minilink pd 5 technical guide - az3controls.com

14
MiniLink PD 5 Technical Guide

Upload: others

Post on 05-Apr-2022

32 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MiniLink PD 5 Technical Guide - az3controls.com

MiniLink PD 5 Technical Guide

AZ 3 MiniLink PD 5 Technical Guide2

MiniLink PD 5 3General 3Features 3

Considerations 4Environmental Requirements 4Mounting 4

Wiring 5Address Setting 6Network Loop amp Local Loop Baud Rate Settings 7System Confi gurations 8

CV Single Loop System 8CV Multiple Loop System 8VAVZone Single Loop System 8VAVZone Multiple Loop System 8VAVZone amp CV Single Loop System 9VAVZone amp CV Multiple Loop System 9

CV System Diagrams 10VAVZone System Diagrams 11VAVZone amp CV Units System Diagrams 12

Table Of Contents

AAON Inc500 NW River Park Drive Parkville MO 64152Factory Technical Support Phone 918-382-6450Controls Support Phone 866-918-1100E-mail controls-orderentryaaoncomVisit our web site at wwwaz2controlscomCopyright October 2020 AAON Inc AAON PN G075300

AAON is a registered trademark of AAON Inc Tulsa OK BACnetreg is a registered trademark of ASHRAE Inc Atlanta GAWindowsreg is registered trademark of Microsoftreg Corporation USAAAONreg does not assume any responsibility for errors or omissions in this document This document is subject to change without notice

wwwaz2controlscom

AZ 3 MiniLink PD 5 Technical Guide 3

General

The ASM02454 MiniLink PD 5 is a RS-485 communications device that is used to integrate multiple local RS-485 commu-nication loops into a RS-485 network communications system See Figure 1 page 4 for dimensions

The MiniLink PD 5 is required on the Auto-Zone 3 (AZ 3) Control System to separate local loops Up to 60 MiniLink loops can be on a system

Local loop terminals on the MiniLink PD 5 are designed to connect to controllers that are daisy-chained together on its local RS-485 communications loop

Network loop terminals on the MiniLink PD 5 are used to daisy-chain multiple MiniLinks back to a CommLink 5 to form a network RS-485 communications loop This provides for a fully networked RS-485 communications system

The MiniLink PD 5 is required for VAV systems to allow infor-mation to be shared between the AZ 3 VAV unit controller and the AZ 3 VAVZone BACnetreg Controllers It is also required for zoning systems to facilitate voting of the zones to determine the HVAC unitrsquos heating and cooling mode of operation and provides tenant-logging capabilities

MiniLink PD 5

Features

The MiniLink PD 5 utilizes token passing communication ar-chitecture The MiniLink PD 5 is designed to serve as the local communications loop master This means that it is responsible for sending a token to all the controllers on the local communi-cations loop

Network communications are RS-485 type operating at 19200 or 115200 baud Local communications are also RS-485 type and operate at 9600 or 57600 baud

The MiniLink PD 5 is factory default set to high speed Dip switches can be changed to low speed if required for your ap-plication See Page 7

Overview

AZ 3 MiniLink PD 5 Technical Guide4

Considerations

Figure 1 MiniLink PD 5 Dimensions

Environmental Requirements

The MiniLink PD 5 needs to be installed in an environment that can maintain a temperature range between -30degF and 150degF and a humidity range between 0 and 95 RH (non-condensing)

Mounting

The MiniLink PD 5 is housed in a plastic enclosure It is designed to be mounted by using the 3 mounting holes in the enclosure base It is important to mount the device in a location that is free from extreme high or low temperatures moisture dust and dirt Be careful not to damage the electronic components when mounting the MiniLink PD 5 The printed circuit board plastic cover has a UL94V0 fl ame rating

Installation

564505

207

414

596

066

273

029

496

149

AZ 3 MiniLink PD 5 Technical Guide 5

Figure 2 MiniLink PD 5 Wiring

WiringInstallation

RR SH

SH

T

T

Connect Local LoopTerminals To T SH amp RLocal Loop Terminals OnFirst Controller On LocalLoop Be Sure To Wire T ToT SH To SH amp R To R

NOTE This Network Wiring Is NotRequired On Single Loop SystemsWithout A CommLink When ACommLink Is Used On Single LoopSystems Connect Network LoopWire Terminals To The CommLink

GN

D

18-3

0 V

AC

Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring

CAUTION

24 VAC TransformerSize For 6 VA Max Load

Some Installers Like To Use One Large 24 VAC TransformerTo Power Several Devices This Is Allowable As Long AsPolarity Is Maintained To Each Device On The TransformerCircuit

Using Separate Transformers Also Allows Redundancy InCase Of A Transformer Failure Instead Of Having 8 DevicesInoperative Because Of A Malfunctioning Transformer YouHave Only 1 Device Off Line

WARNING If Polarity Is Not Maintained Severe DamageTo The Devices May Result AAON Recommends Using ASeparate Transformer For Each Device In Order ToEliminate The Potential For Damaging Devices Due ToIncorrect Polarity

