mos gb 0802-1 nibe flm 40 031190 nibe flm 40 · flm 40 is intended to be installed with ground...
TRANSCRIPT
LEK
MOS GB 0802-1 NIBE FLM 40031190
INSTALLATION AND MAINTENANCE INSTRUCTIONS
NIBE FLM 40
1NIBE FLM 40
For Home Owners
GeneralConcise product description ________________________ 2
Installation data __________________________________ 2
System descriptionPrinciple of operation ______________________________ 3
System diagram __________________________________ 3
Maintenance routinesCleaning the air filter ______________________________ 4
Cleaning the fan __________________________________ 4
Cleaning the ventilation devices _____________________ 5
Checking the condensation water seal _______________ 5
For the Installer
General points for the installation engineerTransport and storage _____________________________ 6
Handling ________________________________________ 6
Frost protection ___________________________________ 6
Installation _______________________________________ 6
Pipe installationCondensation water hose __________________________ 7
Pressure expansion vessel __________________________ 7
Filling and venting the system _______________________ 7
Output transfer to brine ____________________________ 7
Pipe connection (brine) ____________________________ 8
Electrical installationGeneral _________________________________________ 9
External control of fan and brine pump _______________ 9
Ventilation connectionVentilation flow _________________________________ 10
Exhaust air duct ________________________________ 10
Duct installation ________________________________ 10
Adjustment ____________________________________ 10
Fan diagram ___________________________________ 10
Setting the fan capacity __________________________ 11
Setting the DIP-switches
Commissioning and adjustingPreparations ___________________________________ 12
Starting _______________________________________ 12
Setting the ventilation ___________________________ 12
Commissioning _________________________________ 12
Readjustment __________________________________ 12
Electrical circuit diagramElectrical circuit diagram _________________________ 13
Contents
Component locationsComponent locations ____________________________ 14
List of componentsList of components ______________________________ 15
DimensionsDimensions and setting-out coordinates ____________ 16
Technical specificationsTechnical Data __________________________________ 17
Accessories ____________________________________ 17
Enclosed kit ____________________________________ 17
Dealing with malfunctionsLow or a lack of ventilation _______________________ 18
Helping the circulation pump to start _______________ 18
2 NIBE FLM 40
For Home Owners
Installation dataTo be filled in when the exhaust air module has been installed.
The serial number (95), must always be stated in all correspon-dence with NIBE.
_ _ _ _ _ _ _ _ _ _ _ _ _ _Installation date
Installation engineers
Trim valve, number of turns from bottom position
Fan mode, normal ventilation A B C
Date_______________ Sign___________________________
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, un-less they have been given supervision or instruction concerning use of the appli-ance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Rights to make any design modifications are reserved.
In order to get the ultimate benefit from your FLM 40 you should read through the For Home Owners section in this Installation and Maintenance Instruction.
FLM 40 is an exhaust air module. This means it can utilise the energy in the ventilation air. The energy is used to raise the temperature of the ingoing brine to the heat pump.
FLM 40 is intended to be installed with ground source heat pumps from NIBE in houses or the like.
General
3NIBE FLM 40
For Home Owners
LEK
System diagramThe air from the kitchen fan goes directly out into a sepa-rate duct.
NK
Köldbärare ut
Värme, retur
Värme, fram
KVVV
EXP
P
SF
FIGHTER 1220
FLM 40
Frånluft Ø 160
Avluft Ø 160
FIGHTER 1220
FLM 40
Abluft Ø 160
Fortluft Ø 160
Köldbärare ut
Mark-/bergvärmepump
FX 110
Frånluft Ø 160
Avluft Ø 160
Wärmequellen-Eintritt
Wärmequellen-Austritt
Brine in
Brine out
FIGHTER 1220
FLM 40
Exhaust airØ 160
Extract airØ 160
Köldbärare in
Köldbärare in
The fan in FLM 40 can be set to three modes, A, B or C. One of these is used as the normal mode depending on the selected exhaust air flow. If mode B is used as the normal mode, it is possible to obtain greater ventila-tion by using mode C. In the same way, A can be used to temporarily obtain lesser ventilation.
