MODpower Air Circuit Breakers
Sales 1300 NHP NHP nhp.com.auNHP Electrical Engineering Products Pty Ltd
POWER DISTRIBUTION AND PROTECTION
2
Contents
1. On receiving MODPower System1.1 Visual Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.2 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.3 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71.4 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2. Understanding MODPower System2.1 Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112.2 Exploring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122.3 Racking-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152.4 Operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172.5 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3. Installing MODPower System3.1 Mounting & Door cut-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203.2 Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303.3 Loading in Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493.4 Control Circuit Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4. Accessories: Features & Mounting4.1 Cradle Mounted Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 554.2 Breaker Mounted Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5. Protection & Control Units5.1 Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 755.2 Protection Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
6. Putting MODPower System in Operation6.1 Re-loading in panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 906.2 Checking ON-OFF operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 926.3 Testing (SIC and interlocks) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 936.4 Setting P&C unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 946.5 Trip simulation of P&C unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 986.6 MODpower ACB’s in Connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 996.7 Securing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
7. Maintenance schedule & Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
8. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
3
CautionNon-observance of the safety instructions can result in severe personal injury or equipment damage.
Successful and safe operation of the equipment (including accessories) depends on proper handling, installation, operation and maintenance.
Before commencing with installation or maintenance,
- Disconnect power supply of the device
- Ensure that device cannot be accidentally restarted
- Verify isolation from supply and earthing
- Cover and enclose all neighboring live equipment
- Discharge spring
- Follow engineering instructions of the device concerned
- Before touching device, ensure you are free of electrostatic charge
Ensure that deviations of the mains and control voltages do not exceed the specified operating limits, as this may cause malfunction, dangerous operation and damage to product.
4
1.1 Visual Inspection
- Inspect the packaging for any signs of damage from transportation, contact NHP in case of a any damage.
- Check the labeling and ensure the size and ratings are as per order information.
5
1.2 Unpacking
For Fixed Breakers
Cut straps and remove nails.
Lift the carton and remove any accessories taped to the breaker or kept loose on the palette.
Remove Breaker mounting screws (4 nos.)
6
For Draw-Out breakers
Cut straps and remove nails.
Lift the carton and remove any accessories taped to the cradle or kept loose on the palette.
Remove Cradle fixing screws (M10) on all sides.
1
2
Remove Transportation cushion
7
1.3 Handling
For Fixed Breakers
CAUTIONHeavy equipment. Exercise proper care to avoid personal injury and equipment damage.
Lift the breaker using a crane. A special Lifting Handle is available (optional) to facilitate handling.
Frame 1 breakers can also be transported by 2 persons.
8
For Draw-out Breakers
Lift the breaker using hooks at specified places as shown above.
Frame 1 breakers can also be transported by 2 persons.
CAUTION Do not lift the breaker using Facia or Terminals.
9
1.4 Storage
CAUTIONStore the breaker in a cool, dry place, away from dusty/corrosive environment.
When cradle and breaker are not being used for a long time, pack them in the carton and store in a dry place.
11
2.1 Identification
2a- Type designation for Electrical Charging device (ECD)2b- Operating voltage for ECD4a- Type designation for Under-voltage release (UVR)4b- Operating voltage for UVR5a- Type designation for Closing release (CR)5b- Operating voltage for CR6a- Type designation for Shunt release (SR/SRW)6b- Operating voltage for SR/SRW12- ON-OFF indication13- Spring status indication 29b- Rated Uninterrupted Current29c- Rated impulse withstand voltage29d- Utilization Category29e- Suitability for isolation29f- Standards compliance29g- Rated Service breaking capacity29h- Rated operational voltage29j- Rated short-time withstand current
29a
29b
29h
12
13
2a
6a4a 5a
6b5b4b
2b
29j
29g
29c
29d
29e
29f
12
2.2 Exploring
Facia
11- Shroud for ON-OFF Buttons
11a- OFF button
11b- ON button
18- OFF button locking
28- USERS’ identification location
29- Name plate
31- Cover for Protection & Control unit (P&C)
32- Facia fixing screw
11a
11b
11
18
28
29
31
32
13
Breaker
1- Protection & control unit
2- Electrical Charging Device
3a- Auxiliary Contacts
4- Undervoltage Release
4c- Undervoltage Release Controller
5- Closing release
6- Shunt Release
7- Ready-to-Close (Microswitch)
8b- Secondary Isolating Contacts on Breaker
10- Operation Counter
12- ON-OFF Indication
13- Spring Status Indication
14- Charging handle
21- Arc Chute
24b- Lifting location on breaker
33- Projections for resting breaker on cradle
33
24b
21 5
1
4
2
7
6 10
12
8b
3a
4c
13
14
14
Cradle
3e- Hole for Earthing Connection
3j- Jaw Contacts
8c- Secondary Isolating Contacts on Cradle
8e- Electrical Position Indication
15- Racking Handle
16- Smart Racking Shutter
16a- Padlock for Racking shutter
17- Position Indicator
19- Position Lock-1
20- Position Lock-2
22- Arc Shield
23- Rating Error Prevention
24- Lifting Locations (4 nos.)
24a- Additional Lifting Locations
25- Withdrawal Rails
26- Door Racking Interlock
27- Breaker Pull-out Handle
34- Guide for routing Control Wiring
35- Terminal Supports
36- Cradle Bottom cross-component
37- Cradle Top cross-component
38- Slot for placing breaker on Cradle
39- Safety Shutter
40- Door Interlock
201917
26
1615
2527
36
38
35
24
23
24
2237
34
39
8c 8e
3e
40
3j
16a
24a
24a
15
2.3 Racking-outFor D/O Breakers remove the transportation Cushion (2 Nos.) & its instruction label, before doing racking operation of the breaker.
Keeping OFF button (11a) pressed; open the Racking Shutter (16). In case Breaker is out of the panel or the panel door is open, gently press Racking Interlock (26) to defeat it.
Note: Once racking shutter is opened, the breaker can not be closed, even by an electrical closing command.
Rack-out the breaker to Disconnected position.
Note: After removing the racking handle (15), the racking shutter automatically recloses only in distinct “Connected” / “Test” and “Disconnected” positions (17). Hence, Breaker cannot be closed in any intermediate positions to ensure User safety.
CAUTIONExcessive, forceful Racking-out beyond Disconnected position may lead to Product damage.
Remove Transportation Cushion
Remove Caution Flap
12
Take out the handle
Insert the racking handle & rotate anticlockwise
16
Pull the breaker out using pull-out handles (27).
In Maintenance position, Breaker can be removed from the cradle by two persons (Fr.1) or by using a crane.
Please refer “1.3 Handling” on page 7
17
2.4 OperatingInitially, the Breaker is and Spring is
Charge the Main spring through multiple strokes of charging handle (14)
Now the Breaker is and Spring is
Push ‘ON’ button (11b) to close the breaker.
Now, the breaker is and spring has in this situation, spring can be charged again for next operation.
Breakers equipped with Undervoltage (4) cannot be normally closed unless the release is energized. NHP MOD power ACB’s Undervoltage release has a special feature, by which one can still check the operation.
Push ‘OFF’ button (11a) to trip the breaker.
Now, the Breaker is and Spring is
Arc Chute Interlock prevents closing of breaker, if any arc chute is missing or not secured properly
18
2.5 Technical Data
Common Parameters Unit Symbol
Rated Operational voltage at 50/60 Hz V Ue Upto 690
Rated Insulation voltage at 50/60 Hz V Ui 1000
Rated Impulse withstand voltage – Main circuit KV Uimp 12
Rated Impulse withstand voltage – Auxiliary circuit KV Uimp 4
No.of poles 3 & 4
Suitability for isolation Yes
Intrinsic degree of protection of breaker front IP53
Pollution degree suitability 3
Utilization category B
Compliance IS/IEC 60947-2, EN 60947-2, IEC 60497-2
H: Height
W: Width
D: Depth with flat terminals
19
Frame MP1 MP2 MP3
Rated Uninterrupted Current at 40deg.C
A 1250 1600 2000 2500 3200 4000
Rated Ultimate/Service S.C. Breaking Capacity (Icu=Ics)
415VAC
KA
65 80
550VAC 55 70
690VAC 50 55
Rated short Time Withstand Capacity (Icw)
0.5 sec
KA
65 65 80
1.0 sec 65 65 80
3.0 sec 36 42 50
Rated S.C Making Capacity (Icm)
415VAC
KA
143 176
550VAC 121 143
690VAC 105 121
Opening Timems
40
Closing Time 60
Mechanical Life with Maintenance
cycles 20000 15000 10000
Frequency of Operation-Mechanical cycles/hr 60
Electrical life without Maintenance*
cycles 8000 10000 5000 2000
Frequency of Operation-Electrical cycles/hr 40 20
Dimensions (Fixed)
W (3P)
mm
347
D 324
H 396
Dimensions (Withdrawable)
W (3P)
mm
347 447 647
W (4P) 447 581 847
D 421 421 431
H 433 433 433
Pitch-Top/Bottom Terminals
mm 105
Pitch-Phase to Phase/phase to Neutral
mm 100 133 200
Terminal Width mm 65 65 165
Net Weight
Fixed 3P
kg
37 46
W/D 3P 68 77 82 121
W/D 4P 81 91 98 163
*with maintenance, electrical=mechanical
20
3.1 Mounting & Door cut-out
MODpower ACB Door Flange Dimensions
IP40 Gasket MP1 Fixed
Cutout for Main FaciaDOOR EDGE
Bottom Corner of Breaker
321
13
45
341
8 HOLES-DIA.5
17110.5
*70min.