NOTE All Communication Wiring Must Be Plenum-rated Minimum18-gauge 2-conductor Twisted Pair With Shield Wire AAON CanSupply Communication Wire That Meets This Specification And IsColor Coded For The Network Or Local Loop The Local Loop Wire(G038140) Is Color Coded With Green Candy Striping And ComesOn A 1000 Ft Spool The Network Loop Wire (G038150) Is ColorCoded With Red Candy Striping And Comes On A 500 Ft Spool IfDesired 18-Gauge Minimum Belden 82760 Or EquivalentCommunications Wire May Also Be Used For Network Or LocalLoop Wiring

Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring

CAUTION

MINILINK PD 5

PD

DR

V

LO

OP

DR

V

NET DRV

PIC32 MLPDYS102398 REV 3

NETWORK

LOCAL

PD COMM

POWER

COMMML

PD

MADE IN USA

SE

RIA

L

C22

C23

C30

C37

C40

J1

J3

R1

R2

R3

R4 R20

R21

R22

R23R24

R25

R26

R27

R31

PDSTAT1

PDSTAT2

TB1

TB2

U8

U10

U12

D4

J6

J7

J8

R43

R44

R46

C33

T

SH

R

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1uF

1uF

1uF

1uF

1002

1002

T

SH

R

C24

COMM

1

2

4

8

16

32

SW2

OF

F

LOOP

NET

ON FOR

HI SPD

ADDRESS

On Multiple Loop Systems ConnectCable To Next MiniLinkrsquos NetworkComm Connector Or ConnectNetwork Loop Wire Terminals ToCommLink And Daisy-Chain AllMiniLink Network Terminals TogetherBe Sure To Wire T To T SH To SH ampR To R

AZ 3 MiniLink PD 5 Technical Guide6

Address Setting

Figure 3 Address Dipswitch Setting

NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect

1

2

4

8

16

32

SW2

OF

F

LOOP

NET

ON FOR

HI SPD

ADDRESS

Address Dipswitch Setting

MINILINK PD 5

16

32NET

LOOP

8421

Address Switch Shown IsSet For Address 1

Address Switch Shown IsSet For Address 13

ControllerAddress Switch

Address 1

ADD

ADD ADD

The Address For Each MLPD5Must Be Unique To The Other

On The Network Loop And Be Between 1 and 60MLPD5s

16

32NET

LOOP

8421

Address 13

ADD

Installation

AZ 3 MiniLink PD 5 Technical Guide 7

Network Loop amp Local Loop Baud Rate Settings

Figure 4 Baud Rate Dipswitch Setting

Installation

AZ 3 MiniLink PD 5 Technical Guide8

System Confi gurationsSystem Architecture

CV Single Loop System

The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout

CV Multiple Loop System

If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout

VAVZone Single Loop System

If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout

VAVZone Multiple Loop System

If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the

AZ 3 MiniLink PD 5 Technical Guide 9

System Confi gurationsSystem Architecture

other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout

VAVZone amp CV Single Loop System

If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg

Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout

VAVZone amp CV Multiple Loop System

If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide10

CV System DiagramsSystem Architecture

Figure 5 Typical CV Single Loop System Layout

Figure 6 Typical CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 11

VAVZone System DiagramsSystem Architecture

Figure 7 Typical VAVZone Single Loop System Layout

Figure 8 Typical VAVZone Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 2: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide2

MiniLink PD 5 3General 3Features 3

Considerations 4Environmental Requirements 4Mounting 4

Wiring 5Address Setting 6Network Loop amp Local Loop Baud Rate Settings 7System Confi gurations 8

CV Single Loop System 8CV Multiple Loop System 8VAVZone Single Loop System 8VAVZone Multiple Loop System 8VAVZone amp CV Single Loop System 9VAVZone amp CV Multiple Loop System 9

CV System Diagrams 10VAVZone System Diagrams 11VAVZone amp CV Units System Diagrams 12

Table Of Contents

AAON Inc500 NW River Park Drive Parkville MO 64152Factory Technical Support Phone 918-382-6450Controls Support Phone 866-918-1100E-mail controls-orderentryaaoncomVisit our web site at wwwaz2controlscomCopyright October 2020 AAON Inc AAON PN G075300

AAON is a registered trademark of AAON Inc Tulsa OK BACnetreg is a registered trademark of ASHRAE Inc Atlanta GAWindowsreg is registered trademark of Microsoftreg Corporation USAAAONreg does not assume any responsibility for errors or omissions in this document This document is subject to change without notice

wwwaz2controlscom

AZ 3 MiniLink PD 5 Technical Guide 3

General

The ASM02454 MiniLink PD 5 is a RS-485 communications device that is used to integrate multiple local RS-485 commu-nication loops into a RS-485 network communications system See Figure 1 page 4 for dimensions

The MiniLink PD 5 is required on the Auto-Zone 3 (AZ 3) Control System to separate local loops Up to 60 MiniLink loops can be on a system

Local loop terminals on the MiniLink PD 5 are designed to connect to controllers that are daisy-chained together on its local RS-485 communications loop

Network loop terminals on the MiniLink PD 5 are used to daisy-chain multiple MiniLinks back to a CommLink 5 to form a network RS-485 communications loop This provides for a fully networked RS-485 communications system

The MiniLink PD 5 is required for VAV systems to allow infor-mation to be shared between the AZ 3 VAV unit controller and the AZ 3 VAVZone BACnetreg Controllers It is also required for zoning systems to facilitate voting of the zones to determine the HVAC unitrsquos heating and cooling mode of operation and provides tenant-logging capabilities