If mode C is used as the normal mode, it is only possible to obtain lesser ventilation, in two steps, A or B.
Principle of operation
System description
Brine in
Brine out
Extract air Exhaust air
FIGHTER 1240/1250
When the room air has passed through the exhaust air mo-dule it is discharged. The tem-perature has then dropped as FLM 40 has utilised the energy in the room air.
The warm room air is led to FLM 40.
FLM 40 increases the tem-perature of the brine to the heat pump.
Outdoor air is drawn into the house.
The warm room air is drawn into the air duct system.
Air is transported from rooms with outdoor air devices to rooms with exhaust air devices.
FLM 40 is an exhaust air module specially designed to combine recovery of mechanical exhaust air with an energy collector in the ground or in rock. FLM 40 is designed to connect to the FIGHTER 1240/1250 type of ground heat pump.
The integrated DC-fan in FLM 40 extracts the air from the wet areas of the house to the recovery unit. Here the en-ergy is transferred to the heat pump’s brine, whereby the temperature increases and raises the heat pump’s heating factor. Energy is stored in the ground or rock collector even if the heat pump is not in operation, which fully utilises the exhaust air energy.
The heat pump capacity is not bound by the amount of air, but the output can be optimally adapted to suit the size of the house.
FLM 40 is positioned directly on FIGHTER 1240/1250, but can also be mounted using brackets (accessory) on the wall.
4 NIBE FLM 40
For Home Owners
LEK
63
LEK
63
The exhaust air module’s air filter should be cleaned regu-larly (about 4-5 times a year) by taking it out and shaking off any dirt. If the filter is very dirty, turn it upside-down and wash it carefully with water.
Open the front cover by pulling it out by the lower ■
edge, then lifting it up.
Set the switch (8) to ” ■ 0”.
Disconnect the connector (22) from the fan speed ■
switch.
Release the filter holder by turning the two black knobs ■
a quarter of a turn anti-clockwise.
Pull out the holder, take out the filter (63) and shake ■
off any dirt. Check that the filter is not damaged. New original filters can be ordered from NIBE.
��■ Carry out assembly in reverse order.
The interval between cleaning operations varies and de-pends on the amount of dust in the exhaust air.
Gammalt
3
21 TRYCK
1 TRYCK
2 DRAG
1
45
93
3
21
45
1 TRYCK
1 TRYCK
2 DRAG
1 Drücken
1 Drücken
2 Ziehen
1 Drücken
1 Drücken
2 Ziehen
FLM 40 and its ventilation ducting require some regular maintenance where the following points should be checked:
The numbers in brackets refer to the section “List of components”.
Cleaning the air filter
Cleaning the fan
Switch (8)
Avoid distorting the fan blades as this causes imbalance.
Do not use water or detergents.
NOTE!
Maintenance routines
Clean the fan once a year by taking it out of the exhaust air module and carefully brushing the vanes clean.
Open the front cover by pulling it out by the lower ■
edge, then lifting it up.
Set the switch (8) to “0”. ■
Disconnect the connector (22) from the fan speed ■
switch.
Dismantle the inner cover by loosening the 6 cover ■
screws.
The fan is removed by disconnecting the fan cable con- ■
nector and the two screws as illustrated.
Once the inner cover has been removed also check the ■
drip-pan under the heat exchanger. Also check the out-let from the drip-pan (98) to ensure it is not blocked.
Assembly takes place in the reverse order. ■
Pull
Pull
Press
PressPress
Press
5NIBE FLM 40
For Home Owners
LEK
LEK
93
92
98
Maintenance routines
The ventilation devices in the house should be cleaned regularly to maintain the correct ventilation. The device set-tings must not be changed.
NOTE! If you take down more than one ventilation device for cleaning, do not mix them up.
Cleaning the ventilation devices
Check that there is water in the water seal (92) to the drip-pan (93). If the water seal is empty or has a very low water level so that it “gurgles” water can be filled, for example, using a watering can through the condensation water hose which then forms a water seal or directly in the drip-pan (the inner cover plate must then be dismantled). The water seal is maintained during filling.
After using for a period of time dust and other particles can clog the water seal, consequently, you should check this regularly and clean when necessary.
