mtmtipmbprima30 gb
TRANSCRIPT
Technical DossierV3.0, APR.05
Parameters and user interfaceEnglish / MTIPIEPMB300GB (chap. 4)
MicroBASICPRIMA.
Parameters anduser interface
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 I MTIPIEPMB300GB
TABLE OF CONTENTS
CHAPTER 4. MICROBASIC CONTROL UNIT OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
4.1. Compatibility. MicroBasic - MicroBasic Prima . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 714.2. MicroBASIC PRIMA board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
4.2.1 Main components and general scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 724.2.2 Information provided by the controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4.2.2.1. Indicator lights (leds) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 754.2.2.2. 3-digit display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
4.2.2.2.1. First information provided . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 764.1.2.2.2. Program mode information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 764.2.2.2.3. Information in normal operation . . . . . . . . . . . . . . . . . . . . . . . . . . 774.2.2.2.4. Information during inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 814.2.2.2.5. Information in special situations . . . . . . . . . . . . . . . . . . . . . . . . . . 81
4.2.3. Configuration and adjustment of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 824.2.3.1. Parametrization method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
4.2.3.1.1. Elements for configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 824.2.3.1.2. Types of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 824.2.3.1.3. Parametrization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
4.2.3.3. Description of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 894.2.4. Basic functional operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
4.2.4.1. Commissioning. Return Control Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 944.1.4.2. Normal operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 954.2.4.3. Inspection operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 964.2.4.4. Emergency operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 964.2.4.5. Other operations and functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
4.2.4.5.1. Opening and closing of doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 974.2.4.5.2. Relevelling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
4.2.4.5.3. Fireman control unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 994.2.4.5.4. Mixed selective control unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 994.2.4.5.5. Asymmetric lifts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
4.3. Printed circuit board AMB1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1014.3.1. Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1014.3.2. Information provided by the board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1014.3.3. Configuration of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1024.3.4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
4.4. Printed circuit board AMB2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1064.4.1. Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1064.4.2. Information provided by the board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
4.4.2.1. Led light indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1074.4.2.2. 4-Digit display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
4.4.2.2.1. RUN Mode: information indication . . . . . . . . . . . . . . . . . . . . . . . . 1084.4.2.2.2. PROGRAM Mode: Information indication . . . . . . . . . . . . . . . . . . . . 1104.4.2.2.3. Special indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
4.4.3. Configuration and adjustment of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1114.4.3.1. Configuration elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1114.4.3.2. PROGRAM Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1114.4.3.3. Parameters configuration table for MicroBASIC control unit with additional AMB2
board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1134.4.3.4. Configuration of parameters on the AMB2 circuit board . . . . . . . . . . . . . . . . . 113
4.4.4. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1154.4.4.1. Operation in normal configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1154.4.4.2. Redundant operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
4.4.5. Control unit errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 71 MTIPIEPMB300GB
CHAPTER 4. MICROBASIC CONTROL UNIT OPERATION
4.1. Compatibility. MicroBasic - MicroBasic Prima
The new MicroBasic Prima board could replace any MicroBasic board of any previous version with no modification onexisting wiring.This is possible because some parameters have been included for this purpose.See the following changes according to pannel type, its relation to software version and the parameter (and value)that has to be modified to achieve this compatibility.
INSTALACIONTYPE
MICROBASICPRIMA
SOFTWARE
VERSION
MICROBASIC
SOFTWARE
VERSION
FUNCTIONS ACCORDING TO VERSION
STOP
(P/V)
OVER-TEMPERATURE
(P/V)
WELDEDCONTACTOR
(P/V)
LEVELINGCRITERION
(P/V)
Whitoutenlargement
Electric. 1 and 2speed and
oleodinamic
From 165forward
131 / 132/ 133
Terminal J(30 / B)(33 / A)
Terminal F
(30 / B)
Stopped aAnalisys
(29 / B)
No(24/A no leveling24/C leveling
134Terminal J(30 / B)(33 / A)
Terminal F
(30 / B)
Stopped aAnalisys
(29 / B)
YES
(CURRENT)
135 / 137/ 141 /
146
see parameterselection table
(33)
Terminal J
(Actual)
Stopped andMovement Analisys
YES
(CURRENT
Whitoutenlargement
3VFMAC
995Terminal J(30 / B)(33 / A)
Terminal J
(30 / B)
Stopped aAnalisys
(29 / B)
NO(24/A no leveling24/C leveling
E13 / E15TerminalJ(30 / B)(33 / A)
Terminal F
(30 / B)
Stopped andMovement Analisys
(actual)
YES
(CURRENT)
E19 / 136/ 139 /
142 / 148
see parameterselection table
(33)
Terminal J
(actual)
Stopped andMovement Analisys
(CURRENT)
YES
(CURRENT)
Whit enlargementAMB1 / AMB2 From 171
forward
50A / 50B/ 50C /
50D / 50E
Terminal J(30 / B)(33 / A)
Terminal F
(30 / B)
Stopped aAnalisys
(29 / B)
No(24/A no leveling24/C leveling
51CTerminal J(30 / B)(33 / A)
Terminal F
(30 / B)
Stopped aAnalisys
(29 / B)
YES
(CURRENT)
52Asee parameterselection table
(33)
TerminalJ
(CURRENT)
Stopped andMovement Analisys
(CURRENT)
YES
(CURRENT)
P/V is the parameter y its suitable value for compatibility between microBASIC Prima board and the one to bereplaced,
regardless of the version.
As an example, if we replace a V134 board in a hydraulic lift with open doors releveling:
Parameter 24, is C value, because is old directive and has releveling.Parameter 29, is B value, because is welded contactor with stopped lift.Parameter 30, is B value, because is over temperature in F terminal with overload and STOP function is in J terminal .Parameter 33, is A value, because STOP is in J terminal and has any other value unless in this terminal overtemperature has not been analysed.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 72 MTIPIEPMB300GB
Pins
Pin 103 . Aerial connection pin. Safety series reading.
Pin RME . Aerial connection pin. Times RME for hydraulic lifts with cam.
Pin 207 . Aerial connection pin with leveller 538. Indicator light between floors.
R7
RL22
D32
R9
R85
+
R51
R29
C29
C77
C78
C79
U4
U17
C38
R76 R78
U28
C87
U27
D95
PR2
V3
V4
V5
+
RBEXT
RL1
RL5
D1
R1
D11
DZ1
R27
C3
R30
U1
U5
R39
D66
C37
Q1
U9
U13
U15
U18 U19U22
RL2RL3
RL4
C2
RL6RL7 RL8 RL9RL10 RL11RL12RL13
RL14 RL16RL17RL18 RL19 RL20
RL21
D2D3D4
D5
D7
D8
D9
D10
D15
D16
D17
D18
D19
D20
D21
D22
D23
D24
D25
D26
D27
D28
D29
D30
D31
D33
D34
D35
D36
D37
D38
D39
D40
D41
D42
D43
D44
D45
D46
D47 D48
D49
D50
D51
D52
D53
D54
D55
D56
D57
D58D59
D60
D61
D62
D63
D64
U30
D88D75
D76
D77
D78
D79
D80
D81
D82
D83
D84
D85
D86
C85
R3 R4R5 R6R10
R11
R12
R14R
15
R17
R18
F1 / FM
R21 C88
R23
R43
R45
R46
R47
R48
C91
DL10
D12
D13
D14
F4 / FT
F5 / FF1R19
R24
F6 / FL
DZ2
DZ3
DZ4
DZ5
DZ6
DZ7
DZ8
DZ9
DZ10
DZ11
DZ12
DZ13
DZ14
DZ15
DZ16
DZ17
DZ18
DZ19
DZ20
DZ21
DZ22
DZ23
DZ24
DZ25
DZ26DZ27 DZ28 DZ29 DZ30 DZ31 DZ32 DZ33
DZ34
R8
R25 R26
R49
R50
R52
R53
R28
R54
R55
C4
C5 C6
C7C8
C9
C10
C11
C12
C13
C14
C15
C16
C17
C18
C19
C20
C21
C22
C23
C24
C25
C26
C27
C28
C30
C31
C32
C34
C36
C44
C45
C46
C47
C48
C49C50
C51 C52C53
C54
C55
C56
C57
C58
C59 C60 C61 C62 C63 C64 C65 C66
C67
R31
R32
C92
R64
R65
R36
D92
R80
R56
R57
U2
U3
U16
U6 U7
C81
C86
PR3 PR4
PR5 PR6
R68
R60
R62
R59
D87
C80
R61
R63
R69
R81
R70
R71
U26
D90
U24
U23
R82
R74 R75
R79
R67
R72
R73
R83
R77
X16
D96
R87 U29
C90
D94
C89
C119
V8
F3
FF2
FF1
LM2825
J4
FOP
FT
RBCAB
D92
DZ35
D69
D68
RME
RME1RME2
RM
E
5
103
SW
J2
J3
207
J1
10900
R32
CC2
CH2
FM
FL
NO LEVEL
S/N
k
j
i
h
g
f
e
d
c
b
a
SC SP IMP EMERG
P5
P4T2T1
C68
C71
C70
C69
C75
C73
C72C74
C76
X1
RET
ROPAROPCRZSRMPRLDORLBRLS
P3
P2
P1
VREG
DL11 DL7
DL10
+24V
DL8DL5
DL1
DL3 DL4 DL6
DL9
+5V
RB
74HC
164
RM
RMRRS RVR
RMT
PL1
U10
RDIP
0VCC
+24
RB
CA
B
D1D2D3 75176B
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
2212222230VP218103T220102208+12F2171052071062030VCC2103T2282202261040VCC105214294215218217213
CC1
CH1
110
DCBA+24120119118117116115114113112111109
UD
N 2543
RM
INV
RPA
RET RMT2 RMT3 RMT1
RLS RLB RLDO RMP RZS ROPC ROPA
RM RMR RB RS RVR
RDIPRDIPRDIP
UDN2981
74HC16574HC16574HC165
UD
N2987
UD
N2987
UD
N2987
ULN
2003
DM
9368
74HC
1474H
C165
TLP-521
TLP-521
RDIP
74HC165
74HC165
SW
ST9040
FF2
CC3
PULSE SERIES :• ON . PULSE (LIT)• OFF . NO PULSE (NOT LIT)
DOOR SERIES :• ON . CLOSED (LIT)• OFF . OPEN (NOT LIT)
LOCK SERIES :• ON . CLOSED (LIT)• OFF . OPEN (NOT LIT)
D1
IMP
D2
SP
D3
SC
POINTS SIGNALLINGON THE DISPLAYS
P1, P2, P3
Wiring connection terminals incontroller
Jumpers
J1 . Do no fix a jumper if CFE (emergency final contact) is used.
J2 . Fix a jumper, except for 1-speed electric lifts.
J3 . Only fix a jumper in case of universal control unit.
J4 . Fix a jumper except for hydraulic lifts with Kleeman power unit.
PCB MicroBASICSERIGRAPHY OF COMPONENTS
P5
CONFIGURATION ELEMENTS
Fuses
FOP . Operator fuse ( 3A ).
FM . Control unit fuse ( 2A ).
FT . Fuse power supply 5vdc ( 1A ), max ( 1A )
FL . Signals fuse ( 1A ), max ( 3A )
FF1 . Fuse power supply 24 vdc ( 3A ), max ( 3A )
FF2 . Fuse 20 Vs ( 3A ), max ( 3A )
CC1 . CC2 . CC3 . CH1 . CH2
Connections terminals in car and shaft
P4
Communication channel, series (RS - 485) for duplex connections withextension AMB1 and AMB2
4.2. MicroBASIC PRIMA board
4.2.1 Main components and general scheme
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 73 MTIPIEPMB300GB
Relays:
• RB: descent.Active when the car starts or is performing a service in descent, 24Vdc. With red indicator light.
• RCAB: car calls.Deletes car calls during inspection (terminal 109), 24Vdc.
• RBEXT: outside calls.Deletes outside calls if JUMPER J3 is fixed (UNIVERSAL configuration) and relay is connected during service of lift(terminal 110), 24Vdc.
• RET: start-up (hydraulic lifts).Forced draught (electric lifts), 24 Vdc. RUN signal in 3VFMAC.
• RPA: RZS control relay.Directly governed by the microcontroller, enables activating RZS when the CPS safety contact (terminals 00, 103) isclosed, 24Vdc.
• RLB: descent indicator light, 24Vdc.
• RLDO: indicator light free (not active) and occupied (active), 24Vdc.
• RLS: ascent indicator light, 24Vdc.
• RM: run.Active when the car is moving, 24Vdc. With red flashing indicator light.
• RMP: door series.Relay with 110Vac which is activated when ‘semiautomatic’ landing doors are closed, if contacts of safety series havebeen previously closed. With indicator light: on central digit of PCB MicroBASIC display.
• RMR: inspection.Active during inspection, 24Vdc. With red indicator light.
• RMT: voltage applied to control unit.There are 3 relays. Active during normal operation. Not active during emergency operation in hydraulic lifts, 24Vdc.With green indicator light.
• ROPA: automatic door opening relay, commands doors to open.
• ROPC: automatic door closing relay, commands doors to close.
• RS: ascent.Active when the car starts or is performing a service in ascent, 24 Vdc. With red indicator light.
• RVR: high speed.Active during high-speed run of car. With red indicator light.
