JUNCTION BOX, MAXIMUM HEIGHT ABOVE CEILING 2'-0". COUPLING PROVIDE A "KELLEM GRIP", SIZE AS REQUIRED. DROP CORD TO BE TYPE "SO". SIZE AS REQUIRED. 5'-0" ABOVE FLOOR CORD AND MALE CONNECTOR SUPPLIED WITH EQUIPMENT (EQUIPMENT LEAD WIRES). CONDUIT (SIZE AS REQUIRED) SHALL BE RIGIDLY SUPPORTED FROM STRUCTURAL STEEL TO PREVENT BOTH LATERAL AND VERTICAL MOVEMENT. COOLER or CEILING PANEL. PROVIDE OPENING LARGE ENOUGH FOR COUPLING, THEN SILICONE CAULK AFTER INSTALLATION. DATE: SCALE: NONE DRAWN: ELECTRIC DROP CORD DETAIL MASTER SPECIFICATION DETAIL ESD-16 {\C4;10/9/13} COUPLING 5'-0" ABOVE FLOOR COOLER or CEILING PANEL. PROVIDE TWIST-LOCK NEMA CONNECTORS WITH WEATHERPROOF RATED BOOTS, AS REQUIRED FOR EQUIPMENT SERVED WITH DIFFERENT ELECTRICAL REQUIREMENTS. TO BE FED FROM A BREAKER CAPABLE OF SIMULTANEOUSLY DISCONNECTING ALL USED POLES. PROVIDE "SO" CORD AND APPROPRIATE NEMA TWIST-LOCK MALE CONNECTOR PR SINGLE DUPLEX OPTION NOTE: CORD DROP SHALL BE FIELD COORDINATED TO OPERATE 1 TO 3 CIRCUITS. PROVIDE HANDLE TIES AS NECESSARY FOR SIMULTANEOUS BREAKER DISCONNECT. REFER TO CHART BELOW 1 CIRCUIT, 1 TO 2 DEVICES: NEMA L5-30, 3 WIRE SO, (1) DUPLEX. 1 CIRCUIT 3-4 DEVICES: NEMA L5-30, 3 WIRE SO, (2) DUPLEX. 2 CIRCUIT, 1 TO 2 DEVICES: NEMA L14-30, 4 WIRE SO, (1) DUPLEX WITH TABS CUT. 2 CIRCUIT 3-4 DEVICES: NEMA L14-30, 4 WIRE SO, (2) DUPLEX, EACH TO ONE CIRCUIT. 3 CIRCUIT 3-4 DEVICES: NEMA L21-30, 5 WIRE SO, (2) DUPLEX, (1) WITH TABS CUT. PROVIDE OPENING LARGE ENOUGH FOR COUPLING, THEN SILICONE CAULK AFTER INSTALLATION. CONDUIT (SIZE AS REQUIRED) SHALL BE RIGIDLY SUPPORTED FROM STRUCTURAL STEEL TO PREVENT BOTH LATERAL AND VERTICAL MOVEMENT. DROP CORD TO BE TYPE "SO". SIZE AS REQUIRED. PROVIDE A "KELLEM GRIP", SIZE AS REQUIRED. JUNCTION BOX, MAXIMUM HEIGHT ABOVE CEILING 2'-0". DATE: SCALE: NONE DRAWN: ELECTRIC DROP CORD DETAIL FOR MULTIPLE OUTLETS ESD-16A {\C4;10/9/13} ORIGINAL ISSUE DATE 10/9/13 MINIMUM LENGTH ARMORED CABLE (AC), PAINTED TO MATCH STRUCTURE. CABLE SUPPORT, SEE TWO POINT CABLE SUSPENSION. SEE NOTE No. 1 SEE NOTE No. 1 MINIMUM LENGTH ARMORED CABLE (AC) PAINTED TO MATCH STRUCTURE. THREADED ROD SUPPORT, ADJUSTABLE CABLE LOCK. EXTEND CABLE UP BETWEEN JOIST FLANGES AND LOOP OVER TOP CHORD FLANGE AND SECURE WITH CABLE LOCK, AS INDICATED. EXTEND THREADED ROD UP BETWEEN JOIST FLANGES AND SECURELY ATTACHED TO TOP CHORD OF JOIST WITH NUT AND LOCK WASHER, AS INDICATED. Notice: HIGH BAY TYPE OF FIXTURE IS INDICATED IN THIS ILLUSTRATION. Notice: INDIVIDUAL or CONTINUOUS ROW of FIXTURES ARE INDICATED IN THIS ILLUSTRATION. Threaded Rod Cable SEE NOTE No. SEE NOTE No. 6. 3. & 2. NOTE No. SEE NOTE No. 6. 4. & 2. Note: 1. 2. 3. 4. FIXTURE SUPPORT AND POWER CONNECTION FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AS REQUIRED BY GOVERNING CODES. MOUNT FIXTURES BY THREADED RODS OR CABLES. HANG INDIVIDUALLY MOUNTED FIXTURES BY ONE POINT AT EACH END (MINIMUM) PER MANUFACTURER'S INSTRUCTIONS. ATTACHMENTS MUST BE SUPPORTED AT INTERVALS OF EVERY 6'-0", COMPLYING WITH NEC 330.30. 1/8" MINIMUM DIAMETER THREADED ROD SUPPORT (NUMBER AS NEEDED TO SUPPORT FIXTURE RUN), SECURELY ATTACH BOTH ENDS OF ROD TO FIXTURE AND TOP OF JOIST AS REQUIRED. FOR STORE REMODEL USE FIXTURE MOUNTING SUPPORT TO MATCH EXISTING. FIXTURES TO BE LEVEL AND ALIGN WITH SURROUNDING FIXTURES. THREADED ROD MAY BE USED AT LOCATIONS WHERE FIXTURES NEED TO BE PREVENTED FROM SWAYING. ATTACHMENTS CAN BE MADE TO EITHER TOP CHORD OF JOIST OR UNISTRUT CHANNEL SPANNING JOIST, ATTACHMENT OF FIXTURES TO ROOF METAL DECKING WILL NOT BE PERMITTED. 5. 6. ATTACH CABLE TO FIXTURE END WITH FIXTURE MOUNTING WIRE HOOKS. ROUTE ROD AROUND JOIST WEB AS REQUIRED. TYPICAL OUTLET BOX AND CONDUIT LOCATION. 1/16" MINIMUM DIAMETER STANDARD STEEL WIRE ROPE OR STAINLESS STEEL AIRCRAFT CABLE (NUMBER & SIZE AS NEEDED TO SUPPORT FIXTURES). SECURELY ATTACH CABLE TO JOIST AND FIXTURE. SECURE USING ADJUSTABLE CABLE LOCK. TYPICAL OUTLET BOX AND CONDUIT LOCATION. DATE: SCALE: NONE DRAWN: FIXTURE MOUNTING DETAIL MASTER SPECIFICATION DETAIL ESD-51 {\C4;12/13/11} Notes: US1 -- WATTSTOPPER PASSIVE INFRARED OCCUPANCY SENSOR MODEL PW-200. Lighting Load Mens Black Red Green Violet Blue Lighting Load Womens Common Exhaust Fan Neutral Ground Black Blue Lighting Load Family Blue GND GND GND OCCUPANCY SENSOR - US1 CKT1 CKT2 CKT1 CKT2 CKT1 CKT2 LOAD1 LOAD2 Lighting Load Mens Black Red Green Violet Blue Lighting Load Womens Blue Neutral Ground Black Blue GND GND GND CKT1 CKT2 CKT1 CKT2 CKT1 CKT2 LOAD1 LOAD2 LOAD1 LOAD2 LOAD1 LOAD2 *120V FAN LOAD1 LOAD2 LOAD1 LOAD2 Common Exhaust Fan Lighting Load Family REFER TO LIGHTING PLAN REFERENCE DRAWINGS FOR LIGHT FIXTURE AND 1. 2. OCCUPANCY SENSOR - US1 OCCUPANCY SENSOR - US1 OCCUPANCY SENSOR - US1 OCCUPANCY SENSOR - US1 OCCUPANCY SENSOR - US1 OCCUPANCY SENSOR REQUIREMENTS. DATE: SCALE: NONE DRAWN: RESTROOM LIGHTING AND EXHAUST FAN CONTROL ESD-25 {\C4;3/23/11} {\C4;JFQ} MASTER SPECIFICATION DETAIL Motion Sensor Motion Sensor No Motion Sensor No Motion Sensor Motion Sensor Motion Sensor These sensors only control the middle cases. Motion Sensor Motion Sensor No Motion Sensor No Motion Sensor Typical - A Typical - B Based on: Watt Stopper Motion Sensor Model No. FS-705. each motion sensor control 2 cases maximum. When an odd number of cases are in a row one motion sensor will control only one case. See Typical - B. Motion sensors shall only be used on cases in an aisle. No motion sensors are to be placed on end caps, dairy doors, nutrition cases, etc. Motion sensors shall be mounted to one side or the other of the case joint. Watt Stopper motion sensor kit Kit includes (1) power supply, (1) motion sensor, (1) 10' shielded cable, (1) connector and (1) splitter. NOTES: 1. 