Checking the condensation water seal
min 20 cm
min 15 cm
6 NIBE FLM 40
For the Installer
LEK 061211
Alt. 1
Alt. 2
LEK
LEK
LEK
The exhaust air module can contain inflam-mable anti-freeze in the brine circuit (for example ethanol). Special care should be ex-ercised during handling, installation, service, cleaning and scrapping to avoid the risk of leakage.
Handling
Transport and storageThe exhaust air module should be transported and stored in the dry.
Frost protectionFLM 40 features integrated frost protection (65) that auto-matically defrosts the heat exchanger (62) if necessary. This is achieved by the brine flow through the heat exchanger being slowed sufficiently so that the warm room air can thaw the ice.
Normally the temperature of the incoming brine to FLM 40 is shown on the display on the frost protection. The frost protection is set at the factory and should not need adjus-ting. Changes to the parameters can result in the heat ex-changer becoming blocked by frost. The buttons are locked with a code.
In the event of a fault indication the frost protection stops the FLM 40 (however, not the ventilation flow).
Fault indications on the display
Er Memory fault
- - Short circuit temperature sensor (66)
00 Defective temperature sensor (66)
InstallationFLM 40 is installed on FIGHTER 1240/1250 or using brack-ets. Noise from the circulation pump or fan can be transfer-red to the brackets. Consequently, mount on an outside wall if possible. If it is not possible to mount FLM 40 on an outside wall avoid a wall connecting to a bedroom or living-room.
NOTE! Ensure that that there is sufficient space (15 mm) above the exhaust air module to open the front cover, see the section “Dimensions”.
Route pipework so it is not fixed to an internal wall that backs on to a bedroom or living room.
General points for the installation engineer
7NIBE FLM 40
For the Installer
Condensation water hoseThe condensation water hose is routed directly to the floor drain or other water seal. Ensure that the end of the hose runs out above the water level in the floor drain. The pipe installation must be carried out in accordance with current norms.
0
0
l
100 200 l300
10
20
30
Tryckexpansionskärl
Köldbärarvolym
40
50
400 500 600 700 800 900 10000
0
l
100 200 l300
10
20
30
Druckausdehnungsgefäß
Wärme-quellen-volumen
40
50
400 500 600 700 800 900 10000
0
l
100 200 l300
10
20
30
Pressure expansion vessel
Brinevolume
40
50
400 500 600 700 800 900 1000
kW
Luftvolumen-strom (m3/h)
0 °C
5 °C
Wq-Eintritt bei
TYSKA
TYSKA
0
100
(m3/h)
300
0,5
1
1,5
Överförd effekt (kW)
Luftflöde
2
2,5
200
Köldbärare in vid 0 °C
Köldbärare in vid 5 °C
0
100
(m3/h)
300
0,5
1
1,5
Överförd effekt (kW)
Luftflöde
2
2,5
200
Köldbärare in vid 0 °C
Köldbärare in vid 5 °C
0
100 300
0,5
1
1,5
2
2,5
200
kW
Luftvolumen-strom (m3/h)
0 °C
5 °C
Wq-Eintritt bei
0
100 300
0,5
1
1,5
2
2,5
200
Pressure expansion vesselThe brine circuit should be fitted with a pressure expansion vessel. If there is a level vessel this should be replaced. The brine side should be pressurised to at least 0.5 bar.
The pressure expansion vessel should be dimensioned as set out in the diagram, to prevent operating disturban-ces. The pressure expansion vessel covers the temperature range from -10 °C to +20 °C at a pre-pressure of 0.5 (bar) and the safety valve’s opening pressure 3 bar.
Pressure expansion vessel
Brine volume
Filling and venting the systemFLM 40 is filled from the heat pump’s brine, see the Installation and Maintenance instructions in question.
Vent using the venting screw (5). The switch (38) should be set to “0”. when venting
The diagram shows the effect transferred from the ventila-tion air to the brine and applies for an air temperature of +20 °C and 50% relative air humidity.
