi unit cy-cling, internal time clock, vanes open, compressor lowdifferential oil temperature, DC under-voltage, after-cooler high water temperature (manual restart re-quired), remote/local cycling devices and multi-unitsequencing.

System operating information includes: return/leavingchilled liquid temperature, return/leaving condenser liq-uid temperatures, evaporator/condenser refrigerantpressures, differential compressor oil pressure, percentengine load, evaporator/condenser saturation tempera-tures, compressor discharge temperature, compressoroil temperature, operating hours, number-of-startscounter, engine oil pressure, manifold pressure, enginejacket water temperature and engine speed.

The chiller is provided with an RS-232 port to output allsystem operating data, shutdown/cycling messages,and a record of the last four cycling or safety shutdownsto a remote printer (field supplied). The control center isprogrammable to provide data logs to the optional printerat a preset time interval.

The control center is capable of interfacing with a build-ing automation system to provide remote chillerstart/stop; reset of chilled water temperature; remoteengine load limit; and status messages indicating chilleris ready to start, chiller is operating, chiller is shut downon a safety requiring a manual reset, and chiller is shutdown on a cycling safety.

The operating program is stored in non-volatile memory(EPROM) to eliminate chiller failure due to AC powerfailure/battery discharge. In addition, programmed set-points are retained in lithium battery backed TRC mem-ory for a minimum of 5 years.

VARIABLE SPEED CONTROL

Capacity control is achieved by use of prerotationvanes and varying engine speed. Capacity control logicis matched to the specific chiller/compressor system.Control logic continually integrates the actual chilleroperating conditions, including chilled water tempera-ture and temperature set point, evaporator and con-denser refrigerant pressures, engine speed andprerotation vane position. Prerotation vane position andengine speed are automatically controlled by the chillercontrol panel to maintain leaving chilled liquid tempera-ture at the desired setpoint. Engine speed is set tooptimize chiller energy efficiency. The unit is capableof operating with lower water temperature cooling towerwater during part load operation. Prerotation vane po-sition is automatically controlled by an external electricactuator.

POWER PANEL

The power panel enclosure houses the following com-ponents: single point wiring connection for incomingpower supply; fused disconnect switch, main fuses,compressor oil pump motor starter with overloads;heater relay; circuit breakers for 115VAC, and 60 Hz,3KVA control supply transformer.

NATURAL GAS ENGINE CONTROLS

The engine mounted instrument panel consists of ashock-mounted formed and welded enclosure primedfor coastal environment and finished in semi-glossenamel. Metric/English marked gauges with a minimum2.5 inches diameter dial face are mounted in a brushedstainless steel face panel with pressure instrumentspiped to bulk head connections in the enclosure bottom.Read-outs include: engine oil pressure, oil filter differen-tial, fuel pressure, and jacket water temperature. As partof the engine control/safety system the engine andrelated components are monitored and provided withgauges or safety shutdowns to protect against anysystem failures. Safety shutoffs include low oil pressure,high water temperature, low water level and overspeed.

ISOLATION MOUNTING

The unit is provided with vibration isolation mounts forboth the driveline and shell assemblies. These leveladjusting, spring type isolators are designed for one inchdeflection. The driveline is balanced on four vibrationisolator assemblies, using a three point mounting sys-tem. The isolator assemblies are installed between thedriveline base and the mounting surface and have a

10 YORK INTERNATIONAL

Page 11: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

waffle or ribbed pad on their bottom surface. The shellpackage is provided with four vibration isolation mounts.The vibration isolator assemblies are installed under thetube sheets and are provided with non-skid pads.

TESTING

Prototype Testing - YORK will certify that the engine,compressor, speed increaser, clutch, and controls havebeen tested as complete systems of representative en-gineering models (not on equipment sold).

Specific prototype tests include:

ENGINE:

Performance (part load, full load)Oil ConsumptionFuel ConsumptionExhaust EmissionsNoise Levels (mechanical and exhaust)Startability (cold and hot ambients)Piston, Ring, and Liner Wear RatesPiston Structural IntegrityLubrication System EvaluationCooling System EvaluationValve Train Overspeed QualificationDeep Thermal Cycle EnduranceField Endurance

GAS ENGINE COMPRESSOR DRIVELINE:

Mechanical CompatibilityStructural IntegrityMounting EvaluationWiring CompatibilityControl Panel FunctionalityLinear Vibration MeasurementTorsional Vibration AnalysisPart Load PerformanceSafety Shutdowns and AlarmsStart-Stop Evaluations

Production Testing - Each Gas Engine Driveline issubjected to production performance tests and qualitycontrols to insure reliable operation. The refrigerantcompressor is air run tested at YORK’s test facility priorto mounting on the driveline assembly. The drivelinepackage will be run tested after assembly at conditionsthat fully load the engine. The assembled driveline istested to insure smooth, defect free operation. Testingwill only be done at the engine manufacturer’s testfacility. A certified report of these tests is available whenrequested at the time of chiller order.

START-UP AND OPERATOR TRAINING

Factory trained field service representatives will super-vise the final leak testing, charging and the initial start-up. The complete installation will be checked forprocedural and operational compliance by a factorytrained service representative from YORK. YORK willretain factory trained service representatives of the en-gine manufacturer to provide start-up service and opera-tor instruction for the gas engine.

WARRANTY AND SERVICE

The manufacturer’s standard warranty is for a period ofone year from the date of start-up or eighteen monthsfrom shipment, whichever occurs first. The warrantyincludes parts and labor during this period. Additionally,YORK will provide, at no additional cost to the owner, acomplete one year service or 3000 operating hours,which ever comes first, contract. The contract includesall recommended service and preventative maintenancerequired by the chiller and engine manufacturers duringthe first year of operation or 3000 operating hours, whichever comes first. This service will be performed by YORKand Caterpillar factory trained and authorized servicepersonnel. YORK will have a local direct service officethat can provide factory trained service personnel, therequired stock of replacement parts, technical assis-tance, and warranty administration. Engine mainte-nance will be performed by Caterpillar’s local, factorytrained, authorized representative.

YORK INTERNATIONAL 11

Page 12: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Accessories and Modifications

BAS REMOTE CONTROL

A communication interface permitting complete ex-change of chiller data with any BAS System is availablewith optional ISN translator. ISN translator also allowsBAS System to issue commands to the chiller to controlits operation. ISN translators come in two models, con-trolling up to 4 chillers and 8 chillers respectively.

JACKET WATER HEATER(S)

The engine cooling water must reach a stable operatingtemperature before the engine can be loaded. Thisoption provides factory installed and tested jacket waterheater(s) that will keep the engine cooling water atoperating temperature. This will allow the engine to bestarted and loaded without having to wait for the jacketwater to reach operating temperature.

OIL PRE-LUBE PUMP

This option provides a factory installed and tested con-tinuous pre-lube oil pump. This pump will lubricate en-gine components prior to engine start.

WATER FLOW SWITCHES

These are paddle-type, vapor-proof water flow switchessuitable for 150 psig DWP for chilled and condenserwater circuits. Switch for 115v-1-60 service. A chilledwater flow switch is required. Condenser water flowswitch is optional.

SEQUENCE CONTROL KIT

For two, three or four units with chilled water circuitsconnected in series or parallel, the kit consists of returnwater thermostat, lead-lag selector switch for sequencestarting, and time delay relay, with NEMA-1 enclosures,115v-60 service.

REMOTE RESET CONTROLS

Option board card file allows for continuous reset ofeither leaving chilled water temperature or percent en-

gine load with Building Automation System. 4 to 20 mA,0 to 10 Vdc, or discrete stepped signals can be wireddirectly to panel terminal block on the card file withoutany external interfacing.

VICTAULIC CONNECTIONS

Stub-out water nozzle connections with victaulicgrooves. Nozzles are suitable for either victaulic orwelded connections and are capped for shipment.(Available on condenser connections only if pressuredrop is > 17 ft. H2O.) Please consult YORK marketingfor details.

MARINE WATER BOXES

Marine water boxes allow service access for cleaning ofthe heat exchanger tubes without the need to break thewater piping. Bolted-on covers are arranged for conven-ient access. Flanged nozzle connections are standard.Marine water boxes are available for condenser and/orevaporator.

KNOCK-DOWN SHIPMENT

The chiller can be shipped knocked down into majorsubassemblies (cooler, condenser, driveline, etc.) asrequired to rig into tight spaces. This is particularlyconvenient for existing buildings where equipment roomaccess does not allow rigging a factory packaged chiller.

REFRIGERANT STORAGE/RECYCLING SYSTEM

A refrigerant storage/recycling system is a self-con-tained package consisting of a refrigerant compressorwith oil separator, storage receiver, water-cooled con-denser, filter drier and necessary valves and hoses toremove, replace and distill HFC-134a. All necessarycontrols and safety devices are a permanent part of thesystem.

