minilink pd 5 technical guide - az3controls.com
TRANSCRIPT
MiniLink PD 5 Technical Guide
AZ 3 MiniLink PD 5 Technical Guide2
MiniLink PD 5 3General 3Features 3
Considerations 4Environmental Requirements 4Mounting 4
Wiring 5Address Setting 6Network Loop amp Local Loop Baud Rate Settings 7System Confi gurations 8
CV Single Loop System 8CV Multiple Loop System 8VAVZone Single Loop System 8VAVZone Multiple Loop System 8VAVZone amp CV Single Loop System 9VAVZone amp CV Multiple Loop System 9
CV System Diagrams 10VAVZone System Diagrams 11VAVZone amp CV Units System Diagrams 12
Table Of Contents
AAON Inc500 NW River Park Drive Parkville MO 64152Factory Technical Support Phone 918-382-6450Controls Support Phone 866-918-1100E-mail controls-orderentryaaoncomVisit our web site at wwwaz2controlscomCopyright October 2020 AAON Inc AAON PN G075300
AAON is a registered trademark of AAON Inc Tulsa OK BACnetreg is a registered trademark of ASHRAE Inc Atlanta GAWindowsreg is registered trademark of Microsoftreg Corporation USAAAONreg does not assume any responsibility for errors or omissions in this document This document is subject to change without notice
wwwaz2controlscom
AZ 3 MiniLink PD 5 Technical Guide 3
General
The ASM02454 MiniLink PD 5 is a RS-485 communications device that is used to integrate multiple local RS-485 commu-nication loops into a RS-485 network communications system See Figure 1 page 4 for dimensions
The MiniLink PD 5 is required on the Auto-Zone 3 (AZ 3) Control System to separate local loops Up to 60 MiniLink loops can be on a system
Local loop terminals on the MiniLink PD 5 are designed to connect to controllers that are daisy-chained together on its local RS-485 communications loop
Network loop terminals on the MiniLink PD 5 are used to daisy-chain multiple MiniLinks back to a CommLink 5 to form a network RS-485 communications loop This provides for a fully networked RS-485 communications system
The MiniLink PD 5 is required for VAV systems to allow infor-mation to be shared between the AZ 3 VAV unit controller and the AZ 3 VAVZone BACnetreg Controllers It is also required for zoning systems to facilitate voting of the zones to determine the HVAC unitrsquos heating and cooling mode of operation and provides tenant-logging capabilities
MiniLink PD 5
Features
The MiniLink PD 5 utilizes token passing communication ar-chitecture The MiniLink PD 5 is designed to serve as the local communications loop master This means that it is responsible for sending a token to all the controllers on the local communi-cations loop
Network communications are RS-485 type operating at 19200 or 115200 baud Local communications are also RS-485 type and operate at 9600 or 57600 baud
The MiniLink PD 5 is factory default set to high speed Dip switches can be changed to low speed if required for your ap-plication See Page 7
Overview
AZ 3 MiniLink PD 5 Technical Guide4
Considerations
Figure 1 MiniLink PD 5 Dimensions
Environmental Requirements
The MiniLink PD 5 needs to be installed in an environment that can maintain a temperature range between -30degF and 150degF and a humidity range between 0 and 95 RH (non-condensing)
Mounting
The MiniLink PD 5 is housed in a plastic enclosure It is designed to be mounted by using the 3 mounting holes in the enclosure base It is important to mount the device in a location that is free from extreme high or low temperatures moisture dust and dirt Be careful not to damage the electronic components when mounting the MiniLink PD 5 The printed circuit board plastic cover has a UL94V0 fl ame rating
Installation
564505
207
414
596
066
273
029
496
149
AZ 3 MiniLink PD 5 Technical Guide 5
Figure 2 MiniLink PD 5 Wiring
WiringInstallation
RR SH
SH
T
T
Connect Local LoopTerminals To T SH amp RLocal Loop Terminals OnFirst Controller On LocalLoop Be Sure To Wire T ToT SH To SH amp R To R
NOTE This Network Wiring Is NotRequired On Single Loop SystemsWithout A CommLink When ACommLink Is Used On Single LoopSystems Connect Network LoopWire Terminals To The CommLink
GN
D
18-3
0 V
AC
Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring
CAUTION
24 VAC TransformerSize For 6 VA Max Load
Some Installers Like To Use One Large 24 VAC TransformerTo Power Several Devices This Is Allowable As Long AsPolarity Is Maintained To Each Device On The TransformerCircuit
Using Separate Transformers Also Allows Redundancy InCase Of A Transformer Failure Instead Of Having 8 DevicesInoperative Because Of A Malfunctioning Transformer YouHave Only 1 Device Off Line