Transferred effect (kW)
Air flow (m3/h)
Brine in at 0 °C
Brine in at 5 °C
Output transfer to brine
Pipe installation
8 NIBE FLM 40
For the Installer
Köldbärare in
NK
SF
Köldb in
Köldb ut
SÄV
Köldbärare ut
FIGHTER 1250vv
FLM 40
Frånluft Ø 160
Avluft Ø 160
FLM 40
Frånluft Ø 160
Avluft Ø 160
EXP
BV
RVP
SF
Wärme-quellen-eintritt
Wärmequellenaustritt
SÄV
FLM 40
Abluft Ø 160
Fortluft Ø 160
EXP
BV
RVP
SF
Köldb in
Köldb ut
SÄV
FX 110
Frånluft Ø 160
Avluft Ø 160
EXP
BV
RVP
SF
Brine in
Brine out
SÄV
FLM 40
Exhaust airØ 160
Extract airØ 160
EXP
BV
RVP
The lowest permitted incoming brine temperature is -5 °C.
When installing on FIGHTER 1240/150, the space under FLM 40 is limited to 90 mm. This may mean that the pipe connections on FIGHTER 1240/1250 must be shortened.
The brine is connected to FLM 40 as set out on the outline diagram.
When installing on FIGHTER 1240/1250, pipes for the ■
heat medium and water heater and, if necessary hot water circulation, are routed backwards.
Install the check valve horizontally. ■
The distance from the wall must be 50 mm for both ■
FIGHTER 1240/1250 and FLM 40.
Install the supplied angle pieces on FLM 40 so that it ■
points to the left or right, depending on the connec-tions on the heat pump for the brine.
Place FLM 40 on top of FIGHTER 1240/1250. ■
Install the supplied brine hoses through the side door ■
(left or right) on FLM 40. Secure the brine hoses to the angled pieces (from the front or rear) after having first pulled out the junction box.
Slide FIGHTER 1240/1250/FLM 40 to the desired posi- ■
tion.
LEK
Pipe connections (brine)
Extract air Exhaust air
Brine out
Brine in
BV Check valve Included in FLM 40 EXP Pressure expansion vessel According to the recom-
mendations
P Pressure gauge RV Trim valve Included in FLM 40
SF Particle filter SÄV Safety valve
Pipe installation
9NIBE FLM 40
For the Installer
External control of fan and brine pumpTo externally start and stop the fan in FLM 40 remove the bridge between -X14:11 and -X14:12. Connect potential free contact between -X14:11 and -X14:12.
To externally start and stop the brine pump in FLM 40 remove the bridge between -X14:3 and -X14:4. Connect potential free contact between -X14:3 and -X14:4.
5 6 7 8 9 103 41 214 11 12
External control of the brine pump. External control of the fan.
LEKLEK
LEK
38
8
65
914 10
LEK
14
38
8
65
914 10
14
Gammalt
Gammalt
Electrical installation
GeneralWhen FLM 40 is placed directly above the heat pump the power supply can be connected to the heat pump’s termi-nal block. The connection plug must however be cut off.
If FLM 40 is installed independently it can be connected either to an earthed 1-phase wall socket or through per-manent installation. When a permanent installation is used, FLM 40 must be preceded by a circuit-breaker.
If an insulation test is to be carried out in the building, dis-connect the exhaust air module.
Electrical installation and service must be carried out under the
supervision of a qualified electrici-an. Electrical installation and wiring must be carried out in accordance
with the stipulations in force. Work behind screwed covers may only be carried out under the supervision
of a qualified electrician.
NOTE!
10 NIBE FLM 40
For the Installer
Ziehl -EBM G1G 146-AE37-07, Matningsspänning fläkt ca 225 VAC
8 9 10*
0 50 100 150 200 250 300
0
100
200
300
400
500
600
700
Till
gäng
ligt t
ryck
, Pa
800
Luftflöde, m3/h
1 2* 3 4 5 6* 7
Available static pressure
Pa
Air flow
m3/h
Ventilation connection
Ventilation flowFLM 40 is connected so that all ventilation air, except for the kitchen fan, passes the heat exchanger (62) in the exhaust air module. Minimum flow should conform to the demands as set out in applicable norms. The ventilation flow should conform to applicable norms.
Switching the ventilation capacity is described in the sec-tion “Electrical installation” “Setting the fan capacity”.
