mont vs hre uk

120
Kombi Kompakt HRE 24/18 HRE 28/24 HRE 36/30 Installation instructions Read these installation instructions carefully before installing and using the appliance. Intergas Verwarming BV 1

Upload: bibicualin

Post on 18-Dec-2015

62 views

Category:

Documents


4 download

DESCRIPTION

centrala hre

TRANSCRIPT

intergas

Kombi Kompakt HRE 24/18

HRE 28/24

HRE 36/30

Installation instructionsRead these installation instructions carefully before installing and using the appliance.

Keep these installation instructions with the appliance.

Always act in accordance with the instructions indicated.

INDICE

41SAFETY REGULATIONS

41.1General

41.2Central heating installation

41.3Gas installation

41.4Electrical installation

41.5Drinking water installation

41.6Flue pipe and air supply

52Description of appliance

52.1General

52.2Operation

52.3Operating modes

72.4PC Interface

72.5Test programs

92.6Accessories

103Installation

103.1Overall dimensions

123.2Installation location

133.3Assembly

154Connection

154.1Connecting CH installation

174.2Connecting DHW installation

184.3Electrical connection

194.4Gas connection

204.5Flue pipe and air supply

214.6Pipe lengths

224.7Balanced flue assemblies

325COMMISIONING the appliance

325.1Filling and venting the appliance and the installation

335.2Commissioning the appliance

345.3Shutting down

356Setting and adjustment

356.1Directly via the operating panel

366.2Settting via the service code

366.3Parameters

376.4Setting maximum CH power

376.5Adjusting pump setting

376.6Weatherdependent adjustment

386.7Conversion to different gas type

386.8Gas-/air adjustment

396.9Setting gas / air adjustment

407FAults

407.1Fault codes

407.2Other faults

438Maintenance

459Technical specifications

469.1Electrical diamgram

469.2NTC resistances

4710Warranty provisions

4711CE- Verklaring

2007 Intergas Verwarming BV

All rights reserved.

The information provided applies to the standard version of the product. Intergas Verwarming BV cannot therefore be held liable for any loss or damage arising from product specifications deviating from the standard version. The available information has been compiled with all possible care, but Intergas Verwarming BV cannot be held liable for any errors in the information or for the consequences thereof.

Intergas Verwarming BV cannot be held liable for any loss or damage arising from work performed by third parties.

Subject to change

This manual

This manual will enable you to assemble, install and maintain the appliance safely. Follow the instructions meticulously.

In case of doubt contact the manufacturer.

Keep these installation instructions with the appliance.

Abbreviations and descriptions used

DescriptionReffered to as

Hoog RendementHE

Intergas Kombi Kompakt HRE 24/18 wall mounted gas fired boilerAppliance

Appliance plus pipework for central heatingCH installation

Appliance plus pipework for domestic hot waterDHW installation

Pictograms

The following pictograms are used in this manual:

CAUTION

Procedures which if they are not performed with the necessary caution can result in damage to the product, the surrounding area or the environment, or in physical injury.

Service and technical support

For information about specific adjustments, installation, maintenance and repair work, please contact:

Intergas Verwarming BV

De Holwert 1

Postbus 6

7740 AA COEVORDEN

tel. 0524-512345

fax. 0524-516868

www.intergasverwarming.nl

Product identification

You will find the appliance data on the data plate on the underside of the appliance.

A. Appliance type

B. Hot water power rating (kW)

C. Power rating, upper and lower value (kW)

D. Rated power (kW)

E. Gas category

F. Gas connection pressure (mbar)

G. Gas type set

H. Pin

I. Appliance category

J. Maximum CH pressure (bar)

K. Maximum CH water temperature (C)

L. Maximum DHW pressure (bar)

M. Electrical connection

N. NOx number

O. Serial number

P. Year of manufacture

1 SAFETY REGULATIONS

The manufacturer Intergas Verwarming BV accepts no liability whatsoever for damage or injury caused by failure to adhere (strictly) to the safety regulations and instructions, or carelessness during installation of the ntergas Kombi Kompakt High Efficiency wall mounted gas fired boiler and any associated accessories.

1.1 General

The system as awhole must satisfy the applicable safety and other regulations, as indicated in:

These installation instructions.

NEN 1087: Ventilation in buildings Determination methods for new estate

NEN 3215: Drainage systems inside buildings.

The Building Decree.

Local regulations of municipal authority, fire service and public utilities.

1.2 Central heating installation

The entire installation must comply with the applicable safety and other regulations, as indicated in:

NEN 3028: Requirements for fuel combustion installations.

1.3 Gas installation

The entire installation must comply with the applicable safety and other regulations, as indicated in:

NEN 1078 (2004): Supply for gas with an operating pressure up to and including 500 mbar performance requirements- new estate

NPR 1088: Ventilation in dwellings and residential buildings.

NPR 3378: Guidelines for gas installations.

NEN 2920: Requirements for domestic gasconsuming installations and . . . on commercial butane, commercial propane en butane/propane mixtures.

1.4 Electrical installation

The entire installation must comply with the applicable safety and other regulations, as indicated in:

NEN 1010: Safety requirements for low-voltage installations

1.5 Drinking water installation

NEN 1006: General requirements for water supply installations.

1.6 Flue pipe and air supply

The flue pipe and air supply installation must comply with:

NEN 1078 (2004): Supply for gas with an operating pressure up to and including 500 mbar performance requirements- new estate NEN 2757: Air supply and smoke outlet of incineration furnaces in buildings determination methodes. NPR 3378: Guidelines for gas installations.2 Description of appliance

2.1 General

The Intergas Kombi Kompakt HRE wall mounted, gas fired boiler is a closed appliance. The appliance is intended to deliver heat to the water in a CH system and the DHW installation.

The air supply and combustion gas flue can be connected to the appliance by means of two separate pipes. A concentric connection can be supplied if requested. The appliance has been inspected in combination with the Intergas combi duct, but it can also be connected to combi ducts that comply with the universal requirements for combi ducts and which carry a Gaskeur(Dutch gas certification).

Depending on preference, the appliance may be connected to a mounting bracket, a frame with top connection and various connection sets. These are supplied separately.

The Intergas Kombi Kompakt HRE 24/18 wall mounted gas fired boiler carries the CE EP 20 rating and the Gaskeur (Dutch gas certification) labels HR, SV, NZ and CW Class 3.

This means that the appliance is suitable for supplying at least 6 litres of water per minute at 60C (this corresponds with 10 litres per minute at 40C) or filling a bath with 100 litres of water of average 40C within 12 minutes.

At the on and eco settings the appliance complies with the Gaskeur (Dutch gas certification) CW requirements.

It is possible to use the appliance solely for hot water or solely for heating. The unused system does not have to be connected. (See section 6.3)

The appliance is supplied as standard for natural gas (G25). On request an appliance can be supplied for propane (G31).

2.2 Operation

The Intergas Kombi Kompakt HRE wall mounted, gas fired boiler is a modulating high efficiency boiler. This means that the power is adjusted in line with the desired heat requirement.

The aluminium heat exchanger comprises two separate copper circuits.

As a result of the separately constructed circuits for CH and DHW the heating and hot water supply can operate independently of each other. The hot water supply takes priority over the heating. The two systems cannot operate simultaneously.

The appliance is equipped with an electronic burner manager which, each time heat is requested from the heating or the hot water supply, start the fan, opens the gas valve, ignites the burner and continuously monitors and controls the flame, depending on the requested output.

2.3 Operating modes

A code on the service display of the operating panel indicates the appliances operating mode.

- Off

The appliance is out of operation but is supplied with electrical power. No response occurs to calls for DHW or CH. The appliance frost protection is active. This means that the pump operates and the exchanger is heated up if the temperature of the water present in it falls too far.

If the frost protection is actuated, code 7 is displayed (heating exchanger).

In this operating mode the pressure in the CH installation (in Bar) can also be read on the temperature display.

Waiting modeThe LED at the button is lit and possibly one of the LEDs for the DHW comfort function. The appliance is ready to respond to a request for CH of DHW.

0 Running on of CH

After the end of CH operation the pump continues to run. The running on time is factory set at he value in accordance with section 6.3 , page:36. This setting can be changed.

In addition, the pump runs automatically for 10 seconds once every 24 hours in order to prevent seizing. This automatic switching on of the pump occurs at het time of the last call for heat. To change the time, the room thermostat setting should be increased briefly at the desired time.

1 Desired temperature reachedThe burner manager can temporarily block the request for heat. The burner is then stopped. Blocking occurs because the requested temperature has been reached. When the temperature has fallen sufficiently the blocking is cancelled.

2 Self-test

The connected sensors are checked regularly by the burner manager. During the check the manager does not perform any other tasks.

3 VentilationWhen the appliance is started the fan is first brought to starting speed. When the starting speed has been reached the burner is lit. Code 3 is also visible when post-ventilation is taking place after the burner has stopped.

4 Ignition

When the fan has reached the starting speed, the burner is ignited by means of electrical sparks. During ignition the code 4 is visible. If the burner does not ignite, a new ignition attempt occurs after approximately 15 seconds. If after 4 ignition attempts the burner is not yet burning, the burner manager goes into fault mode. (See section 7.2.1).