MiniLink PD 5

Features

The MiniLink PD 5 utilizes token passing communication ar-chitecture The MiniLink PD 5 is designed to serve as the local communications loop master This means that it is responsible for sending a token to all the controllers on the local communi-cations loop

Network communications are RS-485 type operating at 19200 or 115200 baud Local communications are also RS-485 type and operate at 9600 or 57600 baud

The MiniLink PD 5 is factory default set to high speed Dip switches can be changed to low speed if required for your ap-plication See Page 7

Overview

AZ 3 MiniLink PD 5 Technical Guide4

Considerations

Figure 1 MiniLink PD 5 Dimensions

Environmental Requirements

The MiniLink PD 5 needs to be installed in an environment that can maintain a temperature range between -30degF and 150degF and a humidity range between 0 and 95 RH (non-condensing)

Mounting

The MiniLink PD 5 is housed in a plastic enclosure It is designed to be mounted by using the 3 mounting holes in the enclosure base It is important to mount the device in a location that is free from extreme high or low temperatures moisture dust and dirt Be careful not to damage the electronic components when mounting the MiniLink PD 5 The printed circuit board plastic cover has a UL94V0 fl ame rating

Installation

564505

207

414

596

066

273

029

496

149

AZ 3 MiniLink PD 5 Technical Guide 5

Figure 2 MiniLink PD 5 Wiring

WiringInstallation

RR SH

SH

T

T

Connect Local LoopTerminals To T SH amp RLocal Loop Terminals OnFirst Controller On LocalLoop Be Sure To Wire T ToT SH To SH amp R To R

NOTE This Network Wiring Is NotRequired On Single Loop SystemsWithout A CommLink When ACommLink Is Used On Single LoopSystems Connect Network LoopWire Terminals To The CommLink

GN

D

18-3

0 V

AC

Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring

CAUTION

24 VAC TransformerSize For 6 VA Max Load

Some Installers Like To Use One Large 24 VAC TransformerTo Power Several Devices This Is Allowable As Long AsPolarity Is Maintained To Each Device On The TransformerCircuit

Using Separate Transformers Also Allows Redundancy InCase Of A Transformer Failure Instead Of Having 8 DevicesInoperative Because Of A Malfunctioning Transformer YouHave Only 1 Device Off Line

WARNING If Polarity Is Not Maintained Severe DamageTo The Devices May Result AAON Recommends Using ASeparate Transformer For Each Device In Order ToEliminate The Potential For Damaging Devices Due ToIncorrect Polarity

NOTE All Communication Wiring Must Be Plenum-rated Minimum18-gauge 2-conductor Twisted Pair With Shield Wire AAON CanSupply Communication Wire That Meets This Specification And IsColor Coded For The Network Or Local Loop The Local Loop Wire(G038140) Is Color Coded With Green Candy Striping And ComesOn A 1000 Ft Spool The Network Loop Wire (G038150) Is ColorCoded With Red Candy Striping And Comes On A 500 Ft Spool IfDesired 18-Gauge Minimum Belden 82760 Or EquivalentCommunications Wire May Also Be Used For Network Or LocalLoop Wiring

Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring

CAUTION

MINILINK PD 5

PD

DR

V

LO

OP

DR

V

NET DRV

PIC32 MLPDYS102398 REV 3

NETWORK

LOCAL

PD COMM

POWER

COMMML

PD

MADE IN USA

SE

RIA

L

C22

C23

C30

C37

C40

J1

J3

R1

R2

R3

R4 R20

R21

R22

R23R24

R25

R26

R27

R31

PDSTAT1

PDSTAT2

TB1

TB2

U8

U10

U12

D4

J6

J7

J8

R43

R44

R46

C33

T

SH

R

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1uF

1uF

1uF

1uF

1002

1002

T

SH

R

C24

COMM

1

2

4

8

16

32

SW2

OF

F

LOOP

NET

ON FOR

HI SPD

ADDRESS

On Multiple Loop Systems ConnectCable To Next MiniLinkrsquos NetworkComm Connector Or ConnectNetwork Loop Wire Terminals ToCommLink And Daisy-Chain AllMiniLink Network Terminals TogetherBe Sure To Wire T To T SH To SH ampR To R

AZ 3 MiniLink PD 5 Technical Guide6

Address Setting

Figure 3 Address Dipswitch Setting

NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect

1

2

4

8

16

32

SW2

OF

F

LOOP

NET

ON FOR

HI SPD

ADDRESS

Address Dipswitch Setting

MINILINK PD 5

16

32NET

LOOP

8421

Address Switch Shown IsSet For Address 1

Address Switch Shown IsSet For Address 13

ControllerAddress Switch

Address 1

ADD

ADD ADD

The Address For Each MLPD5Must Be Unique To The Other

On The Network Loop And Be Between 1 and 60MLPD5s

16

32NET

LOOP

8421

Address 13

ADD

Installation

AZ 3 MiniLink PD 5 Technical Guide 7

Network Loop amp Local Loop Baud Rate Settings

Figure 4 Baud Rate Dipswitch Setting

Installation

AZ 3 MiniLink PD 5 Technical Guide8

System Confi gurationsSystem Architecture

CV Single Loop System

The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout

CV Multiple Loop System

If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout

VAVZone Single Loop System

If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout

VAVZone Multiple Loop System

If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the

AZ 3 MiniLink PD 5 Technical Guide 9

System Confi gurationsSystem Architecture

other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout

VAVZone amp CV Single Loop System

If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg

Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout

VAVZone amp CV Multiple Loop System

If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide10

CV System DiagramsSystem Architecture

Figure 5 Typical CV Single Loop System Layout

Figure 6 Typical CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 11

VAVZone System DiagramsSystem Architecture

Figure 7 Typical VAVZone Single Loop System Layout

Figure 8 Typical VAVZone Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 3: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide 3

