model for hydrogen kj91 92 is added to kj91 intrinsically...

17
Actual size Diaphragm SUS316L Silicone oil SUS316 Cat.No. B04-18-H Features of sensor KJ9192 Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter KJ91 KJ92 *25.4mm conversion fitting supplied as option. Compact size and light-weight with the same appearance and operability as non-explosion-proof type GC51 and GC52. Adjustment of display and output ranges is possible with scaling function. The display unit provides easy-to-read LCD indication, in which LED backlight is used. You can clearly read measured values even in dark places. Because the insulated safety barrier is used, Type A intrinsic safety ground work is unnecessary. When using the barrier, please order the recommended barrier separately. If using a barrier other than recommended barrier, please observe strictly the "Safety Maintenance Rating" These products are the 2 wire intrinsically safe explosion-proof construction pressure transmitter with a display and SS sensor and the 2 wire intrinsically safe explosion-proof construction differential pressure transmitter with a display and SC sensor (GC52). Please use in combination with insulated safety barrier. Conforming to the IEC intrinsically safe explosion-proof construction standard, they can be used in “ZONE 0” place where explosive gas always exists. (Explosion class: Exia ⅡC T4) In combination with the non-explosion-proof type GC51/GC52, pressure measurement in a wide range of industrial process measurement (Fine pressure to high pressure) is possible. Features KJ91 Pressure Transmitter KJ92 Differential Pressure Transmitter Silicon diaphragm Upper glass plate Lower glass plate Electrodes SC Sensor The semiconductor evaporated type (SS) sensor, which has a record of achievements in various industrial fields, has an integrated construction from the semiconductor strain gauge part and sensing part to pressure connection part and no adhesives and corrosive materials are used. Therefor it has superior durability and stability. Since the sensor section contains a sealed-in silicon capacitance (SC) sensor formed by micromachining and the wetted parts consist of a stainless steel diaphragm, it handles a wide range of medium and can measure minute differential pressure with high reliability and high sensitivity. [KJ92] [KJ91] *25.4mm conversion fitting supplied as option. SS Sensor Model for hydrogen is added to KJ91 Outline Semiconductor Evaporated type (SS) Sensor Silicon Capacitance (SC) Sensor

Upload: others

Post on 04-Apr-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

Actualsize

DiaphragmSUS316L

Silicone oil

SUS316

Cat.No. B04-18-H

Features of sensor

KJ91・92Intrinsically Safe Explosion-Proof Construction

Pressure & Differential Pressure Transmitter

KJ91

KJ92

*25.4mm conversion fitting supplied as option.

●Compact size and light-weight with the same appearance and operability as non-explosion-proof type GC51 and GC52.●Adjustment of display and output ranges is possible with scaling function.●The display unit provides easy-to-read LCD indication, in which LED backlight is used. You can clearly read measured values even in dark places.●Because the insulated safety barrier is used, Type A intrinsic safety ground work is unnecessary.

When using the barrier, please order the recommendedbarrier separately. If using a barrier other than recommendedbarrier, please observe strictly the "Safety Maintenance Rating"

These products are the 2 wire intrinsically safe explosion-proof construction pressure transmitter with a display and SS sensor and the 2 wire intrinsically safe explosion-proof construction differential pressure transmitter with a display and SC sensor (GC52). Please use in combination with insulated safety barrier. Conforming to the IEC intrinsically safe explosion-proof construction standard, they can be used in “ZONE 0” place where explosive gas always exists. (Explosion class: Exia ⅡC T4) In combination with the non-explosion-proof type GC51/GC52, pressure measurement in a wide range of industrial process measurement (Fine pressure to high pressure) is possible.

Features

KJ91 Pressure Transmitter KJ92 Differential Pressure Transmitter

Silicon diaphragm

Upper glass plate

Lower glass plate

Electrodes

SCSensor

The semiconductor evaporated type (SS) sensor, which has a record of achievements in various industrial fields, has an integrated construction from the semiconductor strain gauge part and sensing part to pressure connection part and no adhesives and corrosive materials are used. Therefor it has superior durability and stability.

Since the sensor section contains a sealed-in silicon capacitance (SC) sensor formed by micromachining and the wetted parts consist of a stainless steel diaphragm, it handles a wide range of medium and can measure minute differential pressure with high reliability and high sensitivity.

[KJ92][KJ91]*25.4mm conversion fitting supplied as option.

SS Sensor

Model for hydrogenis added to KJ91

Outline

Semiconductor Evaporated type (SS) Sensor Silicon Capacitance (SC) Sensor

Page 2: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

Standard KJ91 Pressure Transmitter

Item DescriptionGas or Liquid (Not corrosive to the wetted material)For hydrogen of more than 35MPa, please check the “For high pressure hydrogen”-0.1 to 0.1, 0.2, 0.3, 0.5, 1MPa0 to 0.3, 0.5, 1, 2, 3.5, 5, 10, 20, 35, 50, 70, 100, 120MPa200% of pressure range (35 and 50MPa range is 150% 70, 100 and 120MPa range is 120%)24V DC±10%4 to 20mA DC (2 wire system, Output range: 3.2 to 20.8mA DC)Responsiveness: 30ms (With 1 time filter setting)Resolution: 0.1%F.S. Load resistance: 500Ω maximum±0.25%F.S. or ±0.5%F.S. at 23℃ (0.5 to 50MPa)±0.5%F.S. at 23℃ (0.3MPa or lower) (70MPa or higher)

Operating temperature range (-10 to 60℃)±1%F.S. or lowerZero point: -10 to 110% of the full span (To pressure range)Span point: -10 to 110% of the full span (To pressure range)

± (0.25%F.S.+1 digit) or ± (0.5%F.S.+1 digit) at 23℃ (It follows pressure output accuracy)

