moisture performance of walls in energy efficient …/media/files/reports/moisture... · 400 prince...
TRANSCRIPT
-
400 Prince George’s Blvd. | Upper Marlboro, MD 20774 | 800.638.8556 | HomeInnovation.com
MOISTURE PERFORMANCE OF
WALLS IN ENERGY EFFICIENT
HOMES
Prepared For
NAHB Construction Technology Research
Subcommittee (CTRSC)
August 2014
Report No. 5932.001_08142014
-
Disclaimer
Neither Home Innovation Research Labs, Inc., formerly the NAHB
Research Center, Inc., nor any person acting on its behalf, makes any
warranty, expressed or implied, with respect to the use of any
information, apparatus, method, or process disclosed in this publication
or that such use may not infringe privately owned rights, or assumes
any liabilities with respect to the use of, or for damages resulting from
the use of, any information, apparatus, method, or process disclosed in
this publication, or is responsible for statements made or opinions
expressed by individual authors.
-
Home Innovation Research Labs August 2014 Wall Moisture Testing i
TABLE OF CONTENTS
Definitions ........................................................................................................................................ v
Purpose ............................................................................................................................................ 1
Background ...................................................................................................................................... 1
Research Methodology .................................................................................................................... 3
Research Home Criteria and Selected Locations ......................................................................... 3
Wall System Configurations and Sensor Locations ...................................................................... 5
Monitoring System and Data Collection ...................................................................................... 9
In-Service Environmental Conditions Monitoring ..................................................................... 10
Monitoring System ..................................................................................................................... 10
Sensor Calibration ...................................................................................................................... 11
Wall Cavity and Environmental Conditions Measurement Results ............................................... 13
Reference Moisture Content for Oriented Strand Board (OSB) ................................................ 13
OSB Sheathing Moisture Content Results by Test Site .............................................................. 13
Climate Zone 6 ....................................................................................................................... 13
Climate Zone 5 ....................................................................................................................... 16
Climate Zone 4C ..................................................................................................................... 20
Climate Zone 4A ..................................................................................................................... 22
Climate Zone 3 ....................................................................................................................... 26
Climate Zone 2 ....................................................................................................................... 28
Seasonal Average Data Summaries and Analysis ........................................................................... 30
Climate Zone 6 ........................................................................................................................... 30
Climate Zone 5 ........................................................................................................................... 32
Climate Zone 4C ......................................................................................................................... 34
Climate Zone 4 ........................................................................................................................... 35
Climate Zone 3 ........................................................................................................................... 36
Climate Zone 2 ........................................................................................................................... 38
Condensation Resistance Analysis ............................................................................................. 39
Analysis Based on ASHRAE 160-2009 ........................................................................................ 44
-
August 2014 Home Innovation Research Labs ii Wall Moisture Testing
Wall Cavity Inspection ................................................................................................................ 46
General Observations Based on Seasonal Measured Data ............................................................ 47
Indoor Humidity ......................................................................................................................... 47
OSB Moisture Content ............................................................................................................... 48
Dew Point Calculations .............................................................................................................. 49
ASHRAE 160 Criteria ................................................................................................................... 50
Wall orientation ......................................................................................................................... 50
Summary Conclusions .................................................................................................................... 50
Bibliography ................................................................................................................................... 54
Appendix A ..................................................................................................................................... 56
Wall Cavity Temperature Charts .................................................................................................... 56
Appendix B: Wall Cavity Relative Humidity Charts ........................................................................ 67
Appendix C: Summary Moisture Performance by Wall Type ........................................................ 78
Appendix D: Daily Indoor Temperature and Relative Humidity for Each Test Site ....................... 91
-
Home Innovation Research Labs August 2014 Wall Moisture Testing iii
TABLES Table 1. Summary of Test Sites ..................................................................................................................... 5
Table 2. Wall Configurations in Test Houses................................................................................................. 6
Table 3. Summary of Test Wall Configurations by Construction Type ......................................................... 7
Table 4. Winter Average Seasonal Interior House Relative Humidity for CZ 6 Test Walls ......................... 31
Table 5. Winter Average Seasonal Interior House Relative Humidity for CZ 5 Test Walls ......................... 33
Table 6. Winter Average Seasonal Interior House Relative Humidity for CZ 4 Test Walls ......................... 36
Table 7. Winter Average Seasonal Interior Humidity for CZ 3 Test Walls .................................................. 37
Table 8. Winter Average Seasonal House Interior Relative Humidity for CZ 2 Test Walls ......................... 38
Table 9. Standard 160 Condition Criteria Necessary to Minimize Mold Growth ....................................... 45
Table 10. Overall Summary of Highest Average Sheathing Moisture Content ........................................... 51
FIGURES Figure 1. Map Showing Locations of Test Home Sites .................................................................................. 4
Figure 2. Example Sensor Layout for a Test House ....................................................................................... 8
Figure 3. Sensor Installed in OSB Sheathing That Will be Foamed Over in This Test House ........................ 9
Figure 4. Sensor Installed in OSB Sheathing That Will Not be Foamed Over in This Cavity ......................... 9
Figure 5. Sensor After Foam Flash and Before Insulation ............................................................................. 9
Figure 6. Sensor Installed in Lumber in Cavity With Only Foam Sheathing .................................................. 9
Figure 7. Omnisense S-900-1 Sensor .......................................................................................................... 11
Figure 8. Screws used to Install Moisture Sensors...................................................................................... 11
Figure 9. Sensors in the Environmental Chamber for Calibration .............................................................. 12
Figure 10. OSB Moisture Content Sensor Calibration Curves ..................................................................... 12
Figure 11. CZ 6A, MI (1), MC Readings for 2 Winter Periods ...................................................................... 14
Figure 12. CZ 6A, MI (2), MC Readings for the First Winter Period ............................................................ 15
Figure 13. CZ 6A, WI, MC Readings for a 14-Month Period ........................................................................ 16
Figure 14. CZ 5A, MI (1), MC Readings for a 3-Month Period ..................................................................... 17
Figure 15. CZ 5A, MI (2), MC Readings for a 3-Month Period ..................................................................... 17
Figure 16. CZ 5A, MI (3), MC Readings for a 3-Month Period ..................................................................... 18
Figure 17. CZ 5A, IA (1), MC Readings for a 4-Month Period ...................................................................... 19
Figure 18. CZ 5A, IA (2), MC Readings for a 4-Month Period ...................................................................... 19
Figure 19. Climate Zone 5 Test House Precipitation and Temperature Comparison ................................. 20
Figure 20. CZ 4C, WA (1), MC Readings for a 5-Month Period ................................................................... 21
Figure 21. CZ 4C, WA (2), MC Readings for a 6-Month Period ................................................................... 21
Figure 22. CZ 4A, MD-1, MC Readings for a 2-Year Period ......................................................................... 22
Figure 23. CZ 4A, MD-2, MC Readings for an 18-Month Period ................................................................. 23
Figure 24. CZ 4A, MD-3, MC Readings for a 19-Month Period ................................................................... 24
Figure 25. CZ 4A, MD-4, MC Readings for an 18-Month Period ................................................................. 24
Figure 26. Climate Zone 4 MD Test House Precipitation and Temperature Comparison .......................... 25
-
August 2014 Home Innovation Research Labs iv Wall Moisture Testing
Figure 27. CZ 4A, DE, MC Readings for a 14-Month Period ........................................................................ 26
Figure 28. CZ 3A, AL-1, MC Readings for a 6-Month Period ....................................................................... 27
Figure 29. CZ 3A, AL-2, MC Readings for a 6-Month Period ....................................................................... 27
Figure 30. CZ 3A, TX, MC Readings for a 3.5-Month Period ....................................................................... 28
Figure 31. CZ 2A, LA-1, MC Readings for a 4.5-Month Period .................................................................... 29
Figure 32. CZ 2A, LA-2, MC Readings for a 4.5-Month Period .................................................................... 29
Figure 33. CZ 2A, LA-3, MC Readings for a 4.5-Month Period .................................................................... 30
Figure 34. Climate Zone 6 Summary MC Data ............................................................................................ 31
Figure 35. Climate Zone 5 Summary MC Data ............................................................................................ 33
Figure 36. Climate Zone 4C Summary MC Data .......................................................................................... 34
Figure 37. Climate Zone 4 Summary MC Data ............................................................................................ 35
Figure 38. Climate Zone 3 Summary MC Data ............................................................................................ 37
Figure 39. Climate Zone 2 Summary MC Data ............................................................................................ 38
Figure 40. Condensing Surface Calculation Parameters ............................................................................. 40
Figure 41. MI Test Site, Theoretical Condensation Potential ..................................................................... 41
Figure 42. MI Test Site, Measured Condensation Potential ....................................................................... 41
Figure 43. MI Test Site (1), CZ5, Measured Condensation Potential .......................................................... 42
Figure 44. MI Test Site (2), CZ5, Measured Condensation Potential .......................................................... 42
Figure 45. MI Test Site (3), CZ5, Measured Condensation Potential .......................................................... 43
Figure 46. MD Test Site, Theoretical Condensation Potential .................................................................... 43
Figure 47. MD Test Site, Measured Condensation Potential ...................................................................... 44
Figure 48. MI Test Site, ASHRAE 160, S6.1 Duration When Criteria Exceeded in Cavity ............................ 45
Figure 49. Insulation Removed from R-46 Wall for Observation ................................................................ 46
Figure 50. Moisture Sensor Located in Wall Section .................................................................................. 46
Figure 51. Moisture Meter Reading Correlated with Sensor ...................................................................... 47
Figure 52. Indoor Relative Humidity Averages for 20 Test Sites by Climate Zone ...................................... 48
Figure 53. Wall Cavity Seasonal Average Moisture Content ...................................................................... 49
-
Home Innovation Research Labs August 2014 Wall Moisture Testing v
Definitions
ACH50 Building air changes per hour at a 50 Pascal interior pressure differential with
respect to the exterior
batt Insulation configured as a blanket or sheet element that is typically designed to
fit within the framing wall cavity
ccSPF Closed cell spray polyurethane foam
CZ Climate zone (applicable to building energy efficiency analysis) defined based on
heating degree days, average temperatures, and precipitation, and developed
along county lines for the United States.