General

The ASM02454 MiniLink PD 5 is a RS-485 communications device that is used to integrate multiple local RS-485 commu-nication loops into a RS-485 network communications system See Figure 1 page 4 for dimensions

The MiniLink PD 5 is required on the Auto-Zone 3 (AZ 3) Control System to separate local loops Up to 60 MiniLink loops can be on a system

Local loop terminals on the MiniLink PD 5 are designed to connect to controllers that are daisy-chained together on its local RS-485 communications loop

Network loop terminals on the MiniLink PD 5 are used to daisy-chain multiple MiniLinks back to a CommLink 5 to form a network RS-485 communications loop This provides for a fully networked RS-485 communications system

The MiniLink PD 5 is required for VAV systems to allow infor-mation to be shared between the AZ 3 VAV unit controller and the AZ 3 VAVZone BACnetreg Controllers It is also required for zoning systems to facilitate voting of the zones to determine the HVAC unitrsquos heating and cooling mode of operation and provides tenant-logging capabilities

MiniLink PD 5

Features

The MiniLink PD 5 utilizes token passing communication ar-chitecture The MiniLink PD 5 is designed to serve as the local communications loop master This means that it is responsible for sending a token to all the controllers on the local communi-cations loop

Network communications are RS-485 type operating at 19200 or 115200 baud Local communications are also RS-485 type and operate at 9600 or 57600 baud

The MiniLink PD 5 is factory default set to high speed Dip switches can be changed to low speed if required for your ap-plication See Page 7

Overview

AZ 3 MiniLink PD 5 Technical Guide4

Considerations

Figure 1 MiniLink PD 5 Dimensions

Environmental Requirements

The MiniLink PD 5 needs to be installed in an environment that can maintain a temperature range between -30degF and 150degF and a humidity range between 0 and 95 RH (non-condensing)

Mounting

The MiniLink PD 5 is housed in a plastic enclosure It is designed to be mounted by using the 3 mounting holes in the enclosure base It is important to mount the device in a location that is free from extreme high or low temperatures moisture dust and dirt Be careful not to damage the electronic components when mounting the MiniLink PD 5 The printed circuit board plastic cover has a UL94V0 fl ame rating

Installation

564505

207

414

596

066

273

029

496

149

AZ 3 MiniLink PD 5 Technical Guide 5

Figure 2 MiniLink PD 5 Wiring

WiringInstallation

RR SH

SH

T

T

Connect Local LoopTerminals To T SH amp RLocal Loop Terminals OnFirst Controller On LocalLoop Be Sure To Wire T ToT SH To SH amp R To R

NOTE This Network Wiring Is NotRequired On Single Loop SystemsWithout A CommLink When ACommLink Is Used On Single LoopSystems Connect Network LoopWire Terminals To The CommLink

GN

D

18-3

0 V

AC

Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring

CAUTION

24 VAC TransformerSize For 6 VA Max Load

Some Installers Like To Use One Large 24 VAC TransformerTo Power Several Devices This Is Allowable As Long AsPolarity Is Maintained To Each Device On The TransformerCircuit

Using Separate Transformers Also Allows Redundancy InCase Of A Transformer Failure Instead Of Having 8 DevicesInoperative Because Of A Malfunctioning Transformer YouHave Only 1 Device Off Line

WARNING If Polarity Is Not Maintained Severe DamageTo The Devices May Result AAON Recommends Using ASeparate Transformer For Each Device In Order ToEliminate The Potential For Damaging Devices Due ToIncorrect Polarity

NOTE All Communication Wiring Must Be Plenum-rated Minimum18-gauge 2-conductor Twisted Pair With Shield Wire AAON CanSupply Communication Wire That Meets This Specification And IsColor Coded For The Network Or Local Loop The Local Loop Wire(G038140) Is Color Coded With Green Candy Striping And ComesOn A 1000 Ft Spool The Network Loop Wire (G038150) Is ColorCoded With Red Candy Striping And Comes On A 500 Ft Spool IfDesired 18-Gauge Minimum Belden 82760 Or EquivalentCommunications Wire May Also Be Used For Network Or LocalLoop Wiring

Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring

CAUTION

MINILINK PD 5

PD

DR

V

LO

OP

DR

V

NET DRV

PIC32 MLPDYS102398 REV 3

NETWORK

LOCAL

PD COMM

POWER

COMMML

PD

MADE IN USA

SE

RIA

L

C22

C23

C30

C37

C40

J1

J3

R1

R2

R3

R4 R20

R21

R22

R23R24

R25

R26

R27

R31

PDSTAT1

PDSTAT2

TB1

TB2

U8

U10

U12

D4

J6

J7

J8

R43

R44

R46

C33

T

SH

R

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1uF

1uF

1uF

1uF

1002

1002

T

SH

R

C24

COMM

1

2

4

8

16

32

SW2

OF

F

LOOP

NET

ON FOR

HI SPD

ADDRESS

On Multiple Loop Systems ConnectCable To Next MiniLinkrsquos NetworkComm Connector Or ConnectNetwork Loop Wire Terminals ToCommLink And Daisy-Chain AllMiniLink Network Terminals TogetherBe Sure To Wire T To T SH To SH ampR To R