5 CH operationAn of/off thermostat, an OpenTherm thermostat, an external sensor or a combination of the latter can be connected to the burner manager. (See section 9.1)

When a request for heat is received from a thermostat, the fan is started (code 3 ), followed by ignition (code 4 ) and CH operating mode (code 5 ).

During CH operation the fan speed and hence the appliance power are controlled by the burner manager so that the CH water temperature reaches the desired CH supply temperature.

If an on/off thermostat is connected, this is the CH supply temperature set on the display. In the case of an OpenTherm thermostat the desired CH supply temperature is determined by the thermostat. In the case of an external sensor the desired CH suppply temperature is determined by the heating line programmed in the burner manager. For the latter two, however, the maximum is the temperature set on the display.

The CH operation the requested CH supply temperature is indicated on the operating panel.

The CH supply temperature can be set between 30C and 90C. (See section 6.1).

The actual CH supply temperature can be read by pressing the service button during CH operation.

When the DHW comfort function is switched on (See code 7 ) any OpenTherm request for heat of less than 40C is ingored.

The resistance R may be removed if the room thermostat does not need anticipation current. (See section 9.1)

6 DHW operation

The hot water supply takes priority over the heating. If the flow switch detects a need for more than 2 l/min of DHW, any demand for CH will be interrupted. After the fan has reached speed (code 3 ) and ignition has taken place (code 4 ) the manager goes to DHW mode (code 6 ).

During DHW operation the fan speed, and hence the power of the appliance, are controlled by the burner manager so that the DHW water temperature reaches the DHW temperature setting.

The water temperature can be set between 40C and 65C (See section 6.1) and is displayed on the operating panel during DHW operation.

The actual DHW temperature can be read by pressing the service button during DHW operation.

7 Pre heating exchanger

To enable fast delivery of domestic hot water the burner manager is equipped with a so-callde DHW comfort function. This function maintains the temperature of the heat exchanger to an adjustable temperature (See section 6.1.). The DHW comfort function has the following settings:

On: ( LED on) The appliances DHW comfort function is switched on continuously. The appliance always delivers hot water immediately.

Eco: ( LED on) The appliances DHW comfort function is self learning. The appliance will adapt to the patttern of use of the hot water tap. As a result, the temperature of the heat exchanger will not be maintained during the night or in the case of lengthy absence.

Off: (Both LEDs off) The temperature of the heat exchanger is not maintained, as a result of which the delivery of hot tapwater takes a little time. If there is no need for fast delivery of hot tapwater, the DHW comfort function can be switched off.

In the case of the on an eco settings the apppliance meets the Gaskeur(Dutch gas certification) central heating requirements.

2.4 PC Interface

The burner manager is equipped with an interface for a PC, which can be connected by means of a special cable and associated software. This facility allows the behaviour of the burner manager , the appliance and the heating installation to be monitored over a longer period.

2.5 Test programs

The burner manager has a facility for placing the appliance in test mode.

Activation of a test program will result in the appliance starting operation at a fixed fan speed, without the control functions being actuated.

The safety functions do remain active.

The test program is ended by pressing the and simultaneously.

Test programs

Program descriptionButton combinationsDisplay reading

Burner on at minimum CH power and L

Burner on with maximum CH power setting (See section 6.3, parameter 3) and (1x)h

Burner on with maximum DHW power (See section 6.3, parameter 4) and (2x)"H"

Switch off test program and Actuele bedrijfssituatie

2.5.1 Frost protection

To prevent freezing of the appliance it is equipped with appliance frost protection. If the heat exchanger temperature falls to low, the burner swiches on and the pump runs until the heat exchanger temperature is sufficient. When the appliance frost protection is actuated code 7 is displayed (pre heating exchanger).

If the installation (or a part of it) can freeze, an (external) frost thermostat must be fitted to the return line at the coldest location. This must be connected in accordance with the wiring diagram. (See section 9.1.)

NoteIf the appliance is out of operation ( - on the service display) the appliance frost protection is active. However, a request for heat from an (external) frost thermostat will not be responded to.

Principal components

A.

CH pump

L.

Air supply

B.

Gas block

M.

Flue pipe adapter

C.

Burner manager plus operating panel

N.

Connection block / terminal strip X4

D.

Supply sensor S1

O.

Condensate drain pan

E.

Return sensor S2

P.

Hot water sensor S3

F.

Fan

Q.

Siphon

G.

Flow switch

R.

Heat exchanger

H.

CH pressure sensor

S.

Operating panel and read-out

I.

Mains lead 230 V AC with grounded plug

T.

Ionisation / Ignition pin

J.

Manual air bleed

U.

Position of data plate

K.

Sight glass

2.6 Accessories

DescriptionArticle numbers

Mounting bracket HRE 24/18

Connection for supply and return 22 mm

Connection for hot and cold water 15 mm

Gas connection " internal thread

Packet of fastening materials092.297

Complete bottom connection set

T-piece 22x"x22 compression fitting(2 stuks)

Pressure relief valve 3 bar

Filling / drain tap

Inlet assembly 15-15 compression fitting, 8 bar

Gas tap x15 compression fitting 092.557

Universal connection set

T-piece 22x"x22 compression fitting (2 stuks)

Pressure relief valve 3 bar

Filling / drain tap092.547

Top connection frame HRE (small)

Frame

Packet of fastening materials092.257

Top connection set complete

T-piece 22x"x22 knel (2 stuks)

Pressure relief valve 3 bar

Filling / drain tap

Inlet assembly 15-15 compression fitting, 8 bar

Gas tap x15 compression fitting

Top connection pipes092.517

HRE cover plate set092.677

External sensor203.207

Two-way valve set 230 V AC for floor heating and MIT092.637

Concentric connection 80x125

Concentric flue adapter

Sealing cap090.557

Concentrische aansluiting 60x100

Concentric flue adapter

Sealing cap090.547

PC Interface cable090.407

Connection set for solar boiler post-heating090.317

3 Installation

3.1 Overall dimensions

Appliance with connections downwards:

Appliance + mounting bracketA =

Supply CH

22

B =

Return CH

22

C =

Gas

(F)

D =

Cold tap water

15

E =

DHW

15

F =

Condensate drain

25 (flexible)

h=

517

H=

590

Y =

Air supply

80 (sealing ring)

Z1 =

Flue pipe

80 (sealing ring)

Z2 =

Flue pipe / air supply

60/100, or 80/125 (concentric)

Appliance + mounting bracket + complete bottom connection setA =

Supply CH

22 (compression)

B =

Return CH

22 (compression)

C =

Gas

15 (compression)

D =

Cold tap water

15 (compression)

E =

DHW

15

F =

Condensate drain

25 (flexibel)

Y =

Air supply

80 (sealing ring)

Z1 =

Flue pipe

80 (sealing ring)

Z2 =

Flue pipe / air supply

60/100, or 80/125 (concentric)

Appliance with connections upwards:

Appliance + mounting bracket + top connection frame HRE (small)A =

Supply CH

22

B =

Return CH

22

C =

Gas

(F)

D =

Cold tap water

15

E =

DHW

15

F =

Condensate drain

25 (flexible)

h=

834

Y =

Air supply

80 (sealing ring)

Z1 =

Flue pipe

80 (sealing ring)

Z2 =

Flue pipe / air supply

60/100, of 80/125 (concentric)

Appliance + mounting bracket + top connection set completeA =

Supply CH

22

B =

Return CH

22

C =

Gas

15

D =

Cold tap water

15 (top pipe end, bottom compression)

E =

DHW

15 (top pipe, bottom compression)

F =

Condensate drain

32 or 40 (spigot end)

Y =

Air supply

80 (sealing ring)

Z1 =

Flue pipe

80 (sealing ring)

Z2 =

Flue pipe / air supply

60/100, or 80/125 (concentric)

3.2 Installation location

The appliance should be fitted to a wall that has sufficient bearing strength.

In case of light wall structures the possibility exitsts that resonance noise may occur.

There must be an earthed wall socket within 1 m of the appliance.

If the appliance is installed as an open appliance, the installation location should be equipped with the necessary openings for the combustion air supply. (See section 4.5.2, page:20.)

To prevent freezing of the condensate drain pipe, the appliance must be installed in a frost free room.

3.2.1 Installing in a kitchen cupboard

The appliance can be installed between two kitchen cabinets or in a cabinet.

Ensure sufficient ventilation at top and bottom. If the appliance is installed in a cabinet, ventilation openings of at least 50 cm2 must be created.

3.2.2 Removing cover plate and front panel

For various work on the appliance the cover plate and front panel should be removed from the appliance. Proceed as follows:

If cover plate (A), is used, remove to the front.

Unscrew the two screws (1) behind the appliance display window.

Pull the bottom of the front panel (2) forwards.

3.3 Assembly

Depending on the connection situation, to mount the appliance use is made of a suspension strip and mounting bracket or a top connection frame and mounting bracket.

On the mounting bracket the installation can be connected before the appliance is installed.

3.3.1 Fitting the suspension strip and mounting bracket

Secure the suspension strip and the mounting bracket horizontally to the wall with the fastening materials, in accordance with the drilling template. (See section 3.1)

3.3.2 Fit the top connection frame and mounting bracket

Using the fastening materials supplied, secure the frame verticlly to the wall

Slide the connection pipes into the frame (only in the case of the complete top connection set).