6 digits LCD: (Character height: 10mm, with LED backlight)Pressure display, Linear display: 4 LCD digits maximum, Display cycle 500msLCD bar display (With LED backlight)Pressure unit: kPa, MPa, Linear unit: Arbitrary setWith internal key switches (Mode, ▲, ▼)Scaling function: Linear display / outputHolding function: Both the maximum value (Peak) and the minimum value (Bottom) can be indicatedFilter function: Moving average time, Select from 1, 2, 4, 8 and 16Loop check function: Arbitrary setting output (4 to 20mA DC)Zero adjustment function: Pressure sensor zero adjustmentRc1/4 (50MPa or lower, standard) Rc1/2 (With Rc1/4+FJ10-973, option) G3/8B (With Rc1/4+FJ12-373, option) G1/2B (With Rc1/4+FJ12-473, option)G1/4 Female screw (Option)Diaphragm: SUS630 (17-4PH)      High corrosion-proof use (Co-Ni alloy) Fitting: SUS316Casing material: Aluminum die castIP65 10MPa or higherEquivalent of IP65 5MPa or lower With air inlet portDirect mounting Connection: Lower side (Standard), Right side, Upper side, Left side Outlet for electric wire: Right side (Standard), Left sidePanel mounting Connection: Lower side Outlet for electric wire: Right side (Standard), Left sideDIN terminal type: Outlet port cable gland   Applicable cable: 2 wire shielded cable  Sheath outside diameter 6 to 9mm    (Center conductor sectional area: 0.5 to 1.25mm2) Internal connection terminal block   Number of poles: 4 poles (+, -, Ground, NC)   Applicable crimp terminal: Round bare terminal, R1.25-3 (Nominal size)Connector type: TC1108-12A10-7F (Water proof type) (Made by Tajimi Electronics Co., Ltd.)

-10 to 60℃, 35 to 85%RH (No freezing or condensation)Applicable Standard: EN61326/1997, A1/1998, A2/2001Permanently stored by EEP-ROM (Nonvolatile memory)

-20 to 70℃, 35 to 85%RH (No freezing or condensation)

Approx. 520g (Direct mounting: DIN terminal type)Approx. 660g (Direct mounting: Connector type)

10 to 150Hz, Multi-amplitude 0.7mm (60Hz or lower)Acceleration: 50m/s2 (60Hz or higher)Vibrating direction: x, y, z (2.5 hours for each)Impact acceleration: 100mm/s2Impact direction: x, y, z (3 times into forward and backward directions for each)50V DC or higherIt is possible to install in outdoors (Avoid the direct sunlight)

This product is certified to type approval of NK (Nippon Kaiji Kyokai). (Type Approval No. 08T602)

Fluid

Pressure range

Allowable maximum pressurePower sourceOutput

Pressure output accuracy

Pressure display accuracyRange of guaranteed accuracy

Pressure output adjustment range

Numeric display

Unit display

Setting

Connection fitting

Wetted parts material

Casing protection structure

Mounting system

Cable connection

Memory protection

Operating temperature and humidityApplicable Standard

Storage temperature and humidityResistance to vibration

Resistance to shock

Insulation resistanceMounting locationWeight

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

General specification

2

Page 3: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

For high pressure hydrogen KJ91 Pressure Transmitter

General specification

Item DescriptionHydrogen0 to 35, 50, 70, 100, 120MPa35, 50MPa range: 150% of pressure range70, 100, 120MPa range: 120% of pressure range24V DC±10%4 to 20mA DC (2 wire system, Output range: 3.2 to 20.8mA DC)Responsiveness: 30ms (With 1 time filter setting)Resolution: 0.1%F.S.  Load resistance: 500Ω maximum±0.25%F.S. or ±0.5%F.S. at 23℃ (35, 50MPa)±0.5%F.S. at 23℃ (70, 100, 120MPa)

Operating temperature range (-10 to 60℃)±1%F.S. or lowerZero point: -10 to 110% of the full span (To pressure range)Span point: -10 to 110% of the full span (To pressure range)

± (0.25%F.S.+1 digit) or ± (0.5%F.S.+1 digit) at 23℃ (It follows pressure output accuracy)

6 digits LCD: (Character height: 10mm, with LED backlight)Pressure display, Linear display: 4 LCD digits maximum, Display cycle 500msLCD bar display (With LED backlight)Pressure unit: kPa, MPa, Linear unit: Arbitrary setWith internal key switches (Mode, ▲, ▼)Scaling function: Linear display / outputHolding function: Both the maximum value (Peak) and the minimum value (Bottom) can be indicatedFilter function: Moving average time, Select from 1, 2, 4, 8 and 16Loop check function: Arbitrary setting output (4 to 20mA DC)Zero adjustment function: Pressure sensor zero adjustmentG1/4 Female screw 9/16-18UNF Female screw (Option): F250C or equivalent by AutoclaveDiaphragm: SUH660 (A286)Fitting: SUS316Casing material: Aluminum die castIP65Direct mounting Connection: Lower side (Standard), Right side, Upper side, Left side Outlet for electric wire: Right side (Standard), Left sidePanel mounting Connection: Lower side Outlet for electric wire: Right side (Standard), Left sideDIN terminal type: Outlet port cable gland   Applicable cable: 2 wire shielded cable  Sheath outside diameter 6 to 9mm    (Center conductor sectional area: 0.5 to 1.25mm2) Internal connection terminal block   Number of poles: 4 poles (+, -, Ground, NC)   Applicable crimp terminal: Round bare terminal, R1.25-3 (Nominal size)

-10 to 60℃, 5 to 85%RH (No freezing or condensation)Applicable Standard: EN61326/1997, A1/1998, A2/2001Permanently stored by EEP-ROM (Nonvolatile memory)

-20 to 70℃, 35 to 85%RH (No freezing or condensation)

