MODpower Air Circuit Breakers

Sales 1300 NHP NHP nhp.com.auNHP Electrical Engineering Products Pty Ltd

POWER DISTRIBUTION AND PROTECTION

2

Contents

1. On receiving MODPower System1.1 Visual Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.2 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.3 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71.4 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

2. Understanding MODPower System2.1 Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112.2 Exploring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122.3 Racking-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152.4 Operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172.5 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

3. Installing MODPower System3.1 Mounting & Door cut-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203.2 Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303.3 Loading in Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493.4 Control Circuit Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

4. Accessories: Features & Mounting4.1 Cradle Mounted Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 554.2 Breaker Mounted Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

5. Protection & Control Units5.1 Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 755.2 Protection Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

6. Putting MODPower System in Operation6.1 Re-loading in panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 906.2 Checking ON-OFF operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 926.3 Testing (SIC and interlocks) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 936.4 Setting P&C unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 946.5 Trip simulation of P&C unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 986.6 MODpower ACB’s in Connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 996.7 Securing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

7. Maintenance schedule & Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

8. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116

3

CautionNon-observance of the safety instructions can result in severe personal injury or equipment damage.

Successful and safe operation of the equipment (including accessories) depends on proper handling, installation, operation and maintenance.

Before commencing with installation or maintenance,

- Disconnect power supply of the device

- Ensure that device cannot be accidentally restarted

- Verify isolation from supply and earthing

- Cover and enclose all neighboring live equipment

- Discharge spring

- Follow engineering instructions of the device concerned

- Before touching device, ensure you are free of electrostatic charge

Ensure that deviations of the mains and control voltages do not exceed the specified operating limits, as this may cause malfunction, dangerous operation and damage to product.

4

1.1 Visual Inspection

- Inspect the packaging for any signs of damage from transportation, contact NHP in case of a any damage.

- Check the labeling and ensure the size and ratings are as per order information.

5

1.2 Unpacking

For Fixed Breakers

Cut straps and remove nails.

Lift the carton and remove any accessories taped to the breaker or kept loose on the palette.

Remove Breaker mounting screws (4 nos.)

6

For Draw-Out breakers

Cut straps and remove nails.

Lift the carton and remove any accessories taped to the cradle or kept loose on the palette.

Remove Cradle fixing screws (M10) on all sides.

1

2

Remove Transportation cushion

7

1.3 Handling

For Fixed Breakers

CAUTIONHeavy equipment. Exercise proper care to avoid personal injury and equipment damage.

Lift the breaker using a crane. A special Lifting Handle is available (optional) to facilitate handling.

Frame 1 breakers can also be transported by 2 persons.

8

For Draw-out Breakers

Lift the breaker using hooks at specified places as shown above.

Frame 1 breakers can also be transported by 2 persons.

CAUTION Do not lift the breaker using Facia or Terminals.

9

1.4 Storage

CAUTIONStore the breaker in a cool, dry place, away from dusty/corrosive environment.

When cradle and breaker are not being used for a long time, pack them in the carton and store in a dry place.

10

Temp. Range : -5 to 70 °C.

CAUTIONDo not stack more than 4 breakers one above the other.

11

2.1 Identification

2a- Type designation for Electrical Charging device (ECD)2b- Operating voltage for ECD4a- Type designation for Under-voltage release (UVR)4b- Operating voltage for UVR5a- Type designation for Closing release (CR)5b- Operating voltage for CR6a- Type designation for Shunt release (SR/SRW)6b- Operating voltage for SR/SRW12- ON-OFF indication13- Spring status indication 29b- Rated Uninterrupted Current29c- Rated impulse withstand voltage29d- Utilization Category29e- Suitability for isolation29f- Standards compliance29g- Rated Service breaking capacity29h- Rated operational voltage29j- Rated short-time withstand current

29a

29b

29h

12

13

2a

6a4a 5a

6b5b4b

2b

29j

29g

29c

29d

29e

29f

12

2.2 Exploring

Facia

11- Shroud for ON-OFF Buttons

11a- OFF button

11b- ON button

18- OFF button locking

28- USERS’ identification location

29- Name plate

31- Cover for Protection & Control unit (P&C)

32- Facia fixing screw

11a

11b

11

18

28

29

31

32

13

Breaker

1- Protection & control unit

2- Electrical Charging Device

3a- Auxiliary Contacts

4- Undervoltage Release

4c- Undervoltage Release Controller

5- Closing release

6- Shunt Release

7- Ready-to-Close (Microswitch)

8b- Secondary Isolating Contacts on Breaker

10- Operation Counter

12- ON-OFF Indication

13- Spring Status Indication

14- Charging handle

21- Arc Chute

24b- Lifting location on breaker

33- Projections for resting breaker on cradle

33

24b

21 5

1

4

2

7

6 10

12

8b

3a

4c

13

14

14

Cradle

3e- Hole for Earthing Connection

3j- Jaw Contacts

8c- Secondary Isolating Contacts on Cradle

8e- Electrical Position Indication

15- Racking Handle

16- Smart Racking Shutter

16a- Padlock for Racking shutter

17- Position Indicator

19- Position Lock-1

20- Position Lock-2

22- Arc Shield

23- Rating Error Prevention

24- Lifting Locations (4 nos.)

24a- Additional Lifting Locations

25- Withdrawal Rails

26- Door Racking Interlock

27- Breaker Pull-out Handle

34- Guide for routing Control Wiring

35- Terminal Supports

36- Cradle Bottom cross-component

37- Cradle Top cross-component

38- Slot for placing breaker on Cradle

39- Safety Shutter

40- Door Interlock

201917

26

1615

2527

36

38

35

24

23

24

2237

34

39

8c 8e

3e

40

3j

16a

24a

24a

15

2.3 Racking-outFor D/O Breakers remove the transportation Cushion (2 Nos.) & its instruction label, before doing racking operation of the breaker.

Keeping OFF button (11a) pressed; open the Racking Shutter (16). In case Breaker is out of the panel or the panel door is open, gently press Racking Interlock (26) to defeat it.

Note: Once racking shutter is opened, the breaker can not be closed, even by an electrical closing command.

Rack-out the breaker to Disconnected position.

Note: After removing the racking handle (15), the racking shutter automatically recloses only in distinct “Connected” / “Test” and “Disconnected” positions (17). Hence, Breaker cannot be closed in any intermediate positions to ensure User safety.

CAUTIONExcessive, forceful Racking-out beyond Disconnected position may lead to Product damage.

Remove Transportation Cushion

Remove Caution Flap

12

Take out the handle

Insert the racking handle & rotate anticlockwise

16

Pull the breaker out using pull-out handles (27).

In Maintenance position, Breaker can be removed from the cradle by two persons (Fr.1) or by using a crane.

Please refer “1.3 Handling” on page 7

17

2.4 OperatingInitially, the Breaker is and Spring is

Charge the Main spring through multiple strokes of charging handle (14)

Now the Breaker is and Spring is

Push ‘ON’ button (11b) to close the breaker.

Now, the breaker is and spring has in this situation, spring can be charged again for next operation.

Breakers equipped with Undervoltage (4) cannot be normally closed unless the release is energized. NHP MOD power ACB’s Undervoltage release has a special feature, by which one can still check the operation.

Push ‘OFF’ button (11a) to trip the breaker.

Now, the Breaker is and Spring is

Arc Chute Interlock prevents closing of breaker, if any arc chute is missing or not secured properly

18

2.5 Technical Data

Common Parameters Unit Symbol

Rated Operational voltage at 50/60 Hz V Ue Upto 690

Rated Insulation voltage at 50/60 Hz V Ui 1000

Rated Impulse withstand voltage – Main circuit KV Uimp 12

Rated Impulse withstand voltage – Auxiliary circuit KV Uimp 4

No.of poles 3 & 4

Suitability for isolation Yes

Intrinsic degree of protection of breaker front IP53

Pollution degree suitability 3

Utilization category B

Compliance IS/IEC 60947-2, EN 60947-2, IEC 60497-2

H: Height

W: Width

D: Depth with flat terminals

19

Frame MP1 MP2 MP3

Rated Uninterrupted Current at 40deg.C

A 1250 1600 2000 2500 3200 4000

Rated Ultimate/Service S.C. Breaking Capacity (Icu=Ics)

415VAC

KA

65 80

550VAC 55 70

690VAC 50 55

Rated short Time Withstand Capacity (Icw)

0.5 sec

KA

65 65 80

1.0 sec 65 65 80

3.0 sec 36 42 50

Rated S.C Making Capacity (Icm)

415VAC

KA

143 176

550VAC 121 143

690VAC 105 121

Opening Timems

40

Closing Time 60

Mechanical Life with Maintenance

cycles 20000 15000 10000

Frequency of Operation-Mechanical cycles/hr 60

Electrical life without Maintenance*

cycles 8000 10000 5000 2000

Frequency of Operation-Electrical cycles/hr 40 20

Dimensions (Fixed)

W (3P)

mm

347

D 324

H 396

Dimensions (Withdrawable)

W (3P)

mm

347 447 647

W (4P) 447 581 847

D 421 421 431

H 433 433 433

Pitch-Top/Bottom Terminals

mm 105

Pitch-Phase to Phase/phase to Neutral

mm 100 133 200

Terminal Width mm 65 65 165

Net Weight

Fixed 3P

kg

37 46

W/D 3P 68 77 82 121

W/D 4P 81 91 98 163

*with maintenance, electrical=mechanical

20

3.1 Mounting & Door cut-out

MODpower ACB Door Flange Dimensions

IP40 Gasket MP1 Fixed

Cutout for Main FaciaDOOR EDGE

Bottom Corner of Breaker

321

13

45

341

8 HOLES-DIA.5

17110.5

*70min.