12 YORK INTERNATIONAL

Page 13: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Application Data

TABLE 1 - FULL LOAD ENGINE DATA

ENGINE MODEL G3408 G3412 G3508 G3512 G3516 G3606RPM 1800 1800 1500 1500 1500 1000MAX BHP 451 675 717 1075 1435 1765FULL LOAD BTU/BHP HR (HHV) 8255 8050 7880 7890 7950 7670COMBUSTION AIR REQUIREDAT FULL LOAD (SCFM)

635 905 1575 2355 3160 4725

INLET GAS PRESSURE REQUIRED (PSIG) 1.5 - 5 1.5 - 5 1.5 - 5 1.5 - 5 1.5 - 5 43 - 47MAXIMUM EXHAUST BACKPRESSURE(IN W.C.)

27 27 27 27 27 12

EXHAUST FLOW (LB/HR) 2815 6425 6522 8498 13842 20432EXHAUST TEMP (°F) 965 690 795 845 870 865RADIATION (BTU/MIN) 2165 3270 4030 4890 6090 10760RECOVERABLE JACKET WATER HEAT(MBH) AT FULL LOAD

1130 1775 1560 2105 2940 1202

RECOVERABLE EXHAUST HEAT(MBH) AT FULL LOAD

480 600 790 1345 1870 2791

TOWER WATER FLOW (GPM)MAX TEMP IN (°F)TEMP OUT (°F)

16585105

21585

105

39585105

43085105

40085105

41585

100NOx EMISSIONS (GRAM/BHP HR) 12 2 2 2 2 1

LOCATION

The Gas-Engine-Driven chiller operating weight shouldbe considered when choosing the unit location. In select-ing a site, consider structural support, access for service,and tube pull area. The unit site must be a floor, mountingpad or foundation which is level within 1/4" and capableof supporting the operating weight of the unit.

Sufficient clearance to permit normal service and main-tenance work. A minimum of 36" should be provided allaround and above the unit. Additional space equal to theshell length should be provided at one end of the unit topermit cleaning and removal of cooler and condensertubes as required. A doorway or other properly locatedopening may be used.

The standard chiller should be installed in an indoorlocation where the temperature ranges from 50° to110°F.

Ventilation

The ASHRAE Standard 15 Safety Code for MechanicalRefrigeration requires that all machinery rooms bevented to the outdoors utilizing mechanical ventilationby one or more power-driven fans. This standard, plusNational Fire Protection Association Standard 90A,state, local, and other codes should be checked forspecific requirements. These requirements should becompared to the requirements for engine ventilation toensure the equipment room is properly ventilated. (SeeForm 160.60-AD1)

Driveline

An engine converts fuel into shaft horsepower and heat.This heat is removed through the jacket water system,aftercooler, exhaust gas system, and radiation from enginesurfaces. As a result, engine drives require different instal-lation considerations than electric motors.

Engine Driven Chiller equipment room considerationsshould include the following:

Fuel Supply - Natural gas fuel is a mixture of severalgases, each having different characteristics (heat value,specific gravity, etc.). The composition of natural gasvaries, but usually contains large amounts of methane,a smaller amount of ethane, and traces of other hydro-carbons. The amount of combustion air required willvary with the gas mixture provided by the local utility.The consumer must provide gas piping to the fuel inletof the chiller driveline. (Gas pressure required per Table1.) If other than pipeline natural gas is used as the fuelsource, contact your local YORK sales office for projectspecific requirements.

Engine Radiation - Three to six percent of the inputenergy (fuel) is typically lost as heat radiated to thesurrounding air. The removal of this radiated heatcauses an additional ventilation requirement that isadded to the combustion air. (Maximum radiation valuesare provided in Table 1.)

Exhaust Systems - The waste gases produced by theengine must be exhausted from the equipment room.See Form 160.60-AD1 for Exhaust Duct Details. Exhaustsystems must be designed and installed to discharge

YORK INTERNATIONAL 13

Page 14: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Application Data (Continued)

SHELLCODE

PASSCOOLER CONDENSER

MINIMUM MAXIMUM MINIMUM MAXIMUM

LB123

632 316 211

2,2761,138 759

881 441

----

3,1751,588

----

LC123

739 370 246

2,6641,332 888

1,031 515

----

3,7141,857

----123

866 433 289

3,121 1,561 1,040

1,255 627----

4,5222,261

----MB

MC123

1,006 503 335

3,626 1,813 1,209

1,473 736----

5,3072,654

----

NB123

1,185 593 395

4,271 2,136 1,424

1,647 824----

5,935 2,968

----

NC123

1,387 694 462

4,999 2,499 1,666

1,940 970----

6,990 3,495

----

PB123

1,625 812 542

5,855 2,928 1,952

2,3291,165

----

8,393 4,196

----

PC123

1,898 949 633

6,841 3,421 2,280

2,7431,342

----

9,885 4,942

----

QB, QD123

2,2241,112 741

8,014 4,007 2,671

3,0771,538

----

11,085 5,543

----

QC, QE123

2,5981,299 866

9,364 4,682 3,121

3,6121,806

----

13,015 6,508

----

RB, RD123

3,0381,5191,012

10,948 5,474 3,649

4,3102,155

----

15,528 7,764

----

RC, RE123

3,5561,7781,185

12,814 6,407 4,271

5,0662,533

----

18,255 9,128

----

SB, SD123

4,1582,0791,386

14,984 7,492 4,995

6,0883,044

----

21,93510,968

----

SC, SE123

4,8642,4321,621

17,531 8,766 5,844

7,1403,570

----

25,72712,864

----

TABLE 2 − WATER FLOW RATE LIMITS (GPM)

exhaust gases as quickly and silently as possible with aminimum amount of backpressure. Excessive back-pressure can cause horsepower losses and exhausttemperature increases. (Exhaust flows, temperaturesand maximum back pressures are provided in Table 1.)

Heat Recovery - Heat is produced as a byproduct ofcombustion. 20% to 50% of the input energy to theengine must be removed by the cooling system. Engineheat is rejected into the oil cooler and engine jacketwater. The YORK driveline is provided with a unitmounted heat exchanger that has been sized and pre-plumbed and tested at the factory to reject the heat fromthese sources to the cooling tower. This allows for a

single customer cooling tower water connection to thedriveline. (Tower water flows and temperatures are pro-vided in Table 1.)

Heat can be recovered from the engine jacket water andthe exhaust gas (minimum leaving exhaust temperatureof 350°). Heat recovery can significantly increase thethermal efficiency of the system. The recovered heat canbe used for any heating load required by the building orto power a single stage absorption chiller. (Recoverableheat is provided in Table 1.)

Cranckcase Fumes - Normal combustion pressures ofthe internal combustion engine cause a certain amountof blowby past the piston rings into the crankcase. Toprevent pressure buildup in the crankcase, vent tubesare provided on the engine to allow the gas to escape.Crankcase gases must be discharged to the atmosphereand not into the equipment room. A separate ventilationsystem for the crankcase must be installed to connec-tions provided on the engine.

Clutch Air Supply - A regulated clean air supply suffi-cient to provide 7SCFM @ 125 psig is required forpressurization of the air clutch. Instrument quality air isnot required.

ENGINE STARTERS

The GED chiller is provided with factory mounted electricengine starting systems. Electric starting is the mostconvient, and adaptable for remote control and automat-ion. The electric starting system includes a startingmotor, batteries, battery pack and charger.

Air starters are available. The air starting system in-cludes a starting motor(s), silencer, start valve, andpressure regulator. The system has an operating pres-sure of 100 psig.

Each of these items is discussed in detail in Form160.60-AD1.

WATER CIRCUITS

Temperature Ranges - For normal water chilling duty,leaving chilled water temperatures may be selectedbetween 40°F and 50°F for water temperature rangesbetween 3°F and 20°F.

Water Quality - The practical and economical applica-tion of liquid chillers requires that the quality of the watersupply for the condenser and cooler be analyzed by awater treatment specialist. Water quality may affect theperformance of any chiller through corrosion, depositionof heat-resistant scale, sedimentation or organic growth.

14 YORK INTERNATIONAL

Page 15: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

FIG. 1 - STANDARD FLOW SCHEMATIC - NO HEAT RECOVERY

These will hurt chiller performance and increase operat-ing and maintenance costs. Normally, performance maybe maintained by corrective water treatments and peri-odic cleaning of tubes. If water conditions exist whichcannot be corrected by proper water treatment, it maybe necessary to provide a larger allowance for fouling,and/or to specify special materials of construction.

General Piping - All chilled water and condenser waterpiping should be designed and installed in accordancewith accepted piping practice. Chilled water and con-denser water pumps should be located to dischargethrough the chiller to assure positive pressure and flowthrough the unit. Piping should include offsets to provideflexibility and should be arranged to prevent drainage ofwater from the cooler and condenser when the pumpsare shut down. Piping should be adequately supportedand braced independent of the chiller to avoid the impo-sition of strain on chiller components. Hangers mustallow for alignment of the pipe. Isolators in the piping andin the hangers are highly desirable in achieving soundand vibration control.

