Motor Protection Circuit Breakers 140M-C..., 140M-D... Application Instruction for Protection of EEx e Motors Please read this first Time-current characteristics Catalog Number Current Range [A] Drawing 140M-C2E-A16 0.10...0.16 21.022.100 140M-C2E-A25 0.16...0.25 21.022.101 140M-C2E-A40 0.25...0.4 21.022.102 140M-C2E-A63 0.4...0.63 21.022.103 140M-C2E-B10 0.63...1.0 21.022.104 140M-C2E-B16 1.0...1.6 21.022.105 140M-C2E-B25 1.6...2.5 21.022.106 140M-C2E-B40 2.5...4.0 21.022.107 140M-C2E-B63 4.0...6.3 21.022.108 140M-C2E-C10 6.3...10 21.022.109 140M-C2E-C16 10...16 21.022.110 140M-C2E-C20 14.5...20 21.022.111 140M-C2E-C25 18...25 21.022.112 140M-D8E-B25 1.6...2.5 21.022.106 140M-D8E-B40 2.5...4.0 21.022.107 140M-D8E-B63 4.0...6.3 21.022.108 140M-D8E-C10 6.3...10 21.022.109 140M-D8E-C16 10...16 21.022.110 140M-D8E-C20 14.5...20 21.022.111 140M-D8E-C25 18...25 21.022.112 Tag the desired Catalog Number

Upload: trinhkhanh

Post on 26-Apr-2018

236 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Motor Protection Circuit Breakers 140M-C..., 140M-D...Application Instruction for Protection of EEx e Motors Please read this first

Time-current characteristicsCatalog Number Current Range [A] Drawing

140M-C2E-A16 0.10...0.16 21.022.100140M-C2E-A25 0.16...0.25 21.022.101140M-C2E-A40 0.25...0.4 21.022.102140M-C2E-A63 0.4...0.63 21.022.103140M-C2E-B10 0.63...1.0 21.022.104140M-C2E-B16 1.0...1.6 21.022.105140M-C2E-B25 1.6...2.5 21.022.106140M-C2E-B40 2.5...4.0 21.022.107140M-C2E-B63 4.0...6.3 21.022.108140M-C2E-C10 6.3...10 21.022.109140M-C2E-C16 10...16 21.022.110140M-C2E-C20 14.5...20 21.022.111140M-C2E-C25 18...25 21.022.112

140M-D8E-B25 1.6...2.5 21.022.106140M-D8E-B40 2.5...4.0 21.022.107140M-D8E-B63 4.0...6.3 21.022.108140M-D8E-C10 6.3...10 21.022.109140M-D8E-C16 10...16 21.022.110140M-D8E-C20 14.5...20 21.022.111140M-D8E-C25 18...25 21.022.112

Tag the desired Catalog Number

Page 2: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

-Application Instruction for Protection of EEx e Motorswith Motor Protection Circuit Breaker.-Anwendungsanweisung für den Schutz von EEx e Motorenmit Leistungsschalter.-Notice d'application pour la protection des moteurs EEx eavec disjoncteur assurant la protection de moteur.-Prescrizioni per la protezione dei motori EEx econ interruttore automatico.-Prescripciónes para la protección de los motores EEx econ interruptores automáticos.

140M-C140M-D

Attention: To prevent electrical shock, disconnect from power source before installing or servicing. Install insuitable enclosure. Keep free from contaminants. Commissioning and maintenance must be carried outby qualified personnel.

Achtung: Vor Installations- oder Servicearbeiten Stromversorgung unterbrechen, um Unfälle zu vermeiden.Die Geräte müssen in einem passenden Gehäuse eingebaut und gegen Verschmutzung geschützt werden.Inbetriebsetzung und Wartung nur durch Fachpersonal.

Attention: Avant le montage et la mise en service, couper l’alimentation du secteur afin d'éviter tout accident.Prévoir une mise en coffret ou armoire appropriée. Protéger le produit contre les environnements agressifs.Mise en service et maintenance doivent être effectuées par un personnel qualifié.