WARNING If Polarity Is Not Maintained Severe DamageTo The Devices May Result AAON Recommends Using ASeparate Transformer For Each Device In Order ToEliminate The Potential For Damaging Devices Due ToIncorrect Polarity
NOTE All Communication Wiring Must Be Plenum-rated Minimum18-gauge 2-conductor Twisted Pair With Shield Wire AAON CanSupply Communication Wire That Meets This Specification And IsColor Coded For The Network Or Local Loop The Local Loop Wire(G038140) Is Color Coded With Green Candy Striping And ComesOn A 1000 Ft Spool The Network Loop Wire (G038150) Is ColorCoded With Red Candy Striping And Comes On A 500 Ft Spool IfDesired 18-Gauge Minimum Belden 82760 Or EquivalentCommunications Wire May Also Be Used For Network Or LocalLoop Wiring
Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring
CAUTION
MINILINK PD 5
PD
DR
V
LO
OP
DR
V
NET DRV
PIC32 MLPDYS102398 REV 3
NETWORK
LOCAL
PD COMM
POWER
COMMML
PD
MADE IN USA
SE
RIA
L
C22
C23
C30
C37
C40
J1
J3
R1
R2
R3
R4 R20
R21
R22
R23R24
R25
R26
R27
R31
PDSTAT1
PDSTAT2
TB1
TB2
U8
U10
U12
D4
J6
J7
J8
R43
R44
R46
C33
T
SH
R
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1uF
1uF
1uF
1uF
1002
1002
T
SH
R
C24
COMM
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
On Multiple Loop Systems ConnectCable To Next MiniLinkrsquos NetworkComm Connector Or ConnectNetwork Loop Wire Terminals ToCommLink And Daisy-Chain AllMiniLink Network Terminals TogetherBe Sure To Wire T To T SH To SH ampR To R
AZ 3 MiniLink PD 5 Technical Guide6
Address Setting
Figure 3 Address Dipswitch Setting
NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
Address Dipswitch Setting
MINILINK PD 5
16
32NET
LOOP
8421
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
Address 1
ADD
ADD ADD
The Address For Each MLPD5Must Be Unique To The Other
On The Network Loop And Be Between 1 and 60MLPD5s
16
32NET
LOOP
8421
Address 13
ADD
Installation
AZ 3 MiniLink PD 5 Technical Guide 7
Network Loop amp Local Loop Baud Rate Settings
Figure 4 Baud Rate Dipswitch Setting
Installation
AZ 3 MiniLink PD 5 Technical Guide8
System Confi gurationsSystem Architecture
CV Single Loop System
The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout
CV Multiple Loop System
If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout
VAVZone Single Loop System
If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout
VAVZone Multiple Loop System
If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the
AZ 3 MiniLink PD 5 Technical Guide 9
System Confi gurationsSystem Architecture
other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout
VAVZone amp CV Single Loop System
If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg
Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout
VAVZone amp CV Multiple Loop System
If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide10
CV System DiagramsSystem Architecture
Figure 5 Typical CV Single Loop System Layout
Figure 6 Typical CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 11
VAVZone System DiagramsSystem Architecture
Figure 7 Typical VAVZone Single Loop System Layout
Figure 8 Typical VAVZone Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide2
MiniLink PD 5 3General 3Features 3
Considerations 4Environmental Requirements 4Mounting 4
Wiring 5Address Setting 6Network Loop amp Local Loop Baud Rate Settings 7System Confi gurations 8
CV Single Loop System 8CV Multiple Loop System 8VAVZone Single Loop System 8VAVZone Multiple Loop System 8VAVZone amp CV Single Loop System 9VAVZone amp CV Multiple Loop System 9
CV System Diagrams 10VAVZone System Diagrams 11VAVZone amp CV Units System Diagrams 12
Table Of Contents
AAON Inc500 NW River Park Drive Parkville MO 64152Factory Technical Support Phone 918-382-6450Controls Support Phone 866-918-1100E-mail controls-orderentryaaoncomVisit our web site at wwwaz2controlscomCopyright October 2020 AAON Inc AAON PN G075300
AAON is a registered trademark of AAON Inc Tulsa OK BACnetreg is a registered trademark of ASHRAE Inc Atlanta GAWindowsreg is registered trademark of Microsoftreg Corporation USAAAONreg does not assume any responsibility for errors or omissions in this document This document is subject to change without notice
wwwaz2controlscom
AZ 3 MiniLink PD 5 Technical Guide 3
General
The ASM02454 MiniLink PD 5 is a RS-485 communications device that is used to integrate multiple local RS-485 commu-nication loops into a RS-485 network communications system See Figure 1 page 4 for dimensions
The MiniLink PD 5 is required on the Auto-Zone 3 (AZ 3) Control System to separate local loops Up to 60 MiniLink loops can be on a system
