national fire protection association report page … · fixed industrial stairs in accordance with...

63
Second Revision No. 179-NFPA 5000-2013 [ Section No. 29.2.2.10.2 ] 29.2.2.10.2 Fixed industrial stairs in accordance with the minimum requirements for fixed stairs and stair railing systems in ANSI/ASSE A1264.1, Safety Requirements for Workplace Walking/Working Surfaces and Their Access; Workplace, Floor, Wall and Wall Roof Openings, ; Stairs and Railing Guardrail Systems, shall be permitted where fire escape ladders are permitted in accordance with 11.2.9.1. Submitter Information Verification Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Tue Jul 02 16:03:39 EDT 2013 Committee Statement Committee Statement: Proposed text clarifies the intent of the referenced publication, ANSI A1264.1 Note to CC: Update reference title in Chapter 2 Response Message: Page 221 of 346 National Fire Protection Association Report 9/5/2013 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment... BLD-IND SECOND REVISIONS WITH STATEMENTS Page 1 of 63

Upload: nguyenbao

Post on 29-Aug-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

Second Revision No. 179-NFPA 5000-2013 [ Section No. 29.2.2.10.2 ]

29.2.2.10.2Fixed industrial stairs in accordance with the minimum requirements for fixed stairs and stair railing systems in ANSI/ASSE A1264.1, Safety Requirements for Workplace Walking/Working Surfaces and Their Access; Workplace, Floor, Walland Wall Roof Openings, ; Stairs and Railing Guardrail Systems, shall be permitted where fire escape ladders are permitted in accordance with 11.2.9.1.

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 16:03:39 EDT 2013

Committee Statement

CommitteeStatement:

Proposed text clarifies the intent of the referenced publication, ANSI A1264.1 Note to CC: Update reference title in Chapter 2

ResponseMessage:

Page 221 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 1 of 63

Second Revision No. 129-NFPA 5000-2013 [ Sections 29.2.6.1,

29.2.6.2 ]

29.2.6.1Travel distance, measured in accordance with Section 11.6, shall not exceed thatprovided by Table 29.2.6 except as otherwise permitted by 29.2.6.2 .29.2.6.2* Power-Generation Buildings.Buildings of Type I or Type II construction used exclusively for the enclosure of steam generators, steam turbines, gas turbines, heat recovery generators, and flue gas treatment equipment , with shall be permitted to have a maximum travel distance of 400 ft (122 m) where all special hazards are protected by approvedautomatic suppression systems in accordance with one or more of the following standards, as applicable:

(1) NFPA 11 , Standard for Low-, Medium-, and High-Expansion Foam

(2) NFPA 12 , Standard on Carbon Dioxide Extinguishing Systems

(3) NFPA 13 , Standard for the Installation of Sprinkler Systems

(4) NFPA 15 , Standard for Water Spray Fixed Systems for Fire Protection

(5) NFPA 16 , Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems

(6) NFPA 17 , Standard for Dry Chemical Extinguishing Systems

(7) NFPA 750 , Standard on Water Mist Fire Protection Systems

(8) NFPA 2001 , Standard on Clean Agent Fire Extinguishing Systems

NFPA 11 , Standard for Low-, Medium-, and High-Expansion Foam ; NFPA 12 , Standard on Carbon Dioxide Extinguishing Systems ; NFPA 13 , Standard for theInstallation of Sprinkler Systems , NFPA 15 , Standard for Water Spray Fixed Systems for Fire Protection ; NFPA 16 , Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems ; NFPA 17 , Standard for Dry Chemical Extinguishing Systems ; NFPA 750 , Standard on Water Mist Fire Protection Systems ; or NFPA 2001 , Standard on Clean Agent Fire ExtinguishingSystems , shall be permitted to have a maximum travel distance of 400 ft (122 m).

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:33:09 EDT 2013

Committee Statement

Page 222 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 2 of 63

CommitteeStatement:

Clarifies the application of 29.2.6. Change correlates with change made to NFPA 101.

Response Message:

Page 223 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 3 of 63

Second Revision No. 136-NFPA 5000-2013 [ Section No. 29.2.7 ]

29.2.7 Discharge from Exits.Discharge from exits shall be in accordance with Section 11.7 .29.2.7.1Discharge from exits shall be in accordance with Section 11.7 .29.2.7.2Occupant travel to the public way shall be permitted to be delayed within the exit discharge in accordance with 11.7.7.

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 16:19:59 EDT 2013

Committee Statement

Committee Statement: Section 11.7.7 has been deleted from the Code.

Response Message:

Page 224 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 4 of 63

Second Revision No. 130-NFPA 5000-2013 [ Section No. 29.3.2.2 ]

29.3.2.2Alcohol-based hand-rub dispensers in accordance with 8.15.4 shall bepermitted.

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 14:53:48 EDT 2013

Committee Statement

CommitteeStatement:

Text is being relocated to Section 30.4.3 for consistence with other occupancy chapter committee actions and to avoid conflict with 11.5.1.7.