10.5 171

181

181

21

Overall Flange dimensions W=371, H=391, 25mm around cutout

IP40 Gasket MP1,2,3 Withdrawable Left Side Hinge

Cutout for Door Interlock DeviceSee Detail ‘Z’Cutout for Main Facia

DOOR EDGE

8 HOLES-DIA.5

17110.59.2

*70min.

10.5 171

208.

520

8.553

.5

321 13

396

10

Bottom Corner of Breaker

22

Right Side Hinge

Frame Poles Dimension ‘X’

MP1 3 311.8

4 411.8

MP2 3 411.8

4 545.8

MP3 3 611.8

4 811.8

Overall Flange dimensions W=371, H=446, 25mm around cutout

Detail Z

Ø16.5 +0.1-0.1

Ø16.5 +0.10

8

Cutout for Door Interlock DeviceSee Detail ‘Z’

Cutout for Main Facia

321

X

13

396

10

Bottom Corner of Breaker

53.5

23

MP1 3 P- Fixed

A Mounting holes suitable for M10/Equivalent BS bolt

112

347335

430

300

min

AA

6 6142

324

300

min

A

7

2525

Panel Door

24

MP1 3P- Withdrawable

A Mounting holes suitable for M10/Equivalent BS bolt

347

25049.5 47.5

62.4

433

300

min

*

A

421

250280

300

min

*

A

7

25.5

Panel Door

DISCONNECTED

TEST

16

35

(47.5)(250)(2

50)

(280

)

(62.

4)

Use this mounting hole

Use this mounting hole

Use any one of these two mounting holes

Use any one of these two mounting holes

25

MP1 4P - Withdrawable

A Mounting holes suitable for M10/Equivalent BS bolt

447

25010049.5 47.5

62.4

433

300

min

*

A A

421

250280

300

min

*

A

7

25.5

Panel Door

DISCONNECTED

TEST

16

35

(47.5)(250)(100)

(250

)

(280

)

(62.

4)

Use this mounting hole

Use any one of these two mounting holes

Use any one of these two mounting holes

Use any one of these two mounting holes

Use any one of these two mounting holes

26

MP2 3P - Withdrawable

A Mounting holes suitable for M10/Equivalent BS bolt

447

25010049.5 47.5

62.4

433

300

min

*

A A

421

250280

300

min

*

A

7

25.5

Panel Door

DISCONNETCTED

TEST

16

35

(47.5)(250)(100)(2

50)

(280

)

(62.

4)

Use this mounting hole

Use any one of these two mounting holes

Use any one of these two mounting holes

Use any one of these two mounting holes

Use any one of these two mounting holes

27

MP2 4P - Withdrawable

A Mounting holes suitable for M10/Equivalent BS bolt

581

25010049.5 47.5

62.4

433

300

min

*

A A

421

250280

300

min

*

A

7

25.5

Panel Door

DISCONNETCTED

TEST

16

35

49.5 (47.5)(250)(100)

(250

)

(280

)(6

2.4)Use this mounting hole

Use this mounting hole

Use any one of these two mounting holes

Use any one of these two mounting holes

Use any one of these two mounting holes

Use any one of these two mounting holes

28

MP3 3P - Withdrawable

A Mounting holes suitable for M10/Equivalent BS bolt

64725010049.5 47.5

62.4

433

300

min

*

A A

431

250280

300

min

*

A

7

35.5

Panel Door

DISCONNETCTED

TEST

16

35

(47.5)(250)(100)

(250

)

(280

)(6

2.4)

Use this mounting hole

Use this mounting hole

Use any one of these two mounting holes

Use any one of these two mounting holes

Use any one of these two mounting holes

49.5

Use any one of these two mounting holes

29

MP3 4P - Withdrawable

A Mounting holes suitable for M10/Equivalent BS bolt

(47.5)(250)(200) (100)(2

50)

(280

)(6

2.4)

Use this mounting hole

Use this mounting hole Use this

mounting hole

Use any one of these two mounting holes

Use any one of these two mounting holes

Use any one of these two mounting holes

Use any one of these two mounting holes

49.5

847

25010020049.5 47.5

62.4

433

300

min

*

A A A

431

250280

300

min

*

A

7Panel Door

DISCONNETCTED

TEST

16

3535.5

30

3.2 Termination

Terminal Adaptor:

Vertical Adaptors for frame 1 & 3

Horizontal & Vertical Adaptor for frame 2

Horizontal Adaptor for frame 3

For Frame-1, terminal adaptor installation. In Frame-3 use equalizer for vertical & a single adaptor for horizontal between two poles.

Installation of terminal adaptor for frames 2

31

For Fixed Breakers:

CAUTIONInadequate termination support may result in overheating & adverselt affect performance during short circuit conditions.

100MAX.

32

For Draw-out Breakers:With Universal Terminals

With Terminal Adaptor

* maintain adequate clearance between links as per applicable standards.

33

Terminal Dimensions

MP1 3P - Fixed

FRAME 1 A B C

400-1600 S 24 50 65

2000-2500 S 30 55 65

M12/ equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm

Holes (on both sides) for earthing connections by M10/equivalent BS bolt

Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 15 mm.

Bolt length

15347

100 100

M10

C

M10 bolts to be used for link termination Tightening torque: 3.0 kgfm

11

32

BB 10

512

2

41

A

32C

34

M12/ equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm

1569

6910

8.8

40

7463

27100 100

19

Ø12.9

35

M12/ equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm

276540

65

117.

5

74

100100

100 100

19

Ø12.9

15

63

36

MP1 3P - Withdrawable

Flat Terminals

Detail A

Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.

100

100

80.8

7263

100 100

2727

45

19

Ø12.9

100100

20

10.4

36

Ø12.536

14.5

Bolt length

37

M12 bolts to be used for link termination Tightening torque: 3.2 kgfm

Horizontal Terminals400A-2000A

100 73.5100

347

SEE DETAIL A

25.5

16

15

56.8 10

515

0

65

73.5100 100

347

105

150

36

Ø12.9

36

16

36

17.5

65

83.5

15

15

Ø12.9

38

Vertical Terminals400A-2000A

Vertical TerminalsFor 2500A-3P

M12/ Equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm

73.5100 100

105

65

150

36

27

36

17.5

36

15 65

347

Ø12.9

Ø12.9

1683.5

15

73.5100 100

105

140

36

36206590.565 Ø12.9

34716

98

15

2727

15

Ø12.9

39

MP1 4P – Withdrawable

Flat Terminals

Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.

Horizontal Terminals*

400A-2000A N/S/H

Adaptor – CL60963OOOO

SEE DETAIL A

105

150

73.5100100100

44716

25.5

15

3665

73.5100100100

105

150

36

Ø12.9

347

16

15

83.5

36

17.5

Ø12.9

15Bolt length

3665

14.5

(Ø12.5)M12

56.8

36

10.4

40

Vertical Terminals400A-2000A N/S/H

Adaptor – CL60963OOOO

** For 2500A REFER PAGE 3-25

Vertical TerminalsFor 2500A-4P

M12/ Equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm

All dimensions in mm

73.5100100100

105

65

150

36

2736

17.5

36

15 65

447

Ø12.9

Ø12.9

1683.5

15

73.5100100100

105

140

36

90.565 Ø12.9

44716

98

15

2727

15

Ø12.9

3620 65

41

MP2 3P – Withdrawable

Flat Terminals

Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.

Horizontal Terminals

Bolt length

25.5

1615

105

140

M12

3665

133.3 133.3 90

447

3636

77.2

77.2

105

140

133.3 133.3 90

447

75

98

1615

36

Ø12.9

20

15

90.5

42

Vertical Terminals

MP2 4P – Withdrawable

Flat Terminals

Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.

M12/ Equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm

36 20 20

3636

36133.3 133.3 90

447

105

140

1615

36

9898

2727

1590.5

Ø12.9

Bolt length

105

140

3677.2

3677.2

133.3133.3133.390

581

M12

3665

16

25.5

15

43

Horizontal Terminals

Vertical Terminals

98 36

105

140

133.3133.3133.3 90

581

3675

161515

36

90.520

Ø12.9

133.3133.3133.3 90

581

105

140

983620

1615

36

9898

2727

1590.5

Ø12.9

44

MP3 3P – Withdrawable

Flat Terminals

Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.

Horizontal Terminals

Vertical Terminals

Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.

Bolt length

105

179

100100100100100 73.5647

36165

3636

5656

Ø12.9

25.5

1615 Holes (on both sides) for Earthing connections by M10/equivalent BS bolt

10010010010010074.4

5835.5

647

6540

183

36

3665

165

Ø12.9

1615

15

2 HOLES-Ø12.9PITCH 27 mm

Bolt length

45

MP3 4P – Withdrawable

Flat Terminals

Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.

10010010010010074.4

647

1536165

Ø12.9

6540

183

36

5835.5

1615

2719

Ø12.9

Holes (on both sides) for Earthing connections by M10/equivalent BS bolt

Bolt length

100100100100100100100 73.5

847

105

HOLE-Ø12.9

365656

179

36165

16

31.7

11

15

Holes (on both sides) for Earthing connections by M10/equivalent BS bolt

46

Horizontal Terminals

VerticalTerminals

Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.