Approx. 520g

10 to 150Hz, Multi-amplitude 0.7mm (60Hz or lower)Acceleration: 50m/s2 (60Hz or higher)Vibrating direction: x, y, z (2.5 hours for each)Impact acceleration: 100m/s2Impact direction: x, y, z (3 times into forward and backward directions for each)50V DC 100MΩ or higherIt is possible to install in outdoors. (Avoid the direct sunlight)

FluidPressure rangeAllowable maximum pressure

Power sourceOutput

Pressure output accuracy

Pressure display accuracyRange of guaranteed accuracy

Pressure output adjustment range

Numeric display

Unit display

Setting

Connection fitting

Wetted parts material

Casing protection structure

Mounting system

Cable connection

Memory protection

Operating temperature and humidityApplicable Standard

Storage temperature and humidityResistance to vibration

Resistance to shock

Insulation resistanceMounting locationWeight

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

3

Page 4: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

KJ91 Pressure Transmitter

Hazardous area

Item DescriptionTechnology Institution of Industrial Safety Intrinsically safe explosion-proof construction approved product

Safety barrier (Safety area)

The specifications of the recommended safety barrier (insulated barrier) which is combined with the KJ91 pressure transmitter are shown in the table below.

Item Description

Type approval number

  Exia   ⅡC    T4                Temperature class           Gas group      Technological standard intrinsically safe explosion-proof construction

Intrinsic safety explosion-proof construction type

Allowable voltage of intrinsically safe circuit (Ui): 28VAllowable current of intrinsically safe circuit (Ii): 93mAAllowable power of intrinsically safe circuit (Pi): 651mWInternal inductance of intrinsically safe circuit (Li): 0.47mHInternal capacitance of intrinsically safe circuit (Ci): 0.067μFAmbient temperature: 60℃

Safety maintenancerating

Allowable inductance: 2mHAllowable capacitance: 0.015μF

External transmission cable

500V AC, 1min.Withstand voltage

Matched to IP20 (With cover open)The setting switches can be operated by opening the cover

Container protectionclass

・Pepperl + Fuchs K.K. KFD2-STC4-Ex1 No. TC16232 Exia ⅡC

・Cooper Industries Japan K.K. MTL5541 No. TC19435 Exia ⅡC

Type approval number

No. TC17267

No. TC17346

No. TC17347

Pressure range (MPa)

0 to 70, 100, 120

0 to 5, 10, 20, 35, 50

-0.1 to 0.1, 0.2, 0.3, 0.5, 10 to 0.3, 0.5, 1, 2, 3.5

*The safety barrier can be selected by the customer.

*Type A intrinsic safety ground work is unnecessary

Safety maintenance rating of KJ91 Combination condition Safety maintenance rating of safety barrier

Allowable voltage of intrinsically safe circuit (Ui) ≧

Maximum voltage of intrinsically safe circuit (Uo)

Allowable current of intrinsically safe circuit (Ii) Maximum current of intrinsically safe circuit (Io)

Allowable power of intrinsically safe circuit (Pi) Maximum power of intrinsically safe circuit (Po)

Parameters of KJ91 and wiring Combination condition Parameters of safety barrier

Input inductance of KJ91 (Li) + Inductance of the wiring (Lw) ≦

Allowable inductance intrinsically safe circuit (Lo)

Input capacitance of KJ91 (Ci) + Capacitance of the wiring (Cw) Allowable capacitance intrinsically safe circuit (Co)

Combination of conditions related to safety rating

Combination of conditions on parameters

ManufacturerTypeType approval numberIntrinsic safetyexplosion-proofconstruction type

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

Specification of intrinsically safe explosion-proof construction

4

Page 5: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

Item Description

Gas or Liquid (Not corrosive to the wetted material) Liquid temperature range: -10 to +70℃

0 to 1, 2, 5, 10, 20, 50, 100kPa±1, ±2, ±5, ±10, ±20, ±50kPa

Single withstand pressure: 700kPa, Double withstand pressure: 2MPa, Negative pressure side: -90kPa (5kPa or higher, ±2kPa or higher)Single withstand pressure: 200kPa, Double withstand pressure: 2MPa, Negative pressure side: -90kPa (2kPa or lower, ±1kPa)

24V DC±10%

4 to 20mA DC (2 wire system, Output range: 3.2 to 20.8mA DC)Responsiveness: 100ms (With no filter setting) Resolution: 0.1%F.S. Load resistance: 500Ω maximum

±0.5%F.S. at 23℃ (5kPa or higher, ±2kPa or higher)±1%F.S. at 23℃ (2kPa or lower, ±1kPa)

Operating temperature range (-10 to 60℃) ±1% F.S. or lower (5kPa or higher, ±2kPa or higher) ±2% F.S. or lower (2kPa or lower, ±1kPa)

Zero point: -10 to 110% of the full span (To differential pressure range)Span point: -10 to 110% of the full span (To differential pressure range)

± (0.5%F.S.+1 digit) or ± (1.0%F.S.+1 digit) at 23℃ (It follows differential pressure output accuracy)

6 digits LCD: (Character height: 10mm, with LED backlight)Differential pressure display, Scaling display*: 4 LCD digits maximum, display cycle 500msIntegrated volume display: 6 LCD digits maximum

LCD bar display (With LED backlight)Differential pressure unit: kPa, Linear unit: Arbitrary setMomentary flow rate display: m3/h, L/min, arbitrary setIntegrated volume: m3, ×10m3, arbitrary set

With internal key switches (Mode, ▲, ▼)Scaling function: Linear and momentary flow rate display / outputFilter function: Moving average time interval, select from none, 2, 4, 8 and 16 secondsLoop check function: Arbitrary setting output (4 to 20mA DC)Zero adjustment function: Differential pressure sensor zero adjustment

25.4mm conversion fitting (Rc1/4, with equalizing valve, SCS14)Tube conversion fitting with valve (Tube diameter 6mm, SUS316)54mm conversion fitting (SCS14)

Diaphragm: SUS316LBody: SUS316O-ring: Fluoro rubber (JIS type 4 D)Drain seal: Alumina ceramicSealed liquid: Silicone oil