10.5 171
181
181
21
Overall Flange dimensions W=371, H=391, 25mm around cutout
IP40 Gasket MP1,2,3 Withdrawable Left Side Hinge
Cutout for Door Interlock DeviceSee Detail ‘Z’Cutout for Main Facia
DOOR EDGE
8 HOLES-DIA.5
17110.59.2
*70min.
10.5 171
208.
520
8.553
.5
321 13
396
10
Bottom Corner of Breaker
22
Right Side Hinge
Frame Poles Dimension ‘X’
MP1 3 311.8
4 411.8
MP2 3 411.8
4 545.8
MP3 3 611.8
4 811.8
Overall Flange dimensions W=371, H=446, 25mm around cutout
Detail Z
Ø16.5 +0.1-0.1
Ø16.5 +0.10
8
Cutout for Door Interlock DeviceSee Detail ‘Z’
Cutout for Main Facia
321
X
13
396
10
Bottom Corner of Breaker
53.5
23
MP1 3 P- Fixed
A Mounting holes suitable for M10/Equivalent BS bolt
112
347335
430
300
min
AA
6 6142
324
300
min
A
7
2525
Panel Door
24
MP1 3P- Withdrawable
A Mounting holes suitable for M10/Equivalent BS bolt
347
25049.5 47.5
62.4
433
300
min
*
A
421
250280
300
min
*
A
7
25.5
Panel Door
DISCONNECTED
TEST
16
35
(47.5)(250)(2
50)
(280
)
(62.
4)
Use this mounting hole
Use this mounting hole
Use any one of these two mounting holes
Use any one of these two mounting holes
25
MP1 4P - Withdrawable
A Mounting holes suitable for M10/Equivalent BS bolt
447
25010049.5 47.5
62.4
433
300
min
*
A A
421
250280
300
min
*
A
7
25.5
Panel Door
DISCONNECTED
TEST
16
35
(47.5)(250)(100)
(250
)
(280
)
(62.
4)
Use this mounting hole
Use any one of these two mounting holes
Use any one of these two mounting holes
Use any one of these two mounting holes
Use any one of these two mounting holes
26
MP2 3P - Withdrawable
A Mounting holes suitable for M10/Equivalent BS bolt
447
25010049.5 47.5
62.4
433
300
min
*
A A
421
250280
300
min
*
A
7
25.5
Panel Door
DISCONNETCTED
TEST
16
35
(47.5)(250)(100)(2
50)
(280
)
(62.
4)
Use this mounting hole
Use any one of these two mounting holes
Use any one of these two mounting holes
Use any one of these two mounting holes
Use any one of these two mounting holes
27
MP2 4P - Withdrawable
A Mounting holes suitable for M10/Equivalent BS bolt
581
25010049.5 47.5
62.4
433
300
min
*
A A
421
250280
300
min
*
A
7
25.5
Panel Door
DISCONNETCTED
TEST
16
35
49.5 (47.5)(250)(100)
(250
)
(280
)(6
2.4)Use this mounting hole
Use this mounting hole
Use any one of these two mounting holes
Use any one of these two mounting holes
Use any one of these two mounting holes
Use any one of these two mounting holes
28
MP3 3P - Withdrawable
A Mounting holes suitable for M10/Equivalent BS bolt
64725010049.5 47.5
62.4
433
300
min
*
A A
431
250280
300
min
*
A
7
35.5
Panel Door
DISCONNETCTED
TEST
16
35
(47.5)(250)(100)
(250
)
(280
)(6
2.4)
Use this mounting hole
Use this mounting hole
Use any one of these two mounting holes
Use any one of these two mounting holes
Use any one of these two mounting holes
49.5
Use any one of these two mounting holes
29
MP3 4P - Withdrawable
A Mounting holes suitable for M10/Equivalent BS bolt
(47.5)(250)(200) (100)(2
50)
(280
)(6
2.4)
Use this mounting hole
Use this mounting hole Use this
mounting hole
Use any one of these two mounting holes
Use any one of these two mounting holes
Use any one of these two mounting holes
Use any one of these two mounting holes
49.5
847
25010020049.5 47.5
62.4
433
300
min
*
A A A
431
250280
300
min
*
A
7Panel Door
DISCONNETCTED
TEST
16
3535.5
30
3.2 Termination
Terminal Adaptor:
Vertical Adaptors for frame 1 & 3
Horizontal & Vertical Adaptor for frame 2
Horizontal Adaptor for frame 3
For Frame-1, terminal adaptor installation. In Frame-3 use equalizer for vertical & a single adaptor for horizontal between two poles.
Installation of terminal adaptor for frames 2
31
For Fixed Breakers:
CAUTIONInadequate termination support may result in overheating & adverselt affect performance during short circuit conditions.
100MAX.
32
For Draw-out Breakers:With Universal Terminals
With Terminal Adaptor
* maintain adequate clearance between links as per applicable standards.
33
Terminal Dimensions
MP1 3P - Fixed
FRAME 1 A B C
400-1600 S 24 50 65
2000-2500 S 30 55 65
M12/ equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm
Holes (on both sides) for earthing connections by M10/equivalent BS bolt
Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 15 mm.
Bolt length
15347
100 100
M10
C
M10 bolts to be used for link termination Tightening torque: 3.0 kgfm
11
32
BB 10
512
2
41
A
32C
34
M12/ equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm
1569
6910
8.8
40
7463
27100 100
19
Ø12.9
35
M12/ equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm
276540
65
117.
5
74
100100
100 100
19
Ø12.9
15
63
36
MP1 3P - Withdrawable
Flat Terminals
Detail A
Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.
100
100
80.8
7263
100 100
2727
45
19
Ø12.9
100100
20
10.4
36
Ø12.536
14.5
Bolt length
37
M12 bolts to be used for link termination Tightening torque: 3.2 kgfm
Horizontal Terminals400A-2000A
100 73.5100
347
SEE DETAIL A
25.5
16
15
56.8 10
515
0
65
73.5100 100
347
105
150
36
Ø12.9
36
16
36
17.5
65
83.5
15
15
Ø12.9
38
Vertical Terminals400A-2000A
Vertical TerminalsFor 2500A-3P
M12/ Equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm
73.5100 100
105
65
150
36
27
36
17.5
36
15 65
347
Ø12.9
Ø12.9
1683.5
15
73.5100 100
105
140
36
36206590.565 Ø12.9
34716
98
15
2727
15
Ø12.9
39
MP1 4P – Withdrawable
Flat Terminals
Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.
Horizontal Terminals*
400A-2000A N/S/H
Adaptor – CL60963OOOO
SEE DETAIL A
105
150
73.5100100100
44716
25.5
15
3665
73.5100100100
105
150
36
Ø12.9
347
16
15
83.5
36
17.5
Ø12.9
15Bolt length
3665
14.5
(Ø12.5)M12
56.8
36
10.4
40
Vertical Terminals400A-2000A N/S/H
Adaptor – CL60963OOOO
** For 2500A REFER PAGE 3-25
Vertical TerminalsFor 2500A-4P
M12/ Equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm
All dimensions in mm
73.5100100100
105
65
150
36
2736
17.5
36
15 65
447
Ø12.9
Ø12.9
1683.5
15
73.5100100100
105
140
36
90.565 Ø12.9
44716
98
15
2727
15
Ø12.9
3620 65
41
MP2 3P – Withdrawable
Flat Terminals
Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.
Horizontal Terminals
Bolt length
25.5
1615
105
140
M12
3665
133.3 133.3 90
447
3636
77.2
77.2
105
140
133.3 133.3 90
447
75
98
1615
36
Ø12.9
20
15
90.5
42
Vertical Terminals
MP2 4P – Withdrawable
Flat Terminals
Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.
M12/ Equivalent BS bolts to be used for link termination tightening torque: 3.2 kgfm
36 20 20
3636
36133.3 133.3 90
447
105
140
1615
36
9898
2727
1590.5
Ø12.9
Bolt length
105
140
3677.2
3677.2
133.3133.3133.390
581
M12
3665
16
25.5
15
43
Horizontal Terminals
Vertical Terminals
98 36
105
140
133.3133.3133.3 90
581
3675
161515
36
90.520
Ø12.9
133.3133.3133.3 90
581
105
140
983620
1615
36
9898
2727
1590.5
Ø12.9
44
MP3 3P – Withdrawable
Flat Terminals
Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.
Horizontal Terminals
Vertical Terminals
Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.
Bolt length
105
179
100100100100100 73.5647
36165
3636
5656
Ø12.9
25.5
1615 Holes (on both sides) for Earthing connections by M10/equivalent BS bolt
10010010010010074.4
5835.5
647
6540
183
36
3665
165
Ø12.9
1615
15
2 HOLES-Ø12.9PITCH 27 mm
Bolt length
45
MP3 4P – Withdrawable
Flat Terminals
Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.
