motor circuit protectors - ee controls

26
MOTOR CIRCUIT PROTECTORS Modern design to meet the increasing industrial challenges

Upload: others

Post on 26-May-2022

35 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MOTOR CIRCUIT PROTECTORS - EE Controls

MOTOR CIRCUIT PROTECTORS

Modern design to meet the increasing industrial challenges

Page 2: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

2 Motor Circuit Protectors - MN Series

Motor Protective Circuit BreakerSummary

Motor Protective Circuit Breakers MN32 06

Motor Protective Circuit Breaker MN65 08

Motor Protective Circuit Breakers - Accessories 09

Motor Protective Circuit Breakers - Technical Data 14

Motor Protective Circuit Breaker - Dimensions 20

Motor Protective Circuit Breakers - Overview 04

Page 3: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

3Motor Circuit Protectors - MN Series

Motor Protective Circuit Breakers of MN line, the best solution for operating and protection of your electric motor.

CharacteristicsType Conventional starter Compact starter

Number of components 3 components (fuse1) + contactor+ termal O/L relay) 1 component (motor circuit breaker termomagnetic)

Short-circuit protection Yes Yes

Switching Yes Yes

Motor overload protection Yes Yes

Reset after short-circuit No Yes

Reset after overload Yes Yes

Overall dimension Larger Smaller

Mounting time Long Short

Scale cover No Yes (with accessory)

Safety disconnect for maintenance Fuse removal Padlock on handle/button in OFF position

Operational status signalling No Yes

Protection degree Smaller Bigger

Number of connections Bigger Smaller

Maximum operation per hour 15 operations/hour 15 operations/hour

Operation mode Remote Manual

3 Functions in a Single Product!

Switching

Overload protection

Short-circuit protection

I >

Electrical DiagramElectrical Diagram

Short-circuit protection

Switching

Overload protection

Note: 1) Fuse installed on fuse holders IP00.

Page 4: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

4 Motor Circuit Protectors - MN Series

Motor Protective Circuit Breakers MN Series - Overview

EEC's new generation of Manual Motor Protectors provide a very compact solution for operation and protection in motor control applications. The NEC requires four functions to be considered a combination motor starter: Motor Disconnect, Branch Circuit Protection, Motor Controller and Motor Overload Protection. EEC's MN series meets all of these requirements, and the UL/CSA requirements for Self-Protected Motor Controllers to be used in Type-E & F applications. With worldwide approvals the EEC's MN serie s can be used in a variety of applications all over the world.

Combination starters are the most common type of packaged motor controllers. They are called combination because of their construction and combined functions required by the US National Electric Code (NEC) and Canadian Electrical Code (CSA) Motor Disconnect, Motor Branch Circuit Protection, Motor Controller and Motor Overload Protection. UL & CSA (hamonized) currently recognizes six different types of combination starters that meet the requirements of a motor branch circuit.

Constructions Types A through D are traditionalstarters that use either a listed disconnect switch andfuses or a listed circuit breakers as the disconnectmeans and for short circuit protection. Each type usesa separate UL 508 & CSA 22.2 #14 listed motor controller and overload relay. Recently revisions on UL508 & CSA 22.2 #14 introduced the Type "E" and Type "F" starters.

Type "E" starter is a self-protected combination motor controller that combines in a single device all the required functions of a combination starter and eliminates any additional requirements for upstream fuses or circuit breakers. These starters clear faults within their rating without sustaining damage to themselves or the rest of the system, being able to get back into operation. There are two arrangements for aType E starter: manual (as stand-alone) and associatedwith a contactor. Both are submitted to the same testssequences.

Type "F" starter consists of a listed manual Type "E" combined with a UL508 & CSA 22.2 #14 listed contactor. The differencebetween the two types is related to the absence of self-protected characteristic; hence, Type "F" has softened tests sequences allowing damages on the contactor after a fault.

Tests performed in order to fulfill the Type "E" requirements are considered the hardest in UL & CSA, including short-circuit and endurance tests on the same sample. As a comparison, UL Type "E" exceeds the requirements for Type "F" and IEC60947-4-1 Coordination type 2.

EEC's self-protected combination Type "E" combinesall of these functions within a single product for a manual operation or within a set of two products (with a listed contactor) for a remote operation. They are preferred for a wide range of applications where traditional full voltage combination starters have been required. Some examples are: Pumps, Industrial Washing Machines, Compressors, Blowers, Cutting Machines, Conveyors, Lumber Processing and many others.

The Manual Type "E" Starter is a stand-alone product that ranges from fractional up to 60Hp @ 575V motors (0.16 to 65A) with up to 65KA @ 480V and 25KA @ 600V interrupting shortcircuit capability (MN65). Together with a complete line of accessories, the MN series are a compact and reliable solution for starting and protecting motors.

In addition to its popular line of UL/CSA enclosed starters,EEC is now introducing a new line of combination starters, with optional ratings from NEMA 1, 4, 4X, 12 & 13. EEC's enclosed Type "E" & "F" Starter featuring as standard a handle for disconnect means - MN Series are "Suitable as a Motor Disconnect" - through the door and a contactor for remote operation. Provisions for control circuit transformer, operators, pilot lights and a variety of accessories are available to meet each applications requirements.