See Figure 1 for the Standard Flow Schematic.

Convenience Considerations - With a view to facilitat-ing the performance of routine maintenance work, someor all of the following steps may be taken by the pur-chaser. Cooler and condenser water boxes areequipped with plugged vent and drain connections. Ifdesired, vent and drain valves may be installed with or

without piping to an open drain. Pressure gauges withstop cocks, and stop valves, may be installed in the inletsand outlets of the condenser and chilled water line asclose as possible to the chiller. An overhead monorail orbeam may be used to facilitate servicing.

Connections - The standard chiller is designed for 150psig working pressure in both the chilled water andcondenser water circuits. The connections (water noz-zles) to these circuits are furnished with 150 # ANSIraised face flanges. Piping should be arranged for easeof disassembly at the unit for performance of such routinemaintenance as tube cleaning. All water piping should bethoroughly cleaned of all dirt and debris before finalconnections are made to the chiller. Driveline connec-tions include single point electrical power connection, gassupply connection, cooling water connection, exhaust,crankcase ventilation, clutch air supply, and air startsupply (if applicable).

Chilled Water - The chilled water circuit should bedesigned for constant flow. A flow switch must be in-stalled in the chilled water line of every circuit. Theswitch must be located in the horizontal piping close tothe unit, where the straight horizontal runs on each sideof the flow switch are at least five pipe diameters inlength. The switch must be electrically connected to thechilled water interlock position in the unit control center.A water strainer of maximum 1/8" mesh must be field-installed in the chilled water inlet line as close as pos-sible to the chiller. If located close enough to the chiller,

YORK INTERNATIONAL 15

Page 16: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Application Data (Continued)

FIG. 2 _ PARALLEL COOLERS PARALLEL CONDENSERS

FIG. 3 _ SERIES COOLERS PARALLEL CONDENSERS

the chilled water pump may be protected by the samestrainer. The flow switch and strainer assure chilledwater flow during unit operation. The loss or severereduction of water flow could seriously impair the chillerperformance or even result in tube freezeup.

Condenser Water - The chiller is engineered for maxi-mum efficiency at both design and part load operation bytaking advantage of the colder cooling tower water tem-peratures which naturally occur during the winter months.Appreciable power savings are realized from these re-duced heads. Exacting control of condenser water tem-perature, requiring an expensive cooling tower bypass, isnot necessary for most applications.

For the usual full load design of 10°F condenser watertemperature range, the chiller only requires that theminimum entering condenser water temperature be atleast 7°F higher than the leaving chilled water tempera-ture.

The minimum entering condenser water temperature forother full and part load conditions is provided by thefollowing equation:

Min. ECWT = LCHWT _ C RANGE + 17

Where: ECWT = entering condensing water temperature LCHWT = leaving chilled water temperature C RANGE = condensing water temperature range

At initial startup, entering condensing water temperaturemay be as much as 25°F colder than the standby chilledwater temperature. Cooling tower fan cycling will nor-

mally provide adequate control of entering condenserwater temperature on most installations.

Additional tower water is required for driveline cooling.There is a connection on the driveline to provide coolingwater to the driveline mounted heat exchanger. Maxi-mum water temperature allowable to the heat exchangeris 85°F. Water flows and temperatures for each drivelineare provided in Table 1.

MULTIPLE UNITS

Many applications require multiple units to meet the totalcapacity requirements as well as to provide flexibility andsome degree of protection against equipment shutdown.There are several common unit arrangements for thistype of application. The Millennium chiller has beendesigned to be readily adapted to the requirements ofthese various arrangements.

Parallel Arrangement (Refer to Fig. 2) - Chillers maybe applied in multiples with chilled and condenser watercircuits connected in parallel between the units. Assum-ing two units of equal size, each will reduce in capacityas the load decreases to about 40% of the total capacity,at which point one of the units will be shut down by asequence control.

Assuming chilled water flow to the inoperative unit isstopped by pump shutdown and/or a closed valve, theremaining unit will pick up the total remaining load andcontinue to reduce in capacity as the load decreases.The unit will cycle off on the low chilled water tempera-ture control when the load reduces below minimum unit

16 YORK INTERNATIONAL

Page 17: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

capacity. The controls can maintain constant (± 1/2°F)leaving chilled water temperature at all loads.

If chilled water continues to flow through the non-operat-ing unit, the chilled water flowing through the operatingunit will mix with the water leaving the non-operating unitto produce a common water supply to the load. Sincecontrol of the operating unit is from its own leaving chillerwater temperature, the common temperature to the loadwill rise above the full load design temperature. Thishigher chilled water temperature occurs below 40% loadwhen the dehumidification load in normal air conditioningapplications is usually quite low. In such instances, thistemperature rise will save additional energy.

The running time may be apportioned between bothunits by alternating the shutoff sequence.

Series Arrangement (Refer to Fig. 3) - Chillers may beapplied in multiples with chilled water circuits connectedin series and condenser water circuits connected inparallel. All of the chilled water flows through both cool-ers with each unit handling approximately one-half of thetotal load. When the load decreases to about 40% of thetotal capacity, one of the units will be shut down bysequence control. Since all water is flowing through theoperating unit, that unit will cool the water to the desiredtemperature.

REFRIGERANT RELIEF PIPING

Each chiller is equipped with a dual pressure-reliefvalve. The purpose of the relief valve is to quickly relieveexcess pressure of the refrigerant charge to the atmos-phere, as a safety precaution in the event of an emer-gency such as fire. They are set to relieve at an internalpressure of 180 psig, are located on the cooler and areprovided in accordance with the ASHRAE 15 SafetyCode and ASME Code for Unfired Pressure vessels.

Sized to the requirements of applicable codes, a ventline must run from the relief device to the outside of thebuilding. This refrigerant relief piping must include acleanable, vertical-leg dirt trap to catch vent-stack con-densation. Vent piping must be arranged to avoid impos-ing a strain on the relief connection and should includeone flexible connection.

VIBRATION AND SOUND CONSIDERATIONS

A Gas-Engine-Driven Millennium chiller is not a sourceof objectionable vibration in normal air conditioning ap-plications. The unit is furnished with vibration isolation.The driveline base is constructed with a three pointvibration isolation mounting system. The shell package

is shipped with standard, level-adjusting spring isolatorassemblies designed for 1" static deflection.

Control of sound and vibration transmission must betaken into account in the equipment room constructionas well as in the selection and installation of the equip-ment. Sound attenuation may be required for equipmentroom, exhaust gas systems, or mechanical noise. Thedesign of the equipment room should address thesesources of noise. (Additional information is provided inForm 160.60-AD1)

Millennium chiller sound pressure level ratings will befurnished on request.

THERMAL INSULATION

No appreciable operating economy can be achieved bythermally insulating the chiller. However, the chiller’scold surfaces surfaces should be insulated with a vaporbarrier insulation sufficient to prevent condensation. In-sulation requirements are provided in Table 3.

TABLE 3 - INSULATION REQUIREMENTS

COOLERCODE

COOLER WITHCOMPACT

WATER BOXES (sq. ft.)

COOLER WITH MARINE

WATER BOXES (sq. ft.)L 265 275M 280 290N 310 325P 345 365Q 390 410R 440 470S 480 560

Muffler and exhaust pipe insulation is recommended tominimize radiation from these sources to the chillerroom. This will minimize ventilation requirements.

ELECTRICAL DATA

Table 4 contains unit electrical data.

TABLE 4 - ELECTRICAL DATA

WITH OPTIONAL JACKET WATER HEATER

ENGINESERIES

AC POWERPANEL LUGSIZE RANGE

JACKETWATER

HEATER KW

MIN. CIRCUIT

AMPACITY

MIN.FUSE SIZE

MAX. FUSE SIZE

3400 #14 - #4 3 17.1 25 303500 #14 - #4 6 21.8 30 353600 #14 - #4 18 40.6 50 70

WITHOUT OPTIONAL JACKETWATER HEATER

ALL #14 - #4 N/A 12.4 15 20NOTE: All values are for 460 V - 3 Phase - 60 Hz electrical service.