10010010010010074.4
647
1536165
Ø12.9
6540
183
36
5835.5
1615
2719
Ø12.9
Holes (on both sides) for Earthing connections by M10/equivalent BS bolt
Bolt length
100100100100100100100 73.5
847
105
HOLE-Ø12.9
365656
179
36165
16
31.7
11
15
Holes (on both sides) for Earthing connections by M10/equivalent BS bolt
46
Horizontal Terminals
VerticalTerminals
Bolt length for mounting link (s) on flat terminals to be cumulative link (s) thickness + 20 min to 25 max.
Bolt length
10010010010010010010073.5
847
6540
183 36
3665 165
Ø12.9
5835.5
1615
202 HOLES-Ø12.9PITCH 27 mm
100100100100100100 10073.5
847
1536 165Ø12.9
6540
183 36
5835.5
1615
2727
1919
Ø12.9
Holes (on both sides) for Earthing connections by M10/equivalent BS bolt
47
MODpower Ground Fault CT
For earth fault protection and protection of neutral against overloads, neutral CT is required. For 4-pole breakers, the CT is provided inside the breaker, to be used on 4 wire system whereas for 3-pole breakers, external CT is available separately.
It is important that with NHP’s MOD power system of breaker, special neutral CTs supplied by NHP are used.
Frame Size Rating
1, 2 & 3 400/630/800
1, 2 & 3 1000/1250/1600
(ref. “2.5 Technical Data” on page 18)
TERMINAL THICKNESS 15 mm.
Frame Size Rating
1 2000/2500
(ref. “2.5 Technical Data” on page 18)
TERMINAL THICKNESS 30 mm.
90
4065
Ø13
7219
19
4242
40
45.5
45.5
12.5 Ø13
7219
19
65
48
Frame Size Rating
2 & 3 2000/2500
3200/4000
(ref. “2.5 Technical Data” on page 18)
TERMINAL THICKNESS 30 mm.
Frame Size Rating
3 5000/6300
(ref. “2.5 Technical Data” on page 18)
TERMINAL THICKNESS 30 mm.
M12/ Equivalent bolts to be used for links termination. Tightening torque: 3.2 kgfm
All dimensions in mm.
2727
45.5
45.5
22.15 Ø13
7219
19
98.3
Ø13
7219
19
145
45.5
45.5
40404065
12.5
49
3.3 Loading in Panel
1
Pull-out the cradle Rails (27) & ensure that position indication (17) shows ‘DISCONNECTED’.
Load the breaker using crane. Even bottom trolley can be used.
3
Ensure that Breaker rests correctly in 2 slots on either side of cradle rail (39).
CAUTIONImproper loading of breaker may lead to personal injury and damage to product.
2
50
Gently push the breaker to DISCONNECTED position and close the Panel door.
If equipped with Rating Error Preventor (23), Cradle will not accept breaker of different rating.
5
Keeping the OFF button (11a) pressed, open the Racking Shutter (16). In case panel door is open, also gently depress Racking Interlock (26).
Rack-in the breaker to Service position. Two almost–simultaneous ‘click’ sounds confirm ‘CONNECTED’ position.
CAUTIONExcessive forceful racking-in beyond Connected position may lead to product damage.
4
6
51
2
3.4 Control Circuit ConnectionsNHP’s MOD power System of ACB’s Secondary Isolating Contacts (8) facilitate control circuit wiring with following features.
• Cradle SIC block slot & each breaker SIC slot is pre-defined and marked for specific connections.
• Breaker is supplied with SIC
• Every accessory comes pre-wired with breaker SICs. SIC location is printed on the wire for easy identification.
• Breaker SIC are click-fitted and hence, require no tools for fixing.
• SICs offer screwless wire connections, by simply using a connector as shown in the diagram.
• SICs can independently accept 2 wires for ease of terminating multiple wires. Wire specifications: Min 0.75mm2 & max 2.5mm2.
• After termination, control wires can be routed through guides provided in the cradle side plates.
CAUTIONWire bunch to be routed properly to avoid interference with Door interlock (40), if installed..
SICs & SIC Bridge
Quick and Easy Control Wiring
Ensure lug orientation with separations on topStrip Conductors
Tip Width 3 mm
52
Routing Control Wires
Position Indication:
1. All position SIC
2. Connected & Test position SIC
3. Connected position SIC
4. Additional Connected position indication
5. Test position SIC
6. Additional Test position indication
7. Disconnected position SIC
8. Additional Disconnected position indication
8 mm
1
2
4
5
6
7
8
3
Disconnected Test Connected
53
The above diagram gives a generic configuration for control termination on the breaker. For specific details, refer Connection diagram (pages 3-38 to 3-44) specific to the P&C unit installed in the breaker.
#for using electrical accessories with dc control supply. It is recommended to connect D1/A1/C1 to +ve and D2/A2/C2 to –ve.
# m indicates micro switch
54
AS+, AS-: 24V DC Power Supply
AL+ : TRIP ALARM+, TRIP ALARM-
This output can be connected to 5V-30V dc 150 mA Relay or any other indicating device which can give alarm for short circuit and Earth Fault trip.
D+: MOD A
D-: MOD B
N1: External Neutral CT
N2: External Neutral CT
M-G: MOD-GND
V0,V1,V2,V3: N R,Y,B, VOLTAGE I/P.
55
4.1 Cradle Mounted Accessories
Safety Shutter (39):
Function: To prevent inadvertent access to live terminals.
Features: One or individual pole can be padlocked during maintenance.
Tools required: Screw Driver (Blade length 300 mm, Tip width 8 mm)
Installation: Remove bolt on the bottom cross component (36). Click-fit the shutter on the top cross component (37) and refix the bolt on the bottom cross components. This process has to repeated for each pole.
Door Interlock (40):
Converting Door-interlock for RHS hinge
Function: Prevents opening of panel door in Connected & Test positions.
Features: it can be mounted on either side of the cradle and can be converted for RHS hinge doors by simply relocating 2 components.
Tools required: Philip head Screw driver (Tip no. 2), Ring spanner (size 13)
Installation: Door interlock comes in 2 parts, one to be fixed on the cradle and the other on the panel door. Door interlock is mounted inside the side plate of the cradle.
56
Assemble the interlock as shown.
Rest the rear end of the torsion spring on the SIC bridge, as shown.
Also assemble panel-door mounted part of door-interlock.
Cradle RH Side Plate Section views
Cradle RH Side Plate Section views
Cut-out for Door Interlock
57
Mechanical Interlock:Function: Mechanical Interlock is used for interlocking breakers as per the desired control scheme.
Features: it can be interlock upto 3 NHP MOD power breakers of Fixed/Drawout/Mixed versions. The breakers can be interlocked in vertical or horizontal configuration.
Possible mounting arrangements:
Cable length: 2 meters/3 meters/5 meters min. radius of cable bend: 70 mm
Type of Interlock Typical Circuit Interlocks possible
Schematic diagram
Two Incomers (2 I/C)
Two Incomers & One Buscoupler (2 I/C+1 B/C)
O - Breaker Open
I - Breaker Closed
58
MakingInstallation: Mechanical Interlock can be mounted on right side of the breaker as follows,
Tools required: Screw Drivers (Tip widths 8 mm & 6 mm), open spanner (10/11)
Mounting Actuator(Common for Fixed & Draw-out breakers)
Remove facia. Provide a cut in the facia along the guides shown inside the facia.
Install the actuator on the main shaft using 2 screws as shown.
Fixing the Mechanical Interlock plate
Fixed Breaker
60
Adjustments
For 2I/C,3I/C & 2I/C+1S/B:
I. Adjust the Screw (1) till Actuator link (2) just touches Actuator on breaker (3).
II. Tighten nut & locknut (4).
For 2I/C+1B/C:
III. Adjust the screw (1) till Actuator link (2) is horizontal and is in lowermost position.
IV. Tighten Nut & locknut (4).
CAUTIONMechanical Interlock, once installed, must be tested for all possible combinations before actual operation.
1
3
2
4
1
2
4
62
CAUTIONEnsure no free hanging of cable wire. All cable wires should be supported appropriately & rigidly at required no. of locations. Ensure cables are at safe distance (min 50mm) from live parts.
Door Racking Interlock (26):Function: to prevent racking operation when panel door is open.
Tools required: screw driver (tip width 5 mm/ 3 mm)
Installation:
1. Insert lever ‘A’ in the slot on front bend of base Plate ‘F’.
2. Align Screw ‘S’ with the axis of Nut insert on Base plate.
3. Press arm ‘B’ of the spring to trap against Screw support ‘C’.
4. Tighten screw with the help of Screw Driver.
R>70mm
A
BS
63
Safety Cover:Function: To provide Ingress protection.
Features: it can be mounted with Left hinge/Right hinge/Removable/Non-removable combinations.
Tools required: Screw Driver (Tip width 5 mm/ 3 mm)
Installation:
1. Drill holes on Door as shown.
2. Assemble ‘Latching Bracket’, ‘Hinge A’ & Hardware as shown.
3. Assemble ‘Locking Lever’, ‘Hinge B’ & Hardware as shown.
F
C
64
1
32119.719.7
Ø538 HOLES-Ø53
DETAILS OF HOLES TO BE DRILLED ON PANEL DOOR FOR REMOVABLE SAFETY COVER
3030 30
302929
300
300 39
6
2
HINGE ‘A’
LATCHING BRACKET
3
HINGE ‘B’
LOCKING LEVER
65
OPERATION:In order to operate safety cover:
1. Close safety cover against bezel.
2. Trap Latching Lever against Latching bracket.
3. Rotate Latching Lever in order to lock it.
ROTATE LINK TO LOCK
4
66
4.2 Breaker Mounted Accessories
Removing faciaTools required: Screw Driver (Tip width 8 mm)
Facia needs to be removed for fixing/replacing various accessories.