Local loop terminals on the MiniLink PD 5 are designed to connect to controllers that are daisy-chained together on its local RS-485 communications loop
Network loop terminals on the MiniLink PD 5 are used to daisy-chain multiple MiniLinks back to a CommLink 5 to form a network RS-485 communications loop This provides for a fully networked RS-485 communications system
The MiniLink PD 5 is required for VAV systems to allow infor-mation to be shared between the AZ 3 VAV unit controller and the AZ 3 VAVZone BACnetreg Controllers It is also required for zoning systems to facilitate voting of the zones to determine the HVAC unitrsquos heating and cooling mode of operation and provides tenant-logging capabilities
MiniLink PD 5
Features
The MiniLink PD 5 utilizes token passing communication ar-chitecture The MiniLink PD 5 is designed to serve as the local communications loop master This means that it is responsible for sending a token to all the controllers on the local communi-cations loop
Network communications are RS-485 type operating at 19200 or 115200 baud Local communications are also RS-485 type and operate at 9600 or 57600 baud
The MiniLink PD 5 is factory default set to high speed Dip switches can be changed to low speed if required for your ap-plication See Page 7
Overview
AZ 3 MiniLink PD 5 Technical Guide4
Considerations
Figure 1 MiniLink PD 5 Dimensions
Environmental Requirements
The MiniLink PD 5 needs to be installed in an environment that can maintain a temperature range between -30degF and 150degF and a humidity range between 0 and 95 RH (non-condensing)
Mounting
The MiniLink PD 5 is housed in a plastic enclosure It is designed to be mounted by using the 3 mounting holes in the enclosure base It is important to mount the device in a location that is free from extreme high or low temperatures moisture dust and dirt Be careful not to damage the electronic components when mounting the MiniLink PD 5 The printed circuit board plastic cover has a UL94V0 fl ame rating
Installation
564505
207
414
596
066
273
029
496
149
AZ 3 MiniLink PD 5 Technical Guide 5
Figure 2 MiniLink PD 5 Wiring
WiringInstallation
RR SH
SH
T
T
Connect Local LoopTerminals To T SH amp RLocal Loop Terminals OnFirst Controller On LocalLoop Be Sure To Wire T ToT SH To SH amp R To R
NOTE This Network Wiring Is NotRequired On Single Loop SystemsWithout A CommLink When ACommLink Is Used On Single LoopSystems Connect Network LoopWire Terminals To The CommLink
GN
D
18-3
0 V
AC
Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring
CAUTION
24 VAC TransformerSize For 6 VA Max Load
Some Installers Like To Use One Large 24 VAC TransformerTo Power Several Devices This Is Allowable As Long AsPolarity Is Maintained To Each Device On The TransformerCircuit
Using Separate Transformers Also Allows Redundancy InCase Of A Transformer Failure Instead Of Having 8 DevicesInoperative Because Of A Malfunctioning Transformer YouHave Only 1 Device Off Line
WARNING If Polarity Is Not Maintained Severe DamageTo The Devices May Result AAON Recommends Using ASeparate Transformer For Each Device In Order ToEliminate The Potential For Damaging Devices Due ToIncorrect Polarity
NOTE All Communication Wiring Must Be Plenum-rated Minimum18-gauge 2-conductor Twisted Pair With Shield Wire AAON CanSupply Communication Wire That Meets This Specification And IsColor Coded For The Network Or Local Loop The Local Loop Wire(G038140) Is Color Coded With Green Candy Striping And ComesOn A 1000 Ft Spool The Network Loop Wire (G038150) Is ColorCoded With Red Candy Striping And Comes On A 500 Ft Spool IfDesired 18-Gauge Minimum Belden 82760 Or EquivalentCommunications Wire May Also Be Used For Network Or LocalLoop Wiring
Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring
CAUTION
MINILINK PD 5
PD
DR
V
LO
OP
DR
V
NET DRV
PIC32 MLPDYS102398 REV 3
NETWORK
LOCAL
PD COMM
POWER
COMMML
PD
MADE IN USA
SE
RIA
L
C22
C23
C30
C37
C40
J1
J3
R1
R2
R3
R4 R20
R21
R22
R23R24
R25
R26
R27
R31
PDSTAT1
PDSTAT2
TB1
TB2
U8
U10
U12
D4
J6
J7
J8
R43
R44
R46
C33
T
SH
R
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1uF
1uF
1uF
1uF
1002
1002
T
SH
R
C24
COMM
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
On Multiple Loop Systems ConnectCable To Next MiniLinkrsquos NetworkComm Connector Or ConnectNetwork Loop Wire Terminals ToCommLink And Daisy-Chain AllMiniLink Network Terminals TogetherBe Sure To Wire T To T SH To SH ampR To R
AZ 3 MiniLink PD 5 Technical Guide6
Address Setting
Figure 3 Address Dipswitch Setting
NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
Address Dipswitch Setting
MINILINK PD 5
16
32NET
LOOP
8421