Secure the mounting bracket in the frame by inserting it with the flanged side upwards through the openings in the frame and securing it with the two screws and nuts supplied with the frame.

Note:

The appliance is wider than the frame.

3.3.3 Fit the parts from the various connection sets:

Fit the filling/drain tap (A) with T-piece 22-1/2"-22 compression (B) to the return connection.

Fit the overflow valve (C) (3 bar) with the T-piece 22x1/2"-22 compression (D) to the supply connection.

Fit the inlet assembly (E) (15-15 compression 8 bar) to the cold water connection (only in the case of complete (top) connection set).

Fit the gas tap (F) (with coupling) to the gas connection (only in the case of complete (top) connection set).

Assemble the drains for the pressure relief valve (G), the inlet assembly (H) and the siphon (I). Fit the assembly into the mounting bracket (only in the case of complete (top) connection set).

Now install the appliance, or connect the installation.

3.3.4 Installing the appliance

1. Unpack the appliance.

2. Check the contents of the packaging; the consist of:

Appliance (A)

Suspension strip (B)

Siphon (C)

Installation instructions

Operating instructions

Warranty card

3. Check the appliance for possible damage: report damage immediately to the supplier.

4. Check whether the compression rings are sitting squarely in the mounting bracket couplings.

5. Fit the appliance, sliding it downwards over the suspension strip. Ensure at the same time that the pipes slide into the compression fittings.

6. Tighten the compression fittings on the mounting bracket. The nipples must not be allowed to turn!

7. Fit the flexible tube to the siphon outlet.

8. Fill the siphon with water and slide it as far as possible upwards on to the condensate drain connector (C) below the appliance.

9. Connect the flexible tube (A) from the siphon (where applicable together with the overflow pipe from the inlet assembly and the pressure relief valve) to the drain via an open connection (B).

10. Fit the air supply and the combustion gas flue. (See section 4.5)

3.3.5 Fit the cover plate

Hang the flanged upper edge of the cover plate on the washers under the base of the appliance and slide the cover plate as far as possible towards the rear.

4 Connection

4.1 Connecting CH installation

11. Flush the CH system thoroughly to clean.

12. Fit the supply pipe (B) and the return pipe (A) to the mounting bracket.

13. All pipes must be fitted unstressed in order to prevent the pipes from ticking.

14. Existing connections must not be twisted, in order to avoid leakages.

The CH system should be equipped with:

A filling/draining tap (A) in the return pipe immediately below the appliance.

A drain tap at the lowest point(s) of the installation.

A 3 bar pressure relief valve (B) in the supply pipe at a maximum distance of 500 mm from the appliance.

There must be no valve or constriction between the appliance and the overflow valve.

An expansion vessel in the return pipe.

A check valve, if pipes run upwards at a short distance from the appliance. This avoids the occurrence of thermosiphon effect during DHW operation mode.

4.1.1 Thermostatic radiator valves

If all radiators are equipped with thermostatic or regular radiator valves, a bypass must be fitted in order to guarantee minimum water circulation. The bypass must be at a distance of at least 6 m from the appliance in order to prevent overheating of the appliance.

4.1.2 Floor heating

For effective operation of the DHW supply there must not be any undesired circulation through the appliance as a result of a second pump in the CH circuit.

Connect the floor heating system in a hydraulically neutral manner to the appliance, or equip the CH circuit with an electric shut-off valve or check valve to prevent flow through the appliance when there is no CH request for heat.

Connection diagram for floor heating

Q. Boiler

R. Pump

S. Floor heating valve

T. Check valve (spring operated)

U. Electrical valve 230 V AC

V. Radiators

W. Room thermostat

X. Maximum thermostat

4.1.3 Appliance with MIT regulation

The appliance can also be used in combination with an indirectly fired air heater (e.g. Brink Elan) and a heat recovery unit (e.g. Brink Renovent HR). The appliance is suitable for the heating of fresh ventilation air by just a few degrees. This guarantees a Minimum Intake air Temperature.

This MIT regulation can be switched on and off with an external switch.

To save energy the pump setting must be adjusted as low as possible.

MIT regulation connection diagram

A. Intergas Kombi Kompakt

B. Pressure relief valve

C. Expansion vessel

D. Combined fan coil and heat recovery unit

E. Fan

F. Adjustable flow limiter (Taco 23.1202)

H. Electrical Shut-off valve

Operating principle

When the MIT regulation is switched on the appliance pump and DHW comfort function are also switched on. A small heat flow (maximum 500 W) is admitted to the fancoil via the adjustable flow limiter. This heats up the outside air by a few degrees. The shut-off valve is opened when there is a demand for CH heat.

Installation instructions

15. Connect the appliance to the air heater.

16. Construct the system in copper in order to prevent fouling of the flow limiters narrow flow opening.

17. Always install the shut-off valve parallel to the adjustable flow limiter.

18. Insulate the supply pipe to the air heater.

19. Connect the electrically operated shut-off valve (connector X2) and the MIT switch (connector X4). (See sections 4.3.1 and 9.1.)

20. Change prameter 2 of the service code. See Installer settings in section 6.3.

Note

The MIT regulation only operaters when DHW comforton the appliance display is set to on. Consult the thermostat manual when using an OpenTherm room thermostat.

Setting flow limiter

Adjust the flow limiter (F) so that, at minimum air volume, the temperature difference of the air across the fan coil is 5C. The flow will then be approximately 0.2 litres per minute. This is below the minimum measuring range of the flow limiter.4.2 Connecting DHW installation

21. Flush the installation thoroughly to clean.

22. If prescribed, fit an inlet assembly.

23. Fit the cold an hot water pipes (A and B) to the mounting bracket.

Notes

At the settings on and eco the appliance meets the Gaskeur (Dutch gas certification) CW requirements.

For the Kombi Kompakt HRE 24/18 the specific pipe length in the case of a pipe diameter of 12/10 mm is 23.50 metres. In the case of a pipe diameter of 15/13 mm this is 13.90 metres for the Kombi Kompakt HRE 24/18.

If the appliance is only used for the provision of hot water, the heating function can be switched off with the service code on the operating panel. The CH installation does not then have to be connected or filled.

If the appliance is taken out of operation during the winter and disconnected from the mains supply, the sanitary water must be drained in order to prevent freezing. For this purpose the DHW connections below the appliance must be removed.

Flow Resistance graph for appliance DHW circuit

Y. Kombi Kompakt HRE 24/18

X.kPa (Bar)

Y.Litres per minute

4.2.1 Appliance with solar water heater post-heating

The appliance carries the NZ label: suitable for solar water heater post-heating.

A special connection kit is applicable for this purpose.

Connection diagram for solar heater post -heating

A. Boiler

B. Storage tank Solar water heater

C. Cold water inlet

D. Inlet assembly

E. Flow switch

F. T max 85C

G. Hot water outlet T>60C

H. Thermostatic mixing valve 40 - 90C (set to aproxx. 60C)

K. Mixed water outlet

Note

When combined with a solar power system a thermostatic mixing valve must always be fitted after the appliance and set to approx. 60C.

4.3 Electrical connection

CAUTION

An earthed wall socket must be located no more than 1 metre from the appliance.

The wall socket must be easily accessible.

For installation in damp rooms a fixed connection is obligatory.

When workin on the ectrical circuit always remove the plug from the wall socket

If the mains lead has to be replaced, this should be carried out by the manufacturer

24. Slide the cover plate (A) (if present) to the front to remove.

25. Unscrew screw (A) to gain access to the burner manager (B).

26. Pull the burner manager unit forwards; the burner manager will tip downwards to provide access.

27. Consult sections 4.3.1 and 9.1 for the making the connections.

28. After making the desired connections plug the appliance into an earthed wall socket.

4.3.1 Electrical connections

Temperature controlConnector X4Notes

Room thermostat6 - 7-

Modulating thermostat with comfort function in use11 - 126 7 open

Remove connection between 4 5

Outside temperature sensor8 - 9-

External DHW disable- or MIT switch4 - 5Remove connection

Frost protection thermostat6 - 7Parallel to room thermostat

Power supply 24 V DC6 7 - 96= 24 V DC

7= room thermostat

9= 0 V DC

4.3.2 On / Off room thermostat

29. Connect the room thermostat (See section 4.3.1.)

30. Adjust the feedback resistance of the room thermostat to 0.1 A. In case of doubt measure the current and adjust this accordingly The allowed maximum electrical resistance of the room thermostat and wiring is 15 Ohm

4.3.3 Timer - room thermostat

A 3 VA , 24 DC power supply is available for a timer-room thermostat.

Connect the timer room thermostat according to section 4.3.14.3.4 Outside temperature sensor

The appliance is equipped with a connection for an outside temperature sensor. The outside temperature sensor can be used in combination with an on/off room thermostat or an OpenTherm* thermostat.

Connect the outside temperature sensor. (See section 4.3.1.)

For the heating line setting, see weather-dependent regulation. (See section 6.6, page: 37)

* In case of OpenTherm the thermostat determines the heating line. The appliance onl passes on the outside termperature.

4.3.5 Modulating thermostat

The appliance is suitable for connection of a modulating thermostat, in accordance with the OpenTherm communication protocol.