• RZS: safety area.Active when contact CPS ‘terminals 00, 103’ is closed and microcontroller commands bridging of doors, locks and cardoors series. This occurs when the car is in the unlocking area (and the safety contact or circuit connected to terminals00 and 103 is closed). If, in this case, the car is running at slow speed, control unit starts advanced door opening;(approach with doors open). This also happens during re-levelling with open doors, 110Vac.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 74 MTIPIEPMB300GB
PIN
RVR
8 1
18"U
15"
J1
6"R2
9"11
"U13
"10
"U13
"
+24
RMT3
RMT2
RMT1
811 8
81
RMP
ROPA
1 818
43
RS1
65
RSSA
FS
0Vcc
14"U
15"
110
0Vcc
RET
RET
182
57
RET6
e
43
a
c
2
213
0Vp
FP220V
p1
M 3
FCAP
FCCP
223
221
222
ROPC
6
45
24 5
373
6RO
PA
14
PR2
FF1 V2
DL10
+24V
cc
+ -20
Vs
+5Vd
c
U30
DL9
V8FT
10
22 19
0Vs
0Vcc
+24
FL
18
LPA
LDLO
LBLS
RMP
RLB
RLS
214
294
215
218
217
766
3 4 52 7
63 4
5
63 4
5
RLDO
+24
0Vcc
8
16"U
15" D1
322
8
67 RMR
D14D9
0
RM
NIV
IMP
+-
226
0Vcc
56
5
RB
7
6
0Vcc
D11
D12
D89
17"U
15" 81
18
J2
0Vcc
D66
109
P5
RCAB
31
VREG
+24
120
31 RBEX
T
120
111
D40
D16
0Vcc
20"U
5"1"
R27"
SPE1
SPE2
3"R2
7"18
"U5"
0Vcc
D17D4
311
211
3D4
5
D18
0Vcc
16"U
5"5"
R27"
SPE3
SPE4
7"R2
7"14
"U5"
0Vcc
D19D4
711
411
5D5
5
D20
0Vcc
20"U
6"1"
R28"
SPE5
SPE6
3"R2
8"18
"U6"
0Vcc
D21D5
211
611
7D5
0
D22
0Vcc
16"U
6"5"
R28"
SPE7
SPE8
7"R2
8"14
"U6"
0Vcc
D23D4
811
8D6
3
D39
0Vcc
119
20"U
7"1"
R29"
SPE9
D60
D38
0Vcc
18"U
7"3"
R29"
SPE1
0
0Vcc
HRL1
0
SPC1
0
4"R2
9"17
"U7"
0Vcc
D36D5
9
HRL9
SPC9
2"R2
9"19
"U7"
0Vcc
D37D6
111
911
8D5
4
D24
0Vcc
13"U
6"8"
R28"
SPC8
HRL8
HRL7
SPC7
6"R2
8"15
"U6"
0Vcc
D25D4
911
711
6D5
1
D26
0Vcc
17"U
6"4"
R28"
SPC6
HRL6
HRL5
SPC5
2"R2
8"19
"U6"
0Vcc
D27D5
311
511
4D4
1
D28
0Vcc
13"U
5"8"
R27"
SPC4
HRL4
HRL3
SPC3
6"R2
7"15
"U5"
0Vcc
D29D4
611
311
2D4
4
D30
0Vcc
17"U
5"4"
R27"
SPC2
HRL2
HRL1
SPC1
2"R2
7"19
"U5"
0Vcc
D31D4
211
1 AFI
d+24 J
0Vcc
12"U
15"
RPA
RLS
RLB
15"U
15"
11"U
15"
13"U
15"
251 8
81
10 8"R5
5"8"
R29"
b
81RL
DO
11n
SPRS
+24
101
SIR
208
5"R2
9"
J3
8 1
5 2
5 2
0Vcc
0Vcc
0Vcc
RMR
RCAB
RBEX
T
111
+24
101
9
2
SPRB
PAP
SEN
CEL12
"U15
"7"
R29"
207
+24
203 13
"U22
"
R53
R61
+12F
D87
DL11
RB
NO
LEV
EL
21
16
2 552
RME1
R9
RME2
PIN
RME
2D1
5
3
DL7
EMER
G.
RMT2 10
6
ROPC
D92
5CF
E0V
cc13"U
13"
D88
D5
12"U
13"
J4RM0V
cc
HRL1
HRL2
HRL3
HRL4
HRL5
HRL6
HRL7
HRL8
HRL9
HRL1
0
Bridge
for
24vc
c
OU
TSID
E C
ALL
S A
ND
REG
ISTERS (
CH
1)
Sec
ond c
arca
ll Firs
t ca
rca
llIn
spec
ción
Sig
nal
ling
Pow
er s
upplie
s5Vcc
and 2
4Vcc
Fix
a ju
mper
exce
pt
for
1S
elec
tric
lifts
Fix
a ju
mper
exce
pt
for
klee
man
unit
+12f
Hyd
raulic
lift
+24
Ele
ctric
lift
Pin
207 f
or
leve
ller
537
indic
ator
light
bet
wee
n f
loors
Mag
net
icsw
itch
es1S e
lect
ric
lifts
Mac
324/2
4v
2S,
3S e
lect
ric
lifts
Mac
325/2
4v
Hyd
raulic
lifts
Mac
327,
328/1
2v
Sin
gle
-phas
eoper
ator
No f
ix a
jum
per
if c
fe is
use
d(e
mer
gen
cy f
inal
conta
ct)
Only
fix
a j
um
per
in u
niv
ersa
lco
ntr
ol unit
CAR C
ALL
S A
ND
REG
ISTERS
PCB MicroBASIC general scheme:
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 75 MTIPIEPMB300GB
DL6
NO LEVEL EMERG
DL11 DL7
DL10
+24V
DL8
DL5
DL1
DL3 DL4
DL9
+5V
RBRM
RMR
RS RVR
RMT
D1
IMP
D2
SP
D3
SC
PCB MicroBASIC
PL1
4.2.2 Information provided by the controller
PCB MicroBASIC supplies all the information provided by the controller concerning installation, condition ofcomponents, etc..., in three ways:
• Indicator lights (led).• 3-digit display (D1,D2 and D3 in the figure), controlled by pushbutton PL1.• Output for display: every time the car or landing position indicator alternatively displays the two lower floors, there
is information about a serious error in the installation causing the lift to stop completely.
The following figure shows the different indicator lights in the controller:
4.2.2.1. Indicator lights (leds)
• IMP : entry of pulses from pulse generator.At appearance of voltage 24Vdc on terminal 203, indicator light is switched on. In case of correct operation, it will beenergized twice, while the car is moving from one floor to the next (including extreme floors).
• SP : active when door series and the previous safety contacts are closed. That is, terminal 104 is energised with avoltage of 110 Vac.
• SC : active when all series are closed. That is, terminal 106 is energised with a voltage of 110Vac.
• +5V, : red indicator light, active when a voltage of 5Vdc is applied to the microcontroller area. If there is novoltage, check fuse FT.
• +24V. : red indicator light, active when a voltage of 24Vdc is applied to the relay actuation area and all elementsof the installation working with this voltage. In case of no voltage, check fuses FF1 and FF2.
• NO LEVEL : green indicator light.Active while the lift is not at floor level, leveller closed: terminal 207 connected to 0Vdc.
• EMERG : red flashing indicator light.Only active in hydraulic lifts during emergency operation and if the following points are accurate:
< battery voltage is adequate (> 10Vdc) at disconnection of mains supply.< all safety contacts and series are closed.< the lift is not at floor level (jumper J1 fixed) or contact CFE, connected between terminals 5 and 0Vdc, is closed
(jumper J1 not fixed).
• RMT : green indicator light.Active during normal operation of control unit. If fuses FF1 and FF2 blow, the indicator light switches off. Informs aboutthe condition of relays RMT1, RMT2 and RMT3.• RM : red flashing indicator light.Active while the lift is moving. Informs of the condition of run relay RM.
• RMR : red indicator light, lift in inspection operation.Active with voltage 24Vdc on terminal 208. Informs of the condition of relay RMR.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 76 MTIPIEPMB300GB
A B CDISPLAY onPCB MicroBASIC
Selected parameter.Possible values :( 00 ) ( 01 ) ... ( 31 )
Present value of the selected parameter.Possible values :( A ) ( B ) ( C ) ( D )
• RB : red indicator light, active when the lift starts or is performing a service in descent.Informs of the state of relay RB.
• RS : red indicator light, active when the lift starts or is performing a service in ascent.Informs of the condition of relay RS.
• RVR : red indicator light, active when the lift starts or is performing a service at high speed. Informs of thecondition of relay RVR.
4.2.2.2. 3-digit display
The 3-digit display indicates full information about a multiplicity of data concerning the lift.
Name of digits :
4.2.2.2.1. First information provided
When control unit is commissioned for the first time, the number of the software version is displayed for 3 seconds.Please indicate the number of the respective software version when contacting MACPUARSA about any technical aspectconcerning the control unit.
4.1.2.2.2. Program mode information
In PROGRAM mode (see chapter 4.2.3), digits on left-hand side and in centre indicate the number of the recentlyselected parameter, the digit on the right-hand side represents the memorised value of this parameter. That is, thenew value only appears as digit on display, once it has been defined and once PL1 button is pressed, as by pressingthe button the new value is memorised.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 77 MTIPIEPMB300GB
0 X
No. of the installation componentthe condition of which preventsmovement of lift.
(A) indicates the componentwhich mainly preventsmovement of lift
0 X
(0) indicates viewingof position of car
Position of car
4.2.2.2.3. Information in normal operation
Different blocks of information are shown on the display. In order to proceed from one block to the next, press PL1button for a short time. Once the last block is on the display, renewed pressing of button leads to return to the firstblock of information.
• Block 1 :< car position.< reasons preventing movement of car.< floor and type of call served by car.
• Block 2 : memorised car calls.• Block 3 : memorised outside descent calls.• Block 4 : memorised outside ascent calls.• Block 5 : condition of lift components.• Block 6 : stored faults and errors.
Block 1: Car position and movement
< Alternating information about the position of the car:
< Viewing of information while the lift is not moving: number of the component which mainly prevents movement oflift, and position of lift, is displayed alternately (see section 3.3 of this manual).
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 78 MTIPIEPMB300GB
Serves car call on floor 7
Serves outside ascent call on floor 4
Serves outside descent call on floor 8
1 SEC. 1 SEC.
1 SEC.1 SEC.1 SEC.
1 SEC.
1 SEC.
< Display of information during movement of lift: alternating information about type of call and floor served by thelift, and about actual position of the car.
Block 2: Memorised car calls Informs cyclically about all memorised car calls. The following figure shows the way in which the car calls to floors 2, 5and 9 appear on display:
Block 3: Memorised outside descent calls
Informs cyclically about all memorised outside descent calls. The following figure shows the way in which memorisedoutside descent calls to floors 3, 7, 8 and 10 appear on display:
Block 4: Memorised outside ascent calls
Informs cyclically about all memorised outside ascent calls. The following figure shows the way in which memorisedoutside ascent calls to floors 1 and 6 appear on display:
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 79 MTIPIEPMB300GB
No information is displayedin these digits.
PRESSPRESSDO NOTPRESS
PRESS
PROCEED TO NEXT BLOCK
(E) indicates viewing ofthe lift componentscondition
No. of the lift component:Not flashing : circuit closed or connected.Flashing : circuit open or disconnected.
Block 5: Condition of lift components
This block contains information about the conditions of the different components of the installation. Each component isprovided with a number. If this number is flashing, the respective circuit is open, not active; if the number is notflashing, the circuit of the component is closed or connected. Once this block is entered, indication is as follows:
If you wish to enter this block, wait 2 seconds until appearance of the following:
That is, information is being provided concerning the condition of component no.1. By pressing ‘ PL1 ‘ button the othercomponents may be viewed consecutively, until the last one is reached. At renewed pressing of button the (E) appearswithout information. If button is not pressed again afterwards, we remain in block 5; if button is pressed once again,we enter block 6:
Leave ‘ PL1 ‘ button pressed for several seconds, in order to arrive at point ( • ) more quickly.
IMPORTANT NOTE: If digits are blinking, condition or component is contrary to the value indicated in section 3.4 of thismanual.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 80 MTIPIEPMB300GB
PRESS
1 SEC.
1 SEC.
1 SEC.
NEXT BLOCK
PREVIOUSBLOCK
PRESS
DO NOT PRESS
AGE OFERROR
ERROR CODE
FLOOR ON WHICH ERROR OCCURRED 01: LOWEST FLOOR
NEXTBLOCKPRESS
ERRORSDISPLAY
DO NOT PRESS
Block 6: Stored faults and errors
In this block, the last 16 faults and errors which have occurred in the installation may be viewed.When a new error occurs, it appears on display, irrespective of the block which is actually being viewed, and is storedon PCB MicroBASIC. In the process, the oldest memorised error is deleted (if already 16 errors were memorised).At entry into this block of information, the error which has occurred last appears first. This means that the errorsindicated start with the youngest and finish with the oldest. Each error is provided with a number informing about itsage. Accordingly, error no. 3 must have occurred after no. 5.
Technique of representation of errors:
• The following information is displayed cyclically, with an interval of 1 second:
< Age of error and error code. < Floor on which it occurred.
• If PL1 button is pressed for less than 1 second, the next error (older than the previous one) appears, and so forth.
• If PL1 button is pressed permanently at display of any error, the following appears:
• By releasing of button and renewed pressing the following block is entered.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 81 MTIPIEPMB300GB
1 SEC.
Indicates thatinspection controlunit is operating
1 SEC.
Car ascends during inspection
Car descends during inspection
1 SEC.
4.2.2.2.4. Information during inspection
The 6 blocks of information described in the previous point also appear here. Only information offered by block 1changes:
• With the lift stopped.
• If the up button is pressed.
• If the down button is pressed.
If car is not moving, movement is prevented by a component; that is, “AAA” does not appear, but instead a code isdisplayed indicating the component which prevents movement. For further details, see section 3.3.
4.2.2.2.5. Information in special situations
• Return process, “correction”: while the lift is being returned, “effects correction at final floor”, informationconcerning position of the car appears on display (flashing).