ResponseMessage:

Page 225 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 5 of 63

Second Revision No. 131-NFPA 5000-2013 [ New Section after

29.4.2.2 ]

29.4.3 Alcohol-Based Hand-Rub Dispensers.Alcohol-based hand-rub dispensers in accordance with 8.15.4 shall be permitted.

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 14:58:15 EDT 2013

Committee Statement

Committee Statement: Text is relocated from 29.3.2.2.

Response Message:

Page 226 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 6 of 63

Second Revision No. 137-NFPA 5000-2013 [ Section No. 30.2.7 ]

30.2.7 Discharge from Exits.Discharge from exits shall be in accordance with Section 11.7 .30.2.7.1Discharge from exits shall be in accordance with Section 11.7 .30.2.7.2Occupant travel to the public way shall be permitted to be delayed within the exit discharge in accordance with 11.7.7.

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 16:20:47 EDT 2013

Committee Statement

Committee Statement: Section 11.7.7 has been deleted from the Code.

Response Message:

Page 227 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 7 of 63

Second Revision No. 132-NFPA 5000-2013 [ Section No. 30.3.2.1 ]

30.3.2.1Alcohol-based hand-rub dispensers in accordance with 8.15.4 shall bepermitted.

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 15:07:04 EDT 2013

Committee Statement

CommitteeStatement:

Text is being relocated to 30.4.3 for consistency with other occupancy committee actions and to avoid potential conflict with 11.5.1.7.

ResponseMessage:

Page 228 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 8 of 63

Second Revision No. 133-NFPA 5000-2013 [ New Section after

30.4.2 ]

30.4.3 Alcohol-Based Hand-Rub Dispensers. Alcohol-based hand-rub dispensers in accordance with 8.15.4 shall be permitted.

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 15:07:54 EDT 2013

Committee Statement

Committee Statement: Text is relocated from 30.3.2.1.

Response Message:

Page 229 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 9 of 63

Second Revision No. 134-NFPA 5000-2013 [ Section No. 30.8.1.6 ]

30.8.1.6 Minimum Construction Requirements.30.8.1.6.1Those parts of parking structures located within, immediately below, attached to, or less than 3000 mm (120 in.) from a building used for any other purpose shall be separated by walls, partitions, floors, or floor–ceiling assemblies having fire resistance ratings of not less than 2 hours, unless otherwise permitted by 4.1.3 5.2.2 of NFPA 88A, Standard for Parking Structures. [88A:4.1.2 5.2.1 ]Exception: No fire-rated separation shall be required when parts of a parking structure and a building used for any other purpose are separated by 3000 mm (120 in.) or more, and are attached only via open pedestrian balconies or bridges or open vehicle bridges. [ 88A: 4.1.3]30.8.1.6.2No fire-rated separation shall be required when parts of a parking structure and a building used for any other purpose are separated by 3000 mm (120 in.) or more, and are attached only via open pedestrian balconies or bridges or open vehicle bridges. [ 88A: 5.2.2] 30.8.1.6.3Those portions of an open parking structure located within or immediately below a building used for another purpose shall have the principal supporting members and bearing walls in all levels of the parking structure protected to provide a fire-resistive rating equivalent to that required for the other occupancy. [88A:4.1.4 5.2.3 ]30.8.1.6.4 Internal Subdivision.Offices or other similar spaces that are related to the operation of the parking structure and are less than 300 m2 (3000 ft2) in area, other than cashier or attendant booths, shall be separated from parking areas by walls or partitions that resist the passage of smoke. [88A:4.2 5.2.4 ]30.8.1.6.5Floor surfaces shall be of noncombustible material. [88A:5.3.1] Where combustible construction is permitted, floor surfaces shall be noncombustible and liquid tight. [ 88A: 4.3.1, 4.3.1.1]

Asphalt shall be permitted on the finished ground level. [ 88A: 4.3.1.2]

30.8.1.6.5.1Where combustible construction is permitted, floor surfaces shall be noncombustible and liquid tight. [ 88A: 5.3.1 .1 ]30.8.1.6.5.2Asphalt shall be permitted on grade. [ 88A: 5.3.1.2]30.8.1.6.6The maximum building height, number of stories, and area limitations for enclosed parking structures shall be in accordance with Chapter 7.30.8.1.6.7Open parking structures shall be of Type I or Type II construction as defined inNFPA 220, Standard on Types of Building Construction. [88A:4.7.2 5.1.2 ]30.8.1.6.8Heights and floor areas of open parking structures of Type I, Type II (222), or Type II (111) construction shall be permitted to be unlimited. [88A:5.1.3]30.8.1.6.9

Page 230 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 10 of 63

Open parking structures of Type II (000) construction shall be permitted to be ofunlimited area where both of the following conditions are met:

(1) The height does not exceed 25 m (75 ft).

(2) The horizontal distance from any point on any parking level to an exterior wall opening on a street, an alley, a courtyard, or other similar permanent open space does not exceed 60 m (200 ft). [88A:5.1.4]

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 15:26:27 EDT 2013

Committee Statement

Committee Statement: Proposed change updates extracted text from NFPA 88A.

Response Message:

Page 231 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 11 of 63

Second Revision No. 135-NFPA 5000-2013 [ Section No. 30.8.4 ]

30.8.4 Special Provisions — High-Rise Buildings.(See Section 11.8 .)

The provisions of Chapter 33 shall not apply to high-rise, open parkingstructures except as otherwise required in 30.8.4.2 .