DOE
EPA
ERV
Flash coat
HRV
HSPF
United States Department of Energy
United States Environmental Protection Agency
Energy Recovery Ventilator
A layer of closed-cell spray foam installed on the exterior sheathing that does
not take the building cavity typically to allow for installation of another type of
cavity insulation.
Heat Recovery Ventilator
Heating Seasonal Performance Factor, defined as the ratio between the thermal
energy supplied and the electrical energy absorbed by the heat pump over the
heating season
IECC International Energy Conservation Code, an energy conservation building code
for residential and commercial structures, most recently published as the 2012
IECC by the International Code Council
IRC International Residential Code, a building code for residential one- and two-
family structures, most recently published as the 2012 IRC by the International
Code Council
Kraft facing Face layer on batt insulation that is generally vapor semi-impermeable (Class II)
MC Moisture content (gravimetric); defined as the weight of the water contained in
the wood expressed as a percentage of the oven-dry weight of the wood
NAHB National Association of Home Builders, a building trade association
ocSPF Open cell spray polyurethane foam
-
August 2014 Home Innovation Research Labs vi Wall Moisture Testing
OSB Oriented strand board
Poly Polyethylene sheet material that is vapor impermeable (Class I)
Polyiso Polyisocyanurate rigid foam board insulation
RA
R-value
Return air, Air removed from conditioned space and circulated or exhausted
Magnitude of the insulation resistance to heat flow with the dimension of
hr∙°F∙ft2/Btu
SEER Seasonal Energy Efficiency Ratio, is the total cooling output (in British thermal
units or Btu) provided by the air conditioning unit (or heat pump) during its
normal annual usage period divided by its total energy input (in watt-hours)
during the same period
sf
Vinyl
Spray foam
Vinyl siding used as the outermost exterior finish
WME Wood moisture equivalent, a percent value describing the relative moisture
content of a material and used in this study applied to wood species and
compensated for the temperature of the measured element
WRB Water Resistive Barrier (sometimes referred to as a weather resistive barrier)
XPS Extruded polystyrene rigid foam board insulation
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 1
Purpose
Recent changes in the minimum energy code (2012 IECC) significantly increased wall insulation levels
and reduced wall air leakage targets for light-frame wood walls, relative to the 2006 and 2009 IECC. The
long-term moisture performance of these new wall systems is not well understood with regard to vapor
drive, condensation risk, and drying capability. With moisture performance increasingly becoming a
design consideration in the selection of wall systems, home builders and designers need practical
guidance for construction of walls that ensure durability of residential buildings.
As part of a broad multi-year research program on the moisture performance of residential wall
systems, this project focuses on characterization of energy efficient walls in a sample of new, occupied
homes recently constructed around the country in moist or marine climate zones. The data also
provides the range of indoor relative humidity levels measured during the monitoring period. The wall
system designs and target house air infiltration rates were selected to meet or exceed minimum
performance levels outlined in the 2012 IECC, EPA ENERGY STAR V3.0 program, and the DOE Challenge
Home program.
The objectives of this ongoing research are to document seasonal wall cavity moisture characteristics,
wood structural panel sheathing moisture characteristics, and indoor relative humidity levels in
occupied homes. The study scope extends across various climate zones where the wall construction is
designed to substantially increase thermal performance and whole-house air sealing achieves much
lower infiltration rates.
Empirical field moisture data is necessary to evaluate the impact of added wall material layers installed
under realistic construction conditions and subject to occupant driven loads. This testing will help
provide sufficient details to isolate the variables or combination of variables that may result in
unsatisfactory moisture performance of common wall system designs used in high performance homes.
Likewise, the field data provides a unique perspective on the cyclic behavior of wall systems as it
pertains to variable moisture characteristics both inside and outside the thermal enclosure.
The purpose of this ongoing effort is to evaluate wall systems designed and installed by builders in the
field as part of their commercial enterprise. In some cases, deviations from the builder’s standard
practice in terms of material selection and wall layers were requested to provide a comparative
measurement of wall system designs in the same house environment. The wall system designs vary
across climate zones and are based on current best practices from construction experience and building
science knowledge from manufacturers and industry professionals.
Background
With the new code requirements for highly insulated wall systems, concerns were raised by builders
through the NAHB committees of potential moisture problems in walls when new materials are layered
in and outside of the wall cavity in these new wall designs. To better understand the moisture response
of the wall system, an effort to develop a base of wall cavity moisture characteristic field data was
-
August 2014 Home Innovation Research Labs 2 Wall Moisture Testing
embarked upon in 2010. Initial wall moisture measurement results were obtained for a select set of
homes with reported OSB buckling in the Midwestern states and Pennsylvania. The homes were located
in cold climates (Climate Zones 5 and 6) or at the boundary between the cold and mixed-humid climates
(Zone 4).
This original monitoring effort provided details on OSB expansion characteristics, the air-tightness of the
test homes, wall cavity moisture characteristics including the OSB moisture content, the temperature
and humidity in the cavity near the OSB panel, and the indoor temperature and humidity (NAHB
Research Center, 2012). All of the homes in that study were framed 2x4, except for one 2x6 framed
home, and used standard batt insulation with Kraft facing. The infiltration rate for all of the homes was
less than 4 ACH50 (ranging from 2.4 – 3.7 ACH50). The field test results indicated that some OSB panels
had expansion characteristics that could potentially exceed the standard recommended gap between
panels. For some monitored wall cavities, the OSB moisture content (MC) exceeded 20%, with one wall
cavity exceeding 25%. The wall systems monitored exhibited a cyclic response such that, as expected,
winter MC levels were higher than summer levels. Summer levels were typically below 12% MC and
winter levels ranged between 12% and 20% MC with some notable excursions to over 25%.
Analytical tools such as WUFI simulation software1 or simplified “dew point” calculations are used to
analyze the moisture characteristics of a framed wall system given assumed exterior and interior
environmental conditions. Simulation estimates have a range of capabilities depending on the software
and may include specific material characteristics, dimensional heat flows, effects of layered vs. parallel-
path material installation, effects of air leakage and solar effects on the exterior surfaces, and other
variables that can impact moisture and heat transfer. Calculations to estimate the potential for
condensation in the cavity near the sheathing provide a general framework for wall design that limits
moisture-related risk but do not generally predict the resulting moisture content of materials such as
the sheathing. Also, these calculations are dependent on the variable mix of indoor and outdoor
temperature and humidity conditions.
However, these analysis tools are the least cost approach to evaluating wall designs that are resistant to
problematic moisture conditions such as mold growth and material degradation. While software tools
and design methodologies are continually improved, there is a need for field data to complement and
validate the software analysis. The field data can provide the tangible material response to actual
environmental conditions. This relationship is important since it accounts for the variations of diurnal
occupant and environmental drivers, whereas many analysis tools rely on long term averages. Interior
relative humidity is one such driver that is difficult to predict since it is very specific to occupant
behavior.
The ongoing field monitoring effort described herein provides both the measured conditions in the
home and in the wall cavity near the exterior sheathing. The moisture characteristics are reported on a
daily average basis; however, higher resolution data is available should a specific measured result
require more detail. Field monitoring provides a snapshot of actual conditions encountered and thus can
1 WUFI is software for calculating the coupled heat and moisture transfer in building components.
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 3
help provide confidence in assumptions used in analytical tools. The obvious limitation to field
measurements is the relatively narrow band of information provided unless a large sample size is
available. This report provides a set of field data for high performance framed wall assemblies to identify
the range of wall cavity moisture conditions and provides an introduction to the cyclic nature of the
moisture characteristics in walls. The data can also be used to catalog wall systems that, under the
documented conditions, appear to function in a manner that would not be expected to lead to moisture
problems.
Research Methodology
The research methodology used for the field tests was developed in conjunction with NAHB members
including builders, manufacturers, building scientists, and others related to the building industry. The
methodology incorporates the following general outline:
Identify test homes in select climate zones based on a minimum set of design criteria (IECC
2012);
Collect relevant design, construction, and material data for each selected test home;
Locate and install wall cavity moisture sensors in select wall sections;
Compile relevant ‘as-built’ construction documentation and infiltration test results for each
selected home;
Compile and chart moisture-related data; and
Compile a matrix of climate-based wall assemblies and documented moisture characteristics.
This report summarizes the current data set available for test homes with a sufficient data record.
Ongoing monitoring will enable a wider selection of homes as well as multiple years of data to assess
repeatability of the results and identify any changes to the environmental conditions or the response of
the wall cavity moisture characteristics to changing environmental conditions.
