PostedbyAshokKumarApril29
Theoverloadrelayissituatedinthemotorline.Therefore,thecurrenttobeadjustedislowerthanthemotorsratedcurrentbyafactorof1_3=0.58.Duetothethirdharmonicscurrentscirculatinginthemotorwindings,ahighersettingoftheoverloadrelaymayberequired.Thismayonlybecarriedoutonthebasisofutilisingameasuringdevicewhichrecordsthecorrectr.m.s.value.Conductorcrosssectionalareasmustbeofasuitablesizeinorderthattheywillbeprotectedagainsttemperaturerisesresultingfromoverloadconditions.Therefore,theconductorsizeselectedmustbeinaccordancewiththeprotectivedevice(s)rating.
-
5/14/2015 Zone4info.comMotorProtectionandContactorSizing
http://zone4info.com/articles/print/1131/format/smoothbox 2/2
Formotorprotectionbymeansofpowercircuitbreakerswithmotorprotectioncharacteristics,thepowercircuitbreakerisswitchedintothenetworksupplylines,asitalsocarriesoutshortcircuitprotectionofstarterandlines.Inthiscase,thecurrentissettotheratedmotorcurrent.Acorrectionofthesetvaluebecauseofthethirdharmonicsisirrelevantunderthesecircumstances.Thelinesaretobethermallyproportioneddependingonthepowercircuitbreakerssetting.
Fornormalstardeltastarting,thecontrolgearmustbesizedinaccordancewiththefollowingcurrents:
MaincontactorK1M0.58IeDeltacontactorK2M0.58IeStarcontactorK3M0.34Ie
Forstartingtimesexceedingapproximately15seconds,abiggerstarcontactorhastobeselected.Ifthestarcontactorisequaltothemaincontactor,starttimesofuptoapproximatelyoneminutearepermissible.