30.8.4.2The provisions of 33.3.2 shall apply to high-rise, open parking structures.

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 16:12:33 EDT 2013

Committee Statement

CommitteeStatement:

As written, the complete package of high rise provisions in Chapter 33 are applicable to both enclosed and open parking structures. The proposed change in this revision exempts new high rise open parking structures from the provisions of Chapter 33 except for sprinkler systems and standpipe systems. The additional requirements of Chapter 33 are not applicable to a new high rise open parking structure based upon the associated risks and hazards present in that type of structure.

ResponseMessage:

Page 232 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 12 of 63

Second Revision No. 138-NFPA 5000-2013 [ Section No. 34.1.3.1 ]

34.1.3.1* General.Maximum allowable quantities (MAQ) of hazardous materials per control area shall be as specified in Table 34.1.3.1 , except as modified by , , or .Table 34.1.3.1 Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Areaa

Page 238 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 13 of 63

Storage Use-Closed Systems

Material Class

High Hazard

Protection Level

Solid Pounds

Liquid Gallons

(lb)

Gas b

ft 3

(lb) [gal]

Solid Pounds

Liquid Gallons

(lb)

Gas b

ft 3

(lb) [gal]

Combustibleliquid c, d, e,

fII 2 or 3 NA 120 g, h NA NA 120 h NA

III-A 2 or 3 NA 330 g, h NA NA 330 h NA

III-B NA NA 13,200 g,

i NA NA 13,200 i NA

Consumerfireworks

1.4G 3 125 g, h,

k NA NA NA NA NA

Cryogenicfluid flammable 2 NA 45 h t, u NA NA 45 h t, u NA

oxidizing 3 NA 45 g, h NA NA 45 g, h NA

inert NA NA NL NA NA NL NA

Explosives NA 1 1 g, l, m, n (1) g, l, n NA 1 ⁄4 l ( 1 ⁄4 ) l NA

Flammable,gas Gaseous 2 NA NA

1000 g,

h NA NA1000 g,

h

Liquefied 2 NA NA(150)

g,h NA NA(150)

g,h

LiquefiedPetroleum

(LP)2 NA NA

NA(300)

o,pNA NA (300)

Flammableliquid c, d, f,

qI-A 2 or 3 NA 30 g, h NA NA 30 h NA

I-B and IC NA 120 g, h NA NA 120 g, h NA

CombinationI-A, I-B, I-C NA 120 g, h, r NA NA 120 g, h, r NA

Flammablesolid NA 3 125 g, h NA NA 25 h NA NA

Inert gas Gaseous NA NA NA NL NA NA NL

Liquefied NA NA NA NL NA NA NL

Organicperoxide

UD 1 1 g, l (1) g, l NA 1 ⁄4 l ( 1 ⁄4 ) l NA

I 1 5 g, h (5) g, h NA 1 h (1) h NA

II 2 50 g, h (50) g, h NA 50 h (50) h NA

III 3 125 g, h (125) g, h NA 125 h (125) h NA

IV NA NL NL NA NL NL NA

V NA NL NL NA NL NL NA

Oxidizer 4 1 1 g, l (1) g, l NA 1 ⁄4 l ( 1 ⁄4 ) l NA

Page 239 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 14 of 63

Storage Use-Closed Systems

Material Class

High Hazard

Protection Level

Solid Pounds

Liquid Gallons

(lb)

Gas b

ft 3

(lb) [gal]

Solid Pounds

Liquid Gallons

(lb)

Gas b

ft 3

(lb) [gal]

3 j 2 or 3 10 g, h (10) g, h NA 2 h (2) h NA

2 3 250 g, h (250) g, h NA 250 h (250) h NA

1 NA 4,000 g, i (4,000) g,

i NA 4,000 g (4,000) g NA

Oxidizinggas Gaseous 3 NA NA

1,500 g,

h NA NA1,500 g,

h

Liquefied 3 NA(150) g,

h NA(150) g,

h

Pyrophoric 2 4 g, l (4) g, l NA 1 l (1) l NA

PyrophoricGas

Gaseous 2 NA NA 50 g, l NA NA 50 g, l

Liquefied 2 NA NA (4) g, l NA NA (4) g, l

Unstable(reactive)

4 1 1 g, l (1) g, l NA 1 ⁄4 l ( 1 ⁄4 ) l NA

3 1 or 2 5 g, h (5) g, h NA 1 h (1) h NA

2 2 50 g, h (50) g, h NA 50 h (50) h NA

1 NA NL NL NA NL NL NA

Unstable(reactive) Gas

Gaseous 4or 3

detonable1 NA NA 10 g,l NA NA 10 g,l

3 non-detonable

2 NA NA 50 g,h NA NA 50 g,h

2 3 NA NA 750 g,

h NA NA 750 g,

h

1 NA NA NA NL NA NA NL

Unstable(reactive) Gas

Liquefied 4or 3

detonable1 NA NA (1) g,l NA NA (1) g,l

3 non-detonable 2 NA NA (2) g, h NA NA (2) g, h

2 3 NA NA[30] g,

h NA NA[30] g,

h

1 NA NA NA NL NA NA NL

Water(reactive)