2. 3. 4. Refer to Kroger Installation Specifications for Watt Stopper Motion Sensor for additional installation information. 5. The Fixture Electrical Installer shall install to Owner Supplied Items: ePRO number K-0011767. GLASS DOOR CASE MOTION SENSOR EISD-1 {\C4;3/13/12} FRONT ELEVATION NOTES: 1. DASHED LINES INDICATE HIDDEN CONDUIT IN SHELF BACK AND BASE. JUNCTION BOX LOCATED IN STRUCTURAL STEEL RIGID STEEL, IMC CONDUIT FOR ELECTRICAL. PAINT CONDUIT TO MATCH COLUMNS. LOCATE CONDUIT IN THE CENTER OF SHELVING RUN OR IN LINE WITH BUILDING COLUMNS IF POSSIBLE. DO NOT LOCATE VERTICAL CONDUIT AT END OF SHELF LINE. CONDUIT SECURED TO TOP OF SHELVING UNIT. STEEL CONDUIT, RUN BETWEEN BACK TO BACK SHELVING UNITS OR WITHIN THE VERTICAL BACK OF THE UNIT. EMT CONDUIT JUNCTION BOX LOCATED WITHIN BASE OF SHELVING UNIT DUPLEX OUTLET OR JUNCTION BOX FOR ELECTRIC CONNECTION SHELVING ELECTRIC FROM OVERHEAD EISD-2 {\C4;7/23/12} MASTER SPECIFICATION DETAIL MASTER SPECIFICATION DETAIL MASTER SPECIFICATION DETAIL WALL PANEL. INSULATED PREFABRICATED DOOR FREEZER COOLER/ STROBE HORN 120 VAC AC POWER DOOR SWITCH REMOTE ALARM DRY CONTACTS ALARM DELAY SELECT PIN JUMPER SOLENOID 3A, N/C FANS 30A, N/C NOT USED DAC-55 SEE NOTE #6 N O T E S : 1. PIN JUMPER SET TO 'INSTANT'. 2. DIP 1 & 2 DOWN. DIP 3 UP FOR REF. PRE DELAY. DIP 4 UP FOR INSTANT EMS ALARM/LOG. 3. DIP 1 UP. DIPS 2-10 DOWN. 5 MIN. DELAY. 4. ADJUSTED TO THE MIDDLE WHICH IS A 60 SECOND DELAY FOR SHUTTING OFF FANS AND REF.. DAC-55 POWER & SOLENOID 1/2" CONDUIT FOR 120 VAC SEE NOTE #4 SEE NOTE #3 SEE NOTE #2 MC-1-M SEE NOTE #1 DAC-55 DOOR MONITOR MAGNETIC CONTACTS 5. SOLENOID AND FAN CONNECTIONS CONTROLLED ON FREEZERS AND MEAT COOLERS ONLY. FOR EMS WIRE 1/2" CONDUIT TO RESPECTIVE REFRIGERATION CONTROLLER AND FAN WIRING 6. MC-1-M 20" MAX. LENGTH ARMORED CABLE INCLUDED WITH UNIT. WALK-IN DOOR MONITOR EISD-4 {\C4;12/26/13} ORIGINAL ISSUE DATE 12/18/13 MASTER SPECIFICATION DETAIL 1. 2. 3. 4. Notes: 5. 6. 7. 8. FOLLOW INSTRUCTIONS FROM CHECKSTAND MANUFACTURER SUPPLIED WITH POWER POLES FOR ASSEMBLY & INITIAL INSTALLATION. POWER POLE WEIGHT IS SUPPORTED BY CHECKSTAND. CUT TOP OF POWER POLE AS NECESSARY AND ATTACH TO BUILDING STRUCTURE. WHEN TOP OF POWER POLE MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH A METAL SUPPORT, SUCH AS UNISTRUT CHANNEL, ACROSS NEAREST JOISTS. SECURELY ATTACH POWER POLE TO EXISTING STRUCTURE OR NEW METAL SUPPORT. DO NOT DRILL THRU, RUN BOLTS THRU, OR SCREW INTO POLE, PREVENT SHARP EDGES WHICH COULD DAMAGE COMMUNICATION CABLES. 3/8" x 5" INSIDE LENGTH x 4" INSIDE WIDTH SQUARE U-BOLT, TO CONNECT TO SLOTTED METAL SUPPORT (UNISTRUT) CHANNEL, WITHOUT DRILLING, IF POWER POLE IS CENTERED ON A SLOT IN METAL SUPPORT (UNISTRUT) CHANNEL. DO NOT OVER TIGHTEN U-BOLT NUTS, LEAVE LOOSE ENOUGH TO PERMIT VERTICAL MOVEMENT OF ROOF STRUCTURE. SIMILAR UNISTRUT HARDWARE MAY BE USED IN LIEU OF U-BOLTS, TO SECURELY ATTACH POWER POLES. HEIGHTS INDICATED RESULT IN POSITIONING BRACKETS TO PARTIALLY COVER SOME ACCESS HOLES. METAL SUPPORT (UNISTRUT), SQUARE U-BOLT AND ATTACHMENT HARDWARE, MC CABLE SUPPLIED AND INSTALLED BY CONTRACTOR. ALL OTHER COMPONENTS SUPPLIED BY OWNER. LANE LIGHT IS SUPPLIED WITH 10'-0" LONG CORD AND STANDARD GROUNDED PLUG. CONTRACTOR TO RUN LANE LIGHT CORD THROUGH PREDRILLED HOLE IN POWER POLE AND OUT BOTTOM OF POWER POLE TO FACTORY INSTALLED RECEPTACLE IN CHECKSTAND BASE DESIGNATED FOR LANE LIGHT, RECEPTACLE IS CONTROLLED BY FACTORY INSTALLED SWITCH LOCATED ON CHECKSTAND. BEFORE TIGHTENING HARDWARE ON LANE LIGHT, ADJUST TO PARTIALLY CONCEAL HOLE. INSTALL SHELVES AND MONITOR BRACKET AT PREDRILLED LOCATIONS. CONTRACTOR TO RUN POWER CORD THROUGH PREDRILLED HOLES IN POWER 12. {\C256;ONE COMPARTMENT POWER POLES, LANE LIGHTS, BRACKETS AND STANDS COME FROM CHECKSTAND MANUFACTURER SUPPLIED BY OWNER INSTALLED BY CONTRACTOR.} 13. {\C256;ALL HIGH VOLTAGE CONDUCTORS MUST BE WRAPPED WITH STEEL JACKETING (MC CABLE).} {\Le-PRO NUMBERS:} Power Pole #K-0001345 Cube for Lane Light #K-0037228 Express Topper #K-0037230 Light Arm Bracket With Lamp #K-0015235 ADA Topper #K-0015366 (Deactivated) Family Friendly Topper (Fred Meyer Only) #K-0045002 Express Lane Topper (Fred Meyer Only) #K-0045000 NOTE #3 Elevation Plan Top Front Right Side POWER POLE POWER POLE POWER POLE POWER POLE & L c METAL SLOT IN SUPPORT Detail 'A' JOISTS NOTE #5 NOTE No. 5 NOTE No. 5 PRINTER PLATFORMS SUPPLIED WITH POWER POLE. STORE FLOOR SEE NOTE No. 8 POWER POLE LANE LIGHT & BRACKET MOUNTED TOWARD SALES AREA. METAL SUPPORT (UNISTRUT), OPENING FACING POWER POLE. POWER POLE LOCATION POINT. REFER TO CHECKSTAND INSTALLATION INSTRUCTIIONS. (UNISTRUT) CHANNEL 1 JOIST GIRDER SEE DETAIL "A" METAL SUPPORT (UNISTRUT). MONITOR BRACKET SUPPLIED WITH POWER POLE. 2'-2" 3'-8" 11 1/2" 7'-6" A.F.F. L c 1'-1 1/2" CHECKSTAND, MODELS & ACCESSORIES VARY ELEVATION B Elevation B CHECKSTAND TELEPHONE P.O.S.COMPONENT STAND FIRST SECTION OF POWER POLES TO BE {\C10;5'-9"} CHECKOUT POWER POLE AND LANE LIGHT INSTALLATION ESD-62 {\C4;6/5/15} ORIGINAL ISSUE DATE 12/19/07 1. 2. 3. 4. Notes: NOTE #3 Plan Top Front Right Side POWER POLE POWER POLE POWER POLE POWER POLE & L c METAL SLOT IN 5. SUPPORT Detail 'A' JOISTS NOTE #5 6. 7. NOTE No. 5 NOTE No. 5 PRINTER PLATFORMS SUPPLIED WITH POWER POLE. STORE FLOOR SEE NOTE No. 8 8. POWER POLE FOLLOW INSTRUCTIONS FROM CHECKSTAND MANUFACTURER SUPPLIED WITH POWER POLES FOR ASSEMBLY & INITIAL INSTALLATION. POWER POLE WEIGHT IS SUPPORTED BY CHECKSTAND. CUT TOP OF POWER POLE AS NECESSARY AND ATTACH TO BUILDING STRUCTURE. WHEN TOP OF POWER POLE MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH A METAL SUPPORT, SUCH AS UNISTRUT CHANNEL, ACROSS NEAREST JOISTS. SECURELY ATTACH POWER POLE TO EXISTING STRUCTURE OR NEW METAL SUPPORT. DO NOT DRILL THRU, RUN BOLTS THRU, OR SCREW INTO POLE, PREVENT SHARP EDGES WHICH COULD DAMAGE COMMUNICATION CABLES. 