AZ 3 MiniLink PD 5 Technical Guide6

Address Setting

Figure 3 Address Dipswitch Setting

NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect

1

2

4

8

16

32

SW2

OF

F

LOOP

NET

ON FOR

HI SPD

ADDRESS

Address Dipswitch Setting

MINILINK PD 5

16

32NET

LOOP

8421

Address Switch Shown IsSet For Address 1

Address Switch Shown IsSet For Address 13

ControllerAddress Switch

Address 1

ADD

ADD ADD

The Address For Each MLPD5Must Be Unique To The Other

On The Network Loop And Be Between 1 and 60MLPD5s

16

32NET

LOOP

8421

Address 13

ADD

Installation

AZ 3 MiniLink PD 5 Technical Guide 7

Network Loop amp Local Loop Baud Rate Settings

Figure 4 Baud Rate Dipswitch Setting

Installation

AZ 3 MiniLink PD 5 Technical Guide8

System Confi gurationsSystem Architecture

CV Single Loop System

The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout

CV Multiple Loop System

If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout

VAVZone Single Loop System

If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout

VAVZone Multiple Loop System

If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the

AZ 3 MiniLink PD 5 Technical Guide 9

System Confi gurationsSystem Architecture

other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout

VAVZone amp CV Single Loop System

If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg

Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout

VAVZone amp CV Multiple Loop System

If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide10

CV System DiagramsSystem Architecture

Figure 5 Typical CV Single Loop System Layout

Figure 6 Typical CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 11

VAVZone System DiagramsSystem Architecture

Figure 7 Typical VAVZone Single Loop System Layout

Figure 8 Typical VAVZone Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 4: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide4

Considerations

Figure 1 MiniLink PD 5 Dimensions

Environmental Requirements

The MiniLink PD 5 needs to be installed in an environment that can maintain a temperature range between -30degF and 150degF and a humidity range between 0 and 95 RH (non-condensing)

Mounting

The MiniLink PD 5 is housed in a plastic enclosure It is designed to be mounted by using the 3 mounting holes in the enclosure base It is important to mount the device in a location that is free from extreme high or low temperatures moisture dust and dirt Be careful not to damage the electronic components when mounting the MiniLink PD 5 The printed circuit board plastic cover has a UL94V0 fl ame rating

Installation

564505

207

414

596

066

273

029

496

149

AZ 3 MiniLink PD 5 Technical Guide 5

Figure 2 MiniLink PD 5 Wiring

WiringInstallation

RR SH

SH

T

T

Connect Local LoopTerminals To T SH amp RLocal Loop Terminals OnFirst Controller On LocalLoop Be Sure To Wire T ToT SH To SH amp R To R

NOTE This Network Wiring Is NotRequired On Single Loop SystemsWithout A CommLink When ACommLink Is Used On Single LoopSystems Connect Network LoopWire Terminals To The CommLink

GN

D

18-3

0 V

AC

Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring

CAUTION

24 VAC TransformerSize For 6 VA Max Load

Some Installers Like To Use One Large 24 VAC TransformerTo Power Several Devices This Is Allowable As Long AsPolarity Is Maintained To Each Device On The TransformerCircuit

Using Separate Transformers Also Allows Redundancy InCase Of A Transformer Failure Instead Of Having 8 DevicesInoperative Because Of A Malfunctioning Transformer YouHave Only 1 Device Off Line

WARNING If Polarity Is Not Maintained Severe DamageTo The Devices May Result AAON Recommends Using ASeparate Transformer For Each Device In Order ToEliminate The Potential For Damaging Devices Due ToIncorrect Polarity

NOTE All Communication Wiring Must Be Plenum-rated Minimum18-gauge 2-conductor Twisted Pair With Shield Wire AAON CanSupply Communication Wire That Meets This Specification And IsColor Coded For The Network Or Local Loop The Local Loop Wire(G038140) Is Color Coded With Green Candy Striping And ComesOn A 1000 Ft Spool The Network Loop Wire (G038150) Is ColorCoded With Red Candy Striping And Comes On A 500 Ft Spool IfDesired 18-Gauge Minimum Belden 82760 Or EquivalentCommunications Wire May Also Be Used For Network Or LocalLoop Wiring

Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring

CAUTION

MINILINK PD 5

PD

DR

V

LO

OP

DR

V

NET DRV

PIC32 MLPDYS102398 REV 3

NETWORK

LOCAL

PD COMM

POWER

COMMML

PD

MADE IN USA

SE

RIA

L

C22

C23

C30

C37

C40

J1

J3

R1

R2

R3

R4 R20

R21

R22

R23R24

R25

R26

R27

R31

PDSTAT1

PDSTAT2

TB1

TB2

U8

U10

U12

D4

J6

J7

J8

R43

R44

R46

C33

T

SH

R

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1uF

1uF

1uF

1uF

1002

1002

T

SH

R

C24

COMM

1

2

4

8

16

32

SW2

OF

F

LOOP

NET

ON FOR

HI SPD

ADDRESS

On Multiple Loop Systems ConnectCable To Next MiniLinkrsquos NetworkComm Connector Or ConnectNetwork Loop Wire Terminals ToCommLink And Daisy-Chain AllMiniLink Network Terminals TogetherBe Sure To Wire T To T SH To SH ampR To R