Facia can be easily removed only in fully drawn-out (Maintenance) position, which ensures safety of users and equipment.
CAUTIONTo avoid possibility of personal injury, ensure that before opening the facia, breaker is OFF and spring is discharged.
Facia can be taken out by removing 2 screws (32) on either side of the facia.
12
13
67
This is true even for higher frame sizes, where side covers need not be removed for taking out the facia.
After removing the screws on both sides, pull down the charging handle (14) half-way.
Take out the facia by tilting it upwards as shown.
68
Several breaker-mounted accessories are located on the front top side of the breaker and have specific positions.
Auxiliary contact block UN-AX (3a):Function: To reflect breaker ON/OFF state in the control circuit.
Features: Auxiliary contact block is a combination of 4 units of 1NO+1NC each.
Rated insulation voltage Ui: 400 V AC/DC
Rated operational voltage Ue: 400 V AC/DC
Switching capacity:
AC 50/60 Hz Ue Upto 24V 110V 220/230V 400V
In (AC-12) 10A 10A 10A 10A
In (AC-15) 6A 6A 6A 4A
DC Ue 24V 48V 110V 220V
In (DC-12) 10A 8A 3.5A 1A
In (DC-13) 10A 4A 1.2A 0.4A
Auxiliary Contact Block (3a)
Undervoltage Release (4) Closing
Release (5)
Shunt Release (6)
Shunt Trip IndicationUndervoltage Trip Indication
Undervoltage release controller (4c)
Operation Counter (10)
Common Fault Indication
69
Tools required: None
Installation: Auxiliary Contact block is located on the top plate. Slots 1-3 and 5 are to be used for mounting 4 auxiliary contact blocks. 4th slot is designated for routing control wires and 6th slot carried additional auxiliary contact for shunt release circuit.
Click-fit the Auxiliary contact assembly in the specific slots on Top plate as shown.
While making connections, Use NO/NC contact numbers as specified in the wiring diagram and NOT on the auxiliary contact units.
Shunt Release UN-SR (6):Function: To trip the breaker from a remote location.
Features: Available with the following control voltages,
Type Normal Voltage Short-Time Power Consumption
Operating Limit
UN-SR 110,220,240,415 Vac 50/60Hz 200 VA 0.5s
70-110%
24,30,48,60,110,125/127,220,250 Vdc
UN-SRW
(wide band)
240,415V Vac 50Hz 2300 VA 0.2s
10-130%
Tools required: None
Installation: Drop fit the Shunt release in the assigned slot and slide backwards to lock. Also, fix the pre-wired auxiliary Contact Block.
Closing Release UN-SR (5):Function: To remotely close the breaker.
Features: Closing releases are available with the following control voltages.
Normal Voltage Short-time Power Consumption
Operating Limit
110,220,240,415 Vac 50/60Hz 200 VA max. 0.5s 85-110%
24,30,48,60,110,125/127,220,250 Vdc
C2
TCSC1
70
Tools required: None
Installation: Drop fit the Closing release in the assigned slot and slide backwards to lock.
Under Voltage Release UN-UR (4):Function: To trip the breaker in case of system voltage drop.
Features: Under voltage releases are available with the following control voltages,
Type Normal Voltage Short-time Power Consumption
Operating Limit
With/without time delay UN-UR
(Delay setting-0,1,3 & 5 sec)
110,240,415 Vac 50Hz
200 VA max., 3s 85-110%110,220,240,415 Vac 60Hz
24,30,48,110,220 Vdc
A2
A1
D2
D1
71
Tools required: None
Installation: Drop fit the Undervoltage release in the assigned slot and slide backwards to lock. Similarly, click-fit the U/V controller (4c) as shown.
Breakers equipped with Undervoltage release cannot be normally closed unless the release is energized.
In case of NHP MODpower Undervoltage release, the release can be defeated by pressing the latch as shown in adjoining diagram. This enables breaker closing, even without control supply.
To return the release to normal state, energize the release and then disconnect the control supply.
Electrical Charging Device UN-EC (2):Function: To charge the main spring electrically.
Features: A manually charged breaker can be converted to Electrical charging on site, by fixing the Electrical Charging Device.
ECD is available with the following supply voltages,
Rated Voltage Power Consumption Operating Range
110, 220, 240, 415 Vac 50/60Hz300 VA max. 85-110%
24, 30, 48, 60, 110, 125, 220, 250 Vdc
CAUTION To avoid possibility of personal injury, ensure that before opening the facia, breaker is OFF and spring is discharged.
Tools required: Allen key (5 mm)
Align
72
Installation: On the ECD, turn the output shaft in anticlockwise direction till the slot is aligned with corresponding position of charging shaft.
At this position, engage the output shaft of the ECD with charging shaft of the breaker. Fix ECD on the breaker using 2 allen screws at positions indicated by arrows.
Operation Counter (10):Function: Operation counter counts number of ON/OFF operations seen by the breaker.
Tools required: None
Installation:
Click-fit the operational counter on the top plate.
Hook the counter lug to the main shaft.
73
After fixing accessories:
Accessories a-eThe above accessories (except F) are pre-wired with secondary isolating contacts (8b) to be fixed on breaker. SIC positions are printed on the connecting wires and SIC bridge.
Fixing Breaker SICs
Fixing Cradle SICs
Tools required: None
Installation: Click-fit the breaker SICs in the respective positions on the SIC bridge.
Also fix the cradle SIC block with screw at corresponding positions.
Accessories a-fAfter fixing the above accessories, push out the corresponding opaque plug on the facia from inside and plug-in the transparent plug from outside.
74
Locking ‘OFF’ Button (18):Function: To prevent undesirable Closing of breaker.
Tools required: Screw Driver (Tip width 3 mm)
Installation:
Remove knock-out and drill 2 holes (dia 7 mm), at depressed locations.
Ensure that lock is in ‘Locked’ position. Mount the lock from inside and fix plugs.
Fix self-tapping screws inside the plugs
With lock in ‘Unlocked’ position, click-fit the actuator on the OFF button. Refer “6.2 Checking ON-OFF operation” on page 92
75
5.1 Identification
UW-MTX 3.5
Feature no. Description MTX 3.5
1 Protections LSIGN
2 I metering
3 V metering
4 Trip records
5 Event records
6 Additional protections
7 Power Metering o
8 Max Demand o
9 Reverse Power o
10 Modbus o
11 Profibus o
Test Kit Connector
76
Metering Display
Parameter Screen abbreviation Details
Current# I1, I2, I3, IN, Ig Phase, Neutral and Earth
Imax Maximum running current per phase
% Load Percentage Loading per phase
Avg. I Average phase current
**THD current % R, Y, B – Phase
**I1, I2, I3 harmonics Upto 13th harmonic
Voltage# V1, V2, V3 Phase-Neutral voltage
Max V Maximum voltage per phase
V12, V23, V31 Ph-Ph voltage
Max V12, V23, V31 Maximum Ph-Ph voltage
Avg. Vp-p Average Ph-Ph voltage
Avg. Vp-n Average Ph-N voltage
Frequency# F System Frequency
Power Factor# P.F. System Power Factor
Power# W Active Power per phase and total (KW)
VAr Reactive Power per phase and total (KVAr)
VA Apparent Power per phase and total (KVA)
Energy# Wh Active Energy per phase and total (KWh)
VArh Reactive Energy per phase and total (KVArh)
Vah Apparent Energy per phase and total (KVAh)
Max Demand# Wh Active Energy (KWh)
VArh Reactive Energy (KVArh)
VAh Apparent Energy (KVAh)
* Features/Modules available as optional
# Requires Metering moduleMenu
78
Protection Settings
Parameter MTX 3.5
Overload (Phase)
Protection: Enable/Disable
Pick-Up (Ir)= In x …for I T, I T,SI, LI / VI Curves
0.4 to 1 In in steps of 0.05
Delay (tr) in s 0.5-1-2-4-6-12-18-24-30
Pre-alarm 0.5 to 0.95 in steps of 0.05xIr
Thermal Memory ON/OFF
Overload(Neutral)
Protection: Enable/Disable
Pick-Up IN= Ir x… .5 to 2 in steps of .5
Pre-alarm .5 to .95 in steps of .05xIr
Delay (tr) in s Same as Overload Phase
Short Circuit
Protection: Enable/Disable
Double S/C ON/OFF
I2T ON/OFF
Pick-Up Lo, Is= In x… 0.6 to 12 In in steps of 0.05
Pick-Up Hi , Is= In x… 0.6 to 12 In in steps of 0.05
Delay Hi (ts) 20-100-200-300-400 ms
Delay Lo (ts) 20-100-200-300-400 ms
Pre-alarm 0.5 to 0.95 in steps of 0.05xIs
Cold Pick-Up: ON/OFF
Cold Delay 100 ms to 10s in steps of 100ms