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
Address 1
ADD
ADD ADD
The Address For Each MLPD5Must Be Unique To The Other
On The Network Loop And Be Between 1 and 60MLPD5s
16
32NET
LOOP
8421
Address 13
ADD
Installation
AZ 3 MiniLink PD 5 Technical Guide 7
Network Loop amp Local Loop Baud Rate Settings
Figure 4 Baud Rate Dipswitch Setting
Installation
AZ 3 MiniLink PD 5 Technical Guide8
System Confi gurationsSystem Architecture
CV Single Loop System
The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout
CV Multiple Loop System
If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout
VAVZone Single Loop System
If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout
VAVZone Multiple Loop System
If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the
AZ 3 MiniLink PD 5 Technical Guide 9
System Confi gurationsSystem Architecture
other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout
VAVZone amp CV Single Loop System
If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg
Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout
VAVZone amp CV Multiple Loop System
If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide10
CV System DiagramsSystem Architecture
Figure 5 Typical CV Single Loop System Layout
Figure 6 Typical CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 11
VAVZone System DiagramsSystem Architecture
Figure 7 Typical VAVZone Single Loop System Layout
Figure 8 Typical VAVZone Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide 3
General
The ASM02454 MiniLink PD 5 is a RS-485 communications device that is used to integrate multiple local RS-485 commu-nication loops into a RS-485 network communications system See Figure 1 page 4 for dimensions
The MiniLink PD 5 is required on the Auto-Zone 3 (AZ 3) Control System to separate local loops Up to 60 MiniLink loops can be on a system
Local loop terminals on the MiniLink PD 5 are designed to connect to controllers that are daisy-chained together on its local RS-485 communications loop
Network loop terminals on the MiniLink PD 5 are used to daisy-chain multiple MiniLinks back to a CommLink 5 to form a network RS-485 communications loop This provides for a fully networked RS-485 communications system
The MiniLink PD 5 is required for VAV systems to allow infor-mation to be shared between the AZ 3 VAV unit controller and the AZ 3 VAVZone BACnetreg Controllers It is also required for zoning systems to facilitate voting of the zones to determine the HVAC unitrsquos heating and cooling mode of operation and provides tenant-logging capabilities
MiniLink PD 5
Features
The MiniLink PD 5 utilizes token passing communication ar-chitecture The MiniLink PD 5 is designed to serve as the local communications loop master This means that it is responsible for sending a token to all the controllers on the local communi-cations loop
Network communications are RS-485 type operating at 19200 or 115200 baud Local communications are also RS-485 type and operate at 9600 or 57600 baud
The MiniLink PD 5 is factory default set to high speed Dip switches can be changed to low speed if required for your ap-plication See Page 7
Overview
AZ 3 MiniLink PD 5 Technical Guide4
Considerations
Figure 1 MiniLink PD 5 Dimensions
Environmental Requirements
The MiniLink PD 5 needs to be installed in an environment that can maintain a temperature range between -30degF and 150degF and a humidity range between 0 and 95 RH (non-condensing)
Mounting
The MiniLink PD 5 is housed in a plastic enclosure It is designed to be mounted by using the 3 mounting holes in the enclosure base It is important to mount the device in a location that is free from extreme high or low temperatures moisture dust and dirt Be careful not to damage the electronic components when mounting the MiniLink PD 5 The printed circuit board plastic cover has a UL94V0 fl ame rating
Installation
564505
207
414
596
066
273
029
496
149
AZ 3 MiniLink PD 5 Technical Guide 5
Figure 2 MiniLink PD 5 Wiring
WiringInstallation
RR SH
SH
T
T
Connect Local LoopTerminals To T SH amp RLocal Loop Terminals OnFirst Controller On LocalLoop Be Sure To Wire T ToT SH To SH amp R To R
NOTE This Network Wiring Is NotRequired On Single Loop SystemsWithout A CommLink When ACommLink Is Used On Single LoopSystems Connect Network LoopWire Terminals To The CommLink
GN
D
18-3
0 V
AC
Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring
CAUTION
24 VAC TransformerSize For 6 VA Max Load
Some Installers Like To Use One Large 24 VAC TransformerTo Power Several Devices This Is Allowable As Long AsPolarity Is Maintained To Each Device On The TransformerCircuit
