modeling a pcm storage unit for solar thermal cooling in masdar city
DESCRIPTION
Modeling a PCM storage unit for solar thermal cooling in Masdar City. Irene Rubalcaba Montserrat RSC Members: Dr. Matteo Chiesa Dr. Peter Armstrong Dr. Ali Abbas. Solar cooling system. Charging mode. Solar Field. Discharging mode. Generator. Cooling System. Heat Exchanger. - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/1.jpg)
1
Modeling a PCM storage unit for solar thermal cooling in Masdar City
Irene Rubalcaba Montserrat
RSC Members:
Dr. Matteo Chiesa
Dr. Peter Armstrong
Dr. Ali Abbas
![Page 2: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/2.jpg)
2
Solar Field Charging modeDischarging mode
PCM Storage
Unit
Drum
Condenser
EvaporatorPump
Heat Exchanger
Generator
Pump Absorber
Cooling System
Solar cooling system
![Page 3: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/3.jpg)
3
Power profile from the Beam Down [kW]
6:43 7:55 9:07 10:19 11:31 12:43 13:55 15:07 16:19 17:31 18:430
20
40
60
80
100
120
140
Time [hrs]
Q [
kW]
21st of March 2011
![Page 4: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/4.jpg)
4
Supply and demand disparitystorage opportunity
4:48 AM 7:12 AM 9:36 AM 12:00 PM 2:24 PM 4:48 PM 7:12 PM 9:36 PM0
20
40
60
80
100
120
140
Cooling load- 4 Buildings Power from the Beam Down
Q [k
W]
![Page 5: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/5.jpg)
5
Supply and demand disparitystorage opportunity
4:48 AM 7:12 AM 9:36 AM 12:00 PM 2:24 PM 4:48 PM 7:12 PM 9:36 PM0
20
40
60
80
100
120
140
Cooling load- 4 Buildings Power from the Beam Down
Q [k
W]
Extra heat to store
Storage use
![Page 6: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/6.jpg)
6
STORAGE MODELINGGeometry
CYLINDRICAL STORAGE COMPARTMENT
Length=11m
COPPER PIPELength=11m
Outside Diameter= 0.012mThickness=1mm
![Page 7: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/7.jpg)
7
Modeling phase change using COMSOL
Melting range = ΔTm
ΔTm = 490 to 493 K
Cp= 1330 + Latent heat/ΔT
FULLY SOLIDCp = 1330 [J/KgK]
FULLY LIQUIDCp = 1330 [J/KgK]
![Page 8: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/8.jpg)
• Problem Type: Transient Thermal Fluid• Model Used: Time depending - Non Isothermal flow
Incompressible Navier- Stokes:
Heat Transfer by conduction and convection:
• Geometry is considered 2D axial symmetry
Numerical modeling
![Page 9: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/9.jpg)
Maximum Energy Storage Capacity:
400 [MJ] + Sensible Heat
2D Axial symmetry model
![Page 10: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/10.jpg)
Enthalpy Temperature
Numerical Results for 44 tubes after 20700 seconds - 5.75 hr
![Page 11: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/11.jpg)
11
Mesh Sensitivity
Mesh Type Extremely Fine
Normal Coarser
Number of elements
536,068 88,946 82,327
![Page 12: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/12.jpg)
No fins 5 Fins 10 Fins 20 Fins
Effect of fins
![Page 13: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/13.jpg)
13
Effect of inlet velocity
v= 0.0932 m/s v= 0.0832 m/s
v= 0.07992 m/s
v= 0.07629 m/s
![Page 14: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/14.jpg)
14
Solidification temperature outlet
2:24:00 PM 3:36:00 PM 4:48:00 PM 6:00:00 PM 7:12:00 PM 8:24:00 PM0
100
200
300
400
500
600
Storage discharge temperature[K]
Temp out
time
Tem
per
atu
re [
K]
![Page 15: Modeling a PCM storage unit for solar thermal cooling in Masdar City](https://reader035.vdocuments.net/reader035/viewer/2022070418/5681575c550346895dc5067f/html5/thumbnails/15.jpg)
81 tubes
L =11m
ri= 1 cm
r0= 3 cm
Total volume= 5.7m3
Total PCM mass = 4.209 tons
Maximum storage capacity
= 400[ MJ] + sensible heat
Symbol Description Value Units
Latent heat of fusion of the PCM 95000
Density of the PCM 1880
Specific heat of the PCM 1330
Thermal conductivity of the PCM
4
αpcm Thermal diffusivity
Melting Temperature of the PCM
493 / 220 K / C
Material= KNO3-NaNO3(eu)
Final Design