Bolt length

10010010010010010010073.5

847

6540

183 36

3665 165

Ø12.9

5835.5

1615

202 HOLES-Ø12.9PITCH 27 mm

100100100100100100 10073.5

847

1536 165Ø12.9

6540

183 36

5835.5

1615

2727

1919

Ø12.9

Holes (on both sides) for Earthing connections by M10/equivalent BS bolt

47

MODpower Ground Fault CT

For earth fault protection and protection of neutral against overloads, neutral CT is required. For 4-pole breakers, the CT is provided inside the breaker, to be used on 4 wire system whereas for 3-pole breakers, external CT is available separately.

It is important that with NHP’s MOD power system of breaker, special neutral CTs supplied by NHP are used.

Frame Size Rating

1, 2 & 3 400/630/800

1, 2 & 3 1000/1250/1600

(ref. “2.5 Technical Data” on page 18)

TERMINAL THICKNESS 15 mm.

Frame Size Rating

1 2000/2500

(ref. “2.5 Technical Data” on page 18)

TERMINAL THICKNESS 30 mm.

90

4065

Ø13

7219

19

4242

40

45.5

45.5

12.5 Ø13

7219

19

65

48

Frame Size Rating

2 & 3 2000/2500

3200/4000

(ref. “2.5 Technical Data” on page 18)

TERMINAL THICKNESS 30 mm.

Frame Size Rating

3 5000/6300

(ref. “2.5 Technical Data” on page 18)

TERMINAL THICKNESS 30 mm.

M12/ Equivalent bolts to be used for links termination. Tightening torque: 3.2 kgfm

All dimensions in mm.

2727

45.5

45.5

22.15 Ø13

7219

19

98.3

Ø13

7219

19

145

45.5

45.5

40404065

12.5

49

3.3 Loading in Panel

1

Pull-out the cradle Rails (27) & ensure that position indication (17) shows ‘DISCONNECTED’.

Load the breaker using crane. Even bottom trolley can be used.

3

Ensure that Breaker rests correctly in 2 slots on either side of cradle rail (39).

CAUTIONImproper loading of breaker may lead to personal injury and damage to product.

2

50

Gently push the breaker to DISCONNECTED position and close the Panel door.

If equipped with Rating Error Preventor (23), Cradle will not accept breaker of different rating.

5

Keeping the OFF button (11a) pressed, open the Racking Shutter (16). In case panel door is open, also gently depress Racking Interlock (26).

Rack-in the breaker to Service position. Two almost–simultaneous ‘click’ sounds confirm ‘CONNECTED’ position.

CAUTIONExcessive forceful racking-in beyond Connected position may lead to product damage.

4

6

51

2

3.4 Control Circuit ConnectionsNHP’s MOD power System of ACB’s Secondary Isolating Contacts (8) facilitate control circuit wiring with following features.

• Cradle SIC block slot & each breaker SIC slot is pre-defined and marked for specific connections.

• Breaker is supplied with SIC

• Every accessory comes pre-wired with breaker SICs. SIC location is printed on the wire for easy identification.

• Breaker SIC are click-fitted and hence, require no tools for fixing.

• SICs offer screwless wire connections, by simply using a connector as shown in the diagram.

• SICs can independently accept 2 wires for ease of terminating multiple wires. Wire specifications: Min 0.75mm2 & max 2.5mm2.

• After termination, control wires can be routed through guides provided in the cradle side plates.

CAUTIONWire bunch to be routed properly to avoid interference with Door interlock (40), if installed..

SICs & SIC Bridge

Quick and Easy Control Wiring

Ensure lug orientation with separations on topStrip Conductors

Tip Width 3 mm

52

Routing Control Wires

Position Indication:

1. All position SIC

2. Connected & Test position SIC

3. Connected position SIC

4. Additional Connected position indication

5. Test position SIC

6. Additional Test position indication

7. Disconnected position SIC

8. Additional Disconnected position indication

8 mm

1

2

4

5

6

7

8

3

Disconnected Test Connected

53

The above diagram gives a generic configuration for control termination on the breaker. For specific details, refer Connection diagram (pages 3-38 to 3-44) specific to the P&C unit installed in the breaker.

#for using electrical accessories with dc control supply. It is recommended to connect D1/A1/C1 to +ve and D2/A2/C2 to –ve.

# m indicates micro switch

54

AS+, AS-: 24V DC Power Supply

AL+ : TRIP ALARM+, TRIP ALARM-

This output can be connected to 5V-30V dc 150 mA Relay or any other indicating device which can give alarm for short circuit and Earth Fault trip.

D+: MOD A

D-: MOD B

N1: External Neutral CT

N2: External Neutral CT

M-G: MOD-GND

V0,V1,V2,V3: N R,Y,B, VOLTAGE I/P.

55

4.1 Cradle Mounted Accessories

Safety Shutter (39):

Function: To prevent inadvertent access to live terminals.

Features: One or individual pole can be padlocked during maintenance.

Tools required: Screw Driver (Blade length 300 mm, Tip width 8 mm)

Installation: Remove bolt on the bottom cross component (36). Click-fit the shutter on the top cross component (37) and refix the bolt on the bottom cross components. This process has to repeated for each pole.

Door Interlock (40):

Converting Door-interlock for RHS hinge

Function: Prevents opening of panel door in Connected & Test positions.

Features: it can be mounted on either side of the cradle and can be converted for RHS hinge doors by simply relocating 2 components.

Tools required: Philip head Screw driver (Tip no. 2), Ring spanner (size 13)

Installation: Door interlock comes in 2 parts, one to be fixed on the cradle and the other on the panel door. Door interlock is mounted inside the side plate of the cradle.

56

Assemble the interlock as shown.

Rest the rear end of the torsion spring on the SIC bridge, as shown.

Also assemble panel-door mounted part of door-interlock.

Cradle RH Side Plate Section views

Cradle RH Side Plate Section views

Cut-out for Door Interlock

57

Mechanical Interlock:Function: Mechanical Interlock is used for interlocking breakers as per the desired control scheme.

Features: it can be interlock upto 3 NHP MOD power breakers of Fixed/Drawout/Mixed versions. The breakers can be interlocked in vertical or horizontal configuration.

Possible mounting arrangements:

Cable length: 2 meters/3 meters/5 meters min. radius of cable bend: 70 mm

Type of Interlock Typical Circuit Interlocks possible

Schematic diagram

Two Incomers (2 I/C)

Two Incomers & One Buscoupler (2 I/C+1 B/C)

O - Breaker Open

I - Breaker Closed

58

MakingInstallation: Mechanical Interlock can be mounted on right side of the breaker as follows,

Tools required: Screw Drivers (Tip widths 8 mm & 6 mm), open spanner (10/11)

Mounting Actuator(Common for Fixed & Draw-out breakers)

Remove facia. Provide a cut in the facia along the guides shown inside the facia.

Install the actuator on the main shaft using 2 screws as shown.

Fixing the Mechanical Interlock plate

Fixed Breaker

59

Draw-out Breaker

Making cable connections

60

Adjustments

For 2I/C,3I/C & 2I/C+1S/B:

I. Adjust the Screw (1) till Actuator link (2) just touches Actuator on breaker (3).

II. Tighten nut & locknut (4).

For 2I/C+1B/C:

III. Adjust the screw (1) till Actuator link (2) is horizontal and is in lowermost position.

IV. Tighten Nut & locknut (4).

CAUTIONMechanical Interlock, once installed, must be tested for all possible combinations before actual operation.

1

3

2

4

1

2

4

61

Mounting/Installing Cable Wires

Routing of cable should be with no slip arrangement.

62

CAUTIONEnsure no free hanging of cable wire. All cable wires should be supported appropriately & rigidly at required no. of locations. Ensure cables are at safe distance (min 50mm) from live parts.

Door Racking Interlock (26):Function: to prevent racking operation when panel door is open.

Tools required: screw driver (tip width 5 mm/ 3 mm)

Installation:

1. Insert lever ‘A’ in the slot on front bend of base Plate ‘F’.

2. Align Screw ‘S’ with the axis of Nut insert on Base plate.

3. Press arm ‘B’ of the spring to trap against Screw support ‘C’.

4. Tighten screw with the help of Screw Driver.

R>70mm

A

BS

63

Safety Cover:Function: To provide Ingress protection.

Features: it can be mounted with Left hinge/Right hinge/Removable/Non-removable combinations.

Tools required: Screw Driver (Tip width 5 mm/ 3 mm)

Installation:

1. Drill holes on Door as shown.

2. Assemble ‘Latching Bracket’, ‘Hinge A’ & Hardware as shown.

3. Assemble ‘Locking Lever’, ‘Hinge B’ & Hardware as shown.

F

C

64

1

32119.719.7

Ø538 HOLES-Ø53

DETAILS OF HOLES TO BE DRILLED ON PANEL DOOR FOR REMOVABLE SAFETY COVER

3030 30

302929

300

300 39

6

2

HINGE ‘A’

LATCHING BRACKET

3

HINGE ‘B’

LOCKING LEVER

65

OPERATION:In order to operate safety cover:

1. Close safety cover against bezel.

2. Trap Latching Lever against Latching bracket.

3. Rotate Latching Lever in order to lock it.

ROTATE LINK TO LOCK

4

66

4.2 Breaker Mounted Accessories

Removing faciaTools required: Screw Driver (Tip width 8 mm)

Facia needs to be removed for fixing/replacing various accessories.