Using Separate Transformers Also Allows Redundancy InCase Of A Transformer Failure Instead Of Having 8 DevicesInoperative Because Of A Malfunctioning Transformer YouHave Only 1 Device Off Line
WARNING If Polarity Is Not Maintained Severe DamageTo The Devices May Result AAON Recommends Using ASeparate Transformer For Each Device In Order ToEliminate The Potential For Damaging Devices Due ToIncorrect Polarity
NOTE All Communication Wiring Must Be Plenum-rated Minimum18-gauge 2-conductor Twisted Pair With Shield Wire AAON CanSupply Communication Wire That Meets This Specification And IsColor Coded For The Network Or Local Loop The Local Loop Wire(G038140) Is Color Coded With Green Candy Striping And ComesOn A 1000 Ft Spool The Network Loop Wire (G038150) Is ColorCoded With Red Candy Striping And Comes On A 500 Ft Spool IfDesired 18-Gauge Minimum Belden 82760 Or EquivalentCommunications Wire May Also Be Used For Network Or LocalLoop Wiring
Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring
CAUTION
MINILINK PD 5
PD
DR
V
LO
OP
DR
V
NET DRV
PIC32 MLPDYS102398 REV 3
NETWORK
LOCAL
PD COMM
POWER
COMMML
PD
MADE IN USA
SE
RIA
L
C22
C23
C30
C37
C40
J1
J3
R1
R2
R3
R4 R20
R21
R22
R23R24
R25
R26
R27
R31
PDSTAT1
PDSTAT2
TB1
TB2
U8
U10
U12
D4
J6
J7
J8
R43
R44
R46
C33
T
SH
R
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1uF
1uF
1uF
1uF
1002
1002
T
SH
R
C24
COMM
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
On Multiple Loop Systems ConnectCable To Next MiniLinkrsquos NetworkComm Connector Or ConnectNetwork Loop Wire Terminals ToCommLink And Daisy-Chain AllMiniLink Network Terminals TogetherBe Sure To Wire T To T SH To SH ampR To R
AZ 3 MiniLink PD 5 Technical Guide6
Address Setting
Figure 3 Address Dipswitch Setting
NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
Address Dipswitch Setting
MINILINK PD 5
16
32NET
LOOP
8421
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
Address 1
ADD
ADD ADD
The Address For Each MLPD5Must Be Unique To The Other
On The Network Loop And Be Between 1 and 60MLPD5s
16
32NET
LOOP
8421
Address 13
ADD
Installation
AZ 3 MiniLink PD 5 Technical Guide 7
Network Loop amp Local Loop Baud Rate Settings
Figure 4 Baud Rate Dipswitch Setting
Installation
AZ 3 MiniLink PD 5 Technical Guide8
System Confi gurationsSystem Architecture
CV Single Loop System
The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout
CV Multiple Loop System
If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout
VAVZone Single Loop System
If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout
VAVZone Multiple Loop System
If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the
AZ 3 MiniLink PD 5 Technical Guide 9
System Confi gurationsSystem Architecture
other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout
VAVZone amp CV Single Loop System
If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg
Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout
VAVZone amp CV Multiple Loop System
If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide10
CV System DiagramsSystem Architecture
Figure 5 Typical CV Single Loop System Layout
Figure 6 Typical CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 11
VAVZone System DiagramsSystem Architecture
Figure 7 Typical VAVZone Single Loop System Layout
Figure 8 Typical VAVZone Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide4
Considerations
Figure 1 MiniLink PD 5 Dimensions
Environmental Requirements
The MiniLink PD 5 needs to be installed in an environment that can maintain a temperature range between -30degF and 150degF and a humidity range between 0 and 95 RH (non-condensing)
Mounting
The MiniLink PD 5 is housed in a plastic enclosure It is designed to be mounted by using the 3 mounting holes in the enclosure base It is important to mount the device in a location that is free from extreme high or low temperatures moisture dust and dirt Be careful not to damage the electronic components when mounting the MiniLink PD 5 The printed circuit board plastic cover has a UL94V0 fl ame rating
Installation
564505
207
414
596
066
273
029
496
149
AZ 3 MiniLink PD 5 Technical Guide 5
Figure 2 MiniLink PD 5 Wiring
WiringInstallation
RR SH
SH
T
T
Connect Local LoopTerminals To T SH amp RLocal Loop Terminals OnFirst Controller On LocalLoop Be Sure To Wire T ToT SH To SH amp R To R
NOTE This Network Wiring Is NotRequired On Single Loop SystemsWithout A CommLink When ACommLink Is Used On Single LoopSystems Connect Network LoopWire Terminals To The CommLink
GN
D
18-3
0 V
AC
Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring
CAUTION