Attenzione: Per prevenire infortuni, togliere tensione prima dell'installazione o manutenzione.Installare in custodia idonea. Tenere lontano da contaminanti. Messa in servizio e manutensione devoneesser effettuate da un personale qualificato.

Atención: Desconectar la alimentación eléctrica antes de realizar el montaje y la puesta en servicio, con elobjeto de evitar accidentes. Instalado en una caja o armario apropiado. Proteger el producto de los ambientesagresivos. Puesta en servicio y mantenimiento deben ser efectuados por un personal calificado.

- For setting of circuit breaker see page 2- Für Einstellung der Leistungsschalter siehe Seite 2- Pour le choix du disjoncteur voir page 2- Per scegliere il tipo di interruttore automatico vedere pagina 2- Para elegir el tipo de interruptor automático consulte la página 2

- For mounting and electrical connections see page 3 and 4- Für Montage und elektrische Verbindungen siehe Seite 3 und 4- Pour le montage et le câblage des connexions voir page 3 et 4- Per il montaggio ed il cablaggio elettrico vedere pagina 3 e 4- Para el montaje y la conexión consulte página 3 y 4

- For time-current characteristics of all current ranges see page 5 to 17- Für Kennlinienblatt aller Strombereiche siehe Seite 5 bis 17- Pour les caractéristiques de déclenchement temps/courant voir page 5 à 17- Per le caratteristiche di sgancio tempo/corrente vedere pagina 5-17- Para las caracteristícas de desenganche tiempo/corriente consulte página 5-17

1

21.301.961-01Edition 4

9. 2004

IEC 60947-1,-2,-4.1EN 60947-1,-2,-4.1EN 60079-14UL 508CSA 22.2 part 14

PTB 04 ATEX 3039Ex II (2) G

0102

Page 3: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

2

- Set circuit breaker to match the motor characteristic- Den Leistungsschalter an die Charakteristik des Motors anpassen- Régler le disjoncteur afin de correspondre à la caractéristique du moteur- Adattare il interruttore automatico alle caratteristiche del motore- Adaptar el interruptor automático a la particularidad del motor

2) - Make sure that t of motor is longer than the release time t of the circuit breaker at the locked motorcurrent I

- Sicherstellen, dass die t -Zeit des Motors länger ist als die Auslösezeit t des Leistungsschalters beiblockiertem Motor

- Assurez-vous que le temps t du moteur est supérieur au temps de déclenchement t du disjoncteurpour le courant de blocage du moteur I

- Assicurarsi che il tempo t del motore sia superiore al tempo di sgancio t in caso di motore bloccato- Asegurarse que el tiempo t del motor sea mayor que el tiempo de desenganche t en caso de motor bloqueado

L1

T1

L2

T2

L3

T3

In = 15,5A

I

140M-C2E-C16140M-D8E-C16

E

E

E

E

E

A

A

A

A

A

AA

Start

A

I (LRC) / I (Example: 101 / 15,5 = 6,5)

t 15 s

tE

e

1) - Set current of circuit breaker to rated motor current- Den Auslösestrom des Leistungsschalters auf denMotornennstrom einstellen

- Régler le courant du disjoncteur selon le courantassigné du moteur

- Regolare il interruttore automatico sulla correntenominale del motore

- Adaptar el interruptor automático a la corriente

nominal del motor

ExampleBeispielExempleEsempioEjemplo

ExampleBeispielExempleEsempioEjemplo

140M-C

2E-C

16und

140M-D

8E-C

16C

urrentrange10...16

A

N

Page 4: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

3

120°

30°90

° 90°

-UX...-UC...-SN...

-WBE

-W...

-AFA...

-ASAR...

-WT-WTE

-W542 -ASA...

-KN

-KRY

-CA-N45

-N45

-AFA...