3/8" x 5" INSIDE LENGTH x 4" INSIDE WIDTH SQUARE U-BOLT, TO CONNECT TO SLOTTED METAL SUPPORT (UNISTRUT) CHANNEL, WITHOUT DRILLING, IF POWER POLE IS CENTERED ON A SLOT IN METAL SUPPORT (UNISTRUT) CHANNEL. DO NOT OVER TIGHTEN U-BOLT NUTS, LEAVE LOOSE ENOUGH TO PERMIT VERTICAL MOVEMENT OF ROOF STRUCTURE. SIMILAR UNISTRUT HARDWARE MAY BE USED IN LIEU OF U-BOLTS, TO SECURELY ATTACH POWER POLES. HEIGHTS INDICATED RESULT IN POSITIONING BRACKETS TO PARTIALLY COVER SOME ACCESS HOLES. METAL SUPPORT (UNISTRUT), SQUARE U-BOLT AND ATTACHMENT HARDWARE, MC CABLE SUPPLIED AND INSTALLED BY CONTRACTOR. ALL OTHER COMPONENTS SUPPLIED BY OWNER. LANE LIGHT IS SUPPLIED WITH 10'-0" LONG CORD AND STANDARD GROUNDED PLUG. CONTRACTOR TO RUN LANE LIGHT CORD THROUGH PREDRILLED HOLE IN POWER POLE AND OUT BOTTOM OF POWER POLE TO FACTORY INSTALLED RECEPTACLE IN CHECKSTAND BASE DESIGNATED FOR LANE LIGHT, RECEPTACLE IS CONTROLLED BY FACTORY INSTALLED SWITCH LOCATED ON CHECKSTAND. BEFORE TIGHTENING HARDWARE ON LANE LIGHT, ADJUST TO PARTIALLY CONCEAL HOLE. INSTALL SHELVES AND MONITOR BRACKET AT PREDRILLED LOCATIONS. CONTRACTOR TO RUN POWER CORD THROUGH PREDRILLED HOLES IN POWER 12. {\C256;ONE COMPARTMENT POWER POLES, LANE LIGHTS, BRACKETS AND STANDS COME FROM CHECKSTAND MANUFACTURER SUPPLIED BY OWNER INSTALLED BY CONTRACTOR.} 13. {\C256;ALL HIGH VOLTAGE CONDUCTORS MUST BE WRAPPED WITH STEEL JACKETING (MC CABLE).} LANE LIGHT & BRACKET MOUNTED TOWARD SALES AREA. METAL SUPPORT (UNISTRUT), OPENING FACING POWER POLE. POWER POLE LOCATION POINT. REFER TO CHECKSTAND INSTALLATION INSTRUCTIIONS. {\Le-PRO NUMBERS:} Power Pole #K-0001345 Cube for Lane Light #K-0037228 Express Topper #K-0037230 Light Arm Bracket With Lamp #K-0015235 ADA Topper #K-0015366 (Deactivated) Family Friendly Topper (Fred Meyer Only) #K-0045002 Express Lane Topper (Fred Meyer Only) #K-0045000 (UNISTRUT) CHANNEL JOIST GIRDER SEE DETAIL "A" METAL SUPPORT (UNISTRUT). MONITOR BRACKET SUPPLIED WITH POWER POLE. CHECKSTAND, MODELS & ACCESSORIES VARY 2'-2" 3'-8" 7'-6" A.F.F. L c 11 1/2" 1'-1 1/2" Elevation 7 Elevation B CHECKSTAND TELEPHONE P.O.S.COMPONENT STAND ELEV. B FIRST SECTION OF POWER POLES TO BE {\C10;5'-9"} CAROUSEL CHECKOUT POWER POLE AND LANE LIGHT INSTALLATION ESD-62B {\C4;6/5/15} ORIGINAL ISSUE DATE 11/21/14 1. 2. 3. 4. Notes: 5. 6. 7. 8. FOLLOW INSTRUCTIONS FROM CHECKSTAND MANUFACTURER SUPPLIED WITH POWER POLES FOR ASSEMBLY & INITIAL INSTALLATION. POWER POLE WEIGHT IS SUPPORTED BY CHECKSTAND. CUT TOP OF POWER POLE AS NECESSARY AND ATTACH TO BUILDING STRUCTURE. WHEN TOP OF POWER POLE MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH A METAL SUPPORT, SUCH AS UNISTRUT CHANNEL, ACROSS NEAREST JOISTS. SECURELY ATTACH POWER POLE TO EXISTING STRUCTURE OR NEW METAL SUPPORT. DO NOT DRILL THRU, RUN BOLTS THRU, OR SCREW INTO POLE, TO PREVENT SHARP EDGES WHICH COULD DAMAGE COMMUNICATION CABLES. 3/8" x 5" INSIDE LENGTH x 4" INSIDE WIDTH SQUARE U-BOLT, TO CONNECT TO SLOTTED METAL SUPPORT (UNISTRUT) CHANNEL, WITHOUT DRILLING, IF POWER POLE IS CENTERED ON A SLOT IN METAL SUPPORT (UNISTRUT) CHANNEL. DO NOT OVER TIGHTEN U-BOLT NUTS, LEAVE LOOSE ENOUGH TO PERMIT VERTICAL MOVEMENT OF ROOF STRUCTURE. SIMILAR UNISTRUT HARDWARE MAY BE USED IN LIEU OF U-BOLTS, TO SECURELY ATTACH POWER POLES. HEIGHTS INDICATED RESULT IN POSITIONING BRACKETS TO PARTIALLY COVER SOME ACCESS HOLES. METAL SUPPORT (UNISTRUT), SQUARE U-BOLT AND ATTACHMENT HARDWARE, MC CABLE SUPPLIED AND INSTALLED BY CONTRACTOR. ALL OTHER COMPONENTS SUPPLIED BY OWNER. LANE LIGHT IS SUPPLIED WITH 10'-0" LONG CORD AND STANDARD GROUNDED PLUG. CONTRACTOR TO RUN LANE LIGHT CORD THROUGH PREDRILLED HOLE IN POWER POLE AND OUT BOTTOM OF POWER POLE TO FACTORY INSTALLED RECEPTACLE IN CHECKSTAND BASE DESIGNATED FOR LANE LIGHT, RECEPTACLE IS CONTROLLED BY FACTORY INSTALLED SWITCH LOCATED ON CHECKSTAND. BEFORE TIGHTENING HARDWARE ON LANE LIGHT, ADJUST TO PARTIALLY CONCEAL HOLE. INSTALL SHELVES AND MONITOR BRACKET AT PREDRILLED LOCATIONS. CONTRACTOR TO RUN POWER CORD THROUGH PREDRILLED HOLES IN POWER 12. {\C256;ONE COMPARTMENT POWER POLES, LANE LIGHTS, BRACKETS AND STANDS COME FROM CHECKSTAND MANUFACTURER SUPPLIED BY OWNER INSTALLED BY CONTRACTOR.} 13. {\C256;ALL HIGH VOLTAGE CONDUCTORS MUST BE WRAPPED WITH STEEL JACKETING (MC CABLE).} {\Le-PRO NUMBERS:} Cube for Lane Light #K-0037228 Express Topper #K-0037230 Light Arm Bracket With Lamp #K-0015235 ADA Topper #K-0015366 (Deactivated) Family Friendly Topper (Fred Meyer Only) #K-0045002 Express Lane Topper (Fred Meyer Only) #K-0045000 NOTE #3 Elevation Plan Top Front Right Side POWER POLE POWER POLE POWER POLE POWER POLE & L c METAL SLOT IN SUPPORT Detail 'A' JOISTS NOTE #5 NOTE No. 5 NOTE No. 5 STORE FLOOR METAL SUPPORT (UNISTRUT), OPENING FACING POWER POLE. POWER POLE LOCATION POINT. REFER TO CHECKSTAND INSTALLATION INSTRUCTIIONS. (UNISTRUT) CHANNEL JOIST GIRDER SEE DETAIL "A" METAL SUPPORT (UNISTRUT). CHECKSTAND, MODELS & ACCESSORIES VARY 7'-6" A.F.F. 2'-10" 3'-0" 10 1/2" 5" L c FIRST SECTION OF POWER POLES TO BE A FULL 8'-0" SECTION. PRINTER PLATFORMS SUPPLIED WITH POWER POLE. MONITOR BRACKET SUPPLIED WITH POWER POLE. SEE NOTE No. 8 LANE LIGHT & BRACKET ONLY IF CHECKSTAND USED AT FRONT. MOUNT TOWARD SALES AREA. POWER POLE IMAGES SHOWN ARE FOR METRO CHECKOUT - LEFT HAND. RIGHT HAND CHECKOUT MIRROR IMAGE. Power Pole Ceiling Metro Universal #K-0052766 1 EURO - METRO CHECKOUT POWER POLE AND LANE LIGHT INSTALLATION ESD-62C {\C4;6/5/15} ORIGINAL ISSUE DATE 6/5/15 MASTER SPECIFICATION DETAIL MASTER SPECIFICATION DETAIL DATE: SCALE: NONE DRAWN: DATE: SCALE: NONE DRAWN: DATE: SCALE: NONE DRAWN: DATE: SCALE: NONE DRAWN: DATE: SCALE: NONE DRAWN: DATE: SCALE: NONE DRAWN: TRACK INSTALLATION MONOPOINT INSTALLATION NOTES: ELECTRICAL POWER SUPPLY AIRCRAFT CABLE. SEE NOTES No. 1 & No. 3. ELECTRICAL POWER SUPPLY MONOPOINT CANOPY ADAPTER THREADED ROD. SEE NOTES No. 1 & No. 4. THREADED ROD COUPLING, IF NEEDED. EXTEND CABLE OVER JOIST FLANGES AND SECURE WITH CABLE LOCK, AS INDICATED. EXTEND THREADED ROD UP BETWEEN JOIST FLANGES AND SECURELY ATTACH TO JOIST, CONNECTION SEE DETAIL 'B' 1. 