Directional Short Circuit
Protection: Enable/Disable
Direction:Top / Bottom
I T: ON/OFF
Pick - up (Is) : In x… 0.6 to 12 In in steps of 0.05
Delay (ts) 20-100-200-300-400 ms
Pre-alarm 0.5 to 0.95 in steps of 0.05xIs
Cold Pick - Up: ON/OFF
Cold Delay 100 ms to 10s in steps of 0.05xIs
InstantaneousProtection: Enable/Disable
Pick - up (Ip)=In x… 1.5 to 10 in steps of 0.1 ; 10 to 15 in steps of 1
Earth Fault
Protection: Enable/Disable
I T: ON/OFF
Pick-Up (Ig) = In x… 0.2-0.3-0.4-0.5-0.6
I2T OFF (tg) 100ms to 1 s in steps of 100 ms
I2T ON (tg) 100-200-300-400 ms
Pre-alarm 0.5 to 0.95 in steps of 0.05xIg
Cold Pick-Up: ON/OFF
Cold Delay 100ms to 5 s in steps of 0.1s
Mode: Trip/Alarm/Both
Under Current
Protection: Enable/Disable
Pick-Up = Ir x… 0.2 to 0.8 in steps of 0.05
Delay 1 to 255 s in steps of 1 s
Mode: Trip/Alarm/Both
79
Parameter MTX 3.5
Current Unbalance
Protection: Enable/Disable x x
Pick- Up = In x… - - 10 to 97%in steps of 5%
Delay - - 500 ms to 60s in steps of 0.5s
Mode: Trip/Alarm/Both
Under Voltage
Protection: Enable/Disable
Pick up (Vs) =Vn x … 0.7 to 0.95 in steps of 0.01
Delay 100 ms to 5s in steps of 100 ms
Vs reset 1.01 to 1.04 xVs
Mode: Trip/Alarm/Both
Over Voltage
Protection: Enable/Disable
Pick-Up (Vs)= Vn x… 1.05 to 1.5 Vn in steps of 0.01
Delay 100ms to 5s in steps of 100ms
Vs reset 0.95 to 0.99 Vs in steps of 0.01
Voltage Unbalance
Protection: Enable/Disable
Pick- Up (Vs) = Vn x… 5 to 20% in step of 1%
Delay 500ms to 60 s in steps of 0.5s
Vs reset 0.95 to 0.99 Vs in steps of 0.01
Mode: Trip/Alarm/Both
Residual Voltage
Protection: Enable/Disable
Pick-Up (Vs)=Vn x… 0.15/0.2/0.25/0.3/0.4
Delay 100ms to 5s in steps of 0.1s
Vs reset 0.95 to 0.99 Vs in steps of 0.01
Mode: Trip/Alarm/Both
Under Frequency
Protection: Enable/Disable
Pick-Up (Fn) 45-50 Hz in steps of 0.1Hz
Delay 1-30 s in steps of 0.1s
Reset Freq 1.01 to 1.05 Fn in steps of 0.01
Mode: Trip/Alarm/Both
Over Voltage
Protection: Enable/Disable
Pick-Up (Fn) 50-55 Hz in steps of 0.1 Hz
Delay 1-30 s in steps of 0.1s
Reset Freq 0.95 to 0.99 Fn in step of 0.01
Mode: Trip/Alarm/Both
Reverse Powe
Protection: Enable/Disable
Pick- Up = Pn x… 0.05 to 0.4 in steps of 0.01
Delay 100ms-20s in steps of 0.1s
Mode: Trip/Alarm/Both
Leading PF
Protection: Enable/Disable
Pick- Up = Pf x… 0.5 to 0.99 in a steps of 0.01
Delay 1/2/3/4/5 s
Mode: Trip/Alarm/Both
80
Parameter MTX 3.5
Lagging PF
Protection: Enable/Disable
Pick-Up= Pf x… 0.5 to 0.99 in a steps of 0.01
Delay 1/2/3/4/5 s
Mode: trip/Alarm/Both
MD Active
Protection: Enable/Disable
Type Deliver/Receive
Pick-Up = En x… 0.4 to 1 in steps of 0.01
Mode: Trip/Alarm/Both
MD Reactive
Protection: Enable/Disable
Type Deliver/Receive
Pick-Up = En x… 0.4 to 1 in steps of 0.01
Mode: Trip/Alarm/Both
MD Apparent
Protection: Enable/Disable
Type Deliver/Receive
Pick-Up = En x… 0.4 to 1 in steps of 0.01
Mode: Trip/Alarm/Both
Phase Sequence
Protection: Enable/Disable
Delay 100ms to 5s in steps of 100ms
Mode: Trip/Alarm/Both
Breaker FailureProtection: Enable/Disable
Delay 50 ms to 2 s in steps of 0.05 s
Trip Records
Display OLED Display
Time Based set Group
81
5.2 Protection Characteristics
MODpower Protection Curve
Overload I2t for MTX3.5
Tolerance Trip Time: ±20%
90
6.1 Re-loading in panel
Pull-out the Cradle Rails (27) & ensure that position indication (17) shows ‘DISCONNECTED’.
Load the breaker using crane. Even bottom trolley can be used.
Ensure that Breaker rests correctly in 2 slots on either side of cradle rail (39).
CAUTIONImproper loading of breaker may lead to personal injury and damage to product.
1
2
3
91
Gently push the breaker to DISCONNECTED position and close the Panel door.
If equipped with Rating Error Preventor (23), Cradle will not accept breaker of different rating.
Keeping the OFF button (11a) pressed; open the Racking shutter (16). In case panel door is open, also gently depress Racking interlock (26).
CAUTIONWhen panel is live, Carry-out Racking operation only with panel door is closed.
Rack-in the breaker to ‘test’ position.
In Test position, if Control supply is present,
- In Electrical breakers, Electrical charging Device (2) will start charging the spring.
- Undervoltage releases (4) get energized.
4
5
6
92
6.2 Checking ON-OFF operation
Initially, the Breaker is and Spring is
Charge the Main spring through multiple strokes of charging handle (14).
Now the breaker is and spring is
Push ‘ON’ button (11b) to close the breaker.
Now, the breaker is and spring has
In this situation, spring can be charged again for next operation.
Breakers equipped with Undervoltage release (4) cannot be normally closed unless the release is energized. NHP MODpower Undervoltage release has a special feature, by which one can still check the operation.
Push ‘OFF’ button (11a) to trip the breaker. Now, the Breaker is and Spring is
Arc Chute Interlock prevents closing of breaker, if any arc chute is missing or not secured properly
93
6.3 Testing (SIC and interlocks)• Ensure that connected and Main circuit is disconnected.
• Trace the Control circuit wiring based on panel wiring diagrams given by the panel builder and breaker connections.
Based on the accessories fitted on the breaker, carry-out the following tests:
• If breaker is equipped with Electrical Charging Device UN-EC (2), main spring will get charged as soon as breaker reaches ‘Test’ position and Control supply is switched ON. If breaker is not equipped with Electrical Charging Device, charge the spring manually.
• If Undervoltage release UN-UR (4) is installed, but not energized, it will not allow the breaker to Close. However, you can continue the testing by defeating the Undervoltage release
• Ensure that all arc chutes are fitted and secured properly.
• Give supply to Closing release UN-CR (5) to close the breaker. In case not equipped with closing release, manually close the breaker by pushing the ON button (11b).
• Trip the breaker by giving supply to Shunt release UN-SR (6). In case not equipped with shunt release, manually trip the breaker by pushing the OFF button.
• After tripping through Shunt release, also check tripping through Undervoltage release, if it is energized.
• After checking the voltmetric releases, verify the functioning of other electrical interlocks and indications wherein breaker’s auxiliary contacts or SICs are used.
• Also, verify the Mechanical/Key interlocking of NHP MODpower ACB with other breakers / electrical devices in the scheme.
94
6.4 Setting P&C unit
System SettingsSetting Breaker Rating
Follow the mentioned steps for configuration of breaker ratings
I-frame and In values shall be programmed as per following look-up table.
Breaker Frame Size
Breaker rating (A)
I-Frame in A
In in A
1,2,3 400
630
800
800 400
630
800
1,2,3 1000
1250
1600
1600 1000
1250
1600
1 2000
2500
3200
3200 2000
2500
3200
2,3 2000
2500
3200
4000
4000 2000
2500
3200
4000
Rest of the parameters under System settings should be set in same manner. After programming the settings, press key to escape from menu and confirm the changes in Save Settings.
Note: To apply any parameter change in System settings in P&C unit, reset the power supply once settings are saved.
Press “SEL” key in the overlay
Select “Settings” by SEL key
Select “Config” Mode
Enter the password “0000” (Factory set: default)
Select “MTX Unit” in Config Mode
Select “System Settings”
95
Unit SettingsUnit settings can be programmed following menu navigation Sequence given below
Press “SEL” key
Parameters under unit settings are listed below:
Date & Time : Current date & time to be entered. Helpful for fault history time stamping.
Communication : Total 126 Device Ids are provided along with Parity option, Baud type, Baud rate with wide range up to 19.2kbps.
Event Recorder : To capture an event viz alarm, pick-up, trip, module connect/ disconnect and maintenance.
Max Demand : Maximum demand of energy integration and refreshing interval can be selected.
Settings P/W : The factory default settings password is “0000” which can be modified to new password by user.