Page 5: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

5Motor Circuit Protectors - MN Series

Introducing our latest in technology and design, EEC's MN Series Motor Circuit Protectors save panel space and can be used in most applications in motor control.It combines short-circuit and motor overload protections in just one component. These devices include a three-position rotary ON-TRIP-OFF handle, which can be padlocked in the OFF position.

MN32 up to 32 A MN65 up to 65 A

Gene

ral t

echn

ical

dat

a

Maximum rated current Imax(Iu) 32 A 65 A

Number of poles 3 3

Short-circuit release 13 x lu max 13 x lu max 13 x lu max 13 x lu max

Rated operational voltage Ue 600 V 600 V 600V 600 V

Rated frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz

Utilization categoryIEC 60 947-2 (circuit breaker) A A A A

IEC 60 947-4-1 (motor starter) AC-3 AC-3 AC-3 AC-3

UL/CSA Approved Yes Yes Yes Yes

UL 508 Type "F" Certified Yes No Yes No

UL 508 Type "E" Certified Yes No Yes No

Tripping test Yes Yes Yes Yes

Overload protection Yes No Yes No

Phase failure sensitivity Yes No Yes No

Tripping indication Yes Yes Yes Yes

Tripping Class 10 - 10 -

Mechanical life Number of operations 100,000 100,000 50,000 50,000

Electrical life Number of operations 100,000 100,000 25,000 25,000

Temperature compensation -20...+60 °C - -20...+60 °C -

Type of protection ThermomagneticMagnetic*

ThermomagneticMagnetic*

* - Special Order Only * - Special Order Only

Setting overload release

Ir(A)

Reference code

Terminal type Screw

0.1...0.16 MN32H001 MC32H001 - -0.16...0.25 MN32H002 MC32H002 - -0.25...0.4 MN32H004 MC32H004 - -0.4...0.63 MN32H006 MC32H006 - -0.63...1 MN32H010 MC32H010 - -1...1.6 MN32H016 MC32H016 - -

1.6...2.5 MN32H025 MC32H025 - -2.5...4 MN32H040 MC32H040 - -4...6.3 MN32H063 MC32H063 - -6.3...10 MN32H100 MC32H100 - -10...16 MN32H160 MC32H160 - -16...20 MN32H200 MC32H200 - -20...25 MN32H250 MC32H250 - -25...32 MN32H320 MC32H320 - -32...40 - - MN65H400 MC65H40040...50 - - MN65H500 MC65H50050...65 - - MN65H650 MC65H650

Motor Protective Circuit Breakers MN Series - Overview

Page 6: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

6 Motor Circuit Protectors - MN Series

Motor Protective Circuit Breaker MN32 - Overview

1 - Motor protective circuit breaker 2 - Feeder terminal3 - Three-phase busbars4 - Push-in-lugs5 - Side auxiliary contact block 6 - Undervoltage release URMP or shunt release7 - Front auxiliary contact block8 - Door coupling rotary handle RMMP9 - Connector - For LSN4, LSN5, LSN7, LSN1110 - Contactors - LSN4, LSN5, LSN7, LSN1111 - Door coupling rotary handle

12 - Front plate13 - Standard insulated enclosure14 - Large insulated enclosure15 - Trip signalling block16 - Connector - For LSN15, LSN1817 - Contactors - LSN15, LSN1818 - Connector - For BA09, BA16, BA2519 - Mini-contactor - BA09, BA16, BA220 - Feeder terminal for “Type E” motor starter according to UL21 - Current limiter Unit (Special Order)

1212

11

11

1818

1616

19191010 1717

99

11

77

88

1515

55

1166

3344

44

2020

2121

1414

1111

11

1313

22

Page 7: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

7Motor Circuit Protectors - MN Series

Motor Protective Circuit Breaker MN32 - Selection Table

J • Suitable for manual motor controller, group installation, Tap conductor and combination starters - Type "E" & Type "F"

J • Built-in protection: disconnect means, short-circuit protection, motor control and overload protection

J • Short-circuit interrupting capacity up to 50kA @ 480Vac & 25kA @ 600Vac J • Fixed short-circuit release 13 x Iu J • Phase loss sensitivity J • Ambient temperature compensation -20…+60ºC ( -4…+140ºF)

Single-phase motor 50/60 Hz Three-phase motor 50/60 Hz Rated current

Iu(A)

Setting overload release

Ir(A)

Instantaneous magnetic trip

Irm(A)