2. 3. 4. FIXTURE SUPPORT AND POWER CONNECTION FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AS REQUIRED BY GOVERNING CODES. THIS DETAIL IS ASSOCIATED WITH THE INSTALLATION OF TR15, TR16, TR17, TR18 AND TR19 LED TRACK LIGHT FIXTURES. HANG ELECTRIFIED TRACK FOR MULTIPLE FIXTURES WITH AIRCRAFT CABLE AND THREADED ROD FOR MONOPOINT FIXTURE INSTALLATION. THREADED ROD SHOULD BE USED TO SUPPORT ELECTRIFIED TRACK AT LOCATIONS WHERE HVAC DIFFUSERS CAN CAUSE TRACK TO SWAY. \A1;INSTALL ELECTRIFIED TRACK WITH MIN 1/16" DIAMETER STANDARD STEEL WIRE ROPE OR STAINLESS STEEL AIRCRAFT CABLE WITH CABLE LOCK CONNECTED TO 1/4" EYE BOLT THRU FACTORY DRILLED HOLES WITH LOCK NUT WITH NYLON INSERT ON BOTTOM AND STANDARD JAMB NUT ON TOP OF THE TRACK. 4' TRACK TO BE INSTALLED BY 2 POINTS OF ATTACHMENT, 8' BY 3 POINTS AND 12' BY 4 POINTS. LIGHT TRACK LENGTH AND HEIGHT ABOVE FLOOR VARIES PER LOCATION. REFER TO LIGHTING PLAN FOR MOUNTING HEIGHT AND LOCATIONS. \A1;WHERE MOUNTING CABLE OR THREADED ROD MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH METAL SUPPORT BETWEEN STEEL USING STEEL CHANNEL 7/8" MIN, 1" x 1" ANGLE IRON OR 3/4" IMC OR RIGID CONDUIT. 6. 5. \A1;MONOPOINT FIXTURE TO BE HUNG BY 1/4" THREADED ROD ATTACHED TO STEEL AND JUNCTION BOX, FOR LONGER DROPS INSTALL THREADED COUPLING AS HIGH AS POSSIBLE. ATTACH TO BOTTOM CHORD OF JOIST BY EXTENDING THREADED ROD BETWEEN JOIST FLANGES AND HOLE IN JUNCTION BOX BY ATTACHING WITH LOCK NUT WITH NYLON INSERT ON TOP AND STANDARD JAMB NUT & WASHER ON BOTTOM. SEE DETAIL 'B' FOR TYPICAL THREADED ROD CONNECTION NYLON INSERT LOCK NUT AND WASHER JAMB NUT AND WASHER SEE DETAIL 'A' FOR TYPICAL EYE BOLT CONNECTION JAMB NUT DETAIL 'A' DETAIL 'B' JUNCTION BOX, CONNECTION SEE DETAIL 'B' DATE: SCALE: NONE DRAWN: LED TRACK LIGHT & MONOPOINT DETAIL ESD-50 {\C4;11/5/13} NOTES: 1. 2. FIXTURE SUPPORT AND POWER CONNECTION FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AS REQUIRED BY GOVERNING CODES. REFER TO LIGHTING PLAN FOR MOUNTING HEIGHT AND LOCATIONS. \A1;WHERE THREADED ROD MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH METAL SUPPORT BETWEEN STEEL USING STEEL CHANNEL 7/8" MIN, 1" x 1" ANGLE IRON OR 3/4" IMC OR RIGID CONDUIT. 4. 3. \A1;PENDANT TO BE HUNG BY 1/4" THREADED ROD ATTACHED TO STEEL AND JUNCTION BOX, FOR LONGER DROPS INSTALL THREADED COUPLING AS HIGH AS POSSIBLE. ATTACH TO BOTTOM CHORD OF JOIST BY EXTENDING THREADED ROD BETWEEN JOIST FLANGES AND HOLE IN JUNCTION BOX BY ATTACHING WITH LOCK NUT WITH NYLON INSERT ON TOP AND STANDARD JAMB NUT & WASHER ON BOTTOM. NYLON INSERT LOCK NUT AND WASHER JAMB NUT AND WASHER DETAIL 'B' EXTEND THREADED ROD UP BETWEEN JOIST FLANGES AND SECURELY ATTACH TO JOIST, CONNECTION SEE DETAIL 'B' SEE DETAIL 'B' FOR TYPICAL THREADED ROD CONNECTION THREADED ROD COUPLING, IF NEEDED. THREADED ROD. SEE NOTE No. 2. ELECTRICAL POWER SUPPLY CANOPY PLATE JUNCTION BOX PENDANT LIGHT INSTALLATION PENDANT. SEE NOTE No. 4. 6'-0" 6'-0" ADJUSTABLE CORD PROVIDED WITH FIXTURE PENDANT LIGHT MOUNTING DETAIL ESD-50A {\C4;12/5/13} ORIGINAL ISSUE DATE 12/5/13 MASTER SPECIFICATION DETAIL DATE: SCALE: NONE DRAWN: MASTER SPECIFICATION DETAIL ISSUE DATE: PROJECT NO.: SHEET NUMBER: NO. REVISIONS K n o x v i l l e , T e n n e s s e e 37915 phone: 865-546-9374 fax: 865-673-9028 e - m a i l : [email protected] 111 E. J a c k s o n A v e n u e S u i t e "1 0 1 " FURNISHED BY DOLLAR & EWERS ARCHITECTURE, INC. C O P Y R I G H T THEY ARE TO BE USED ONLY WITH RESPECT TO THIS PROJECT PROJECT AND ARE NOT TO BE USED WITH ANY OTHER ARE AND SHALL REMAIN THE PROPERTY OF DEA, INC. FOR EACH PARTY TO THE CONTRACT, SUCH DOCUMENTS ARE TO BE RETURNED OR SUITABLY ACCOUNTED FOR TO DEA, INC. ON REQUEST AT THE COMPLETION OF THE WORK. SUBMISSION DISTRIBUTION TO MEET OFFICIAL REGULATORY REQUIREMENTS OR FOR OTHER PURPOSES IN CONNECTION WITH THE PROJECT IS NOT TO BE CONSTRUED AS PUBLICATION IN DEROGATION DEA'S COMMON LAW COPYRIGHT OR OTHER RESERVED RIGHTS. PROJECT. WITH THE EXCEPTION OF ONE CONTRACT SET C O P Y R I G H T ALL DRAWINGS, SPECIFICATIONS AND COPIES THEREOF A With-in-the-Walls Remodel for: KROGER STORE #U-523 - DICKSON 143 HENSLEE DRIVE, DICKSON, TENNESSEE 37055 DECEMBER 16, 2020 220269 /20072 C E E 1 M T o. N E T A F O S M O 7 5 3 0 E E T N N E S S E C R S E V R E D E R E N R AGRICULTURE XVI K T R E G I S N G I I E R E E. N I N O 4 THIS DRAWING IS GENERALLY DIAGRAMMATIC AND, EXCEPT WHERE SPECIFICALLY DIMENSIONED OR DETAILED, INDICATES THE GENERAL ARRANGEMENT OF THE WORK. THE CONTRACTOR SHALL INSTALL HIS WORK TO CONFORM AS NEARLY AS POSSIBLE TO THE LOCATIONS AND ARRANGEMENTS SHOWN. COORDINATE THE WORK WITH ALL OTHER TRADES TO AVOID THE EXPRESS WRITTEN AUTHORIZATION OF NORRIS & NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT OF NORRIS & ASSOCIATES ENGINEERS INC. AND SHALL THIS DRAWING AND IT'S CONTENTS ARE THE PROPERTY ENGINEERS 865-584-3065 FAX: PHONE: KNOXVILLE, TN 5518 WALLWOOD ROAD 37912 865-584-3063 INC. INTERFERENCES. ASSOCIATES ENGINEERS INC. ASSOCIATES NORRIS & www.norrisengineers.com E1.3-2 ELECTRICAL STANDARD DETAILS (ESD'S)

