    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 1of 14

    Page 1 of 14

    Inspected by: Juber Anwar Khan (Asst. Maint. Engineer)

    Sl.No Picture Remarks

    1.

    2 & 3

    Rusted tapchanger leaver in Tx1

    Breather not in good condition in Tx- 1 Cooling fan is missing in Tx -1

  • 8/13/2019 Mudhaibi Grid Station

    2/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 2of 14

    Page 2 of 14

    4 & 5

    6.

    Transformer Oil leak in Tx 1 Rusted cooling fan in Tx - 1

    Oil on the top of tapchanger oil filter system in Tx 1

  • 8/13/2019 Mudhaibi Grid Station

    3/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 3of 14

    Page 3 of 14

    7 & 8

    9 &10

    Fire fighting system paint removed in Tx

    1 Proper padlocks should be use in Tx - 1

    Transformer climbing lader is not locked in Tx - 1 Broken cable clids in Earthing TFR1

  • 8/13/2019 Mudhaibi Grid Station

    4/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 4of 14

    Page 4 of 14

    11&12

    13.

    Temporary sealing of cable box in Earthing TFR 1 Rusted pad locks in Earthing TFR 1

    Oil leak in Earthing TFR 1

  • 8/13/2019 Mudhaibi Grid Station

    5/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 5of 14

    Page 5 of 14

    14&15

    16.

    Control Cable dressing is not proper in EAT 1 Rusted Handle of NER 1

    Rusted body of NER 1

  • 8/13/2019 Mudhaibi Grid Station

    6/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 6of 14

    Page 6 of 14

    17.

    18&19

    Bird nest on Circuit Breaker

    Damage Tx1 Oil drainage pump switch Damage Gland Shrouds

  • 8/13/2019 Mudhaibi Grid Station

    7/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 7of 14

    Page 7 of 14

    20.

    21.

    Damage Cable Gland Shrouds

    Damage Cable Gland Shrouds

  • 8/13/2019 Mudhaibi Grid Station

    8/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 8of 14

    Page 8 of 14

    22&23

    24.

    Bird nest in the centre of busbar Damage earth pit

    Damage Cable Gland Shrouds Damage Cable Gland Shrouds

  • 8/13/2019 Mudhaibi Grid Station

    9/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 9of 14

    Page 9 of 14

    25.

    26.

    Damage Cable Gland Scroud

    Oil leak in CT ( PhaseB )

  • 8/13/2019 Mudhaibi Grid Station

    10/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 10of 14

    Page 10 of 14

    27.

    28&29

    Rusted transformer cooling fans in Tx - 2

    Damage gland scroud at MK box in Tx - 2 Old breathers in Tx - 2

  • 8/13/2019 Mudhaibi Grid Station

    11/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 11of 14

    Page 11 of 14

    30&31

    32&33

    Cable cleats missing in Tx2 Paint removed in EAT- 2

    Temporary seald Cable box in EAT2 Rusted body in NER2

  • 8/13/2019 Mudhaibi Grid Station

    12/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 12of 14

    Page 12 of 14

    34.

    35&36

    Missing foundation in fire

    Broken Earth pit Broken wall foundation

  • 8/13/2019 Mudhaibi Grid Station

    13/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 13of 14

    Page 13 of 14

    37.

    Faded Phase plates Faded Phase plate

  • 8/13/2019 Mudhaibi Grid Station

    14/14

    Visual Inspection Report (RAY)Region: Sharqyia

    Location: Mudhaibi Grid station

    Ref. OETC/2013

    March 2013

    Page 14of 14