motor starting dynamic acceleration• maximum motor size that can be started across the line •...

63
© 1996-2009 Operation Technology, Inc. Workshop Notes: Motor Acceleration Motor Starting Dynamic Acceleration

Upload: others

Post on 18-Mar-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Motor Starting

Dynamic Acceleration

Page 2: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 2© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Why to Do MS Studies?

• Ensure that motor will start with voltage drop

• If Tst<Tload at s=1, then motor will not start

• If Tm=Tload at s<sr, motor can not reach rated speed

• Torque varies as (voltage)^2

• Ensure that voltage drop will not disrupt other loads

• Utility bus voltage >95%

• 3% Sag represents a point when light flicker becomes visible

• 5% Sag represents a point when light flicker becomes irritating

• MCC bus voltage >80%

• Generation bus voltage > 93%

Page 3: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 3© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Why to Do MS Studies?

• Ensure motor feeders sized adequately

(Assuming 100% voltage at Switchboard or MCC)

• LV cable voltage drop at starting < 20%

• LV cable voltage drop when running at full-load < 5%

• HV cable voltage drop at starting < 15%

• HV cable voltage drop when running at full-load < 3%

• Maximum motor size that can be started across the line

• Motor kW < 1/6 kW rating of generator (islanded)

• For 6 MW of islanded generation, largest motor size < 1 MW

Page 4: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 4© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Motor Sizing

• Positive Displacement Pumps / Rotary Pumps

• p = Pressure in psi

• Q = fluid flow in gpm

• n = efficiency

• Centrifugal Pumps

• H = fluid head in feet

Page 5: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 5© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Motor Types

• Synchronous

• Salient Pole

• Round Rotor

• Induction

• Wound Rotor (slip-ring)

• Single Cage CKT Model

• Squirrel Cage (brushless)

• Double Cage CKT Model

Page 6: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 6© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Induction Motor Advantages

• Squirrel Cage

• Slightly higher efficiency and power factor

• Explosive proof

• Wound Rotor

• Higher starting torque

• Lower starting current

• Speed varied by using external resistances

Page 7: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 7© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Typical Rotor Construction

• Rotor slots are not parallel to the shaft but

skewed

Page 8: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 8© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Wound Rotor

Page 9: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 9© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Operation of Induction

Motor

• AC applied to stator winding

• Creates a rotating stator magnetic field in air gap

• Field induces currents (voltages) in rotor

• Rotor currents create rotor magnetic field in air gap

• Torque is produced by interaction of air gap fields

Page 10: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 10© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Slip Frequency

• Slip represents the inability of the rotor to

keep up with the stator magnetic field

• Slip frequency

S = (ωs-ωn)/ωs where ωs = 120f/P

ωn = mech speed

Page 11: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 11© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Static Start - Example

Page 12: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 12© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Static Start - Example

Page 13: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 13© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Service Factor

Page 14: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 14© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Inrush Current

Page 15: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 15© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Motor Torque – Speed Curve

Page 16: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 16© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Resistance / Reactance

• Torque Slip Curve is changed by altering

resistance / reactance of rotor bars.

• Resistance ↑ by ↓cross sectional area or

using higher resistivity material like brass.

• Reactance ↑ by placing conductor deeper in

the rotor cylinder or by closing the slot at the

air gap.

Page 17: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 17© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Rotor Bar Resistance ↑

• Increase Starting Torque

• Lower Starting Current

• Lower Full Load Speed

• Lower Efficiency

• No Effect on Breakdown Torque

Page 18: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 18© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Rotor Bar Reactance ↑

• Lower Starting Torque

• Lower Starting Current

• Lower Breakdown Torque

• No effect on Full Load Conditions

Page 19: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 19© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Motor Torque Curves

Page 20: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 20© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Rotor Bar Design

• Cross section Large (low

resistance) and positioned deep in

the rotor (high reactance).

(Starting Torque is normal and

starting current is low).

• Double Deck with small conductor

of high resistance. During starting,

most current flows through the

upper deck due to high reactance

of lower deck. (Starting Torque is

high and starting current is low).

Page 21: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 21© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Rotor Bar Design

• Bars are made of Brass or

similar high resistance

material. Bars are close to

surface to reduce leakage

reactance. (Starting torque is

high and starting current is

low).

Page 22: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 22© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Load Torque – ID Fan

Page 23: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 23© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Load Torque – FD Fan

Page 24: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 24© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Load Torque – C. Pump

Page 25: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 25© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Double Cage Motor

Page 26: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 26© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Motor Full Load Torque

• For example, 30 HP 1765 RPM Motor

Page 27: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 27© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Motor Efficiency

• kW Saved = HP * 0.746 (1/Old – 1/New)

• $ Savings = kW Saved * Hrs /Year * $/kWh

Page 28: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 28© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Acceleration Torque

• Greater

Acceleration

Torque means

higher inertia

that can be

handled by the

motor without

approaching

thermal limits

Page 29: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 29© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Acceleration Torque

Page 30: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 30© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Operating Range

• Motor, Generator, or Brake

Page 31: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 31© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Rated Conditions

• Constant Power

Page 32: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 32© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Starting Conditions

• Constant Impedance

Page 33: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 33© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Voltage Variation

• Torque is proportional to V^2

• Current is proportional to V

Page 34: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 34© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Frequency Variation

• As frequency decreases, peak torque shifts toward lower

speed as synchronous speed decreases.