Exhaust air ductThe kitchen flue must not be connected to FLM 40
A duct in a masonry chimney stack must not be used for extract air.
NOTE!
Duct installationTo prevent fan noise being transferred to the exhaust air devices, it may be a good idea to install a silencer in the duct. This is especially important if there are exhaust air devices in bedrooms.
Connections can be made using flexible hoses, which should be stretched well and routed to allow easy replace-ment. The extract air duct must be provided with diffusion-tight insulation over its entire length. Provision must be made for inspection of the duct. Make sure that there are no reductions of cross-sectional area in the form of creases, tight bends etc, since this will reduce the ventilation capa-city. All joins in the ducting must be sealed and pop-riveted to prevent leakage. The duct system must be carried out in accordance with current norms.
AdjustmentTo obtain the necessary air exchange in every room of the house, the exhaust air devices must be correctly positioned and adjusted. A defective ventilation installation may lead to reduced exhaust air module efficiency and thus poo-rer operating economy, and may result in damage to the house.
Fan diagram
11NIBE FLM 40
For the Installer
Setting the fan capacity Default setting: ■
Switch in position A, set on curve 2. Switch in position B, set on curve 6. Switch in position C, set on curve 10.
Open the front cover by pulling it out by the lower ■
edge, then lifting it up.
Switch off the voltage by turning the switch (8) to ” ■ 0”.
Disconnect the wiring for the fan speed switch. ■
Unscrew the screw that holds the junction box, see im- ■
age.
Select fan curves for the three modes A, B and C by set- ■
ting the DIP-switches on the fan, see image and table. The numbering of the fan curves refer to “Ventilations connection – Fan diagram”.
DIP-switch 5 and 6 corresponds to position A on the knob.
DIP-switch 1 and 2 corresponds to position B on the knob.
DIP-switch 3 and 4 corresponds to position C on the knob.
Setting the DIP-switchesFan mode A
DIP-switch 5 DIP-switch 6 Fan mode A, fan curve
off off not used
off on not used
on off 1
on on 2
Fan mode B
DIP-switch 3 DIP-switch 3 Fan mode B, fan curve
off off 3
off on 4
on off 5
on on 6
Fan mode C
DIP-switch 5 DIP-switch 6 Fan mode A, fan curve
off off 7
off on 8
on off 9
on on 10
Assembly takes place in the reverse order. ■
Check the obtained air flow for fan modes A, B and C. ■
Note which one is the normal mode, see “Installation data” section.
33
3
3
21 TRYCK
1 TRYCK
2 DRAG
1
4
93
3
21
4
1 TRYCK
1 TRYCK
2 DRAG
1 Drücken
1 Drücken
2 Ziehen
1 Drücken
1 Drücken
2 Ziehen
DIP
1 2 3
ON
4 5 6
C B A
33
LEK
LEK
3
21 TRYCK
1 TRYCK
2 DRAG
1
4
93
3
21
4
93
1 TRYCK
1 TRYCK
2 DRAG
1 Drücken
1 Drücken
2 Ziehen
1 Drücken
1 Drücken
2 Ziehen
DIP
1 2 3
ON
4 5 6
C B A
33
LEK
LEK
3
21 TRYCK
1 TRYCK
2 DRAG
1
4
93
3
21
4
93
1 TRYCK
1 TRYCK
2 DRAG
1 Drücken
1 Drücken
2 Ziehen
1 Drücken
1 Drücken
2 Ziehen
DIP
1 2 3
ON
4 5 6
C B A
DIP-switches, under cover
Factory setting, all switches set to “ON”
Ventilation connection
Pull
Pull
Press
PressPress
Press
12 NIBE FLM 40
For the Installer
PreparationsBefore commissioning check that the brine circuit is filled and vented.
Check the pipe system for leaks.
Check that the brine circuit is pressurised to at least 0.5 bar.
Setting the ventilationSee the section “Ventilation connection” - “Setting the fan capacity”.
CommissioningStart the heat transfer pump on the heat pump, see the Installation and Maintenance instructions in question.
The brine flow across the FLM 40 is controlled by means of the circulation pump (16) and trim valve (81) so that the temperature difference on the brine in and out through FLM 40 is 3 - 4 degrees. Adjustments are made when the heat pump is running. The temperature difference applies at a room temperature of 20 degrees and 0 degrees on the brine.