Facia can be easily removed only in fully drawn-out (Maintenance) position, which ensures safety of users and equipment.

CAUTIONTo avoid possibility of personal injury, ensure that before opening the facia, breaker is OFF and spring is discharged.

Facia can be taken out by removing 2 screws (32) on either side of the facia.

12

13

67

This is true even for higher frame sizes, where side covers need not be removed for taking out the facia.

After removing the screws on both sides, pull down the charging handle (14) half-way.

Take out the facia by tilting it upwards as shown.

68

Several breaker-mounted accessories are located on the front top side of the breaker and have specific positions.

Auxiliary contact block UN-AX (3a):Function: To reflect breaker ON/OFF state in the control circuit.

Features: Auxiliary contact block is a combination of 4 units of 1NO+1NC each.

Rated insulation voltage Ui: 400 V AC/DC

Rated operational voltage Ue: 400 V AC/DC

Switching capacity:

AC 50/60 Hz Ue Upto 24V 110V 220/230V 400V

In (AC-12) 10A 10A 10A 10A

In (AC-15) 6A 6A 6A 4A

DC Ue 24V 48V 110V 220V

In (DC-12) 10A 8A 3.5A 1A

In (DC-13) 10A 4A 1.2A 0.4A

Auxiliary Contact Block (3a)

Undervoltage Release (4) Closing

Release (5)

Shunt Release (6)

Shunt Trip IndicationUndervoltage Trip Indication

Undervoltage release controller (4c)

Operation Counter (10)

Common Fault Indication

69

Tools required: None

Installation: Auxiliary Contact block is located on the top plate. Slots 1-3 and 5 are to be used for mounting 4 auxiliary contact blocks. 4th slot is designated for routing control wires and 6th slot carried additional auxiliary contact for shunt release circuit.

Click-fit the Auxiliary contact assembly in the specific slots on Top plate as shown.

While making connections, Use NO/NC contact numbers as specified in the wiring diagram and NOT on the auxiliary contact units.

Shunt Release UN-SR (6):Function: To trip the breaker from a remote location.

Features: Available with the following control voltages,

Type Normal Voltage Short-Time Power Consumption

Operating Limit

UN-SR 110,220,240,415 Vac 50/60Hz 200 VA 0.5s

70-110%

24,30,48,60,110,125/127,220,250 Vdc

UN-SRW

(wide band)

240,415V Vac 50Hz 2300 VA 0.2s

10-130%

Tools required: None

Installation: Drop fit the Shunt release in the assigned slot and slide backwards to lock. Also, fix the pre-wired auxiliary Contact Block.

Closing Release UN-SR (5):Function: To remotely close the breaker.

Features: Closing releases are available with the following control voltages.

Normal Voltage Short-time Power Consumption

Operating Limit

110,220,240,415 Vac 50/60Hz 200 VA max. 0.5s 85-110%

24,30,48,60,110,125/127,220,250 Vdc

C2

TCSC1

70

Tools required: None

Installation: Drop fit the Closing release in the assigned slot and slide backwards to lock.

Under Voltage Release UN-UR (4):Function: To trip the breaker in case of system voltage drop.

Features: Under voltage releases are available with the following control voltages,

Type Normal Voltage Short-time Power Consumption

Operating Limit

With/without time delay UN-UR

(Delay setting-0,1,3 & 5 sec)

110,240,415 Vac 50Hz

200 VA max., 3s 85-110%110,220,240,415 Vac 60Hz

24,30,48,110,220 Vdc

A2

A1

D2

D1

71

Tools required: None

Installation: Drop fit the Undervoltage release in the assigned slot and slide backwards to lock. Similarly, click-fit the U/V controller (4c) as shown.

Breakers equipped with Undervoltage release cannot be normally closed unless the release is energized.

In case of NHP MODpower Undervoltage release, the release can be defeated by pressing the latch as shown in adjoining diagram. This enables breaker closing, even without control supply.

To return the release to normal state, energize the release and then disconnect the control supply.

Electrical Charging Device UN-EC (2):Function: To charge the main spring electrically.

Features: A manually charged breaker can be converted to Electrical charging on site, by fixing the Electrical Charging Device.

ECD is available with the following supply voltages,

Rated Voltage Power Consumption Operating Range

110, 220, 240, 415 Vac 50/60Hz300 VA max. 85-110%

24, 30, 48, 60, 110, 125, 220, 250 Vdc

CAUTION To avoid possibility of personal injury, ensure that before opening the facia, breaker is OFF and spring is discharged.

Tools required: Allen key (5 mm)

Align

72

Installation: On the ECD, turn the output shaft in anticlockwise direction till the slot is aligned with corresponding position of charging shaft.

At this position, engage the output shaft of the ECD with charging shaft of the breaker. Fix ECD on the breaker using 2 allen screws at positions indicated by arrows.

Operation Counter (10):Function: Operation counter counts number of ON/OFF operations seen by the breaker.

Tools required: None

Installation:

Click-fit the operational counter on the top plate.

Hook the counter lug to the main shaft.

73

After fixing accessories:

Accessories a-eThe above accessories (except F) are pre-wired with secondary isolating contacts (8b) to be fixed on breaker. SIC positions are printed on the connecting wires and SIC bridge.

Fixing Breaker SICs

Fixing Cradle SICs

Tools required: None

Installation: Click-fit the breaker SICs in the respective positions on the SIC bridge.

Also fix the cradle SIC block with screw at corresponding positions.

Accessories a-fAfter fixing the above accessories, push out the corresponding opaque plug on the facia from inside and plug-in the transparent plug from outside.

74

Locking ‘OFF’ Button (18):Function: To prevent undesirable Closing of breaker.

Tools required: Screw Driver (Tip width 3 mm)

Installation:

Remove knock-out and drill 2 holes (dia 7 mm), at depressed locations.

Ensure that lock is in ‘Locked’ position. Mount the lock from inside and fix plugs.

Fix self-tapping screws inside the plugs

With lock in ‘Unlocked’ position, click-fit the actuator on the OFF button. Refer “6.2 Checking ON-OFF operation” on page 92

75

5.1 Identification

UW-MTX 3.5

Feature no. Description MTX 3.5

1 Protections LSIGN

2 I metering

3 V metering

4 Trip records

5 Event records

6 Additional protections

7 Power Metering o

8 Max Demand o

9 Reverse Power o

10 Modbus o

11 Profibus o

Test Kit Connector

76

Metering Display

Parameter Screen abbreviation Details

Current# I1, I2, I3, IN, Ig Phase, Neutral and Earth

Imax Maximum running current per phase

% Load Percentage Loading per phase

Avg. I Average phase current

**THD current % R, Y, B – Phase

**I1, I2, I3 harmonics Upto 13th harmonic

Voltage# V1, V2, V3 Phase-Neutral voltage

Max V Maximum voltage per phase

V12, V23, V31 Ph-Ph voltage

Max V12, V23, V31 Maximum Ph-Ph voltage

Avg. Vp-p Average Ph-Ph voltage

Avg. Vp-n Average Ph-N voltage

Frequency# F System Frequency

Power Factor# P.F. System Power Factor

Power# W Active Power per phase and total (KW)

VAr Reactive Power per phase and total (KVAr)

VA Apparent Power per phase and total (KVA)

Energy# Wh Active Energy per phase and total (KWh)

VArh Reactive Energy per phase and total (KVArh)

Vah Apparent Energy per phase and total (KVAh)

Max Demand# Wh Active Energy (KWh)

VArh Reactive Energy (KVArh)

VAh Apparent Energy (KVAh)

* Features/Modules available as optional

# Requires Metering moduleMenu

77

Navigation for MTX3.5

78

Protection Settings

Parameter MTX 3.5

Overload (Phase)

Protection: Enable/Disable

Pick-Up (Ir)= In x …for I T, I T,SI, LI / VI Curves

0.4 to 1 In in steps of 0.05

Delay (tr) in s 0.5-1-2-4-6-12-18-24-30

Pre-alarm 0.5 to 0.95 in steps of 0.05xIr

Thermal Memory ON/OFF

Overload(Neutral)