Any relevant conclusions are drawn based on the analysis completed to date and are expected to
undergo updates as the monitoring effort continues.
Research Home Criteria and Selected Locations
Using a network of builder relationships throughout the U.S., a matrix of homes was developed that
included climate zone and wall system variables. Test homes were selected from all Moist climate zones
(CZ) except for CZ1, CZ7, CZ8 and from CZ4 Marine. Efforts were made to select multiple homes in one
climate zone with similar wall systems to provide more data for any given wall system.
The builder or the builder’s representative provided all documentation of the house construction
details, installation of sensors, and infiltration measurements.
Builders and homes were solicited based on a set of minimum requirements:
Insulation levels that meet or exceed prescriptive requirements of the 2012 IECC;
-
August 2014 Home Innovation Research Labs 4 Wall Moisture Testing
Infiltration target rate of 3 ACH50 (5 ACH50 in Climate Zone 2) per 2012 IECC; and
Whole-house ventilation using exhaust fans or a dedicated ventilation system.
A total of 22 homes were identified by the Home Innovation Research Labs for acceptance into the
study. All of the homes have been instrumented and are under test for the 2012-2013 heating season.
Figure 1 diagrams the location of the 22 test homes.
Figure 1. Map Showing Locations of Test Home Sites
A summary of the test house locations and other key relevant parameters is provided in Table 1. Blower
door tests were used to determine infiltration rates and were performed after completion of
construction.
3
1
2
1
1
1 3
1
3 2
2
1
4
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 5
Table 1. Summary of Test Sites
Test Site
State + ID
Climate Zone
Conditioned Floor Area, sf
Foundation Infiltration
ACH50 Ventilation
Monitoring Start Date
1 LA1 2A 1,896 crawlspace 4.4 Exhaust fans
3/30/2012
2 LA2 2A 1,896 crawlspace 4.3 Exhaust fans
3/30/2012
3 LA3 2A 1,896 crawlspace 2.0 Exhaust fans
3/30/2012
4 AL1 3A 1,094 slab on grade 1.3 Exhaust fans
2/17/2012
5 AL2 3A 1,094 slab on grade 2.2 Exhaust fans
2/17/2012
6 TX1 3A 2,115 slab on grade 1.8 HRV 6/30/2012
7 MD1 4A 4,407 basement 1.9 RA supply 5/24/2011
8 MD2 4A 4,648 basement 2.3 RA supply 12/8/2011
9 MD3 4A 4,371 basement 2.4 RA supply 11/10/2011
10 MD4 4A 4,486 basement 2.3 RA supply 11/9/2011
11 DE1 4A 4,893 basement 1.0 RA supply 1/26/2012
12 WA1 4C 3,199 slab on grade 3.1 Exhaust fans
11/1/2012
13 WA2 4C 2,735 slab on grade 3.4 Exhaust fans
10/3/2012
14 WA3 4C 2,815 slab on grade 2.2 HRV 4/25/2013
15 IA1 5A 5,293 basement
-
August 2014 Home Innovation Research Labs 6 Wall Moisture Testing
Table 2. Wall Configurations in Test Houses Test Site
Wall Ref.
State + ID
CZ Framing OSB WRB3 Ext. Insulating Sheathing
and Nominal R-value1 Cavity Insulation and Nominal R-
value2 Interior Vapor
Retarder/Barrier Exterior Cladding
1 A LA1
2A
2x4 Y Y N/A Fiberglass Batt (R13) Gypsum/paint Fiber Cement (FC)
2 B LA2 2x4 Y N 1/2" Foam (R3) Spray Cellulose (R15) Gypsum/paint Vinyl Siding (VS)
3 I LA3 2x6 Y Y N/A Spray Rockwool (R24) Gypsum/paint L.P. Smart Siding
2x6 Y Y Reflective WRB (E/W) Spray Rockwool (R24) Gypsum/paint L.P. Smart Siding
4 C AL1
3A
2x4 Y N 1" XPS Foam (R5) Fiberglass Batt (R13) Gypsum/paint Vinyl Siding
5 G AL2 2x4 Y Y N/A Closed Cell Foam (R18) Gypsum/paint Vinyl Siding
6 P TX1 2x6 Y Y N/A Open Cell Foam (R16) Gypsum/paint Brick Veneer
7 H
MD1
4A
2x6 Y Y N/A Blown Fiberglass (R23) Gypsum/paint Fiber Cement
U (2) 2x6 Y Y N/A Blown Fiberglass (R46) Gypsum/paint Fiber Cement
8 H MD2 2x6 Y Y N/A Blown Fiberglass (R23) Gypsum/paint Fiber Cement
9 H MD3 2x6 Y Y N/A Blown Fiberglass (R23) Gypsum/paint Fiber Cement
10 H MD4 2x6 Y Y N/A Blown Fiberglass (R23) Gypsum/paint Stone Front, FC
11 H DE1 2x6 Y Y N/A Blown Fiberglass (R23) Gypsum/paint Vinyl Siding
12 Q WA1
4C
Offset 2x4 Y Y N/A Blown Fiberglass (R24) Gypsum/paint FC, Shake Siding
13 Q WA2 Offset 2x4 Y Y N/A Blown Fiberglass (R24) Gypsum/paint FC, Shake Siding
14 Q
WA3 Offset 2x4 Y Y N/A Blown Fiberglass (R24) Gypsum/paint Fiber Cement
D 2x4 Y N 1" XPS Foam (R5) Blown Fiberglass (R15) Gypsum/paint Fiber Cement
15 X IA1
5A
2x6 Y Y N/A Blown Fiberglass (R23) 4 mil Polyethylene Stone Front, VS
16 X IA2 2x6 Y Y N/A Blown Fiberglass (R23) 4 mil Polyethylene Stone Front, VS
17 R
MI1 2x6 Y Y 1" XPS Foam (R5) ccSPF Flash, Blown Cellulose (R21) Gypsum/paint Fiber Cement
W 2x6 Y Y 1" XPS Foam (R5) Blown Cellulose (R21) Gypsum/paint Fiber Cement
18 R
MI2 2x6 Y Y 1" XPS Foam (R5) ccSPF Flash, Blown Cellulose (R21) Gypsum/paint Fiber Cement
W 2x6 Y Y 1" XPS Foam (R5) Blown Cellulose (R21) Gypsum/paint Fiber Cement
19 T
MI3 Offset 2x4 Y Y 1.5" XPS Foam (R7.5) Blown Cellulose (R21) Gypsum/paint Vinyl Siding
V Offset 2x4 Y Y 1.5" XPS Foam (R7.5) ccSPF Flash, Blown Cellulose (R21) Gypsum/paint Vinyl Siding
20 J
WI1
6A
2x6 Y N 1/2" Foil Faced Foam (R2.5) Blown Cellulose (R19) Vapor barrier paint Cedar Siding
K 2x6 N N 1" Foil Faced Foam (R5) Blown Cellulose (R19) Vapor barrier paint Cedar Siding
21
N
MI1
2x6 Y N 1" XPS Foam (R5) ccSPF Flash, Blown Fiberglass (R23) Gypsum/paint Vinyl Siding
O 2x6 N N 1" XPS Foam (R5) ccSPF Flash, Blown Fiberglass (R23) Gypsum/paint Vinyl Siding
L 2x6 Y N 1" XPS Foam (R5) Blown Fiberglass (R20) Gypsum/paint Vinyl Siding
M 2x6 N N 1" XPS Foam (R5) Blown Fiberglass (R20) Gypsum/paint Vinyl Siding
E 2x4 Y N 2" XPS Foam (R10) Blown Fiberglass (R13) Gypsum/paint Vinyl Siding
F 2x4 N N 2" XPS Foam (R10) Blown Fiberglass (R13) Gypsum/paint Vinyl Siding
22 S MI2 6A 2x6 Y N 2" XPS Foam (R10) Blown Fiberglass (R20) Gypsum/paint Vinyl Siding
ST – State; CZ – Climate Zone; N/A –not applicable/not installed 1The nominal R-value of the insulating sheathing. 2The nominal R-value of the cavity portion of the wall (excluding the insulating sheathing). 3The WRB represents spun-bonded polyolefin house wrap.
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 7
Table 3 organizes the different wall sections monitored in this study by construction type.
Table 3. Summary of Test Wall Configurations by Construction Type
Wall I.D.