24 VAC TransformerSize For 6 VA Max Load
Some Installers Like To Use One Large 24 VAC TransformerTo Power Several Devices This Is Allowable As Long AsPolarity Is Maintained To Each Device On The TransformerCircuit
Using Separate Transformers Also Allows Redundancy InCase Of A Transformer Failure Instead Of Having 8 DevicesInoperative Because Of A Malfunctioning Transformer YouHave Only 1 Device Off Line
WARNING If Polarity Is Not Maintained Severe DamageTo The Devices May Result AAON Recommends Using ASeparate Transformer For Each Device In Order ToEliminate The Potential For Damaging Devices Due ToIncorrect Polarity
NOTE All Communication Wiring Must Be Plenum-rated Minimum18-gauge 2-conductor Twisted Pair With Shield Wire AAON CanSupply Communication Wire That Meets This Specification And IsColor Coded For The Network Or Local Loop The Local Loop Wire(G038140) Is Color Coded With Green Candy Striping And ComesOn A 1000 Ft Spool The Network Loop Wire (G038150) Is ColorCoded With Red Candy Striping And Comes On A 500 Ft Spool IfDesired 18-Gauge Minimum Belden 82760 Or EquivalentCommunications Wire May Also Be Used For Network Or LocalLoop Wiring
Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring
CAUTION
MINILINK PD 5
PD
DR
V
LO
OP
DR
V
NET DRV
PIC32 MLPDYS102398 REV 3
NETWORK
LOCAL
PD COMM
POWER
COMMML
PD
MADE IN USA
SE
RIA
L
C22
C23
C30
C37
C40
J1
J3
R1
R2
R3
R4 R20
R21
R22
R23R24
R25
R26
R27
R31
PDSTAT1
PDSTAT2
TB1
TB2
U8
U10
U12
D4
J6
J7
J8
R43
R44
R46
C33
T
SH
R
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1uF
1uF
1uF
1uF
1002
1002
T
SH
R
C24
COMM
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
On Multiple Loop Systems ConnectCable To Next MiniLinkrsquos NetworkComm Connector Or ConnectNetwork Loop Wire Terminals ToCommLink And Daisy-Chain AllMiniLink Network Terminals TogetherBe Sure To Wire T To T SH To SH ampR To R
AZ 3 MiniLink PD 5 Technical Guide6
Address Setting
Figure 3 Address Dipswitch Setting
NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
Address Dipswitch Setting
MINILINK PD 5
16
32NET
LOOP
8421
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
Address 1
ADD
ADD ADD
The Address For Each MLPD5Must Be Unique To The Other
On The Network Loop And Be Between 1 and 60MLPD5s
16
32NET
LOOP
8421
Address 13
ADD
Installation
AZ 3 MiniLink PD 5 Technical Guide 7
Network Loop amp Local Loop Baud Rate Settings
Figure 4 Baud Rate Dipswitch Setting
Installation
AZ 3 MiniLink PD 5 Technical Guide8
System Confi gurationsSystem Architecture
CV Single Loop System
The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout
CV Multiple Loop System
If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout
VAVZone Single Loop System
If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout
VAVZone Multiple Loop System
If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the
AZ 3 MiniLink PD 5 Technical Guide 9
System Confi gurationsSystem Architecture
other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout
VAVZone amp CV Single Loop System
If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg
Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout
VAVZone amp CV Multiple Loop System
If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide10
CV System DiagramsSystem Architecture
Figure 5 Typical CV Single Loop System Layout
Figure 6 Typical CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 11
VAVZone System DiagramsSystem Architecture
Figure 7 Typical VAVZone Single Loop System Layout
Figure 8 Typical VAVZone Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide 5
Figure 2 MiniLink PD 5 Wiring
WiringInstallation
RR SH
SH
T
T
Connect Local LoopTerminals To T SH amp RLocal Loop Terminals OnFirst Controller On LocalLoop Be Sure To Wire T ToT SH To SH amp R To R
NOTE This Network Wiring Is NotRequired On Single Loop SystemsWithout A CommLink When ACommLink Is Used On Single LoopSystems Connect Network LoopWire Terminals To The CommLink
GN
D
18-3
0 V
AC
Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring
CAUTION
24 VAC TransformerSize For 6 VA Max Load
Some Installers Like To Use One Large 24 VAC TransformerTo Power Several Devices This Is Allowable As Long AsPolarity Is Maintained To Each Device On The TransformerCircuit
Using Separate Transformers Also Allows Redundancy InCase Of A Transformer Failure Instead Of Having 8 DevicesInoperative Because Of A Malfunctioning Transformer YouHave Only 1 Device Off Line
WARNING If Polarity Is Not Maintained Severe DamageTo The Devices May Result AAON Recommends Using ASeparate Transformer For Each Device In Order ToEliminate The Potential For Damaging Devices Due ToIncorrect Polarity
