NYC Department of Education Building Condition Assessment Survey 2018-2019 X338 Architectural Inspection Inspection Type Last Edited Time In InspectionId MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR MARTIN LUTHER KING JR BLVD, BRONX, NY, 10453 School: 2844 2019-03-07 07:11AM 2019-06-27 10:15AM ARCHITECTURAL - ASSOCIATE 2923 2019-03-07 07:33AM 2019-03-26 03:26PM ARCHITECTURAL - SENIOR Asset Data Question Answer Was the Building Fully Accessible for Inspection? Yes Principal(s) Information Principal Name Amanda Blatter Principal Organization P.S. 204 - Bronx Meeting with Principal? Yes Principal Feedback The Principal provided the following comments: 1- All spaces are either too hot or too cold and the climate controls need adjusting or replacement. 2- The BMS system is not reliable and this needs to be addressed. Principal Name Shante Chunn Principal Organization X723 SPED - Bronx Meeting with Principal? No Principal Feedback The Unit Coordinator provided the information on the Questionnaire on behalf of the Principal, and provided the following comment; The Walls throughout the school are tarnished and needs to be repainted. Custodian Was not present Fireman Christian Perez Building Square Footage 98,000 Comments on the Area (Square Feet) None Comments on the Stories (Floors) plus Basements 4+B+ PH Comments on the Year Built 2010 Comments on the Student Population 628 Comments on the Staff Population 112 Comments on the Number of Classrooms 33 Weather Fair Facade Photo Corner of University Avenue and Macombs Road - West View Page 1 of 19 Print Date: 7/3/2019 Mobile Validity Version 2.0 (P)

Upload: others

Post on 17-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Inspection Type Last EditedTime InInspectionId

MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR MARTIN LUTHER KING JR BLVD, BRONX, NY, 10453School:

2844 2019-03-07 07:11AM 2019-06-27 10:15AMARCHITECTURAL - ASSOCIATE

2923 2019-03-07 07:33AM 2019-03-26 03:26PMARCHITECTURAL - SENIOR

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? Yes

Principal(s) Information

Principal Name Amanda Blatter

Principal Organization P.S. 204 - Bronx

Meeting with Principal? Yes

Principal Feedback The Principal provided the following comments:

1- All spaces are either too hot or too cold and the climate

controls need adjusting or replacement.

2- The BMS system is not reliable and this needs to be addressed.

Principal Name Shante Chunn

Principal Organization X723 SPED - Bronx

Meeting with Principal? No

Principal Feedback The Unit Coordinator provided the information on the

Questionnaire on behalf of the Principal, and provided the

following comment; The Walls throughout the school are

tarnished and needs to be repainted.

Custodian Was not present

Fireman Christian Perez

Building Square Footage 98,000

Comments on the Area (Square Feet) None

Comments on the Stories (Floors) plus Basements 4+B+ PH

Comments on the Year Built 2010

Comments on the Student Population 628

Comments on the Staff Population 112

Comments on the Number of Classrooms 33

Weather Fair

Facade Photo

Corner of University Avenue and Macombs Road - West View

Page 1 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 2: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural InspectionMain Entrance Photo

Facade A - University Ave

Roof Photo

Roof - Northeast View

No System UpgradedHave any Systems/Major Building Components been upgraded?

Have there been any New Building Additions? No New Construction

Tandem No Tandem

Leased Space? No

Priority ConditionExist

Last Year?