The most important function of the modulating thermostat is calculation of the supply temperature for a desired room temperature, in order to make optimum use of modulation. In the case of each request for heat the desired supply temperature is indicated on the appliance display.

Connect the modulating thermostat. (See section 4.3.1.)

If it is desired to make use of the DHW on/off switching function of the OpenTherm thermostat, connector 4-5 on X4 should be removed and the DHW comfort function set to eco or on. (See section 4.3.1.).

For further information consult the thermostat manual.

4.4 Gas connection

31. Fit a gas tap (A) between the gas supply and the appliance.

32. Fit the connection from the gas tap preferably directly into the connection at the mounting braket.

33. Install a gas filter mesh in the connection for the appliance if the gas may be contaminated.

34. Connect the appliance to the gas supply.

35. Check the gas carrying parts for leakage at a maximum pressure of 500 mmH2O

4.5 Flue pipe and air supply

The pipes for combustion gases and air supply must have a diameter of 80 mm.For other diameters contact the manufacturer.

A concentric flue and air supply pipe must have minimum diameters of 80x125 mm or 60x100mm.

4.5.1 Draught, materials and insulation

PipeDiameterMaterial

Air supply 80 mmAs per the local fire service and/or power company regulations.

Spiralotube, single-walled aluminium, galvanised sheet steel, stainless steel or plastic.

Possibly insulated with 10 mm vapour-tight insulation material or plastic.

Combustion gas flue 80 mmAs per table 8 of NEN 1078 (1987).

Insulation-10 mm vapour-tight insulation material in case of possibility of condensation on the outside as a result of a low wall temperature and a high room temperature with high relative humidity.

4.5.2 Open appliance connection

CAUTION

Ensure the necessary ventilation of the installation location.

36. Fit the pipe for the combustion gas flue into the flue outlet. The integral sealing ring ensures an airtight connection.

4.5.3 Closed appliance connections

Two-pipe connection

37. Fit the pipes for the air supply and combustion gas flue into the appliance inlet and outlet. The integral sealing rings ensure an airtight connection.

Concentric connection

With the concentric adapter set the standard two-pipe connection can be changed to a concentric connection (80/125 or 60/100).

38. Seal the open air supply connection in the appliance with the sealing cap supplied with the kit..

39. Remove the flue pipe adapter from the top of the appliance by turning it anti-clockwise.

40. Remove the o-ring from the adapter flange and fit it around the flange of the concentric adapter.

41. Place the concentric adapter in the top of the appliance and turn it clockwise so that the measurement nipple points straight forwards.

42. Fit the concentric pipe for the air supply and combustion gas flue into the adapter. The integral sealing rings ensure an airtight connection.

4.6 Pipe lengths

As the resistance of the flue pipe and air supply pipe increases the appliance power will decline. The maximum permitted reduction in power is 5 %.

The resistance of the air supply pipe and combustion gas flue depends on the length, the diameter and all components of the pipe system. The total permitted pipe length of the air supply and the combustion gas flue is indicated for each appliance category.

The indication of pipe length in metres is based on 80 mm.

4.6.1 Equivalent lengths

Bend 90R/D=12 m

Bend 45R/D=11 m

Elbow 90R/D=0,54 m

Elbow 45R/D=0,52 m

In the case of larger or smaller pipe diameters the permissible pipe length is greater or smaller respectively.

In the case of smaller diameters the following applies:

70: 0,59x the permissible pipe length for 80

60: 0,32x the permissible pipe length for 80

50: 0,15x the permissible pipe length for 80

Contact the manufacturer for check calculations for the resistance of the air supply and combustion gas flue pipe and the wall temperature at the end of the combustion gas flue pipe.

4.6.2 Sample calculation

PipePipe lengthsTotal pipe length

Flue pipeL1 + L2 + L3 + 2x2 m13 m

Air supplyL4 + L5 + L6 + 2x2m12 m

Note

The total pipe length is:Sum of the straight pipe lengths + sum of the equivalent pipe lengths of bends/elbows.

Permissible length of air supply pipe and flue outlet pipe totals 85 m, excluding the lenght of the combi duct or the dual-pipe duct.

4.7 Balanced flue assemblies

Assembly general:

The assembly described below applies to all flue systems:

43. Slide the combustion gas flue pipe into the appliance flue outlet.

44. Slide the combustion gas flue pipes into each other.Working from the appliance each pipe must be pushed into the previous pipe

45. Fit a non-vertical combustion gas flue pipe with a fall towards the appliance of minimal 5mm per metre

46. Fit flanged seams oriented upwards in a horizontal section.

47. Seal non-gastight connections with heat-and moisture-resistant aluminium tape.

Assemble all air supply pipes as indicates below:

48. Slide the air supply pipe into the appliance inlet.

49. Seal non-airtight connections with moisture-resistant tape.

50. Fit insulation if necessary.

Materials to be used:

Appliance categoryMaterialsSupplier

C13DuctIntergas

Other partsGastec QA or Intergas

C33DuctIntergas

Duct in the case of PrefabGastec QA, Intergas or third parties

Other parts

C43All materialsGastec QA or Intergas

For the combined air supply / combustion flue systemThird parties

C53Inlet grilleIntergas

Other parts and flue cowlGastec QA or Intergas

C63All materials and ductGastec QA

C83Inlet grilleIntergas

Main channelThird parties

Other partsGastec QA or Intergas

4.7.1 Dual-pipe wall duct, horizontal terminal

Appliance category: C13

CAUTION

Pipes for the connection of the air supply and the combustion gas flue between the appliance and the dual-pipe terminal must have a diameter of 80 mm.

Intergas dual-pipe horizontal duct.Can be extended, for purposes of a gallery balcony terminal, with one or two standard pipes ( 80 mm).

Permissible pipe length

Air supply and flue pipe: together 100 metres, including the length of the dual-pipe terminal.

Combustion gas flue and air supply pipe

For assembly, see section 4.7 Assembly general.

Fitting dual-pipe duct

51. Fit the dual-pipe duct with a fall towards the appliance.

52. Make two openings of 90 mm in the wall.

53. Shorten the dual-pipe duct to the correct length.

54. Slide the supply and flue pipes into the openings.

55. Cover the openings with the wall cover plates.

56. Fit the outlet grilles to the supply and flue pipes.

57. Secure them to the pipes.

Fitting double-pipe extension pipe(s) for gallery balcony terminal.

If the free end of the terminal is obstructed by a roof overhang, balcony, gallery or otherwise, the air supply pipe and the combustion gas flue pipe must be extended to at least the front of the protruding part.

If the air supply cannot be disturbed by obstacles, such as a support or dividing wall and if the terminal is not at the edge of a building, the air supply pipe does not have to be extended.

58. Extend the combustion gas flue pipe, and where appropriate also the air supply pipe, of the dual-pipe duct with a standard combustion gas flue and air supply pipe of the correct length in accordance with the dimensions indicated.

59. Slide the combustion gas flue and where appropriate also the air supply pipe into the inlet and outlet pipe of the dual-pipe duct.

60. Fit the combustion gas flue and air supply pipe with a fall towards the appliance.

61. Fit the outlet grilles to both pipes.

4.7.2 Horizontal wall and roof terminal with a combi duct

Appliance category: C13

CAUTION

Pipes for connecting the air supply and the combustion gas flue between the appliance and the combi duct must have a diameter of 80 mm.

Intergas combi duct-horizontal.For wall or roof terminal - horizontal.

Intergas combi duct-horizontal.For extension of a balcony/gallery discharge.

Permitted pipe lengths

Two-pipe

Air supply and combustion gas flue pipe: together 85 m, excluding the length of the combi duct.Concentric

Air supply and combustion gas flue pipe, excluding the length of the combi duct:In the case of 80/125 mm is 29 metresIn the case of 60/100 mm is 11 meter

Combustion gas flue and air supply pipe

For assembly see section 4.7 Assembly general.

Assembly of combi duct horizontal wall terminal

62. Fit the combi duct with a fall towards the appliance

63. Make an opening of 130 mm in the wall at the position of the discharge.

64. Cut the combi duct to the correct length according to the dimensions indicated.

65. Fit the outlet grille and secure this to the inner pipe.

66. Slide the combi duct into the opening and fit the rosettes to cover the opening.

Fitting a combi extension pipe for balcony/gallery terminal

If the free end of the terminal is obstructed by a roof overhang, balcony, gallery or otherwise, the combi duct must be extended to at least the front of the protruding part.

67. Fit the combi extension pipe to the combi duct.

68. Shorten the combi duct or the combi duct extension pipe to the corrrect lenght in accordance with the dimensions indicated.

69. Fit the outlet grille and secure it to the inner pipe.

70. Fit the combi duct and combi extension pipe with a fall towards the appliance.

Fitting a combi duct horizontal roof terminal

71. The terminal can be placed at any point in the roof surface.

72. Fit a horizontal roof flashing (D) (suitable for pipe 120 mm).

73. Fit the outlet grille to the combi duct and secure it to the inner pipe.

74. Slide the combi duct (C) from inside to outside through the horizontal flashing, in accordance with the dimensions indicated.

75. Fit the combi duct (C) with a fall towards the appliance.

4.7.3 Vertical roof terminal with combi duct and dual-pipe duct.

Appliance category: C33

CAUTION

If the Intergas vertical combi duct cannot be used, the air supply and combustion gas flue must be constructed separately.