YORK INTERNATIONAL 17

Page 18: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Dimensions - 3400 Series Engines

18 YORK INTERNATIONAL

Page 19: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Dimensions - 3400 Series Engines

DIM.G 3408 ENGINE - G4, H0 & H1 COMPRESSORS G 3412 ENGINE - H1 & H2 COMPRESSORS

COOLER - CONDENSER CODE COOLER - CONDENSER CODE

L-L M-M N-N P-P Q-Q N-N P-P Q-Q

A 15’ 6-3/8" 15’ 7-3/8" 16’ 3-3/8" 16’ 9-7/8" 17’ 5-3/8" 16’ 3-3/8" 16’ 9-7/8" 17’ 5-3/8"

B 7’ 9-7/8" 7’ 9-7/8" 7’ 9-7/8" 7’ 9-7/8" 8’ 7’ 9-7/8" 7’ 9-7/8" 8’ 1"

C 6’ 11-1/2" 6’ 11-1/2" 6’ 11-1/2" 6’ 11-1/2" 6’ 11-1/2" 6’ 11-1/2" 6’ 11-1/2" 6’ 11-1/2"

D 6’ 5" 6’ 6" 7’ 2" 7’ 8-1/2 8’ 4" 7’ 2" 7’ 8-1/2" 8’ 4"

E 15’ 3-1/8" 15’ 3-1/8" 15’ 3-1/8" 15’ 3-1/8" 15’ 3-1/8" 16’ 5-1/2" 16’ 5-1/2" 16’ 5-1/2"

F 5’ 5’ 5’ 5’ 5’ 6’ 1-1/4" 6’ 1-1/4" 6’ 1-1/4"

G 9-7/8" 9-7/8" 9-7/8" 9-7/8" 9-7/8" 9-7/8" 9-7/8" 9-7/8"

H 2’ 1-1/2" 2’ 1-1/2" 2’ 1-1/2" 2’ 1-1/2" 2’ 1-1/2" 2’ 1-1/2" 2’ 1-1/2" 2’ 1-1/2"

I 2’ 7-1/8" 2’ 7-1/8" 2’ 7-1/8" 2’ 7-1/8" 2’ 7-1/8" 2’ 7-1/8" 2’ 7-1/8" 2’ 7-1/8"

J 2’ 5/8" 2’ 5/8" 2’ 5/8" 2’ 5/8" 2’ 5/8" 2’ 5/8" 2’ 5/8" 2’ 5/8"

K 2’ 6-5/8" 2’ 6-5/8" 2’ 6-5/8" 2’ 6-5/8" 2’ 6-5/8" 2’ 6-5/8" 2’ 6-5/8" 2’ 6-5/8"

L 3’ 4-7/8" 3’ 4-7/8" 3’ 4-7/8" 3’ 4-7/8" 3’ 4-7/8" 3’ 4-7/8" 3’ 4-7/8" 3’ 4-7/8"

M 2’ 11-1/4" 2’ 11-1/4" 2’ 11-1/4" 2’ 4" 2’ 4" 2’ 4" 2’ 4" 2’ 4"

N 1’ 8-1/2" 1’ 9-1/2" 2’ 2’ 1-1/4" 2’ 3" 2’ 2’ 1-1/4" 2’ 3"

P 1’ 6" 1’ 5-1/2" 1’ 7" 1’ 9" 1’ 11" 1’ 7" 1’ 9" 1’ 11"

Q 2’ 8-5/8" 2’ 8-5/8" 2’ 8-5/8" 2’ 8-5/8" 2’ 8-5/8" 2’ 8-5/8" 2’ 8-5/8" 2’ 8-5/8"

R 6’ 1-3/8" 6’ 1-3/8" 6’ 1-3/8" 6’ 1-3/8" 6’ 1-3/8" 6’ 1-3/8" 6’ 1-3/8" 6’ 1-3/8"

S 9-3/8" 9-3/8" 9-3/8" 9-3/8" 9-3/8" 10-1/8" 10-1/8" 10-1/8"

T 1’ 7-1/2" 1’ 7-1/2" 2’ 1/2" 2’ 1/2" 2’ 1/2" 2’ 1/2" 2’ 1/2" 2’ 1/2"

U 14’ 14’ 14’ 14’ 14’ 14’ 14’ 14’

V 16’ 6-7/8" 16’ 6-3/8" 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8"

YORK INTERNATIONAL 19

Page 20: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Dimensions - 3500 Series Engines

20 YORK INTERNATIONAL

Page 21: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Dimensions - 3500 Series Engines

DIM.

G 3508 ENGINEH2 COMPRESSOR

G 3508 ENGINEJ1 COMPRESSOR

G 3512 ENGINEJ1 & J2 COMPRESSORS

G 3516 ENGINEJ2, J3 & J4 COMPRESSORS

COOLER - CONDENSER CODE

P-P Q-Q R-R Q-Q R-R Q-Q R-R S-S R-R S-S

A 19’ 2-3/8" 19’ 9-7/8" 21’ 4-3/8" 19’ 8-3/8" 21’ 7/8" 19’ 8-3/8" 21’ 7/8" 21’ 10-7/8" 20’ 1-7/8" 21’ 10-7/8"

B 7’ 1" 8’ 2-1/8" 8’ 8-7/8" 8’ 11-1/2" 9’ 4" 8’ 11-1/2" 9’ 4" 9’ 8-1/2" 9’ 8-1/2" 10’ 1-1/2"

C 8’ 7" 8’ 7" 8’ 7" 8’ 7" 8’ 7" 8’ 7" 8’ 7" 8’ 7" 8’ 7" 8’ 7"

D 7’ 8-1/2" 8’ 4" 9’ 10-1/2" 8’ 2-1/2" 9’ 7" 8’ 2-1/2" 9’ 7" 10’ 5" 9’ 7" 10’ 5"

E 18’ 7/8" 18’ 7/8" 18’ 7/8" 18’ 5-1/4" 18’ 5-1/4" 20’ 8-5/8" 20’ 8-5/8" 20’ 8-5/8" 23’ 2-5/8" 23’ 2-5/8"

F 7’ 1-1/8" 7’ 1-1/8" 7’ 1-1/8" 7’ 1-1/8" 7’ 1-1/8" 9’ 3-7/8" 9’ 3-7/8" 9’ 3-7/8" 10’ 7-3/8" 10’ 7-3/8"

H 2’ 3-5/8" 2’ 3-5/8" 2’ 3-5/8" 2’ 3-5/8" 2’ 3-5/8" 2’ 3-5/8" 2’ 3-5/8" 2’ 3-5/8" 2’ 3-5/8" 2’ 3-5/8"

I 3’ 3/4" 3’ 3/4" 3’ 3/4" 3’ 3/4" 3’ 3/4" 3’ 3/4" 3’ 3/4" 3’ 3/4" 3’ 3/4" 3’ 3/4"

J 2’ 2-1/2" 2’ 2-1/2" 2’ 2-1/2" 2’ 2-1/2" 2’ 2-1/2" 2’ 2-1/2" 2’ 2-1/2" 2’ 2-1/2" 2’ 2-1/2" 2’ 2-1/2"

K 2’ 6-1/4" 2’ 6-1/4" 2’ 6-1/4" 2’ 6-1/4" 2’ 6-1/4" 2’ 6-1/4" 2’ 6-1/4" 2’ 6-1/4" 2’ 6-1/4" 2’ 6-1/4"

L 3’ 10-3/4" 3’ 10-3/4" 3’ 10-3/4" 3’ 10-3/4" 3’ 10-3/4" 3’ 10-3/4" 3’ 10-3/4" 3’ 10-3/4" 3’ 10-3/4" 3’ 10-3/4"

M 1’ 6" 1’ 6" 1’ 6" 1’ 6" 1’ 6" 1’ 6" 1’ 6" 1’ 6" 1’ 3" 1’ 3"

N 2’ 1-1/4" 2’ 3" 2’ 7-1/4" 2’ 2-1/4" 2’ 5-1/2" 2’ 2-1/4" 2’ 5-1/2" 2’ 8" 2’ 5-1/2" 2’ 8"

P 1’ 9" 1’ 11" 2’ 4" 1’ 11" 2’ 4" 1’ 11" 2’ 4" 2’ 6-1/2" 2’ 4" 2’ 6-1/2"

Q 4’ 6-3/8" 4’ 6-3/8" 4’ 6-3/8" 4’ 6-3/8" 4’ 6-3/8" 4’ 6-3/8" 4’ 6-3/8" 4’ 6-3/8" 4’ 6-3/8" 4’ 6-3/8"

R 6’ 10-1/2" 6’ 10-1/2" 6’ 10-1/2" 6’ 10-1/2" 6’ 10-1/2" 6’ 10-1/2" 6’ 10-1/2" 6’ 10-1/2" 6’ 10-1/2" 6’ 10-1/2"

S 11-5/8" 11-5/8" 11-5/8" 11-5/8" 11-5/8" 11-5/8" 11-5/8" 11-5/8" 11-5/8" 11-5/8"

T 2’ 1/2" 2’ 1/2" 2’ 1/2" 2’ 1/2" 2’ 1/2" 2’ 1/2" 2’ 1/2" 2’ 1/2" 2’ 1/2" 2’ 1/2"

U 14’ 14’ 14’ 14’ 14’ 14’ 14’ 14’ 14’ 14’

V 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8" 17’ 3-3/8"

YORK INTERNATIONAL 21

Page 22: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Dimensions - 3600 Series Engines

22 YORK INTERNATIONAL

Page 23: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

DIM.G 3603 ENGINE - J3 & J4 COMPRESSORS

COOLER - CONDENSER CODE

R-R S-S

A 20’ 7/8" 20’ 10-7/8"