No. Homes
Wall Configuration Climate Zones
Where Installed
A 1 2x4, OSB, R13 batt cavity 2A
B 1 2x4, 1/2" XPS, OSB, R15 spray cellulose 2A
C 1 2x4, 1" XPS, OSB, R13 fiberglass batt 3A
D 1 2x4, 1" XPS, OSB, R15 blown fiberglass 4C
E 1 2x4, 2" XPS, OSB, blown fiberglass 6A
F 1 2x4, 2" XPS, blown fiberglass 6A
G 1 2x4, OSB, CC foam cavity 3A
H 5 2x6, OSB, blown fiberglass 4A
I 1 2x6, Foil WRB, OSB, R24 blown rockwool 2A
J 1 2x6, 1/2" Foil Faced Foam, OSB, R19 blown cellulose 6A
K 1 2x6, 1" Foil Faced Foam, R19 blown cellulose 6A
L 1 2x6, 1" XPS, OSB, blown fiberglass 6A
M 1 2x6, 1" XPS, blown fiberglass 6A
N 1 2x6, 1" XPS, OSB, flash/blown fiberglass 6A
O 1 2x6, 1" XPS, flash/blown fiberglass 6A
P 1 2x6, OSB, OC foam 4"-5" of cavity 3A/B
Q 3 2x6 plates, 2x4 offset studs, OSB, R24 blown fiberglass 4C
R 2 2x6, 1" XPS, OSB, flash/blown cellulose 5A
S 1 2x6, 2" XPS, OSB, blown fiberglass 6A
T 1 2x6 plates, 1-1/2" XPS, OSB, 2x4 offset studs, blown cellulose 5A
U 1 (2) 2x6, OSB, blown fiberglass 4A
V 1 2x6 plates, 1-1/2" XPS, OSB, 2x4 offset studs, flash/blown cellulose 5A
W 2 2x6, 1" XPS, OSB, blown cellulose 5A
X 2 2x6, OSB, blown fiberglass, 4 mil poly 5A
Each Test House has specific wall sections in which sensors are located. Generally, multiple sensors are
placed in the north and east orientations with fewer sensors located in the west and south orientations
since previous experience has demonstrated that the north and east orientations generally show the
highest moisture content of sheathing (reduced or no direct solar radiation). Where the same homes
have differing wall configurations, additional sensors have been employed. Figure 2 shows an example
layout of sensor locations identified for the builder. Once the sensors are installed, the builder returns
this layout with ID labels from the individual sensor installed at that location. Figure 3 through Figure 5
show pictures of installed sensors.
In some wall cavities in the same test house, an effort was made to compare the moisture
characteristics of the sheathing with and without a layer of foam (ccSPF) flash in the cavity. In another
comparison, the wall cavity moisture characteristics are compared in homes with OSB sheathing and
without sheathing. Sensors installed in cavities without OSB sheathing are installed in the wood framing
near the foam sheathing (see Figure 6).
-
August 2014 Home Innovation Research Labs 8 Wall Moisture Testing
Figure 2. Example Sensor Layout for a Test House
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 9
Figure 3. Sensor Installed in OSB Sheathing That Will
be Foamed Over in This Test House
Figure 4. Sensor Installed in OSB Sheathing That Will
Not be Foamed Over in This Cavity
Figure 5. Sensor After Foam Flash and Before
Insulation
Figure 6. Sensor Installed in Lumber in Cavity With
Only Foam Sheathing
Builders of the test homes were asked to install the sensors in the identified locations prior to cavity
insulation and identify a sensor ID with each location. Sensors were also installed in the interior of the
home near the thermostat, in the main bathroom where wall cavity sensors were installed, in the
basement (if applicable), and on the exterior of the home and preferably on the north side of the house.
Monitoring System and Data Collection
Once the house was completed, the builder installed a receiver box containing the sensor receiver and a
transmitter. When activated, the receiver records data from each sensor on at least a 15-minute basis
and transmits the data to a website. As long as the receiver has power, data will be recorded by the
receiver regardless of the internet connection. During a power outage, the sensor data is not recorded.
The data collected from the sensors includes the temperature and relative humidity at the sensor body
and, via screw pin terminals, the moisture content (from the conductance of the wood). The moisture
content of the wood is temperature compensated based on the sensor temperature reading. The data
set available based on sensor measurements include temperature, relative humidity, wood moisture
-
August 2014 Home Innovation Research Labs 10 Wall Moisture Testing
content, dew point temperature, grains of moisture per pound of dry air, and the battery voltage of the
sensor. The system is described in greater detail in the following section.
Sensors were installed in test homes in wall sections identified by orientation. For multi-story above
grade homes, sensors were placed in both the first and second story wall sections. Interior sensors
provide temperature and relative humidity data in the main living space and are located as near the
thermostat as practical. A second interior sensor is located in the main bathroom and where wall cavity
sensors are located. For basement foundations, a third interior sensor is located in the basement area to
provide temperature and humidity data in the below grade portion of the home. An exterior sensor is
used to record the ambient temperature and relative humidity and is shielded using a white PVC cap.
Sensor data is transmitted at a minimum on a 15-minute basis. All data is uploaded continuously to a
website capable of data storage. The raw data is processed to calculate the dew point and grains of
moisture based on the temperature and relative humidity. The moisture content data is calibrated to a
standard wood moisture content based on the temperature at the wood surface.
The data set stored on the website is downloaded periodically and averaged on a daily basis for further
analysis and charting. Each sensor is associated with a wall room location and orientation and ultimately
with a wall and house configuration.
In-Service Environmental Conditions Monitoring
Wall cavity moisture characterization of higher efficiency wall systems is used as a means to support
wall system design methodologies by providing a field-based data set of wall systems under actual field
conditions in various climates. The field data differs from modeling exercises and laboratory testing as
neither the interior nor ambient conditions that drive the moisture cycles in the wall system are
controlled. In addition, the wall systems are constructed using typical methodologies and materials
found in the field and as specified by the builder. It is the intent of the project to monitor field walls
consistent with builder’s standard practice (i.e., Home Innovation Research Labs didn’t engage with the
builder’s design and construction processes). This was generally achieved in most of the locations except
for one location where the ventilation system was designed, specified, and inspected through support of
a trade association, and in instances where the builder used specific types of wall materials in order to
expand the range of wall systems for the field study.
Monitoring System
Small wireless sensors (Omnisense S-900-1 shown in Figure 7 and Figure 8) were installed in walls in all
analyzed homes to measure the following parameters:
Cavity Temperature (-40 to 185°F);
Cavity Relative Humidity (0 to 100%);
Cavity Dew Point Temperature; and
OSB Sheathing Moisture Content (7 to 40%).
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 11
The temperature (T) and relative humidity (RH) are measured by an internal sensor located inside the
plastic housing. The wood moisture content (MC) is determined using two screw pins driven into the
sheathing and is based on the measured resistivity of the OSB material. The sensors are prepared at
Home Innovation with a protective covering that inhibits moisture or other materials from entering the
sensor body through the battery compartment and the stand-off legs are removed so that the T and RH
sensor directly abuts the interior surface of the OSB. In this manner, the sensors have been successfully
fielded in locations where expanding foam covers the sensor body.
Figure 7. Omnisense S-900-1 Sensor
Figure 8. Screws used to Install Moisture Sensors
Sensor Calibration
The manufacturer stated accuracy for the sensor models used is +/- 2.0%RH and +/-0.3°C. The Home
Innovation Research Labs has performed numerous calibrations to verify both sensor accuracy and the
correlations with moisture content. Moisture content correlations have been performed comparing to
readings on handheld electrical conductance type moisture meters as well as comparing moisture
content readings with gravimetric measurement calculations. The wood moisture content values
reported through the sensor technology is the ratio of the water content of wood relative to the dry
weight as a percentage. The sensor manufacturer calibrates their devices based on wood species and
temperature compensation relationships outlined by the U.S. Department of Agriculture. For calibration
purposes, a set of sensors were installed in OSB samples and placed inside an environmental chamber
capable of controlling relative humidity and temperature. Figure 9 shows the set of sensors in the
environmental chamber where temperature and humidity were tightly controlled at various levels of
humidity for calibration purposes. At various levels of humidity and when equilibrium was achieved
(equilibrium moisture content, EMC) based on specimen weight consistency, the specimens were
removed weighed, oven dried and weighed once again. The resultant ratio of the measurements
provides the gravimetric moisture content of the specimen.
-
August 2014 Home Innovation Research Labs 12 Wall Moisture Testing
Figure 9. Sensors in the Environmental Chamber
for Calibration
Figure 10 plots the sensor moisture content reading, the oven dry moisture content and various
reference curves from literature and shows the calibration relationship between the sensor reading and
the measured OSB specimen moisture content. A curve for solid wood is also included as a reference. In
all cases, the reported sensor reading is higher than the gravimetric calculation by 1-3% MC. The NIST
reference curves align well with the gravimetric measurements. The OSB moisture content sensor
readings presented in this report have been adjusted based on calibration to the gravimetric
measurements as shown in Figure 10. Stud measurements are based on the sensor manufacturers’
calibration to solid lumber species and reported without adjustment.
Figure 10. OSB Moisture Content Sensor Calibration Curves
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 13
Wall Cavity and Environmental Conditions Measurement Results
The available recorded measurements for each home are presented individually to demonstrate the
differences in wall orientation and where available, to compare various wall configurations. Indoor and
ambient environmental conditions are also presented to provide a context for the wall cavity moisture
characteristics.
Reference Moisture Content for Oriented Strand Board (OSB)
The fiber saturation point refers to the moisture content where the wood fibers cannot absorb more
water within the cellular structure. Though equilibrium moisture content varies for different wood
species, generally 30% moisture content is considered the maximum fiber saturation point MC for solid
wood (Wood Handbook, FPL). For OSB the equilibrium moisture content is three to five percentage
points below that of solid wood products (Carll and Wiedenhoeft). An OSB fiber saturation point of 26%
is used in this report.