3 2 5 g, h (5) g, h NA 5 h (5) h NA

2 3 50 g, h (50) g, h NA 50 h (50) h NA

1 NA NL NL NA NL NL NA

Corrosive NA 4 5,000 g,

h 500 g, h NA 5,000 h 500 NA

Page 240 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 15 of 63

Storage Use-Closed Systems

Material Class

High Hazard

Protection Level

Solid Pounds

Liquid Gallons

(lb)

Gas b

ft 3

(lb) [gal]

Solid Pounds

Liquid Gallons

(lb)

Gas b

ft 3

(lb) [gal]

Corrosivegas Gaseous 4 NA NA

810 g,

h NA NA810 g,

h

Liquefied NA NA(150) g,

h NA NA(150) g,

h

Highly toxic NA 4 10 g, h (10) g, h NA 10 h (10) h NA

Highly toxicgas Gaseous 4 NA NA 20 h, s NA NA 20 h, s

Liquefied NA NA (4) h, s NA NA (4) h, s

Toxic NA 4 500 g, h (500) g, h NA 500 h (500) h NA

Toxic gas Gaseous 4 NA NA 810 g,

h NA NA 810 g,

h

Liquefied NA NA (150) g,

h NA NA (150) g,

h

a See 34.1.3.2 for exceptions to tabular amounts. For use of control areas, see 34.2.4 . Table values in parentheses correspond to the unit name in parentheses at the top of the column. The aggregate quantity in use and storage is not permitted to exceed the quantity listed for storage. In addition, quantities in specific occupancies are not permitted to exceed the limits in 34.1.3.2 .

b Measured at 70 °F (21°C) and 14.7 psi (30 kPa).

c Inside a building, the maximum capacity of a combustible liquid storage system that is connected to a fuel-oil piping system is permitted to be 660 gal (2,500L), provided that such system conforms to NFPA 31 , Standard for the Installation of Oil-Burning Equipment .

d Flammable and combustible liquids and flammable gases in the fuel tanks of mobile equipment or vehicles are permitted to exceed the MAQ where the equipment is stored and operated in accordance with the NFPA 1 .

e In storage, low, and ordinary hazard occupancies, the storage of Class II combustible liquids is required to be limited to a maximum quantity of 1,375 gal (5204L); Class IIIA combustible liquids are required to be limited to a maximum quantity of 13,750 gal (52,044 L) where stored in accordance with all the requirements in NFPA 30 for general-purpose warehouses.

f The quantity of fuel in aircraft in hangars is required to be in accordance with NFPA 409 , Standard on Aircraft Hangars .

g Quantities are permitted to be increased 100 percent where stored or used in approved cabinets, gas cabinets, exhausted enclosures, gas rooms, explosives magazines, or safety cans, as appropriate for the material stored, in accordance with NFPA 1 . Where Footnote h also applies, the increase for both footnotes is permitted to be applied accumulatively.

Page 241 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 16 of 63

h Maximum quantities are permitted to be increased 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with NFPA 13 , Standard for the Installation of Sprinkler Systems . Where Footnote g also applies, the increase for both footnotes is permitted to be applied accumulatively.

i The permitted quantities are not limited in a building equipped throughout with an automatic sprinkler system in accordance with NFPA 13 .

j A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizers is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

k Unless the actual weight of the pyrotechnic composition of the consumer fireworks, 1.4G, is known, 25 percent of the gross weight of the fireworks, including packaging, is permitted to be used to determine the weight of the fireworks for the purpose of this table.

l Permitted only in buildings equipped throughout with an automatic sprinkler system in accordance with NFPA 13 .

m Maximum quantities of black powder, smokeless propellant, and small arms primers stored or displayed in mercantile occupancies or stored in one- or two-family dwellings are permitted to exceed the amount specified by this table where such storage complies with the requirements of NFPA 495 , Explosive Materials Code , Chapter 13.

n In lieu of the maximum allowable quantity limit per control area, the maximum aggregate quantity per building of special explosive devices in industrial, mercantile, and storage occupancies shall be limited to 50 lb.

o Additional storage locations are required to be separated by a minimum of 300 ft (92 m).

p In mercantile occupancies, storage of LP-Gas is limited to a maximum of 200 lb (91 kg) in nominal 1 lb (0.45 kg) LP-Gas Containers.

q In storage, low, and ordinary hazard occupancies, the storage of Class IA flammable liquids is not permitted, and the combination storage of Class IB and Class IC flammable liquids is required to be limited to a maximum quantity of 660 gal (2,500 L) where stored in accordance with all the requirements in NFPA 30 for general-purpose warehouses.

r Containing not more than the maximum allowable quantity per control area of Class I-A, Class I-B, or Class I-C flammable liquids.

s Allowed only where stored or used in gas rooms or in approved, gas cabinets or enclosures, as specified in NFPA 1 .

t None allowed in unsprinklered buildings unless stored or used in gas rooms or in approved gas cabinets or exhausted enclosures, as specified in NFPA 1 .

u With pressure-relief devices for stationary or portable containers vented directly outdoors or to an exhaust hood.