• Error in installation: irrespective of the information actually on display, any error occurring in the installation isdisplayed, until ‘PL1’ button is pressed. The error remains memorised in non-volatile storage, for later display.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 82 MTIPIEPMB300GB
C78
R76
C87
Q1
U9
R21
R23
R19
R24
C34
C36
C46
R36
U16R60
R62
R59
C80
R77
R87
SW1
S/N
SC SP IMP
P4T2T1
X1PL1D1D2D3 75176B
DM
9368
74HC
165
74HC165
8761 2 3 4 5ON
OFF
MicroSWITCH (1) in OFF positionNormal operating mode of lift
8761 2 3 4 5ON
OFF
SW1RUN MODE
4.2.3. Configuration and adjustment of parameters
One of the most important features of the control unit is the possibility to modify a number of up to 30 parameterswith which certain functions may be adjusted (type of landing doors, main floor level, deceleration for relevelling,etc...).In normal conditions, the installer needs not to modify any parameter, since they are factory adjusted for eachinstallation.If necessary parameters may be modified according to the following method.
4.2.3.1. Parametrization method
4.2.3.1.1. Elements for configuration
Microswitches SW1 and PL1 button are used for adjusting the parameters in the control unit. They are situated in theupper left-hand area of the MicroBASIC printed circuit board. The 3-digit display (D1, D2, D3) is located next to them,enabling to view the value of the selected parameter.
4.2.3.1.2. Types of parameters
Determine which parameters are to be modified, before performing any operation.Two different groups:• Group 1: Timers TG, TE and MTR.• Group 2: Parameters [0] to [25].Depending on which group it belongs to, parametrization may vary.
4.2.3.1.3. Parametrization
• Group 1 parameters
Firstly, disconnect the controller with thermomagnetic switch QIG.
Select RUN MODE if only one of the timers (TG, TE or MTR) is meant to be changed. For this purpose microswitch no. 1of bank of microswitches SW1 is brought in OFF position.
By means of the 7 remaining microswitches the exact time for each timer may now be defined (see tables):
< TG: General timer (microswitches 2 - 3 - 4), defining the following:
! maximum door closing time (lock error detection).! time passing between the end of run and initiation of the next (collective / selective operation).
In universal operating mode, it corresponds to car timer.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 83 MTIPIEPMB300GB
SW12 Seg.
54321 6 7 8
OFFON
SW15 Seg.
54321 6 7 8ON
OFF
SW154321 6 7 86 Seg.ON
OFF
SW154321 6 7 87 Seg.ON
OFF
SW154321 6 7 88 Seg.ON
OFF
SW154321 6 7 810 Seg.ON
OFF
SW154321 6 7 812 Seg.ON
OFF
SW154321 6 7 815 Seg.ON
OFF
SW1
2 Seg.
54321 6 7 8
OFFON
SW14 Seg.
54321 6 7 8ON
OFF
SW154321 6 7 8
6 Seg.ONOFF
SW154321 6 7 8
10 Seg.ONOFF
SW1
8 Seg.
54321 6 7 8
OFFON
SW112 Seg.
54321 6 7 8ON
OFF
SW154321 6 7 8
16 Seg.ONOFF
SW154321 6 7 8
20 Seg.ONOFF
Table: Parameters TG selection:
• TE: Outside call timer (microswitches 5 - 6).
Once the general timer is finished, this timer records the time, from which the lift serves an outside call withoutpreviously choosing direction. In universal operating mode, this timer coincides with the classical outside call timer.
Table: Parameters TE selection:
• MTR: Maximum running time (microswitches 7 - 8).
Defines the maximum running time of the lift between two consecutive pulse signals. If this value is exceeded, there isan error concerning maximum running time. This points to an abnormal operating situation (for example rope slip ontraction pulleys).
Table: Parameters MTR selection:
Parameter No. 23 in PROGRAM mode enables duplicating these times for special situations.
Re-connect the controller with thermomagnetic switch QIG after fixing the positions of microswitches as indicated inthe previous tables, and the lift will operate normally with the new values of timers.
• Group 2 parameters
In MBAS PRIMAhave been inserted 32 new parameters, wich are incorporated to 32 former parameters existing , So,ther are two bank of parameters: the first one from [0] to [31] and the second from [32] to [63].
First, disconnect the controller with thermomagnetic QIG.
PROGRAM mode is used for changing parameters [0] to [31]. For this purpose, microswitch no. 1 is brought in ONposition and the control panel is re-connected. For changing parameters [32 ] to [63], in program mode, microswitchno.1 is brought in OFF position from 1 position. So, 0 parameter position corresponding with 32, 1 with 33, etc.
Subsequently, PCB MicroBASIC starts showing information on the three-digit display.
Using the following diagram, select the desired parameter and value from the microswitches bank SW1, shown in thetable Parameters Configuration.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 84 MTIPIEPMB300GB
PARAMETER (1)
PARAMETER (2)
PARAMETER (31)
VALUE (D)
VALUE (C)
VALUE (B)
VALUE (A)PARAMETER (0)
In (ON) positionPROGRAM MODE Defines binary
No. of parameter:Defines new value ofselected parameter
872 3 4 5 6
54321 6 7 8
ONOFF SW1
ONOFF
2 3 4 5 6
ONOFF
2 3 4 5 6
ONOFF
2 3 4 5 6
ONOFF
ONOFF
ONOFF
7 8
ONOFF
7 8
ONOFF
7 82 3 4 5 6
ONOFF
21
ONOFF
PARAMETER (2)
To second parameters bank
Selected parameters.Possible values:(00), (01), ... (31)
Present value of the selected parameter.Possible values :( A ) ( B ) ( C ) ( D )
< Bank of microswitches (SW1).
! Microswitch No. 1, always in ON position, program mode. En OFF for second bank, when it is in programmode.
! Microswitches No. 2, 3, 4, 5, 6, defines binary number of parameter.! Microswitches No. 7, 8, defines the new value of the selected parameter.
Once selected, it is memorised on PCB MicroBASIC by pressing of button PL1.On the display, digits on left-hand side and in centre indicate the number of the recently selected parameter, the digit
on the right-hand side represents the memorised value of this parameter. That is, the new value only appears as digiton display, once it has been defined and once PL1 button is pressed, as by pressing the button the new value ismemorised.Repeat this operation as many times as the number of parameters to be altered.Once the desired parameters are modified, the controller is once again disconnected, RUN MODE is entered and valuesof timers are defined (see previous point). Then, control panel is activated. That is, after modifying any parameter ofgroup 2 (PROGRAM MODE) disconnect control panel, enter RUN MODE and adjust group 1 parameters (timers).Then, controller is re-activated.
NOTE: In RUN MODE group 1 parameters are adjusted and in PROGRAM MODE parameters of group 2, the latter beingthe normal operating mode of lift.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 85 MTIPIEPMB300GB
MAIN FLOOR
5 - 9 - 13 2 - 6 - 10 - 14 3 - 7 - 11 - 15 4 - 8 - 12 - 16
13 - 14 - 15 - 169 - 10 - 11 - 125 - 6 - 7 - 82 - 3 - 4
4º3º2º1º
5432
3210
3210
2518105
4 - 8 - 12 - 163 - 7 - 11 - 152 - 6 - 10 - 14 1 - 5 - 9 - 13
13 - 14 - 15 - 169 - 10 - 11 - 125 - 6 - 7 - 8 1 - 2 - 3 - 4
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
PARAMETERS VALUE
NUMBERDISPLAYED MICROSWITCHES FUNCTION
NUMBER OF FLOORSOF THE INSTALLATION
FIREMAN’S KEY SWITCH FLOOR
TYPE OF LANDING DOORS MANUALSEMI-AUTOMATIC
AUTOMATIC
OPERATING MODE SELECTIVEUNIVERSAL MIXEDSELECTIVE
SELECTIVEASCENTAND DESCENT
TYPE OF INSTALLATION SIMPLEXSIMPLEXMIXED SELEC.2 CALLSDESCENT
DUPLEXLIFT 1
DUPLEXLIFT 2
NUMBER OF FLOORSASCENT INMIXED SELECTIVE
No. OF FLOORS IN LOWERAREA FOR ASYMMETRIC LIFT
No. OF FLOORS IN UPPERAREA FOR ASYMMETRIC LIFT
TYPE OF LIFT ELECTRIC HYDRAULICSPEED REGULATIONCHANGE 1C
SPEED REGULATIONCHANGE 2C
AUXILIARYTIMER (SEC)
Hydraulic Phase 8Elec. Forced Draught
0.2 SEC.DIRECT
1 SEC 2 SEC 3 SEC
AUXILIARY INPUT FUNCTIONS
- OVERTEMP.- AREA RPA- PCP
- OVERTEMP.- RPA- ELECTRIC GENERATOR
- OVERTEMP.- RPA- RELEVELLING START
- OVERTEMP.- AREA (RPA)- GONG
TYPE OF HYDRAULIC POWER UNIT STANDARD KLEEMAN
AUXILIARY OUTPUT FUNCTIONS
- COMING- CAM
- COMING+ STANDSTILL- CAM
- DIRECTION ARROWS- CAM
- OCCUPIED- CAM
Parameters configuration table [ 1 ] - [ 15 ]
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 86 MTIPIEPMB300GB
RETURN TIME TO MAIN FLOOR
ON TERM. K(COMPATIB.ANCIENTDIRECTIVE)
FIRE FIGHTERS STANDAR U 36 AUSTRAL. FIRE119 CC1+OPENDOOR CONTACT
AUSTARL. FIRE119 CC1+ OPEN DOOR TIMER
0.5 1 2 5
7 8ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65
OFF
1 2 3 4 65ON
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
OFF
ON
STICKED CONTACTER ANALYSIS STOPPED +MOVEMENT
STOPPED
ENGINE TEMPERATURESTOP FUNCTION
ENGINE TEMP.ON TERMINAL KSTOP PARAMETER 33
TERMINAL FTOGETHER WITHOVERLOADSTOP TERM. J
RECEPTIONVIA SERIESPARAMETERS
ONTERMINAL K
UTILITIES AUTO CHECK SENDINGVIA SERIESPARAMETERS
LOWESTFLOOR
UPPERFLOOR
NOT ACTIVE
NO MTR and TG
NORELEVELLING
OMRON INVERTERNO NEAR FLOOR
NEAR FLOOR
IMMEDIATE
FLOORS WITH RETURN TO MAIN FLOOR
PARAMETERS VALUE
NUMBERDISPLAYED MICROSWITCHES
3 LOWEST FLOORS
FUNCTION
NO RETURNFUNCTION
1 MINUTE 14 MINUTES
ALL FLOORS LOWEST FLOOR
2 LOWEST FLOORS
DECELERATION FOR RELEVELLING
DELETION OF CAR CALLS NODELETION
DOES NOTDELETE, IF SERIESOR PHOTOCELL ARE SWITCHED
MAXIMUMNo. OF CARCALLS: 3
MAXIMUMNo. OF CARCALLS: 6
OPTIONS FOR DIRECTION INDICATOR TYPE A
STANDARDTYPE B TYPE C
RETURN FLOOR
APPROACH WITH OPEN DOORS
DOUBLING MTR and TG TGMTR
DECISION CRITERION FORRELEVELLING DIRECTION
PARAMETERS DISPLAY(PRESS PL1)
ACTIVE
PLANTAACTUAL
REPRESENTATIONIN PERMANENTOUT-OF-SERVICE DISPLAY
LOWER FLOORSALTERNATELY.
PRESENTFLOOR
PRESENTFLOOR
PRESENTFLOOR
Parameters configuration table [ 16 ] - [ 31 ]
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 87 MTIPIEPMB300GB
PERMANENT SERVICEOUT LIGHT
NUMBERDISPLAYED
NO
MICROSWITCHES
VALUEPARAMETERS
YESNO
OUT ACTIVATION2ND SPEED BENCH
SIMULATION MODE
OUT OF ORDERDOOR PARK
ATTENDANT MODE
AUTOMATIC DOORAND ELECTRIC CAM
SHORT FLOOR 3C
PERMANENT SERVICE OUT CAM
STOP
CALLS FILTERING
terminal G
terminal K
terminal CC1-118
Terminal CH1-120
Terminal CC1-118
Both
Next FloorOut CH1-120
Next FloorOut CC1-120
Calls
terminal CC1-119
terminal CC1-119
Terminal CH1-119
terminal CH1-120
terminal CH1-120
CarMotion
Next FloorOut G
Closed
terminal CC1-120
terminal CC1-120
Terminal CC1-119
Terminal CC1-120
Terminal CC1-120
YES(terminal G)
Open
NO
NO
NO
NO
NO
NO
FUNCIÓNFUNCTION
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
NO APPLICATION
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 88 MTIPIEPMB300GB
FUNCTION
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NOFLOOR CHANGE TYPE1,2
FLOOR CHANGE TYPE15,16
FLOOR CHANGE TYPE14,15
FLOOR CHANGE TYPE13,14
FLOOR CHANGE TYPE12,13
FLOOR CHANGE TYPE11,12
FLOOR CHANGE TYPE10,11
FLOOR CHANGE TYPE9,10
FLOOR CHANGE TYPE8,9
FLOOR CHANGE TYPE7,8
FLOOR CHANGE TYPE6,7
FLOOR CHANGE TYPE5,6
FLOOR CHANGE TYPE4,5
FLOOR CHANGE TYPE3,4
FLOOR CHANGE TYPE2,3
VALUEPARAMETERS
MICROSWITCHESDISPLAYED NUMBER
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 89 MTIPIEPMB300GB
DDDDCCCCBBBBAAA
DCBADCBADCBADCB
1615141312111098765432
PARAMETER [0]
PARAMETER [1]
FLOORS
4.2.3.3. Description of parameters
• Parameters [ 0 ] [ 1 ] : Number of floors of the installation.