Reference code

Weight

Lbs

120 V

hp

230 V

hp

208 V

hp

230 V

hp

480 V

hp

600 V

hp

- - - - - - 0.16 0.1...0.16 2.0 MN32H001

0.8

- - - - - - 0.25 0.16...0.25 3.2 MN32H002

- - - - - - 0.4 0.25...0.4 5.2 MN32H004

- - - - - 1/4 0.63 0.4...0.63 8.1 MN32H006

- - - - 1/2 1/2 1 0.63...1 13 MN32H010

- 1/10 1/4 1/3 3/4 1 1.6 1...1.6 20.8 MN32H016

- 1/6 1/2 1/2 1.5 1.5 2.5 1.6...2.5 32.5 MN32H025

1/8 1/3 3/4 1 2 3 4 2.5...4 52 MN32H040

1/4 3/4 1.5 1.5 3 5 6.3 4...6.3 81.9 MN32H063

1/2 1.5 3 3 5 7.5 10 6.3...10 130 MN32H100

1 3 5 5 10 15 16 10...16 208 MN32H160

1.5 3 5 7.5 15 15 20 16...20 260 MN32H200

2 3 7.5 7.5 15 20 25 20...25 325 MN32H250

- 5 10 10 20 25 32 25...32 416 MN32H320

Motor Protective Circuit Breaker MN32H - Thermomagnetic

Motor Protective Circuit Breaker MC32H - Magnetic

Single-phase motor 50/60 Hz Three-phase motor 50/60 Hz Rated current

Iu(A)

Instantaneous magnetic trip

Irm(A)

Reference code

Weight

Lbs

120 V

hp

230 V

hp

208 V

hp

230 V

hp

480 V

hp

600 V

hp

- - - - - - 0.16 2.0 MC32H001

0.8

- - - - - - 0.25 3.2 MC32H002

- - - - - - 0.4 5.2 MC32H004

- - - - - 1/4 0.63 8.1 MC32H006

- - - - 1/2 1/2 1 13 MC32H010

- 1/10 1/4 1/3 3/4 1 1.6 20.8 MC32H016

- 1/6 1/2 1/2 1.5 1.5 2.5 32.5 MC32H025

1/8 1/3 3/4 1 2 3 4 52 MC32H040

1/4 3/4 1.5 1.5 3 5 6.3 81.9 MC32H063

1/2 1.5 3 3 5 7.5 10 130 MC32H100

1 3 5 5 10 15 16 208 MC32H160

1.5 3 5 7.5 15 15 20 260 MC32H200

2 3 7.5 7.5 15 20 25 325 MC32H250

- 5 10 10 20 25 32 416 MC32H320

Note: 1) Some motors characteristics may vary according to each manufacturer.

Page 8: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

8 Motor Circuit Protectors - MN Series

Motor Protective Circuit Breaker MN65 - Overview

1

5

6

2

2

3

4

7

8

9

10

1 - Motor protective circuit breaker2 - Push-in-lugs3 - Side auxiliary contact block4 - Undervoltage release or shunt release5 - Frontal auxiliary contact block

6 - Trip signalling block7 - Door coupling rotary handle - NEMA 3R/128 - Door coupling rotary handle - NEMA 4/4X9 - Scale cover10 - Feeder terminal for “Type E” motor starter according to UL/CSA

Motor Protective Circuit Breaker MN65 - Selection Table J • Suitable for manual motor controller, group installation, Tap conductor and

combination starters - Type "E" & Type "F" J • Built-in protection: disconnect means, short-circuit protection, motor control

and overload protection J • Short-circuit interrupting capacity up to 35kA @ 480Vac & 10kA @ 600Vac J • Fixed short-circuit release 13 x Iu J • Phase loss sensitivity J • Ambient temperature compensation -20…+60ºC ( -4…+140ºF)

Single-phase motor 50/60 Hz Three-phase motor 50/60 Hz Rated current

Iu(A)

Setting overload release

Ir(A)

Instantaneous magnetic trip

Irm(A)

Reference code

Weight

Lbs

120 V

hp

230 V

hp

208 V

hp

230 V

hp

480 V

hp

600 V

hp

3 7.5 - 15 25 30 40 32...40 520 MN65H400

2.36- 10 15 15 30 40 50 40...50 650 MN65H500

5 10 20 20 50 60 65 50...65 845 MN65H650

Motor Protective Circuit Breaker MN65H - Thermomagnetic

Motor Protective Circuit Breaker MC65H - Magnetic

Single-phase motor 50/60 Hz Three-phase motor 50/60 Hz Rated current

Iu(A)

Instantaneous magnetic trip

Irm(A)Reference code

Weight

Lbs

120 V

hp

230 V

hp

208 V

hp

230 V

hp

480 V

hp

600 V

hp

3 7.5 - 15 25 30 40 520 MC65H400

2.36- 10 15 15 30 40 50 650 MC65H500

5 10 20 20 50 60 65 845 MC65H650

Page 9: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

9Motor Circuit Protectors - MN Series

For use with Illustrative pictureAuxiliary contacts

Reference codeWeight

LbsNO NC

MN32 / MC32MN65 / MC65

1 1 MNA11S

0.012 - MNA20S

- 2 MNA02S

For use with Illustrative pictureAuxiliary contacts

Reference codeWeight

LbsNO NC

MN32 / MC32MN65 / MC65

1 1 MNA11T 0.06

Front Auxiliary Contact Block - MNA11T

Left Side Auxiliary Contact Block

Motor Protective Circuit Breakers - Accessories

For use with Illustrative picture Description Reference codeWeight

Lbs

MN32 / MC32MN65 / MC65

- Equipped with 2 auxiliary contacts (1NO + 1NC) for overload trip signalling and 2 other auxiliary contacts (1NO + 1NC) for short-circuit trip signalling.

