Zone4info.com Motor Protection and Contactor Sizing Motor Protection and Contactor Sizing Posted by Ashok Kumar April 29 The overload relay is situated in the motor line. Therefore, the current to be adjusted is lower than the motor’s rated current by a factor of 1√ _ 3 = 0.58. Due to the third harmonics currents circulating in the motor windings, a higher setting of the overload relay may be required. This may only be carried out on the basis of utilising a measuring device which records the correct r.m.s. value. Conductor cross sectional areas must be of a suitable size in order that they will be protected against temperature rises resulting from overload conditions. Therefore, the conductor size selected must be in accordance with the protective device(s) rating.

Upload: mohamed-ahmed-fawzy

Post on 17-Sep-2015

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 5/14/2015 Zone4info.comMotorProtectionandContactorSizing

    http://zone4info.com/articles/print/1131/format/smoothbox 1/2

    Zone4info.comMotorProtectionandContactorSizing

    MotorProtectionandContactorSizing

    PostedbyAshokKumarApril29

    Theoverloadrelayissituatedinthemotorline.Therefore,thecurrenttobeadjustedislowerthanthemotorsratedcurrentbyafactorof1_3=0.58.Duetothethirdharmonicscurrentscirculatinginthemotorwindings,ahighersettingoftheoverloadrelaymayberequired.Thismayonlybecarriedoutonthebasisofutilisingameasuringdevicewhichrecordsthecorrectr.m.s.value.Conductorcrosssectionalareasmustbeofasuitablesizeinorderthattheywillbeprotectedagainsttemperaturerisesresultingfromoverloadconditions.Therefore,theconductorsizeselectedmustbeinaccordancewiththeprotectivedevice(s)rating.

  • 5/14/2015 Zone4info.comMotorProtectionandContactorSizing

    http://zone4info.com/articles/print/1131/format/smoothbox 2/2

    Formotorprotectionbymeansofpowercircuitbreakerswithmotorprotectioncharacteristics,thepowercircuitbreakerisswitchedintothenetworksupplylines,asitalsocarriesoutshortcircuitprotectionofstarterandlines.Inthiscase,thecurrentissettotheratedmotorcurrent.Acorrectionofthesetvaluebecauseofthethirdharmonicsisirrelevantunderthesecircumstances.Thelinesaretobethermallyproportioneddependingonthepowercircuitbreakerssetting.

    Fornormalstardeltastarting,thecontrolgearmustbesizedinaccordancewiththefollowingcurrents:

    MaincontactorK1M0.58IeDeltacontactorK2M0.58IeStarcontactorK3M0.34Ie

    Forstartingtimesexceedingapproximately15seconds,abiggerstarcontactorhastobeselected.Ifthestarcontactorisequaltothemaincontactor,starttimesofuptoapproximatelyoneminutearepermissible.

    Reference:

    www.rockwellautomation.com