OSB Sheathing Moisture Content Results by Test Site
A primary performance factor of interest in evaluating the moisture characteristics of wall systems is the
peak level and seasonal cyclic behavior of the moisture content (MC) in the sheathing material. This is of
particular interest because the wood sheathing provides structural support for the framing (and often
the siding) and sustained high levels of moisture in the sheathing may compromise the long-term
structural performance. Similarly, high levels of moisture at the sheathing, under certain conditions of
temperature, can lead to mold growth on organic surfaces. Using the available data for each site, charts
of the average sheathing (or where no sheathing is used, stud) moisture content are shown. The OSB
moisture content sensor readings have been calibrated based on the sensor calibration discussion
above. All Figures in this section are daily average MC readings over at least one winter period for walls
in an individual test house in the specific location. For reference, wood fiber saturation level estimates
for OSB panels (estimated at 26 percent MC) are shown on charts. Where multiple homes are located in
the same climate zone, a numeric designation is used to identify the home. Summary analyses for each
climate zone are provided following either a specific test home or a set of test homes.
Climate Zone 6 Summary results are shown in Figure 11 for a test home in Michigan, Climate Zone 6A. The following
observations can be made:
North and east walls have generally higher MC than west or south;
Use of a closed cell spray polyurethane foam (ccSPF) flash coat over the interior OSB lowers the
MC of the OSB in the first winter after construction, and helps to maintains lower MC in
subsequent years;
Use of a ccSPF flash coat over the interior OSB appears to inhibit the OSB drying in the summer
months compared to OSB without a flash coat;
The bathroom shower wall cavity MC (orange curve) increases to a higher level in late winter
and does not dry to as low a level compared with other wall sections;
-
August 2014 Home Innovation Research Labs 14 Wall Moisture Testing
The uninsulated exposed cavity in an unheated garage (yellow curve) follows a similar pattern as
other sensors located in wall cavities adjacent to conditioned space; and
Use of exterior foam greater than 1 inch in thickness, generally results in lower OSB moisture
content readings than wall systems with less or no exterior foam.
Figure 11. CZ 6A, MI (1), MC Readings for 2 Winter Periods
Summary results for a second test home in Michigan, Climate Zone 6A, are shown in Figure 12. This data
is from the first winter following construction. The indoor relative humidity is relatively high compared
with other homes tested in the climate zone. Since this is the first winter following construction, it is less
representative of long term performance. The moisture content levels are expected to drop through the
cooling season, and due to the exterior insulation are not expected to rise to these initial levels in
subsequent winter heating periods.
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 6A - Michigan - Site 21 - Wall Cavity Moisture ContentE-LvRm1E-LvRm2E-MbathN-DnRm, exp (L)N-GarageN-Mbath, stud (O)N-MBath, stud, exp (M)N-MbedN-Mbed, exp (L)S-1Fl-Bed2S-2Fl-2x4+2, exp (E)S-2Fl-2x4+2, stud, exp (F)S-2Fl-StairW-MbathOSB Fiber SaturationWood Fiber Saturation
Average 2011-2012 winter indoor RH, 34%Average 2012-2013 winter indoor RH, 32%
Note: Wall Type N - 1" XPS, OSB, 2x6, ccSPF flash, blown fiberglass, gypsum/paintWall Type O- 1" XPS, 2x6, ccSPF flash, blown fiberglass, gypsum/paintWall Type L - 1" XPS, OSB, 2x6, blown fiberglass, gypsum/paintWall Type M - 1" XPS, 2x6, blown fiberglass, gypsum/paintWall Type E - 2" XPS, OSB, 2x4, blown fiberglass, gypsum/paintWall Type F - 2" XPS, 2x4, blown fiberglass, gypsum/paint
Average 2011-2012 winter indoor RH, 34%Average 2012-2013 winter indoor RH, 32%
Note: Wall Type N - 1" XPS, OSB, 2x6, ccSPF flash, blown fiberglass, gypsum/paintWall Type O- 1" XPS, 2x6, ccSPF flash, blown fiberglass, gypsum/paintWall Type L - 1" XPS, OSB, 2x6, blown fiberglass, gypsum/paintWall Type M - 1" XPS, 2x6, blown fiberglass, gypsum/paintWall Type E - 2" XPS, OSB, 2x4, blown fiberglass, gypsum/paintWall Type F - 2" XPS, 2x4, blown fiberglass, gypsum/paint
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 15
Figure 12. CZ 6A, MI (2), MC Readings for the First Winter Period
Summary results are shown in Figure 13 for a test home in Wisconsin, Climate Zone 6A. Unfortunately,
at this test site, most of the sensors appeared to have suffered damage as they ceased reading following
the installation of the insulation, likely due to the use of wet blown cellulose insulation. All sensors had
initial high MC readings, even in solid wood members, and the three remaining wall cavity sensors do
appear to trend downward into the summer months. However, this limited data set does not provide a
high degree of confidence in generalizing the results.
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 6A - Michigan - Site 22 - Wall Cavity Moisture Content
N-Kit/GarN-2Fl-Bed1N-2Fl-BathE-LvRm1E-LvRm2E-2Fl-Bed4E-2Fl-Bed1S-StairS-2Fl-Bed3W-LaunW-2Fl-Bed2W-2Fl-Bed3OSB Fiber SaturationWood Fiber Saturation
Note: Wall Type S - 2" Foam, OSB, 2x6 framing, ccSPF flash, R23 spider insulation, gypsum/paint Average 2012-2013 winter indoor RH, 46%
-
August 2014 Home Innovation Research Labs 16 Wall Moisture Testing
Figure 13. CZ 6A, WI, MC Readings for a 14-Month Period
Climate Zone 5 Summary results are shown in Figure 14 and Figure 15 for two test homes in Michigan, Climate Zone 5A.
The following observations can be made:
In the 2x6 walls without ccSPF, the OSB MC shows a slow upward trend to about 20%;
In the same 2x6 walls without the ccSPF, the MC levels exceed 26% but remain fairly flat;
These results suggest that one inch of exterior foam is insufficient for controlling OSB sheathing
moisture in walls without an adequate vapor retarder; and
Generally, higher MC levels are seen in the north and east walls, consistent with other test
home data.
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 6A - Wisconsin - Site 20 - Wall Cavity Moisture Content
E-KitE-Kit2, 1", studN-Laun, 1", studN-Mbath, 1", studN-MbedS-KitW-2Fl-StorW-LvRmW-Mbed, 1", studOSB Fiber SaturationWood Fiber Saturation
Note: Wall J (solid/OSB) - 1/2" Plfoil, OSB, 2x6, R23 blown cellulose, gypsum/vapor barrier paint Wall K (dash/stud) - 1" Plfoil, 2x6, R23 blown cellulose, gypsum/vapor barrier paint
Average 2011-2012 winter indoor RH, 44%Average 2012-2013 winter indoor RH, 43%
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 17
Figure 14. CZ 5A, MI (1), MC Readings for a 3-Month Period
Figure 15. CZ 5A, MI (2), MC Readings for a 3-Month Period
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 5A - Michigan - Site 17 - Wall Cavity Moisture Content
N-Kit 1N-Kit 2N-stairN-Mbath, no spfN-MbathE-DnRm, no spf 1E-DnRm 1E-DnRm 2E-DnRm, no spf 2E-2Fl-BedS-MbedS-LvRmW-MbedW-2Fl-bedOSB Fiber SaturationWood Fiber Saturation
Note: Wall Type R (solid line) - 1" Ext Foam, WRB, OSB, 2x6, 1" ccSPF flash, R23 blown cellulose, gypsum/paintWall Type W (dash line) - 1" Ext Foam, WRB, OSB, 2x6, R23 blown cellulose, gypsum/paint
Average 2012-2013 winter indoor RH, 38%
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 5A - Michigan - Site 18 - Wall Cavity Moisture Content
N-Kit 1N-Kit 2N-stairN-Mbath, no spfN-MbathE-DnRm, no spf 1E-DnRm 1E-DnRm, no spf 2E-DnRm 2E-2Fl-BedS-MbedS-LvRmW-MbedW-2Fl-bedOSB Fiber SaturationWood Fiber Saturation
Note: Wall Type R (solid line) - 1" Ext Foam, WRB, OSB, 2x6, 1" ccSPF flash, R23 blown cellulose, gypsum/paintWall Type W (dash line) - 1" Ext Foam, WRB, OSB, 2x6, R23 blown cellulose, gypsum/paint
Average 2012-2013 winter indoor RH, 32%
-
August 2014 Home Innovation Research Labs 18 Wall Moisture Testing
Summary results are shown in Figure 16 for a test home in Michigan, Climate Zone 5A. The following observations can be made:
The MC for all sections with ccSPF flash remain below 20% and are slightly lower than the 2x6
walls shown in Figures 14 and 15 above;
The MC for wall sections without ccSPF show similar results to the 2x6 walls shown in Figures 14
and 15 with MC exceeding 26% MC (the coat of ccSPF flash reduces the vapor transfer to the
sheathing and keeps the cavity warmer); and,
Measurements in framing are consistently lower than MC in the OSB sheathing.
Figure 16. CZ 5A, MI (3), MC Readings for a 3-Month Period
Summary results are shown in Figures 17 and 18 for two test homes in Iowa, Climate Zone 5A. The
following observations can be made:
As a result of using poly as an interior vapor retarder, the MC of the 2x6 walls without ccSPF is
generally lower than the CZ5 Michigan wall measurements;
The MC in this first winter after construction are generally flat for all sensors – another indicator
of the effectiveness of poly as a vapor retarder; and
The home with the higher interior average relative humidity demonstrates clearly higher MC
levels than the home with a low interior RH. This effect is likely attributed to air leakage around
the poly.