Functional adjustment of parameter [ 0 ] and parameter [ 1 ] to the number of floors.
Table: Adjustment of parameters [ 0 ] [ 1 ]
• Parameter [ 2 ] : Floor on which fireman’s key switch is located.
< Value A : key switch on 1st floor.< Value B : key switch on 2nd floor.< Value C : key switch on 3rd floor.< Value D : key switch on 4th floor.
• Parameter [ 3 ] : Type of landing doors.
< Value A : semiautomatic landing doors (both with or without car doors).< Value B : automatic landing doors.
• Parameter [ 4 ] : Operating mode.
< Value A : Universal.
Only 1 or 2 landing calls are accepted (simplex or duplex, respectively). Function according to the number of floors:! Up to 10 floors : connection of calls identical to selective control unit in descent. Possibility of memorising 1
car call. Landing signalling ‘coming’ is equivalent to register of landing calls.
! From 11 to 16 floors : special connection of calls. See diagrams. Only 1 car call is accepted. Landing signalling‘coming’ may be procured by adding a MS-MPX printed circuit board controlled by terminals 117, 118, 119and 120 of group CH1.
Maximum number of calls:! Simplex: 10! Duplex: 10
< Value B : Selective control unit in descent.
Maximum number of stops:! Simplex: 10! Duplex: 10
Note: It is possible to increase the number of floors with extension boards AMB1, AMB2 and AMB3.
< Value C : Mixed selective control unit.
This value is valid for simplex lifts. In operating mode mixed ‘selective control unit’, several lower floors may bedefined as ‘selective control unit in ascent’, defining the others as ‘selective control unit in descent’. Parameter No. 6defines how many lower floors belong to ‘selective control unit in ascent’. It may be that the highest floor of thosedefined as ‘selective control unit in ascent’ receives a call in ascent and descent mode, the lower ones with up callpushbutton, and the higher ones with down call pushbutton (see value B of parameter No. 5).
Maximum number of floors (1 pushbutton on «main floor») 10; (2 pushbuttons on «main floor») 9.
< Value D : Selective control unit in ascent and descent.
Maximum number of stops :! Simplex: 6! Duplex: 6
Note: It is possible to increase the number of floors with extension circuits AMB1 and AMB2.
• Parameter [ 5 ] : Type of installation.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 90 MTIPIEPMB300GB
ABC
CBC
BAC
120119118117116115114113112111654
FLOOR 1
FLOOR 2
FLOOR 3
FLOOR 4
FLOOR 5
FLOOR 6
FLOOR 7
FLOOR 8
FLOOR 9
FLOOR 10
SIMPLEX, 2ON M. FLOOR
2 FLOORSMIXED
SIMPLEX, 2ON M. FLOOR
4 FLOORSMIXED
MIXED 3 FLOORSSIMPLEX
LANDING CALLS CONNECTION (CH1)PARAMETER
FLOOR 1
FLOOR 2
FLOOR 3
FLOOR 4
FLOOR 5
FLOOR 6
FLOOR 7
FLOOR 9
FLOOR 10
FLOOR 9
FLOOR 8
FLOOR 7
FLOOR 6
FLOOR 5
FLOOR 4
FLOOR 3
FLOOR 2
FLOOR 1
FLOOR 10
FLOOR 8
< Value A : simplex.
Always fix this value in lifts with simplex universal control unit, selective control unit in descent, selective in ascent anddescent or mixed selective control unit with only 1 call pushbutton on the main floor; in this case, this floor must bethe highest with landing call in ascent.
See value C of parameter 4.
< Value B : simplex, mixed selective control unit, 2 call buttons on main floor.
This value may only be selected if the value of parameter 4 is C (simplex lift, mixed selective control unit). With thisparameter some lower floors may be defined as ‘selective control unit in ascent’, defining the others as ‘selectivecontrol unit in descent’.
Value B is selected if the highest floor of ‘selective control unit in ascent’, the typical «MAIN FLOOR», is to beprovided with a double button: ascent and descent. Thus, calls below this level will be ‘selective in ascent’ and callsabove this level will be ‘selective in descent’. In this situation, the maximum number of floors is 9.
< Value C or D : Lift 1 or lift 2 in duplex.
If control unit is duplex, one PCB MicroBASIC must be configured with value C, and the other one with value D.Assignation is indifferent.
• Parameter [ 6 ] : Number of floors ‘ascent’ in ‘mixed selective control unit’.
< Value A : 2 floors.< Value B : 3 floors.< Value C : 4 floors.< Value D : 5 floors.
Defines the number of lower floors with ascent pushbutton in the configuration ‘mixed selective control unit’ (see valueC of parameter 4). Floors above the defined floors are provided with descent buttons. If the value of parameter 5 is B‘mixed selective control unit, 2 pushbuttons on main floor’, the highest floor of those defined in parameter 6, theremust be 2 call pushbuttons, both ascent and descent. Floors above this floor are defined as ‘descent’.
See examples:
• Parameter [ 7 ] [ 8 ] : Number of floors in lower and upper area, respectively, for asymmetric lift.
< Value A : 0< Value B : 1< Value C : 2< Value D : 3
This function is only valid for Duplex installations. It enables definition of how many floors one of the lifts does notserve in the lower area (parameter 7) or in the upper area (parameter 8), with respect to the other lift. Value A isselected for the lift which arrives at all floors. The lift which does not serve some of the floors receives value B, C, orD.
IMPORTANT NOTE:Both PCB MicroBASIC must have the same value for parameters 0 and 1 (number of floors of the installation),corresponding to the number of floors of the lift which serves them all.
In any asymmetric lift, the terminals for connection of car calls corresponding with the floors not served must be free.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 91 MTIPIEPMB300GB
That is, if a lift is asymmetric on 2 floors in the lower area, terminals 111 and 112 of plug CC1 remain free.
• Parameter [ 9 ] : Type of lift.
< Value A : electric lift, 1 or 2 speeds.NOTE: Jumper J2 must always be fixed in value A, B, C and D, except in 1-speed electric lift.< Value B : hydraulic lift.< Value C : speed regulation electric lift with 3VFMAC1, change 1C (see point 5.4.3).< Value D : speed regulation electric lift with 3VFMAC1, change 2C (see point 5.4.3).
• Parameter [ 10 ] : Auxiliary Timer.
For electric lift, timer for forced draught:
< Value A : 5 sec.< Value B : 10 sec. < Value C : 18 sec.< Value D : 25 sec.
For hydraulic lift, star phase timer:
< Value A : 0,2 sec. Select this value in case of direct starting.< Value B : 1 sec.< Value C : 2 sec.< Value D : 3 sec.
• Parameter [ 11 ] : Auxiliary inputs functions.
Facilitates definition of specific functions of auxiliary entries, terminals ‘j’ and ‘k’ of group P2, and terminal 20 of groupP3.‘Complete’ signal is obtained through terminal g for all possible values of parameter 11, unless parameter 13 is givenvalue C, in which case this terminal is used to connect a cam activating relay.In OMRON frequency variation, this output is used to energize relay R2AC, which indicates service between consecutivefloors with parameter [25] in B.
< Value A :
! Terminal j (P2). Overtemperature. If voltage on this terminal (+24) disappears, the control unit stops the liftafter the end of run and remains in this condition, until once again energised, causing a return to normalservice. During the described period no car calls or landing calls are served.
! Terminal k (P2): Unlocking area for relevelling. Once control unit decides to start relevelling (hydraulic lift), itanalyses the voltage value on this terminal. If there is no voltage, it understands that the lift is below floorlevel and initiates relevelling upwards. If there is a voltage of 24Vdc, control unit knows that the lift is abovefloor level and starts relevelling downwards. See parameter no. 24.
! Terminal 20 (P3): Door closing pushbutton. As soon as voltage 24Vdc is applied to this terminal, the dooropening timer is switched off, and closing of door is initiated immediately (only if there are car calls). Makesure that voltage appears on this terminal (door closing pushbutton connected), when door is fully opened.Doors with three-phase operator must be provided with a contact (normally closed) of the door opening relay.
< Value B :
! Terminal j (P2). Overtemperature. See value A, terminal j (P2).
! Terminal k (P2): Unlocking area for relevelling. See value A, terminal k (P2).
! Terminal 20 (P3): Electric generator operation. As soon as voltage 24Vdc is applied to this terminal, controlunit knows that it is being supplied by an emergency unit and not by the mains. Only in duplex installationwithout AMB2.
< Value C :
! Terminal j (P2). Overtemperature. See value A, terminal j (P2).
! Terminal k (P2). Unlocking area for relevelling. See value A, terminal k (P2).
! Terminal 20 (P3). Command to initiate relevelling. PCB MicroBASIC initiates relevelling once the followingfactors occur simultaneously: A. Car is between floors.B. Terminal 20 is energised with 24Vdc.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 92 MTIPIEPMB300GB
If parameter 11 is given any other value, relevelling is only initiated once A) (car is between floors) occurs.
< Value D:
! Terminal f (P2). Output for GONG relay. Actuates GONG at arrival on floor.
! Terminal j (P2). Overtemperature. See value A, terminal j (P2).
! Terminal k (P2). Unlocking area for relevelling. See value A, terminal k (P2).
• Parameter [ 12 ] : Type of power unit ( hydraulic lift ).
< Value A : standard.
< Value B : Kleeman.
Delays power failure of pump behind floor on which car is stationed (ascents) for 1 second. In this case, control panelis provided with a special circuit for internal connection.
• Parameter [ 13 ] : Auxiliary outputs functions.
Facilitates definition of specific functions of auxiliary outlets, terminals h and i of group P2.
< Value A: coming, cam.
! Terminal h (P2) activates the relay for the neutral feeder of the signal voltage of ‘coming’. It is activatedwhile the lift is moving in slow speed, and remains activated after end of run, until general timer TG isfinished.
! Terminal i (P2) activates a relay which in turn actuates the cam.
< Value B: coming + standstill, cam.
! Terminal h (P2) activates the relay for the neutral feeder of the signal voltage of coming and standstill. It isactivated while the lift moves in slow speed and remains activated after end of run, until timer TG is finished,after end of operation coming. It is also activated while the lift is situated at floor level, without starting a runstandstill.
! Terminal i (P2) activates a relay which in turn actuates the cam.
< Value C: direction arrows, cam.
! Terminals h and i (P2) activate two relays for the neutral feeder of the direction arrows for descent andascent. Parameter [20] enables definition of different functional logics for direction arrows.
! Terminal g (P2). Terminal for ‘complete’ signalling, except if this value is activated temporarily and deletedafterwards, during use of this terminal for connection of a relay which in turn actuates the cam.
In frequency variation OMRON, it is used to activate relay R2AC, which indicates service between consecutive floorswith parameter [25] in B.
< Value D:
! Terminal h (P2) for special signalling in shaft, basically for lifts with universal control unit: If semiautomaticdoor is open (contact of doors open series) signal remains permanently lit.Intermittent signal, with intervals of 1 sec., during movement of lift. In other situations, signals are notactive.
! Terminal i (P2) activates relay which actuates cam.
• Parameter [ 14 ] [ 15 ] : Main floor.
In hydraulic lifts, standards require that both parameters be given value A.Functional adjustment of parameters 14 and 15 to floor defined as main floor:
Table: Adjustment of parameters [ 0 ] [ 1 ]
FLOORS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PARAMETER [0] A B C D A B C D A B C D A B C D
PARAMETER [1] A A A A B B B B C C C C D D D D
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 93 MTIPIEPMB300GB
• Parameter [ 16 ] : Return time to main floor.
< Value A : return function to main floor not initiated.
< Value B : return function initiated immediately after completing service of memorised calls.
< Value C : returns after 1 minute without operating.
< Value D : returns after 14 minutes without operating.
In hydraulic lifts, standards require not to put value A.Control unit enables return of lift to floor defined as main floor (floor defined in parameter 14 and parameter 15) aftera certain period of time. It is possible to initiate this function only when lift is situated on certain floors (see parameter17).
• Parameter [ 17 ] : Floors on which return to main floor is initiated.
< Value A : function of return to main floor is initiated, irrespective of the floor on which lift is situated.
< Value B : function of return to main floor is initiated only if lift is on the next floor in down direction.
< Value C : only in case of the two next floors in down direction.
< Value D : only in case of the three next floors in down direction.
The function of return to main floor may be limited to a fixed number of floors on which the lift is situated.
NOTE: In case of hydraulic lifts, the following parameter values become obligatory for compliance with standard EN 81-2:
< parameter 14: VALUE A.< parameter 15: VALUE A.< parameter 16: VALUE D.< parameter 17: VALUE A.
• Parameter [ 18 ] : Deceleration for relevelling.
Time during which lift must be situated between floors, for initiation of relevelling.
< Value A : 0.5 sec.
< Value B : 1 sec.
< Value C : 2 sec.
< Value D : 5 sec.
• Parameter [ 19 ] : Deletion of car calls.
Control unit is provided with different functions for deletion of car calls. Multiple car calls may occur, due to improperhandling of control station (example: 1 single passenger presses all car buttons).
< Value A : Without deletion. If this value is selected, control unit does not take any action in case of multiple carcalls.
< Value B : No deletion if door series or photocell are switched. If, by means of this system, control unit discoversthat in 2 consecutive runs of a lift, there has been no opening of door series (connection 103-104) or actuation ofphotocell (connection 2-24 Vdc), all car calls are deleted, as nobody has entered or left the car during both runs.
< Value C : Maximum number of car calls: 3. Limits number of car calls which may be registered by control unit.
< Value D : Maximum number of car calls: 6. Limits number of car calls which may be registered by control unit.
• Parameter [ 20 ] : Options for imminent departure indicator.