• As frequency decrease, current increases due reduced

impedance.

Page 35: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 35© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Number of Poles Variation

• As Pole number increases, peak torque shifts toward lower

speed as synchronous speed decreases.

Page 36: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 36© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Rotor Z Variation

• Increasing rotor Z will shift peak torque towards lower

speed.

Page 37: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 37© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Modeling of Elements

• Switching motors – Zlr, circuit model, or characteristic model

• Synch generator - constant voltage behind X’d

• Utility - constant voltage behind X”d

• Branches – Same as in Load Flow

• Non-switching Load – Same as Load flow

• All elements must be initially energized, including motors to start

Page 38: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 38© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Motor Modeling

1. Operating Motor

– Constant KVA Load

2. Starting Motor

– During Acceleration – Constant Impedance

– Locked-Rotor Impedance

– Circuit Models

Characteristic Curves

After Acceleration – Constant KVA Load

Page 39: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 39© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Locked-Rotor Impedance

• ZLR = RLR +j XLR (10 – 25 %)

• PFLR is much lower than operating PD.

Approximate starting PF of typical squirrel

cage induction motor:

Page 40: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 40© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Circuit Model I

• Single Cage Rotor

– “Single1” – constant rotor resistance and

reactance

Page 41: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 41© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Circuit Model II

• Single Cage Rotor

– “Single2” - deep bar effect, rotor resistance and

reactance vary with speed [Xm is removed]

Page 42: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 42© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Circuit Model III

• Double Cage Rotor

– “DB1” – integrated rotor cages

Page 43: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 43© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Circuit Model IV

• Double Cage Rotor

– “DB2” – independent rotor cages

Page 44: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 44© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Characteristic Model

• Motor Torque, I, and PF as function of Slip

– Static Model

Page 45: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 45© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Calculation Methods I

• Static Motor Starting

– Time domain using static model

– Switching motors modeled as Zlr during starting and

constant kVA load after starting

– Run load flow when any change in system

• Dynamic Motor Starting

– Time domain using dynamic model and inertia model

– Dynamic model used for the entire simulation

– Requires motor and load dynamic (characteristic) model

Page 46: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 46© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Calculation Methods II

Page 47: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 47© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Static versus Dynamic

• Use Static Model When

– Concerned with effect of motor starting on other

loads

– Missing dynamic motor information

• Use Dynamic Model When

– Concerned with actual acceleration time

– Concerned if motor will actually start

Page 48: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 48© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

MS Simulation Features

• Start/Stop induction/synchronous motors

• Switching on/off static load at specified loading category

• Simulate MOV opening/closing operations

• Change grid or generator operating category

• Simulate transformer LTC operation

• Simulate global load transition

• Simulate various types of starting devices

• Simulate load ramping after motor acceleration

Page 49: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 49© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Automatic Alert• Starting motor terminal V

• Motor acceleration failure

• Motor thermal damage

• Generator rating

• Generator engine continuous & peak rating

• Generator exciter peak rating

• Bus voltage

• Starting motor bus

• Grid/generator bus

• HV, MV, and LV bus

• User definable minimum time span

Page 50: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 50© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Starting Devices Types

• Auto-Transformer

• Stator Resistor

• Stator Reactor

• Capacitor at Bus

• Capacitor at Motor

Terminal

• Rotor External Resistor

• Rotor External Reactor

• Y/D Winding

• Partial Wing

• Soft Starter

• Stator Current Limit

– Stator Current Control

– Voltage Control

– Torque Control

Page 51: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 51© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Starting Device

• Comparison of starting conditions

Page 52: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 52© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Starting Device – AutoXFMR

• C4 and C3 closed initially

• C4 opened, C2 is closed with C3 still closed. Finally C3 is open

Page 53: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 53© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Starting Device – AutoXFMR

• Autotransformer

Page 54: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 54© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Starting Device – YD Start

• During Y connection Vs = VL / √3

• Phase current Iy = Id / √3 and 3 to 1 reduction in torque

Page 55: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 55© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Starting Device – Rotor R

Page 56: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 56© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Starting Device – Stator R

• Resistor

Page 57: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 57© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Starting Device Stator X

• Reactor

Page 58: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 58© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

Transformer LTC Modeling

• LTC operations can be simulated in motor

starting studies

• Use global or individual Tit and Tot

Page 59: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 59© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

MOV Modeling I

• Represented as an impedance load during operation

– Each stage has own impedance based on I, pf, Vr

– User specifies duration and load current for each stage

• Operation type depends on MOV status

– Open statusclosing operation

– Close statusopening operation

Page 60: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 60© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

MOV Modeling II

• Five stages of operation

Opening Closing

Acceleration Acceleration

No load No load

Unseating Travel

Travel Seating

Stall Stall

• Without hammer blow Skip “No Load” period

• With a micro switch Skip “Stall” period

• Operating stage time extended if Vmtr < Vlimit

Page 61: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 61© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

MOV Closing

• With Hammer Blow- MOV Closing

Page 62: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 62© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

MOV Opening

• With Hammer Blow- MOV Opening

Page 63: Motor Starting Dynamic Acceleration• Maximum motor size that can be started across the line • Motor kW < 1/6 kW rating of generator (islanded) • For 6 MW of islanded generation,

Slide 63© 1996-2009 Operation Technology, Inc. – Workshop Notes: Motor Acceleration

MOV Voltage Limit

• Effect of Voltage Limit Violation