module v – advanced fire modeling · module v – advanced fire modeling. example a: control room...
TRANSCRIPT
Joint EPRI/NRC-RES Fire PRA WorkshopAugust 13-17, 2018
Kevin McGrattan – NIST
Fred Mowrer – Cal. Poly State University
Module V – Advanced Fire Modeling
Example A: Control Room Fire
Example B: Switchgear Cabinet Room Fire
A Collaboration of the Electric Power Research Institute (EPRI) & U.S. NRC Office of Nuclear Regulatory Research (RES)
2
Step 1. Define Fire Modeling Goals
Determine the length of time that the Main Control Room (MCR) remains habitable after the start of a fire within a low-voltage control cabinet. Follow guidance provided in Chapter 11 of NUREG/CR-6850
(EPRI 1011989), Volume 2, “Detailed Fire Modeling (Task 11).” Note that MCR fire scenarios are treated differently than fires
within other compartments, mainly because it is necessary to consider and evaluate forced abandonment in addition to equipment damage.
3
Step 2. Characterize Fire Scenarios
General DescriptionGeometryMaterialsFire Protection SystemsVentilationFireHabitability and Human Factors
4
5
Typical “open grate” ceiling
6
7
Typical Control Room Cabinet
8
Material Properties
For non-burning materials, the most important properties are thermal conductivity, k, density, ρ, and specific heat, cFor specified burning rates, you need:
– Heat Release Rate (HRR) or HRR Per Unit Area (HRRPUA)– Heat of Combustion – energy released per unit mass consumed
For predicting the burning rate, you need:– Heat of Vaporization (liquids)– Heat of Gasification (solids)– Kinetic constants for reaction rates– (typically not used for NPP applications)
9
Typical material properties for common construction and cable materials
10
Ventilation
25 Air Changes Per Hour (ACH) for purge modeTwo scenarios – purge mode or ventilation inoperativeLeakage – often the “leakage area” is the area of the crack
under the doorExact supply and exhaust location only important for CFDZone models usually only consider height of mechanical
ventilation injection and extraction grilles
11
Fire
HRR taken from Appendix G, NUREG/CR 6850 (EPRI 1011989)
Note: This guidance has been replaced by RACELLE-FIRE
12
New Guidance for Electrical Enclosure HRR
RACHELLE-FIRE (Refining And Characterizing Heat Release Rate from ElectricalEnclosures During Fire) NUREG-2178, EPRI 3002005578
13
14
Fire
What is burning?
Cables made of polyethylene (C2H4) and neoprene (C4H5Cl)
Assume effective fuel: C3H4.5Cl0.5
15
Habitability
Criteria for habitability (NUREG/CR-6850, Vol 2, Chap 11)• Gas Temperature 2 m off the floor is 95 °C• Heat Flux exceeds 1 kW/m2
• Optical Density exceeds 3 m-1
What is Optical Density?
Smoke Concentration (kg/m3)
Mass Extinction Coefficient (8700 m2/kg)
16
Step 3. Select Fire Models
Algebraic Models: FPA algorithm in FIVE and FDTs provides estimate of HGL temperature within a closed, ventilated compartment. – FDTs do not allow for time-dependent HRR
Zone Models: CFAST includes smoke obscuration. MAGIC does not.CFD: Provides more detailed information at exact location of
operators
17
Applicability of Validation
YesNUREG-1824, Supplement 1
0.2-9.1
YesNew Range
0.0-0.6
YesNew Range
0.3-8.0
18
From: NUREG-1824, Supplement 1
19
Applicability of Validation
For the scenario with no ventilation, the classic definition of the Equivalence Ratio does not apply because there is no supply of oxygen in the room. However, it can be shown that there is sufficient oxygen in
the room to sustain the specified fire.
20
Step 4. Calculate Fire-Generated Conditions
21
Step 4. Calculate Fire-Generated Conditions
Temperature in smoke purge scenario– Use FPA correlation in FIVE-rev1 or FDTs
Need equivalent length / width of non-rectangular rooms
Other input parameters
22
Step 4. Calculate Fire-Generated Conditions
23
24
CFAST Calculation
25
FDS Simulation
26
Step 4. Calculate Fire-Generated Conditions
0
20
40
60
80
100
120
140
0 600 1200 1800 2400 3000 3600
Tem
pera
ture
(C)
Time (s)
Temperature near Operator
FPA (Purge)
CFAST (No Vent.)
CFAST (Purge)
FDS (No Vent.)
FDS (Purge)
27
Step 4. Calculate Fire-Generated Conditions
0
1
2
3
4
5
6
0 600 1200 1800 2400 3000 3600
Heig
ht (m
)
Time (s)
HGL Height
CFAST (No Ventilation)
FDS (No Ventilation)
28
Step 4. Calculate Fire-Generated Conditions
0.0
0.2
0.4
0.6
0.8
1.0
0 600 1200 1800 2400 3000 3600
Hea
t Flu
x (k
W/m
2 )
Time (s)
Heat Flux to Operator
FIVE (Purge)
CFAST (No Vent.)