< Value A : direction arrows are activated while the lift is moving in one direction and calls not yet served arememorised, during slow speed and until start for serving of next call (moment at which it is deactivated). If thereare no calls not yet served, both arrows remain luminous, until timer (TG) is finished.
< Value B :Equivalent to value A, with the exception that both arrows remain luminous indefinitely, if there is nomemorisation of calls not yet served.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 94 MTIPIEPMB300GB
< Value C : Equivalent to value B, with the exception that both arrows are deactivated, if there is no memorisationof calls not yet served.
• Parameter [ 21 ] : Return floor.
Initiates return control unit for correction, at activation of lift or in case of miscorrection between floors.
Possible options:
< Value A : correction on the lowest floor.
< Value B : correction on the highest floor.
• Parameter [ 22 ] : Approach with doors open.
Activates pre-opening function of doors during approach to floor:
< Value A : not active.< Value B : active.
Note: Board 538 should be installed to activate this function.
• Parameter [ 23 ] : Doubling time of timer MTR (maximum running time) and TG (general timer).
Option only applicable to installations with very long running times between two consecutive floors (more than 20seconds).
< Value A : Normal option (values indicated in section RUN mode).
< Value B : Doubles times selected in MTR.
< Value C : Doubles times selected in TG.
< Value D : Triples MTR and doubles TG.
• Parameter [ 24 ] : Decision criterion for relevelling direction.
In this parameter, the decision criterion for direction of movement during re-levelling is defined.
< Value A : relevelling function disconnected.
< Value B : through terminal k.
Depending on the presence or absence of voltage on terminal K (P2), relevelling will be carried out by control unit inone direction or the other:
No voltage on terminal K: relevelling in up direction.24Vdc on terminal K: relevelling in down direction.
• Parameter [25] :
Only operative in VVVF with inverter OMRON. Activates running signal between consecutive floors through terminal g.
• Parameter [ 26 ] : Representation in permanent out-of-service display.
< Value A: Representation of the two lower floors alternately.
< Value B, C, and D: Representation of the floor where the car is parked.
< Parameter [ 28 ] : Parameters display.
By pressing PL1, all parameters introduced sequentially may be viewed in this parameter. To display parameters 7 and 8, they should have value A.
4.2.4. Basic functional operations
4.2.4.1. Commissioning. Return Control Unit
< Actuation of main switch QIG leads to the following:
< led 5V on, red: supply in microcontroller area.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 95 MTIPIEPMB300GB
CURRENT POSITION OF CAR
1 SEC.
IN CASE OF SEMIAUTOMATIC LANDING DOORS IN CASE OF AUTOMATIC LANDING DOORS
CURRENT POSITION OF CAR
1 SEC.
< led 24V on, red: supply with 24Vdc.< led RMT on, green: supply with 24Vdc correct.
These three led indicator lights must always be active during normal operation of lift. In the course of 3 seconds afterthe luminous sequence, a number corresponding to the software version appears on the 3 displays. Note it down incase you need to contact MACPUARSA.After commissioning, return control unit will automatically be carried out.
< Return control unit (correction on lowest and highest floors).
< The information of block 1 indicated on display is blinking.< Selection of correction direction:! If the car is situated on intermediate floors, correction is effected on furthest floor, as defined in parameter
[21] (value A: lowest floor; value B: highest floor).! If car is situated on lowest or highest floors (stopping switch open), it directly goes into normal operation.
There is no movement of the lift, except for the special case stipulated in the next point.! In case of hydraulic lifts on lowest or highest floors (stopping switch open) and between floors, relevelling will
be carried out by actuating a call to the next floor.
After completion of return control unit, information is displayed in block 1 (4.1.2.2.3), not flashing.
Return control unit always begins after luminous sequence, when the lift undergoes a miscorrection (example: throughlack of pulses) and after completion of an inspection operation.
All other indicator lights and relays are connected as in normal unit.
4.1.4.2. Normal operation
Once the lift is parked, the following information alternately appears on the displays:
In the first case, there is indication of door series being closed (central point on display active): SP (door series), andof there being no possibility for starting, as door locks are not closed (A08); logical, as in this case, there is no closure(whereby cam is actuated or car doors are closed), as long as there is no door movement.
In the case of automatic landing doors, door series is bridged (central point on display always active). At closing doorlocks, display-point on left-hand side is activated. This is normally the case, as lift is stationed with closed doors. Theinformation (AAA) shows that lift is ready for service and capable of performing any requested run.
It may happen that the information does not appear as described above. For example:
• the central display-point is not active (SP): indicates that door series or a previous contact of the safety series isopen.
• (A08) or (AAA) do not appear: another cause prevents readiness for service (example: (A07) photocell in carcovered). See tables with possible causes which prevent run of lift in chapter 3.
If a call is actuated in this situation and the lift is ready to serve this demand, the normal sequence is as follows:
• closure of car door and actuation of cam. For this purpose, relay ROPA is deactivated, and relay ROPC, as well ashigh-speed relay RVR, (led DL6) are activated. In case of electric lifts, ascent relay RS, (led DL3) or descent relayRB, (led DL4) are activated, whereby the corresponding contact (relay) is connected. If there is cam, the externalrelay of PCB MicroBASIC (RLE) is connected. In case of hydraulic lifts, only relay (RLE), which actuates the cam,is connected.
• once all series are closed (display-point on left-hand side active), interlock circuit, relay RM, with intermittent,red led indicator light: DL5, is activated. In case of hydraulic lifts, RS, with DL3 or RB, with led DL4, is activated.
In case of hydraulic lifts, relay RET (without led in the upper left-hand corner of the relay block on PCBMicroBASIC) produces the delay between the main switch relay (KCG) and run (KCM, direct starting) or the timeof the star phase, (star/delta starting).
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 96 MTIPIEPMB300GB
1 SEC.
PRESENT POSITION OF CAR
1 SEC.
INDICATES THAT INSPECTIONCONTROL UNIT IS OPERATING
• during movement, information on displays (block 1) alternately shows present position of the lift and type of callas well as floor served.
Between two floors, 2 pulses coming from the photoswitch will be received. These appear on the display-point onthe right-hand side (IMP). Furthermore, the NO LEVEL led is always active (green), with the exception of theshort moment of levelling at each stop.
• at change of speed (once the last pulse of the photoswitch is reached), relay RVR (led DL6) is deactivated.Information block 1 of the displays has the following indication:
• once the point of levelling is reached (signal 207: 0Vdc, open), NO LEVEL led is switched off and relay RM(intermittent led DL5) drops. Shortly afterwards, ascent relay RS (red led DL4) or descent relay (RB, led DL3)also drops.
4.2.4.3. Inspection operation
• Inspection operation is initiated by actuation of inspection switch. By means of this switch the circuit betweenterminals 24Vdc and 208 is closed:
! relay RMR (led DL1) of PCB MicroBASIC is activated.! any activity of control unit just taking place is stopped.! car and landing doors (if any) are closed.! information block 1 of the displays has the following indication:
! If, for example, (A06) appears instead of (AAA), information is provided that car may not be moved ininspection operation, as door series is open; see table with causes which prevent movement of lift, indocument 4.
• In order to make the lift move under inspection operation, the same point 208 is used as control station (ascentand descent) which at actuation of pushbuttons for last and first car call, respectively, is supplied with (24Vdc).
PLEASE NOTE: During inspection operation, the lift may not be moved further than stopping switches; that is,once, during ascent, the upper stopping switch is reached, the lift stops and is only able to continue in downdirection.
• In order to change from inspection operation to normal operation, change inspection switch, disconnect relayRMR (led DL1) and actuate return control unit (correction).
VERY IMPORTANT: When accessing the car roof, inspection control unit should be active.
4.2.4.4. Emergency operation
Only used in hydraulic lifts.
In case of hydraulic lifts, MicroBASIC control panel is provided with a thermomagnetic switch QIB (6A) which mustalways be activated, except if control unit will not be operating for a long period. Thus, the battery may be rechargedfrom the PCB MicroBASIC loader during normal operation and will be able to supply energy in case of emergencyoperation. Normal voltage of battery must be between 13 and 13.8Vdc (except in unloaded condition). IMPORTANT:Check regularly for correct voltage.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 97 MTIPIEPMB300GB
PCB MicroBASIC is provided with a drain sensor for the lower battery voltage. Once this voltage reaches a value ofapproximately 9 Vdc, emergency control unit is disconnected and aborted.
Emergency control unit may be actuated in case of the following:
• power failure (energy supply from mains disconnected), therefore led indicator lights RMT (DL8), 24V (DL10) and5V (DL9) are switched off.
• thermomagnetic switch QIB (6 A) is activated.
• there must be a factor informing about end of emergency operation. There are two possibilities:
A) emergency operation is finished once the lift has reached next floor in down direction. For this purpose,magnet switches 326, 327, 328 or photoswitch (MAC 524/12) may be used: supply is from points +12F and0Vdc, and their LEVELLER outlet is connected to terminals 207 and 0Vdc. In this case, jumper J1 (lower right-hand area of PCB MicroBASIC) must be fixed. The green NO LEVEL led is always luminous while lift is betweenfloors. That is, in this case, lift will only perform emergency operation if led NO LEVEL is active.
B) in the second case, emergency operation is completed at any other point of the run of lift, generally on thelowest floor.In this context, the following points must be accurate:! do not fix jumper J1 (lower right-hand area of PCB MicroBASIC).! install additional contact in shaft which is connected to terminals 5 and 0Vdc, normally closed. Opening of this
contact leads to end of emergency operation (CFE).
• in addition to the points mentioned, it is necessary that all contacts of the safety series are closed, so thatemergency operation may be initiated.
• if all previously points are accurate, there is a voltage of 12Vdc which is the voltage the battery has at thismoment, minus the voltage drop on cables at terminals 281 (+) and 280 (-), points of connection of emergencyvalve. Indicator light EMER, (red flashing indicator light) is switched on while outlet for emergency valve isenergised. NO LEVEL indicator light stays on, until lift is at floor level.
4.2.4.5. Other operations and functions
4.2.4.5.1. Opening and closing of doors
• Normal operation of car doors
If lift is provided with automatic landing doors and is stationed with doors closed, doors may be opened:! From outside : by pressing call button.! From car : by pressing door open button or call button for the floor on which car is situated.
If lift is closing doors to initiate run, closure of doors may be aborted:! From outside : by pressing call button corresponding with service defined as next service to be carried out by car. ! From car : by interrupting photocell beam, by actuating microswitch for door sensitivity (presence of obstacle), or
by pressing door open button or call button for the floor on which the car is situated.
In this case, door opening time is equal to door closing time, plus two seconds.
After the end of a run, command is given to open doors within a fixed time TG. Once this time has passed, command isgiven to close doors, if calls not yet served are memorised or if landing doors are automatic.
• Repeated door close or lock error.
Control unit will close doors and actuate cam within a fixed time TG.If series cannot be closed, command is given to open doors and/or cam is disconnected. This is followed by arenewed attempt at closing, up to 12 times maximum. If series cannot be closed, lift changes into conditioncalled ‘temporary out of service or FST’. On PCB MicroBASIC display, error F05 is indicated which remainsmemorised for later display. In this situation, the lift does not serve any landing calls. In order to return tonormal operation, there must be a car call.
• Interruption of photoelectric cell in car or opening of automatic landing door.
If beam of photoelectric cell in car is interrupted, if door open button is pressed or microswitch for doorsensitivity is open, or semiautomatic landing door remains open for more than 48 seconds, lift changes into atemporary out of service and does not serve any landing calls (error F12 or F11 are indicated). In order to returnto normal operation it is sufficient that the respective component changes into the closed circuit condition for fiveconsecutive seconds.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 98 MTIPIEPMB300GB
D
B FS
FB
FZS
10300K2 K3 K1
A
E C Shaft configurationwhen using PCB 538
Safety seriesjumperPCB 538
RELEVELLING DURING ASCENT
AREA CPS
FLOOR
RELEVELLING DURING DESCENT
4.2.4.5.2. Relevelling
• Levelling area (D) : area which defines stopping of car. Established by contact connected to terminals 207 and0Vdc (leveller):
< Open : within levelling area.< Closed : outside levelling area.
• Relevelling area : once car reaches this area, control unit is informed that relevelling must be initiated.Conventionally, this function is fulfilled by means of the same levelling component and/or contact of the safetyarea, in order to keep the number of components in shaft as low as possible. A is the relevelling area in ascentand B is the relevelling area in descent.
As standard in MicroBASIC, relevelling is initiated at leaving of levelling area, that is, when contact betweenterminals 207 and 0Vdc closes (leveller closed).
Normally, this solution is acceptable. Exceptions are cases in which levelling area is very short (hydraulic lifts withgreat stopping precision) and/or in which frequency and risk of misregulation are very high (example: hydraulic carlifts).
For such situations, there is an entry by means of which, at energising with 24Vdc, control unit is informed thatrelevelling area is reached (only in this case relevelling begins). For this purpose, parameter 11 must be configuredwith value C. In this case, an additional component must be fixed in shaft which closes contact by energising with24Vdc at entry.
• Relevelling direction : if car escapes from levelling area in up direction, relevelling must occur in down direction. Ifcar escapes in down direction, relevelling must occur in up direction. Depending on the value of parameter 24,control unit offers two possibilities for relevelling. See parameter [24] in section 4.1.3.2.
• Safety area : area within unlocking area of landing doors in which a safety contact or circuit may be fixed forbridging of door series, locks and car (connections 103-104, 104-105, 105-106), so that relevelling will take placewith open doors (EN-81).
Safety area is defined by its safety contact or circuit which is connected between terminals 00 and 103, fromgroup CC2:
! safety circuit open: outside of safety area.! safety circuit closed: within safety area.
PCB MicroBASIC always connects terminals (00) and (106) internally, thereby bridging door series, locks and car,when relevelling is initiated or when car finishes slow-speed run (see special function ‘approach with opendoors’).