Maximum allowable quantities (MAQ) of hazardous materials per control area shall be as specified in Table 34.1.3.1 , except as modified by 34.1.3.2 , 34.1.3.3 , or 34.1.3.4 .

Table 34.1.3.1 Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Area a

Page 242 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 17 of 63

Material Class

High Hazard

ProtectionLevel

Storage Use — Closed Systems

Solid Pounds

Liquid Gallons

(lb)Gas b

scf (lb)Solid

Pounds

Liquid Gallons

(lb)Gas b

scf (lb)

Physical Hazard Materials

Combustibleliquid See note See note See note See note

See note See note See note

See note

Consumerfireworks See note See note See note See note

See note See note See note

See note

Combustiblemetals See note See note See note See note

See note See note See note

See note

Cryogenic fluid Flammable 2 N/A 45 j,k N/A N/A 45 j,k N/A

[55: Table6.3.1] Oxidizing 3 N/A 45 c,d N/A N/A 45 c,d N/A

Inert N/A N/A NL N/A N/A NL N/A

Explosives See note See note See note See noteSee note See note See note

See note

Flammable gas l Gaseous 2 N/A N/A 1000 c,d N/A N/A 1000 c,d

[55: Table 6.3.1] Liquefied 2 N/A N/A

(150)c,d N/A N/A

(150)c,d

LiquefiedPetroleum

(LP) See note See note See noteSeenote See note See note

Seenote

Flammable liquid IA See note See note See note

See note See note See note

Seenote

IB and IC See note See note See noteSee note See note See note

Seenote

Combination(IA, IB, IC) See note See note See note

Seenote See note See note

Seenote

Flammable solid N/A 3 125 c,d N/A N/A 125 c, d N/A N/A

Inert Gas Gaseous N/A N/A N/A NL N/A N/A NL

Liquefied N/A N/A N/A NL N/A N/A NL

Organicperoxide UD 1 1 c,i (1) c,i N/A 1/4 i (1/4) i N/A

I 1 5 c,d (5) c,d N/A 1 c,d (1) c,d N/A

II 2 50 c,d (50) c,d N/A 50 d (50) d N/A

III 3 125 c,d (125) c,d N/A 125 d (125) d N/A

IV N/A NL NL N/A NL NL N/A

V N/A NL NL N/A NL NL N/A

Oxidizer 4 1 1 c,i (1) c,i N/A 1/4 i (1/4) i N/A

3f 2 or 3 10 c,d (10) c,d N/A 2 d (2) d N/A

2 3 250c,d (250)c,d N/A 250d (250)d N/A

Page 243 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 18 of 63

Material Class

High Hazard

ProtectionLevel

Storage Use — Closed Systems

Solid Pounds

Liquid Gallons

(lb)Gas b

scf (lb)Solid

Pounds

Liquid Gallons

(lb)Gas b

scf (lb)

Physical Hazard Materials

1 N/A 4000c,e(4000)

c,e N/A 4000e (4000)e N/A

Oxidizinggas [55: Table 6.3.1] Gaseous 3 N/A N/A 1500 c,d N/A N/A 1500 c,d

Liquefied 3 N/A N/A(150)

c,d N/A N/A(150)

c,d

Pyrophoric N/A 2 4 c,i (4) c,i N/A 1 i (1) i N/A

PyrophoricGas [55: Table 6.3.1] Gaseous 2 N/A N/A 50 c,i N/A N/A 50 c,i

Liquefied 2 N/A N/A (4) c,i N/A N/A (4) c,i

Unstable(reactive) Gas [55: Table 6.3.1] 4 1 1 c,i (1) c,i N/A 1/4 i (1/4) i N/A

3 1 or 2 5 c,d (5) c,d N/A 1 d (1) d N/A

2 2 50 c,d (50) c,d N/A 50 d (50) d N/A

1 N/A NL NL N/A NL NL NL

Unstable(reactive) Gas

Liquefied 4 or 3

detonable 1 N/A N/A (1) c,i N/A N/A (1) c,i

3 non-detonable 2 N/A N/A (2) c,d N/A N/A (2) c,d

2 3 N/A N/A(150)

c,d N/A N/A(150)

c,d

1 N/A N/A N/A NL N/A N/A NL

Water-reactive 3 2 5 c,d (5) c,d N/A 5 d (5) d N/A

2 3 50 c,d (50) c,d N/A 50 d (50) d N/A

1 N/A NL NL N/A NL NL N/A

Health Hazard Materials

Corrosive N/A 4 5000 c,d 500 c,d N/A 5000 d 500d N/A

CorrosiveGas [55: Table 6.3.1] Gaseous 4 N/A N/A 810 c,d,g N/A N/A 810 c,d,g

Liquefied 4 N/A N/A(150)

c,d N/A N/A(150)

c,d

Highly toxic N/A 4 10 c,d (10) c,d N/A (10) d (10) d N/A

Highly toxicgas [55: Table 6.3.1] Gaseous 4 N/A N/A 20 d,g N/A N/A 20 d,g

Page 244 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 19 of 63

Material Class

High Hazard

ProtectionLevel

Storage Use — Closed Systems

Solid Pounds

Liquid Gallons

(lb)Gas b

scf (lb)Solid

Pounds

Liquid Gallons

(lb)Gas b

scf (lb)

Physical Hazard Materials

Liquefied 4 N/A N/A (5) d,g N/A N/A (5) d,g

Toxic N/A 4 500 c,d (500) c,d N/A 500 d (500) d N/A

Toxic gas Gaseous 4 N/A N/A 810 c,d N/A N/A 810 c,d

Liquefied 4 N/A N/A(150)

c,d N/A N/A(150)

c,d

UD: Unclassified detonable For SI units, 1 lb = 0.454 kg; 1 gal = 3.785 L; 1 scf =0.0283 Nm 3 .