Command password : The factory default command password is “0000”. This password is valid for following commands enlisted in “Restore settings” menu, namely Maint. operation, Clear MD. Set Group, Factory Setting, Clear Max I, Clear Max V, Clear Energies and Earth Fault test of the P & C unit. It is configurable.
Contrast : Screen contrast can be adjusted.
Auto set GRP : As per the factory load requirements, protections can be configured using time based set groups. Active set group will switch over to dor-mant set group after the set time elapsed.
Maintenance : This is password protected. Breaker installation date shall be programmed by the service engineer.
Day light saving : Day light saving can be programmed through this option. Enable the Day light saving option, using “DST Mode” Enable and set the Start and End DST dates and the time which is required to add.
Select “MTX Unit” in Config Mode
Select “System Settings”
Select “Settings” by SEL key
Select “Config” Mode
Enter the password “0000” (Factory set: default)
96
ProtectionSet the protection settings as per the following menu navigation sequence.
Press “SEL” key in the overlay
*Two interchangeable protection set groups are provided to meet different load requirements in plant.
Set group 1 is Default active Set group. Time based set group can be programmed through “AUTO SET GRP”.
Protections under I-protection:Overload : It’s a protection against over current. The characteristics are I2t, I4t LI, SI, VI
with Thermal memory. Thermal memory help to reduce the trip time of the unit in case of recursions of overload.
Short Circuit : Excessive currents though the conductors can cause circuit damage, fire, explosion. This protection prevents such conditions.
Directional SC :The protection is a short circuit protection with the ability to recognize the direction of the phases current during the fault period. The current direction makes is possible to determine whether the fault is on the supply or load side of the circuit-breaker. Particularly in ring distribution systems, this makes it possible to identify and disconnect the distribution feeder where the fault has occurred, whilst keeping the rest of the system running.
Instantaneous : This protection works as short circuit protection with no intentional time delay which means release operates in 20 milliseconds as soon as the fault current exceeds the set pick-up.
Note: Refer UW-MTX Release manual for the programming of further pro-tections in detail.
Earth Fault : When fault current flows from phase to earth due to rupturing of insulation, this can lead to arc flash events and electric shock. This causes more damage to the distribution system. This feature provides protection against earth fault current.
Neutral Overload : This provides protection against neutral overload at 50%, 100% & 200% of rated current. It follows overload characteristics.
Under current : Decrease in any phase current below threshold leads to under current.
Current Unbalance : It provides protection against any unbalance in phase currents.
Select “MTX Unit” in Config Mode
Select “Protection”
Select desired set group as active.*
Select “Settings” by SEL key
Select “Config” Mode
Enter the password “0000” (Factory set: default)
97
Settings: Overload configuration:
Similarly set all protection parameters.
After programming the settings, press key to escape from menu and confirm the changes in Save Settings. After doing all the settings Save the set group by pressing the escape key. “Save in Progress” message confirms the Set Group has saved.
Protections under V-protection:Under voltage : When the voltage in one of the phases reduces than threshold, this
protection gets activated.
Over voltage : When the voltage in one of the phases increases above threshold, this protection gets activated.
Voltage unbalance : Voltage unbalance creates damage to the distribution system. This protection checks voltage unbalance in all three phases.
Residual voltage : Give protection against the residual voltage present in the system.
Protections under Freq-protection:Under frequency } applicable for both control frequencies 50HZ & 60Hz.
Over frequency
Protections under Power-protection:Reverse Power : When the direction of the total active power reverses to that of the
set direction, this protection gets activated. The direction of power depends on that of the current flowing.
Leading PF : It checks whether the power factor is dropping down the set value when load is capacitive.
Lagging PF : When the power factor for inductive load goes below the set value, this protection gets activated. Its important for any plant to maintain the power factor to unity.
Protections under other-protection:MD active } When max. demand of active, reactive & apparent
power exceeds the set value, then this protection gets activated.
MD reactive
MD apparent
Phase sequence : Mostly used for motor applications where phase reversal can be seen.
Breaker failure : In case if the breaker fails to open under fault condition (mechanism jam, FSD malfunctions etc.) release issues one more trip command to FSD to operate the breaker as per the set delay through this protection.
Enable O/L Protection Select O/L Char. from the drop down list.
Select delay from the drop down list
98
6.5 Trip simulation of P&C unit
The Salient Features:
• Generation of 3 phase current & voltage test signal (configurable Amplitude, frequency and Phase angles)
• Simulation Kit Active Mode (Powering of Release): 2 hours & stand by mode : 2 days
• Smart GUI with multi functional key operation
• Graphical display (OLED)
• Continuous battery monitoring feature
• CT Continuity test feature
• Memory card for data storage of test scripts and records (extendable up to 32GB)
• Real Time Clock & Temperature sensing feature
• Dual Power ON - Battery or external supply
• Auto sensing of Release connectivity
99
6.6 MODpower ACB’s in Connected1. Rack-in NHP MODpower ACB from ‘Test’ to ‘Connected’ position
Keeping the OFF button (11a) pressed; open the Racking Shutter (16). In case panel door is open, also gently depress racking interlock (26).
CAUTION Carry-out racking operation only when panel door is closed.
Rack-in the breaker to Connected position. Two almost-simultaneous ‘click’ sounds confirm ‘connected’ position.
CAUTIONExcessive forceful racking-in beyond Connected position may lead to product damage.
2. Check tightness of Termination on NHP MODpower ACB and other link/busbars.
3. Complete other Commissioning activities.
4. Check LED indication on P&C unit:
5
6 “Click”“Click”
100
Once breaker starts carrying current, check status of ‘POWER ON’ LED in MTX1.0/MTX1G and OLED displaying 1.5G/2.5/2.5G/3.5/3.5EC. Blinking Green LED implies that the P&C unit is healthy and is protecting your circuit. ‘POWER ON’ LED and OLED display is OFF when there is no/minimal current in the main circuit.
Metering display:Once breaker starts carrying current, UW-MTX units display current values in default metering screen. UW-MTX units display current, Voltage, Frequency, PF, Power, Energy, Max Demand, Temperatures values in auto scrolling mode*. Default current metering screen is shown as an example.1,2,3 represent R, Y, B phases respectively.
*depending on the configuration selected.
POWER ON LED
101
6.7 Securing
ON-OFF Button padlocking (11):
To prevent unauthorized access, ON/OFF buttons can be padlocked or sealed, together or individually.
Sealing the Release cover (31):
Protection setting for Release can be secured using a standard lead seal.
Smart Racking shutter padlocking (16a):
Tools required: Screw Driver (Tip width 3 mm)
To prevent inadvertent racking operation, smart racking shutter can be padlocked, when breaker is in distinct Service, Test or Isolated positions and racking shutter is closed. Upto 3 padlocks can be used at a time.
Padlocking both Buttons
Locking any one Button Sealing Either/Both
buttons
102
7. Maintenance schedule & OperationsRegular maintenance of NHP MODpower Series of breaker will help ensure proper operation, reliable protection and enhanced product life.
CAUTION
• This device should be maintained by authorised qualified personal only.
• Ensure that main and control supply is disconnected, before commencing any work on the device.
• Failure to meet the above precautions can lead to electrocution and result in serious injury/death to personnel.
• It is recommended to call L&T’s Authorised Service Centre for servicing the breaker.
• After maintenance, in P&C unit MTX3.5 give “yes” command to the “maintenance” in “Restore settings”.
Nature of
MaintenanceSchedule/Frequency Actions Reference
Routine
Monthly Check LED indication on P&C unit 7.1a
QuartelySelf-diagnostic test of P&C unit 7.1bTemperature check at termination 7.1c
Yearly
Open & Re-close the breaker 7.1dRack-out & Rack-in breaker 7.1eInspect Arc Chutes for erosion 7.1fInspect Contacts for erosion 7.1g Trip simulation of P&C unit 6.5
1 year or 500 operations (whichever is earlier)
Greasing of Operating Mechanism 7.1h
Specific
When P&C unit trips the breaker
Identify the fault & Reset P&C unit 7.1i
When any Electrical acces-sory needs replacement
Replace the specific accessory 7.1j
When breaker cleares a major fault
Inspect Arc Chutes for erosion & replace, if required
7.1g
Inspect contacts for erosion & replace Main Contacts, if required
7.1g & 7.1k
In case of an abnormal external
event, such as flashover in panel
Inspect Jaw Contacts & replace, if required 7.1l
Inspect Cradle Terminals and replace, if required
7.1m
On completion of Electri-cal life
Replace all Arc Chutes 7.1fReplace all Main Contacts 7.1k
Checking LED indication on P&C unit
POWER ON LED
103
Tools required: None
If ‘POWER ON’ LED is Blinking Green, it implies that the P&C unit is healthy and is protecting your circuit.
If ‘POWER ON’ LED is OFF when there is no/minimal current in the main circuit.
Earth fault test of P&C unit
Tools required: Screw Driver (Tip width 6 mm max)
Remove cover of P&C unit and press ‘T’ button. Enter the command password (default factory set password is “0000”). Unit issues trip in EF and trip, E/F LED glows.
To reset the LEDs, again press the ‘T’ button once the breaker is closed and re-enter the password. This procedures verifies unit is healthy to issue trip in Earth Fault.