IP65 (Casing material: Aluminum die cast)

Direct mounting, Panel mounting (Option), 2B pipe mounting (Option)

Upper inlet connection, Lower inlet connection

Right side (Standard), Left side

DIN terminal type: Outlet port cable gland   Applicable cable: 2 wire shielded cable  Sheath outside diameter 6 to 9mm     (Center conductor sectional area: 0.5 to 1.25mm2) Internal connection terminal block   Number of poles: 4 poles (+, -, Ground, NC)   Applicable crimp terminal: Round bare terminal, R1.25-3 (Nominal size)

Permanently stored by EEP-ROM (Nonvolatile memory)

Applicable Standard EN61326/1997, A1/1998, A2/2001

-10 to 60℃, 35 to 85%RH (No freezing or condensation)

-15 to 65℃, 35 to 85%RH (No freezing or condensation)

±2.0%F.S. /MPa (kPa)±1.0%F.S. /MPa (2kPa, ±1kPa)±0.5%F.S. /MPa (5kPa, ±2kPa or higher)

At zero point 90° in front behind the element vertical reference line: ±(0.1%F.S.+1 digit) at 23℃At zero point 90° to the right and left: ±150Pa maximum at 23℃

Vertical with respect to display

*Linear or instantaneous flow (Square root) scale marking is available.

Fluid

Differential pressurerange

Allowable maximum pressure

Power source

Output

Differential pressureoutput accuracy

Differential pressuredisplay accuracy

Range of guaranteed accuracy

Differential pressure output adjustment range

Numeric display

Unit display

Setting

Connection fitting (Option)

Wetted parts material

Casing protection structure

Mounting system

Cable connection

Outlet for electric wire

Cable connection

Memory protection

Applicable Standard

Operating temperature and humidity

Storage temperature and humidity

Basic pressure effect

Inclination effect

Mounting posture

KJ92 Differential Pressure Transmitter

General specification 1

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

5

Page 6: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

KJ92 Differential Pressure Transmitter

General specification 2

Hazardous area

Item Description

No. TC17268Technology Institution of Industrial Safety Intrinsically safe explosion-proof construction approved product

Type approval number

  Exia   ⅡC    T4                Temperature class           Gas group      Technological standard intrinsically safe explosion-proof construction

Intrinsic safety explosion-proofconstruction type

Allowable voltage of intrinsically safe circuit (Ui): 28VAllowable current of intrinsically safe circuit (Ii): 93mAAllowable power of intrinsically safe circuit (Pi): 651mWInternal inductance of intrinsically safe circuit (Li): 1mHInternal capacitance of intrinsically safe circuit (Ci): 0.063μFAmbient temperature: 60℃

Safety maintenance rating

Allowable inductance: 2mHAllowable capacitance: 0.015μF

External transmission cable

Matched to IP20 (With cover open)The setting switches can be operated by opening the cover

Container protectionclass

500V AC, 1min.Withstand voltage

Item Description

Approx. 670g

10 to 150Hz, multi-amplitude 0.7mm (60Hz or lower)Acceleration: 50m / s2 (60Hz or higher)Vibrating direction: x, y, z (2.5 hours for each)

Impact acceleration: 100m / s2Impact direction: x, y, z (3 times into forward and backward directions for each)

50V DC 100MΩ or higher

It is possible to install in outdoors. (Avoid the direct sunlight)

Safety barrier (Safety area)The specifications of the recommended safety barrier (Insulated barrier) which is combined with the KJ92 differential pressure transmitter are shown in the table below.

 Item Description

*The safety barrier can be selected by the customer.

*Type A intrinsic safety ground work is unnecessary

・Pepperl + Fuchs K.K.

KFD2-STC4-Ex1

No. TC16232

Exia ⅡC

・Cooper Industries Japan K.K.

MTL5541

No. TC19435

Exia ⅡC

Safety maintenance rating of KJ92 Combination condition Safety maintenance rating of safety barrier

Allowable voltage of intrinsically safe circuit (Ui) ≧

Maximum voltage of intrinsically safe circuit (Uo)

Allowable current of intrinsically safe circuit (Ii) Maximum current of intrinsically safe circuit (Io)

Allowable power of intrinsically safe circuit (Pi) Maximum power of intrinsically safe circuit (Po)

Parameters of KJ92 and wiring Combination condition Parameters of safety barrier

Input inductance of KJ92 (Li) + Inductance of the wiring (Lw) ≦

Allowable inductance intrinsically safe circuit (Lo)

Input capacitance of KJ92 (Ci) + Capacitance of the wiring (Cw) Allowable capacitance intrinsically safe circuit (Co)

Combination of conditions related to safety rating

Combination of conditions on parameters

Resistance to vibration

Resistance to shock

Insulation resistance

Mounting location

Weight

Manufacturer

Type

Type approval number

Intrinsic safety explosion-proof construction type

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

Specification of intrinsically safe explosion-proof construction

6

Page 7: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

Bracket t2.0

80 70

60

70 4-φ4.5Bracket t2.0

8070

60

704-φ4.5

Unit: mm

《Direct mounting》Right side (Outlet for electric wire) For panel mounting

《Direct mounting》Left side (Outlet for electric wire)

《Panel mounting》Right side (Outlet for electric wire)

Others

KJ91

kPaMPaNAGANO KEIKI0

KJ91

kPaMPaNAGANO KEIKI0

Outlet for electric wire Upper side Outlet for electric wire Lower side

《Panel mounting》Left side (Outlet for electric wire)

KJ91-1□□

KJ91-5□□

KJ91-2□□ KJ91-6□□

KJ91-17□KJ91-1P□

(27)

(104)

12

3-M4

Air inlet port

Air inlet port

46

20

25

10

67

(20)

(120)

φ65

(92)

41.5

φ6

5

φ3

KJ91

kPaMPaNAGANO KEIKI0

KJ91

kPaMPaNAGANO KEIKI0

Detailed drawing of air inlet port(5MPa or lower)

Back view

15

 Pressure inlet Rc1/4G1/4 Female screw Conforming cable diameter: 6 to 9mm

DIN terminal type

22x25.4 Hex.