If at beginning of relevelling, there is a voltage of 110 Vac on terminal (00, that is, a safety contact or circuit isexternally bridged (103 with 00)), control unit starts relevelling, without changing condition of doors.
Further features of relevelling in MicroBASIC control units:
Parameter 18 enables delaying initiation of relevelling.
Control unit always effects relevelling as quickly as possible.
In certain situations, relevelling control unit is not actuated, as this would make no sense in practice (example:
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 99 MTIPIEPMB300GB
lift initiates new run).
The installation (leveller 538) + magnetic kit switch 327/328, is provided with all functions for relevelling andapproach with open doors. These functions are applicable both to hydraulic and electric lifts.
• Approach with open doors.
Parameter 22 enables decision about whether this function is to be actuated.
Approach with open doors may be carried out during slow-speed run of car (in approach area). A safety contactor circuit must be used which informs about door unlocking area and which in turn bridges door series, locks andcar (terminals 103, 104|104, 105|105, 106). Connection at points (00) and (103, of CC2). This component is alsoused for relevelling with open doors.
During slow-speed run, PCB MicroBASIC tests voltage on terminal (00). If there is 110 Vac, this terminal isconnected internally with (106, thereby bridging series) and command is given to open doors.
• Stopping on lowest floor (hydraulic lifts)
If lift remains stationed for more than 14 minutes without running, it is automatically returned to lowest floor.Only operative in hydraulic lifts if parameter [16] = d.
4.2.4.5.3. Fireman control unit
There are two types of lift, concerning fireman control unit. Lifts prepared for Fireman Use and lifts for Non FiremanUse (fire).
• Non fireman use (fire):
Activation by closing of circuit on terminal 10 (CH2).In this case, fireman’s key switch in car, terminal 9 (CC2), is not bridged. It should remain free.When activating terminal 10 (CH2), the lift will go to the fireman floor which has been configured, will open doorsand once the door timer time has passed (TG), it will close them. In this situation, neither car calls nor landingcalls are served.If it is disconnected and re-activated in less than 5 seconds, fireman’s key switch will open and close doors.
• Fireman Use:
Activation by closing of circuit on terminal 10 (CH2).In this case, fireman’s key switch in car, terminal 9 (CC2), must be bridged.Move lift to the fireman floor which has been configured (parameter [2]).Once reached, doors will open and will remain open. In order to register a call, button should be pressed until halfthe door clear entrance is closed; otherwise, doors begin once again to open. Once closure is completed, lift startsmoving. Once on the floor, doors will not open, unless button PAP is pressed, at least, until half the door clearentrance has open. In this case, doors will remain open. If button PAP is no longer pressed and half the door clearentrance is not still open, doors begin to close again.If fireman’s key switch in shaft is disconnected and re-activated in less than 5 seconds, lift doors will close and liftwill return to fireman floor, where doors will open and close.If stationed at fireman floor, doors will open and close.
4.2.4.5.4. Mixed selective control unit
This function is only applicable in case of simplex configuration.
In addition to the current functions of selective control unit in descent and ascent, MicroBASIC facilitates operation inmixed selective control unit. Several landing calls to lower floors may operate as selective control unit in ascent. Theremaining higher floors then operate as selective control unit in descent. This may for example be useful in buildingswith garages.
Configuration technique:
• Parameter [4] : with value C, operates in mixed selective control unit.
• Parameter [5] : with value B, enables provision of the highest floor of those configured as selective control unit inascent, with 2 landing pushbuttons, one for ascent and one for descent. In order to achieve this function,parameter 4 must have value C.
• Parameter [6] : defines number of lower floors which operate in selective control unit in ascent.
Mixed selective control unit is applicable to buildings with up to 10 or 9 floors, if parameter 5 receives value B (twolanding pushbuttons on main floor).
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 100 MTIPIEPMB300GB
4.2.4.5.5. Asymmetric lifts
If one of the lifts of a duplex installation has no access to any final floor, it is called asymmetric.
This function is only applicable in case of duplex configuration.
In both lifts, parameters [0] and [1], corresponding to the number of floors of the installation, must be configured withthe same value (the total number of floors in the building).The displays for the binary input connected to both control units must have the same programming (sequence). Thismust also coincide with the total number of floors of the installation.
In parcel for connection of car calls (CC1) terminals corresponding with floors on which lift does not stop (due toabsence of pushbutton on car control station) must remain free.
• Parameter [7] : defines number of floors in lower area on which lift does not stop.
• Parameter [8] : defines number of floors in upper area on which lift does not stop. That is, asymmetry may occureither in lower or upper area; moreover, one lift may be asymmetric on lower floors and the other may beasymmetric on upper floors.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 101 MTIPIEPMB300GB
Extension inputs/outputs
Jum
per
(JP
1)
must
be
fixe
din
the
upper
are
a
R251
R220
C75
R252
D72
U17
D68
V3
Q3
U3
R255
U20
C101
R244
R243
R236
VR1
R241
R237
C91
R238
R256 R257
C98
C99
R235
R242
R219
R218
R217
R216
R215
R214
R213
R212
R211
R210
R209
R208
R207
R206R205
R204
R203
R202
R201
R200
R199
R198
R197
R196
R195
R194
R193
R150
R149
R148
R98
R97
R96
R95
R94
R93
R92
R91
R90
R89
R88
R87
R86
R85
R84
R83
R82
R81
R80
R79
R78
R77
R76
R75
R74
R73
R72
R71
R70
R69
R68
R67
R192
R191
R190
R189
R66
R65
R64
R63
R62
R61
R60
R59
R58
R57
R56
R55
R54
R53
R52
R51
R50
R49
R48
R47
R46
R45
R44
R43
R42
R41
R40
R39
R38
R37
R36
R35
R221
R1
R223
R224
R226
R227
C43
C42
C41
C40
C39
C38
C37
C36
C35
C34
C33
C32
C31
C30
C29
C28
C27
C26
C25
C24
C23
C22
C21
C20
C19
C18
C17
C16
C15
C14
C13
C12
C11
C10
C9C8
C2
F2
U35
F1
C82C83
C84
C85
R248
V4
R258
DL3
DL4
DL5
D2
C92
U16
U15
U14
D67
D66
D65
D64
D63
D62
D61
D60
D59
D58
D57
D56
D55
D54
D53
D52 D51
D50D49
D48
D47
D46D45
D44
D43
D42
D41
D40
D39
D38
D37
D36
D35
D34
D33
D32
D31
D30
D29
D28
D27
D26
D25
D24
D23
D22
D21
D20
D19
D18D17
D16
D15
D14
D13
D12 D11
D10D9
D8
D7D6
D5
R259
U2
DZ29
DZ28
DZ26
DZ25
DZ24
DZ22
DZ27
DZ21
DZ20
DZ19
DZ18
DZ17
DZ16
DZ15
DZ14
DZ13
DZ12
DZ11
DZ10
DZ9
DZ8
DZ7
DZ6
DZ5
DZ4
DZ3
DZ2
DZ23
DZ32
DZ30
DZ31
DZ1
R250
U34
C105
R249
R173
C104
R247 U3
3
C103
U32
C102
U31
C65
C64
R246
R245
C90
U30
Q2
U29
R254
TW2
TW1
Q1
1232
SYMA
C200
0
1487
*JP1
TXD
PTT
RXD
S/N
UDN2987
UDN2987
T2T1
UDN2
987
UDN2
987
C1
(-)(+) 0VCCVREG+24
IO
b a
100
100
126
125
125
124
124
123
123
122
122
121
121
120
120
119
119
118
118
117
117
116
116
115
115
114
114
113
113
112
112
111
111
110
110
DL2
1
+
D73
DL1
+
C63
154
XT1
ST90
T40
2
( * )
( * )
Printed circuit board AMB1 is alwaysinstalled to a MicroBASIC board, thusincreasing its features, as explained inchapter 1.
Description of terminals:
Plug connections (9) and (8).110 Common for outside calls (+24 Vdc).100 Common for register calls (0 Vdc).
The printed circuit board must be mountedwith an earthed special separatingincrement in the holes marked with a ( * ).It is assembled on earthed metal plate.
Ser
ial co
mm
unic
atio
n R
S485
(T1-T
2 M
icro
BASIC
)
Landin
g c
all up
To r
epla
ce A
MB1 w
ith b
oar
d A
MB1 •
,fix
jum
per
SYM
AC2000
Landin
g c
all dow
n
SILK-SCREENING OF BOARD AMB1
24 VdcMicroBASIC
Rated voltage:24Vdc (bridge between VREG and +24)
4.3. Printed circuit board AMB1
4.3.1. Main components
4.3.2. Information provided by the board
The printed circuit board AMB1 does not include display for viewing information. This information is however offered byPCB MicroBASIC, as it does without the extension. Possible errors of the installation are also registered on PCBMicroBASIC.It does include LED indicator lights providing the following information:
• DL1: Internal power supply (+5 V).• DL2: External power supply (+24 V).• DL3, DL4: Connected serial communication.• DL5: Data transmission.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 102 MTIPIEPMB300GB
No. OF FLOORS IN LOWER AREA FOR ASYMMETRIC LIFT
5 - 9 - 13 2 - 6 - 10 - 14 3 - 7 - 11 - 15 4 - 8 - 12 - 16
13 - 14 - 15 - 169 - 10 - 11 - 125 - 6 - 7 - 82 - 3 - 4
4º3º2º1º
3210
3210
2518105
4 - 8 - 12 - 163 - 7 - 11 - 152 - 6 - 10 - 14 1 - 5 - 9 - 13
13 - 14 - 15 - 169 - 10 - 11 - 125 - 6 - 7 - 8 1 - 2 - 3 - 4
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
AMB2
PARAMETERS VALUE
DISPLAYED NUMBER MICROSWITCHES FUNCTION
NUMBER OF FLOORSOF THE INSTALLATION
FLOOR WITH FIREMAN’S KEY SWITCH
TYPE OF LANDING DOORS
MANUALSEMI-AUTOMATIC
AUTOMATIC
OPERATING MODE SELECTIVEUNIVERSAL MIXEDSELECTIVE
SELECTIVEIN ASCENTANDDESCENT
TYPE OF INSTALLATION AMB1
NOT USED
No. OF FLOORS IN UPPERAREA FOR ASYMMETRIC LIFT
TYPE OF LIFT ELECTRIC HYDRAULICSPEEDADJUSTMENTCHANGE 1C
SPEEDADJUSTMENTCHANGE 2C
AUXILIARYTIMER (SEC)
Hydraulic Phase 8Elec. Forced Draught
0.2DIRECT
1 2 3
AUXILIARY INPUT FUNCTIONS
- OVERTEMP.- RPA- PCP
- OVERTEMP.- RPA- ELECTRICGENERATOR
- OVERTEMP.- RPA- START OFRELEVELLING
- OVERTEMP.- RPA- GONG
TYPE OF HYDRAULIC POWER UNIT
STANDARD KLEEMAN
AUXILIARY OUTPUT FUNCTIONS
- COMING- CAM
- COMING+ STANDSTILL- CAM
- DIRECTIONARROWS- CAM
- OCCUPIED- CAM
MAIN FLOOR
4.3.3. Configuration of parameters
If an installation includes the AMB1 board, control unit configuration is directly carried out on it, as explained in thefollowing tables.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 103 MTIPIEPMB300GB
AUSTRAL. FIRE.119CC1 +OPEN DOORTIMER
AUSTRAL. FIRE.119 CC1 +OPEN DOORCONTACT
U36
0.5 1 2 5
7 8ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65
OFF
1 2 3 4 65ON
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
OFF
ON
PRESENTFLOOR
TERMINAL FTOGETHER WITHOVERLOADSTOP TERM. J
STANDAR
RECEPTIONVIA SERIESPARAMETERS
SENDINGVIA SERIESPARAMETERS
STOPPED
ENGINE TEMP.ON TERMINAL KSTOPPARAMETER 33
AUTO CHECK
STOPPED +MOVEMENT
UTILITIES
ENGINE TEMPERATURESTOP FUNCTION
STICKED CONTACTER ANALYSIS
FIREFIGHTERS
NEAR FLOORACTIVE IN CONSECUTIVEFLOORS 1P, 3C
PRESENTFLOOR
PRESENTFLOOR
REPRESENTATIONIN PERMANENTOUT-OF-SERVICE DISPLAY
LOWER FLOORS ALTERNATELY
DOES NOTDELETE IF SERIES OR PHOTOCELL ARE SWITCHED
3 LOWEST FLOORS
PARAMETERSDISPLAY(PRESS PL1)
ON TERMINAL KNORELEVELLING
ALL FLOORS
LOWESTFLOOR
UPPERFLOOR
NOT ACTIVE
NONE BOTH
OMRON INVERTER NO NEARFLOOR
IMMEDIATE
FLOORS WITH RETURN TO MAIN FLOOR. IN HYDRAULIC LIFTS STANDARDSREQUIRE OPTION “A”.