Upload: others

Post on 04-Feb-2022

10 views

Category:

Documents


0 download

TRANSCRIPT

JUNCTION BOX, MAXIMUM HEIGHTABOVE CEILING 2'-0".

COUPLING

PROVIDE A "KELLEM GRIP",SIZE AS REQUIRED.

DROP CORD TO BE TYPE "SO".

SIZE AS REQUIRED.

5'-0" A

BOVE

FLOO

R

CORD AND MALE CONNECTORSUPPLIED WITH EQUIPMENT

(EQUIPMENT LEAD WIRES).

CONDUIT (SIZE AS REQUIRED)SHALL BE RIGIDLY SUPPORTEDFROM STRUCTURAL STEEL TOPREVENT BOTH LATERAL ANDVERTICAL MOVEMENT.

COOLER or CEILING PANEL.

PROVIDE OPENING LARGEENOUGH FOR COUPLING,THEN SILICONE CAULK AFTERINSTALLATION.

DATE:

SCALE: NONEDRAWN:ELECTRIC DROP CORD DETAIL

MASTER SPECIFICATION DETAILESD-16

{\C4;10/9/13}

COUPLING

5'-0" A

BOVE

FLOO

R

COOLER or CEILING PANEL.

PROVIDE TWIST-LOCK NEMA CONNECTORS WITH WEATHERPROOF RATED BOOTS, AS REQUIRED FOR EQUIPMENT SERVED WITH DIFFERENT ELECTRICAL REQUIREMENTS.

TO BE FED FROM A BREAKER CAPABLE OF SIMULTANEOUSLY DISCONNECTING ALL USED POLES.

PROVIDE "SO" CORD AND APPROPRIATE NEMA TWIST-LOCK MALE CONNECTOR

PRSINGLE DUPLEX OPTION

NOTE:CORD DROP SHALL BE FIELDCOORDINATED TO OPERATE1 TO 3 CIRCUITS. PROVIDEHANDLE TIES AS NECESSARYFOR SIMULTANEOUSBREAKER DISCONNECT.REFER TO CHART BELOW

1 CIRCUIT, 1 TO 2 DEVICES:NEMA L5-30, 3 WIRE SO, (1) DUPLEX.

1 CIRCUIT 3-4 DEVICES:NEMA L5-30, 3 WIRE SO, (2) DUPLEX.

2 CIRCUIT, 1 TO 2 DEVICES:NEMA L14-30, 4 WIRE SO, (1) DUPLEXWITH TABS CUT.

2 CIRCUIT 3-4 DEVICES:NEMA L14-30, 4 WIRE SO, (2) DUPLEX,EACH TO ONE CIRCUIT.

3 CIRCUIT 3-4 DEVICES:NEMA L21-30, 5 WIRE SO, (2) DUPLEX,(1) WITH TABS CUT.

PROVIDE OPENING LARGE ENOUGH FOR COUPLING, THEN SILICONE CAULK AFTER INSTALLATION.

CONDUIT (SIZE AS REQUIRED) SHALL BE RIGIDLY SUPPORTED FROM STRUCTURAL STEEL TO PREVENT BOTH LATERAL AND VERTICAL MOVEMENT.

DROP CORD TO BE TYPE "SO". SIZE AS REQUIRED.

PROVIDE A "KELLEM GRIP", SIZE AS REQUIRED.

JUNCTION BOX, MAXIMUM HEIGHT ABOVE CEILING 2'-0".

DATE:

SCALE: NONEDRAWN:ELECTRIC DROP CORD DETAIL FOR MULTIPLE OUTLETS

ESD-16A

{\C4;10/9/13}

ORIGINAL ISSUE DATE 10/9/13

MINIMUM LENGTH ARMOREDCABLE (AC), PAINTED TO

MATCH STRUCTURE.CABLESUPPORT, SEE

TWO POINT CABLESUSPENSION.SEE

NOTENo. 1

SEE

NOTE

No. 1MINIMUM LENGTH

ARMORED CABLE (AC)PAINTED TO MATCHSTRUCTURE.

THREADED ROD SUPPORT, ADJUSTABLE

CABLE LOCK.

EXTEND CABLE UPBETWEEN JOIST FLANGES ANDLOOP OVER TOP CHORDFLANGE AND SECURE WITH

CABLE LOCK, AS INDICATED.EXTEND THREADED ROD UP

BETWEEN JOIST FLANGES AND

SECURELY ATTACHED TO TOPCHORD OF JOIST WITH NUT AND

LOCK WASHER, AS INDICATED.

Notice:HIGH BAY TYPE OF FIXTURE IS

INDICATED IN THIS ILLUSTRATION.

Notice:INDIVIDUAL or CONTINUOUS ROW of FIXTURES

ARE INDICATED IN THIS ILLUSTRATION.

Threaded Rod Cable

SEE NOTE No.

SEE NOTE No. 6.

3.

& 2.NOTE No.

SEE NOTE No. 6.

4.& 2.

Note:

1.

2.

3.

4.

FIXTURE SUPPORT AND POWER CONNECTION FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AS REQUIRED BY GOVERNING CODES. MOUNT FIXTURES BY THREADED RODS OR CABLES.

HANG INDIVIDUALLY MOUNTED FIXTURES BY ONE POINT AT EACH END (MINIMUM) PER MANUFACTURER'S INSTRUCTIONS. ATTACHMENTS MUST BE SUPPORTED AT INTERVALS OF EVERY 6'-0", COMPLYING WITH NEC 330.30.

1/8" MINIMUM DIAMETER THREADED ROD SUPPORT (NUMBER AS NEEDED TO SUPPORT FIXTURE RUN), SECURELY ATTACH BOTH ENDS OF ROD TO FIXTURE AND TOP OF JOIST AS REQUIRED.

FOR STORE REMODEL USE FIXTURE MOUNTING SUPPORT TO MATCH EXISTING. FIXTURES TO BE LEVEL AND ALIGN WITH SURROUNDING FIXTURES. THREADED ROD MAY BE USED AT LOCATIONS WHERE FIXTURES NEED TO BE PREVENTED FROM SWAYING.ATTACHMENTS CAN BE MADE TO EITHER TOP CHORD OF JOIST OR UNISTRUT CHANNEL SPANNING JOIST, ATTACHMENT OF FIXTURES TO ROOF METAL DECKING WILL NOT BE PERMITTED.

5.

6.

ATTACH CABLE TO FIXTURE END WITH FIXTURE MOUNTING WIRE HOOKS.

ROUTE ROD AROUND JOIST WEB AS REQUIRED.

TYPICAL OUTLET BOX AND CONDUIT LOCATION.

1/16" MINIMUM DIAMETER STANDARD STEEL WIRE ROPE OR STAINLESS STEEL AIRCRAFT CABLE (NUMBER & SIZE AS NEEDED TO SUPPORT FIXTURES). SECURELY ATTACH CABLE TO JOIST AND FIXTURE.

SECURE USING ADJUSTABLE CABLE LOCK.

TYPICAL OUTLET BOX AND CONDUIT LOCATION.

DATE:

SCALE: NONEDRAWN:FIXTURE MOUNTING DETAIL

MASTER SPECIFICATION DETAILESD-51

{\C4;12/13/11}

Notes:

US1 -- WATTSTOPPER PASSIVE INFRARED OCCUPANCY SENSOR MODEL PW-200.

LightingLoadMens

Black

Red

Green

Violet

Blue

LightingLoadWomens

CommonExhaustFan

NeutralGround

Black

BlueLightingLoadFamily

Blue

GND GND GND

OCCUPANCY

SENSOR - US1

CKT1

CKT2

CKT1

CKT2

CKT1

CKT2

LOAD1

LOAD2

LightingLoadMens

Black

Red

Green

Violet

Blue

LightingLoadWomens

Blue

NeutralGround

Black

Blue

GND GND GND

CKT1

CKT2

CKT1

CKT2

CKT1

CKT2

LOAD1

LOAD2

LOAD1

LOAD2

LOAD1

LOAD2

*120V FAN

LOAD1

LOAD2

LOAD1

LOAD2

CommonExhaustFan

LightingLoadFamily

REFER TO LIGHTING PLAN REFERENCE DRAWINGS FOR LIGHT FIXTURE AND

1.

2.

OCCUPANCY

SENSOR - US1

OCCUPANCY

SENSOR - US1

OCCUPANCY

SENSOR - US1

OCCUPANCY

SENSOR - US1

OCCUPANCY

SENSOR - US1

OCCUPANCY SENSOR REQUIREMENTS.

DATE:

SCALE: NONEDRAWN:RESTROOM LIGHTING AND EXHAUST FAN CONTROLESD-25

{\C4;3/23/11}

{\C4;JFQ}

MASTER SPECIFICATION DETAIL

Mo

tio

n S

en

so

rM

otion S

ensor

No Motion

Sensor

No Motion

Sensor

Motion S

ensor

Motion S

ensor These sensors

only control themiddle cases.Motion SensorMotion S

ensor

No Motion

Sensor

No Motion

Sensor

Typical-A

Typical-B

Based on:Watt Stopper Motion Sensor Model No. FS-705.

each motion sensor control 2 cases maximum. When an

odd number of cases are in a row one motion sensor will control only one case. See Typical - B.

Motion sensors shall only be used on cases in an aisle. No motion sensors are to be placed on end caps, dairy doors, nutrition cases, etc.Motion sensors shall be mounted to one side or the other of the case joint.

Watt Stopper motion sensor kit Kit includes (1)power supply, (1) motion sensor, (1) 10' shielded cable, (1) connector and (1) splitter.

NOTES:

1.

2.

3.

4.

Refer to Kroger Installation Specifications for Watt Stopper Motion Sensor for additional installation information.5.

The Fixture Electrical Installer shall install to

Owner Supplied Items: ePRO number K-0011767.

GLASS DOOR CASE MOTION SENSOREISD-1

{\C4;3/13/12}

FRONT ELEVATION

NOTES:1. DASHED LINES INDICATE HIDDEN CONDUIT IN SHELF BACK AND BASE.