AZ 3 MiniLink PD 5 Technical Guide6

Address Setting

Figure 3 Address Dipswitch Setting

NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect

1

2

4

8

16

32

SW2

OF

F

LOOP

NET

ON FOR

HI SPD

ADDRESS

Address Dipswitch Setting

MINILINK PD 5

16

32NET

LOOP

8421

Address Switch Shown IsSet For Address 1

Address Switch Shown IsSet For Address 13

ControllerAddress Switch

Address 1

ADD

ADD ADD

The Address For Each MLPD5Must Be Unique To The Other

On The Network Loop And Be Between 1 and 60MLPD5s

16

32NET

LOOP

8421

Address 13

ADD

Installation

AZ 3 MiniLink PD 5 Technical Guide 7

Network Loop amp Local Loop Baud Rate Settings

Figure 4 Baud Rate Dipswitch Setting

Installation

AZ 3 MiniLink PD 5 Technical Guide8

System Confi gurationsSystem Architecture

CV Single Loop System

The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout

CV Multiple Loop System

If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout

VAVZone Single Loop System

If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout

VAVZone Multiple Loop System

If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the

AZ 3 MiniLink PD 5 Technical Guide 9

System Confi gurationsSystem Architecture

other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout

VAVZone amp CV Single Loop System

If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg

Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout

VAVZone amp CV Multiple Loop System

If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide10

CV System DiagramsSystem Architecture

Figure 5 Typical CV Single Loop System Layout

Figure 6 Typical CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 11

VAVZone System DiagramsSystem Architecture

Figure 7 Typical VAVZone Single Loop System Layout

Figure 8 Typical VAVZone Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 5: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide 5

Figure 2 MiniLink PD 5 Wiring

WiringInstallation

RR SH

SH

T

T

Connect Local LoopTerminals To T SH amp RLocal Loop Terminals OnFirst Controller On LocalLoop Be Sure To Wire T ToT SH To SH amp R To R

NOTE This Network Wiring Is NotRequired On Single Loop SystemsWithout A CommLink When ACommLink Is Used On Single LoopSystems Connect Network LoopWire Terminals To The CommLink

GN

D

18-3

0 V

AC

Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring

CAUTION

24 VAC TransformerSize For 6 VA Max Load

Some Installers Like To Use One Large 24 VAC TransformerTo Power Several Devices This Is Allowable As Long AsPolarity Is Maintained To Each Device On The TransformerCircuit

Using Separate Transformers Also Allows Redundancy InCase Of A Transformer Failure Instead Of Having 8 DevicesInoperative Because Of A Malfunctioning Transformer YouHave Only 1 Device Off Line

WARNING If Polarity Is Not Maintained Severe DamageTo The Devices May Result AAON Recommends Using ASeparate Transformer For Each Device In Order ToEliminate The Potential For Damaging Devices Due ToIncorrect Polarity

NOTE All Communication Wiring Must Be Plenum-rated Minimum18-gauge 2-conductor Twisted Pair With Shield Wire AAON CanSupply Communication Wire That Meets This Specification And IsColor Coded For The Network Or Local Loop The Local Loop Wire(G038140) Is Color Coded With Green Candy Striping And ComesOn A 1000 Ft Spool The Network Loop Wire (G038150) Is ColorCoded With Red Candy Striping And Comes On A 500 Ft Spool IfDesired 18-Gauge Minimum Belden 82760 Or EquivalentCommunications Wire May Also Be Used For Network Or LocalLoop Wiring

Disconnect All Communication Loop WiringFrom The MiniLink Before Removing PowerFrom The Controller Reconnect Power AndThen Reconnect Communication Loop Wiring

CAUTION

MINILINK PD 5

PD

DR

V

LO

OP

DR

V

NET DRV

PIC32 MLPDYS102398 REV 3

NETWORK

LOCAL

PD COMM

POWER

COMMML

PD

MADE IN USA

SE

RIA

L

C22

C23

C30

C37

C40

J1

J3

R1

R2

R3

R4 R20

R21

R22

R23R24

R25

R26

R27

R31

PDSTAT1

PDSTAT2

TB1

TB2

U8

U10

U12

D4

J6

J7

J8

R43

R44

R46

C33

T

SH

R

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1uF

1uF

1uF

1uF

1002

1002

T

SH

R

C24

COMM

1

2

4

8

16

32

SW2

OF

F

LOOP

NET

ON FOR

HI SPD

ADDRESS

On Multiple Loop Systems ConnectCable To Next MiniLinkrsquos NetworkComm Connector Or ConnectNetwork Loop Wire Terminals ToCommLink And Daisy-Chain AllMiniLink Network Terminals TogetherBe Sure To Wire T To T SH To SH ampR To R