PARAMETERS VALUE
DISPLAYEDNUMBER MICROSWITCHES FUNCTION
NO RETURN 1 MINUTE 14 MINUTES
LOWEST FLOOR
2 LOWEST FLOORS
DECELERATION FOR RELEVELLING
DELETION OF CAR CALLS NODELETION
MAX. No.OF CARCALLS: 3
MAX. No.OF CARCALLS: 6
OPTIONS FORDIRECTION INDICATOR
TYPE ASTANDARD TYPE B TYPE C
RETURN FLOOR
APPROACH WITH OPEN DOORS
DOUBLING TIMERS(MTR and/or TG) TGMTR
DECISION CRITERION FORRELEVELLING DIRECTION
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 104 MTIPIEPMB300GB
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
MICROSWITCHES
VALUEPARÁMETROS
DISPLAYED NUMBER
CH119:functionalactivation
CH118:indicateto car to star bydown call
CH117:indicate to car to star byup call
OUT ACTIVATION2nd SPEED BENCH
SIMULATION MODE
OUT OF ORDER DOOR PARK
ATTENDANT MODE
AUTOMATIC DOOR AND ELECTRIC CAM
3C SHORT FLOOR
PERMANENT SERVICE OUT CAM
PERMANENT SERVICE OUT LIGHT
STOP
CALLS FILTERING
terminal CH1-120
terminal K
terminal CH1-120
terminal CH1-117
terminal CH1-120
Both
118 CH1119 CH1
Calls
terminal CH1-118
Terminal CH1-118
terminal CH1-118
terminal CH1-118
Terminal CH1-117
Car Motion
120 CH1
Closed
terminal CH1-119
Terminal CH1-120
terminal CH1-117
terminal CH1-119
Terminal CH1-118
YES(terminal G )
N/A
Open
NO
NO
NO
NO
NO
NO
NO
FUNCIÓNFUNCTION
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 105 MTIPIEPMB300GB
FUNCTION
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1P2C 3C
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
1 2 3 4 65ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
7 8ONOFF
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NOFLOOR CHANGE TYPE1,2
FLOOR CHANGE TYPE15,16
FLOOR CHANGE TYPE14,15
FLOOR CHANGE TYPE13,14
FLOOR CHANGE TYPE12,13
FLOOR CHANGE TYPE11,12
FLOOR CHANGE TYPE10,11
FLOOR CHANGE TYPE9,10
FLOOR CHANGE TYPE8,9
FLOOR CHANGE TYPE7,8
FLOOR CHANGE TYPE6,7
FLOOR CHANGE TYPE5,6
FLOOR CHANGE TYPE4,5
FLOOR CHANGE TYPE3,4
FLOOR CHANGE TYPE2,3
VALUEPARAMETERS
MICROSWITCHESDISPLAYED NUMBER
4.3.4 OperationOperation is identical to MicroBASIC simplex control unit, but more features are included, as indicated in chapter 1.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 106 MTIPIEPMB300GB
EX
TEN
SIO
NIN
PUTS
/OU
TPU
TS
SE
RIA
L C
OM
. RS
485
(T1-
T2 M
BA
S)
LIFT
4
U1
U2
R1
TW1
C2
C105
D1
D75
V2
U8
U12
U52
+ C48
V6
D5
V15
U14
U18
R234
DL1
U29
R171
U30
V16
U31
U35
9
1 5
6
XL2
X1
U37
L1
U3
R103
R3R4
R5
R6
R7
R8
C106
R104
R105
R106
C107
R108
R109
R110
R111
R112
R113
R114
R115
C108
R117
R118
R119
R120
R121
R122
R123
C110
R125
R126
R31
R127
C111
R35
R36
R37
R38
R39
R40
R41
R42
R43
R44
R46
R216
R48
R49
R50
R51
R52
R53
R54
R55
R56
R57
R58
R59
R60
R61
R62
R63
R64
R65
R66
R67R68R69R70R71R72
R73
R74
R75R76R77R78R79R80R81R82
R83
R84
R85
R86 R87 R88 R89 R90
R91
R92
R93
R94R95
R96
R97
R98
R129
R130
R131
R132
R133
R134
R135 R136
C112
R138
R139
R140
C113
R142
R143 R144
R145
R146
R147
R148
R149
R150R151
R152
R153
R154
R155
R156
R157
R158
R159 R160
R161R162
R163
R164
R165
R166
R167
R168
R169
R170
R173
R174
R175R176
R177
R178R179
R180
R181
R182
R183
R184
R185
R186
R187
R188
C3
C4
C49
C50
C51
C52
C53
C54
C55
C8
C9
C10
C11
C12C13
C14C15
C16C17
C18C19
R217
C21
C22
C23
C24C25
C26C27
C28
C29
C30
C31
C32C33
C34C35
C36
C37
C38
C39
C40
C41
C42
C43
C44
C45
C46
C47
C56
C57
C58
C59
C63
C64
C65
C66
C67
U50
C69
C70C71
C72
C68 U3
6
C75
F3 F4
D69
D2D3
D4
D70
D71
D72
V3
V4
V5
V10
V11
V12
V13
C114
XL1
U25
U27
U28
C130
CV1
+
C60
+
C61
+
C62
V7
V8V9
D6D7D8
D9 D10
D11
D12
D13 D1
4D1
5
D16
D17 D1
8D1
9
D20
D21
D22
D23
D24
D25
D26
D27
D28
D29 D30
D31
D32
D33 D34
D35
D36
D37 D3
8D3
9
D40
D41 D4
2D4
3
D44
D45
D46
D47
D48
D49 D5
0D5
1
D52
D53 D5
4D5
5
D56
D57 D5
8D5
9
D60
D61 D6
2D6
3
D64
D65 D6
6D6
7
D68
D74
U53
TW8
TW9
TW5
D77
R231
R229
R230
R232
R227
R218
R225
R226
R228
C116C117C118
C119
C120
C121
C122
C123
R224
C76
C77
U15
U16
U17
R219
U20
U21
DL2DL
3
DL4
DL5
DL6
U32
U33
U34
X2X3
R220
R215
R213
R212
R211
R210
R209
R208
R207
R205
R203
R202
R201
R200
R199
R198
R197
R196
R195
R194
R193
U19
R192
R190
R189
R214
R204
C20
R47
R191
C79
V14
+
C83
R223
+C82
+C8
1
D76
+C8
0C7
8
U46
U45
R222
C115
U44
TR1
U43
U42
U41
R221
U49
U48
U47
C104
C103
C102
C101
C100
C99
C98
C96
C95
C94
C93
C92
C91
DZ32
C109
C90
C89
DZ31
DZ30
DZ29
DZ28
DZ26
DZ25
DZ24
DZ23
DZ22
DZ21
DZ20
DZ19
DZ18
DZ16
DZ15
DZ14
DZ13
DZ12
DZ11
DZ10
DZ27
DZ8
DZ17
DZ7
DZ6
DZ5
DZ4
DZ3
DZ2
DZ1
C88
C87
C86
C85
C84
D78
R233
R235R236
D79
C129
TW4
TW7
U51
C134
C133 C132
U55
PS2
PS3
PS4
PS5
U54 C1
47
C144
C145
C143
C146
TW6TW
2+
TW3
PS1
R238
R237
CON4CON3
CON1
CON2
S/N
C1
A1A2
A3 A4
PFC8573
1232
HC244
SAA1064
HC20
MIC5
841
HC244
HC16
5HC
165
HC16
5HC
165
MAX1
480
MAX1
480
ST90
T40
LM28
25
MAX250
4N26
4N264N26
MAX1480MAX251
MAX1480
UDN2987
UDN2987
UDN2
987
UDN2
987
D4D3
D2D1
b a
IO
1
100
100
126
125
125
124
124
123
123
122
122
121
121
120
120
119
119
118
118
117
117
116
116
115
115
114
114
113
113
112
112
111
111
110
110
43
21
T2T1T2T1
T2T1
T2T1
(+)(-)
(+)(-)
(+) (-) (+) (-) 0VCCVREG+24
F5
+
BAT
BAT
F1F2
RS-232C
L1
ASC.
424
Vdc µ
B
ASC.
324
Vdc µ
B
ASC.
224
Vdc µ
BAS
C. 1
24 Vd
c µB
CHB1
CHB2
CHS2
CHS1
( * )
( * )
SE
RIA
L C
OM
. RS
485
(T1-
T2 M
BA
S)
LIFT
3 SE
RIA
L C
OM
M.
RS
232C
TELE
CO
NTR
OL
LAN
DIN
G C
ALL
UP
LAN
DIN
G C
ALL
DO
WN
SE
RIA
L C
OM
. RS
485
(T1-
T2 M
BA
S)
LIFT
2
SE
RIA
L C
OM
. RS
485
(T1-
T2 M
BA
S)
LIFT
1
RO
W 1
RO
W 2
SILK-SCREENING OF BOARD AMB2
RA
TED
VOLT
AGE
24 V
dc (B
RID
GE
BET
WEE
NV
RE
G A
ND
+24
)
4.4. Printed circuit board AMB2
4.4.1. Main components
Printed circuit board AMB2 is always installed to a MicroBASIC board, thus increasing its features, as explained inchapter 1.
Description of terminals:
Plug connections CHB1, CHB2 (9) and CHS1, CHS2 (8).110 Common for outside calls (+24 Vdc).100 Common for registers/calls (0 Vdc), except in universal control unit, which is 110 of CH1 of MicroBASIC.
The printed circuit board must be mounted with an earthed special separating increment in the holes marked with a(*). It is assembled on earthed metal plate.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 107 MTIPIEPMB300GB
Figure 1 Figure 2
RED LED STATUS GREEN LED STATUS STATUS OF LIFT DESCRIPTION
ON OFF OUT OF SERVICE
Cause :• No connection.• The lift is CONSTANTLY OUT OF SERVICE (control unitindicator error).
BLINKING ONOUT OF SERVICE FOR PASSENGERS
Lift in :• INSPECTION.• FIREMAN operation.• Emergency operation.
BLINKING BLINKINGOUT OF SERVICEFOR PASSENGERS
RETURN (reset to initial position).
BLINKING OFFOUT OF SERVICEFOR PASSENGERS
LIFT TEMPORARILY OUT OF SERVICE:• Indication of cause in control unit.
OFF ONIN SERVICE
FOR PASSENGERSLIFT IS IDLE, safety series OPEN.
OFF SLOWLY BLINKINGOUT OF SERVICEFOR PASSENGERS
LIFT IS IDLE, safety series CLOSED.
OFF BLINKINGOUT OF SERVICEFOR PASSENGERS
LIFT OPERATING.
OFF OFF NONE NOT APPLICABLE.
4.4.2. Information provided by the board
The information indicator of the MicroBASIC printed circuit board with the AMB1 and AMB2 extensions provides thesame information as the standard MicroBASIC control unit, both in LED-indicators and in the 3 digits on the display.
When the PCB MicroBASIC operates with AMB2, in the case of down (Figure 1) or up (Figure 2) landing calls, only thecall, as allocated in real-time through the AMB2 printed circuit board is indicated. In order to display all stored landingcalls, information provided by the AMB2 printed circuit board must be displayed.
AMB2 printed circuit board includes the following information indicators:
• 13 led light indicators.• 1 4-digit display.
4.4.2.1. Led light indicators
• Every single one of the four possible voltage feeders ( +, - ) with 24 Vdc which exit from the MicroBASIC controlunits, have a green led-indicator for verification of each connected voltage. Each led-indicator is located in theimmediate area of the corresponding connection. If the led-indicator is not illuminated, although there is voltageon the terminals, inspect the condition of the respective fuse.
• Next to the microprocessor is a green led which indicates that 5 Vdc are connected to the microprocessor.
• One green an one red led-indicator belong to each one of the four possible lifts. The following table indicates theinformation displayed according to the led status.
Notes:
Be certain that all 8 led-indicators respond simultaneously for some seconds upon switching on the control unit. In PROGRAM mode, all 8 led-indicators are in the on position (see point 4.3.3.2).In the stand-by mode, all 8 leds are in the off position (see point 4.3.4.2).
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 108 MTIPIEPMB300GB
P/R
PUSHBUTTONS
DISPLAY
ERROR CODE No. OF LIFT AND No. OF FLOOR DATE TIME
4.4.2.2. 4-Digit display
Under the display there are three pushbuttons enabling configuration of the printed circuit board and information aboutit (see point 4.3.3.1 also).
The equipment has two modes of operation: RUN mode and PROGRAM mode. One switches between the two with theP/R pushbutton.
4.4.2.2.1. RUN Mode: information indication
In this operating mode, information about lifts in operation can be indicated on the display. In order to view variousinformation, press button (<) and the following information will alternately appear:
• Stored landing calls, down.• Stored landing calls, up.• Present position and destination landing of the lifts (* 1).• Time and date (* 2).• List of past error messages registered by the control unit (* 3).
The remaining information can be retrieved with pushbutton (>) which pertain to the above mentioned blocks markedwith a (*):
• (* 1) Switching between the different lifts. Information about present position and destination of lift (if any) is indicated cyclically.
• (* 2) Switching between time and date by pressing button (>).
• (* 3) By pressing button (>), one obtains the error messages from further in the past, in recorded time segments. The following information alternately appears for each stored error message:
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 109 MTIPIEPMB300GB
UP CALLS IN MEMORYALTERNATING INDICATION OFALL STORED CALLS
1
2
3
4
5 ( * )
( * )
PRESSING BUTTON (>), THE PREVIOUS ERROR MESSAGESAPPEAR
TIME:PRESSING BUTTON (>), THE TIME IS SHOWN
LIFT 1 IS LOCATED AT LANDING 4. WHEN BUTTON (>) IS PRESSED, LOCATION OF THEOTHER LIFTS IS SHOWN
ERROR CODE No. 13 DATE OF THE ERROR
PRESS
TIME OF THE ERRORLIFT 2 FLOOR 12
LIFT IS LOCATED AT LANDING 4 AND RESPONDS TO THE DOWNLANDING CALL FROM LANDING 12
DOWN CALLS IN MEMORYALTERNATING INDICATION OF ALL STORED CALLS
Flow Diagram: RUN Mode
(*) Alternating indication
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 110 MTIPIEPMB300GB
Value of parameter
No. of parameter
Press (>)
4.4.2.2.2. PROGRAM Mode: Information indication
In this operating mode, configuration parameters may be displayed and modified (also see point 4.3.3.2).
Initially, display shows a number of parameter PX; pressing (<) the desired number of parameter may be selected.
Pressing (>) the value of this parameter is indicated.