Temperature Check:Tools required: Infrared Temperature Scanner
Overheating at terminals and joints can result in serious accidents including flashovers. Regular temperature checks at termination using an ‘Infrared Temperature Scanner’ will help detect any overheating for timely preventive action.
Breaker operation:Tools required: None
In several cases, breaker is rarely operated. Hence, it is important to open and re-close the breaker at regular intervals. Also check for healthy operation of accessories such as Electrical charging device, Closing release and Shunt release.
Racking operation:Tools required: None
If breaker is not being racked-out in a year, it is recommended to carry-out racking operation of the breaker as a part of routine maintenance. Procedure for Racking out & in is detailed in “2.3 Racking-out” on page 15
Door interlock defeat (40):
123
104
Tools required: Philips Head Screw driver (Tip number 2) or Screw driver (Tip width 6 mm)
If the breaker is equipped with Door interlock, panel door cannot be opened when breaker is in Service condition.
If it is necessary to open the panel door with breaker in Service condition, Door interlock can be defeated as illustrated herewith.
CAUTIONOpening panel door when breaker terminals are live, may lead to electric shock and personal injury.
Door Racking Interlock Defeat (26):
Tools required: none
Door Racking interlock prevents opening of smart racking shutter (16) and thus, racking in/out of the breaker when panel door is open.
If it is necessary to rack-out the breaker with panel door open, racking interlock can be defeated. For opening racking shutter with panel door open, gently depress the racking interlock lever (26) in addition to keeping ‘OFF’ button (11a) depressed.
CAUTIONIt is recommended to carry-out racking operation only with panel door closed.
Inspecting Arc-Chutes (21) for erosion:Tools required: None
Pull back the knob and lift the front side of the arc chute.
105
Disengage the rear side and lift arc chute.
Check deion plates for erosion. If plates develop sharp knife-edges, replace arc chutes.
Inspection of Contacts for erosion:Once Arc shuts are opened, contacts are visible and can be inspected for erosion.
Tools required: None
NHP MODpower ACB poles are equipped with an indicator for contact condition.
The adjoining detailed sketch shows the rear edge of the moving contact with breaker in ‘closed’ condition. As contact get eroded, the rear edge moves in the direction indicated by an arrow in the shaded area.
Condition of contact is indicated by alignment of the rear edge with one of 3 markings on the indicator.
This feature is only for indication purposes and contacts should replaced after clearing major fault/on completion of electrical life indicated.
Deion plates
Visual Inspection of Arcing and Main contacts
Cut-view of Moving part Cut-view of Fixed part
106
Greasing of Mechanism:
Greasing schedule Mechanism: 1 year or 500 operations, whichever is earlier grease to be used: Mobilith SHC-100 of mobill. Greasing schedule Cradle: 1 year or 50 operations, whichever is earlier Grease to be used: Mobilith SHC-100 of Mobill.
The following components can be greased, without dismantling any accessory or component, using a brush.
1: Pole shaft bearing (all)
2: Bearings (both sides of mechanism)
3: Cam Profile
4: Top surface of links (2)
5: Top surface of link
6: Rubbing surface of link
CAUTION
Non-adherence to greasing schedule or using other-than-specified grease may lead to malfunction.
Ensure that ACB is OFF and Spring is Discharged, before commencing greasing operation.
1: Racking Screw
2: Racking Cam & Drop Pin joint
3: Base Plate
4: Rail Sliding surface on side plate
5: Racking Cam & Service Latch follower
6: Gear Teeth & Rack Slots
7: Bottom & side Sliding Surfaces of Rails on Side Plate
8: Service Latch on Side Plates
9: Guiding surface of cradle SIC Bridge
Needs replacement
Indicator on each pole
Rear edge of moving contact moves forward due to erosion
Intermediate
Good
107
Apply grease to the specified components at rubbing surfaces.
Simplified diagram for identification of components to be greased.
Simplified diagram for identification of components to be greased.
9
5
4
21
3 6
7
8
3
4
5
6
1
2
108
Fault Identification and Resetting:Tools required: Screw Driver (Tip width 6 mm max)
Fault identification:
1. When P&C unit trips the breaker, a mechanical indication is provided through popping-out of the red pointer at the upper end of the unit.
With Auto reset feature, the pointer will reset automatically.
2. To identify the type of fault, open the P&C unit cover and press ‘Query’ button. The LED corresponding to the fault seen by the breaker will glow. This local fault indication is independent of auxiliary supply or batteries and is available to USERS for repeat usage* after the fault.
Reclosing the breaker:
3. After taking the necessary corrective action. Press ‘clear’ button to reset the fault indication.
4. For breakers with ‘Manuals resetting mode’, push-in the red pointer and fix the release cover back.
Now, breaker can be reclosed.
Replacement of Electrical Accessories:Tools required: Screw Driver (Tip width 3 mm)
Allen key 5 mm (for Electrical Charging Device)
After removing facia access breaker SIC
*Availability of indication depends on time elapsed after the fault and duration for which ‘Query’ button is pressed.
4
1
109
Pull out the specific breaker SIC from the bridge with the screw driver.
For removing Volumetric release, depress the lever under the release and slide it out.
For removing Electrical Charging Device, remove 2 allen screws.
Install the new accessory and fix new breaker SICs, pre-wired with the new accessory.
Replacement of Main Contacts:MODpower facilitates replacement of pole assembly in a phase-by-phase manner. USERS can determine whether to replace one pole or multiple poles, based on condition of contacts. However, at the end of electrical life, all poles need to be replaced.
Tools required:
- Screw Drivers: a. Tip width 8 mm or Philip head (tip no. 2)
- b. Length 200 mm min, Tip width 6 mm, Tip thickness 1 mm max
- Allen key : 5 mm, Shank length 120 mm
- Box spanner : M6, length 300 mm min.
First close the breaker and then remove arc chutes & CT covers
110
Remove the CTs, without disturbing their connections with the P&C unit.
Remove connector pin and trip the breaker.
Remove hex socket head screws (10 nos.), using min. 80 mm long M6 key.
111
Separate rear housing from front housing, without disturbing CT wires.
Remove fasteners.
Moving part of the pole can now be removed
112
To take out fixed part of the pole, remove 1 screw from rear side and 2 screws from top as shown.
Replace fixed part of the pole.
Also, replace Moving part of the pole.
113
Refix fasteners, Align front & rear housings and tighten hex socket head screws.
Depress Arc-chute interlock lever to defeat the interlock and close the breaker.
Refix the connector pin, followed by CTs and CT covers. After verifying closing of poles through few ON-OFF operations, refix the arc chutes.
114
Replacement of Jaw Contacts (3j):Contacts Jaws may require replacement in the event of a flashover or on clearing a major fault.
Tools required: None*
Jaws can be replaced without using any tool. Slightly rotate the jaw left or right to remove it.
Replacement of Cradle Terminals & Supports (35):Tools required: Screw Driver (Blade-Length 300 mm & Dia 8 mm, Tip width 8 mm)
Remove screws ‘A’ and loosen screws ‘B’. As a result, Removing of Safety Shutter, jaws and Terminal support clamp will drop down.
115
Pull out the cradle terminal assembly using projections on the terminal support.
Now you can replace the cradle terminals & jaw cluster assemblies.
116
8. TroubleshootingSituation Probability Solution
ACB does not close on pressing “ON” button
One or more arc-chute (s) not secured properly
Press each arc chute firmly by hand
U/V release is present but not energized
Energize U/V release
Mechanism spring is not charged. Indicator is in black background
Charge the mechanism spring manually till a distinct sound is heard & indicator turns yellow
Trip Reset link is projecting out Press trip reset link to reset position
Smart Racking Shutter is open Close the Smart Racking Shutter (Insert Racking Handle once & pull back)
“OFF” button is locked Unlock “OFF” button
Mechanical Interlock disables closing
Re-check before attempting to close the breaker
Smart Racking Shutter does not re-close automatically after racking handle is pulled out
Breaker is in-between Connected/Test/Disconnected position. Position indicator is not aligned with any of the positions
Rack-in or out the breaker to any of the distinct positions
ACB cannot be pushed into disconnected position
Breakers & Cradle ratings do not match
Put correct breaker
Smart Racking Shutter does not open
“OFF” button not kept pressed fully Keep OFF button pressed
Door open/missing: hence door Racking Interlock (26) is active
Clear/provide door; else press door racking interlock lever (on extreme lower left side) manually
Position lock(s) active Unlock
ACB does not close electrically Electrical antipumping is active Interrupt ‘Close’ command once
“Ready to close” (RTC) conditions are not met
Check all RTC conditions
ACB trips after closing Overload fault exists if tripping is after several seconds or minutes. Other fault(S) exist if tripping is within a second
Press “QUERY” button on Protection & Control (P&C) Unit to confirm type of fault. Clear the cause of fault. Press “CLEAR” button on P&C Unit. Push back the red Reset Link
(RED) reset link projects out
Shunt Release is getting command continuously
Check the source of command
117
MODpower Air Circuit Breakers
MP1 3 pole MODbreak ACB
Features• Customer fit accessories
• LSIG Protection
• Fixed or Withdrawable
• 3 or 4 pole types
• MP1 and MP2 65kA interrupting capacity
• MP3 80kA interrupting capacity
• Fault interruption ratings Icu = Ics
• Internal and external accessory range
• Selectivity and other data available
• NHP MODcurve selectivity and Cadblocks available
118
Withdrawable ACBs
Frame Size Ampere Rat-ing (A)
Mounting Poles Catalogue Number
3 pole Price $
1250 MP1S12E3WD
1600 MP1S16E3WD
MP1 2000 withdrawable 3 MP1S20E3WD
2500 MP1S25E3WD
MP2 3200 MP2S32E3WD
MP3 4000 MP3H40E3WD i1250 MP1S12E4WD i1600 MP1S16E4WD i
MP1 2000 withdrawable 4 MP1S20E4WD i2500 MP1S25E4WD i
MP2 3200 MP2S32E4WD iMP3 4000 MP3H40E4WD i
Fixed ACBs
Frame Size Ampere Rat-ing (A)
Mounting Poles Catalogue Number
3 pole Price $
1600 MP1S16E3FD
MP1 2000 Fixed 3 MP1S20E3FD
2500 MP1S25E3FD
Neutral Pole Ground Fault CTs
Ampere Rating (A)
Catalogue Number
3 pole Price $
1250 MPGFCT12
1600 MPGFCT16
2000 MPGFCT20
2500 MPGFCT25
3200 MPGFCT32
4000 MPGFCT40 ii Refers to Indent Items
Refer www.nhp.com.au Mod-series web page for additional technical product information.