N/A: Not applicable. NL: Not limited. NP: Not permitted.

Note: The hazardous material categories and MAQs that are shaded in this table are not regulated by NFPA 400 but are provided here for informational purposes. See Chapter 2 of NFPA 400 for the reference code or standard governing these materials and establishing the MAQs. In accordance with 1.1.1.2 of NFPA 400, materials having multiple hazards that fall within the scope of NFPA 400 shall comply with NFPA 400.

a Table values in parentheses correspond to the unit name in parentheses at the top of the column. The aggregate quantity in use and storage is not permitted to exceed the quantity listed for storage.

b Measured at NTP or 70°F (21°C) and 14.7 psia (101.3 kPa).

c Quantities are permitted to be increased 100 percent where stored or used in approved cabinets, gas cabinets, exhausted enclosures, gas rooms explosives magazines, or safety cans, as appropriate for the material stored, in accordance with NFPA 400. Where footnote d also applies, the increase for both footnote c and footnote d is permitted to be applied accumulatively.

d Maximum quantities are permitted to be increased 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems . Where footnote c also applies, the increase for both footnote c and footnote d is permitted to be appliedaccumulatively.

e The permitted quantities are not limited in a building equipped throughout with an automatic sprinkler system in accordance with NFPA 13.

f A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

g Allowed only where stored or used in gas rooms or approved cabinets, exhausted gas cabinets or exhausted enclosures, as specified in NFPA 400.

h Conversion. Where quantities are indicated in pounds and when the weight per gallon of the liquid is not provided to the AHJ, a conversion factor of 10 lb/gal (1.2 kg/L) shall be used.

i Permitted only in buildings equipped throughout with an automatic sprinkler system in accordance with NFPA 13.

Page 245 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 20 of 63

j None allowed in unsprinklered buildings unless stored or used in gas rooms or in approved gas cabinets or exhausted enclosures, as specified in NFPA 400.

k With pressure-relief devices for stationary or portable containers vented directly outdoors or to an exhaust hood. [ 55: Table 6.3.1.1]

l Flammable gases in the fuel tanks of mobile equipment or vehicles are permitted to exceed the MAQ where the equipment is stored and operated in accordance with the fire code.

[ 400: Table 5.2.1.1.3]

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 16:21:45 EDT 2013

Committee Statement

CommitteeStatement:

NFPA 400 is the expert document on maximum allowable quantities and the requirements for hazardous materials. Now that NFPA 400 is an established document, NFPA 5000 is able to extract applicable provisions regarding hazardous materials. All MAQ tables should be extracted from NFPA 400 for this edition of NFPA 5000 and those going forward.

ResponseMessage:

Page 246 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 21 of 63

Second Revision No. 139-NFPA 5000-2013 [ Section No. 34.1.3.2 ]

34.1.3.2 Special Occupancy Limits.The MAQ of hazardous materials per control area in assembly, ambulatory health care, business, educational, day-care, health care, detention and correctional, and residential occupancies consisting of lodging or rooming houses, hotels, dormitories, apartments, and residential board and care facilities shall be as specified in Table 34.1.3.2(a) through Table 34.1.3.2(g).Table 34.1.3.2(a) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Area in Assembly Occupancies

Page 247 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 22 of 63

Material Class Solid LiquidGas a (atNTP)

Flammable and combustibleliquid b,c I and II combined NP 10 gal NP

IIIA NP 60 gal NP

IIIB NP 120 gal NP

Cryogenic liquid Flammable NP 10 gal NP

Oxidizing NP 10 gal NP

Explosives d,e,f,g NP NP NP NP

Flammable gas c,h Gaseous NP NP NP

Liquefied NP 20 lb NP

Liquefied petroleum NP 20 lb NP

Consumer fireworks 1.4G NP NP NP

Flammable solid NP 5 lb NP NP

Oxidizers 4 NP NP NP

3 10 lb i 1 gal i NP

2 250 lb 25 gal NP

1 4000lb

400 gal NP

Oxidizing gas h Gaseous NP NP NP

Liquefied NP 15 gal NP

Organic peroxides Unclassifieddetonatable

NP NP NP

I NP NP NP

II NP NP NP

III 1 lb 1 lb NP

IV 10 lb 10 lb NP

V NL NL NP

Pyrophoric materials NP 1 lb 1 lb NP

Unstable reactives 4 1 ⁄4 lb 1 ⁄4 lb NP

3 1 lb 1 lb NP

2 10 lb 10 lb NP h

1 NL NL NP

Water-reactive 3 1 lb 1 lb NP

2 10 lb 10 lb NP

1 NL NL NP

Corrosives NP1000lb 100 gal NP

Highly toxic NP 3 lb 3 lb NP j

Toxic NP 125 lb 125 lb NP j

For SI units, 1 gal = 3.785 L; 1 lb = 0.454 kg.