JUNCTION BOX LOCATED IN STRUCTURAL STEEL

RIGID STEEL, IMC CONDUIT FOR ELECTRICAL. PAINT CONDUIT TO MATCH COLUMNS. LOCATE CONDUIT IN THE CENTER OF SHELVING RUN OR IN LINE WITH BUILDING COLUMNS IF POSSIBLE. DO NOT LOCATE VERTICAL CONDUIT AT END OF SHELF LINE.CONDUIT SECURED TO TOP OF SHELVING UNIT.

STEEL CONDUIT, RUN BETWEEN BACK TO BACK SHELVING UNITS OR WITHIN THE VERTICAL BACK OF THE UNIT.

EMT CONDUITJUNCTION BOX LOCATED WITHIN BASE OF SHELVING UNIT DUPLEX OUTLET OR JUNCTION BOX FOR ELECTRIC CONNECTION

SHELVING ELECTRIC FROM OVERHEADEISD-2

{\C4;7/23/12}

MASTER SPECIFICATION DETAIL

MASTER SPECIFICATION DETAIL

MASTER SPECIFICATION DETAIL

WALL PANEL.

INSULATED

PREFABRICATED

DOOR

FREEZERCOOLER/

STROBE

HORN

120 VAC

AC POWER

DOOR SWITCH

REMOTE ALARM DRY CONTACTS

ALARM DELAYSELECT

PIN JUMPER

SO

LEN

OID

3A, N

/C

FAN

S30

A, N

/C

NO

TU

SE

D

DAC-55

SEE NOTE #6

N O T E S :

1. PIN JUMPER SET TO 'INSTANT'.

2. DIP 1 & 2 DOWN.

DIP 3 UP FOR REF. PRE DELAY.DIP 4 UP FOR INSTANT EMS ALARM/LOG.

3. DIP 1 UP. DIPS 2-10 DOWN. 5 MIN. DELAY.

4. ADJUSTED TO THE MIDDLE WHICH IS A 60SECOND DELAY FOR SHUTTING OFF FANSAND REF..

DAC-55 POWER & SOLENOID1/2" CONDUIT FOR 120 VAC

SEE NOTE #4

SEE NOTE #3

SEE NOTE #2

MC-1-M

SEE NOTE #1

DAC-55 DOOR MONITOR

MAGNETIC CONTACTS

5. SOLENOID AND FAN CONNECTIONS CONTROLLEDON FREEZERS AND MEAT COOLERS ONLY.

FOR EMS WIRE1/2" CONDUIT

TO RESPECTIVE REFRIGERATIONCONTROLLER

AND FAN WIRING

6. MC-1-M 20" MAX. LENGTH ARMORED CABLEINCLUDED WITH UNIT.

WALK-IN DOOR MONITOREISD-4

{\C4;12/26/13}

ORIGINAL ISSUE DATE 12/18/13MASTER SPECIFICATION DETAIL

1.

2.

3.

4.

Notes:

5.

6.

7.

8.

FOLLOW INSTRUCTIONS FROM CHECKSTAND MANUFACTURER SUPPLIED WITH POWER POLES FOR ASSEMBLY & INITIAL INSTALLATION.POWER POLE WEIGHT IS SUPPORTED BY CHECKSTAND. CUT TOP OF POWER POLE AS NECESSARY AND ATTACH TO BUILDING STRUCTURE.WHEN TOP OF POWER POLE MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH A METAL SUPPORT, SUCH AS UNISTRUT CHANNEL, ACROSS NEAREST JOISTS.SECURELY ATTACH POWER POLE TO EXISTING STRUCTURE OR NEW METAL SUPPORT. DO NOT DRILL THRU, RUN BOLTS THRU, OR SCREW INTO POLE, PREVENT SHARP EDGES WHICH COULD DAMAGE COMMUNICATION CABLES.

3/8" x 5" INSIDE LENGTH x 4" INSIDE WIDTH SQUARE U-BOLT, TO CONNECT TO SLOTTED METAL SUPPORT (UNISTRUT) CHANNEL, WITHOUT DRILLING, IF POWER POLE IS CENTERED ON A SLOT IN METAL SUPPORT (UNISTRUT) CHANNEL. DO NOT OVER TIGHTEN U-BOLT NUTS, LEAVE LOOSE ENOUGH TO PERMIT VERTICAL MOVEMENT OF ROOF STRUCTURE. SIMILAR UNISTRUT HARDWARE MAY BE USED IN LIEU OF U-BOLTS, TO SECURELY ATTACH POWER POLES.HEIGHTS INDICATED RESULT IN POSITIONING BRACKETS TO PARTIALLY COVER SOME ACCESS HOLES.

METAL SUPPORT (UNISTRUT), SQUARE U-BOLT AND ATTACHMENT HARDWARE, MC CABLE SUPPLIED AND INSTALLED BY CONTRACTOR. ALL OTHER COMPONENTS SUPPLIED BY OWNER.LANE LIGHT IS SUPPLIED WITH 10'-0" LONG CORD AND STANDARD GROUNDED PLUG. CONTRACTOR TO RUN LANE LIGHTCORD THROUGH PREDRILLED HOLE IN POWER POLE AND OUT BOTTOM OF POWER POLE TO FACTORY INSTALLEDRECEPTACLE IN CHECKSTAND BASE DESIGNATED FOR LANE LIGHT, RECEPTACLE IS CONTROLLED BY FACTORY INSTALLEDSWITCH LOCATED ON CHECKSTAND.BEFORE TIGHTENING HARDWARE ON LANE LIGHT, ADJUST TO PARTIALLY CONCEAL HOLE. INSTALL SHELVES AND MONITORBRACKET AT PREDRILLED LOCATIONS. CONTRACTOR TO RUN POWER CORD THROUGH PREDRILLED HOLES IN POWER

12. {\C256;ONE COMPARTMENT POWER POLES, LANE LIGHTS, BRACKETS AND STANDS COME FROM CHECKSTAND MANUFACTURER SUPPLIED BY OWNER INSTALLED BY CONTRACTOR.}13. {\C256;ALL HIGH VOLTAGE CONDUCTORS MUST BE WRAPPED WITH STEEL JACKETING (MC CABLE).}

{\Le-PRO NUMBERS:}Power Pole #K-0001345

Cube for Lane Light #K-0037228Express Topper #K-0037230

Light Arm Bracket With Lamp #K-0015235

ADA Topper #K-0015366 (Deactivated)

Family Friendly Topper (Fred Meyer Only) #K-0045002

Express Lane Topper (Fred Meyer Only) #K-0045000

NOTE #3

Elevation

Plan

Top

Front Right Side

POWERPOLE

POWERPOLE

POWER POLE

POWERPOLE &

Lc

METAL

SLOT INSUPPORT

Detail 'A'

JOISTS

NOTE #5

NOTENo. 5

NOTENo. 5

PRINTER PLATFORMS SUPPLIED WITH POWER POLE.STORE FLOOR

SEE NOTE No. 8

POWER POLE

LANE LIGHT & BRACKET MOUNTED TOWARD SALES AREA.

METAL SUPPORT (UNISTRUT), OPENING FACING POWER POLE.

POWER POLE LOCATION POINT. REFER TO CHECKSTAND INSTALLATION INSTRUCTIIONS.

(UNISTRUT)CHANNEL

1

JOIST GIRDER SEE DETAIL "A"METAL SUPPORT (UNISTRUT).

MONITOR BRACKET SUPPLIED WITH POWER POLE.

2'-2"3'-8"

11 1

/2"

7'-6

" A.F

.F.

Lc

1'-1 1/2"

CHECKSTAND, MODELS & ACCESSORIES VARY

ELEVATION B

Elevation B

CHECKSTAND

TELEPHONE

P.O.S.COMPONENT STAND

FIRST SECT

ION OF POW

ER POLES T

O BE {\C10;5

'-9"}

CHECKOUT POWER POLE AND LANE LIGHT INSTALLATIONESD-62

{\C4;6/5/15}

ORIGINAL ISSUE DATE 12/19/07

1.

2.

3.

4.

Notes:

NOTE #3

Plan

Top

Front Right Side

POWERPOLE

POWER

POLE

POWER POLE

POWERPOLE &

Lc

METAL

SLOT IN

5.

SUPPORT

Detail 'A'

JOISTS

NOTE #5

6.

7.

NOTENo. 5

NOTENo. 5

PRINTER PLATFORMS SUPPLIED WITH POWER POLE.STORE FLOOR

SEE NOTE No. 8

8.

POWER POLE

FOLLOW INSTRUCTIONS FROM CHECKSTAND MANUFACTURER SUPPLIED WITH POWER POLES FOR ASSEMBLY & INITIAL INSTALLATION.POWER POLE WEIGHT IS SUPPORTED BY CHECKSTAND. CUT TOP OF POWER POLE AS NECESSARY AND ATTACH TO BUILDING STRUCTURE.WHEN TOP OF POWER POLE MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH A METAL SUPPORT, SUCH AS UNISTRUT CHANNEL, ACROSS NEAREST JOISTS.SECURELY ATTACH POWER POLE TO EXISTING STRUCTURE OR NEW METAL SUPPORT. DO NOT DRILL THRU, RUN BOLTS THRU, OR SCREW INTO POLE, PREVENT SHARP EDGES WHICH COULD DAMAGE COMMUNICATION CABLES.