AZ 3 MiniLink PD 5 Technical Guide6

Address Setting

Figure 3 Address Dipswitch Setting

NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect

1

2

4

8

16

32

SW2

OF

F

LOOP

NET

ON FOR

HI SPD

ADDRESS

Address Dipswitch Setting

MINILINK PD 5

16

32NET

LOOP

8421

Address Switch Shown IsSet For Address 1

Address Switch Shown IsSet For Address 13

ControllerAddress Switch

Address 1

ADD

ADD ADD

The Address For Each MLPD5Must Be Unique To The Other

On The Network Loop And Be Between 1 and 60MLPD5s

16

32NET

LOOP

8421

Address 13

ADD

Installation

AZ 3 MiniLink PD 5 Technical Guide 7

Network Loop amp Local Loop Baud Rate Settings

Figure 4 Baud Rate Dipswitch Setting

Installation

AZ 3 MiniLink PD 5 Technical Guide8

System Confi gurationsSystem Architecture

CV Single Loop System

The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout

CV Multiple Loop System

If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout

VAVZone Single Loop System

If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout

VAVZone Multiple Loop System

If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the

AZ 3 MiniLink PD 5 Technical Guide 9

System Confi gurationsSystem Architecture

other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout

VAVZone amp CV Single Loop System

If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg

Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout

VAVZone amp CV Multiple Loop System

If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide10

CV System DiagramsSystem Architecture

Figure 5 Typical CV Single Loop System Layout

Figure 6 Typical CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 11

VAVZone System DiagramsSystem Architecture

Figure 7 Typical VAVZone Single Loop System Layout

Figure 8 Typical VAVZone Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 6: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide6

Address Setting

Figure 3 Address Dipswitch Setting

NOTE The Power To The MiniLink Must Be RemovedAnd Reconnected After Changing The Address SwitchSettings In Order For Any Changes To Take Effect

1

2

4

8

16

32

SW2

OF

F

LOOP

NET

ON FOR

HI SPD

ADDRESS

Address Dipswitch Setting

MINILINK PD 5

16

32NET

LOOP

8421

Address Switch Shown IsSet For Address 1

Address Switch Shown IsSet For Address 13

ControllerAddress Switch

Address 1

ADD

ADD ADD

The Address For Each MLPD5Must Be Unique To The Other

On The Network Loop And Be Between 1 and 60MLPD5s

16

32NET

LOOP

8421

Address 13

ADD

Installation

AZ 3 MiniLink PD 5 Technical Guide 7

Network Loop amp Local Loop Baud Rate Settings

Figure 4 Baud Rate Dipswitch Setting

Installation

AZ 3 MiniLink PD 5 Technical Guide8

System Confi gurationsSystem Architecture

CV Single Loop System

The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout

CV Multiple Loop System

If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout

VAVZone Single Loop System

If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout

VAVZone Multiple Loop System

If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the

AZ 3 MiniLink PD 5 Technical Guide 9

System Confi gurationsSystem Architecture

other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout

VAVZone amp CV Single Loop System

If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg

Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout

VAVZone amp CV Multiple Loop System

If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide10

CV System DiagramsSystem Architecture

Figure 5 Typical CV Single Loop System Layout

Figure 6 Typical CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 11

VAVZone System DiagramsSystem Architecture

Figure 7 Typical VAVZone Single Loop System Layout

Figure 8 Typical VAVZone Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 7: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide 7

Network Loop amp Local Loop Baud Rate Settings

Figure 4 Baud Rate Dipswitch Setting

Installation

AZ 3 MiniLink PD 5 Technical Guide8

System Confi gurationsSystem Architecture

CV Single Loop System

The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout

CV Multiple Loop System

If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout

VAVZone Single Loop System

If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout

VAVZone Multiple Loop System

If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the

AZ 3 MiniLink PD 5 Technical Guide 9

System Confi gurationsSystem Architecture

other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout

VAVZone amp CV Single Loop System

If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg

Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout

VAVZone amp CV Multiple Loop System

If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide10

CV System DiagramsSystem Architecture

Figure 5 Typical CV Single Loop System Layout

Figure 6 Typical CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 11

VAVZone System DiagramsSystem Architecture

Figure 7 Typical VAVZone Single Loop System Layout

Figure 8 Typical VAVZone Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 8: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide8

System Confi gurationsSystem Architecture

CV Single Loop System

The most basic of the Auto-Zone 3 systems is the CV Single Loop System It consists of one or more Constant Volume (CV) Make-up Air Units (MUA) andor Single Zone VAV (SZVAV) units each having their own AZ 3 Controller and associated expansion module(s)

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 5 on page 10 for a Typical CV Single Loop System Layout

CV Multiple Loop System

If you have more than 59 CV MUA andor SZVAV Units or other controllers such as the GPC-XP on your building project you will need to use a CV Multiple Loop System It is very similar to the CV Single Loop System except it has more than one local communications loop This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 6 on page 10 for a Typical CV Multiple Loop System Layout

VAVZone Single Loop System

If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and have VAVZones on your system you should select the VAVZone Single Loop System On a Variable Volume Variable Temperature Zoning System up to 16 VAVZone BACnetreg Controllers can be voting zones and additional zone controllers can be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained to-gether back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local oop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply communication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 7 on page 11 for a Typical VAVZone Single Loop System Layout