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (30 kPa)]. NP: Not permitted. NL: Not limited.

Page 248 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 23 of 63

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with the fire code.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495 .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopoeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g The storage and use of small arms ammunition, and components thereof, are permitted where in accordance with NFPA 495 .

h Fuel or oxidizing gas used for maintenance, repair, and operation of equipment is not permitted to exceed 250 ft 3 (7.1 m 3 ).

i A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

j Gas cylinders not exceeding 20 ft 3 (0.57 m 3 ) at NTP are permitted in gas cabinets or fume hoods.

Table 34.1.3.2(a) Maximum Allowable Quantities (MAQ) of Hazardous Materials per Control Area in Assembly Occupancies

Page 249 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 24 of 63

Material ClassSolid

Pounds

Liquid Gallons k

(lb)

Gas a (at NTP) scf

(lb)

Flammable andcombustible liquid b,c See note See note See note See note

Cryogenic fluid Flammable N/A 10 N/A

Oxidizing N/A 10 N/A

Explosives d,e,f,g See note See note See note See note

Flammable gas c,h Gaseous N/A N/A NP

Liquefied N/A N/A (20)

Liquefied Petroleum N/A N/A (20)

Consumer fireworks See note See note See note See note

Flammable solid N/A 5 N/A N/A

Oxidizers 4 NP NP N/A

3 10 i 1 gal i N/A

2 250 25 N/A

1 4,000 400 N/A

Oxidizing gash Gaseous N/A N/A NP h

Liquefied N/A N/A NP h

Organic peroxides I NP NP N/A

II NP NP N/A

III 25 (25) N/A

IV NL NL N/A

V NL NL N/A

Pyrophoric materials N/A 1 (1) NP

Unstable reactives 4 ¼ ¼ NP

3 1 1 NP

2 10 10 NP h

1 NL NL NP

Water-reactive 3 1 (1) N/A

2 10 (10) N/A

1 NL NL N/A

Corrosives N/A 1,000 100 NP

Highly toxic N/A 3 (3) NP j

Toxic N/A 125 (125) NP j

For SI units, 1 lb = 0.454 kg; 1 gal = 3.785 L.

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (101 kPa)]. N/A: Not applicable. NP: Not permitted. NL: Not limited.

Page 250 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 25 of 63

Note: The hazardous material categories and MAQs that are shaded in this table are not regulated by NFPA 400 but are provided here for informational purposes. See Chapter 2 of NFPA 400 for the reference code or standard governing these materials and establishing the MAQs. In accordance with 1.1.1.2 of NFPA 400, materials having multiple hazards that fall within the scope of NFPA 400 shall comply with NFPA 400.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with NFPA 400.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495, Explosive Materials Code .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g The storage and use of small arms ammunition, and components thereof, are permitted where in accordance with NFPA 495, Explosive Materials Code .

h Containers, cylinders, or tanks not exceeding 250 scf3 (7.1 m3) content measured at 70°F (21°C) and 14.7 psi (101 kPa) and used for maintenance purposes, patient care, or operation of equipment shall be permitted.

i A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

j Gas cylinders not exceeding 20 scf 3 (0.57 m 3 ) measured at 70°F (21°C) and 14.7 psi (101 kPa) are permitted in gas cabinets or fume hoods.

k Conversion. Where quantities are indicated in pounds and when the weight per gallon of the liquid is not provided to the AHJ, a conversion factor of 10 lb/gal (1.2 kg/L) shall be used.kConversion.

[ 400: Table 5.2.1.2]

Table 34.1.3.2(c) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Area in Ambulatory Health Care Occupancies

Page 251 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 26 of 63

Material Class Solid Liquid Gas a (at NTP)

Flammable and combustible liquid b,c

I and II combined NP 10 gal NP

IIIA NP 60 gal NP

IIIB NP120

gal d NP

Cryogenic liquid Flammable NP 10 gal NP

Oxidizing NP 10 gal NP

Explosives e,f,g NP NP NP NP

Flammable gas c,h Gaseous NP NP NP

Liquefied NP 20 lb NP

Liquefiedpetroleum NP 20 lb NP

Consumer fireworks 1.4G NP NP NP

Flammable solid NP 5 lb NP NP

Oxidizers 4 NP NP NP

3 10 lb i 1 gal i NP

2 250 lb 25 gal NP

14000lb d

400gal d NP

Oxidizing gas Gaseous NP NPper NFPA 99 ,

Health Care FacilitiesCode

Liquefied NP 15 gal NP

Organic peroxides Unclassified detonatable

NP NP NA

I NP NP NA

II NP NP NA

III 1 lb 1 lb NP

IV 10 lb 10 lb NP

V NL NL NA

Pyrophoric materials NP NP NP NP

Unstable reactives 4 NP NP NP

3 NP NP NP

2 10 lb 10 lb NP h

1 NL NL NP

Water-reactive 3 1 lb 1 lb NA

2 10 lb 10 lb NA

1 NL NL NA

Corrosives NP 1000 lb 100 gal NP

Highly toxic NP 3 lb 3 lb NP j

Toxic NP 125 lb 125 lb NP j

For SI units, 1 gal = 3.785 L; 1 lb = 0.454 kg.