- To reset the circuit breaker after a short-circuit, the flag must be manually reset after the cause of the failure has been solved.

- Lateral auxiliary contacts can be assembled together with the trip signalling block.

- Left side assembly only.

MNTSB 0.29

Trip Signalling Block

Undervoltage Release

For use with Illustrative picture Voltage1) Reference codeWeight

Lbs

MN32 / MC32MN65 / MC65

Note: - Operating voltage > 0.85 x Ue

- Non operating voltage 0.35...0.7 x Ue

24 V 50/60 Hz110 V 50 Hz / 120 V 60 Hz

208 V 50 Hz / 200-240 V 60 Hz230-240 V 50 Hz / 277 V 60 Hz

325 V 50 Hz / 380 V 60 Hz400-415 V 50 Hz / 480 V 60 Hz

500 V 50 Hz / 600 V 60 Hz

MNAUVTGMNAUVTAMNAUVTCMNAUVTHMNAUVTDMNAUVTEMNAUVTF

0.29

Notes: 1) Other voltages avaliable upon request

Page 10: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

10 Motor Circuit Protectors - MN Series

Motor Protective Circuit Breakers - Accessories

Notes: 1) Other voltages avaliable upon request

For use with Illustrative picture Voltage1) Reference codeWeight

Lbs

MN32 / MC32MN65 / MC65

Note: - Operating voltage > 0.7 x Ue

20-24 V 50/60 Hz100-127 V 50/60 Hz200-240 V 50/60 Hz365-440 V 50/60 Hz

MNASHTGMNASHTAMNASHTCMNASHTE

0.29

Shunt Release

Block Modules for Motor Protective Circuit Breaker Assembly + Contactors

For use with Illustrative picture Description ContactorsReference

codeWeight

Lbs

MN32 / MC32

- For direct connection (electrical and mechanical) of motor circuit breakers to contactors.

Note: - Not applicable to LSN contactors with DC coils, but suitable for use with BA contactors with DC coils

BA09...BA16 MNADBA1

0.06

BA25 MNADBA2

LSN4...LSN11LSN15,LSN18

MNADLS1MNADLS2

Door Coupling Rotary Handle

For use with Illustrative picture DescriptionHandle color

Reference codeWeight

Lbs

MN32 / MC32

- Degree of protection IP55; - Shows circuit breaker position “I”(ON) or “O”(OFF);- Panel door can only be opened in OFF position;- Adjustable shaft length. There are shaft size: 330-355 mm. - To assembled the handle on the circuit breaker the shaft must have a length of at least 80 mm;- Up to 3 padlocks can be used in the OFF position. This blocks

circuit breaker operation and opens panel door;- Handle can be mounted on panels with a thickness of 1 to 5 mm;- Handle can be assembled even with circuit breaker turned in

90º position.

Black / Grey

MNAHS1N1

0.56

Red/Yellow

MNAHR1N1

MN65 / MC65

Black / Grey

MNAHS2N1

Red/Yellow

MNAHR2N1

MN32 / MC32- Panel door can be opened in ON position (thermometry);- Degree of protection: IP65/Nema 4X;- Shows circuit breaker position “I”(ON) or “O”(OFF);- Adjustable shaft length. There are shaft size: 330-355 mm. - To assembled the handle on the circuit breaker the shaft must have a length of at least 80 mm;- Up to 3 padlocks can be used in the OFF position. This blocks

circuit breaker operation and opens panel door;- Handle can be mounted on panels with a thickness of 1 to 5 mm

Black / Grey

MNAHS1N4X

Red/Yellow

MNAHR1N4X

MN65 / MC65

Black / Grey

MNAHS2N4X

Red/Yellow

MNAHR2N4X

Page 11: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

11Motor Circuit Protectors - MN Series

Front Plate

For use with Illustrative picture DescriptionHandle color

Reference codeWeight

Lbs

MN32 / MC32

- For motor protective circuit breaker assembly in panel door or side

- Degree of protection: IP55 - MN32 fits directly into base - Rotary handle in enclosure- Handle can be locked with up to 3 padlocks at OFF position - Signalling lamps can be installed on enclosure

Black / Grey

MNE55FB 0.44

Red / Yellow MNE55FY 0.44

For use with Illustrative picture Description Terminals Handle color Reference codeWeight

Lbs

MN32 / MC32

- Empty plastic enclosure- Degree of protection IP55- 2 inputs/outputs for cable gland ØPG16 on top/bottom, and 2 inputs/outputs ØM20 in the back- Rotary handle on the cover- Handle can be locked with up to 3 padlocks in the “OFF” position- Color: cover (gray RAL 7035) and base (black RAL 7021).