The brine flow through FLM 40 will be from 0.1 l/s (360 l/h) to 0.15 l/s (540 l/h) at the above temperature differences, depending on the ventilation flow.
When the heat pump is at a standstill the internal circula-tion pump in FLM 40 gives from 0.085 l/s (306 l/h) to 0.125 l/s (450 l/h) in the return charging flow to the collector. This applies to a heat pump with an approximate rated output of 4 kW. For a 15 kW heat pump the corresponding flow is from 0.09 l/s (324 l/h) to 0.14 l/s (504 l/h).
ReadjustmentVenting may be necessary after a period of use. Vent using the venting screw (5). The switch (38) should be set to “0” when venting.
Commissioning and adjusting
StartingSet the switch (38) to 1.
Set the switch (8) to 1.
Check that the fan and circulation pump are running.
13NIBE FLM 40
For the Installer
Electrical circuit diagram
Electrical circuit diagram
Från
luft
sfläk
t
Exha
ust
air
fan
Fros
tvak
t
Fros
t pr
otec
tion
Köl
dbär
arpu
mp
Brin
e pu
mp
14 NIBE FLM 40
For the Installer
Flödesriktning
LEK
90
16
36 74 731937
62
5 91
66
93
63
22
2021
LEKLEK
LEK
38
8
65
914 10
LEK
14
38
8
65
914 10
14
Gammalt
Gammalt
Component locations
Component locations
Direction of flow for brine
15NIBE FLM 40
For the Installer
List of components3 Flexible hose out from FLM 404 Flexible hose in to FLM 405 Venting screw8 Switch, positions 0 - 1, main switch9 Terminal block, incoming supply10 Cord with connection plug14 Terminal block, internal16 Circulation pump19 Connector, fan, male20 Connector, fan, female21 Connector, fan speed switch, female22 Connector, fan speed switch, male36 Fan37 Fan speed switch , mode A – B – C38 Switch, positions 0 - 1, circulation pump62 Heat exchanger63 Air filter65 Frost protection66 Temperature sensor, frost protection73 Brine out, compression ring Ø 15 mm74 Brine in, compression ring Ø 15 mm81 Trim valve, DN 1582 Check valve90 Ventilation connection exhaust air, Ø160 mm 91 Ventilation connection extract air, Ø160 mm 92 Condensation water hose93 Drip-pan95 Type plate98 Drip-pan drain
List of components
16 NIBE FLM 40
For the Installer
Dimensions
445
115
305
Avluft
ˇ 160
Fr¬nluft
ˇ 160
625
600
15
Min avstånd50 mm från vägg
440
400
365
235
180
Köldbärare in Ø 15
445
100
50
Köldbärare ut Ø 15
Droppskålsavlopp
74
73
98
95
90
300
90
510
250350
90
510
250350
70
Erforderligt utrymme för demontering av frontlucka
Vy sedd underifrån
Fritt installationsutrymmei FLM 40
Fritt installationsutrymmei FLM 40
445
115
305
Abluft
ˇ 160
Fortluft
ˇ 160
625
600
15
Mindestabstand 50 mm von der Wand
440
400
365
235
180
Wärmequelleneintritt Ø 15
445
100
50
Wärmequellenaustritt Ø 15
Kondensatwannenablauf
74
73
98
95
90
300
70
Erforderlicher Platz zur Frontabdeckungsdemontage
Ansicht von unten
Installationshöheim FLM 40
Freier Installationsbereichim FLM 40
Ansicht von obenVy sedd ovanifrån
445
115
305
Avluft
ˇ 160
Fr¬nluft
ˇ 160
626
598
15
Min avst¬nd
50 mm fr¬n vâgg
440
400
365
235
180
Kàldbârare in ˇ 15
445
100
50
Kàldbârare ut ˇ 15
Droppsk¬lsavlopp
90
300
250
90
510
350
70
Erforderligt utrymme fàrdemontering av frontlucka
Vy sedd underifr¬n
Fritt installationsutrymmei FX 110
Fritt installationsutrymmei FX 110
445
115
305
Avluft
ˇ 160
Fr¬nluft
ˇ 160
625
600
15
Min avstånd50 mm från vägg
440
400
365
235
180
Köldbärare in Ø 15
445
100
50
Köldbärare ut Ø 15