Intergas vertical combi duct.

Permitted pipe length.

Dual pipeAir supply and combustion gas flue pipe: together 85 m, excluding the length of the combi duct or the dual-pipe duct.Concentric

Air supply and combustion gas flue pipe excluding the length of the combi duct:In the case of 80/125 mm is 29 metresIn the case of 60/100 mm is 11 metres

Combustion gas flue and air supply pipe

For assembly see section 4.7 Assembly general

Fitting a vertical combi duct

76. Fit a vertical flashing for a sloping roof at the position of the discharge.On a flat roof a flashing plate for a 126 mm must be fitted.

77. Remove the branch from the combi duct (C).

78. Slide the combi duct (C) from the outside inwards.

79. Fit the branch for the combi duct (C) and secure it with a sheet metal screw or rivet.

Fitting a vertical two pipe terminal

CAUTION

The discharges of the cobution gas flue and air supply should be made in the same pressure surface.

The air supply through the sloping roof surface and the combustion gas flue through a structural chimney is also possible, but not the reverse.

80. Fit a standard double-walled flue pipe ( 80 mm) with Giveg approved flue cowl on a sloped roof flashing at the desired position.

81. Fit a standard ventilation pipe ( 80 mm) with cross cowl and roof flashing for the air supply.

82. Fit a standard double-walled flue pipe ( 80 mm) with Giveg approved cowl at the desired position .In the case of a flat roof or a structural chimney, for the purposes of the air supply fit a standard ventilation duct ( 80 mm) with cross cowl in an accompanying flashing plate.

CAUTION

Two terminals must be at least 200 mm apart.

4.7.4 Roof terminal, prefabricated chimney systems

Appliance category: C33

If there is too little room in a shaft, a roof terminal through a prefab chimney system may be necessary.

The prefab chimney should be equipped with flue pipe and air supply openings of at least 150 cm2 per connected appliance and must satisfy the minimum dimensions indicated. The supplier must guarantee the effective operation of the prefabricated chimney with regard to wind attack, ice formation, rain penetration etc.

As a result of the various designs and dimensions the prefabricated chimneys have to be adapted to the local situation.

CAUTION

The connection of the air supply and the combustion gas flue between the appliance and the prefabricated chimney must be constructed in 80 mm pipe.

Permitted pipe length

Air supply and combustion gas flue pipe: toegether 105 metres.

Combustion gas flue and air supply pipe

For assembly see section 4.7 Assembly general.

Fitting prefabricated chimney system

The terminal can be constructed at any point in the sloping or flat roof surface.

4.7.5 Roof terminal and air supply through an external wall

Appliance category: C53

CAUTION

The air supply in the external wall must be fitted with an Intergas inlet grill (A).

Combustion gas flue (B) through a prefabricated chimney, or through an 80 mm diameter double-walled roof duct with Giveg' flue cowl.

The prefab chimney should be equipped with flue pipe and air supply openings of at least 150 cm2 per connected appliance and must satisfy the minimum dimensions indicated. The supplier must guarantee the effective operation of the prefabricated chimney with regard to wind attack, ice formation, rain penetration etc.

Permitted pipe length

Air supply and flue pipe: toegether 100 metres, including the length of the duct.Flue pipe and air supply pipe

For assembly see section 4.7 Assembly general

Fitting horizontal air supply

The air supply (A) may be constructed at any point in the external wall.

83. At the position of the inlet make a 90 mm opening

84. Cut the air supply pip to the desired length away from the wall.

85. Fit the Intergas inlet grille and secure it to the pipe.

86. Slide the air supply pipe into the opening and cover the opening with a rosette if necessary.

87. Fit the air supply, at the position of the external wall duct, sloping downwards to the outside, in order to avoid rain penetration.

Fitting combustion gas duct - vertical

88. In a sloping roof, fit the terminal with the appropriate flashing. In a flat roof fit a flashing plate, suitable for a 80 mm (diameter 96 mm) double-walled flue pipe.

89. Slide the double-walled flue pipe from the outside inwards through the roof duct. The termination height must be at least 500 mm above the roof surface.

4.7.6 Air supply from an external wall and a roof terminal with common flue system

Appliance category: C83

An air supply from an external wall and a roof terminal with common flue system is permitted.

CAUTION

The air supply in the external wall must be fitted with an Intergas inlet grille (A).

The terminal of the common flue system must be fitted with a cowl which creates a draught (B) in the flue.

The minimum bore of the common flue system

Number of appliancesFlue diameter

2110

3130

4150

5180

6200

7220

8230

9240

10260

11270

12280

Permitted pipe length

Air supply and combustion gas flue pipe between appliance and common flue and air supply pipe: together 100 metres.

Flue and air supply pipe

For assembly see section 4.7 Assembly general

Common flue

The terminal for the common flue may be constructed at any point in the sloping roof surface, provided that the terminal in the roof surface has the same orientation as the ari supply in the external wall. In the case of a flat roof the terminal for the common flue must be constructed in the free termination area.

Fit a condensate drain.

CAUTION

The common flue system must be equipped with a draught creating flue cowl (B).

If the common flue system is situated in the outside air, the flue pipe must be double-walled or insulated.

Note

The common flue system has been tested in combination with the appliance.

4.7.7 Roof terminal for combined air supply / combustion flue system

Appliance category: C43

CAUTION

A roof terminal through a combined air supply / combustion flue system is permitted.

A certificate of no objection or a Gaskeur(Dutch gas certifiction) from the Dutch Gastec-Gasinsitute is required for the common flue cowl and air supply cowl.

The common air supply and the common flue may be of a concentric or separate design.

Permitted pipe length

Air supply an flue pipe between appliance and combined air supply / flue system: 100 metres.

Flue pipe and air supply pipe

For assembly see section 4.7 Assembly generalNote

The draught of the common air supply and flue system should be indicated by the manufacturer of the combined air supply / combustion flue system.

5 COMMISIONING the appliance

5.1 Filling and venting the appliance and the installation

5.1.1 CH system

WARNING

If an additive is added to the CH water, this must be suitable for the materials used in the appliance, such as copper, brass, stainless steel, steel, plastic and rubber.

90. Insert the appliance plug into a wall socket.

The appliance may perform a self test: 2 (on service display).The appliance will then go into wait mode: - (on service display).

91. Connect the filling hose to the filling/drain tap and fill the installation with clean drinking water, to a maximum pressure of 1-2 bar in the case of a cold installation. (Indicated on the temperature display.)

92. Bleed the appliance with the manual bleed screw (A).An automatic air bleeding device may be fitted to the appliance in place of the manual bleed screw.

93. Bleed the air in the installation with the manual bleed screws on the radiators.

94. Top up the CH installation if the pressure has dropped too far as a result of the air bleeding.

95. Check all copulings for leakage.

96. Fill the siphon with water.

5.1.2 Hot water supply

97. Open the main tap to pressurise the hot water section.

98. Vent the exchanger and the pipe system by opening a hot water tap.

99. Leave the tap open until all air has disappeared from the system.

100. Check all connections for leaks.

5.1.3 Gas supply

101. Vent the gas supply with the pre-pressure measurement nipple (D) on the gas block.

102. Check the connections for leaks.

103. Check the pre-pressure and the burner pressure. (See section 6.8.)

5.2 Commissioning the appliance

Read-outOperation

1On / offAOn / Off button

2CH operation or setting maximum CH temperatureBDHW / CH button, for setting desired temperature

3DHW operation or setting DHW termperatureC- button

4Desired temperature of cH or DHW in C / Ch water pressure in bar / Fault codeD+ button

5DHW comfort function eco or setting number of memory daysEDHW comfort function off / eco / on

6DHW comfort function on (continuous) or set heat maintenance temperatureFService button / current temperature read out during DHW operation

7Operating codeGReset button

8Flashes to indicate fault

Once the preceding actions have been carried out, the apliance may be started up.

104. Press the button , to start the appliance.The heat exchanger is heated up and the service display will show 3., 4 and 7 (depending on the status of the DHW disabling switch and/or Open Therm regulation)

105. Adjust the pump setting depending on the maximum power set and the resistance in the CH installation. For the water head of the pump and the pressure loss of the appliance see section 6.5.

106. Set the room thermostat higher than the room temperature. The appliance will now switch to CH operation: 5 will show on the display.

107. Heat the installation an dthe appliance to apporximately 80C.

108. Check the temperature difference between the supply and return for the appliance and the radiators. This must be approximately 20C. For this purpose set the maximum power on the service panel. See seting maximum power. If necessary adjust the pump setting and/or the radiator valves. The minimum flow is:

155 l/h at a power setting of 5.4 kW

510 l/h at a power setting of 17,8 kW

109. Switch the appliance off..

110. Bleed the appliance and the installation after cooling. (if necessary top up.)

111. Check correct operation of the heating and hot water supply.

112. Instruct the user on filling, bleeding and the operation of the heating and hot water supply.

Notes

The appliance is equipped with an electronic burner manager, which ingites the burner and continuously monitors the flame during each request for heat from the heating or from the hot water supply.

The circulation pump starts running in response to every request for heat from the heating. The pump continues running for 1 minute after heating. This post purge period can be changed if desired.(See section 6.3.)