With neutral and ground terminals

Black / grey MNE55HB 0.93

Red / Yellow MNE55HR 0.93

Standard Insulated Enclosure - Surface Mount

Motor Protective Circuit Breakers - Accessories

For use with Illustrative picture Lamp color Voltage Reference codeWeight

Lbs

All models

Red

24 V 50/60 Hz / V dc MNILRG

0.012

110...130 V 50/60 Hz MNILRA

210...230 V 50/60 Hz MNILRC

400...575 V 50/60 Hz MNILRF

Green

24 V 50/60 Hz / V dc MNILGG

110...130 V 50/60 Hz MNILGA

210...230 V 50/60 Hz MNILGC

400...575 V 50/60 Hz MNILGF

White

24 V 50/60 Hz / V dc MNILWG

110...130 V 50/60 Hz MNILWA

210...230 V 50/60 Hz MNILWC

400...560 V 50/60 H75 MNILWF

Pilot Lights

Page 12: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

12 Motor Circuit Protectors - MN Series

For use with Illustrative picture Description Contactors Reference codeWeight

Lbs

MN32 / MC32

Used for direct on line starters

45 mm width

BA09...BA25LSN4…LSN11

MNAPKD 0.06

MN32 / MC32

Used for reversing starters

90 mm width

2 x BA09...BA252 x LSN4…LSN11

MNAPKR 0.06

MN32 / MC32

Used for wye-delta motor starters

90 mm width

2 x BA09...BA252 x LSN4…LSN11

MNAPKW 0.06

Motor Protective Circuit Breaker Mounting Adapter + Contactor

Motor Protective Circuit Breakers - Accessories

For use with Illustrative picture Description Reference codeWeight

Lbs

MN32 / MC32

- Block module for “ Type E“ Combination motor Controller” only required in use with MN32B - Bus Links

- Rated insulation voltage: 690 V ac; - Ie: 63 A.- Terminals: 8-20 AWG.

MNAEAD1 0.1

MN65 / MC65

- Block module for “ Type E“ Combination motor Controller” only required in use with bus links or wire jumpers

- Rated insulation voltage: 690 V ac;- Ie: 63 A;- Terminals: 4-8 AWG.

MNAEAD2 0.4

Three-Phase Feeder Terminal

For use with Illustrative picture Description Reference codeWeight

Lbs

MN32MC32

For protecting electrical circuits where extra high shortcircuitbreaking capacity is required: - 100kA @ 480VAC & 50KA @ 600V

Note: This accessory must be used together with a MNmotor protector.

MNACLT 0.69

Current Limiter

Page 13: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

13Motor Circuit Protectors - MN Series

Three-Phase Busbars for Circuit Breakers Without Side Fitted Auxiliary Contacts

For use with Illustrative picture DescriptionNumbers of circuit

protectorReference code

Weight Lbs

MN32 / MC32

- For parallel blocking of side-by-side mounted circuit breakers. without side auxiliary contacts -

- Enables the use of frontal auxiliary contact block

- Ue: 600 V ac- Ie: 63 A

2 MN32BN02 0.01

3 MN32BN03 0.16

4 MN32BN04 0.23

5 MN32BN05 0.27

Three-Phase Busbars for Motor Protection Circuit Breakers with Side Fitted Auxiliary Contacts

For use with Illustrative picture DescriptionNumbers of circuit

protectorReference code

Weight Lbs

MN32 / MC32

- For parallel blocking of side-by-side mounted circuit breakers

- Enables the use of side auxiliary contact block mounted on each motor protective circuit breaker

- Ue: 600 V ac - Ie: 63 A.

2 MN32BD02 0.01

3 MN32BD03 0.16

4 MN32BD04 0.23

5 MN32BD05 0.27

Motor Protective Circuit Breakers - Accessories

Scale Cover / Terminal Adjustable Dial

Panel Screw Mounting Adaptor Kits - Direct Mount vs. Din-rail Mount (Din-rail Integrated with MN Series)

For use with Illustrative picture Description Reference codeWeight

Lbs

MN32 / MC32MN65 / MC65

Protects the current adjustment dial against direct contact while enabling the adjusted current to be viewed.

MNADCP 0.01

For use with Illustrative picture Description Reference codeWeight

Lbs

MN32 / MC32MN65 / MC65

For direct assembly of motor protective circuit breaker onto any surface using screws.

MNASPAK 0.01

Page 14: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

14 Motor Circuit Protectors - MN Series

The MN32 and MN65 motor protective circuit breakers can also be used for operating continuous current loads. For such operation it is necessary to connect 2 or 3 poles in series.See recommended circuits and their voltage limits in the table on the right.

Time constant t = 5ms

Short-circuit breaking capacity Icu = 10 kA for all configurations.

Circuits Max. V dc Notes

150 V dcSystem notgrounded

2 pole series connected

300 V dcSystem

grounded2 pole series connected

450 V dcSystem

grounded 3 pole series connected

DC Operation

Reference code MN32 MC32 MN65 MC65

Maximum rated current Imax(Iu) 32 A 32 A 65 A 65 A

Number of poles 3 3 3 3

Instantaneous short-circuit 13 x Iemax. 13 x Iemax. 13 x Iemax. 13 x Iemax.