B 10’ 2-1/8" 10’ 2-1/8"

C 7’ 5-7/8" 7’ 5-7/8"

D 9’ 7" 10’ 5"

E 28’ 3-1/2" 28’ 3-1/2"

F 14’ 8-1/4" 14’ 8-1/4"

G 1’ 3-1/8" 1’ 3-1/8"

H 2’ 6-3/8" 2’ 6-3/8"

I 1’ 2-7/8" 1’ 2-7/8"

J 8’ 1/8" 8’ 1/8"

K 4’ 1-3/4" 4’ 1-3/4"

L 6’ 6" 6’ 6"

N 2’ 5-1/2" 2’ 8"

P 2’ 4" 2’ 6-1/2"

Q 3’ 1-5/8" 3’ 1-5/8"

T 2’ 1/2" 2’ 1/2"

U 14’ 14’

V 17’ 3-3/8" 17’ 3-3/8"

Dimensions - 3600 Series Engines

YORK INTERNATIONAL 23

Page 24: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

WATER BOX DIMENSIONS

COMP.CODE

SHELLCODE

COOLER CONDENSER

AB

C MD

E F N2 PASS 3 PASS 1 PASS 2 PASS

G & H

L 3’ 3-1/2" 1’ 5-1/2" 1’ 4-1/2" 2’ 2" 1’ 8-1/2" 4’ 6-3/4" 4’ 7-1/4" 1’ 11-3/4" 1’ 5-1/4" 1’ 6"M 3’ 4-1/2" 1’ 6-1/2" 1’ 5-1/2" 2’ 2" 1’ 9-1/2" 4’ 9-3/4" 4’ 9-3/4" 1’ 11-1/4" 1’ 4-3/4" 1’ 5-1/2"N 3’ 9-5/8" 1’ 6-3/4" 1’ 4-5/8" 2’ 5" 2’ 0" 5’ 1-3/4" 5’ 1-1/4" 1’ 7-3/4" 1’ 6-1/4" 1’ 7"P 3’ 10-3/8" 1’ 7-1/2" 1’ 5-3/8" 2’ 5" 2’ 1-1/4" 5’ 8-1/4" 5’ 6-3/4" 1’ 11-3/4" 1’ 8-1/4" 1’ 9"Q 4’ 0-1/4" 1’ 9-3/4" 1’ 8-1/4" 2’ 7-1/4" 2’ 3" 5’ 11-3/4" 5’ 11-3/4" 2’ 0-3/4" 1’ 10-1/4" 1’ 11"R 4’ 1" 1’ 11" 1’ 10" 2’ 10-1/4" 2’ 7-1/4" 6’ 10-3/4" 6’ 10-3/4" 2’ 2-1/4" 2’ 3-1/4" 2’ 4"

J

QD 4’ 3-1/2" 2’ 1" 1’ 11-1/2" 2’ 7-1/4" 2’ 2-1/4" 6’ 6-3/4" 6’ 6-3/4" 2’ 7-3/4" 1’ 10-1/4" 1’ 11"E 4’ 4-1/4" 2’ 1-3/4" 2’ 0-1/4"

RD 4’ 5-1/4" 2’ 3-1/4" 2’ 2-1/4" 2’ 10-1/4" 2’ 5-1/2" 7’ 5-3/4" 7’ 5-3/4" 2’ 9-1/4" 2’ 3-1/4" 2’ 4"E 4’ 6" 2’ 4" 2’ 3"

S 6’ 10" 1’ 10-1/2" 1’ 8-1/2" 2’ 7-1/4" 2’ 8" 7’ 11-1/4" 7’ 11-1/4" 2’ 8-3/4" 2’ 5-3/4" 2’ 6-1/2"

Dimensions - Nozzle Arrangements (Marine Water Boxes)

24 YORK INTERNATIONAL

Page 25: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

NOTE:

1. All dimensions are approximate. Certified dimensions are available upon request.

2. Standard water nozzles are furnished with 150 lb. ANSI raised face flanges. Companion flanges, nuts, bolts and gaskets are not furnished.Victaulic groove connections, suitable for victaulic or welded connections, are available (Consult YORK Marketing for exact availability ofvictaulic connections for condenser water circuit.)

3. One, two and three pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles used incombination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with marine water boxes on theother heat exchanger.

4. Condenser water must enter the water box through the bottom connection for proper operation of the sub-cooler to achieve rated performance.

CONDENSER NOZZLE DIMENSIONS

SHELLCODE

NO. OFPASSES

J K L

L1 9-7/8" 1’ 9" -2 8-7/8" 1’ 7" 6-7/8"

M1 11" 1’ 11-1/2" -2 10" 1’ 9-1/2" 7-5/8"

N1 1’ 1-3/8" 2’ 4-3/8" -2 10-3/8" 1’ 10-3/8" 8-3/8"

P1 1’ 1-5/8" 2’ 5" -2 11-5/8" 2’ 1" 9-3/8"

Q1 1’ 2-5/8" 2’ 7-1/4" -2 1’ 0-5/8" 2’ 3-1/4" 10-3/8"

R1 1’ 3-1/8" 2’ 8-3/4" -2 1’ 2-1/8" 2’ 6-3/4" 11-3/4"

S1 1’ 4-1/2" 2’ 11-5/8" -2 1’ 4-1/2" 2’ 11-5/8" 1’ 1-5/8"

COOLER NOZZLE DIMENSIONS

SHELLCODE

NO. OFPASSES

G H

L1 10-1/8" 1’ 10"2 9-1/8" 1’ 8"3 8-1/8" 1’ 6"

M1 10-1/8" 1’ 10"2 9-1/8" 1’ 8"3 8-1/8" 1’ 6"

N1 11-1/8" 2’ 0-1/2"2 10-1/8" 1’ 10-1/2"3 9-1/8" 1’ 8-1/2"

P1 1’ 0-1/8" 2’ 2-1/2"2 10-1/8" 1’ 10-1/2"3 9-1/8" 1’ 8-1/2"

Q1 1’ 1-1/8" 2’ 4-3/4"2 11-1/8" 2’ 0-3/4"3 10-1/8" 1’ 10-3/4"

R1 1’ 2" 2’ 6-3/4"2 1’ 0-1/8" 2’ 2-3/4"3 11-1/8" 2’ 0-3/4"

S1 1’ 4-1/4" 2’ 11-1/8"2 1’ 2-3/4" 2’ 8-1/8"3 1’ 1-3/4" 2’ 6-1/8"

NOZZLE SIZES

COOLERCODE

COOLER CONDENSERNO. OF PASSES NO. OF PASSES

1 2 3 1 2L 10" 8" 6" 10" 8"M 10" 8" 6" 12" 10"N 12" 10" 8" 16" 10"P 14" 10" 8" 16" 12"Q 16" 12" 10" 18" 14"R 18" 14" 12" 18" 16"S 18" 16" 14" 18" 18"

NOZZLE ARRANGEMENTS

NO. OFPASSES

COOLER CONDENSER

IN OUT IN OUT

11 6 11 146 1 14 11

22 3 12 137 8 15 16

34 10 - -9 5 - -

Dimensions - Nozzle Arrangements (Marine Water Boxes)

YORK INTERNATIONAL 25

Page 26: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

WATER BOX DIMENSIONS

COMP.CODE

SHELLCODE

COOLER CONDENSER

AA EE FF BB CC DD GG

G & H

L 1’ 9" 8-1/2" 1’ 8-1/2" 2’ 2-1/4" 2’ 10-3/4" 3’ 7-1/4" 1’ 6"M 1’ 10" 8-1/2" 1’ 9-1/2" 2’2-3/4" 3’ 0-1/4" 3’ 9-3/4" 1’ 5-1/2"N 1’ 11-5/8" 10" 2’ 0" 2’ 3-1/2" 3’ 1-3/4" 4’ 0" 1’ 7"P 2’ 0-3/8" 11" 2’ 1-1/4" 2’ 6-1/4" 3’ 5-3/4" 4’ 5-1/4" 1’ 9"Q 2’ 2-1/4" 11" 2’ 3" 2’ 8-1/8" 3’ 8-3/4" 4’ 9-3/8" 1’ 11"R 2’ 3" 1’ 1" 2’ 7-1/4" 3’ 0-3/4" 4’ 2-3/4" 5’ 4-3/4" 2’ 4"

J

QD 2’ 6-1/4" 11" 2’ 2-1/4" 3’ 3-1/8" 4’ 3-3/4" 5’ 4-3/8" 1’ 11"E 2’ 7"

RD 2’ 7-1/4" 1’ 1" 2’ 5-1/2" 3’ 7-3/4" 4’ 9-3/4" 5’ 11-3/4" 2’ 4"E 2’ 8"

S 2’ 11-3/4" 1’ 3" 2’ 8" 3’ 7-7/8" 4’ 11-3/4" 6’ 3-5/8" 2’ 6-1/2"

NOZZLE ARRANGEMENTS

NO. OFPASSES

COOLER CONDENSER

IN OUT IN OUT

1A D G KD A K G

2

B C J HC B M LE F - -F E - -

3A D - -D A - -

NOTES:

1. All dimensions are approximate. Certified dimensions are available upon request.

2. Standard water nozzles are furnished with 150 lb. ANSI raised face flanges. Companion flanges, nuts, bolts and gaskets are not furnished.Victaulic groove connections, suitable for victaulic or welded connections, are available (Consult YORK Marketing for exact availability ofvictaulic connections for condenser water circuit.