NOTE All Communication Wiring Must Be Plenum-rated Minimum18-gauge 2-conductor Twisted Pair With Shield Wire AAON CanSupply Communication Wire That Meets This Specification And IsColor Coded For The Network Or Local Loop The Local Loop Wire(G038140) Is Color Coded With Green Candy Striping And ComesOn A 1000 Ft Spool The Network Loop Wire (G038150) Is ColorCoded With Red Candy Striping And Comes On A 500 Ft Spool IfDesired 18-Gauge Minimum Belden 82760 Or EquivalentCommunications Wire May Also Be Used For Network Or LocalLoop Wiring
Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring
CAUTION
MINILINK PD 5
PD
DR
V
LO
OP
DR
V
NET DRV
PIC32 MLPDYS102398 REV 3
NETWORK
LOCAL
PD COMM
POWER
COMMML
PD
MADE IN USA
SE
RIA
L
C22
C23
C30
C37
C40
J1
J3
R1
R2
R3
R4 R20
R21
R22
R23R24
R25
R26
R27
R31
PDSTAT1
PDSTAT2
TB1
TB2
U8
U10
U12
D4
J6
J7
J8
R43
R44
R46
C33
T
SH
R
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1002
1uF
1uF
1uF
1uF
1002
1002
T
SH
R
C24
COMM
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
On Multiple Loop Systems ConnectCable To Next MiniLinkrsquos NetworkComm Connector Or ConnectNetwork Loop Wire Terminals ToCommLink And Daisy-Chain AllMiniLink Network Terminals TogetherBe Sure To Wire T To T SH To SH ampR To R
AZ 3 MiniLink PD 5 Technical Guide6
Address Setting
Figure 3 Address Dipswitch Setting
NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
Address Dipswitch Setting
MINILINK PD 5
16
32NET
LOOP
8421
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
Address 1
ADD
ADD ADD
The Address For Each MLPD5Must Be Unique To The Other
On The Network Loop And Be Between 1 and 60MLPD5s
16
32NET
LOOP
8421
Address 13
ADD
Installation
AZ 3 MiniLink PD 5 Technical Guide 7
Network Loop amp Local Loop Baud Rate Settings
Figure 4 Baud Rate Dipswitch Setting
Installation
AZ 3 MiniLink PD 5 Technical Guide8
System Confi gurationsSystem Architecture
CV Single Loop System
The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout
CV Multiple Loop System
If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout
VAVZone Single Loop System
If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout
VAVZone Multiple Loop System
If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the
AZ 3 MiniLink PD 5 Technical Guide 9
System Confi gurationsSystem Architecture
other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout
VAVZone amp CV Single Loop System
If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg
Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout
VAVZone amp CV Multiple Loop System
If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide10
CV System DiagramsSystem Architecture
Figure 5 Typical CV Single Loop System Layout
Figure 6 Typical CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 11
VAVZone System DiagramsSystem Architecture
Figure 7 Typical VAVZone Single Loop System Layout
Figure 8 Typical VAVZone Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide6
Address Setting
Figure 3 Address Dipswitch Setting
NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
Address Dipswitch Setting
MINILINK PD 5
16
32NET
LOOP
8421
Address Switch Shown IsSet For Address 1
Address Switch Shown IsSet For Address 13
ControllerAddress Switch
Address 1
ADD
ADD ADD
The Address For Each MLPD5Must Be Unique To The Other
On The Network Loop And Be Between 1 and 60MLPD5s
16
32NET
LOOP
8421
Address 13
ADD
Installation
AZ 3 MiniLink PD 5 Technical Guide 7
Network Loop amp Local Loop Baud Rate Settings
Figure 4 Baud Rate Dipswitch Setting
Installation
AZ 3 MiniLink PD 5 Technical Guide8
System Confi gurationsSystem Architecture
CV Single Loop System
The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout
CV Multiple Loop System
If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout
VAVZone Single Loop System
If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout
VAVZone Multiple Loop System
If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the
AZ 3 MiniLink PD 5 Technical Guide 9
System Confi gurationsSystem Architecture
other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout
VAVZone amp CV Single Loop System
If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg
Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout
VAVZone amp CV Multiple Loop System
If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide10
CV System DiagramsSystem Architecture
Figure 5 Typical CV Single Loop System Layout
Figure 6 Typical CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 11
VAVZone System DiagramsSystem Architecture