*Besides, it is possible to install like the fig. Please ask about this. Note) Upper side becomes equal to 10MPa or higher.  *It is possible to specify the direction of the pressure connection mouth. (Right, Left, Upper, Lower side)

Air inlet port

(120)

(55)

67

KJ91

kPaMPaNAGANO KEIKI0

KJ91

kPaMPaNAGANO KEIKI0

(5MPa or lower)

(5MPa or lower)

(5MPa or lower)

Standard KJ91 Pressure Transmitter (DIN terminal type)

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

Dimensions 1

7

Page 8: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

Unit: mm

《Direct mounting》Right side (Outlet for electric wire)

《Panel mounting》Right side (Outlet for electric wire)

KJ91-3□□

KJ91-4□□(27)

(104)12

(92)

φ65

Pressure inlet

41.5

Cable length 2m (Standard)

φ6.2, Shielded cable

Plug

Connector

Air inlet port

(125)

67

KJ91

kPaMPaNAGANO KEIKI0

Air inlet port

22x25.4 Hex.

KJ91

kPaMPaNAGANO KEIKI0

Bracket t2.0

80 70

60

70 4-φ4.5

Connector, cable

With shielded cable (Standard)

Environmentaltemperature Cross-section area (mm2)

ConductorConstruction (Quantity/mm)

Cable outer diameter (mm)

-20 to 60℃

-20 to 105℃

-40 to 80℃

0.2

0.3

0.3

7/0.18

12/0.18

12/0.18

φ6.2

φ6.2

φ6.0

With heat resistant cable

With cold resistant cable

Connector: TC1108-12A10-7F (Water proof type) (Made by Tajimi Electronics Co., Ltd.)

46

15

φ6

5

φ3

Detailed drawing of air inlet port(5MPa or lower)

*It is possible to specify the direction of the pressure connection mouth. (Right, Left, Upper, Lower side)

(5MPa or lower)

(5MPa or lower)

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

Standard KJ91 Pressure Transmitter (Connector Type)

Dimensions 2

8

Page 9: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

Bracket t2.0

80 70

60

70 4-φ4.5Bracket t2.0 60

704-φ4.5

Unit: mm

《Direct mounting》Right side (Outlet for electric wire) For panel mounting

《Direct mounting》Left side (Outlet for electric wire)

《Panel mounting》Right side (Outlet for electric wire)

Others

《Panel mounting》Left side (Outlet for electric wire)

KJ91-1□H

KJ91-5□H

KJ91-2□H KJ91-6□H

KJ91-1PH KJ91-1UH

(27)

(104)

12

3-M4

46

20

25

10

67

(20)

(120)

φ65

(92)

41.5

KJ91

kPaMPaNAGANO KEIKI0

KJ91

kPaMPaNAGANO KEIKI0

Back view

15

  Pressure inlet G1/4 Female screw9/16-18UNF Female screw

Conforming cable diameter: 6 to 9mmDIN terminal type 22x25.4Hex.

KJ91

kPaMPaNAGANO KEIKI0

KJ91

kPaMPaNAGANO KEIKI0

*Besides, it is possible to install like the fig. Please ask about this.  *It is possible to specify the direction of the pressure connection mouth. (Right, Left, Upper, Lower side)

Outlet for electric wire Upper side Outlet for electric wire Lower side

(120)

(55)

67

KJ91

kPaMPaNAGANO KEIKI0

KJ91

8070

kPaMPaNAGANO KEIKI0

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

For high pressure hydrogen KJ91 Pressure Transmitter (DIN terminal type)

Dimensions 3

9

Page 10: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

KJ92 Differential Pressure Transmitter

Dimensions 4

◎Conversion fitting (Option)●Tube conversion fitting with valve (With 25.4mm conversion fitting)

Unit: mm

φ6

L sidevalve

H sidevalve

Fully opened (147)mm

50

130

25.4

(193)

60

120

4-φ5.5

●54mm conversion fitting (Mounting system: Direct mounting only)

4-7/16-20UNF85.5

55

41.2

54

61.2

●25.4mm conversion fitting

8.545.4

25.4

35

1421

21Hex.2-Rc1/4

Equalizingvalve

Bracket t2.0

(85)

587492

φ65

35

113.6

6052.5

120

130

5060

Drain outlet

4-φ5.5

Panel mounting (With 25.4mm conversion fitting)Lower inlet connection Right side (Outlet for electric wire)

Lower inlet connection Left side (Outlet for electric wire) Upper inlet connection Left side (Outlet for electric wire)

Equalizingvalve

Rc1/4High pressure sideconnection (H)

Rc1/4Low pressure sideconnection (L)

Bracket t2.0

587492

φ65

113.6

120

130

5060

4-φ5.5

52.5

60

22

35

Drain outlet

Upper inlet connection Right side (Outlet for electric wire)

Equalizing valve

Rc1/4High pressure sideconnection (H)

Rc1/4Low pressure sideconnection (L)

OPTION

(85)

KJ92-212

KJ92-211

KJ92-612 KJ92-611

KJ92-222

67

(20)

(120)

(76)

0 NAGANO KEIKI

KJ92

0 NAGANO KEIKI

KJ92

Conforming cable diameter: 6 to 9mm

DIN terminal type

67

(20)

(120)

(76)

0 NAGANO KEIKI

KJ92

Conforming cablediameter: 6 to 9mm

DIN terminal type

4-φ5.5Bracket t2.0

(76)60

50

130

120

(55)

67(120)

KJ92

NAGANO KEIKI0

4-φ5.5Bracket t2.0

(76)60

50

130

120

(55)

67(120)

KJ92

NAGANO KEIKI0

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

10

Page 11: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

Function

Panel display

①LCD display The bright and clear LED backlight ensures excellent visibility in a dark place or at night.②Scaling Pressure linearly converted to an arbitrary physical quantity and displayed/output.③Zero adjustment The zero point at 4 to 20mA DC can be adjusted by key operation.④Loop check Without applying pressure, 4 to 20 mA DC can be output arbitrarily. This makes maintenance easy.⑤Filter Pulsations and other pressure changes can be smoothened by moving averages to reduce display fluctuations.⑥Holding display Both the maximum value (Peak) and the minimum value (Bottom) can be indicated.