Figure 19 compares the exterior conditions for the Climate Zone 5 sites in Michigan and Iowa.
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 5A - Michigan - Site 19 - Wall Cavity Moisture Content
N-DnRm, osb, no spf N-DnRm, studN-DnRm N-MbedN-2Fl-Bed2 E-LvRmE-DnRm, osb, no spf E-DnRm, studE-DnRm E-2Fl-Bed4S-Mbath S-LvRmS-2Fl Bed4 W-MbedW-2Fl Bed2 OSB Fiber SaturationWood Fiber Saturation
Note: Wall Type T - 1-1/2" Foam, 2x6 plates, 2x4 offset framing,1" ccSPF, R23 blown cellulose, gypsum/paintWall Type V - 1-1/2" Foam, 2x6 plates, 2x4 offset framing,1" ccSPF, R23 blown cellulose, gypsum/paintSpecial Note: 16"x24" OSB plates for testing
Average 2012-2013 winter indoor RH, 38%
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 19
Figure 17. CZ 5A, IA (1), MC Readings for a 4-Month Period
Figure 18. CZ 5A, IA (2), MC Readings for a 4-Month Period
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 5A - Iowa - Site 15 - Wall Cavity Moisture Content
N-Mbed1N-Mbed2N-MbathE-FamRmE-MbedE-LaunS-BathS-Bed2W-Bed2OSB Fiber SaturationWood Fiber Saturation
Note: Wall Type X - OSB, 2x6, R23 blown fiberglass, interior v.b., gypsum/paint
Average 2012-2013 winter indoor RH, 28%
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 5A - Iowa - Site 16 - Wall Cavity Moisture Content
N-BsmtBedN-BsmtRec1N-BsmtRec2N-FamRmN-KitN-MbedE-BsmtBathE-MbathE-MbedS-BathS-Bed2W-KitW-LaunOSB Fiber SaturationWood Fiber Saturation
Note: Wall Type X - OSB, 2x6, R23 blown fiberglass, interior v.b., gypsum/paint Average 2012-2013 winter indoor RH, 40%
-
August 2014 Home Innovation Research Labs 20 Wall Moisture Testing
Figure 19. Climate Zone 5 Test House Precipitation and Temperature Comparison
Climate Zone 4C Summary results are shown in Figures 20 and 21 for two of three test homes in Washington, Climate
Zone 4C. Data are somewhat limited, but the following observations can be made:
The sheathing MC show increasing levels in the winter; and
MC levels trend over 20% when the interior relative humidity is higher.
Note: Specific sensor locations are not shown for these two sites. The locations are unknown as a result of
builder’s staffing changes.
0
10
20
30
40
50
60
0
2
4
6
8
10
12
Exte
rio
r Te
mp
era
ture
, °F
Dai
ly P
reci
pit
aio
n, R
un
nin
g To
tal,
Inch
es
Precipitation Comparison for Mi and IA Test Houses
Grand Rapids, MI Precipitation, In
Iowa City, IA Precipitation, In
Grand Rapids, Temperature
Iowa City, Temperature
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 21
Figure 20. CZ 4C, WA (1), MC Readings for a 5-Month Period
Figure 21. CZ 4C, WA (2), MC Readings for a 6-Month Period
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 4C - Washington - Site 12 - Wall Cavity Moisture Content
sensor 9sensor 1sensor 2sensor 3sensor 4sensor 5sensor 6sensor 7sensor 8OSB Fiber SaturationWood Fiber Saturation
Note: Wall Q - WRB, OSB, 2x6 plates,2x4 offset studs, R24, gypsum/paint
Average 2012-2013 winter indoor RH, 43%
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 4C - Washington - Site 13 - Wall Cavity Moisture ContentSensor7Sensor8Sensor4Sensor5Sensor6Sensor1Sensor2Sensor3Sensor9Sensor10Sensor11Sensor12OSB Fiber SaturationWood Fiber Saturation
Note: Wall Q - WRB, OSB, 2x6 plates,2x4 offset studs, R24, gypsum/paint
Average 2011-2012 winter indoor RH, 34%Average 2012-2013 winter indoor RH, 32%
-
August 2014 Home Innovation Research Labs 22 Wall Moisture Testing
Climate Zone 4A
Summary results are shown in (Figure 22) for a test home in Maryland, Climate Zone 4A. Over two full heating seasons, the following observations can be made:
OSB sheathing on the northeast and northwest directions has generally higher MC than other
orientations (consistent with other test sites);
Moisture contents in the standard wall construction (R23) for the test house range from 7% to
18% at the same point during the winter period;
The much higher wall insulation (~R46 compared with ~R23) results in an increase of about 2%
MC over the highest standard wall MC in the winter season and a MC in summer that is slightly
higher, but in line with, than the standard wall sections;
All wall sections dry to less than 10% MC in summer season; and
The home was unoccupied during the first heating period but is used as an active model by the
builder with a humidifier operating; the home was occupied during most of the second winter
period.
Figure 22. CZ 4A, MD-1, MC Readings for a 2-Year Period
Summary results are shown in Figure 23, Figure 24, and Figure 25 for three test homes in Maryland, Climate Zone 4A (MD-2, MD-3, MD-4). The following observations can be made:
OSB sheathing MC for most wall sections are less than 17% the first winter following
construction (not all homes are occupied, use of installed humidifier may be employed);
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 4A - Maryland - Site 7 - Wall Cavity Moisture ContentNE-1Fl-GrRm1 NE-1Fl-GrRm2NW-1Fl-Hall-R46 NW-1Fl-BathNW-1Fl-GrRm SE-1Fl-Kit1SE-1Fl-Kit2 SE-1Fl-Kit3SE-1Fl-DR SW-1Fl-DRNE-2Fl-Mbed NE-2Fl-MbathNW-2Fl-Hall NW-2Fl-MbedSE-2Fl-Bed3 SE-2Fl-BathSW-2Fl-Bed2 SW-2Fl-HallNW-3Fl-Bed4 SE-3Fl-LoftNW-Bsmt SE-BsmtOSB Fiber Saturation Wood Fiber Saturation
Note: Wall Type H - WRB, OSB, 2x6, R23 blown fiberglass, gypsum/paintWall Type U - WRB, OSB, (2) 2x6, R46 blownfiberglass, gypsum/paint
Average 2011-2012 winter indoor RH, 44%Average 2012-2013 winter indoor RH, 41%
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 23
Sites MD-2 and MD-4 each have an outlier trending 5% or more above the rest of the sensors for
an extended period of time. The reason for these outliers is unknown. It can be stipulated that
there is an air leak present in the vicinity of these sensors;
All OSB moisture contents decrease to less than 10% MC;
The homes were unoccupied for the first winter and occupied for the second winter period; all
homes have a humidifier installed and operating (the specific control of the humidifier is
unknown in MD-2, MD-3, MD-4); and
MD-3 shows the most remarkable change in the sheathing MC during the second heating season
when occupied, even though the measured interior humidity was the same for both seasons.
A comparison of the weather (see Figure 26) for each winter heating period (2011-2012, 2012-2013)
shows some variation but only about a 15% difference in total rainfall.
Figure 23. CZ 4A, MD-2, MC Readings for an 18-Month Period
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 4A - Maryland - Site 8 - Wall Cavity Moisture ContentNE-1Fl-GrRm1NE-1Fl-KitNW-1Fl-GrRmSE-1Fl-DnRmSE-1Fl-KitSW-1Fl-DenNE-2Fl-MbathNE-2Fl-MbedNW-2Fl-MbedSE-2Fl-Bed2SE-2Fl-MbathSW-2Fl-Bed3OSB Fiber SaturationWood Fiber Saturation
Note: Wall Type H - WRB, OSB, 2x6, R23 blown fiberglass, gypsum/paint
Average 2011-2012 winter indoor RH, 35%Average 2012-2013 winter indoor RH, 38%
-
August 2014 Home Innovation Research Labs 24 Wall Moisture Testing
Figure 24. CZ 4A, MD-3, MC Readings for a 19-Month Period
Figure 25. CZ 4A, MD-4, MC Readings for an 18-Month Period
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 4A - Maryland - Site 9 - Wall Cavity Moisture Content
NE-1Fl-GrRm1NE-1Fl-GrRm2NW-1Fl-GrRmSE-1Fl-DenSE-1Fl-KitSW-1Fl-DenNE-2Fl-MbathNE-2Fl-MbedNW-2Fl-MbedSE-2Fl-Bed2SE-2Fl-LaunSW-2Fl-Bed3SE-3Fl-LoftOSB Fiber SaturationWood Fiber Saturation
Note: Wall Type H - WRB, OSB, 2x6, R23 blown fiberglass, gypsum/paint
Average 2011-2012 winter indoor RH, 47%Average 2012-2013 winter indoor RH, 48%
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 4A - Maryland - Site 10 - Wall Cavity Moisture Content
NE-1Fl-GrRm1
NE-1Fl-GrRm2
NW-1Fl-Kit1
NW-1Fl-Kit2
SE-1Fl-Bath
SW-1Fl-DnRm
NE-2Fl-Mbed
NW-2Fl-Bath
NW-2Fl-bed3
NW-2Fl-Mbath
SE-2Fl-Mbed
SW-2Fl-Bed2
SE-3Fl-Loft
OSB Fiber Saturation
Wood Fiber Saturation
Note: Wall Type H - WRB, OSB, 2x6, R23 blown fiberglass, gypsum/paint
Average 2011-2012 winter indoor RH, 32%Average 2012-2013 winter indoor RH, 34%
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 25
Figure 26. Climate Zone 4 MD Test House Precipitation and Temperature Comparison
Summary results for a test home in Delaware, Climate Zone 4A, are shown in Figure 27. The following observations can be made:
Maximum MC levels of 15% immediately following construction and similar for the second
season except for one measurement in a bathroom wall that was about 3% higher;
All OSB moisture contents had summertime minimums of less than 10% MC; and
One wall cavity (exterior facing garage wall in unconditioned garage) shows an increasing OSB
sheathing MC progressing through the summer months where all other sensors in conditioned
space remain somewhat constant.