Figure 7 Typical VAVZone Single Loop System Layout
Figure 8 Typical VAVZone Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide 7
Network Loop amp Local Loop Baud Rate Settings
Figure 4 Baud Rate Dipswitch Setting
Installation
AZ 3 MiniLink PD 5 Technical Guide8
System Confi gurationsSystem Architecture
CV Single Loop System
The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout
CV Multiple Loop System
If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout
VAVZone Single Loop System
If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout
VAVZone Multiple Loop System
If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the
AZ 3 MiniLink PD 5 Technical Guide 9
System Confi gurationsSystem Architecture
other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout
VAVZone amp CV Single Loop System
If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg
Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout
VAVZone amp CV Multiple Loop System
If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide10
CV System DiagramsSystem Architecture
Figure 5 Typical CV Single Loop System Layout
Figure 6 Typical CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 11
VAVZone System DiagramsSystem Architecture
Figure 7 Typical VAVZone Single Loop System Layout
Figure 8 Typical VAVZone Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide8
System Confi gurationsSystem Architecture
CV Single Loop System
The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout
CV Multiple Loop System
If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout
VAVZone Single Loop System
If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout
VAVZone Multiple Loop System
If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the
AZ 3 MiniLink PD 5 Technical Guide 9
System Confi gurationsSystem Architecture
other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout
VAVZone amp CV Single Loop System
If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg
Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout
VAVZone amp CV Multiple Loop System
If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide10
CV System DiagramsSystem Architecture
Figure 5 Typical CV Single Loop System Layout
Figure 6 Typical CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 11
VAVZone System DiagramsSystem Architecture
Figure 7 Typical VAVZone Single Loop System Layout
Figure 8 Typical VAVZone Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide 9
System Confi gurationsSystem Architecture
other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout
VAVZone amp CV Single Loop System
If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg
Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes
The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout
VAVZone amp CV Multiple Loop System
If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes
Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used
The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide10
CV System DiagramsSystem Architecture
Figure 5 Typical CV Single Loop System Layout
Figure 6 Typical CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 11
VAVZone System DiagramsSystem Architecture
Figure 7 Typical VAVZone Single Loop System Layout
Figure 8 Typical VAVZone Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide10
CV System DiagramsSystem Architecture
Figure 5 Typical CV Single Loop System Layout
Figure 6 Typical CV Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 11
VAVZone System DiagramsSystem Architecture
Figure 7 Typical VAVZone Single Loop System Layout
Figure 8 Typical VAVZone Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide 11
VAVZone System DiagramsSystem Architecture
Figure 7 Typical VAVZone Single Loop System Layout
Figure 8 Typical VAVZone Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide12
VAVZone amp CV Units System DiagramsSystem Architecture
Figure 9 Typical VAVZone amp CV Units Single Loop System Layout
Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AZ 3 MiniLink PD 5 Technical Guide 13
Notes
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative
AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100
AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved
Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904
AAON Factory Technical Support 918-382-6450techsupportaaoncom
AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM
central standard time
NOTE Before calling Technical Support please have the model and serial number of the unit available
PARTS For replacement parts please contact your local AAON Representative