3. One, two and three pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of cooler nozzles used incombination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with marine water boxes on theother heat exchanger.

4. Condenser water must enter the water box through the bottom connection for proper operation of the sub-cooler to achieve rated performance.

5. Connected piping should allow for removal of compact water box for tube access and cleaning.

NOZZLE SIZES

SHELLCODE

COOLER CONDENSERNO. OF PASSES NO. OF PASSES

1 2 3 1 2L 10" 8" 6" 10" 8"M 10" 8" 6" 12" 10"N 12" 10" 8" 16" 10"P 14" 10" 8" 16" 12"Q 16" 12" 10" 18" 14"R 18" 14" 12" 18" 16"S 18" 16" 14" 18" 18"

Dimensions - Nozzle Arrangements (Compact Water Boxes)

26 YORK INTERNATIONAL

Page 27: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Guide Specifications

Furnish and install where indicated on the drawings_____Gas-Engine-Driven Centrifugal Liquid ChillingUnit(s). Each unit shall produce a capacity of _____ tonscooling ______GPM of water from_____°F to _____ °Fwhen supplied with ______ GPM of tower water at 85°F.Shaft power requirements shall not exceed______HP.Unit COP shall not be less than ______ at full load. Thecooler shall be selected for 000025 fouling factor with amaximum chilled water pressure drop of______feet.Evaporator water side shall be designed for 150 psigworking pressure. The condenser shall be selected for.00025 fouling factor with a maximum condenser waterpressure drop of _____ feet. Condenser water side shallbe designed for 150 psig working pressure. The drivelinecooling system heat exchanger shall be selected for.00025 fouling factor with a maximum tower water pres-sure drop of _____feet when supplied with_____GPMof tower water. Power shall be supplied to the unit at 460volts-3 phase-60 hertz.

Each unit shall ship as two packages; a shell packageand a driveline package. Units with the engine mountedon the same base as the shells are not acceptable unlessthe manufacturer provides a 20 year guarantee againsttube failure. The shell package shall include an evapo-rator, and condenser with integral subcooler. Thedriveline package shall include a compressor, compres-sor lubrication system, natural gas engine, air actuatedclutch, speed increaser, torsional vibration reducing cou-pling, power panel, engine PLC panel, and chiller controlpanel. Interconnecting piping and wiring shall ship loosefor field connection. The chiller shall be painted withdurable alkyd-modified, vinyl enamel machinery paintprior to shipment.

The unit shall operate with an HFC refrigerant. Chillersthat operate with refrigerants having phase out dates arenot acceptable. R-11,12, 22, or 500 are not acceptablerefrigerants.

The initial charge of oil and refrigerant (HFC-134a) shallbe supplied, shipped in containers and cylinders for fieldinstallation by the manufacturer.

Driveline

The driveline shall be a skid mounted, factory packagedassembly consisting of a heavy duty, industrial grade,turbocharged-aftercooled gas engine; speed increaser;torsional vibration reducing coupling; air actuated clutch;compressor; and oil reservoir with submersible pump.

Mounting Base --Three Point Suspension

The engine, speed increaser, clutch, and compressorshall be mounted to a common base by the enginemanufacturer. The driveline base shall be designed andbuilt by the engine manufacturer to resist deflection,maintain alignment, and to minimize linear vibration.

The driveline base shall be of heavy duty I - beamconstruction reinforced to maintain equipment alignmentduring chiller operation. The base shall be a minimum of18". It shall accommodate an accessory module whichshall include an expansion tank, heat exchanger, andinstrument panel with engine controls.

The base shall support the full driveline weight on steelspring isolators. The isolators shall be bolted to the basein a 3-point mounting arrangement to help maintain shaftalignment. The isolators shall be installed between thedriveline base and mounting surface and shall haveeither a waffle or ribbed pad on their bottom surface.

Engine

The industrial gas engine shall be manufactured byCaterpillar Inc. The engine shall be a stationary, liquid-cooled, 1000-1800 rpm, four-stroke design, vertical in-line or V-type configuration. The engine shall beequipped with air filters, pressure gauges, lubricating oilcooler and filter, water pump and pressure gauge, serv-ice hour-meter, flywheel and flywheel housing.

Structure and Metallurgy - The design of the basicengine shall provide for maximum structural integrity toextend service life. Materials used in the engine shallincorporate the highest level of proven metallurgical andmanufacturing technology.

The block shall be of one piece design and cast of hightensile strength iron in the engine manufacturer’s ownfoundry.

Counterboring for cylinder liners shall not be permitted.Cylinder wear surfaces shall be induction hardened overtheir entire length. Pistons shall be a lightweight alumi-num alloy which is elliptically ground across the skirt andtapered from crown to skirt. For medium and high speedengines, compression rings in aluminum bodies shallhave integral cast iron ring bands. Compression rings insteel piston crowns shall seat in hardened steel groves.Oil jets shall supply piston cooling and lubricating oil.Valves shall be hard-faced with replaceable inserts.

The crankshaft shall be a one piece design. Multiplesection crankshaft will not be acceptable. Connectingrods shall be of high strength steel with tapered pin bore.Drilled passages to supply oil from rod bearing for pistoncooling and lubricating oil will not be permitted.

Starting System - The engine starting system shall beeither electric or air start.

The electric starting system shall include 24 volt DCstarting motor(s), starter relay, and automatic reset circuitbreaker to protect against butt engagement. Batteriesshall be maintenance free, lead acid type mounted on acorrosion resistant rack near the starting motor.

YORK INTERNATIONAL 27

Page 28: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Guide Specifications (Continued)

An air start system shall include air starting motor(s),silencer, start valve, and pressure regulator. The systemshall have an operating pressure of 100 psig.

Both systems shall be capable of starting a properlyequipped engine within 10 seconds at ambient tempera-tures greater than 70° F.

Engine Lubrication System - The lubrication oil pumpshall be positive displacement type that is integral withthe engine and gear driven from the engine gear train.The system shall incorporate full flow filtration with by-pass valve to continue lubrication in the event of filterclogging. The chiller manufacture shall be able to providean optional continuous pre-lube oil pump to lubricateengine components prior to engine starting.

The bypass valve must be integral with the engine filterbase or receptacle. Systems with bypass valves locatedin the replaceable oil filter are not acceptable. Pistonsshall be oil cooled by continuous jet spray to the under-side or inside of the crown and piston ring.

Gaseous Fuel System - The gaseous fuel system shallconsist of gas pressure regulators and carburetors. Abalance line between the regulator and engine inlet airmanifold shall be provided to compensate for air cleanerrestriction and turbocharger boost. Carburetors shall beof the diaphragm type with throttle body with a load screwfor air-fuel ratio adjustment.

Ignition System - The unit shall be equipped with anelectronic ignition system. The unit shall include detona-tion sensitive timing. The ignition system shall incorpo-rate a control system that senses and reacts tocombustion detonation by controlling ignition timing.

An accelerometer and electronic buffer unit shall bemounted on each side of the cylinder block to detectdetonation level (if any). If detonation is detected theelectronic timing control shall adjust ignition timing toeliminate detonation.

Governor - The engine governor shall be a WoodwardElectronic Speed Control with EG Electro-Hydraulic Ac-tuator. Speed shall be sensed by a magnetic pickup offthe engine flywheel ring gear. A provision for remotespeed adjustment shall be included to allow the chillercontrol panel to adjust engine speed based on load.

Cooling System - All waterside heat rejection from thedriveline shall be accomplished through a manifoldedassembly of heat exchangers such that only a singlepoint tower water supply and return connection is re-quired. The engine jacket water cooling system shall bea closed circuit design with provision for filling, expan-sion, and deaeration. The engine water pump shall bedriven by the engine. The engine jacket coolant loop shallin turn be cooled with a plate type heat exchanger

operating with cooling tower water. The chiller manufac-turer shall be able to provide an optional jacket waterheater to warm the engine water to operating levels priorto starting. Aftercooler and engine oil coolers shall beplate and frame type heat exchangers. Coolant pumpsrequired for heat exchangers or separate circuit after-cooling shall be engine driven. Coolant temperature shallbe regulated to disconnect external cooling systems untiloperating temperature is achieved.

Inlet Air System - The engine air cleaner shall be enginemounted with dry element. If external ducting is required,maximum restriction to the combustion air inlet shall be27 in H2O.

