mlc connectivity to slc 500 via devicenet. equipment needed for connecting n mlc 9000 bcm n...

36
MLC Connectivity to SLC 500 via DeviceNet

Upload: cody-daykin

Post on 22-Dec-2015

227 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

MLC Connectivity to SLC 500 via DeviceNet

Page 2: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Equipment Needed for Connecting

MLC 9000 BCM Allen-Bradley SLC 500 CPU 5/02 or higher

– 5/02 smallest CPU to support M0/M1 File Transfer Allen-Bradley 1747-SDN DeviceNet Scanner Allen-Bradley RSNetworx or DeviceNet Manager Software RSLogix PLC Programming Software PC Interface(i.e 1770-KFD for programming) DeviceNet Cabling

– Thick Trunk Cable with Mini-Connectors– Thin Drop Cable with Micro or Mini-Connectors– T-Connectors– Terminating connectors(110 Ohms)

Page 3: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

How SLC500 Communicates with 1747-SDN

Two methods used– I/O Transfer

1747 occupies 32 Input Words and 32 Output Words– 1 word of input, 1 word of output used for module status

and command– 62 words available for devices

Intended for devices transmitting small blocks of information– Proximity and Photoelectric Switches– “Slice” I/O– Valves

Page 4: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

How SLC 500 Communicates with 1747-SDN

Block Transfer via M0/M1 Files– M1 File

150 Words Available for Input from Network Devices (M1:1.0-M1:1.149)

74 Diagnostic Words (M1:1.150-M1:1.223) 32 Words for Inbound Explicit Message Control

(M1:1.224-M1:1.255)

Page 5: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

How SLC 500 Communicates to 1747-SDN

Block Transfer via M0/M1 Files– M0 File

150 Words of data used for output to network devices (M0:1.0-M0:1.149)

74 Words Reserved/Unused (M0:1.150-M0:1.223) 32 Words used for outgoing explicit message

control (M0:1.224-M0:1.255)

Page 6: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

How MLC 9000 Communicates with 1747-SDN

MLC 9000 Gateway– Converts DeviceNet Messages from Scanner into

Modbus Messages to Bus Control Module Uses Polled Messaging for Implicit I/O

Connection– One Loop Control Module takes up 16 Bytes of

Input and 6 Bytes of Output Uses Explicit Messaging to gain access to

parameters not supported through implicit connection

Page 7: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Implicit I/O Connection Data

Offset Input Output0 Process Variable(High Byte) Setpoint 1 (High Byte)1 Process Variable(Low Byte) Setpoint 1 (Low Byte)2 Actual Setpoint (High Byte) Setpoint 2 (High Byte)3 Actual Setpoint (Low Byte) Setpoint 2 (Low Byte)4 Setpoint 1 (High Byte) Setpoint Switch (High Byte)5 Setpoint 1 (Low Byte) Setpoint Switch (Low Byte)6 Setpoint 2 (High Byte) Unused7 Setpoint 2 (Low Byte) Unused8 Setpoint Switch (High Byte) Unused9 Setpoint Switch (Low Byte) Unused10 Heat Output Power (High Byte) Unused11 Heat Output Power (Low Byte) Unused12 Cool Output Power (High Byte) Unused13 Cool Output Power (Low Byte) Unused14 PID Bit Parameters (High Byte) Unused15 PID Bit Parameters (Low Byte) Unused

Page 8: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Setting Up PC to Communicate via DeviceNet

In RSLinx, Select Communications and Configure driver

Page 9: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Setting Up PC to Communicate via DeviceNet

Under Available Driver Types, select DeviceNet Drivers and select Add new

Page 10: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Setting Up PC to Communicate via DeviceNet

Select 1747-SDNPT

Page 11: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Setting Up PC to Communicate via DeviceNet

Select Processor to Connect to and slot where 1747-SDN resides

Page 12: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Setting Up PC to Communicate via DeviceNet

1747-SDNPT-1 should be seen running

Page 13: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Setting Up SLC500 to Pull Information from 1747-SDN

Start RSLogix and Select File-New

Page 14: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Setting Up SLC500 to Pull Information from 1747-SDN

Select processor from list

Page 15: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Setting Up SLC500 to Pull Information from 1747-SDN

From Menu Tree, Select IO Configuration then add 1747-SDN into Slot 1 of Rack

Page 16: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Setting Up SLC500 to Pull Information from 1747-SDN

Highlight on Rung in Ladder Window

Page 17: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Setting Up SLC500 to Pull Information from 1747-SDN

•Insert one Normally Closed Contact and Two Copy Instructions into Rung 1

•Copy Instructions move data from M0/M1 Files to usable data areas

Page 18: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Setting Up SLC500 to Pull Information from 1747-SDN

•Last Rung Energizes Output Run coil and disables in event of error in module

•Download to PLC and place in Run Mode

Page 19: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

•To Configure Network, Gateway EDS file must be installed

•EDS (Electronic Data Sheet) carries configuration properties for DeviceNet products

•Start RSNetworx then select Tools-EDS Wizard

Page 20: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

Select Register EDS File then select Choose File

Page 21: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

•Select A: Drive then select West0456•Click Open

Page 22: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

Wizard will run test on EDS

Page 23: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

Wizard will prompt you to associate a graphic icon with EDS

Page 24: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

This will finish the EDS Installation

Page 25: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

Select 1747-SDN from Device List

Page 26: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

Insert MLC 9000 Gateway form Device List

Page 27: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

Double Click on 1747-SDN and select Scanlist

Page 28: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

•Click on arrow to add Gateway to 1747-SDN’s scanlist

•Select edit I/O parameters

Page 29: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

•Adjust the Polled Rx and Tx parameters to match the number of I/O taken up by LCM’s

•16 bytes of Rx and 6 bytes Tx for every LCM (up to 8 LCM’s)

Page 30: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

•Select Input•Select Memory Type M file•Select AutoMap

Page 31: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

•Select Output•Select Memory Type M file•Select AutoMap

Page 32: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

•From Main Screen, select Tools then Node Commissioning•Nodes must be commissioned with proper baud rate and node address before the configuration can be downloaded to network•Select Browse

Page 33: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

•Select 1747-SDNPT from list of drivers•RSNetworx will detect connected devices•Select Node to adjust

Page 34: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

Change Node Address and click Apply if changes are needed

Page 35: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

•To prepare for download, network connection must be established online first

•Click Network, then Online

Page 36: MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting n MLC 9000 BCM n Allen-Bradley SLC 500 CPU 5/02 or higher – 5/02 smallest CPU

Configuring the DeviceNet Network

After Online connection established, select network-download to network to send configuration