Unit of pressure

Pressure displayLinear scaling display

ScalingUnit of arbitrary

MODE key DOWN key UP key

KJ91 Pressure Transmitter

Panel display

①LCD display The bright and clear LED backlight ensures excellent visibility in a dark place or at night.②Scaling Differential pressure linearly converted to an arbitrary physical quantity and displayed/output. The square root of the differential pressure is extracted and the instantaneous flow is displayed and output③Zero adjustment Zero point at 4 to 20mA DC can be adjusted by key operation.④Loop check Without applying pressure, 4 to 20 mA DC can be output arbitrarily. This makes maintenance easy.⑤Filter Pulsations and other differential pressure changes can be smoothened by moving averages to reduce display fluctuations.⑥Integrated volume display The integrated volume is displayed form independently from or alternately with the scaling.

Momentary flow rateUnit of standard

Unit of differential pressure

Integrated volumeUnit of standard

Scaling display (Linear, Momentary flow rate),Integrated volume display

Differential pressure display,Scaling display (Linear, Momentary flow rate),Integrated volume display

KJ92 Differential Pressure Transmitter

MODE key DOWN key UP key

Integrated volumeUnit of arbitrary

CH+ CH-

kPaMPa

M

KJ91

NAGANO KEIKI

CH+ CH-

kPa m3/h L/min

×10m3m3

M

KJ92

NAGANO KEIKI

11

Page 12: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

Wiring

Safety barrier (Insulated barrier)KJ91, 92

General device

1

3

1

2

8

7

14

15

Power supply20 to 35V DC

Receivergauge

KFD2-STC4-Ex1

+

+

++

Safety barrier (Insulated barrier)

2

1

12

11

14

13

MTL5541

+

+

+

--E

Safety areaHazardous area

+

+

3

2

1

Shield cable

Terminal blockPlug

Gasket

Terminal block Socket

ScrewBody (KJ91)

Cable gland

・Example of gas or steam which can apply Exia ⅡC T4 (Within bold-line rectangle)

T1

IIA

IIB

IIC

T2 T3 T4 T5 T6GroupTemperature

class

Acetone

Ammonia

Carbon monoxide

Ethane

Propane

Methanol

Methane

Ethanol

1-butanol

Butane

Ethylene

Ethylene oxide

Hexane

Gasoline

Oil naphtha

Coal tar naphtha

DME

Hydrogen

Water gas

Coal gas

Acetylene

Acetaldehyde

Ethyl ether

Ethyl methyl

Ether

Carbon bisulfide Nitric acid ethyl

・Classification of applicable to hazardous area (Whole range) ・Ignition point of gas or steam which T4 can apply (Within bold-line rectangle)

Applicable temperature class

Higher than 450℃

Higher than 300℃

Higher than 200℃

Higher than 135℃

Higher than 100℃

Higher than 85℃

Ignition point of gas or steam

T1 T2 T3 T4 T5 T6

T2 T3 T4 T5 T6

T3 T4 T5 T6

T4 T5 T6

T5 T6

T6

Hazardousarea Contents

Zone 0

Zone 1

Zone 2

Reference data

Wiring of DIN type terminal

1 Power source +

2 Power source -

3 N.C.

  Earth (E)

A place where hazardous atmosphere iscontinuously present or present for a longperiod under ordinary circumstances.

A place where hazardous atmosphere islikely to occur under ordinary circumstances.

A place where hazardous atmosphere islikely to occur under abnormal circumstances.

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

12

Page 13: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

Standard KJ91 Pressure Transmitter (DIN terminal type)

Please specify the model number, each specs and the range for ordering.Model number configuration

Model

K J 9 1 1 11 0 0①Pressure Transmitter

(DIN terminal type)② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪ ⑫ ⑬ ⑭ ⑮

Selective spec.Model number Additional spec. (Option)

Please specify applicablerange code as well aspressure range.

1RightOutlet for electric wire

Mounting Pressure Connection

Direct mounting

Mounting system①

2 Panel mountingA Direct mountingB Direct mountingC

5Left

6GHJ Direct mounting

LowerLowerRightUpperLeft

*1

7 Rc1/4 (Standard)Connection *2fitting

②3 G3/8 (With Rc1/4+FJ12-373, option)4 G1/2 (With Rc1/4+FJ12-473, option)9 Rc1/2 (With Rc1/4+FJ10-973, option)P G1/4 Female screw (Option)

36

Diaphragm: SUS630 (17-4PH) Fitting: SUS316Wetted partsmaterial

③Diaphragm: Co-Ni alloy (High corrosion-proof use) Fitting: SUS316

0Outlet forelectric wire

0 NilTreatment⑪

1 Use no oil2 Use no water3 Use no oil & water

0 NilDocument⑮

1 Required(Please specify the desired documents separately) Submission drawings, instruction manual, test report (1 pc 1 copy) inspection / traceability certificate

DIN terminal type (Conforming electric wire diameter: 6 to 9mm)

0Cable kind⑨ Nil

1Output⑦ 4 to 20mA DC (2 wire system)

1Power source⑥ 24V DC ±10%

50MPa or lowercan be selected

2

Pressure range(MPa)