Turbocharging - Only single stage turbocharging shallbe allowed. The turbocharger shall be of the axial turbinetype driven by engine exhaust gases and direct - con-nected to the compressor supplying engine combustionair.

Aftercooling aftercooler(s) shall be provided to lower theair\fuel mixture’s temperature after compression. After-cooler core air surfaces shall be coated with a corrosioninhibitor to minimize oxidation.

Speed Increaser - The system driveline shall beequipped with a factory aligned gear-set that increasesthe rotating speed from full load engine RPM to 3600RPM for input to the compressor. The speed increasershall be supplied with face hardened, double helicalgears and sleeve bearings.

Torsional Coupling - A torsional coupling shall be se-lected to assure that excessive torsional vibration levelsare not transmitted to the gearbox and compressor at alloperating speeds.

Air Actuated Clutch - The unit shall be equipped with adrive disconnect. The drum type clutch shall be air actu-ated and specifically designed and manufactured forheavy equipment applications. The clutch shall allow theengine to warm up before engaging and loading thecompressor. The clutch shall also allow the engine tocomplete a cool down sequence, as recommended bythe engine manufacturer, without the compressor beingengaged. Units without a clutch shall not be considered.

Compressor

The compressor shall be a single stage centrifugal type.Screw compressors are not acceptable. The housingshall be fully accessible with vertical circular joints. Thecomplete operating assembly shall be removable fromthe compressor and scroll housing. Compressor cast-ings shall be designed for a minimum working pressureof 200 psig and hydrostatic pressure tested at a minimumof 300 psig. The rotor assembly shall consist of a heattreated alloy steel drive shaft and impeller shaft with a

28 YORK INTERNATIONAL

Page 29: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

cast aluminum, fully shrouded impeller. The compressorshaft shall be laser aligned to the speed increaser in thefactory. The impeller shall be designed for balancedthrust and is dynamically balanced, and overspeedtested for smooth, vibration free operation. Insert typejournal bearings shall be fabricated of aluminum alloy,precision bored and axially grooved.

Internal single helical gears with crowned teeth shall bedesigned so that more than one tooth is in contact at alltimes to provide even distribution of the compressor load.Each gear shall be individually mounted in its own journaland thrust bearings to isolate it from impeller and driveforces.

The open drive compressor shaft seal shall consist of aspring loaded, precision carbon ring, high temperatureelastometer "O" ring static seal, and stress relieved,precision lapped collars. The seal shall feature a smallface area and low rubbing speed. It shall provide anefficient seal under high pressure conditions. The sealshall be oil flooded at all times and pressure-lubricatedduring compressor operation.

Capacity control shall be achieved by use of impellerspeed variation and prerotation vanes. Engine speedand prerotation vane position shall be automatically con-trolled by the chiller control panel to maintain leavingchilled liquid temperature at the desired setpoint withoutoverloading the engine. Engine speed shall be set tooptimize energy efficiency. At operating conditions re-quiring less than full impeller speed, engine speed shallbe reduced to improve system efficiency. The unit shallbe capable of operating with entering condenser wateras low as 60° F at full load without need for a condenserwater bypass. Also, the chiller shall be able to operatewith lower condenser water temperature during part loadoperation.

Compressor Lubrication System

Lubrication oil shall be force-fed to all bearings, gears,and rotating surfaces by an oil pump which operates priorto start-up and continuously during operation and duringcoastdown. A gravity-fed oil reservoir shall be built intothe top of the compressor to provide lubrication duringcoastdown in the event of a power failure. An oil reser-voir, separate from the compressor, shall contain a sub-mersible oil pump and two immersion-type oil heaters,thermostatically controlled to remove refrigerant from theoil. Oil shall be filtered by an externally mounted replace-able cartridge oil filter equipped with service valves, andcooled by a water cooled oil cooler before entering thecompressor. Oil piping on the driveline shall be com-pletely factory installed. Interconnecting oil piping be-tween the shell and driveline skid must be provided forand installed in the field.

Evaporator

The evaporator shall be of the shell-and-tube, floodedtype, designed for 180 psig working pressure on therefrigerant side, and tested at 270 psig. The shell shallbe fabricated from rolled carbon steel plate with fusionwelded seams; have carbon steel tube sheets, drilled toaccommodate the tubes; and intermediate tube sup-ports spaced no more than three feet apart. The refrig-erant side shall be designed, tested and stamped inaccordance with ASME Boiler and Pressure VesselCode, Section VIII-Division 1. Tubes shall be high effi-ciency, externally and internally enhanced type. Eachtube shall be roller expanded into tube sheets providinga leak-proof seal. Tubes shall be individually replace-able. Water velocity through the tubes shall not exceed12 FPS. Two liquid level sight glasses shall be locatedon the side of the shell to aid in determining properrefrigerant charge. The evaporator shall have a refriger-ant relief device sized to meet the requirements ofASHRAE 15 Safety code for Mechanical Refrigeration.

Water boxes shall be removable to permit tube clean-ing and replacement. Stubout water box connectionswith 150 lb ANSI raised face flanges shall be provided.Water boxes shall be designed for 150 psig designworking pressure and be tested at 225 psig. Vent anddrain connections with plugs shall be provided in eachwater box.

Condenser

The condenser shall be of the shell-and-tube type, de-signed for 180 psig working pressure on the refrigerantside, and tested at 270 psig. The shell shall be fabricatedfrom rolled carbon steel plate with fusion welded seams;have carbon steel tube sheets, drilled to accommodatethe tubes; and intermediate tube supports spaced nomore than four feet apart. An integral refrigerant sub-cooler shall be provided for improved cycle efficiency.The refrigerant side shall be designed, tested andstamped in accordance with ASME Boiler and PressureVessel Code, Section VIII-Division 1. Tubes shall behigh efficiency, externally and internally enhanced type.Each tube shall be roller expanded into tube sheetsproviding a leak-proof seal. Tubes shall be individuallyreplaceable. Water velocity through the tubes shall notexceed 12 FPS.

Water boxes shall be removable to permit tube cleaningand replacement. Stubout water box connections with150 lb ANSI raised face flanges shall be provided. Waterboxes shall be designed for 150 psig design workingpressure and be tested at 225 psig. Vent and drainconnections with plugs shall be provided in each waterbox.

YORK INTERNATIONAL 29

Page 30: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

Guide Specifications (Continued)

Refrigerant Flow Control

Refrigerant flow to the evaporator shall be controlled bya variable orifice. The variable orifice control shall auto-matically adjust to maintain proper refrigerant level in thecondenser and evaporator. This shall be controlled bymonitoring refrigerant liquid level in the condenser, as-suring optimal subcooler performance.

Chiller Microcomputer Control Center

Each unit shall be furnished complete with a micro com-puter control center in a locked enclosure. The chillershall be controlled through a single panel. The panelshall have the capability to control inlet guide vaneposition as well as engine speed in response to chillerload requirements. The control center shall include a 40character alphanumeric display showing all system pa-rameters in the English language with numeric data inEnglish or metric units.

Digital programming of setpoints through a color coded,non-tactile keypad shall include: leaving chilled liquidtemperature, percent engine load limit, seven day timeclock for starting and stopping chiller and pumps (com-plete with holiday schedule), remote reset temperaturerange, and data logger.

Security access shall be provided to prevent unauthor-ized change of setpoints, to allow local or remote controlof the chiller, and to allow manual operation of theprerotation vanes and compressor oil pump.

All safety and cycle shutdowns shall be annunciatedthrough an alpha numeric display and consist of day,time, cause of shutdown, and type of restart required.Safety shutdowns shall include: low evaporator pres-sure, high condenser pressure, auxiliary safety, highdischarge temperature, faulty discharge temperaturesensor, high compressor oil temperature, power failure(manual restart), compressor rotation fault, engine over-load, loss of chilled water flow, high engine water tem-perature, low engine oil pressure, low compressor oilpressure, high compressor oil pressure, evaporatortransducer or probe error, clutch failure, manual engineshutdown, faulty compressor oil pressure transducer,proximity sensor fault, high speed thrust bearing oil draintemperature, faulty proximity probe, open thermocoupleprobe, engine cranking, engine fault, engine overspeed,compressor overspeed, engine PLC fault, engine panelshutdown, surge shutdown, 24V DC fault, faulty condenserpressure transducer and remote stop (field supplied signal).Cycling shutdowns shall include: low compressor oil tem-perature, power failure (auto restart), low chilled watertemperature, remote unit cycling, multi unit cycling, internaltime clock, vanes open, compressor low differential oiltemperature, DC under-voltage, and aftercooler high watertemperature (manual restart required), remote/local cycling

devices and multi-unit sequencing.

System operating information shall include: return/leav-ing chilled liquid temperature, return/leaving condenserliquid temperatures; evaporator/condenser refrigerantpressures; differential compressor oil pressure, percentengine load, evaporator/condenser saturation tempera-tures, compressor discharge temperature, compressoroil temperature, operating hours, number of startscounter engine oil pressure, engine manifold pressure,engine jacket water temperature and engine speed.