Priority

Category

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Structural Engineer Required

Structural

Condition Type

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Accessibility

Accessibility Status Question Response

Physical Breakdown Structure Exists Complies Required Deficiency

FUNCTIONAL ACCESSIBILITY

Exterior Routes

YesExterior Entrances & Exits

NoNoExterior H/C Lifts

NoYesExterior Ramps and Railings

Interior Routes

Page 2 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 3: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Physical Breakdown Structure Exists Complies Required Deficiency

NoNoCorridor and Lobby H/C Lifts

NoYesInterior Corridor Doors And Hardware

YesInterior Corridors & Lobbies

YesYesInterior Elevators

YesInterior Lobby Doors And Hardware

NoInterior Ramps

Rooms & Spaces

NoArt Rooms

Auditorium

Yes Yes1st Floor

Cafeteria

Yes YesBasement

Classrooms

Yes Yes1st to 4th Floors

NoComputer Rooms

Gymnasium

Yes Yes3rd Floor

Library

Yes YesRoom 426

Main Office

Yes YesRooms 101 ( P723X @ P338X) and 124

( P.S. 204)

NoMulti-purpose Room

Nurse's Office

Yes YesRoom 227

NoPool

Science Lab

Yes YesRoom 401 and 405,

Toilet Rooms (boys)

Yes YesBasement to 4th Floors

Toilet Rooms (girls)

Yes YesBasement to 4th Floors

Toilet Rooms (staff)

Yes YesBasement to 4th Floors

Page 3 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 4: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Building Template

Inspection

Question Response

Architectural

ATHLETIC FIELDS Does not exist

EXTERIOR Inspected

InspectedAREAWAY

Instance on AW1 Inspected

2- Between Good and FairInstance Condition

Instance Quantity 1

Instance Quantity Uom EACH

No deficiencies recordedDeficiency

Does not existAWNINGS AND CANOPIES

Does not existCHIMNEY

InspectedCOPING

Condition 3- Fair

CAST STONE:OPEN TRANSVERSE JOINTS WITH

DAMAGED CAULKING

Deficiency

Deficiency Location/Instance

90Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 4 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 5: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

EXTERIOR

COPING

Deficiency Photo 1

Facade B

Violations No violations recorded

Does not existCORNICE

InspectedDOORS

InspectedDOOR HARDWARE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDOORS AND FRAMES

Condition 3- Fair

METAL CLAD:DETERIORATED DOOR AND FRAME -

MINOR DETERIORATION

Deficiency

Deficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Door B01 shown, similar condition at Exit 6

Violations No violations recorded

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTRANSOM/SIDE LIGHT

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedEXTERIOR SOFFITS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedEXTERIOR WALLS

Masonry, OtherMaterial Type(s)

27,000Replacement Quantity

Page 5 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 6: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Replacement Uom S.F.

Instance on All Facades Inspected

2- Between Good and FairInstance Condition

Instance Quantity 27,000

Instance Quantity Uom S.F.

BRICK:MINOR CRACKS AND SPALLINGDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facade A, B, C

40Deficiency Quantity

Quantity Uom S.F.

Potential Action RESTITCH

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade C

Violations No violations recorded

BRICK:OPEN JOINTSDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facade A

250Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

Page 6 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 7: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

Does not existLOADING DOCK

InspectedLOUVER

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedPARAPETS

Masonry, OtherMaterial Type(s)

2,900Replacement Quantity

Replacement Uom C.F.

Instance on All Facades Inspected

2- Between Good and FairInstance Condition

Instance Quantity 2,900

Instance Quantity Uom CF

No deficiencies recordedDeficiency

Does not existPLAZA DECK

InspectedROOF

InspectedROOFING

Replacement Quantity 20,000

Replacement Uom S.F.

InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existROOF BARRIER

Does not existROOF CAGE

Does not existROOF FENCE

InspectedROOF HATCH/SMOKE HATCH

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedROOFING

Instance on IRMA:All Roofs Inspected

2- Between Good and FairInstance Condition

Instance Quantity 20,000

Instance Quantity Uom S.F.

“Does the roof have major mechanical equipment sitting on Dunnage

Steel less than 18" above the Roofing?"