3/8" x 5" INSIDE LENGTH x 4" INSIDE WIDTH SQUARE U-BOLT, TO CONNECT TO SLOTTED METAL SUPPORT (UNISTRUT) CHANNEL, WITHOUT DRILLING, IF POWER POLE IS CENTERED ON A SLOT IN METAL SUPPORT (UNISTRUT) CHANNEL. DO NOT OVER TIGHTEN U-BOLT NUTS, LEAVE LOOSE ENOUGH TO PERMIT VERTICAL MOVEMENT OF ROOF STRUCTURE. SIMILAR UNISTRUT HARDWARE MAY BE USED IN LIEU OF U-BOLTS, TO SECURELY ATTACH POWER POLES.HEIGHTS INDICATED RESULT IN POSITIONING BRACKETS TO PARTIALLY COVER SOME ACCESS HOLES.

METAL SUPPORT (UNISTRUT), SQUARE U-BOLT AND ATTACHMENT HARDWARE, MC CABLE SUPPLIED AND INSTALLED BY CONTRACTOR. ALL OTHER COMPONENTS SUPPLIED BY OWNER.LANE LIGHT IS SUPPLIED WITH 10'-0" LONG CORD AND STANDARD GROUNDED PLUG. CONTRACTOR TO RUN LANE LIGHTCORD THROUGH PREDRILLED HOLE IN POWER POLE AND OUT BOTTOM OF POWER POLE TO FACTORY INSTALLEDRECEPTACLE IN CHECKSTAND BASE DESIGNATED FOR LANE LIGHT, RECEPTACLE IS CONTROLLED BY FACTORY INSTALLEDSWITCH LOCATED ON CHECKSTAND.BEFORE TIGHTENING HARDWARE ON LANE LIGHT, ADJUST TO PARTIALLY CONCEAL HOLE. INSTALL SHELVES AND MONITORBRACKET AT PREDRILLED LOCATIONS. CONTRACTOR TO RUN POWER CORD THROUGH PREDRILLED HOLES IN POWER

12. {\C256;ONE COMPARTMENT POWER POLES, LANE LIGHTS, BRACKETS AND STANDS COME FROM CHECKSTAND MANUFACTURER SUPPLIED BY OWNER INSTALLED BY CONTRACTOR.}13. {\C256;ALL HIGH VOLTAGE CONDUCTORS MUST BE WRAPPED WITH STEEL JACKETING (MC CABLE).}

LANE LIGHT & BRACKET MOUNTED TOWARD SALES AREA.

METAL SUPPORT (UNISTRUT), OPENING FACING POWER POLE.

POWER POLE LOCATION POINT. REFER TO CHECKSTAND INSTALLATION INSTRUCTIIONS.

{\Le-PRO NUMBERS:}Power Pole #K-0001345

Cube for Lane Light #K-0037228Express Topper #K-0037230

Light Arm Bracket With Lamp #K-0015235

ADA Topper #K-0015366 (Deactivated)

Family Friendly Topper (Fred Meyer Only) #K-0045002Express Lane Topper (Fred Meyer Only) #K-0045000

(UNISTRUT)CHANNEL

JOIST GIRDER SEE DETAIL "A"METAL SUPPORT (UNISTRUT).

MONITOR BRACKET SUPPLIED WITH POWER POLE.

CHECKSTAND, MODELS & ACCESSORIES VARY

2'-2"3'-8"

7'-6

" A

.F.F

.

L

c 11 1

/2"1'-1 1/2"

Elevation

7

Elevation B

CHECKSTAND

TELEPHONE

P.O.S.COMPONENT STAND

ELEV. B

FIRST SECT

ION OF POW

ER POLES T

O BE {\C10;5

'-9"}

CAROUSEL CHECKOUT POWER POLE AND LANE LIGHT INSTALLATIONESD-62B

{\C4;6/5/15}

ORIGINAL ISSUE DATE 11/21/14

1.

2.

3.

4.

Notes:

5.

6.

7.

8.

FOLLOW INSTRUCTIONS FROM CHECKSTAND MANUFACTURER SUPPLIED WITH POWER POLES FOR ASSEMBLY & INITIAL INSTALLATION.POWER POLE WEIGHT IS SUPPORTED BY CHECKSTAND. CUT TOP OF POWER POLE AS NECESSARY AND ATTACH TO BUILDING STRUCTURE.WHEN TOP OF POWER POLE MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH A METAL SUPPORT, SUCH AS UNISTRUT CHANNEL, ACROSS NEAREST JOISTS.SECURELY ATTACH POWER POLE TO EXISTING STRUCTURE OR NEW METAL SUPPORT. DO NOT DRILL THRU, RUN BOLTS THRU, OR SCREW INTO POLE, TO PREVENT SHARP EDGES WHICH COULD DAMAGE COMMUNICATION CABLES.

3/8" x 5" INSIDE LENGTH x 4" INSIDE WIDTH SQUARE U-BOLT, TO CONNECT TO SLOTTED METAL SUPPORT (UNISTRUT) CHANNEL, WITHOUT DRILLING, IF POWER POLE IS CENTERED ON A SLOT IN METAL SUPPORT (UNISTRUT) CHANNEL. DO NOT OVER TIGHTEN U-BOLT NUTS, LEAVE LOOSE ENOUGH TO PERMIT VERTICAL MOVEMENT OF ROOF STRUCTURE. SIMILAR UNISTRUT HARDWARE MAY BE USED IN LIEU OF U-BOLTS, TO SECURELY ATTACH POWER POLES.HEIGHTS INDICATED RESULT IN POSITIONING BRACKETS TO PARTIALLY COVER SOME ACCESS HOLES.

METAL SUPPORT (UNISTRUT), SQUARE U-BOLT AND ATTACHMENT HARDWARE, MC CABLE SUPPLIED AND INSTALLED BY CONTRACTOR. ALL OTHER COMPONENTS SUPPLIED BY OWNER.LANE LIGHT IS SUPPLIED WITH 10'-0" LONG CORD AND STANDARD GROUNDED PLUG. CONTRACTOR TO RUN LANE LIGHTCORD THROUGH PREDRILLED HOLE IN POWER POLE AND OUT BOTTOM OF POWER POLE TO FACTORY INSTALLEDRECEPTACLE IN CHECKSTAND BASE DESIGNATED FOR LANE LIGHT, RECEPTACLE IS CONTROLLED BY FACTORY INSTALLEDSWITCH LOCATED ON CHECKSTAND.BEFORE TIGHTENING HARDWARE ON LANE LIGHT, ADJUST TO PARTIALLY CONCEAL HOLE. INSTALL SHELVES AND MONITORBRACKET AT PREDRILLED LOCATIONS. CONTRACTOR TO RUN POWER CORD THROUGH PREDRILLED HOLES IN POWER

12. {\C256;ONE COMPARTMENT POWER POLES, LANE LIGHTS, BRACKETS AND STANDS COME FROM CHECKSTAND MANUFACTURER SUPPLIED BY OWNER INSTALLED BY CONTRACTOR.}13. {\C256;ALL HIGH VOLTAGE CONDUCTORS MUST BE WRAPPED WITH STEEL JACKETING (MC CABLE).}

{\Le-PRO NUMBERS:}

Cube for Lane Light #K-0037228Express Topper #K-0037230

Light Arm Bracket With Lamp #K-0015235

ADA Topper #K-0015366 (Deactivated)

Family Friendly Topper (Fred Meyer Only) #K-0045002

Express Lane Topper (Fred Meyer Only) #K-0045000

NOTE #3

Elevation

Plan

Top

Front Right Side

POWERPOLE

POWERPOLE

POWER POLE

POWERPOLE &

Lc

METAL

SLOT INSUPPORT

Detail 'A'

JOISTS

NOTE #5

NOTENo. 5

NOTENo. 5

STORE FLOOR

METAL SUPPORT (UNISTRUT), OPENING FACING POWER POLE.

POWER POLE LOCATION POINT. REFER TO CHECKSTAND INSTALLATION INSTRUCTIIONS.

(UNISTRUT)CHANNEL

JOIST GIRDERSEE DETAIL "A"METAL SUPPORT (UNISTRUT).

CHECKSTAND, MODELS & ACCESSORIES VARY7'-6

" A.F

.F.

2'-10"

3'-0

"10

1/2

"

5"

Lc

FIR

ST

SE

CT

ION

OF

PO

WE

R P

OLE

ST

O B

E A

FU

LL

8'-0

" S

EC

TIO

N.

PRINTER PLATFORMS SUPPLIED WITH POWER POLE.MONITOR BRACKET SUPPLIED WITH POWER POLE.

SEE NOTE No. 8

LANE LIGHT & BRACKET ONLY IF CHECKSTAND USED AT FRONT. MOUNT TOWARD SALES AREA.POWER POLE

IMAGES SHOWN ARE FOR METRO CHECKOUT - LEFT HAND. RIGHT HAND CHECKOUT MIRROR IMAGE.