35

CEG

Pressure range Maximumdisplay value

1

6

-0.1 to 0.2MPa-0.1 to 0.3MPa-0.1 to 0.5MPa

-0.1 to 0.1MPa

-0.1 to 1.0MPa

JKLNQRSTUV

Whether or not available by accuracy±0.25%F.S. at 23℃ ±0.5%F.S. at 23℃

---○○-○○○○○○○○○---

○○○○○○○○○○○○○○○○○○

0 to 0.3MPa0 to 0.5MPa0 to 1MPa0 to 2MPa0 to 3.5MPa0 to 5MPa0 to 10MPa0 to 20MPa0 to 35MPa0 to 50MPa0 to 70MPa0 to 100MPa0 to 120MPa

0.2000.100

0.3000.5001.0000.3000.5001.0002.0003.505.0010.0020.0035.050.070.0100.0120.0

4Accuracy⑤ ±0.25%F.S. at 23℃

5 ±0.5%F.S. at 23℃

0 NilAdditional spec.⑩

1 Specify Diaphragm-Seal type (Please contact us separately)

0 Standard spec.Use⑫

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

*1 Standard is "Outlet for electric wire: right, Pressure Connection: lower"*2 Please contact us separately, concerning 9/16-18UNF

・Please contact us separately, concerning high corrosion resistance material.

Specify and order the recommended barrier separately.When using a barrier other than the recommended barrier,strictly observe the "Safety Maintenance Rating".

*Specify by code "X" if there is no applicable specification.

Treatment of wetted parts■Use no oil Oil used in manufacturing the gauges had been flushed out & no oil residue remained inside its wetted parts.■Use no water Water used in manufacturing the gauges had been flushed out & no water residue remained inside its wetted parts.■Use no oil & water Oil/Water used in manufacturing the gauges had been flushed out & no oil/water residue remained inside its wetted parts.

13

Page 14: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

Standard KJ91 Pressure Transmitter (Connector Type)

Please specify the model number, each specs and the range for ordering.Model number configuration

Model

K J 9 1 1 0 01①Pressure Transmitter

(Connector Type)② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪ ⑫ ⑬ ⑭ ⑮

Selective spec.Model number Additional spec. (Option)

*1 Standard is "Outlet for electric wire: right, Pressure Connection: lower"*2 Please contact us separately, concerning 9/16-18UNF

・Please contact us separately, concerning high corrosion resistance material.

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

3RightOutlet for electric wire

Mounting Pressure Connection

Direct mounting

Mounting system①

4 Panel mountingD Direct mountingE Direct mountingF

7Left

8KLM Direct mounting

LowerLowerRightUpperLeft

7 Rc1/4 (Standard)Connection *2fitting

②3 G3/8 (With Rc1/4+FJ12-373, option)4 G1/2 (With Rc1/4+FJ12-473, option)9 Rc1/2 (With Rc1/4+FJ10-973, option)P G1/4 Female screw (Option)

36

Diaphragm: SUS630 (17-4PH) Fitting: SUS316Wetted partsmaterial

③Diaphragm: Co-Ni alloy (High corrosion-proof use) Fitting: SUS316

0Outlet forelectric wire

0 NilTreatment⑪

1 Use no oil2 Use no water3 Use no oil & water

0 NilDocument⑮

1 Required(Please specify the desired documents separately) Submission drawings, instruction manual, test report (1 pc 1 copy) inspection / traceability certificate

Nil

1Cable kind⑨ With shielded cable 2m (Standard)

1Output⑦ 4 to 20mA DC (2 wire system)

1Power source⑥ 24V DC ±10%

*1

50MPa or lowercan be selected

2

Pressure range(MPa)

35

CEG

Pressure range Maximumdisplay value

1

6

-0.1 to 0.2MPa-0.1 to 0.3MPa-0.1 to 0.5MPa

-0.1 to 0.1MPa

-0.1 to 1.0MPa

JKLNQRSTUV

Whether or not available by accuracy±0.25%F.S. at 23℃ ±0.5%F.S. at 23℃

---○○-○○○○○○○○○---

○○○○○○○○○○○○○○○○○○

0 to 0.3MPa0 to 0.5MPa0 to 1MPa0 to 2MPa0 to 3.5MPa0 to 5MPa0 to 10MPa0 to 20MPa0 to 35MPa0 to 50MPa0 to 70MPa0 to 100MPa0 to 120MPa

0.2000.100

0.3000.5001.0000.3000.5001.0002.0003.505.0010.0020.0035.050.070.0100.0120.0

4Accuracy⑤ ±0.25%F.S. at 23℃

5 ±0.5%F.S. at 23℃

2 With heat resistant cable3 With cold resistant cable

0 NilAdditional spec.⑩

1 Specify Diaphragm-Seal type (Please contact us separately)

0 Standard spec.Use⑫

Please specify applicablerange code as well aspressure range.

Specify and order the recommended barrier separately.When using a barrier other than the recommended barrier,strictly observe the "Safety Maintenance Rating".

*Specify by code "X" if there is no applicable specification.

Treatment of wetted parts■Use no oil Oil used in manufacturing the gauges had been flushed out & no oil residue remained inside its wetted parts.■Use no water Water used in manufacturing the gauges had been flushed out & no water residue remained inside its wetted parts.■Use no oil & water Oil/Water used in manufacturing the gauges had been flushed out & no oil/water residue remained inside its wetted parts.

14

Page 15: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

For high pressure hydrogen KJ91 Pressure Transmitter (DIN terminal type)

Please specify the model number, each specs and the range for ordering.Model number configuration

Model

K J 9 1 1 11H 0 0 3①Pressure Transmitter

(DIN terminal type)② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪ ⑫ ⑬ ⑭ ⑮

Selective spec.Model number Additional spec. (Option)

1RightOutlet for electric wire Mounting Pressure Connection

Direct mounting

Mounting system①

2 Panel mountingA Direct mountingB Direct mountingC

5Left

6GHJ Direct mounting

LowerLowerRightUpperLeft

P G1/4 Female screwConnection fitting②

U 9/16-18UNF Female (Option) F250C or equivalent by Autoclave

H Diaphragm: SUH660 (A286)Fitting: SUS316LWetted parts

material

Please specify applicablerange code as well aspressure range.