No

Installation Year 2010

Source of Installation Year Documented

IRMA:ROOFING:MAJOR ACTIVE ROOF LEAKS IN

INSTRUCTIONAL SPACE

Deficiency

Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENT

REMOVAL

PRIORITY 5Urgency of Action

Page 7 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 8: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor near Room 426

Violations No violations recorded

InspectedROOFING DRAINS

2- Between Good and FairCondition

DETERIORATEDDeficiency

Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1 - Facade I

Violations No violations recorded

InspectedSPECIALTIES

InspectedBULKHEAD/PENTHOUSE

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existCUPOLA/ SPIRES/ TOWERS

Does not existDORMER

Does not existDUNNAGE STEEL

Does not existROOF/GRAVITY TANK

Does not existSKYLIGHT/ROOF VENT

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedBUILDING CHEEK/FLANK WALLS

Condition 3- Fair

CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency

Page 8 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 9: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade G

Violations No violations recorded

InspectedRAILINGS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedSTAIRS/RAMPS

Condition 2- Between Good and Fair

CONCRETE:CRACKS/SPALLING - MINORDeficiency

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Ramp

Violations No violations recorded

InspectedWINDOWS

13,000Replacement Quantity

Replacement Uom S.F.

Page 9 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 10: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

EXTERIOR

WINDOWS

InspectedEXTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWINDOWS

Material Type(s) Aluminum, Other

Instance on Aluminum - Other:All Facades Inspected

2- Between Good and FairInstance Condition

Instance Quantity 13,000

Instance Quantity Uom S.F.

Installation Year 2010

Source of Installation Year Documented

No deficiencies recordedDeficiency

INTERIOR Inspected

AUDITORIUM

Instance on 1st Floor (378 Seats) Inspected

Ceiling

Instance on 1st Floor (378 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor (378 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed H/C Lift

Instance on 1st Floor (378 Seats) Does not exist

Fixed Seating

Instance on 1st Floor (378 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 1st Floor (378 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 1st Floor (378 Seats) Does not exist

Stage

Instance on 1st Floor (378 Seats) Inspected

Stage

Instance on 1st Floor (378 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtain Rigging

Instance on 1st Floor (378 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtains

Instance on 1st Floor (378 Seats) Inspected

2- Between Good and FairInstance Condition

Page 10 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 11: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

INTERIOR

AUDITORIUM

Stage

Stage Curtains

No deficiencies recordedDeficiency

Walls

Instance on 1st Floor (378 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 1st Floor (378 Seats) Does not exist

CAFETERIA

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on Basement Does not exist

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on Basement Does not exist

Stage

Instance on Basement Does not exist

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on Basement Does not exist

InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedCeiling

Condition 2- Between Good and Fair

ACOUSTIC TILES:DAMAGED/MISSINGDeficiency

Corridor near Room 426Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 11 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 12: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Deficiency Photo 1

Corridor near Room 426

Violations No violations recorded

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existSpecialties

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

GYMNASIUM

Instance on 3rd Floor Inspected

Ceiling

Instance on 3rd Floor Does not exist

Door(s)

Instance on 3rd Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on 3rd Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 3rd Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Seating

Instance on 3rd Floor Inspected

4- Between Fair and PoorInstance Condition

INOPERABLE BLEACHERSDeficiency

West, East Sides of RoomDeficiency Location/Instance

360Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 12 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 13: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

INTERIOR

GYMNASIUM

Seating

Deficiency Photo 1

West Side of Room

Violations No violations recorded

Sliding-folding Partition

Instance on 3rd Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage

Instance on 3rd Floor Does not exist

Walls

Instance on 3rd Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 3rd Floor Does not exist

InspectedINTERIOR DOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedINTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

KITCHEN

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

LIBRARY

Instance on Room 426 Inspected

Built-in Furnishing

Instance on Room 426 Does not exist

Ceiling

Page 13 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 14: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

INTERIOR

LIBRARY

Ceiling

Instance on Room 426 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Room 426 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Room 426 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on Room 426 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

LOCKER ROOM

Instance on Room 305 - Girls Inspected

YesAlternative Use

Instance on Room 327 - Boys Inspected

YesAlternative Use

Ceiling

Instance on Room 305 - Girls Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 327 - Boys Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Room 305 - Girls Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 327 - Boys Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Room 305 - Girls Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 327 - Boys Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Locker Room Lockers