Power Pole Ceiling Metro Universal #K-0052766

1

EURO - METRO CHECKOUT POWER POLE AND LANE LIGHT INSTALLATIONESD-62C

{\C4;6/5/15}

ORIGINAL ISSUE DATE 6/5/15

MASTER SPECIFICATION DETAIL MASTER SPECIFICATION DETAIL

DATE:

SCALE: NONE

DRAW

N:DATE:

SCALE: NONEDRAWN:

DATE:

SCALE: NONE

DRAW

N:DATE:

SCALE: NONE

DRAW

N:DATE:

SCALE: NONEDRAWN:

DATE:

SCALE: NONEDRAWN:

TRACK INSTALLATION MONOPOINT INSTALLATION

NOTES:

ELECTRICAL POWER SUPPLY

AIRCRAFT CABLE. SEE NOTES No. 1 & No. 3.

ELECTRICAL POWER SUPPLY MONOPOINT CANOPY ADAPTER

THREADED ROD. SEE NOTES No. 1 & No. 4.

THREADED ROD COUPLING, IF NEEDED.

EXTEND CABLE OVER JOIST FLANGES AND SECURE WITH CABLE LOCK, AS INDICATED. EXTEND THREADED ROD UP BETWEEN JOIST FLANGES AND SECURELY ATTACH TO JOIST, CONNECTION SEE DETAIL 'B'

1.

2.

3.

4.

FIXTURE SUPPORT AND POWER CONNECTION FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AS REQUIRED BY GOVERNING CODES.THIS DETAIL IS ASSOCIATED WITH THE INSTALLATION OF TR15, TR16, TR17, TR18 AND TR19 LED TRACK LIGHT FIXTURES. HANG ELECTRIFIED TRACK FOR MULTIPLE FIXTURES WITH AIRCRAFT CABLE AND THREADED ROD FOR MONOPOINT FIXTURE INSTALLATION. THREADED ROD SHOULD BE USED TO SUPPORT ELECTRIFIED TRACK AT LOCATIONS WHERE HVAC DIFFUSERS CAN CAUSE TRACK TO SWAY.

\A1;INSTALL ELECTRIFIED TRACK WITH MIN 1/16" DIAMETER STANDARD STEEL WIRE ROPE OR STAINLESS STEEL AIRCRAFT CABLE WITH CABLE LOCK CONNECTED TO 1/4" EYE BOLT THRU FACTORY DRILLED HOLES WITH LOCK NUT WITH NYLON INSERT ON BOTTOM AND STANDARD JAMB NUT ON TOP OF THE TRACK. 4' TRACK TO BE INSTALLED BY 2 POINTS OF ATTACHMENT, 8' BY 3 POINTS AND 12' BY 4 POINTS.

LIGHT TRACK LENGTH AND HEIGHT ABOVE FLOOR VARIES PER LOCATION. REFER TO LIGHTING PLAN FOR MOUNTING HEIGHT AND LOCATIONS.\A1;WHERE MOUNTING CABLE OR THREADED ROD MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH METAL SUPPORT BETWEEN STEEL USING STEEL CHANNEL 7/8" MIN, 1" x 1" ANGLE IRON OR 3/4" IMC OR RIGID CONDUIT.

6.

5.

\A1;MONOPOINT FIXTURE TO BE HUNG BY 1/4" THREADED ROD ATTACHED TO STEEL AND JUNCTION BOX, FOR LONGER DROPS INSTALL THREADED COUPLING AS HIGH AS POSSIBLE. ATTACH TO BOTTOM CHORD OF JOIST BY EXTENDING THREADED ROD BETWEEN JOIST FLANGES AND HOLE IN JUNCTION BOX BY ATTACHING WITH LOCK NUT WITH NYLON INSERT ON TOP AND STANDARD JAMB NUT & WASHER ON BOTTOM.

SEE DETAIL 'B' FOR TYPICAL THREADED ROD CONNECTION

NYLON INSERT LOCK NUT AND WASHERJAMB NUT AND WASHER

SEE DETAIL 'A' FOR TYPICAL EYE BOLT CONNECTION

JAMB NUT

DETAIL 'A' DETAIL 'B'

JUNCTION BOX, CONNECTION SEE DETAIL 'B'

DATE:

SCALE: NONEDRAWN:LED TRACK LIGHT & MONOPOINT DETAILESD-50

{\C4;11/5/13}

NOTES:1.

2.

FIXTURE SUPPORT AND POWER CONNECTION FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AS REQUIRED BY GOVERNING CODES.

REFER TO LIGHTING PLAN FOR MOUNTING HEIGHT AND LOCATIONS.

\A1;WHERE THREADED ROD MISSES EXISTING STRUCTURAL STEEL, PROVIDE & SECURELY ATTACH METAL SUPPORT BETWEEN STEEL USING STEEL CHANNEL 7/8" MIN, 1" x 1" ANGLE IRON OR 3/4" IMC OR RIGID CONDUIT.4.

3.

\A1;PENDANT TO BE HUNG BY 1/4" THREADED ROD ATTACHED TO STEEL AND JUNCTION BOX, FOR LONGER DROPS INSTALL THREADED COUPLING AS HIGH AS POSSIBLE. ATTACH TO BOTTOM CHORD OF JOIST BY EXTENDING THREADED ROD BETWEEN JOIST FLANGES AND HOLE IN JUNCTION BOX BY ATTACHING WITH LOCK NUT WITH NYLON INSERT ON TOP AND STANDARD JAMB NUT & WASHER ON BOTTOM.

NYLON INSERT LOCK NUT AND WASHERJAMB NUT AND WASHER

DETAIL 'B'

EXTEND THREADED ROD UP BETWEEN JOIST FLANGES AND SECURELY ATTACH TO JOIST, CONNECTION SEE DETAIL 'B'

SEE DETAIL 'B' FOR TYPICAL THREADED ROD CONNECTION THREADED ROD COUPLING, IF NEEDED.

THREADED ROD. SEE NOTE No. 2.

ELECTRICAL POWER SUPPLY

CANOPY PLATE

JUNCTION BOX

PENDANT LIGHT INSTALLATION

PENDANT. SEE NOTE No. 4.

6'-0" 6'-0" ADJUSTABLE CORD PROVIDED WITH FIXTURE

PENDANT LIGHT MOUNTING DETAILESD-50A

{\C4;12/5/13}

ORIGINAL ISSUE DATE 12/5/13

MASTER SPECIFICATION DETAIL

DATE:

SCALE: NONEDRAWN:

MASTER SPECIFICATION DETAIL

ISSUE DATE:

PROJECT NO.:

SHEET NUMBER:

NO. REVISIONS

K n o x v i l l e , T e n n e s s e e 37915phone: 865-546-9374 fax: 865-673-9028e - m a i l : [email protected]

111 E. J a c k s o n A v e n u e S u i t e "1 0 1 "

FURNISHED BY DOLLAR & EWERS ARCHITECTURE, INC.

C O P Y R I G H T

THEY ARE TO BE USED ONLY WITH RESPECT TO THIS PROJECTPROJECT AND ARE NOT TO BE USED WITH ANY OTHER

ARE AND SHALL REMAIN THE PROPERTY OF DEA, INC.

FOR EACH PARTY TO THE CONTRACT, SUCH DOCUMENTS ARETO BE RETURNED OR SUITABLY ACCOUNTED FOR TO DEA, INC.ON REQUEST AT THE COMPLETION OF THE WORK. SUBMISSIONDISTRIBUTION TO MEET OFFICIAL REGULATORY REQUIREMENTSOR FOR OTHER PURPOSES IN CONNECTION WITH THE PROJECTIS NOT TO BE CONSTRUED AS PUBLICATION IN DEROGATIONDEA'S COMMON LAW COPYRIGHT OR OTHER RESERVED RIGHTS.

PROJECT. WITH THE EXCEPTION OF ONE CONTRACT SET

C O P Y R I G H TALL DRAWINGS, SPECIFICATIONS AND COPIES THEREOF

A W

ith-in

-the-

Wal

ls R

emod

el fo

r:

KR

OG

ER S

TOR

E #U

-523

- D

ICK

SON

143

HEN

SLEE

DR

IVE,

DIC

KSO

N, T

ENN

ESSE

E 37

055

DECEMBER 16, 2020

220269 /20072

C

E E

1M

T o.N ETA FO

SMO

75 30 E

ET NNES

SE

C

R

SE

VR E D

ERE N R

AGRICULTUREXVIK

TREGI

SNG

II

ERE

E.NI N

O4

THIS DRAWING IS GENERALLY DIAGRAMMATIC AND,EXCEPT WHERE SPECIFICALLY DIMENSIONED ORDETAILED, INDICATES THE GENERAL ARRANGEMENTOF THE WORK. THE CONTRACTOR SHALL INSTALL HISWORK TO CONFORM AS NEARLY AS POSSIBLE TO THELOCATIONS AND ARRANGEMENTS SHOWN. COORDINATETHE WORK WITH ALL OTHER TRADES TO AVOID

THE EXPRESS WRITTEN AUTHORIZATION OF NORRIS &NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT

OF NORRIS & ASSOCIATES ENGINEERS INC. AND SHALLTHIS DRAWING AND IT'S CONTENTS ARE THE PROPERTY

ENGINEERS

865-584-3065FAX:

PHONE:

KNOXVILLE, TN5518 WALLWOOD ROAD

37912

865-584-3063

INC.

INTERFERENCES.

ASSOCIATES ENGINEERS INC.

ASSOCIATESNORRIS &

www.norrisengineers.com E1.3-2

ELEC

TRIC

AL

STA

ND

AR

D D

ETA

ILS

(ESD

'S)