The pump runs automatically for 10 seconds every 24 hours in order to prevent seizing. This will occur at the the time of the last request for heat. To change this time the room thermostat should be turned up briefly at het desired time.

The pump does not run during DHW operation.

5.3 Shutting down

CAUTION

Drain the appliance and the installation if mains power has been interrupted and ther is apossibility of freezing.

113. Drain the appliance at het filling/drain tap.

114. Drain the installation at the lowest point.

115. Close the main cock for the water supply to the DHW section.

116. Drain the appliance by removing the DHW couplings below the appliance.

5.3.1 Frost protection

To avoid freezing of the condensate drain pipe the appliance must be installed in a frost-free area.

To avoid freezing of the appliance it is equipped with frost protection. If the temperature of the geat exchanger becomes too low, the burner switches on until the temperature of the heat exchanger is sufficient. If there is a possibility of the installation (or part of it) freezing, an (external) frost thermostat must be installed at the coldest point of the return pipe. This must be connected in accordance with the wiring diagram. (See section 9.1.)

Note

If an (external) frost thermostat has been fittted to the installation and connected to the appliance, this will not be active when the appliance is switched off at the operating panel ( - on service display).6 Setting and adjustment

The functioning of the appliance is determined primarily by the (parameter) settings in the burner manager. Part of this can be set directly via the operating panel; another part can only be adjusted using the installer code.

6.1 Directly via the operating panel

The following functions can be operated directly:

Appliance on/off

The appliance is started using the key.

When the appliance is in operation the green LED above the key will light up. When the appliance is off a singe dash lights up on the service display ( - ) to indicate that supply voltage is present. In this operating mode the pressure in the CH installation (in bar) can also be read on the temperature display.

DHW comfort

The DHW comfort function can be operated with the DHW comfort key and has the following settings:

On: ( LED on) The appliances DHW comfort function is switched on continuously. Th eheat exchanger is kept continuoulsy hot. The appliance always delivershot water immediately.

Eco: ( LED on) The appliances DHW comfort function is self-learning. The appliance will adapt to the pattern of use of hot tap water. As a result, the temperature of the heat exchanger will not be maintained during the night or in the case of long absence. Uit: (Both LEDs off.) The temperature of the heat exchanger is not maintained, as a result of which the delivery of hot tap water takes a little time. If there is no need for hot tap water or its immediate delivery, the DHW comfort function can be switched off.

Resetting

When a blocking fault is indicated by means of a flashing LED above the key and a figure on the display, the appliance can be restarted by pressing the reset key. Check the nature of the fault on the basis of the fault codes in section 7.1 and resolve the cause of the fault if possible before resetting the appliance.

Changing the settings of the various functions:

Holding the key pressed in for 2 seconds takes you to the user settings menu(LED at and the figure display start to flash). Pressing the key repeatedly results in a different function LED flashing each time. When the LED is flashing th eindicated function can be set with the and key . The value set is shown on the display.

The on/off key closes the settings menu without storing the changes.

The reset key closes the settings menu and the changes are stored.

If no key is pressed during a period of 30 seconds, the settings menu is closed automatically and the changes are stored.

Maximum CH supply temperature

Press the key until the LED at starts to flash.

With the and key s set the temperature between 30C and 90C (default value 80C).

DHW temperature

Press the key until the LED at starts to flash.

With the and keys set the temperature between 40C and 65C (default value 60C).

Eco comfort memory days

The number of days with a non-standard DHW usage pattern that is filtered out of the memory can be set.

Press the key until the LED at starts to flash.

With the and keys set the number of non-standard days between 1 and 10 (default value 3).

Comfort mode temperature

When the DHW comfort function is switched on (On or Eco) the temperature of the heat exchanger is maintained. This can be set.

Press the key until the LED at starts to flash.

With the and keys set the temperature between 40C and 65C (default value 57C).

6.2 Settting via the service code

The burner manager in the appliance is factory set in accordance with the parameters in section 6.3.

These parameters can only be changed using the service code. Proceed as follows to activate the program memory:

117. Press the and keys simultanously until a 0 appears on the service- and temperature display.

118. Using the and keys set 15 (service code) on the temperature display.

119. Using the key set the parameter to be set on the service display.

120. Using the and keys set the paramter to the desired value (visible) on the temperature display.

121. Once all desired changes have been entered, press the key until a P appears on the service display.

The burner manager has now been reprogrammed.

NotePressing the key in takes you out of the menu without storing the parameter changes.

6.3 Parameters

ParaKombi Kompakt HRE

meterSetting24/18defaultDescription

0Servicecode [15]--Access to installer settings. The service code must be entered (=15).

1Installation type000=Kombi-Kompakt He

1=Kompakt Solo HE + boiler

2=Kompakt Tap HE

3=Kompakt Solo HE

2CH-pomp continuous000=only post purge period

1=pump continuously active

2=pump continuously active with MIT-switch

3Maximum CH power set7070Adjustment range of set value parameter c up to 85%

4Maximum DHW power set9999Adjustment range of set valeu parameter d up to 99%

5Min. Supply temperature of the heating line2525Adjustment range 10C to 25C

6Min. outside temperature of the heating line-7-7Adjustment range -9C to 10C

7Max. outside temperature of the heating line2525Adjustment range 15C to 30C

8CH pump post purge period11Adjustment range 0 to 15 minutes

9CH pump post purge period after DHW operation11Adjustment range 0 to 15 minutes (N/A. for Kombi appliance)

APosition of three-way valve or MIT valve000=actuated during CH operation

1=actuated during DHW operation

bBooster100=off

1=on

CStep modulation110=step modulation off during CH operation

1=step modulation on during CH operation

cMinimal CH rpm 4040Adjustment range 25 to 50 % (40=propane)

dMinimal DHW rpm3030Adjustment range 25 to 50%. (40=propane)

EMin. Supply temperature during OT demand

(OT = OpenTherm thermostat)4040Adjustment range 10C tot 60C

E .OT response110=ignore OT if < E

1=limit OT if < E

2=OT on-off

FStart rpm7070Adjustment range 50 to 99% of the set maximum rpm.

H

Max.fan rpm4545Adjustment range 40 to 50. (40=4000rpm, 50=5000rpm) with this parameter the maximum rpm can be set.

nSetpoint CH during DHW operation (Ta)7575Adjustment range 60C to 90C

oWaiting time after a DHW demand before a CH demand is answered00Adjustment range 0 to 15 minutes

PAnti-hunting period during CH operation55Minimal switch-off time in CH operation

Adjustable from 0 to 15 minutes

6.4 Setting maximum CH power

The maximum CH power is set at 70% in the factory. If more or less power is necessary for the CH installation, the maximum CH power can be changed by changing the fan rpm. See table Setting CH power.

This table shows the relationship between the fan rpm and the appliance power.

Setting CH power

Desired CH power

(in kW (aproxx.))Setting on service display

(in % of max. rpm)

Kombi Kompakt HRE

24/18

17.885

16,980

14,870

12,760

10,650

8,540

6,430

5.425

NB

The power during burning is increased slowly and is reduced as soon as the set supply temperature is reached (modulatie on Ta).

6.5 Adjusting pump setting

The switch for adjusting the pump setting is located on the CH pump connection box. (Factory setting III)

122. Adjust the pump setting depending on the maximum power set an the water resistance of the installation. See diagram: pressure loss of appliance and pump water head, positions I, II and III.

123. Check the temperature difference between the appliance supply and return: this must be approximately 20C bedragen.

The minimum flow quantityPower setting

155 l/h5.4 kW

510 l/h17,8 kW

Appliance pressure loss graph, CH side

A.Kombi Kompakt HRE 24/18 IPump setting IIIPump setting IIIIIPump setting IIIXFlow in l/hYPressure loss / water head in mH2O

6.6 Weatherdependent adjustment

When an external sensor is connected the supply temperature is adjusted automatically depending on the outside temperature, in accordance with the heating line set.

The maximum supply temperature (Tmax) is set via the temperature display. If desired, the heating line can be changed with the service code. See section 6.3.

Heating line graph

X.Outside T in CY.Supply T in C

A.Factory setting

(Tmax CH = 80C, Tmin CH=25C, Tmin out=-7C, Tmax out= 25C)

B.Example

(Tmax CH = 60C, Tmin CH=25C, Tmin out=-7C, Tmax out= 25C)

6.7 Conversion to different gas type

CAUTION

Work on gas carrying parts may only be carried out by an authorised installer.

If a different type of gas is connected to the appliance than that for which the appliance has been set by the manufacturer, the gas metering ring should be replaced. Conversion sets for other types of gas are available to order.

Converting the metering ring

124. Switch the boiler off and remove the plug from the mains socket.

125. Close the gas tap.

126. Remove the front panel from the appliance.

127. Unscrew the coupling (A) above the gas block and twist the gas mixing rube towards the rear (B).

128. Replace the O-ring (C) and the gas metering ring (D) with the rings from th econversion set.

129. Re-assemble in reverse sequence.

130. Open the gas tap.

131. Check the gas connections before the gas block for gas-tightness.

132. Insert the plug back into the wall socket and switch the boiler on.

133. Check the gas connections after the gas block for gas-tightness(during operation).

134. Now check the setting of the gas/air ratio. (See section 6.9 )

135. Place a sticker for the gas type set over the existing sticker next to the gas block.

136. Place a sticker for the gas type set next to the identification plate.

137. Fit the appliance front panel.

6.8 Gas-/air adjustment

The gas-/air adjustment has been set in the factory and in principle requires no adjustments.