Instance on Room 305 - Girls Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 327 - Boys Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on Room 305 - Girls Inspected

Page 14 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 15: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

INTERIOR

LOCKER ROOM

Walls

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 327 - Boys Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Does not existMULTI-PURPOSE ROOM

Does not existPOOLS

Does not existSCIENCE DEMO ROOM

SCIENCE LAB

Instance on Room 401 Inspected

YesAlternative Use

Instance on Room 405 Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 401 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 405 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

SCIENCE PREP ROOM

Instance on Room 403 Inspected

YesAlternative Use

Instance on Room 407 Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 403 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 407 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Does not existSHOWER ROOM

InspectedSTAIRS/RAMPS: INTERIOR

Do Letter Stair Signs Exist? 1

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existPartition

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs and Landings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

Page 15 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 16: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls

No deficiencies recordedDeficiency

InspectedSTRUCTURAL

InspectedCOLUMNS/BEAMS/BEARING WALLS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFLOOR STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFOUNDATION WALLS

Material Type(s) Concrete

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedROOF STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existVAULTS-BUNKERS

InspectedTOILET ROOMS - STAFF

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existStalls

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTOILET ROOMS - STUDENTS

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

LIFE SAFETY Inspected

Does not existF.D. HOLDING AREA

Does not existSTEEL STAIRS

SITE Inspected

Page 16 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 17: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

SITE

Does not existCONTAINERIZATION

InspectedDRAINAGE SYSTEM FOR ASPHALT

InspectedCatch Basins/Manhole - Surrounded by Asphalt

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCulverts - Asphalt Covering

Does not existDRAINAGE SYSTEM FOR CONCRETE

Does not existDRAINAGE SYSTEM FOR SOIL

Does not existDRINKING FOUNTAINS

InspectedFENCES

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existIRRIGATION SYSTEM

InspectedPAVING

InspectedDOT Sidewalk

Does not existAsphalt

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existPavers

InspectedSite Sidewalks & Walkways

InspectedAsphalt

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existPavers

InspectedStudent Non-Use

Gravel Exists? No

InspectedAsphalt

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existConcrete

Does not existPavers

InspectedStudent Use

Gravel Exists? No

InspectedAsphalt

4- Between Fair and PoorCondition

CRACKS - MAJORDeficiency

SchoolyardDeficiency Location/Instance

550Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Page 17 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 18: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

SITE

PAVING

Student Use

Asphalt

Schoolyard

Violations No violations recorded

Does not existConcrete

Does not existPavers

InspectedPLAYGROUNDS

Adjacent to Harrison AvenueInstance

Benches

Instance on Adjacent to Harrison Avenue Does not exist

Fence

Instance on Adjacent to Harrison Avenue Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Pavement

Instance on Adjacent to Harrison Avenue Does not exist

Play Equipment

Instance on Adjacent to Harrison Avenue Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Safety Surfacing

Instance on Adjacent to Harrison Avenue Inspected

3- FairInstance Condition

DETERIORATED/MISSINGDeficiency

PlaygroundDeficiency Location/Instance

225Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Playground

Violations No violations recorded

Unpaved Area

Instance on Adjacent to Harrison Avenue Does not exist

Does not existPLAYING SURFACE

InspectedRETAINING WALLS

Condition 2- Between Good and Fair

Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No

No deficiencies recordedDeficiency

Does not existSEATING

Does not existSITE WALLS (NOT RETAINING WALLS)

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedRailings

Condition 2- Between Good and Fair

Page 18 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 19: MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR … · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X338 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X338Architectural Inspection

Question Response

SITE

STAIRS/RAMPS: EXTERIOR

Railings

No deficiencies recordedDeficiency

InspectedSite Cheek/flank Walls

Condition 2- Between Good and Fair

CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency

Near Exit 5Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Exit 5

Violations No violations recorded

InspectedStairs/ramps

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Page 19 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)