The chiller shall be provided with an RS-232 port tooutput all system operating data, shutdown/cycling mes-sages, and a record of the last four cycling or safetyshutdowns to a remote printer (field supplied). The con-trol center shall be programmable to provide data logs tothe optional printer at a preset time interval.

The control center shall be able to interface with abuilding automation system to provide remote chillerstart/stop; reset of chilled water temperature; remoteengine load limit; and status messages indicating chilleris ready to start, chiller is operating, chiller is shutdownon a safety requiring a manual reset, and chiller isshutdown on a cycling safety.

The operating program shall be stored in non-volatilememory (EPROM) to eliminate chiller failure due to ACpower failure\battery discharge. In addition, programmedsetpoints shall be retained in lithium battery-backed TRCmemory for a minimum of 5 years.

Variable Speed Control

Capacity control shall be achieved by use of prerotationvanes and varying engine speed. Capacity control logicshall be matched to the specific chiller/compressor sys-tem. Control logic shall continually integrate the actualchiller operating conditions, including chilled water tem-perature and temperature set point, evaporator and con-denser refrigerant pressures, engine speed andprerotation vane position. Prerotation vane position andengine speed shall be automatically controlled by thechiller control panel to maintain leaving chilled liquidtemperature at the desired setpoint. Engine speed shallbe set to optimize chiller energy efficiency. The unit shallbe capable of operating with lower water temperaturecooling tower water during part load operation. Prerota-tion vane position shall be automatically controlled by anexternal electric actuator.

Power Panel

The power panel enclosure shall house the followingcomponents: single point wiring connection for incomingpower supply; fused disconnect switch, main fuses, com-pressor oil pump motor starter with overloads; heater

30 YORK INTERNATIONAL

Page 31: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

relay; circuit breakers for 115 VAC, 60 Hz, 3 KVA controlsupply transformer.

Natural Gas Engine Controls

The engine mounted instrument panel shall consist of ashock-mounted formed and welded enclosure primed forcoastal environment and finished in semi-gloss enamel.Metric/English marked gauges with a minimum 2.5inches diameter dial face shall be mounted in a brushedstainless steel face panel with pressure instrumentspiped to bulk head connections in the enclosure bottom.Gauges shall include: engine oil pressure, oil filter differ-ential, fuel pressure, and jacket water temperature. Aspart of the engine control/safety system the engine andrelated components shall be monitored and providedwith gauges or safety shutdowns to protect against anysystem failures. The safety shutoffs shall be low oilpressure, high water temperature, low water level andoverspeed.

Isolation Mounting

The unit shall be provided with vibration isolation mountsfor both the driveline and shell assemblies. These leveladjusting, spring isolators shall be designed for one inchdeflection. The driveline shall be balanced on four vibra-tion isolator assemblies using a three point mountingsystem. The isolator assemblies shall be installed be-tween the driveline base and the mounting surface andshall have a waffle or ribbed pad on their bottom surface.The shell package shall be provided with four vibrationisolation mounts. The vibration isolator assemblies shallbe installed under the tube sheets and shall be providewith non-skid pads.

Testing

Prototype Testing - The system manufacturer must beable to certify that the engine, compressor, speed in-creaser, and controls have been tested as completesystems of representative engineering models (not onequipment sold).

Specific prototype tests shall include:

ENGINE:

Performance (part load, full load)Oil ConsumptionFuel ConsumptionExhaust EmissionsNoise Levels (mechanical and exhaust)Startability (cold and hot ambients)Piston, Ring, and Liner Wear RatesPiston Structural IntegrityLubrication System EvaluationCooling System EvaluationValve Train Overspeed Qualification

Deep Thermal Cycle EnduranceField Endurance

GAS ENGINE COMPRESSOR DRIVELINE:

Mechanical CompatibilityStructural IntegrityMounting EvaluationWiring CompatibilityControl Panel FunctionalityLinear Vibration MeasurementTorsional Vibration Analysis Part Load Performance Safety Shutdowns and AlarmsStart-Stop Evaluations

Production Testing - The refrigerant compressor shallbe air run tested at the compressor manufacturers testfacility prior to mounting on the driveline assembly. Theengine shall be run tested at full and part loads prior toassembly of the driveline. The driveline package shall berun tested after assembly at conditions that fully load theengine at the engine manufacturer’s test facility. Thetesting of the assembled driveline shall insure smooth,defect free operation. Field or assembly shop tests arenot acceptable. A certified report of these tests shall beavailable when requested at the time of chiller order.

Start-up and Operator Training

Factory trained field service representatives shall super-vise the final leak testing, charging and the initial start-up.The complete installation shall be checked for proceduraland operational compliance by a factory trained servicerepresentative from the chiller manufacturer. The chillermanufacturer shall retain factory trained service repre-sentatives of the engine manufacturer to provide start upservice and operator instruction for the gas engine.

Warranty and Service

The manufacturer’s standard warranty shall be for aperiod of one year from the date of start-up or eighteenmonths from shipment, whichever occurs first. The war-ranty shall include parts and labor during this period.Additionally, the unit manufacturer shall provide, at noadditional cost to the owner, a complete one year servicecontract. The contract shall include all recommendedservice and preventative maintenance required by thechiller and engine manufacturer during the first year ofoperation or 3000 operating hours, whichever comes first.This service shall only be performed by factory trainedservice personnel. The chiller manufacturer shall have alocal direct service office that can provide factory trainedand authorized servicemen, the required stock of replace-ment parts, technical assistance, and warranty admini-stration. Engine maintenance shall only be performed bythe engine manufacturer’s local, factory trained, author-ized representative.

YORK INTERNATIONAL 31

Page 32: MILLENNIUM TM GAS-ENGINE-DRIVE CHILLERS 1,435 7,939 1.5 - 5 1,500 G3606 1,765 7,685 43 - 47 1,000 EVAPORATOR ... Gas-Engine-Driven Chiller, provides the ultimate in effi - ciency and

SI Metric Unit Conversion

MEASUREMENTMULTIPLY THISENGLISH VALUE BY

TO OBTAIN THISMETRIC VALUE

CAPACITY TONS REFRIGERANT EFFECT (ton) 3.516 KILOWATTS (kW)

POWERKILOWATTS (kW) NO CHANGE KILOWATTS (kW)

HORSEPOWER (hp) 0.7457 KILOWATTS (kW)FLOW RATE GALLONS / MINUTE (gpm) 0.0631 LITERS / SECOND (L/s)

LENGTHFEET (ft) 304.8 MILLIMETERS (mm)

INCHES (in) 25.4 MILLIMETERS (mm)WEIGHT POUNDS (lb) 0.4536 KILOGRAMS (kg)

VELOCITY FEET / SECOND (fps) 0.3048 METERS / SECOND (m/s)

PRESSURE DROPFEET OF WATER (ft) 2.989 KILOPASCALS (k Pa)

POUNDS / SQ. INCH (psi) 6.895 KILOPASCALS (k Pa)

Values provided in this manual are in the English inch-pound (I-P) system.The following factors can be used to convert from English to the most common SI Metric values.

INTEGRATED PART LOAD VALUE (IPLV)

In the English I-P system, IPLV is calculated by thefollowing formula. A full explanation is shown on page 3:

IPLV 1

or =

APLV 0.17 + 0.39 + 0.33 + 0.11

A B C D

Where:A = kW / ton at 100% LoadB = kW / ton at 75% LoadC = kW / ton at 50% LoadD = kW / ton at 25% Load

In SI Metric, the formula is:

IPLV or = 0.17A + 0.39B + 0.33C + 0.11D APLV

Where:A = COP at 100% LoadB = COP at 75% LoadC = COP at 50% Load D = COP at 25% Load

FOULING FACTOR

ENGLISH I-P(ft2 °F hr/Btu)

EQUIVALENT SI METRIC(m2 °C/W)

0.00025 0.000044

0.0005 0.000088

0.00075 0.000132

TEMPERATURE

To convert degrees Fahrenheit (°F) to degrees Celsius(°C), subtract 32° and multiply by 5/9 or 0.5556.

To convert a temperature range (i.e., 10°F or 12°Fchilled water range) from Fahrenheit to Celsius, multiplyby 5/9 or 0.5556.

EFFICIENCY

In the English I-P system, chiller efficiency is measuredin kW / ton:

kW / ton = kW input tons refrigerant effect

In the SI Metric system, chiller efficiency is measured inCoefficient of Performance (COP).

COP = kW refrigeration effect kW input

kW / ton and COP are related as follows:

kW / ton = 3.516 COP

COP = 3.516 kW / ton

P.O Box 1592, York, Pennsylvania USA 17405-1592Copyright © by York International Corporation 1996

Subject to change without notice. Printed in USAALL RIGHTS RESERVED