2
MTN-Dual 1-3 kVA MTN-Dual 6-10 kVA MTN-Dual series is online double-conversion UPS with full DSP control technology. With 19 inch standard rack design, self-adjusting output frequency, smart battery management system and network management. MTN-Dual is a perfect choice for computers, IT equipment and other sensitive device. DSP Technology: The advanced DSP digital control technology enables UPS more stable performance. Active input power factor correction (PFC): Digitalized control of the PFC enable the UPS to keep input power factor above 0.99 to prevent possible electric grid pollution and meanwhile mostly save the cost. Zero power switch delay: When the utility power fails, UPS will automatically switch from AC mode to battery mode with no delay, which ensures stable power supply of operating system. Environment Friendly: This UPS is eco-designed and manufactured to meet the most local pollution control requirement of Electronic Products, which means it will cause no harm to environment and human beings in normal usage. FEATURES Wide range of input voltage while input PF>99% Output PF of 1.0 (6-10kVA) Full protection of overvoltage, circuit short and over temperature Network/fax/modem surge protection LCD/LED display, monitoring all the operation status 19 inch standard cabinet and battery cabinet Automatic fan speed adjustment Abundant interfaceRS232,USB, SNMP, Intelligent Card Generator Compatibility: The wide range of input voltage and frequency can effectively separate the harmful electric wave produces by the generators and provide safe and reliable power supply. Large LCD screen Wide range of input voltage and frequency: We intentionally widen the range of input factors to make sure the UPS can apply to various environment, which will effectively sustain the battery charging even in unstable power environment so that the service life of the UPS could be obviously prolonged. MTN - Dual 1kVA~10kVA Online Double Conversion Tower or 19" rack mount UPS

Upload: others

Post on 02-Apr-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MTN-Dual 1kVA~10kVA - EPI UPSepi-ups.com/wp-content/uploads/2018/11/MTN-Dual-rev5.pdf · make sure the UPS can apply to various environment, which will effectively sustain the battery

MTN-Dual 1-3 kVA MTN-Dual 6-10 kVA

MTN-Dual series is online double-conversion UPSwith full DSP control technology. With 19 inchstandard rack design, self-adjusting output frequency,smart battery management system and networkmanagement. MTN-Dual is a perfect choice forcomputers, IT equipment and other sensitive device.

DSP Technology: The advanced DSP digital controltechnology enables UPS more stable performance.

Active input power factor correction (PFC): Digitalizedcontrol of the PFC enable the UPS to keep input powerfactor above 0.99 to prevent possible electric gridpollution and meanwhile mostly save the cost.

Zero power switch delay: When the utility power fails,UPS will automatically switch from AC mode to batterymode with no delay, which ensures stable powersupply of operating system.

Environment Friendly: This UPS is eco-designed andmanufactured to meet the most local pollution controlrequirement of Electronic Products, which means itwill cause no harm to environment and human beingsin normal usage.

FEATURES• Wide range of input voltage while input PF>99%• Output PF of 1.0 (6-10kVA)• Full protection of overvoltage, circuit short andover temperature• Network/fax/modem surge protection• LCD/LED display, monitoring all the operationstatus• 19 inch standard cabinet and battery cabinet• Automatic fan speed adjustment• Abundant interface:RS232,USB, SNMP, IntelligentCard

Generator Compatibility: The wide range of inputvoltage and frequency can effectively separate theharmful electric wave produces by the generatorsand provide safe and reliable power supply.

Large LCD screen

Wide range of input voltage and frequency: Weintentionally widen the range of input factors tomake sure the UPS can apply to various environment,which will effectively sustain the battery chargingeven in unstable power environment so that theservice life of the UPS could be obviously prolonged.

MTN-Dual

1kVA~10kVA Online Double Conversion

Tower or 19" rack mount UPS

Page 2: MTN-Dual 1kVA~10kVA - EPI UPSepi-ups.com/wp-content/uploads/2018/11/MTN-Dual-rev5.pdf · make sure the UPS can apply to various environment, which will effectively sustain the battery

Specification

This publication is issued to provide outline information only and is not deemed to form any part of any offer and contract. EPI has a policy of continuous product development and improvement, and we therefore reserve the right to vary any information without prior notice.

EPI UPS (Asia-Pacific) Pte Ltd101 Thomson Road, United Square, #06-01/06, Singapore 307591

Website: www.epi-ups.com Tel. +65-6809 3073 Fax: +65-6491 5230

EPI UPS (Italy) SRLVia Decio Raggi, 411 Forli 447121, Italy

MODELMTN-Dual1101S MTN-Dual1102S MTN-Dual1103S MTN-Dual1106S MTN-Dual1110S

MTN-Dual1101L MTN-Dual1102L MTN-Dual1103L MTN-Dual1106L MTN-Dual1110L

Capacity 1kVA/.9kW 2kVA/1.8kW 3kVA/2.7kW 6kVA/6kW 10kVA/10kW

Input voltage range

110VAC-288VAC

100% load@>176VAC; 80% load@>154VAC100% load@>176VAC;

90% load@>160VAC

70% load@>132VAC; 50% load@>110VAC80% load@>140VAC;

60% load@>110VAC

Input frequency 40-70Hz

Input PF ≥0.97 ≥0.99

Voltage regulation ±1 %

Output frequency 50/60Hz

Output PF 0.9 1

Overload capability

(Inverter mode)

105%-130%: to bypass 1 min;

150%: to bypass after 30 sec

110%: for 10 min;

125%: for 1 min;

150%: for 30sec

Overload capability

(Battery mode)

105%-130%: shutdown after 10 sec;

150%: shutdown after 5 sec

110%: shutdown after 10 min;

130%: shutdown after 10 sec;

>130%: shutdown after 200 ms

Crest factor 3:1

Efficiency 87% 91% 90% 95%

Display LED+LCD

Battery voltage 36VDC 72VDC 96VDC 192VDC

Battery

type/number

12V,7Ah*3 12V,7Ah*6 12V,7Ah*8 12V,7Ah*16 12V,9Ah*16

External

Interface RS232, SNMP

Optional USB, SNMP, Dry contactsUSB, SNMP, ECO kit, Dry contacts,

Battery cabinet

Operation

temperature0-40℃

Relative humidity 0-95%(non-condensing)

W*D*H(mm)440*430*86 440*480*173 440*480*173 440*660*173

440*430*86 440*480*86 440*480*86 440*550*86

Weight(kg)11.5 25 31 59 67

7 8 9.5 17.5 20.5