Protection: Enable/Disable

Pick-Up IN= Ir x… .5 to 2 in steps of .5

Pre-alarm .5 to .95 in steps of .05xIr

Delay (tr) in s Same as Overload Phase

Short Circuit

Protection: Enable/Disable

Double S/C ON/OFF

I2T ON/OFF

Pick-Up Lo, Is= In x… 0.6 to 12 In in steps of 0.05

Pick-Up Hi , Is= In x… 0.6 to 12 In in steps of 0.05

Delay Hi (ts) 20-100-200-300-400 ms

Delay Lo (ts) 20-100-200-300-400 ms

Pre-alarm 0.5 to 0.95 in steps of 0.05xIs

Cold Pick-Up: ON/OFF

Cold Delay 100 ms to 10s in steps of 100ms

Directional Short Circuit

Protection: Enable/Disable

Direction:Top / Bottom

I T: ON/OFF

Pick - up (Is) : In x… 0.6 to 12 In in steps of 0.05

Delay (ts) 20-100-200-300-400 ms

Pre-alarm 0.5 to 0.95 in steps of 0.05xIs

Cold Pick - Up: ON/OFF

Cold Delay 100 ms to 10s in steps of 0.05xIs

InstantaneousProtection: Enable/Disable

Pick - up (Ip)=In x… 1.5 to 10 in steps of 0.1 ; 10 to 15 in steps of 1

Earth Fault

Protection: Enable/Disable

I T: ON/OFF

Pick-Up (Ig) = In x… 0.2-0.3-0.4-0.5-0.6

I2T OFF (tg) 100ms to 1 s in steps of 100 ms

I2T ON (tg) 100-200-300-400 ms

Pre-alarm 0.5 to 0.95 in steps of 0.05xIg

Cold Pick-Up: ON/OFF

Cold Delay 100ms to 5 s in steps of 0.1s

Mode: Trip/Alarm/Both

Under Current

Protection: Enable/Disable

Pick-Up = Ir x… 0.2 to 0.8 in steps of 0.05

Delay 1 to 255 s in steps of 1 s

Mode: Trip/Alarm/Both

79

Parameter MTX 3.5

Current Unbalance

Protection: Enable/Disable x x

Pick- Up = In x… - - 10 to 97%in steps of 5%

Delay - - 500 ms to 60s in steps of 0.5s

Mode: Trip/Alarm/Both

Under Voltage

Protection: Enable/Disable

Pick up (Vs) =Vn x … 0.7 to 0.95 in steps of 0.01

Delay 100 ms to 5s in steps of 100 ms

Vs reset 1.01 to 1.04 xVs

Mode: Trip/Alarm/Both

Over Voltage

Protection: Enable/Disable

Pick-Up (Vs)= Vn x… 1.05 to 1.5 Vn in steps of 0.01

Delay 100ms to 5s in steps of 100ms

Vs reset 0.95 to 0.99 Vs in steps of 0.01

Voltage Unbalance

Protection: Enable/Disable

Pick- Up (Vs) = Vn x… 5 to 20% in step of 1%

Delay 500ms to 60 s in steps of 0.5s

Vs reset 0.95 to 0.99 Vs in steps of 0.01

Mode: Trip/Alarm/Both

Residual Voltage

Protection: Enable/Disable

Pick-Up (Vs)=Vn x… 0.15/0.2/0.25/0.3/0.4

Delay 100ms to 5s in steps of 0.1s

Vs reset 0.95 to 0.99 Vs in steps of 0.01

Mode: Trip/Alarm/Both

Under Frequency

Protection: Enable/Disable

Pick-Up (Fn) 45-50 Hz in steps of 0.1Hz

Delay 1-30 s in steps of 0.1s

Reset Freq 1.01 to 1.05 Fn in steps of 0.01

Mode: Trip/Alarm/Both

Over Voltage

Protection: Enable/Disable

Pick-Up (Fn) 50-55 Hz in steps of 0.1 Hz

Delay 1-30 s in steps of 0.1s

Reset Freq 0.95 to 0.99 Fn in step of 0.01

Mode: Trip/Alarm/Both

Reverse Powe

Protection: Enable/Disable

Pick- Up = Pn x… 0.05 to 0.4 in steps of 0.01

Delay 100ms-20s in steps of 0.1s

Mode: Trip/Alarm/Both

Leading PF

Protection: Enable/Disable

Pick- Up = Pf x… 0.5 to 0.99 in a steps of 0.01

Delay 1/2/3/4/5 s

Mode: Trip/Alarm/Both

80

Parameter MTX 3.5

Lagging PF

Protection: Enable/Disable

Pick-Up= Pf x… 0.5 to 0.99 in a steps of 0.01

Delay 1/2/3/4/5 s

Mode: trip/Alarm/Both

MD Active

Protection: Enable/Disable

Type Deliver/Receive

Pick-Up = En x… 0.4 to 1 in steps of 0.01

Mode: Trip/Alarm/Both

MD Reactive

Protection: Enable/Disable

Type Deliver/Receive

Pick-Up = En x… 0.4 to 1 in steps of 0.01

Mode: Trip/Alarm/Both

MD Apparent

Protection: Enable/Disable

Type Deliver/Receive

Pick-Up = En x… 0.4 to 1 in steps of 0.01

Mode: Trip/Alarm/Both

Phase Sequence

Protection: Enable/Disable

Delay 100ms to 5s in steps of 100ms

Mode: Trip/Alarm/Both

Breaker FailureProtection: Enable/Disable

Delay 50 ms to 2 s in steps of 0.05 s

Trip Records

Display OLED Display

Time Based set Group

81

5.2 Protection Characteristics

MODpower Protection Curve

Overload I2t for MTX3.5

Tolerance Trip Time: ±20%

82

Overload I4t for MTX3.5

Tolerance Trip Time: ±20%

83

Overload SI for MTX3.5

Tolerance Trip Time: ±20%

84

Overload LI/VI for MTX3.5

Tolerance Trip Time: ±20%

85

Short Circuit I2t ON for MTX3.5

86

Short Circuit I2t OFF for MTX3.5

87

Instantaneous I2t OFF for MTX3.5

88

Ground Fault I2t ON for MTX3.5

89

Ground Fault I2t OFF for MTX3.5

90

6.1 Re-loading in panel

Pull-out the Cradle Rails (27) & ensure that position indication (17) shows ‘DISCONNECTED’.

Load the breaker using crane. Even bottom trolley can be used.

Ensure that Breaker rests correctly in 2 slots on either side of cradle rail (39).

CAUTIONImproper loading of breaker may lead to personal injury and damage to product.

1

2

3

91

Gently push the breaker to DISCONNECTED position and close the Panel door.

If equipped with Rating Error Preventor (23), Cradle will not accept breaker of different rating.

Keeping the OFF button (11a) pressed; open the Racking shutter (16). In case panel door is open, also gently depress Racking interlock (26).

CAUTIONWhen panel is live, Carry-out Racking operation only with panel door is closed.

Rack-in the breaker to ‘test’ position.

In Test position, if Control supply is present,

- In Electrical breakers, Electrical charging Device (2) will start charging the spring.

- Undervoltage releases (4) get energized.

4

5

6

92

6.2 Checking ON-OFF operation

Initially, the Breaker is and Spring is

Charge the Main spring through multiple strokes of charging handle (14).

Now the breaker is and spring is

Push ‘ON’ button (11b) to close the breaker.

Now, the breaker is and spring has

In this situation, spring can be charged again for next operation.

Breakers equipped with Undervoltage release (4) cannot be normally closed unless the release is energized. NHP MODpower Undervoltage release has a special feature, by which one can still check the operation.

Push ‘OFF’ button (11a) to trip the breaker. Now, the Breaker is and Spring is

Arc Chute Interlock prevents closing of breaker, if any arc chute is missing or not secured properly

93

6.3 Testing (SIC and interlocks)• Ensure that connected and Main circuit is disconnected.

• Trace the Control circuit wiring based on panel wiring diagrams given by the panel builder and breaker connections.

Based on the accessories fitted on the breaker, carry-out the following tests:

• If breaker is equipped with Electrical Charging Device UN-EC (2), main spring will get charged as soon as breaker reaches ‘Test’ position and Control supply is switched ON. If breaker is not equipped with Electrical Charging Device, charge the spring manually.

• If Undervoltage release UN-UR (4) is installed, but not energized, it will not allow the breaker to Close. However, you can continue the testing by defeating the Undervoltage release

• Ensure that all arc chutes are fitted and secured properly.

• Give supply to Closing release UN-CR (5) to close the breaker. In case not equipped with closing release, manually close the breaker by pushing the ON button (11b).

• Trip the breaker by giving supply to Shunt release UN-SR (6). In case not equipped with shunt release, manually trip the breaker by pushing the OFF button.

• After tripping through Shunt release, also check tripping through Undervoltage release, if it is energized.

• After checking the voltmetric releases, verify the functioning of other electrical interlocks and indications wherein breaker’s auxiliary contacts or SICs are used.

• Also, verify the Mechanical/Key interlocking of NHP MODpower ACB with other breakers / electrical devices in the scheme.

94

6.4 Setting P&C unit

System SettingsSetting Breaker Rating

Follow the mentioned steps for configuration of breaker ratings

I-frame and In values shall be programmed as per following look-up table.

Breaker Frame Size

Breaker rating (A)

I-Frame in A

In in A

1,2,3 400

630

800

800 400

630

800

1,2,3 1000

1250

1600

1600 1000

1250

1600

1 2000

2500

3200

3200 2000

2500

3200

2,3 2000

2500

3200

4000

4000 2000

2500

3200

4000

Rest of the parameters under System settings should be set in same manner. After programming the settings, press key to escape from menu and confirm the changes in Save Settings.

Note: To apply any parameter change in System settings in P&C unit, reset the power supply once settings are saved.

Press “SEL” key in the overlay

Select “Settings” by SEL key

Select “Config” Mode

Enter the password “0000” (Factory set: default)

Select “MTX Unit” in Config Mode

Select “System Settings”

95

Unit SettingsUnit settings can be programmed following menu navigation Sequence given below

Press “SEL” key

Parameters under unit settings are listed below:

Date & Time : Current date & time to be entered. Helpful for fault history time stamping.

Communication : Total 126 Device Ids are provided along with Parity option, Baud type, Baud rate with wide range up to 19.2kbps.

Event Recorder : To capture an event viz alarm, pick-up, trip, module connect/ disconnect and maintenance.