Rated operational voltage Ue 690 V1) 690 V1) 690 V 690 V

Rated operational frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz

Insulation voltage Ui 690 V 690 V 690 V 690 V

Rated impulse withstand voltage Uimp 6 kV 6 kV 6 kV 6 kV

UL/CSA Approved Yes Yes Yes Yes

UL 508 Type "F" Certified Yes No Yes No

UL 508 Type "E" Certified Yes No Yes No

Tripping test Yes Yes Yes Yes

Overload protection Yes No Yes No

Phase failure sensitivity Yes No Yes No

Tripping indication Yes Yes Yes Yes

Tripping class 10 - 10 -

Maximum operating frequency

Operations/hour 15 15 15 15

Altitude (m) 2,000 2,000 2,000 2,000

Degree of protection IP20 IP20 IP20 IP20

Mechanical life span Number of operations 100,000 100,000 50,000 50,000

Electrical life span Number of operations 100,000 100,000 25,000 25,000

Ambient temperatures allowed

Transport and storage -50...+80 °C -50...+80 °C -50...+80 °C -50...+80 °C

Operation1) -20...+70 °C -20...+70 °C -20...+70 °C -20...+70 °C

Temperature compensation -20...+60 °C - -20...+60 °C -

Resistance to impact (g) 15 15 15 15

Standards

IEC/EN 60 947-1, DIN VDE 0660 (part 100) Yes Yes Yes Yes

IEC/EN 60 947-2, DIN VDE 0660 (part 101) Yes Yes Yes Yes

IEC/EN 60 947-4-1, DIN VDE 0660 (part 102) Yes Yes Yes Yes

Terminal capacity

Type of terminal Flat Flat Box Box

Tightening torqueN.m 2...2.5 2...2.5 4...6 4...6

lb.in 18...22 18...22 35...55 35...55

Type of screws Philips (Nº2) Philips (Nº2) Allen (4 mm) Allen (4 mm)

Dimensions

Width (mm) 45 45 54 54

Height (mm) 97 97 125 125

Note: 1) Reduce current for temperatures exceeding +60 °C (87% to 70 °C).

Motor Protective Circuit Breakers - Technical Data

Page 15: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

15Motor Circuit Protectors - MN Series

Main Terminal Capacity

Note: 1) 8 AWG for flexible cable only.

Reference code Type Number of conductors Cross-section

MN32 / MC32 Rigid or flexible cable 1 or 21...2.5 mm2

2.5...6 mm2

14...8 AWG1)

MN65 / MC65

Type 1 conductor connection on top only Cross-section

Rigid cable 1...35 mm2

Cable without terminal 1.5...35 mm2

Cable with terminal 1...35 mm2

Flexible cable1.5...35 mm2

17...2 AWG

Type 1 conductor connection on top only Cross-section

Rigid cable 2.5...35 mm2

Cable without terminal 6...35 mm2

Cable with terminal 2.5...35 mm2

Flexible cable6...35 mm2

13...2 AWG

Type 1 conductor connection on top only Cross-section

Rigid cable

Conductor on top (A)

1...35 mm2

Cable without terminal 1.5...35 mm2

Cable with terminal 1...35 mm2

Flexible cable1.5...35 mm2

17...2 AWG

Type Cross-section

Rigid cable

Conductor on bottom (B)

2.5...35 mm2

Cable without terminal 6...35 mm2

Cable with terminal 2.5...35 mm2

Flexible cable6...35 mm2

13...2 AWG

Mounting Configurations for MN Motor Protective Circuit BreakerLive or grounded parts distance to the circuit breaker

Description Ue

Minimum distance between the circuit breaker and live or grounded parts (mm)

A B C

MN32 / MC32 Up to 600 V 9 30 95

MN65 / MC65 Up to 600 V 10 50 150

*- According to IEC 60447 & UL/CSA standards, the “On - I” indicator must be to the right, or up.

B

A

Page 16: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

16 Motor Circuit Protectors - MN Series

Auxiliary Contact BlockReference code MNA11T MNA11S, MNA20S, MNA02S

For use with MN32, MC32, MN65, MC65

Utilization category 24 V ac 220-230 V ac 24 V ac 230 V ac 400 V ac 690 V ac

UL/CSA 2.5A 2.5A 6 A 6 A 3 A 1 A

AC-15 2.5 A 2.5 A 10 A 10 A 10 A 10 A

DC-1324 V dc 48 V dc 60 V dc 24 V dc 110 V dc 220 V dc 440 V dc

1 A 0.3 A 0.15 A 2 A 0.5 A 0.25 A 0.1 A

Type of terminal Flat

Type of screw Philips (Nº2)

Tightening torque 0.8…1.2 N.m (7…10 lb.in)

Rigid cable1 or 2 x (0.5...1.5 mm2). 1 or 2 x (0.75…2.5 mm2). 2 x (18…14 AWG)

Flexible cable

Backup MCB (UL1077) 6A IEC / 5A UL/CSA

Backup fuses 10 A

Undervoltage and Shunt ReleaseReference code MNAUVT* MNASHT*

For use with MN32, MC32, MN65, MC65

Operating voltage (enables cir. breaker switch on)

0.85...1.1xUs 0.7...1.1xUs

Non-operating voltage (guarantees circuit breaker switch OFF)