Droppskålsavlopp
74
73
98
95
90
300
90
510
250350
90
510
250350
70
Erforderligt utrymme för demontering av frontlucka
Vy sedd underifrån
Fritt installationsutrymmei FLM 40
Fritt installationsutrymmei FLM 40
445
115
305
Abluft
ˇ 160
Fortluft
ˇ 160
625
600
15
Mindestabstand 50 mm von der Wand
440
400
365
235
180
Wärmequelleneintritt Ø 15
445
100
50
Wärmequellenaustritt Ø 15
Kondensatwannenablauf
74
73
98
95
90
300
70
Erforderlicher Platz zur Frontabdeckungsdemontage
Ansicht von unten
Installationshöheim FLM 40
Freier Installationsbereichim FLM 40
Ansicht von obenVy sedd ovanifrån
445
115
305
Avluft
ˇ 160
Fr¬nluft
ˇ 160
626
598
15
Min avst¬nd
50 mm fr¬n vâgg
440
400
365
235
180
Kàldbârare in ˇ 15
445
100
50
Kàldbârare ut ˇ 15
Droppsk¬lsavlopp
90
300
250
90
510
350
70
Erforderligt utrymme fàrdemontering av frontlucka
Vy sedd underifr¬n
Fritt installationsutrymmei FX 110
Fritt installationsutrymmei FX 110
Clearance in front of FLM 40 should be at least 600 mm for maintenance and servicing.
The distance to the wall must be at least 50 mm with the installation of FLM 40 on FIGHTER 1240/1250.
Minimum distance from wall 50 mm
Space required for removal of front access panel
Clear installationspace in FLM 40
Brine in Ø 15
Brine out Ø 15
Drip-pan drain
Exhaust air
Extract air
View from below
View from above
Dimensions and setting-out coordinates
17NIBE FLM 40
For the Installer
LEK
** A-weighted sound power level (LwA). The value varies with the selected fan speed.
*** A-weighted sound pressure level (LpA). The value varies with the room’s damping capacity. These values apply with a damping of 4 dB.
82
Check valve
Technical specifications
Technical data
IP 21
Type
Height 400 mm
Width 600 mm
Depth 625 mm
Net weight 60 kg
Supply voltage 230 V 50 Hz
Rated output fan 113 W
Rated output, circulation pump 95 W
Max air flow ca 250 m3/h
Max cooling effect 1,6 kW
Enclosure class IP 21
Sound power level** 38-48 dB(A)
Sound level in the boiler house*** 34-44 dB(A)
Part No 067 030
Accessories
Enclosed kit
Brackets and cover plateWall mounting of FLM 40
Part no 089 304
LEK
LEK
Emalj
Pipe kitFor docking to FIGHTER 1240/1250
Part no 089 318 Stainless steel/Copper
Part no 089 319 Enamel
LEK
Trim valve
Drip-pan water hose
92
81
LEK
3
Hose kit for connecting brine in/out for FLM 40 (flexible hose, insulation pipe, angle connection,
gasket)
4
18 NIBE FLM 40
For the Installer
Low or a lack of ventilationCause: Filter(63) clogged.
Action: Clean or replace the filter, see the section “Maintenance procedures” - “Cleaning the air filter”.
Cause: Exhaust air device blocked or choked down too much.
Action: Check and measure the air flow.
Cause: Circuit or main MCB tripped.
Action: Reset or replace the MCB.
Cause: Fan blocked.
Action: Contact installer
Cause: The battery blocked by frost.
Action: Switch off the circulation pump using switch (38). Leave it switched off for 24 hours.
Helping the circulation pump to start Open the front cover by pulling it out by the lower ■
edge, then lifting it up.
Set the switch (8) “0”. ■
Disconnect the connector (22) from the fan speed ■
switch.
Dismantle the inner cover by loosening the 6 cover ■
screws.
Loosen the venting screw with a screwdriver. Hold a ■
cloth around the screwdriver blade as a certain amount of fluid may run out.