Max Demand : Maximum demand of energy integration and refreshing interval can be selected.

Settings P/W : The factory default settings password is “0000” which can be modified to new password by user.

Command password : The factory default command password is “0000”. This password is valid for following commands enlisted in “Restore settings” menu, namely Maint. operation, Clear MD. Set Group, Factory Setting, Clear Max I, Clear Max V, Clear Energies and Earth Fault test of the P & C unit. It is configurable.

Contrast : Screen contrast can be adjusted.

Auto set GRP : As per the factory load requirements, protections can be configured using time based set groups. Active set group will switch over to dor-mant set group after the set time elapsed.

Maintenance : This is password protected. Breaker installation date shall be programmed by the service engineer.

Day light saving : Day light saving can be programmed through this option. Enable the Day light saving option, using “DST Mode” Enable and set the Start and End DST dates and the time which is required to add.

Select “MTX Unit” in Config Mode

Select “System Settings”

Select “Settings” by SEL key

Select “Config” Mode

Enter the password “0000” (Factory set: default)

96

ProtectionSet the protection settings as per the following menu navigation sequence.

Press “SEL” key in the overlay

*Two interchangeable protection set groups are provided to meet different load requirements in plant.

Set group 1 is Default active Set group. Time based set group can be programmed through “AUTO SET GRP”.

Protections under I-protection:Overload : It’s a protection against over current. The characteristics are I2t, I4t LI, SI, VI

with Thermal memory. Thermal memory help to reduce the trip time of the unit in case of recursions of overload.

Short Circuit : Excessive currents though the conductors can cause circuit damage, fire, explosion. This protection prevents such conditions.

Directional SC :The protection is a short circuit protection with the ability to recognize the direction of the phases current during the fault period. The current direction makes is possible to determine whether the fault is on the supply or load side of the circuit-breaker. Particularly in ring distribution systems, this makes it possible to identify and disconnect the distribution feeder where the fault has occurred, whilst keeping the rest of the system running.

Instantaneous : This protection works as short circuit protection with no intentional time delay which means release operates in 20 milliseconds as soon as the fault current exceeds the set pick-up.

Note: Refer UW-MTX Release manual for the programming of further pro-tections in detail.

Earth Fault : When fault current flows from phase to earth due to rupturing of insulation, this can lead to arc flash events and electric shock. This causes more damage to the distribution system. This feature provides protection against earth fault current.

Neutral Overload : This provides protection against neutral overload at 50%, 100% & 200% of rated current. It follows overload characteristics.

Under current : Decrease in any phase current below threshold leads to under current.

Current Unbalance : It provides protection against any unbalance in phase currents.

Select “MTX Unit” in Config Mode

Select “Protection”

Select desired set group as active.*

Select “Settings” by SEL key

Select “Config” Mode

Enter the password “0000” (Factory set: default)

97

Settings: Overload configuration:

Similarly set all protection parameters.

After programming the settings, press key to escape from menu and confirm the changes in Save Settings. After doing all the settings Save the set group by pressing the escape key. “Save in Progress” message confirms the Set Group has saved.

Protections under V-protection:Under voltage : When the voltage in one of the phases reduces than threshold, this

protection gets activated.

Over voltage : When the voltage in one of the phases increases above threshold, this protection gets activated.

Voltage unbalance : Voltage unbalance creates damage to the distribution system. This protection checks voltage unbalance in all three phases.

Residual voltage : Give protection against the residual voltage present in the system.

Protections under Freq-protection:Under frequency } applicable for both control frequencies 50HZ & 60Hz.

Over frequency

Protections under Power-protection:Reverse Power : When the direction of the total active power reverses to that of the

set direction, this protection gets activated. The direction of power depends on that of the current flowing.

Leading PF : It checks whether the power factor is dropping down the set value when load is capacitive.

Lagging PF : When the power factor for inductive load goes below the set value, this protection gets activated. Its important for any plant to maintain the power factor to unity.

Protections under other-protection:MD active } When max. demand of active, reactive & apparent

power exceeds the set value, then this protection gets activated.

MD reactive

MD apparent

Phase sequence : Mostly used for motor applications where phase reversal can be seen.

Breaker failure : In case if the breaker fails to open under fault condition (mechanism jam, FSD malfunctions etc.) release issues one more trip command to FSD to operate the breaker as per the set delay through this protection.

Enable O/L Protection Select O/L Char. from the drop down list.

Select delay from the drop down list

98

6.5 Trip simulation of P&C unit

The Salient Features:

• Generation of 3 phase current & voltage test signal (configurable Amplitude, frequency and Phase angles)

• Simulation Kit Active Mode (Powering of Release): 2 hours & stand by mode : 2 days

• Smart GUI with multi functional key operation

• Graphical display (OLED)

• Continuous battery monitoring feature

• CT Continuity test feature

• Memory card for data storage of test scripts and records (extendable up to 32GB)

• Real Time Clock & Temperature sensing feature

• Dual Power ON - Battery or external supply

• Auto sensing of Release connectivity

99

6.6 MODpower ACB’s in Connected1. Rack-in NHP MODpower ACB from ‘Test’ to ‘Connected’ position

Keeping the OFF button (11a) pressed; open the Racking Shutter (16). In case panel door is open, also gently depress racking interlock (26).

CAUTION Carry-out racking operation only when panel door is closed.

Rack-in the breaker to Connected position. Two almost-simultaneous ‘click’ sounds confirm ‘connected’ position.

CAUTIONExcessive forceful racking-in beyond Connected position may lead to product damage.

2. Check tightness of Termination on NHP MODpower ACB and other link/busbars.

3. Complete other Commissioning activities.

4. Check LED indication on P&C unit:

5

6 “Click”“Click”

100

Once breaker starts carrying current, check status of ‘POWER ON’ LED in MTX1.0/MTX1G and OLED displaying 1.5G/2.5/2.5G/3.5/3.5EC. Blinking Green LED implies that the P&C unit is healthy and is protecting your circuit. ‘POWER ON’ LED and OLED display is OFF when there is no/minimal current in the main circuit.

Metering display:Once breaker starts carrying current, UW-MTX units display current values in default metering screen. UW-MTX units display current, Voltage, Frequency, PF, Power, Energy, Max Demand, Temperatures values in auto scrolling mode*. Default current metering screen is shown as an example.1,2,3 represent R, Y, B phases respectively.

*depending on the configuration selected.

POWER ON LED

101

6.7 Securing

ON-OFF Button padlocking (11):

To prevent unauthorized access, ON/OFF buttons can be padlocked or sealed, together or individually.

Sealing the Release cover (31):

Protection setting for Release can be secured using a standard lead seal.

Smart Racking shutter padlocking (16a):

Tools required: Screw Driver (Tip width 3 mm)

To prevent inadvertent racking operation, smart racking shutter can be padlocked, when breaker is in distinct Service, Test or Isolated positions and racking shutter is closed. Upto 3 padlocks can be used at a time.

Padlocking both Buttons

Locking any one Button Sealing Either/Both

buttons

102

7. Maintenance schedule & OperationsRegular maintenance of NHP MODpower Series of breaker will help ensure proper operation, reliable protection and enhanced product life.

CAUTION

• This device should be maintained by authorised qualified personal only.

• Ensure that main and control supply is disconnected, before commencing any work on the device.

• Failure to meet the above precautions can lead to electrocution and result in serious injury/death to personnel.

• It is recommended to call L&T’s Authorised Service Centre for servicing the breaker.

• After maintenance, in P&C unit MTX3.5 give “yes” command to the “maintenance” in “Restore settings”.

Nature of

MaintenanceSchedule/Frequency Actions Reference

Routine

Monthly Check LED indication on P&C unit 7.1a

QuartelySelf-diagnostic test of P&C unit 7.1bTemperature check at termination 7.1c

Yearly

Open & Re-close the breaker 7.1dRack-out & Rack-in breaker 7.1eInspect Arc Chutes for erosion 7.1fInspect Contacts for erosion 7.1g Trip simulation of P&C unit 6.5

1 year or 500 operations (whichever is earlier)

Greasing of Operating Mechanism 7.1h

Specific

When P&C unit trips the breaker

Identify the fault & Reset P&C unit 7.1i

When any Electrical acces-sory needs replacement

Replace the specific accessory 7.1j

When breaker cleares a major fault

Inspect Arc Chutes for erosion & replace, if required

7.1g

Inspect contacts for erosion & replace Main Contacts, if required

7.1g & 7.1k

In case of an abnormal external

event, such as flashover in panel

Inspect Jaw Contacts & replace, if required 7.1l

Inspect Cradle Terminals and replace, if required

7.1m

On completion of Electri-cal life

Replace all Arc Chutes 7.1fReplace all Main Contacts 7.1k

Checking LED indication on P&C unit

POWER ON LED

103

Tools required: None

If ‘POWER ON’ LED is Blinking Green, it implies that the P&C unit is healthy and is protecting your circuit.

If ‘POWER ON’ LED is OFF when there is no/minimal current in the main circuit.

Earth fault test of P&C unit

Tools required: Screw Driver (Tip width 6 mm max)

Remove cover of P&C unit and press ‘T’ button. Enter the command password (default factory set password is “0000”). Unit issues trip in EF and trip, E/F LED glows.

To reset the LEDs, again press the ‘T’ button once the breaker is closed and re-enter the password. This procedures verifies unit is healthy to issue trip in Earth Fault.