0.7...0.35xUs N/A

Energization consumption 20.2 VA / 13 W 8.5 VA / 6 W

Consumption 7.2 VA / 2.4 W N/A

Max. opening time 20ms

Type of terminal Flat

Type of screws Philips (Nº2)

Tightening torque 0.8…1.2 N.m (7…10 lb.in)

Rigid cable 1 or 2 x (0.5...1.5 mm2). 1 or 2 x (0.75…2.5 mm2) 2 x (18…14 AWG)

1 or 2 x (0.5...1.5 mm2). 1 or 2 x (0.75…2.5 mm2) 2 x (18…14 AWG)Flexible cable

Backup MCB (UL1077) 6A IEC / 5A UL/CSA

Back-up fuses 10 A

Page 17: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

17Motor Circuit Protectors - MN Series

Single-phase motor 50/60 Hz Three-phase motor 50/60 Hz Setting overload release

Ir(A)

Short-Circuit

InterruptionCapacity

Short-Circuit

InterruptionCapacity

Reference code

Weight

Lbs

120 V

hp

230 V

hp

208 V

hp

230 V

hp

480 V

hp

600 V

hp

- - - - - - 0.1...0.16

50kA 25kA

MN32CH001-N4*

0.8

- - - - - - 0.16...0.25 MN32CH002-N4*

- - - - - - 0.25...0.4 MN32CH004-N4*

- - - - - 1/4 0.4...0.63 MN32CH006-N4*

- - - - 1/2 1/2 0.63...1 MN32CH010-N4*

- 1/10 1/4 1/3 3/4 1 1...1.6 MN32CH016-N4*

- 1/6 1/2 1/2 1.5 1.5 1.6...2.5 MN32CH025-N4*

1/8 1/3 3/4 1 2 3 2.5...4 MN32CH040-N4*

1/4 3/4 1.5 1.5 3 5 4...6.3 MN32CH063-N4*

1/2 1.5 3 3 5 7.5 6.3...10 MN32CH100-N5*

1 3 5 5 10 15 10...16 MN32CH160-N7*

1.5 3 5 7.5 15 15 16...20 MN32CH200-N11*

2 3 7.5 7.5 15 20 20...25 MN32CH250-N15*

- 5 10 10 20 25 25...32 MN32CH320-N15*

3 7.5 10 15 25 30 30...40

35kA 10kA

MN65CH400-N22*

- 10 15 15 30 40 40...50 MN65CH500-N30*

5 10 20 20 50 60 50...65 MN65CH650-N37*

J * - Replace with Coil Suffix: J A = 110-120VAC - 50/60Hz J C = 208-240VAC - 50/60Hz J D = 380VAC - 60Hz J E = 480VAC - 50/60Hz J F = 600VAC - 50/60Hz J G = 24VAC - 50/60Hz J H = 277VAC - 60Hz

Type “E” Coordination - LSN Series

Manual Self-Protected Combination Motor Controller - Type "E"

• No need of upstream protective devices such as UL489 MCCB or UL248 fuses• Built-in protections: disconnect means, short-circuit protection, motor control and overload protection• Short-circuit interrupting capacity up to 100kA@480Vac (50kA@600Vac)• Compact combination starter• Phase loss sensitivity• Ambient temperature compensation -4…+140ºF (-20…+60ºC)

Ordering example: the type can be found in the “Rated operational power” column alongside the selected rating 5.0hp @ 575V with a 120VAC desired type: MN32CH063-N4A = MN32H063 + MNADLS1 + LSN4-310-A (120VAC Coil - 50/60Hz).

Page 18: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

18 Motor Circuit Protectors - MN Series

Motor Protective Circuit Breakers - Rated Short-Circuit Breaking Capacity

MN32, MC32, MN65, MC65

Setting overload release

(A)

MN32/MC32 without MNACLT MN32/MC32 with MNACLT MN65/MC65

480V 600V 480V 600V 480V 600V

kA kA kA kA kA kA

0.10...0.16 65 25 100 50 - -

0.16...0.25 65 25 100 50 - -

0.25...0.4 65 25 100 50 - -

0.4...0.63 65 25 100 50 - -

0.63...1 65 25 100 50 - -

1...1.6 65 25 100 50 - -

1.6...2.5 65 25 100 50 - -

2.5...4 65 25 100 50 - -

4...6.3 65 25 100 50 - -

6.3...10 65 25 100 50 - -

8...12 65 25 100 50 - -

10...16 3) 65 25 100 50 - -

0.10...0.16 65 25 100 50 - -

0.16...0.25 65 25 100 50 - -

0.25...0.4 65 25 100 50 - -

0.4...0.63 65 25 100 50 - -

0.63...1 65 25 100 50 - -

1...1.6 65 25 100 50 - -

1.6...2.5 65 25 100 50 - -

2.5...4 65 25 100 50 - -

4...6.3 65 25 100 50 - -

6.3...10 65 25 100 50 - -

10...16 65 25 100 50 - -

16...20 50 25 100 50 - -

20...25 50 25 100 50 - -

25...32 50 25 100 50 - -

30...40 - - - - 35 10

40...50 - - - - 35 10

50...65 - - - - 35 10

Page 19: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

19Motor Circuit Protectors - MN Series

Motor Protective Circuit Breakers - Characteristics Curves

The tripping characteristic shows the motor circuit breaker trip time in relation to the rated current.The curves show average tolerance range values for an ambient temperature of 20 °C, starting in cold state. Thermal trip time when working in operating temperature is reduced to around 25% of the presented values. Under normal operating conditions, all 3 circuit breaker phases must be conducting.