1Outlet forelectric wire

3 Use no oil & waterTreatment⑪

0 NilDocument⑮

1 Required(Please specify the desired documents separately) Submission drawings, instruction manual, test report (1 pc 1 copy) inspection / traceability certificate

DIN terminal type (Conforming electric wire diameter: 6 to 9mm)

0Cable kind⑨ Nil

1Output⑦ 4 to 20mA DC (2 wire system)

1Power source⑥ 24V DC ±10%

*1 Standard is "Outlet for electric wire: right, Pressure Connection: lower"

Specify and order the recommended barrier separately.When using a barrier other than the recommended barrier,strictly observe the "Safety Maintenance Rating".

*Specify by code "X" if there is no applicable specification.

Treatment of wetted parts■Use no oil Oil used in manufacturing the gauges had been flushed out & no oil residue remained inside its wetted parts.■Use no water Water used in manufacturing the gauges had been flushed out & no water residue remained inside its wetted parts.■Use no oil & water Oil/Water used in manufacturing the gauges had been flushed out & no oil/water residue remained inside its wetted parts.

*1

Pressure range(MPa)

④ Pressure range Maximumdisplay value

RSTUV

Whether or not available by accuracy±0.25%F.S. at 23℃ ±0.5%F.S. at 23℃

○○---

○○○○○

0 to 35MPa0 to 50MPa0 to 70MPa0 to 100MPa0 to 120MPa

35.050.070.0100.0120.0

4Accuracy⑤ ±0.25%F.S. at 23℃

5 ±0.5%F.S. at 23℃

0 NilAdditional spec.⑩

7 [Standard] Air tightness test report (Helium leak test)Use

A Proof pressure, leak test report (Additional document)

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

15

Page 16: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

KJ92 Differential Pressure Transmitter

Please specify the model number, each specs and the range for ordering.Model number configuration

K J 9 2 1 1 1①Differential Pressure Transmitter

Model

② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪ ⑫ ⑬ ⑭ ⑮

Selective spec.Model number Additional spec. (Option)

1RightOutlet for electric wire Mounting

Direct mounting

Mounting system①

2 Panel mounting3

5Left

67 2B pipe mounting

0 NilConversion fitting②

1 25.4mm conversion fitting (Rc1/4) (With equalizing valve, option)2 Tube conversion fitting with valve (Option)3 54mm conversion fitting (Option) Direct mounting only can be serecled

1 Upper inlet connectionPressureconnection

③2 Lower inlet connection

R 0 to 1kPaDifferentialpressure range

S 0 to 2kPaT 0 to 5kPaU 0 to 10kPaV 0 to 20kPaW 0 to 50kPaX 0 to 100kPaF ± 1kPa

Range Maximum display value

G ± 2kPaH ± 5kPaJ ±10kPaK ±20kPaL ±50kPa

1.0002.005.0010.0020.050.0100.0±1.00±2.00±5.00±10.0±20.0±50.0

Accuracy (Standard)

±1.0%F.S. at 23℃

±0.5%F.S. at 23℃

±1.0%F.S. at 23℃

±0.5%F.S. at 23℃

5Accuracy⑤ ±0.5%F.S. at 23℃ (5kPa or higher, ±2kPa or higher)

7 ±1.0%F.S. at 23℃ (2kPa or lower, ±1kPa)

1Outlet for electric wire

⑧ DIN terminal type(Conforming electric wire diameter: 6 to 9mm)

1Output⑦ 4 to 20mA DC (2 wire system)

1Power source⑥ 24V DC ±10%

0 NilTreatment⑩

1 Use no oil2 Use no water3 Use no oil & water0 Nil

Documents⑮

1 Required(Please specify the desired documents separately.) Submission drawings, instruction manual, test report (1 pc 1 copy) inspection / traceability certificate

*Specify a pressure Connection by ③

Specify and order the recommended barrier separately.When using a barrier other than the recommended barrier,strictly observe the "Safety Maintenance Rating".

Please specify applicablerange code as well asdifferential pressure range and engineering unit.

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

*Specify by code "X" if there is no applicable specification.

Treatment of wetted parts■Use no oil Oil used in manufacturing the gauges had been flushed out & no oil residue remained inside its wetted parts.■Use no water Water used in manufacturing the gauges had been flushed out & no water residue remained inside its wetted parts.■Use no oil & water Oil/Water used in manufacturing the gauges had been flushed out & no oil/water residue remained inside its wetted parts.

16

Page 17: Model for hydrogen KJ91 92 is added to KJ91 Intrinsically ...products.naganokeiki.co.jp/assets/files/1079/E-KJ91_92_H_17P_201… · Features of sensor KJ91・92 Intrinsically Safe

Introduction of related products

GC51 Pressure Transmitter

GC51 Pressure Transmitter (Explosion proof type KJ91)

NV80 Pitot Tube Type Digital Flow meter NV81/82/83 Orifice Type Digital Flow meter

■ Non-explosion proof type

◎ Pressure range

■ Flow meter

GC52Differential Pressure Transmitter (Explosion proof type KJ92)

-0.1 0 0.1 1 10 100 (MPa)

-100 -10 -1 0 1 10 100

120

100

-0.1 1

-50 50

(kPa)

0 to 1kPa→0 to 100kPa-1 to 1kPa→-50 to 50kPa

0 to 0.3MPa→0 to 120MPa-0.1 to 0.1MPa→      -0.1 to 1MPa

Gauge pressure

Compound

Differential pressure

Differential pressure"(± Range)"

GC52 Differential Pressure Transmitter

KJ91・92Intrinsically Safe Explosion-Proof Construction Pressure & Differential Pressure Transmitter

17