Temperature Check:Tools required: Infrared Temperature Scanner

Overheating at terminals and joints can result in serious accidents including flashovers. Regular temperature checks at termination using an ‘Infrared Temperature Scanner’ will help detect any overheating for timely preventive action.

Breaker operation:Tools required: None

In several cases, breaker is rarely operated. Hence, it is important to open and re-close the breaker at regular intervals. Also check for healthy operation of accessories such as Electrical charging device, Closing release and Shunt release.

Racking operation:Tools required: None

If breaker is not being racked-out in a year, it is recommended to carry-out racking operation of the breaker as a part of routine maintenance. Procedure for Racking out & in is detailed in “2.3 Racking-out” on page 15

Door interlock defeat (40):

123

104

Tools required: Philips Head Screw driver (Tip number 2) or Screw driver (Tip width 6 mm)

If the breaker is equipped with Door interlock, panel door cannot be opened when breaker is in Service condition.

If it is necessary to open the panel door with breaker in Service condition, Door interlock can be defeated as illustrated herewith.

CAUTIONOpening panel door when breaker terminals are live, may lead to electric shock and personal injury.

Door Racking Interlock Defeat (26):

Tools required: none

Door Racking interlock prevents opening of smart racking shutter (16) and thus, racking in/out of the breaker when panel door is open.

If it is necessary to rack-out the breaker with panel door open, racking interlock can be defeated. For opening racking shutter with panel door open, gently depress the racking interlock lever (26) in addition to keeping ‘OFF’ button (11a) depressed.

CAUTIONIt is recommended to carry-out racking operation only with panel door closed.

Inspecting Arc-Chutes (21) for erosion:Tools required: None

Pull back the knob and lift the front side of the arc chute.

105

Disengage the rear side and lift arc chute.

Check deion plates for erosion. If plates develop sharp knife-edges, replace arc chutes.

Inspection of Contacts for erosion:Once Arc shuts are opened, contacts are visible and can be inspected for erosion.

Tools required: None

NHP MODpower ACB poles are equipped with an indicator for contact condition.

The adjoining detailed sketch shows the rear edge of the moving contact with breaker in ‘closed’ condition. As contact get eroded, the rear edge moves in the direction indicated by an arrow in the shaded area.

Condition of contact is indicated by alignment of the rear edge with one of 3 markings on the indicator.

This feature is only for indication purposes and contacts should replaced after clearing major fault/on completion of electrical life indicated.

Deion plates

Visual Inspection of Arcing and Main contacts

Cut-view of Moving part Cut-view of Fixed part

106

Greasing of Mechanism:

Greasing schedule Mechanism: 1 year or 500 operations, whichever is earlier grease to be used: Mobilith SHC-100 of mobill. Greasing schedule Cradle: 1 year or 50 operations, whichever is earlier Grease to be used: Mobilith SHC-100 of Mobill.

The following components can be greased, without dismantling any accessory or component, using a brush.

1: Pole shaft bearing (all)

2: Bearings (both sides of mechanism)

3: Cam Profile

4: Top surface of links (2)

5: Top surface of link

6: Rubbing surface of link

CAUTION

Non-adherence to greasing schedule or using other-than-specified grease may lead to malfunction.

Ensure that ACB is OFF and Spring is Discharged, before commencing greasing operation.

1: Racking Screw

2: Racking Cam & Drop Pin joint

3: Base Plate

4: Rail Sliding surface on side plate

5: Racking Cam & Service Latch follower

6: Gear Teeth & Rack Slots

7: Bottom & side Sliding Surfaces of Rails on Side Plate

8: Service Latch on Side Plates

9: Guiding surface of cradle SIC Bridge

Needs replacement

Indicator on each pole

Rear edge of moving contact moves forward due to erosion

Intermediate

Good

107

Apply grease to the specified components at rubbing surfaces.

Simplified diagram for identification of components to be greased.

Simplified diagram for identification of components to be greased.

9

5

4

21

3 6

7

8

3

4

5

6

1

2

108

Fault Identification and Resetting:Tools required: Screw Driver (Tip width 6 mm max)

Fault identification:

1. When P&C unit trips the breaker, a mechanical indication is provided through popping-out of the red pointer at the upper end of the unit.

With Auto reset feature, the pointer will reset automatically.

2. To identify the type of fault, open the P&C unit cover and press ‘Query’ button. The LED corresponding to the fault seen by the breaker will glow. This local fault indication is independent of auxiliary supply or batteries and is available to USERS for repeat usage* after the fault.

Reclosing the breaker:

3. After taking the necessary corrective action. Press ‘clear’ button to reset the fault indication.

4. For breakers with ‘Manuals resetting mode’, push-in the red pointer and fix the release cover back.

Now, breaker can be reclosed.

Replacement of Electrical Accessories:Tools required: Screw Driver (Tip width 3 mm)

Allen key 5 mm (for Electrical Charging Device)

After removing facia access breaker SIC

*Availability of indication depends on time elapsed after the fault and duration for which ‘Query’ button is pressed.

4

1

109

Pull out the specific breaker SIC from the bridge with the screw driver.

For removing Volumetric release, depress the lever under the release and slide it out.

For removing Electrical Charging Device, remove 2 allen screws.

Install the new accessory and fix new breaker SICs, pre-wired with the new accessory.

Replacement of Main Contacts:MODpower facilitates replacement of pole assembly in a phase-by-phase manner. USERS can determine whether to replace one pole or multiple poles, based on condition of contacts. However, at the end of electrical life, all poles need to be replaced.

Tools required:

- Screw Drivers: a. Tip width 8 mm or Philip head (tip no. 2)

- b. Length 200 mm min, Tip width 6 mm, Tip thickness 1 mm max

- Allen key : 5 mm, Shank length 120 mm

- Box spanner : M6, length 300 mm min.

First close the breaker and then remove arc chutes & CT covers

110

Remove the CTs, without disturbing their connections with the P&C unit.

Remove connector pin and trip the breaker.

Remove hex socket head screws (10 nos.), using min. 80 mm long M6 key.

111

Separate rear housing from front housing, without disturbing CT wires.

Remove fasteners.

Moving part of the pole can now be removed

112

To take out fixed part of the pole, remove 1 screw from rear side and 2 screws from top as shown.

Replace fixed part of the pole.

Also, replace Moving part of the pole.

113

Refix fasteners, Align front & rear housings and tighten hex socket head screws.

Depress Arc-chute interlock lever to defeat the interlock and close the breaker.

Refix the connector pin, followed by CTs and CT covers. After verifying closing of poles through few ON-OFF operations, refix the arc chutes.

114

Replacement of Jaw Contacts (3j):Contacts Jaws may require replacement in the event of a flashover or on clearing a major fault.

Tools required: None*

Jaws can be replaced without using any tool. Slightly rotate the jaw left or right to remove it.

Replacement of Cradle Terminals & Supports (35):Tools required: Screw Driver (Blade-Length 300 mm & Dia 8 mm, Tip width 8 mm)

Remove screws ‘A’ and loosen screws ‘B’. As a result, Removing of Safety Shutter, jaws and Terminal support clamp will drop down.

115

Pull out the cradle terminal assembly using projections on the terminal support.

Now you can replace the cradle terminals & jaw cluster assemblies.

116

8. TroubleshootingSituation Probability Solution

ACB does not close on pressing “ON” button

One or more arc-chute (s) not secured properly

Press each arc chute firmly by hand

U/V release is present but not energized

Energize U/V release

Mechanism spring is not charged. Indicator is in black background

Charge the mechanism spring manually till a distinct sound is heard & indicator turns yellow

Trip Reset link is projecting out Press trip reset link to reset position

Smart Racking Shutter is open Close the Smart Racking Shutter (Insert Racking Handle once & pull back)

“OFF” button is locked Unlock “OFF” button

Mechanical Interlock disables closing

Re-check before attempting to close the breaker

Smart Racking Shutter does not re-close automatically after racking handle is pulled out

Breaker is in-between Connected/Test/Disconnected position. Position indicator is not aligned with any of the positions

Rack-in or out the breaker to any of the distinct positions

ACB cannot be pushed into disconnected position

Breakers & Cradle ratings do not match

Put correct breaker

Smart Racking Shutter does not open

“OFF” button not kept pressed fully Keep OFF button pressed

Door open/missing: hence door Racking Interlock (26) is active

Clear/provide door; else press door racking interlock lever (on extreme lower left side) manually

Position lock(s) active Unlock

ACB does not close electrically Electrical antipumping is active Interrupt ‘Close’ command once

“Ready to close” (RTC) conditions are not met

Check all RTC conditions

ACB trips after closing Overload fault exists if tripping is after several seconds or minutes. Other fault(S) exist if tripping is within a second

Press “QUERY” button on Protection & Control (P&C) Unit to confirm type of fault. Clear the cause of fault. Press “CLEAR” button on P&C Unit. Push back the red Reset Link

(RED) reset link projects out

Shunt Release is getting command continuously

Check the source of command

117

MODpower Air Circuit Breakers

MP1 3 pole MODbreak ACB

Features• Customer fit accessories

• LSIG Protection

• Fixed or Withdrawable

• 3 or 4 pole types

• MP1 and MP2 65kA interrupting capacity

• MP3 80kA interrupting capacity

• Fault interruption ratings Icu = Ics

• Internal and external accessory range

• Selectivity and other data available

• NHP MODcurve selectivity and Cadblocks available

118

Withdrawable ACBs

Frame Size Ampere Rat-ing (A)

Mounting Poles Catalogue Number

3 pole Price $

1250 MP1S12E3WD

1600 MP1S16E3WD

MP1 2000 withdrawable 3 MP1S20E3WD

2500 MP1S25E3WD

MP2 3200 MP2S32E3WD

MP3 4000 MP3H40E3WD i1250 MP1S12E4WD i1600 MP1S16E4WD i

MP1 2000 withdrawable 4 MP1S20E4WD i2500 MP1S25E4WD i

MP2 3200 MP2S32E4WD iMP3 4000 MP3H40E4WD i

Fixed ACBs

Frame Size Ampere Rat-ing (A)

Mounting Poles Catalogue Number

3 pole Price $

1600 MP1S16E3FD

MP1 2000 Fixed 3 MP1S20E3FD

2500 MP1S25E3FD

Neutral Pole Ground Fault CTs

Ampere Rating (A)

Catalogue Number

3 pole Price $

1250 MPGFCT12

1600 MPGFCT16

2000 MPGFCT20

2500 MPGFCT25

3200 MPGFCT32

4000 MPGFCT40 ii Refers to Indent Items

Refer www.nhp.com.au Mod-series web page for additional technical product information.