CFAST (Purge)
FDS (No Vent.)
FDS (Purge)
29
Step 4. Calculate Fire-Generated Conditions
0.0
10.0
20.0
30.0
40.0
50.0
60.0
0 600 1200 1800 2400 3000 3600
Optic
al D
ensi
ty (1
/m)
Time (s)
Optical Density near Operator
SFPE (Purge)CFAST (No Vent.)CFAST (Purge)FDS (No Vent.)FDS (Purge)
30
Step 5. Sensitivity and Uncertainty Analysis
Uncertainty Analysis quantifies the model uncertainty– List the predicted quantities and the critical values of these quantities
Sensitivity Analysis can be used to assess parameter uncertainty
31
Step 5. Sensitivity and Uncertainty Analysis
32
Step 5. Sensitivity and Uncertainty Analysis
33
Step 5. Sensitivity and Uncertainty Analysis
34
Step 5. Sensitivity and Uncertainty Analysis
35
Step 5. Sensitivity and Uncertainty Analysis
36
Step 5. Sensitivity and Uncertainty Analysis
37
Step 6. Document the Analysis
Follow the steps; clearly explain the entire processAnswer the original questionReport model predictions with uncertainty and sensitivity
included Include all references
38
Step 6. Document the Analysis
39
Step 6. Document the Analysis
Joint RES/EPRI Fire PRA Workshop
August, 2018
Rockville, Maryland
EPRI/NRC-RES FIRE PRA METHODOLOGY
Module 5Advanced Fire ModelingExample B: Switchgear Room Cabinet Fire
41
Step 1. Define Fire Modeling Goals
Estimate the effects of fire in a cabinet in a Switchgear Room on nearby cable and cabinet targets. Switchgear Room contains safety-related equipment for both
Train A and Train B that are not separated as required by Appendix R. The purpose of the calculation is to analyze this condition
and determine whether these targets fail, and, if so, at what time failure occurs.Follow guidance provided in Chapter 11 of NUREG/CR-6850
(EPRI 1011989), Volume 2, “Detailed Fire Modeling (Task 11).”
42
Step 2. Characterize Fire Scenarios
General DescriptionGeometryMaterialsVentilationFireFire Protection Systems
– None credited for this scenario
43
44
Material Properties
45
Ventilation
Design flowrate specified for each of three supply and return registers.Normal operation continues during the fire.Leakage – often the “leakage area” is the area of the crack
under the door.Exact supply and exhaust location only important for CFD.Zone models usually only consider height of ducts off floor
and orientation of the vent.
46
Fire
HRR taken from Appendix G, NUREG/CR 6850 (EPRI 1011989)
Note: This guidance has been replaced by RACHELLE-FIRE
47
New Guidance for Electrical Enclosure HRR
RACHELLE-FIRE (Refining And Characterizing Heat Release Rate from ElectricalEnclosures During Fire) NUREG-2178, EPRI 3002005578
48
Fire
• Original fire source is specified atop the central cabinet.
• FLASH-CAT model (NUREG/CR-7010, Volume 1) is used to determine the ignition, flame spread and extinction of the cables above the original fire source.
49
Fire
What is burning?
Cables made of polyethylene (C2H4) and polyvinylchloride (C2H3Cl).
Assume effective fuel: C2H3.5Cl0.5
50
Step 3. Select Fire Models
Algebraic Models: FPA algorithm in FIVE provides estimate of HGL temperature within a closed, ventilated compartment. FDTs do not allow for time-dependent HRR. Both FIVE and FDTs can estimate heat flux from a fire to a target.Zone Models: Both CFAST and MAGIC include algorithms
to estimate the heat flux to and temperature of cable targets.CFD: Typical application of FDS. The primary advantage of a
CFD model for this fire scenario is that the CFD model can predict local conditions at the specific location of the target cables and adjacent cabinet.
51
Applicability of Validation
0.2-9.1
0.0-1.6
0.0-8.3
0.0-0.6
0.6-8.3
0.3-8.0
Yes
52
Step 4. Calculate Fire-Generated Conditions
53
Step 4. Calculate Fire-Generated Conditions
54
Step 4. Calculate Fire-Generated Conditions
Should be 6.1 m
55
Step 4. Calculate Fire-Generated Conditions
56
CFAST Calculation
57
FDS – Smokeview rendering of SWGR fire
58
FDS – Smokeview rendering of SWGR fire
59
Step 4. Calculate Fire-Generated Conditions
60
Step 4. Calculate Fire-Generated Conditions
61
Step 4. Calculate Fire-Generated Conditions
62
Step 4. Calculate Fire-Generated Conditions
63
Step 5. Sensitivity and Uncertainty Analysis
64
Step 5. Sensitivity and Uncertainty Analysis
65
Step 5. Sensitivity and Uncertainty Analysis
66
Step 5. Sensitivity and Uncertainty Analysis
67
Step 6. Document the Analysis
Follow the steps; clearly explain the entire processAnswer the original questionReport model predictions with uncertainty and sensitivity
included Include all references
68
Step 6. Document the Analysis