VAVZone Multiple Loop System

If you have multiple HVAC units that will be using VAV Terminal Units or will be using a Zoning System and donrsquot have any CV units you should select the VAVZone Multiple Loop System On a Zoning System each local loop allows up to 16 VAVZone BACnetreg Controllers to be vot-ing zones and additional controllers to be non-voting zones For VAV systems you can have up to 58 total VAVZone BACnetreg controllers in addition to the HVAC unit controller that serves those VAV boxes This system allows for up to 60 of these local loops to be tied together

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the

AZ 3 MiniLink PD 5 Technical Guide 9

System Confi gurationsSystem Architecture

other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout

VAVZone amp CV Single Loop System

If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg

Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout

VAVZone amp CV Multiple Loop System

If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide10

CV System DiagramsSystem Architecture

Figure 5 Typical CV Single Loop System Layout

Figure 6 Typical CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 11

VAVZone System DiagramsSystem Architecture

Figure 7 Typical VAVZone Single Loop System Layout

Figure 8 Typical VAVZone Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 9: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide 9

System Confi gurationsSystem Architecture

other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 9 on page 11 for a Typical VAVZone Multiple Loop System Layout

VAVZone amp CV Single Loop System

If you have a single HVAC unit with VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of controllers is less than 58 you should select the VAVZone amp CV Single Loop System The local loop provides for up to 58 previously mentioned controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers On the local loop up to 16 VAVZone BACnetreg

Controllers can be voting zones and additional controllers can be made up of non-voting zones or the other previously mentioned controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers andor previously mentioned controllers in addition to the HVAC unit controller that serves those VAV boxes

The communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the local loop This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface wires to the MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control system See Figure 10 on page 12 for a Typical VAVZone amp CV Single Loop System Layout

VAVZone amp CV Multiple Loop System

If you have multiple HVAC units using VAV Terminal Units or a Zoning system also have CV MUA andor SZVAV units and other controllers such as the GPC-XP controller andor your total number of control-lers exceeds 58 you should select the VAVZone amp CV Multiple Loop System Each local loop provides for up to 58 Zone VAV CV MUA SZVAV and GPC-XP controllers in addition to the HVAC unit controller that is connected to the VAVZone BACnetreg Controllers This system allows for up to 60 of these local loops to be tied together On a zoning system local loop up to 16 VAVZone BACnetreg Controllers can be voting zones and additional controllers can be made up of non-voting zones CV MUA SZVAV units and GPC-XP controllers For VAV systems you can also have up to 58 total VAVZone BACnetreg Controllers CV MUA SZVAV units and GPC-XP controllers in addition to the HVAC unit controller that serves those VAV boxes

Each local communications loop can have up to 59 controllers daisy-chained together back to a MiniLink PD This is called a Local Loop The MiniLink provides for alarm polling of all controllers and also has the capability of broadcasting select sensor values to all controllers on the control system This can be useful for example if you want to have one Outdoor Air Temperature Sensor to be used by all the controllers All communication wiring must be plenum-rated minimum 18-gauge 2-conductor twisted pair with shield cable AAON can supply com-munication wire that meets this specifi cation and is color coded for the network or local loop or if desired Belden 82760 or its equivalent wire may also be used

The CommLink 5 communications interface is daisy-chained to one MiniLinkrsquos Network communication terminals and from it to all the other MiniLinkrsquos Network communication terminals This is called the Network Loop The CommLink 5 also connects via a USB cable to any Windowsreg computer with Prism 2 software installed for confi guring and monitoring of the system Prism 2 is a Windowsreg based graphical interface designed by AAON An optional IP Module is also available to provide IntranetInternet connectivity to the control systemSee Figure 11 on page 12 for a Typical VAVZone amp CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide10

CV System DiagramsSystem Architecture

Figure 5 Typical CV Single Loop System Layout

Figure 6 Typical CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 11

VAVZone System DiagramsSystem Architecture

Figure 7 Typical VAVZone Single Loop System Layout

Figure 8 Typical VAVZone Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 10: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide10

CV System DiagramsSystem Architecture

Figure 5 Typical CV Single Loop System Layout

Figure 6 Typical CV Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 11

VAVZone System DiagramsSystem Architecture

Figure 7 Typical VAVZone Single Loop System Layout

Figure 8 Typical VAVZone Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 11: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide 11

VAVZone System DiagramsSystem Architecture

Figure 7 Typical VAVZone Single Loop System Layout

Figure 8 Typical VAVZone Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 12: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide12

VAVZone amp CV Units System DiagramsSystem Architecture

Figure 9 Typical VAVZone amp CV Units Single Loop System Layout

Figure 10 Typical VAVZone amp CV Units Multiple Loop System Layout

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 13: MiniLink PD 5 Technical Guide - az3controls.com

AZ 3 MiniLink PD 5 Technical Guide 13

Notes

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative

Page 14: MiniLink PD 5 Technical Guide - az3controls.com

AAON Inc bull 8500 NW River Park Drive bull Parkville MO bull 64152Ph (816) 505-1100

AAONreg PN G075300 Rev 01A 200904 Printed in the USA bull Copyright October 2020 bull All Rights Reserved

Auto-Zone 3 MiniLink Technical GuideG075300 Rev 01A 200904

AAON Factory Technical Support 918-382-6450techsupportaaoncom

AAON Controls Support 866-918-1100Monday through Friday 700 AM to 500 PM

central standard time

NOTE Before calling Technical Support please have the model and serial number of the unit available

PARTS For replacement parts please contact your local AAON Representative