The setting can be checked by measuring the CO2 percentage in the combusion gases or by measurement of the pressure difference.

In the case of possible disturbance of the adjustment, replacement of the gas block or conversion to another gas type the adjustment must be checked and if necessary set in accordance with the table below.

GastypeNatural gas LPropane P

Gas category2L

G25

25mBar3P G31(propaan)

29mBar

CO2% at low setting (L) ( and )

With opened casing9,0 0,29,5 0,2

CO2% at high setting(H) ( and 2x)

With opened casing9,1 0,510,0 0,5

Gas supply pressure (mBar)20-30 25-35

gas metering ring (mm)6,954.90

Minimum rpm (% of max) (parameter d)2540

Min. start rpm (% of max) (parameter F)7050

6.9 Setting gas / air adjustment

Setting by measurement of the CO2 content of the combustion gases

Note

A CO2 measurement nipple must have been fitted or must now be fitted in the flue pipe.

A. Cover screw (slotted or torx T15)

B. Adjusting screw for low position ( 4 mm socket screw key or torx T15)

C. Offset pressure measurement nipple

D. Gas supply pressure measurement nipple

138. Switch the appliance off with the on/off key. ( - on service display).

139. Unscrew the CO2 measuring nipple and connect the measuring hose.

140. Switch the appliance on with the on/off key.

141. Adjust the appliance to the lowest power by simultaneously pressing the keys and and on the operating panel until an L. appears on the display.

142. Measrue the CO2 value. If the CO2 value does not correspond with the in the table in section 6.8 proceed with setting as follows:

143. Remove the front panel from the apppliance..

144. Remove the cover cap (A).

145. Adjust the set screw (B) to the correct CO2 value (clockwise higher and anti-clockwise lower).

146. After measurement and setting replace the cover cap (A) and close the CO2 measurement nipple.

147. Press simultaneously on the and keys to leave the test program.

148. Fit the front panel to the appliance.

NB

Check that the measurement nipples used are gas-tight.Adjusting of gas block by means of pressure measurement:

This method is less accurate but generally gives an adequate result..

149. Switch the appliance off with the on/off key ( - on service display ).

150. Remove the front panel from the appliance.

151. Open the measurement nipple (C) on the gas block 2 turns and connect it by means of a hose to the plus connection of the pressure meter.

152. Turn the appliance on with the on/off key.

153. Set the appliance to the lowest power by pressing simultaneously on the and of the operating panel until an L. appears.

154. Read the pressure, which must be approximately -5Pa (-0,05mBar) (min.10Pa, max.0Pa. (min.0,1mBar max.0mBar)). If this is not the case proceed with adjustment as follows:

155. Remove the cover cap (A).

156. With adjusting screw (B) adjust the pressure (clockwise higher and anti-clockwise lower).

157. After measurement and adjustment replace the cover cap (A) and close the measurement nipple (C).

158. Press the and keys simultaneously to leave the test program.

159. Fit the front panel to the appliance.

NB

Check that the measurement nipples used are gas-tight.

7 FAults

7.1 Fault codes

If the fault LED is flashing, the burner manager has detected a fault. A fault code will be indicated on the temperature display.

Once the fault has been rectified the burner manager can be restarted:

Press the reset key on the operating panel.

The following faults are distinguished

Temperatuur displayOmschrijvingMogelijke oorzaak/oplossing

10, 11, 12, 13, 14Sensor fault S1Check wiring for break

Replace S1

20, 21, 22, 23, 24Sensor fault S2Check wiring for break

Replace S2

0Sensor fault after self checkReplace S1 and/or S2

1Temperature too highAir in installation

Pump not running

Too little flow in installation, radiators closed, pump setting too

Flow switch sticking

2S1 and S2 interchangedCheck cable loom

Replace S1 or S2

4No flame signalGas tap closed

No or incorrect ignition gap

Gas supply pressure too low of failling

Gas block or ignition unit not receiving current

5Poor flame signalCondensate drain blocked

Check adjustment of gas block

6Flame detection faultReplace ignition cable + spark plug cap

Replace ignition unit

Replace burner manager

8Incorrect fan speedFan catching on casing

Wiring between fan and casing

Check wiring for poor wire contact

Replace fan

29,30Gas valve relay faultyReplace burner manager

7.2 Other faults

7.2.1 Burner does not ignite

Possible causes:Oplossing:

Gas tap is closed.Ja Open gas tap.

Nee

Air in the gas pipe.Ja Remove air form gas pipe.

Nee

Gas supply pressure to low.Ja Contct the gas company.

Nee

No ignition.Ja Replace ignition pin.

Nee

No spark. Ignition unit on gas block faulty.Ja Check the cabling. Check the spark plug cap. Replace the ignition unit.

Nee

Gas/air adjustment not correctly set.Ja Check adjustment. See gas/air adjustment

Nee

Fan faultyJa Check the wiring. Check the fuse , if necessary, replace the fan.

Nee

Fan dirty.Ja Clean the fan

Nee

Gas block faulty.Ja Replace the gas block. Re-adjust the gas block, see gas/air adjustment

7.2.2 Burner ignites noisily

Possible causes:Solution:

Gas supply pressure to high.Ja The house pressure switch may be faulty.Contact the gas company

Nee

Incorrect ignition gap.Ja Replace the ignition pin

Check the ignition pin gap.

Nee

Gas/air adjustment not correctly set.Ja Check the setting. See gas/air adjustment.

Nee

Weak spark.Ja Check the ignition gap.

Replace the ignition pin.

Replace the ignition unit on the gas block.

7.2.3 Burner resonating

Possible causes:Solution:

Gas supply pressure to lowJa The house pressure switch may be faulty. Contact the gas company.

Nee

Recirculation of combustion gasses.Ja Check the gas flue an the air supply.

Nee

Gas/air adjustment not correctly set.Ja Check the setting, see gas/air adjustment.

7.2.4 No heating (CH)

Possible causes:Solution:

Room thermostat / weather-dependent adjustment not closed or faulty.Ja Check the wiring.

Replace the thermostat.

Replace the weather-dependant adjustment.

Nee

No current (24 V).Ja Check the wiring against the diagram.

Check the connector X4.

Replace the faulty manager.

Nee

Pump not running.Ja Check the power supply.

Check connector X2.

Replace faulty pump.

Replace faulty manager.

Nee

Burner not firing on CH: sensor S1 or S2 faulty.Ja Replace sensor S1 or S2. See fault code, temperature display: 1 or 2.

Nee

Burner does not ignite.Ja See burner does not ignite.

7.2.5 The power is reduced

Possible causes:Solution:

At high rpm the power has fallen by more than 5%.Ja Check appliance and flue system for fouling.

Clean the appliance and flue system.

7.2.6 CH does not reach temperature

Possible causes:Solution:

Room thermostat setting incorrect.Ja Check the settting and if necessary adjust: Set to 0.1A.

Nee

Temperature is too low.Ja Increase the CH temperature. See Operating CH . Check esternal sensor for short-circuiting. Rectify.

Nee

Pump not running correctly. Pump setting is too low.Ja Increase pump setting, or replace the pump.

Nee

No circulation in the installation.Ja Check whether there is circulation: at least 2 or 3 radiators must be open

Nee

The boiler power has not been correctly set for the installation.Ja Adjust the power. See setting maximum CH power.

Nee

No heat transfer as a result of lime scale or fouling in the heat exchanger.Ja Descale or flush the heat exchanger on the CH side.

7.2.7 No hot water (DHW)

Possible causes:Solution:

Flow switch not switching.Ja DHW flow < 2.0 l/min.

Replace the flow switch.

Nee

No current at the flow switch (5V DC).Ja Check the wiring according to the diagram.

Nee

Burner not firing on DHW: S3 faulty.Ja Replace S3.

Nee

Burner does not igniteJa See burner does not ignite.

7.2.8 Hot water does not reach temperature

Possible causes:Solution:

DHW flow higher than 9 l/min.Ja Adjust the inlet assembly.

Nee

Temperature setting for water circuit too low.Ja Set the hot water circuit, depending on the desired temperature.

Nee

No heat transfer as a result of lime scale or fouling in the heat exchanger DHW side.Ja Descale or flush the exchanger DHW side.

Nee

Cold water temperature 10C.

8 Maintenance

The appliance and the installation should be checked and if necessary cleaned every year by a registered expert.

CAUTION

Work on gas-carrying parts may only be carried out by an authorised installer.

When the appliance has just been operating parts may be hot.

8.1.1 Disassembly

160. Switch the appliance off with the key.

161. Remove the plug from the wall socket.

162. Close the gas tap.

163. Open the display cover and turn the two screws on the left- and right-hand side of the display and remove the front panel.

164. Wait until the appliance has cooled down.

165. Unscrew the coupling nut at the base of the flue pipe anti-clockwise.

166. Slide the flue pipe upwards (1) turning it anti-clockwise until the bottom of the pipe is above the condensate drain pan connection.Pull the bottom of the pipe forwards (2) and remove the pipe downwards (3) turning it anti-clockwise.