-TE

L11

L23

L35

2T1

4T2

6T3

No. 3

Pozidriv No. 2

2...2,5 Nm18...22 lb-in

Use 75°C Cu wire only

2 x 1...4 mm2

2 x No. 16...10 AWG

2 x 1...4 mm2

2 x No. 16...10 AWG

2 x 1...4 mm2

2 x No. 16...10AWG

1, 3, 52, 4, 6

9 mm

Page 5: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

4

12

1

- Minimum distance to grounded parts or walls- Minimaler Abstand gegen geerdete Teile oder

Wände- Distance minimale envers pièces mises à terre

ou parois- Distanza minimale per pezzi a massa o pareti- Distancia minima a chasis o paredes

H1H2

140M-C2...4462

140M-D8...5472

For single-phase applications set to105% of motor current.

Bei einphasigem Betrieb stellen Sie105% des Motorstromes ein.

En service monophasé régler à105% de la valeur du courant moteur.

Per il funzionamento monofase regolarea 105% della corrente del motore.

Para aplicaciones monofásicas ajustara 105% de la corriente del motor.

L1

T1

L2

T2

115 VAC/DC

L3

T3

L1

T1

L2

T2

230 VAC/DC

L3

T3

1)

1)

1)

1)

1)

1)

1)

Motor Protector / Circuit BreakerThis device meets the requirements of IEC 60947-2 as a circuit breaker.

It is cUL us listed (UL and CSA approved) as:- A Manual Motor Controller with optional approvals for Group Motor, MotorDisconnect and Tap Conductor Protection.

- A Manual, Self-Protected Combination Motor Controller (Construction Typ E).

All installations, commissioning and maintenance must be carried out by qualifiedpersonnel, taking local regulations into account.

I

18

25A

Warning:Warnung:Attention:Attenzione:Atención:

-Do not set outside scale !

-Nicht ausserhalb Skala einstellen !

-Défense d'ajuster le couranten dehors de la plage indiquée !

-E vietato di regolare la correntefuori dal campo di taratura !

- Prohibido de regular la corrientefuera del campo de la escala !

!

9

8 824,8

90

18

4,5

45

H1

H2

4,5

7,5

45

45

4525

25

*)

*)

Page 6: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-A16

Strom

bereich0,1...0,16

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-A16

Currentrange

0,1...0,16A

Page 7: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-A25

Strom

bereich0,16...0,25

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-A25

Currentrange

0,16...0,25A

Page 8: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-A40

Strom

bereich0,25...0,4

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-A40

Currentrange

0,25...0,4A

Page 9: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-A63

Strom

bereich0,4...0,63

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-A63

Currentrange

0,4...0,63A

Page 10: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-B10

Strom

bereich0,63...1

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-B10

Currentrange

0,63...1A

Page 11: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-B16

Strom

bereich1...1,6

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-B16

Currentrange

1...1,6A

Page 12: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-B25

und140M

-D8E

-B25

Strom

bereich1,6...2,5

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-B25

and140M

-D8E

-B25

Currentrange

1,6...2,5A

Page 13: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-B40

und140M

-D8E

-B40

Strom

bereich2,5...4

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-B40

and140M

-D8E

-B40

Currentrange

2,5...4A

Page 14: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-B63

und140M

-D8E

-B63

Strom

bereich4...6,3

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-B63

and140M

-D8E

-B63

Currentrange

4...6,3A

Page 15: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-C10

und140M

-D8E

-C10

Strom

bereich6,3...10

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-C10

and140M

-D8E

-C10

Currentrange

6,3...10A

Page 16: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-C16

und140M

-D8E

-C16

Strom

bereich10...16

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-C16

and140M

-D8E

-C16

Currentrange

10...16A

Page 17: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-C20

und140M

-D8E

-C20

Strom

bereich14,5...20

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-C20

and140M

-D8E

-C20

Currentrange

14,5...20A

Page 18: Motor Protection Circuit Breakers 140M-C, 140M-Ddocs-europe.electrocomponents.com/webdocs/14b6/0900766b...-Application Instruction for Protection of EEx e Motors with Motor Protection

Kennlinienblattvom

Leistungsschalter140M

-C2E

-C25

und140M

-D8E

-C25

Strom

bereich18...25

AT

ime-currentcharacteristics

ofcircuitbreaker140M

-C2E

-C25

and140M

-D8E

-C25

Currentrange

18...25A