119

MODpower Air Circuit Breakers

Internal Accessories – MODpower ACBsAll internal accessories can be fitted by the user.

Accessory type Voltage Catalogue number Price $

Shunt Trip Coil 24VDC MPSHUNT24VDC

240VAC MPSHUNT240VAC

415VAC MPSHUNT415VAC

Shunt Indication Contact MPSHTCONTACT

Time delay UVT 24VDC MPUVT24VDC

240VAC MPUVT240VAC

415VAC MPUVT415VAC

UVT Indication Contact MPUVTCONTACT

Remote Close Coil 24VDC MPCLOSE24VDC

240VAC MPCLOSE240VAC

415VAC MPCLOSE415VAC

Spring Charge Motor 24VDC MPMOTOR24VDC

240VAC MPMOTOR240VAC

415VAC MPMOTOR415VAC

Common Trip Contact MPCTCONTACT

Ready to Close Contact MPRTCCONTACT

Key Interlock MPKEYINTERLOCK

Position Contact MPPOSCONTACTSTI

Cycle Counter MPCYCLECOUNTER

Refer www.nhp.com.au Mod-series web page for additional technical product information.

120

121

OCR Accessories – MODpower ACBsAll OCR accessories can be fitted by the user.

Accessory type Voltage Catalogue number Price $

Power Supply Module 85-265 VAC MPPSMODULEAC

120-375 VDC

OCR Plug in Modules:

MODBUS MPMODMODBUS

PROFIBUS MPMODPROFIBUS i Energy Metering MPMODVOLTAGE

Smartcard MPMODSMARTCARD iMTX OCR Checker MPOCRTESTDEVICE

i Refers to Indent Items

Refer www.nhp.com.au Mod-series web page for additional technical product information

PS

Power Supply (24Vdc)

- Operating voltage 85-265 Vac, 125-300Vdc

- DIN rail/Base mountable module

122

123

MODpower Air Circuit Breakers

External Accessories – MODpower ACBsAll external accessories can be fitted by the user.

Accessory type Catalogue number Price $

Racking Error Device MPRACKERROR

Mechanical Interlock

1 of 2 interlock

2 Meter MPMECHINT2MT12

3 Meter MPMECHINT3MT12

5 Meter MPMECHINT5MT12 i

1 of 3 interlock

2 Meter MPMECHINT2MT13 i 3 Meter MPMECHINT3MT13 i 5 Meter MPMECHINT5MT13 i

2 of 3 interlock

2 Meter MPMECHINT2MT23

3 Meter MPMECHINT3MT23

5 Meter MPMECHINT5MT23 i

Door Interlock MPDOORINTERLOCK

Additional Position Contact 1 MPPOSCONTACTX1 iAdditional Position Contact 2 MPPOSCONTACTX2 i

IP40 Gasket (Fixed ACB) MPGASKETFD

IP40 Gasket (Withdrawable ACB) MPGASKETWD

IP54 Hinged Cover MPCOVER

i Refers to Indent Items

Refer www.nhp.com.au Mod-series web page for additional technical product information.

124

MODpower Air Circuit Breakers

Spare parts list

Body - MODpower ACBs

Description Catalogue number Price $

Auxiliary Contacts (4NO4NC) MPAUXCONTACTS

OCR MTX3.5 24VDC MPOCRMTX35

ON/OFF Button Cover MPONOFFCOVER

10 x Control Wiring Contacts MPSICCONTACTS

Cradle – MODpower ACBs

Description Catalogue number Price $

Racking Handle MPRACKINGHANDLE

Safety Shutter MPSHUTTER

MP1 3P Cradle 1250A MP1CRADLE123

MP1 3P Cradle 1600A MP1CRADLE163

MP1 3P Cradle 2000A MP1CRADLE203

MP1 3P Cradle 2500A MP1CRADLE253

MP2 3P Cradle 3200A MP2CRADLE323 iMP3 3P Cradle 4000A MP3CRADLE403 i

MP1 3P Arc Shield MP13ARCSHIELD iMP1 4P Arc Shield MP14ARCSHIELD iMP2 3P Arc Shield MP23ARCSHIELD iMP2 4P Arc Shield MP24ARCSHIELD i

MP1 Fixed 2000A - Terminal (V or H) MP1TERM2000FD

MP1 Withdrawable 2000A - Terminal (V or H) MP1TERM2000WD

MP1 Fixed 2500A - Terminal (V Only) MP1TERM2500FD

MP1 Withdrawable 2500A - Terminal (V Only) MP1TERM2500WD

MP2 Withdrawable Terminal (V or H) MP2TERM3200WD

MP3 Withdrawable Terminal (V only) MP3TERM4000WD iRefer www.nhp.com.au Mod-series web page for additional technical product information

NHP Electrical Engineering Products Pty LtdA.B.N. 84 004 304 812

FILENAME MONTH YEAR © Copyright NHP 2013

AUSTRALIAnhp.com.au

SALES 1300 NHP NHP

FAX 1300 NHP FAX

VICTORIAMelbourne 43-67 River Street Richmond VIC 3121 Tel +61 3 9429 2999

Laverton 104-106 William Angliss Drive Laverton North VIC 3026 Tel +61 3 9368 2901

Albury / Wodonga 847 Ramsden Drive Albury NSW 2640 Tel +61 2 6049 0600 Fax +61 3 6025 0592

Dandenong 40-42 Cyber Loop Dandenong South VIC 3175 Tel +61 3 8773 6400 Fax +61 3 8768 8522

TASMANIAHobart 29B Lampton Ave Derwent Park TAS 7009 Tel +61 3 6228 9575 Fax +61 3 6228 9757

Launceston Unit 3 13-17 Merino Street Kings Meadows TAS 7249 Tel +61 3 6345 2600 Fax +61 3 6344 6324

NEW SOUTH WALESSydney 30-34 Day Street North Silverwater NSW 2128 Tel +61 2 9748 3444

Newcastle 575 Maitland Road Mayfield West NSW 2304 Tel +61 2 4960 2220 Fax +61 2 4960 2203

Wollongong 34 Industrial Road Unanderra NSW 2526 Tel +61 2 4272 5763 Fax +61 2 4272 5957

ACTCanberra Unit1 187 Gladstone Street Fyshwick ACT 2609 Tel +61 2 6280 9888 Fax +61 2 6280 9588

WESTERN AUSTRALIAPerth 38 Belmont Ave Rivervale WA 6103 Tel +61 8 9277 1777

NORTHERN TERRITORYDarwin 3 Steele Street Winnellie NT 0820 Tel +61 8 8947 2666 Fax +61 8 8947 2049

QUEENSLANDBrisbane 16 Riverview Place Murarrie QLD 4172 Tel +61 7 3909 4999

Townsville 5 Leyland Street Garbutt QLD 4814 Tel +61 7 4779 0700 Fax +61 7 4775 1457

Rockhampton 1 Lawson Street Parkhurst QLD 4702 Tel +61 7 4927 2277 Fax +61 7 4922 2947

Toowoomba Cnr Carroll Street and Struan Court QLD 4350 Tel +61 7 4634 4799 Fax +61 7 4633 1796

Cairns Unit 2 1 Bramp Close Portsmith QLD 4870 Tel +61 7 4035 6888 Fax +61 7 4035 6999

SOUTH AUSTRALIAAdelaide 36-38 Croydon Road Keswick SA 5035 Tel +61 8 8297 9055

NEW ZEALANDnhp-nz.com

SALES 0800 NHP NHP

FAX 0800 FAX NHP

PO Box 62-009 Sylvia Park Auckland 1644 New Zealand

Auckland 118a Carbine Road Mt Wellington 1060

Hamilton 78 Rostrevor Street Hamilton 3204

Napier 126 Taradale Road Onekawa 4110

New Plymouth 2 Dean Place Waiwhakaiho 4312

Wellington 52 Victoria Street Lower Hutt 5010

Christchurch 27 Iversen TerraceWaltham 8011

Dunedin 30 Fox StreetSouth Dunedin 9012

Scan the QR code to download the eCatalogues App