119
MODpower Air Circuit Breakers
Internal Accessories – MODpower ACBsAll internal accessories can be fitted by the user.
Accessory type Voltage Catalogue number Price $
Shunt Trip Coil 24VDC MPSHUNT24VDC
240VAC MPSHUNT240VAC
415VAC MPSHUNT415VAC
Shunt Indication Contact MPSHTCONTACT
Time delay UVT 24VDC MPUVT24VDC
240VAC MPUVT240VAC
415VAC MPUVT415VAC
UVT Indication Contact MPUVTCONTACT
Remote Close Coil 24VDC MPCLOSE24VDC
240VAC MPCLOSE240VAC
415VAC MPCLOSE415VAC
Spring Charge Motor 24VDC MPMOTOR24VDC
240VAC MPMOTOR240VAC
415VAC MPMOTOR415VAC
Common Trip Contact MPCTCONTACT
Ready to Close Contact MPRTCCONTACT
Key Interlock MPKEYINTERLOCK
Position Contact MPPOSCONTACTSTI
Cycle Counter MPCYCLECOUNTER
Refer www.nhp.com.au Mod-series web page for additional technical product information.
121
OCR Accessories – MODpower ACBsAll OCR accessories can be fitted by the user.
Accessory type Voltage Catalogue number Price $
Power Supply Module 85-265 VAC MPPSMODULEAC
120-375 VDC
OCR Plug in Modules:
MODBUS MPMODMODBUS
PROFIBUS MPMODPROFIBUS i Energy Metering MPMODVOLTAGE
Smartcard MPMODSMARTCARD iMTX OCR Checker MPOCRTESTDEVICE
i Refers to Indent Items
Refer www.nhp.com.au Mod-series web page for additional technical product information
PS
Power Supply (24Vdc)
- Operating voltage 85-265 Vac, 125-300Vdc
- DIN rail/Base mountable module
123
MODpower Air Circuit Breakers
External Accessories – MODpower ACBsAll external accessories can be fitted by the user.
Accessory type Catalogue number Price $
Racking Error Device MPRACKERROR
Mechanical Interlock
1 of 2 interlock
2 Meter MPMECHINT2MT12
3 Meter MPMECHINT3MT12
5 Meter MPMECHINT5MT12 i
1 of 3 interlock
2 Meter MPMECHINT2MT13 i 3 Meter MPMECHINT3MT13 i 5 Meter MPMECHINT5MT13 i
2 of 3 interlock
2 Meter MPMECHINT2MT23
3 Meter MPMECHINT3MT23
5 Meter MPMECHINT5MT23 i
Door Interlock MPDOORINTERLOCK
Additional Position Contact 1 MPPOSCONTACTX1 iAdditional Position Contact 2 MPPOSCONTACTX2 i
IP40 Gasket (Fixed ACB) MPGASKETFD
IP40 Gasket (Withdrawable ACB) MPGASKETWD
IP54 Hinged Cover MPCOVER
i Refers to Indent Items
Refer www.nhp.com.au Mod-series web page for additional technical product information.
124
MODpower Air Circuit Breakers
Spare parts list
Body - MODpower ACBs
Description Catalogue number Price $
Auxiliary Contacts (4NO4NC) MPAUXCONTACTS
OCR MTX3.5 24VDC MPOCRMTX35
ON/OFF Button Cover MPONOFFCOVER
10 x Control Wiring Contacts MPSICCONTACTS
Cradle – MODpower ACBs
Description Catalogue number Price $
Racking Handle MPRACKINGHANDLE
Safety Shutter MPSHUTTER
MP1 3P Cradle 1250A MP1CRADLE123
MP1 3P Cradle 1600A MP1CRADLE163
MP1 3P Cradle 2000A MP1CRADLE203
MP1 3P Cradle 2500A MP1CRADLE253
MP2 3P Cradle 3200A MP2CRADLE323 iMP3 3P Cradle 4000A MP3CRADLE403 i
MP1 3P Arc Shield MP13ARCSHIELD iMP1 4P Arc Shield MP14ARCSHIELD iMP2 3P Arc Shield MP23ARCSHIELD iMP2 4P Arc Shield MP24ARCSHIELD i
MP1 Fixed 2000A - Terminal (V or H) MP1TERM2000FD
MP1 Withdrawable 2000A - Terminal (V or H) MP1TERM2000WD
MP1 Fixed 2500A - Terminal (V Only) MP1TERM2500FD
MP1 Withdrawable 2500A - Terminal (V Only) MP1TERM2500WD
MP2 Withdrawable Terminal (V or H) MP2TERM3200WD
MP3 Withdrawable Terminal (V only) MP3TERM4000WD iRefer www.nhp.com.au Mod-series web page for additional technical product information
NHP Electrical Engineering Products Pty LtdA.B.N. 84 004 304 812
FILENAME MONTH YEAR © Copyright NHP 2013
AUSTRALIAnhp.com.au
SALES 1300 NHP NHP
FAX 1300 NHP FAX
VICTORIAMelbourne 43-67 River Street Richmond VIC 3121 Tel +61 3 9429 2999
Laverton 104-106 William Angliss Drive Laverton North VIC 3026 Tel +61 3 9368 2901
Albury / Wodonga 847 Ramsden Drive Albury NSW 2640 Tel +61 2 6049 0600 Fax +61 3 6025 0592
Dandenong 40-42 Cyber Loop Dandenong South VIC 3175 Tel +61 3 8773 6400 Fax +61 3 8768 8522
TASMANIAHobart 29B Lampton Ave Derwent Park TAS 7009 Tel +61 3 6228 9575 Fax +61 3 6228 9757
Launceston Unit 3 13-17 Merino Street Kings Meadows TAS 7249 Tel +61 3 6345 2600 Fax +61 3 6344 6324
NEW SOUTH WALESSydney 30-34 Day Street North Silverwater NSW 2128 Tel +61 2 9748 3444
Newcastle 575 Maitland Road Mayfield West NSW 2304 Tel +61 2 4960 2220 Fax +61 2 4960 2203
Wollongong 34 Industrial Road Unanderra NSW 2526 Tel +61 2 4272 5763 Fax +61 2 4272 5957
ACTCanberra Unit1 187 Gladstone Street Fyshwick ACT 2609 Tel +61 2 6280 9888 Fax +61 2 6280 9588
WESTERN AUSTRALIAPerth 38 Belmont Ave Rivervale WA 6103 Tel +61 8 9277 1777
NORTHERN TERRITORYDarwin 3 Steele Street Winnellie NT 0820 Tel +61 8 8947 2666 Fax +61 8 8947 2049
QUEENSLANDBrisbane 16 Riverview Place Murarrie QLD 4172 Tel +61 7 3909 4999
Townsville 5 Leyland Street Garbutt QLD 4814 Tel +61 7 4779 0700 Fax +61 7 4775 1457
Rockhampton 1 Lawson Street Parkhurst QLD 4702 Tel +61 7 4927 2277 Fax +61 7 4922 2947
Toowoomba Cnr Carroll Street and Struan Court QLD 4350 Tel +61 7 4634 4799 Fax +61 7 4633 1796
Cairns Unit 2 1 Bramp Close Portsmith QLD 4870 Tel +61 7 4035 6888 Fax +61 7 4035 6999
SOUTH AUSTRALIAAdelaide 36-38 Croydon Road Keswick SA 5035 Tel +61 8 8297 9055
NEW ZEALANDnhp-nz.com
SALES 0800 NHP NHP
FAX 0800 FAX NHP
PO Box 62-009 Sylvia Park Auckland 1644 New Zealand
Auckland 118a Carbine Road Mt Wellington 1060
Hamilton 78 Rostrevor Street Hamilton 3204
Napier 126 Taradale Road Onekawa 4110
New Plymouth 2 Dean Place Waiwhakaiho 4312
Wellington 52 Victoria Street Lower Hutt 5010
Christchurch 27 Iversen TerraceWaltham 8011
Dunedin 30 Fox StreetSouth Dunedin 9012
Scan the QR code to download the eCatalogues App