167. Lift the condensate drain pan on the left-hand side from the connection to the siphon (4) and turn it to the right with the siphon connection over the edge of the base tray (5). Push the back of the condensate drain pan downward from the connection to the heat exchanger (6) and remove it from the appliance..

168. Remove the connector from the fan and the ignition unit from the gas block.

169. Unscrew the coupling below the gas block.

170. Unscrew the socket head screws from the front cover and remove this complete with gas block and fan to the front. (NB ensure that the burner, insulation plate, gas block, gas supply and fan do not get damaged.)

171. Remove the stem strips positioned crossways in the heat exchanger plates.

8.1.2 Cleaning

172. Clean the stem strips and plates of the heat exchanger from top to bottom with a brush or compressed air..

173. Clean the underside of the heat exchanger.

174. Clean the condensate drain pan with water.

Clean the siphon with water. (if necessary, the side branch on the siphon may be sawn off.)

8.1.3 Assembly

When fitting the various seals check for damage, hardening, tears or hairline tears and/or discoloration. Where necessary fit a new seal. Also check whether seals ar still correctly positioned.

Failure to fit the sensors S1 and/or S2, or the stem strips, or to fit them correctly, can result in serious damage.

175. Fit the stem strips in the heat exchanger..

176. Check that the seal around the front cover is correctly installed. Place the front cover on the heat exchanger and secure it using the socket head screws plus serrated lock washers. Tighten the socket head screws equally hand-tight, working crosswise.

177. Fit the gas connecion below the gas block.

178. Fit the connector to the fan and the ignition unit to the gas block.

179. Fit the condensate drain by sliding t on to the exchanger outlet stump (1) with the siphon connection still inf ont of the base tray. Then turn it to the left (2) and push it downwards into the siphon connection (3). Make sure in doing this that the back of the ondensate drain pan comes to rest on the lug at the back of the base tray (A).

180. Fill the siphon with water and fit it to the connection below the condensate drain pan.

181. Slide the flue pipe, turning it anti-clockwise, with the top around the flue adapter, into the top cover. Insert the bottom into the condensate drain pan and tighten the coupling nut clockwise..

182. Open the gas tap and check the gas connections below the gas block and on the mounting bracket for leakage.

183. Check the CH and the water pipes for leakage..

184. Insert the plug into the wall socket..

185. Switch the appliance on with the key.

186. Check the font cover, the fan connection on the front cover and the flue pipe components for leakage.

187. Check the gas/air adjustment. (See section 6.9.)

188. Fit the casing, tighten the two screws left and right of the display and close the display cover.

189. Check the geating and the got water supply

9 Technical specifications

Appliance categoryC13; C 33; C 43; C53; C63; C83

Gas supply pressure20 - 30 mbar

Suitable for gas typeII2L3P

Technical dataKombi Kompakt HRE

24/18Kombi Kompakt HRE

28/24Kombi Kompakt HRE

36/30

DHW

Nom. Power rating lower valuekW5,6 22,17.1 28.07.2 32.7

Rated power*kW6,1 21,0 7.8 27.08.0 31.5

DHW thresholdl/min22.02.0

DHW flow 60C l/min67.59.0

DHW flow 40C (gemengd)l/min1012.515,0

DHW temperatureC606060

Effective appliance waiting time*sec< 1< 1< 1

DHW-side pressure loss kPaZie 5.2 Zie 5.2 Zie 5.2

CH

Nom. Power rating lower value**kW5,6 18,7 7.1 23.77.2 27.3

Rated power at 80/60C**kW5,4 17,8 6.9 22.87.1 26.3

Rated power at 50/30C**kW5,9 18,5 7.6 - 23.4 7.8 27.1

Max. CH-water pressurebar33,03,0

Max. CH-water temperatureC909090

Other data

Gas consumption (G20)m3/h0,59 2,300,75 2.900.75 - 3.40

Appliance pressure loss (CH)mWkSee section 6.5See section 6.5See section 6.5

Elektrical data

Mains powerV230230230

Safety classIPIP20 IP20 IP20

Power consumption : full loadW105105105

Power consumption: partial loadW404040

Power consumption: stanbyW2,42,42,4

Boiler dimensions and weight

Heightmm590650710

Widthmm450450450

Depthmm240240240

Weightkg303336

* Time required from start of drawing water to achieve a temperature increase of 40K at the DHW outlet of the appliance, based on the CW (Comfort hot water) DHW flow.

**The maximum CH power is factory set at 70% of the highest value. (See section 6.4 Setting maximum CH power).

9.1 Electrical diagram

9.2 NTC resistances

NTC 12kOhm

T [C]R[ohm]T [C]R[ohm]T [C]R[ohm]

-15760202512000652752

-1058880309805702337

-545950358055751994

036130406653801707

528600455522851467

1022800504609901266

1518300553863951096

2014770603253100952

10 Warranty provisions

With due regard for the conditions indicated below Intergas Heating BV guarantees to the registered installer the soundness of the materials used, as well as the effective operation of its Central Heating products, when used for the purpose for which they are supplied. As the case arises we should be given the opportunity where necessary to ascertain in situ the soundness of the warranty claim.

The warranty comprises:

The warranty is limited to re-supplying free of charge the parts that entirely in our judgement display material or manufacturing faults during the warranty period, which are not the result of normal wear etc. Such parts should be sent to us carriage paid with an indication of the defect and after replacement will become our property.

190. The warranty period on parts is 2 years, calculated from the date of installation. However, the following parts are excluded from warranty: ignition and ionisation pin, glass fuse, thermocouple and air bleed

191. The warranty period on the sealing of the appliance heat exchanger is 15 years provided, however, that, if in our view locally unavoidable leakages occur as a result of corrosion, we supply solely this boiler component on the basis of reimbursement of old for new calculated from the date of installation at the time of replacement: the first 5 years free, the 6th year 10%, the 7th year 20%, and so on up to the 14th year 90% of the current price of the boiler part to be replaced.

192. The warranty ceases to apply if it is determined that the defects, damage or excessive wear are attributable to improper use or injudicious handling or inexpert repair, adjustment, installation or maintenance, by unauthorised installers or to exposure to substances containing aggressive chemicals (including hair lacquer) and other harmful substances.

193. The warranty also ceases to apply if pipes and couplings have been used in the installation which can cause oxygen diffusion or if the defect is the result of boiler scale deposits (harmful to the appliance and the installation).Surface damage and transport damage are not covered by the warranty. The right to warranty lapses if it cannot be demonstrated that, following commissioning, the central heating boiler or central heating stove has been subjected to a service at least once a year by an installer authorised for that purpose by or on behalf of the gas company. The installation and operating instructions that we issue for the appliances and stoves concerned should be fully adhered to.

194. The manufacturers liability under the agreement is expressly limited to fulfilment of the warranty obligations described in this article. Any claim for compensation with the exception of those relating to non-fulfilment of the warranty obligations is excluded. With due regard for the mandatory legal provisions regarding liability and product liability, no rights may ever be derived with regard to any consequential loss, purely final loss or any loss whatsoever arising from defects in materials supplied or work undertaken by the manufacturer. Furthermore all offers of and agreements regarding products to be supplied and/or services to be provided by us are subject to the general conditions of delivery for the metal and electrical engineering industry, filed by the Dutch Vereniging F.M.E.-C.W.M. on 18 October 1998 with the registry of the district court of The Hague (number 119/1998). A copy of these conditions will be sent free of charge on request. Other conditions are expressly rejected.

195. The warranty is applicable solely if the appendix to the warranty certificate has been signed by the purchaser and returned to us within 8 days following installation. By signing the warranty card the purchaser declares that he/she is in agreement with the sound condition of that which has been delivered.

196. If the installers business ceases operations before expiry of the warranty period, the user may have recourse to our warranty obligations to the installer.

Use as intended.

The appliance, as described in this documentation, is intended for heating rooms via a central heating installation and/or for supplying hot water. Any other use lies outside the intended use of the appliance. No liability can be accepted for loss or damage arising from incorrect use.

11 CE- Verklaring

Declaration of conformity in accordance with ISO IEC GUIDE 22.

ManufacturerIntergas Verwarming BV

AddressHolwert 1, 7741 KC COEVORDEN

Hereby declares that the CH appliances:

Kombi Kompakt HRE 24/18

Kombi Kompakt HRE 28/24

Kombi Kompakt HRE 36/30

Meets the provisions of the following directives:

Machinery Directive (89/392/EEC) as amended in Directive (93/68/EEC)

Low Voltage Directive (73/23/EEC) as amended in Directive (93/68/EEC)

Gas Appliances Directive (90/396/EEC)

Boiler Efficiency Directive for new oil- and gas-fired central heating boilers (92/42/EEC)

EMC Directive (89/336/EEC) as last amended in (93/68/EEC).

Coevorden, juni 2006

H. Bosscher DirecteurIntergas Verwarming BV

88234703.doc

De Holwert 1

Postbus 6

7740 AA Coevorden

Tel: 0524-512345

Fax: 0524-516868

www.intergasverwarming.nl

Intergas Verwarming BV47Intergas Verwarming BV 2Intergas Verwarming BV3

_1160465929.doc

_1156932065.doc