Insert a screwdriver and turn the pump rotor. ■
Screw in the venting screw. ■
Start FLM 40 and check whether the circulation pump ■
runs.
It is usually easier to start the circulation pump with FLM 40 running, switch (8) set to “1”. If helping the circulation pump to start is performed with FLM 40 running, be pre-pared for the screwdriver to jerk when the pump starts.
Luftningsskruv
16
Luftningsskruv
16
LE
KL
EK
GR
UN
DFO
SType
UP
S25 -
60
130
P/N
:59526447
230V
-P
C;0
017N
IB50H
z
IP 44
TF
110
Cla
ss H
Max. 1
0bar
2.5
uF
45
0.2
065
0.3
090
0.4
0
1m(A
)P,
(W)
GR
UN
DFO
SType
UP
S25 -
60
130
P/N
:59526447
230V
-P
C;0
017N
IB50H
z
IP 44
TF
110
Cla
ss H
Max. 1
0bar
2.5
uF
45
0.2
065
0.3
090
0.4
0
1m(A
)P,
(W)
Entlüfterschraube
16
LE
K
GR
UN
DFO
STyp
eU
PS
25
- 6
01
30
P/N
:59
52
64
47
23
0V
-P
C;0
01
7N
IB5
0H
z
IP
44
TF
1
10
Cla
ss
HM
ax. 1
0b
ar
2.5
uF
45
0.2
06
50
.30
90
0.4
0
1m(A
)P,
(W)
Venting screw
16
LE
K
GR
UN
DFO
STyp
eU
PS
25
- 6
01
30
P/N
:59
52
64
47
23
0V
-P
C;0
01
7N
IB5
0H
z
IP
44
TF
1
10
Cla
ss
HM
ax. 1
0b
ar
2.5
uF
45
0.2
06
50
.30
90
0.4
0
1m(A
)P,
(W)
GB
DE
In the event of malfunction or operating disturbances first check the points below:
Venting screw
The product’s serial number should always be stated with all
correspondence with NIBE. _ _ _ _ _ _ _ _ _ _ _ _ _ _
NOTE!
Dealing with malfunctions
If the operating disturbance cannot be rectified by means of the above an installation engineer should be called.
19NIBE FLM 40
20 NIBE FLM 40
PL
NO
NL
FI
DK
DE
CZ
NIBE – Haato, Valimotie 27, 01510 Vantaa
3C Broom Business Park, Bridge Way, Chesterfield S41 9QG
Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: [email protected] www.haato.fi
NIBE-BIAWAR Sp. z o. o. Aleja Jana Pawła II 57, 15-703 BIAŁYSTOKTel: 085 662 84 90 Fax: 085 662 84 14 E-mail: [email protected] www.biawar.com.pl
NIBE AB, Jerikoveien 20, 1067 OsloTel: 22 90 66 00 Fax: 22 90 66 09 E-mail: [email protected] www.nibe-villavarme.no
NIBE Energietechniek B.V., Postbus 2, NL-4797 ZG WILLEMSTAD (NB)Tel: 0168 477722 Fax: 0168 476998 E-mail: [email protected] www.nibenl.nl
Vølund Varmeteknik, Filial af NIBE AB, Brogårdsvej 7, 6920 VidebækTel: 97 17 20 33 Fax: 97 17 29 33 E-mail: [email protected] www.volundvt.dk
NIBE Systemtechnik GmbH, Am Reiherpfahl 3, 29223 CelleTel: 05141/7546-0 Fax: 05141/7546-99 E-mail: [email protected] www.nibe.de
NIBE CZ, V Zavetri 1478/6, CZ-170 00 Prague 7Tel: +420 266 791 796 Fax: +420 266 791 796 E-mail: [email protected] www.nibe-cz.com
NIBE AB Sweden, Box 14, Järnvägsgatan 40, SE-285 21 MarkarydTel: +46-(0)433-73 000 Fax: +46-(0)433-73 190 E-mail: [email protected] www.nibe.eu
GBNIBE Energy Systems Ltd,Tel: 0845 095 1200 Fax: 0845 095 1201 E-mail: [email protected] www.nibe.co.uk