Characteristic I2t at 460 V - MN32 / MC32

Presumed short-circuit current (kA) [RMS]

Characteristic I2t at 460 V - MN65 / MC65

1

10

100

1000

0,1 1 10 100

I².t x

10³

(A².s

)

Prospektiver kurzchlusstrom (kA) [RMS]

Durchlasswerte I2t at 415V - MPW65/65i

65

50

40

Presumed short-circuit current (kA) [RMS]

I2.t

x 1

03 (A

2.s

)

Page 20: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

20 Motor Circuit Protectors - MN Series

MN32 / MC32 + BA09…BA16

MN32 / MC32 + AccessoriesMounting Position

MC32MN32

165

MNADBA1

BA09...BA16

98

45

MNTSBMNAUVTMNASHT

MNA**S

ON

L

OFF

D

DIN35mm

90

45 1818

MNA11S

MNASHTMNAUVT

Ø4.

8

118

105

98 30

97MNTSB

9

Page 21: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

21Motor Circuit Protectors - MN Series

MN32 / MC32 + LSN4...LSN7

MN32 / MC32 + LSN11

MN32 / MC32 + BA25

ON

L

OFF

D

176

165

MNADBA2

BA25

MC32MN32

9845

MNADLS1

LSN4LSN5LSN7

9845 98 4.80

MNASPAK

4.50

35

1018

3

18319

3

4.80

4.50

35

10

MNASPAK

30

9845

MNADLS1

LSN11

183

183

193

MC32MN32

Din rail-35 mm(DIN EM50022)

MC32MN32

Page 22: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

22 Motor Circuit Protectors - MN Series

MN32 / MC32 + LSN15

Front Plate - MNE55F

Insulated Enclosure - MNE55H (IP55)

Current Limiter - MNACLT

167

M25M25

92129

157

109

155

Ø4.

5

Maximum trickness ≤ 5

105

85 89

A<5

55

DIN35mm

7230

MN32MC32

MNADLS2

200

LSN15

98

45

118

105

Ø4.8

55

105

Page 23: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

23Motor Circuit Protectors - MN Series

Accessories:

Door Coupling Rotary Handle - MNAHS1N1

MN65 + MNAEAD2

Ref. code MN32BN02 MN32BN03 MN32BN04 MN32BN05

A 85 130 175 220

Ref. code MN32BD02 MN32BD03 MN32BD04 MN32BD05

B 94 149 202 256

143

133

118

LST25

98

to

A

B 133.

512

7.5

118

123

143

133

118

MN32BNMN32BD

MN32MC32

MN32MC32

MNAEAD1

MNAEAD2

MN65MC65

33.6

63

54 32

44

156.63

72

9 18

12.2

118

97

5.5

6.9 45119.4

Panel door drillings97

149 302

Door panel thichness1.0 to 5.0 mm

Shaft (330 mm)

105

30

169177

4098

98

25

51

54

44 24

28

28

2540

13

20

14.4

45

Ø4.8

Ø4R20

Ø16

45°

Page 24: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

24 Motor Circuit Protectors - MN Series

Door Coupling Rotary Handle - MNAHS1N4X

Door Coupling Rotary Handle - MNAHS2N1

Door Coupling Rotary Handle - MNAHS2N4X

MN65 / MC65 + Accessories Mounting Position

DIN35mm

Drilling the panel door

11.5

0

7.20

430

Shaft (330 mm)

154 276

50.70

97A

99

157

213 302

51519.22

Shaft (330 mm)

Panel door drillings

Ø16Ø4R2

0

45°

52,60

A < 5.0 mm

3.50

125

54

10

Shaft (330 mm)

50.70

MRX

54

A

B

213

489

27648.50

24.25

48.5

0

24.2

5

Ø22.50

Ø4

23.5

0

3.20

A < 5.0 mm

MPW65MPW65i

33

125

10

30

Ø4.80

144

125

ACBS URMPSRMP

TSB

5418 18

9

MNA11SMNASHTMNAUVT

MNTSB

Panel door drillings

3.50

48.50

24.2

5

48.5

0

24.25

Ø22.50Ø4

23.5

0

3.20

Page 25: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

25Motor Circuit Protectors - MN Series

Notes

Page 26: MOTOR CIRCUIT PROTECTORS - EE Controls

www.eecontrols.ca

The values shown are subject to change without prior notice. The information contained is reference values.

ED: 01 | Rev: 01 | Date: 08/2020.

LOW VOLTAGE CONTROL

Orangeville - ON - Canada

(519) 941-6845

[email protected]

For more EEC products visit our website