0
10
20
30
40
50
60
70
80
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Exte
rtio
r Te
mp
era
ture
, °F
Pre
cip
itat
ion
, Ru
nn
ing
Tota
l fo
r P
eri
od
, in
che
s
Precipitation and Temperature Comparison - 2 Heating Seasons in CZ4
2011-2012 Precipitation 2012-2013 Precipitation
2011-2012 Temperature 2012-2013 Temperature
-
August 2014 Home Innovation Research Labs 26 Wall Moisture Testing
Figure 27. CZ 4A, DE, MC Readings for a 14-Month Period
Climate Zone 3 Summary results for two test homes in Alabama, Climate Zone 3, are shown in Figure 28 and Figure 29. The following observations can be made:
Low MC measurements were recorded for all wall and roof sections (roofs are insulated with
SPF at the deck);
AL-2 test house has slightly higher MC readings in the house with higher indoor average
humidity. Because walls in AL-2 house were insulated with ccSPF, it is assumed that the drying is
slowed in this house compared with the house with 1 inch of exterior foam sheathing; and
MC readings are generally flat for the entire winter period.
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 4A - Delaware - Site 11 - Wall Cavity Moisture Content
NE-Kit1NE-Kit2NE-MbedNW-MbathNW-MbathNW-GarSE-Bed3SE-FmRmSW-Bed2aSW-Bed2bBsmtFlDeckroof deckOSB Fiber SaturationWood Fiber Saturation
Note: Wall Type H - WRB, OSB, 2x6, R23 blown fiberglass, gypsum/paint
Average 2011-2012 winter indoor RH, 40%Average 2012-2013 winter indoor RH, 37%
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 27
Figure 28. CZ 3A, AL-1, MC Readings for a 6-Month Period
Figure 29. CZ 3A, AL-2, MC Readings for a 6-Month Period
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 3A - Alabama - Site 4 - Wall Cavity Moisture Content
N-Bed3N-LvRmE-Roof1E-Roof2E-LvRmE-DnRmS-Bed1W-Roof1W-Roof2W-Roof-TrussW-Bed1W-MbathW-Bed2OSB Fiber SaturationWood Fiber Saturation
Note: Wall Type C - 1" XPS, OSB, 2x4, R13 Fiberglass Batts, gypsum/paint unless noted
Average 2012-2013 winter indoor RH, 44%
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -
%
Average Daily Data
CZ 3A - Alabama - Site 5 - Wall Cavity Moisture Content
N-Bed3N-LvRmE-Roof1E-Roof2E-LvRmE-DnRmS-Bed1W-Roof1W-Roof2W-Roof-TrussW-Bed1W-MbathW-Bed2IntTstatInt-MbathOutdoorOSB Fiber SaturationWood Fiber Saturation
Note: Wall Type G - OSB, 2x4, R18 ccSPF, gypsum/paint unless noted
Average 2012-2013 winter indoor RH, 50%
-
August 2014 Home Innovation Research Labs 28 Wall Moisture Testing
Summary results for a test home in Texas, Climate Zone 3, are shown in Figure 30. The following observations can be made:
Moisture contents for all wall and roof sheathing remain below 10% (this test house location is
in a relatively drier area of the state); and
Interior relative humidity is on the lower range of the test homes.
Figure 30. CZ 3A, TX, MC Readings for a 3.5-Month Period
Climate Zone 2 Summary results for three test homes in Louisiana, Climate Zone 2, are shown in Figure 31, Figure 32, and Figure 33. The following observations can be made:
Moisture contents for wall sections in all three homes are similar despite the significant
difference in wall configuration;
LA-2 home with exterior insulating sheathing shows the lowest sheathing MC of all test houses
in this set but has the lowest interior RH as well; and
All of these test homes show relatively little change over the heating season, although a
significant portion of the data is missing due to equipment problems.
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 3A - Texas - Site 6 - Wall Cavity Moisture Content
N-bath, studN-Kit, studN-Bed1N-MbathN-Bed1, studE-Bed1-1E-Bed1-2E-Bed2S-MbedS-LvRmW-Mbed1W-MbathW-Mbed2W-Mbed, studN-Roof1N-Roof2S-Roof1S-Roof2S-Roof3Attic1Attic2OSB Fiber SaturationWood Fiber Saturation
Note: Waal Type P - WRB, OSB, 2x6, R16 Open Cell Cavity Foam, gypsum/paint Roof sensors located in the underside of the roof sheathing buried in SPFAttic sensors located in truss framing of unvented attic space
Average 2012-2013 winter indoor RH, 29%
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 29
Figure 31. CZ 2A, LA-1, MC Readings for a 4.5-Month Period
Figure 32. CZ 2A, LA-2, MC Readings for a 4.5-Month Period
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 2A - Louisiana - Site 1 - Wall Cavity Moisture ContentE-MbathE-Mbed, studE-MbedN-Bed2, studN-Bed2N-Bed3, studN-Bed3S-Mbed, studS-MbedW-KitW-Util, studW-UtilOSB Fiber SaturationWood Fiber Saturation
Note: Wall Type A - WRB, OSB, 2x4, R13 Fiberglass Batts, gypsum/paint
Average 2012-2013 winter indoor RH, 56%
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 2A - Louisiana - Site 2 - Wall Cavity Moisture Content
E-MbathE-Mbed, studE-MbedN-Bed2, studN-Bed2N-Bed3, studN-Bed3S-Mbed, studS-MbedW-KitW-Util, studW-UtilOSB Fiber SaturationWood Fiber Saturation
Note: Wall Type B - 1/2" Foam, OSB, 2x4, R15 Spray Cellulose, gypsum/paint
Average 2012-2013 winter indoor RH, 53%
-
August 2014 Home Innovation Research Labs 30 Wall Moisture Testing
Figure 33. CZ 2A, LA-3, MC Readings for a 4.5-Month Period
Seasonal Average Data Summaries and Analysis
The average seasonal moisture content for the different wall sections are plotted for each climate zone.
The seasonal moisture contents are based on the daily average moisture content measurements for all
available wall sections and across either one or two heating seasons. This summarized data allows for a
quick overview of the performance of the wall systems by climate zone. Only data from the northerly
facing walls are used because this orientation generally shows the highest, sustained moisture levels in
the home and all other wall orientations would be equal or less in seasonal average levels. Where a
single winter season data bar is shown, this indicates the first winter season following construction.
Climate Zone 6
Climate zone 6 has the widest array of wall systems in the study as shown in Figure 34. Some of the wall
sections have wood sheathing and others are sheathed with rigid foam board. In the cases of foam
sheathing, the moisture content is read at the framing exterior edge. The seasonal data for wall sections
is associated with interior relative humidity levels reported in Table 4.
5
10
15
20
25
30
Mo
istu
re C
on
ten
t -%
Average Daily Data
CZ 2A - Louisiana - Site 3 - Wall Cavity Moisture Content
E-MbathE-Mbed, studE-MbedN-Bed2, studN-Bed2N-Bed3, studN-Bed3S-Mbed, studS-MbedCrawl FloorW-DnRmW-Util, studW-UtilOSB Fiber SaturationWood Fiber Saturation
Note: Wall Type I - WRB, OSB, 2x6, R24 Spray Rockwool, gypsum/paintEast West - Reflective Wrb, OSB, 2x6, R24 Spray Rockwool, gypsum/paint
Average 2012-2013 winter indoor RH, 63%
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 31
Figure 34. Climate Zone 6 Summary MC Data
Table 4. Winter Average Seasonal Interior House Relative Humidity for CZ 6 Test Walls
Wall Type I.D. Interior RH
E, L, N, F, M, O 2011-2012 – 32%; 2012-2013 – 33% S 2012-2013 – 46% K 2011-2012 – 46%; 2012-2013 – 43%
Based on the seasonal moisture content of sheathing, the following summary conclusions are identified
for walls with exterior foam:
All wall configurations demonstrate capacity for drying during non-heating seasons. In walls
without spray foam, it is suggested that the drying occurs to the inside. In walls with spray foam,
the drying rate is reduced; however, moisture fluctuations are also less pronounced with lower
winter peaks.
Summer periods show a drying in the wall cavity to an average of no more than 15% MC for all
walls regardless of the winter peak MC in any wall section.