4.4.2.2.3. Special indications
• Blinking indications on the displays.
The control unit indicates that the stored information for the DATE and TIME are INCORRECT through a blinkingindicator in the RUN mode. Parameters 11 (time) and 12 (date) must be correspondingly re-programmed. Shouldthe date and time still be incorrectly shown, then the AMB2 circuit board must be replaced.
• Redundancy situation.
The MicroBASIC control unit with AMB2 circuit board can work redundantly (see chapter 4.3.4.2). In this case,one AMB2 board functions in normal operation, while the other remains in STAND-BY mode, whereby theindicator displays:
• Error Display.
The AMB2 circuit board stores the last 25 errors that occurred in the equipment and shows them on the display.
Should an error occur, the current indication on the display goes out and the error message appears, alternatelyshowing all relevant information (also see chapter 4.3.5).
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 111 MTIPIEPMB300GB
P/R
PUSHBUTTONS
DISPLAY
4.4.3. Configuration and adjustment of parameters
4.4.3.1. Configuration elements
If the AMB2 circuit board is included in an installation, parametrization is carried out both on the AMB2 board and onthe MicroBASIC control unit. Parametrization of the latter was described in point 4.1.3, even though in this caseparameters differ, and new functions and values are indicated in point 4.3.3.3.
The AMB2 circuit board can be configured with the assistance of the following elements:
• 4-digit display.• 3 pushbuttons.
The equipment has two modes of operation: RUN mode and PROGRAM mode. One switches between the two with theP/R pushbutton. Configuration should be carried out in PROGRAM mode.
4.4.3.2. PROGRAM Mode
In this operating mode in AMB2, the configuration parameters can be indicated and/or changed.
The various operating elements have the following functions :
• The 4-digit display informs of the selected parameter and the value at which it is currently set. Stores a newvalue.
• P/R button switches between RUN and PROGRAM mode.
• Button (<) serves the purpose of selecting the parameter and positioning, changing the values within the display.
• Button (>) serves the purpose of indicating the value of the selected parameter and modifying the value of theselected digit.
Operating mode:
• In RUN mode, pressing P/R switches to PROGRAM mode.
• In PROGRAM mode, the 8 led-indicators (4 pairs, one per lift) are in the on position. The received landing callsare NOT deleted, but are NOT served by any lift while the PROGRAM mode is running.
• In order to select a parameter press (<) repeatedly, until the display indicates the desired parameter.
• Once selected, press (>) to display the value at which it is set. Left-hand digit will be blinking to indicate it isbeing edited.
• In order to modify the value of the parameter press (<) until the digit to be changed appears (blinking). Then,press (>) to modify the value of the digit. Pressing P/R, stores the new value.
• If only the parameters should be indicated (without change), press P/R directly (without performing the last twopoints). If P/R is pressed again, you should reach the RUN mode.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 112 MTIPIEPMB300GB
BY PRESSING P/R, THE NEW VALUE OF THE PARAMETER WILL BE STORED
PRESS (<) REPEATEDLY UNTIL THE DESIRED PARAMETER BLINKS
AFTER PRESSING (>) 3 TIMES, THE VALUE OF PARAMETER 2 IS NOW 13 LANDINGS
FOR 1 SEC THE MESSAGE PO APPEARS ON THE DISPLAY. THAT MEANS THAT THE NEW VALUE IS CORRECT AND IS STORED IN THE CHANGER. IF THE NEW ENTERED VALUE ISNOT PERMITTED, THE MESSAGE PF APPEARS ON THE DISPLAY AND THE PREVIOUS VALUE IS INDICATED AGAIN.
PR
ES
SIN
G P
/R, W
ITH
A P
AR
AM
ETE
RB
EIN
G S
ELE
CTE
D, C
HA
NG
ES
INTO
RU
N M
OD
E.
SELE
CTI
ON
OF
PA
RA
ME
TER
SSE
LEC
TIO
N O
F TH
E D
IGIT
VAL
UE
OF
THE
PA
RA
ME
TER
TO
BE
MO
DIF
IED
CH
AN
GIN
G A
ND
STO
RIN
GTH
E N
EW
PA
RA
ME
TER
VA
LUE
1
2
3
4
5
6
7
PRESS P/R
DISPLAY OF STORED DOWN CALLS
CHANGE TO PROGRAM MODE. PARAMETER 1 APPEARS
FOR EXAMPLE, CHANGE PARAMETER 2: No. OF LANDINGS
PRESS (<) REPEATEDLY UNTIL THE DESIRED PARAMETER IS INDICATED
THE CURRENT VALUE OF PARAMETER 2 IS 10 FLOORS.THE LEFT-HAND DIGIT IS BLINKING.
PRESS (>) REPEATEDLY UNTIL THE DESIRED VALUE CAN BE SET
PRESSING (>) THE SELECTED PARAMETER IS DISPLAYED
AFTER PRESSING (<) 3 TIMES, THE FOURTH DIGITIS NOW BLINKING. THIS VALUE IS TO BE CHANGED
The following diagram shows the above-mentioned information.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 113 MTIPIEPMB300GB
CALL TO CENTRAL CONTROL OFFICE0 : Deactivated1 : Activated
TYPE OF MODEM0 : conventional1 : GSM
TYPE OF ERROR WHICH TRIGGERS A CALL OR SMS0 : Only serious errors1 : All errors
SHORT MESSAGES-SMS SERVICE (Message to a mobile phone GSM)0 : Deactivated1 : Activated
4.4.3.3. Parameters configuration table for MicroBASIC control unit with additional AMB2 board
To configurated this parameters see point 4.3.3.
4.4.3.4. Configuration of parameters on the AMB2 circuit board
PARAMETER No. VALUE DESCRIPTION
1 1 - 4 Number of lifts controlled by AMB2.
2 2 - 16 Total number of landings in the building.
3 0000 - FFFF Calls not served in downward motion lift 1 (in hexadecimal). (5)
4 0000 - FFFF Calls not served in downward motion lift 2 (in hexadecimal). (5)
5 0000 - FFFF Calls not served in downward motion lift 3 (in hexadecimal). (5)
6 0000 - FFFF Calls not served in downward motion lift 4 (in hexadecimal). (5)
7 0000 - FFFF Calls not served in upward motion lift 1 (in hexadecimal). (5)
8 0000 - FFFF Calls not served in upward motion lift 2 (in hexadecimal). (5)
9 0000 - FFFF Calls not served in upward motion lift 3 (in hexadecimal). (5)
10 0000 - FFFF Calls not served in upward motion lift 4 (in hexadecimal). (5)
11 00.00 - 23.59 Time of operation.
12 01.01 - 31.12 Date of operation.
13 0000 NONEAccess code: Should the access to the PROGRAM mode be protected through a code, avalue other than 0000 must be entered.
14 0000-1111 Communications control.
15 - 18 -3 Telephone number of the central control office.
19 - 21 -3 GSM telephone number for short messages (SMS). (1)
22 - 24 -3 Telephone number of the central message server (SMSC). (1)
25 - 27 -3 Own telephone number. (2)
28 0 - 1 0: Normal - 1: Redundant circuit board
(1) Enter international telephone number (without the dialling code).
(2) This number must be consistent with the number of the central control office in the data base.
(3) All telephone numbers must be entered with letter ‘E’ to designate end of telephone number.
(4) Meaning of digits of parameter 14:
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 114 MTIPIEPMB300GB
FLOORS LIFT 1 LIFT 2 LIFT 3 LIFT 4
6 X DOWN DOWN X
5 X UP/DOWN UP/DOWN DOWN
4 DOWN UP/DOWN UP/DOWN UP/DOWN
3 UP/DOWN UP/DOWN UP/DOWN UP/DOWN
2 UP/DOWN UP UP/DOWN UP
1 UP X UP X
ASYMMETRYThe asymmetry must be configured for each individual lift on the MicroBASICcircuit board.
ABOUT THE CALLSUp calls from the uppermost landing arenot accepted and down calls from the lowest landing are not accepted.
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
0000 00001 10010 20011 30100 40101 50110 60111 71000 81001 91010 A1011 B1100 C1101 D1110 E1111 F
1 100
Group 4 Group 3 Group 2Group 1
Calls which lift 1 does not accept in descent (5and 6)
Binary-Hexadecimal ConversionHexadecimalBinary
Landings
DisplayParameter 3
(5) Practical example of an asymmetric quadruplex control unit.
A. Lift 1 accepts no down calls from landings 5 and 6. Parameter 3 / Display [0030]
B. Lift 1 does not accept calls from landings 4 and 5 in ascent.Parameter 7 / Display [0018].
C. Lift 2 does not accept calls from landing 1 in ascent.Parameter 8 / Display [0001].
D. Lift 2 does not accept calls from landing 2 in descent.Parameter 4 / Display [0002].
E. Lift 4 does not accept calls from landings 2 and 6 in descent.Parameter 6 / Display [0022].
F. Lift 4 does not accept calls from landings 1 and 5 in ascent.Parameter 10 / Display [0011].
G. Parameters 5 (lift down travels 3) and 9 (lift up travels 3) are set to [0000].
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 115 MTIPIEPMB300GB
4.4.4. Operation
4.4.4.1. Operation in normal configuration
Operation of the MicroBASIC + AMB2 assembly is identical to the simplex MicroBASIC control unit, but more featuresare included, as indicated in chapter 1.
4.4.4.2. Redundant operation
The MicroBASIC control unit can operate redundantly with the installed AMB2 extension module, when two AMB2circuit boards are installed, instead of one (normal configuration). This redundant procedure should reduce the risksthat can arise when only one AMB2 controls the lift group. As a standard, MACPUARSA installs the redundant groupsafety system for all triplex and quadruplex groups.
Basically, the operating mode is such that one of the two AMB2 circuit boards controls the lift group and the otherremains in the STAND-BY mode (indication on the display ‘STBY’).
The second circuit board constantly controls the correct operation of the first AMB2. Should it be determined that it isno longer operating correctly with all the lifts of the group, the second one takes over the control of the entire group.The time between the failure of the one and the take-over by the other circuit board should not exceed 20 seconds.
When the second circuit board, originally in STAND-BY mode, has taken over the control, it can no longer leave thismode of operation independently. In order to reset this circuit board in the STAND-BY mode, change to the PROGRAMmode and back again or briefly interrupt the electrical supply.
Notes about the redundant operating mode:
• Redundancy is always operated with two AMB2 circuit boards, for duplex, triplex or quadruplex groups. Theredundant control is always possible, even though for triplex and quadruplex groups it is recommended.
• The wiring for a redundant control unit (two AMB2 circuit boards) is identical with the wiring for only one AMB2.The wires end in both printed circuit boards; that means, they operate parallel to one another, the wires must beattached to the same points of each printed circuit board.
• Parametrization of both circuit boards must be identical with the exception of parameter [28], which defines whichone is the normally operating circuit board and which one remains in STAND-BY mode.
Information on the active redundant operation:
If the circuit board normally in STAND-BY mode should change to operating mode (after an error was determined inthe AMB2 which normally controls operations), a signal is activated which indicates this active redundant operation.The output wiring (a) from the EXTENSION PACKAGE INPUTS/OUTPUTS of the redundant AMB2 circuit board(STAND-BY) is activated when it takes over the control of the lift group. If between this point and 0Vdc a led-indicator is connected (not a light bulb) and installed in the main floor of the building, then the users of theequipment will be made aware of the special operation status.
During the regular inspections, the following maintenance work must be completed on the AMB2 redundant system:
< Check to see whether the circuit board is operating in normal operation mode and the redundant AMB2 circuitboard (STAND-BY) offers the information on the display. If the redundant circuit board is currently in operationmode, investigate the cause for this (possible failure of the first AMB2).
• The correct operation of the redundant operation of the lifts must be checked. To do so, proceed as follows:
! During normal operation of the lifts, all 24Vdc incoming mains cables to the first AMB2 (the controlling circuitboard under normal conditions) should be removed.
! Within 20 seconds, the AMB2 changes from the STAND-BY mode to the operation mode and controls the lifts.Check for several minutes, to see that this is the case.
! In order to set the first circuit board back into the general operation mode, connect the electrical supply againcompletely. Be certain that all connections are connected again.
! After that, the second redundant AMB2 is switched to PROGRAM mode and switched off again, so that itconclusively remains again in the STAND-BY mode.
TECHNICAL DOSSIER
PRE-ASSEMBLED ELECTRICAL INSTALLATION MICROBASIC
V3.0, APR.05 Page 116 MTIPIEPMB300GB
4.4.5. Control unit errors
When an error occurs on one lift, it is stored by the MicroBASIC as well as by the AMB2. The coding of the errors is thesame in both, however, the following information is stored additionally by the AMB2:
! number of lift.! landing at which the error occurred.! time.! date.
The error codes displayed by the AMB2 circuit board are identical to those by the MicroBASIC (see point 4.1.5), withthe exception of certain special operation errors of AMB2:
• F50: Communication failure.If the communication between the AMB2 and a MicroBASIC control unit definitely fails, this error message will beindicated together with the number of the relevant control unit.
• F80: Parameter loss.This occurs when it is determined that the configuration parameters of the AMB2 are incorrect. Consequently, theerror message [F80] appears (the information about the lift number is no longer relevant). Start over and enterthe correct values for the individual parameters.
When error F80 occurs, the AMB2 circuit board is self-configured to an operating situation so that lifts are notstopped. They would continue operating, even though this situation would not be quite correct.
Should an error occur, the current indication on the display goes out and the error message appears, alternatelyshowing all relevant information.
www.macpuarsa.es
HEAD QUATER
Pabellón MP
Leonardo Da Vinci, 15 Isla de la Cartuja – 41092 Sevilla
Tel. +34.95.4630562 Fax +34.95.4657955
e-mail: [email protected]