OSB sheathing on 2x6 wall framing with 1 inch of exterior foam and without an interior vapor
retarder is consistently reaching average moisture contents of over 20% during winter months
suggesting that this wall configuration may not be appropriate for colder climate zones. It is
0
5
10
15
20
25
30
Ave
rage
Se
aso
nal
Mo
istu
re C
on
ten
t, %
Climate Zone 6A - Moisture Content -North Wall (unless noted otherwise)
Seasonal Maximum
Winter Season 2011-12
Summer Season 2012
Winter Season 2012-13
1"XPS2X6
Damp Bl. FG(L-MI1)
2"XPS2X4
Damp Bl. FG(South)(E-MI1)
1"XPS2X6
1"ccSPFDamp Bl. FG
(N-MI-1)
2"XPS2X6
Damp Bl. FG(S-MI2)
2"XPS2X4
Damp Bl. FG(South)(F-MI1)
1"FF Foam2x6
Wet Bl. Cell.(K-WI1)
1"XPS2X6
Damp Bl. FG(M-MI1)
1"XPS,2X6,
1"ccSPF,Damp Bl. FG
(O-MI-1)
Exterior OSB Sheathing
Winter - 12/15 - 3/15Summer - 6/15 - 9/15
---------------------------------------------------------------------------------------------------
No Exterior OSB Sheathing (sensor in stud)
-
August 2014 Home Innovation Research Labs 32 Wall Moisture Testing
recommended to investigate the effect of a class-2 (e.g., Kraft faced batt) or variable (“smart”)
vapor retarder to control interior vapor drive in the winter without overly restricting drying
potential to the inside.
A combination of 1 inch of exterior foam and an interior flash coat of closed spray foam is
effective at controlling OSB moisture uptake from the interior vapor drive. However, this system
would be susceptible to retaining moisture that penetrated the drainage plane as a result of the
reduced drying rates.
OSB sheathing in 2x6 walls with 2 inches of exterior foam without an interior vapor retarder
showed high moisture content in the first winter following construction. Further monitoring
results are needed to understand the summer drying and the interior vapor drive effect in the
second winter without the effect of high construction moisture loads.
South-facing 2x4 walls with 2 inches of exterior foam without interior vapor retarder
consistently show low moisture content levels in OSB and framing. It is suggested that the solar
vapor drive was effective at drying any construction moisture to the inside. Further study is
needed to expand testing to include north facing exposure. Also, because builders may have a
preference to use fiberglass batts with Kraft facing, monitoring of such walls to understand the
impact on interior drying is needed.
Because observed framing moisture content is always lower than OSB and because equilibrium
moisture content of framing is always higher than OSB, the OSB is a more critical wall
component than framing when evaluating moisture characteristics and effects.
Climate Zone 5
Climate zone 5 also has a wide array of wall systems in the study as shown in Figure 35. All of the wall
sections have wood sheathing on the exterior of the cavity and others are sheathed with rigid foam
board. In the cases of foam sheathing, the moisture content is read at the framing exterior edge. The
seasonal data for wall sections is associated with interior relative humidity levels as shown in Table 5.
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 33
Figure 35. Climate Zone 5 Summary MC Data
Table 5. Winter Average Seasonal Interior House Relative Humidity for CZ 5 Test Walls
Wall Type I.D. Interior RH
X (IA1) 2012-2013 – 28% X (IA2) 2012-2013 – 40% R, W 2012-2013 – 35% V, T 2012-2013 – 38%
Based on the seasonal moisture content of sheathing and the interior humidity, the following summary
conclusions are identified:
Given that no summer data has yet been analyzed, the summer drying potential for all wall
configurations is needed. As with climate zone 6, drying is expected to below 15% MC. In walls
without spray foam, drying is expected to occur to the inside. In walls with spray foam, the
drying rate is expected to be reduced.
In the first winter after construction, OSB sheathing on 2x6 wall framing with either 1 inch or
1.5 inches of exterior foam and without an interior vapor retarder reached average moisture
contents of over 30%. Summer data and second winter data are needed to uncouple the impact
of construction moisture absorbed from wet-blown cellulose from the effects of seasonal vapor
0
5
10
15
20
25
30
Ave
rage
Se
aso
nal
Mo
istu
re C
on
ten
t, %
Climate Zone 5A - Moisture Content -North Wall
Seasonal Maximum
Winter Season 2012-13
2X6Dry Blown FG w/
4 mil poly v.b.(X-IA2)
2X6Dry Blown FG w/
4 mil poly v.b.(X-IA1)
1"XPS Foam2X6
1" cc SPFWet Bl. Cell.(R-MI1&2)
Winter = 12/15 - 3/15
1.5"XPS Foam2X6 Plates2x4 offset1" cc SPF
Wet Bl. Cell.(V-MI3)
1"XPS Foam2X6
Wet Bl. Cell.(W-MI1&2)
1.5"XPS Foam2X6 Platesoffset 2x4
Wet Bl. Cell.(T-MI3)
Winter = 12/15 - 3/15
-
August 2014 Home Innovation Research Labs 34 Wall Moisture Testing
drive. Following the next winter data, it may be appropriate to investigate the effect of a class-2
(e.g., Kraft faced batt) or variable (“smart”) vapor retarder to control interior vapor drive in the
winter without overly restricting drying potential to the inside.
A combination of 1 inch of exterior foam and an interior flash coat of closed spray foam is
effective at blocking moisture from wet-blown cellulose and controlling OSB moisture uptake
from the interior vapor drive. However, subsequent drying data is needed to determine if this
system would be susceptible to retaining moisture that penetrated the drainage plane as a
result of the reduced drying rates.
2x6 construction with Class I vapor retarder (poly) showed low moisture content over the first
winter. Continued monitoring is needed to have confidence in the initially observed
performance.
Climate Zone 4C
Only one wall type (2x6 plates with offset 2x4 studs) over a single winter season is available from
climate zone 4C as shown in Figure 36. An interior relative humidity of 47% was measured in the second
of the two test homes (no RH data is available for the first test home (WA1) for the first heating season).
Figure 36. Climate Zone 4C Summary MC Data
0
5
10
15
20
25
30
Av
era
ge
Se
aso
na
l Mo
istu
re C
on
ten
t, %
Climate Zone 4C - Moisture Content -North Wall
Seasonal Maximum
Winter Season 2012-13
2x6 Plates
offset 2x4Blown FG(Q-WA2)
2X6 Platesoffset 2x4Blown FG(Q-WA1)
Winter = 12/15 - 3/15
-
Home Innovation Research Labs August 2014 Wall Moisture Testing 35
Based on the limited available seasonal moisture content of sheathing and the interior relative humidity,
the following observations are identified:
Even with this first winter period following construction, the average MC is just over 20%
indicating that the wall system is sufficiently robust as designed and installed. However, the
moisture response for this wall system (no vapor retarder or exterior foam) appears dependent
on interior relative humidity in the house. For the conditions where RH is measured to be high,
the OSB moisture content approached its fiber saturation point for a short period of time.
Given that no summer data has yet been analyzed, the summer drying potential for all wall
configurations is needed. As with climate zone 5, drying is expected to below 15% MC.
Climate Zone 4
Climate zone 4 has a wider array of homes with a 2x6 wall system as shown in Figure 37 (except for one
test wall Type U – double 2x6). This allows for a larger comparison of the same wall system in different
homes. Figure 37 shows all of the homes and the data through two heating seasons. All of the wall
sections have wood sheathing on the exterior of the 2x6 cavity. The seasonal data for wall sections is
associated with interior house relative humidity levels as shown in Table 6.
Figure 37. Climate Zone 4 Summary MC Data
-
August 2014 Home Innovation Research Labs 36 Wall Moisture Testing
Table 6. Winter Average Seasonal Interior House Relative Humidity for CZ 4 Test Walls
Wall Type I.D. Interior RH
H (MD1), U 2011-2012 – 44%, 2012-2013 – 41% H (MD2) 2011-2012 – 34%, 2012-2013 – 38% H (MD3) 2011-2012 – 48%, 2012-2013 – 48% H (MD4) 2011-2012 – 31%, 2012-2013 – 35% H (DE1) 2011-2012 – 40%, 2012-2013 – 37%
Based on the seasonal moisture content of sheathing and the interior humidity, the following summary
conclusions are identified:
All of the 2x6 walls tested demonstrated a very similar range of performance with the winter
peak sheathing moisture contents below 20% and the average winter moisture content of below
16% (excluding wall type U).
While the much thicker fully-insulated cavity wall (double 2x6 wall type U) showed an increase
in moisture content of approximately 4-5%, the overall performance did not reach levels that
would lead to rejecting this wall system.
There is no clear relationship between the interior house relative humidity levels and observed
OSB moisture content (e.g., MD2 and MD3 have a 15% difference between interior RH, but have
nearly identical OSB moisture contents). It should be noted that wall cavities were effectively
sealed in all four Maryland houses, limiting bulk air leakage interior moisture loads to the
diffusion vapor drive.
Summertime drying to moisture contents below 10% is observed in all cases indicating excellent
drying capabilities for this wall system.
The wall design for climate zone 4, 2x6 framing, air sealing, and no interior vapor retarder other
than painted gypsum, demonstrates cyclic moisture characteristics that in typical service, leads
to a robust wall design.
Climate Zone 3
Climate zone 3 includes three houses each with a different wall system as shown in Figure 38. While
data is available only for a single winter season, OSB moisture content for all walls is below 15%. The
seasonal data for wall sections is associated with interior house relative humidity levels as shown in
Table 7.
-
H