Page 252 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 27 of 63

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (30 kPa)]. NP: Not permitted. NA: Not applicable. NL: Not limited.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with the fire code.

d The permitted quantities are not limited in a building protected throughout by automatic sprinkler systems in accordance with NFPA 13 .

e The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495 .

f The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopoeia or the National Formulary are not required to be limited.

g The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

h Fuel or oxidizing gas used for maintenance, repair, and operation of equipment is not permitted to exceed 250 ft 3 (7.1 m 3 ).

i A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

j Gas cylinders not exceeding 20 ft 3 (0.57 m 3 ) at NTP are permitted in gas cabinets or fume hoods.

Table 34.1.3.2(b) Maximum Allowable Quantities (MAQ) of Hazardous Materials per Control Area in Educational Occupancies

Page 253 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 28 of 63

Material ClassSolid

Pounds

Liquid Gallons m

(lb)

Gas a (at NTP) scf

(lb)

Flammable andcombustible liquid b,c See note See note See note See note

Cryogenic fluid Flammable N/A 10 N/A

Oxidizing N/A 10 N/A

Explosives d,e,f,g See note See note See note See note

Flammable gas c,h Gaseous N/A N/A NP

Liquefied N/A N/A (20)

Liquefied Petroleum N/A N/A (20)

Consumer fireworks See note See note See note See note

Flammable solid N/A 5 N/A N/A

Oxidizers 4 NP NP N/A

3 10 i 1 i N/A

2 250 25 N/A

1 4,000 400 N/A

Oxidizing gas h Gaseous N/A N/A NP

Liquefied N/A N/A NP h

Organic peroxides I NP NP N/A

II NP NP N/A

III 25 (25) N/A

IV NL NL N/A

V NL NL N/A

Pyrophoric materials N/A 1 (1) NP

Unstable reactives 4 1 ⁄4 1 ⁄4 NP

3 1 1 NP

2 10 10 NPh

1 NL NL NP

Water-reactive 3 1 (1) N/A

2 10 (10) N/A

1 NL NL N/A

Corrosives N/A 1,000 100 NP

Highly toxic N/A 3 (3) NP j

Toxic N/A 125 (125) NP j

For SI units, 1 lb = 0.454 kg; 1 gal = 3.785 L; 1 ft 3 = 0.0283 m 3 .

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (101 kPa)]. N/A: Not applicable. NP: Not permitted. NL: Not limited.

Page 254 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 29 of 63

Note: The hazardous material categories and MAQs that are shaded in this table are not regulated by NFPA 400 but are provided here for informational purposes. See Chapter 2 of NFPA 400 for the reference code or standard governing these materials and establishing the MAQs. In accordance with 1.1.1.2 of NFPA 400, materials having multiple hazards that fall within the scope of NFPA 400 shall comply with NFPA 400.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with NFPA 400.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495, Explosive Materials Code .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g The storage and use of small arms ammunition, and components thereof, are permitted where in accordance with NFPA 495, Explosive Materials Code .

h Containers, cylinders, or tanks not exceeding 250 scf (7.1 m 3 ) content measured at 70°F (21°C) and 14.7 psi (101 kPa) and used for maintenance purposes, patient care, or operation of equipment shall be permitted.

i A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

j The permitted quantities are not limited in a building protected throughout by automatic sprinkler systems in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems .

k Storage in laboratories only; additional 20 lb (9 kg) units are permitted where minimum 20 ft (6.1 m) separation is provided.

l Gas cylinders not exceeding 20 scf (0.57 m 3 ) measured at 70°F (21°C) and 14.7 psi (101 kPa) are permitted in gas cabinets or fume hoods.

m Conversion. Where quantities are indicated in pounds and when the weight per gallon of the liquid is not provided to the AHJ, a conversion factor of 10 lb/gal (1.2 kg/L) shall be used.

[ 400: Table 5.2.1.3]

Table 34.1.3.2(e) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Area in Business Occupancies

Page 255 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 30 of 63

Material Class Solid LiquidGas a (at

NTP)

Flammable and combustible liquid b,c I and II combined NP 10 gal NP

IIIA NP 60 gal NP

IIIB NP 120 gal NP

Cryogenic liquid Flammable NP 10 gal NP

Oxidizing NP 10 gal NP

Explosives d,e,f,g NP 1 ⁄4 lb 1 ⁄4 lb NP

Flammable gas c Gaseous NP NP 1000 ft 3

Liquefied NP 20 lb NP

Liquefied petroleum NP 20 lb NP

Consumer fireworks 1.4G NP NP NP

Flammable solid NP 5 lb NP NP

Oxidizers 4 NP NP NP

3 10 lb h 1 gal h NP

2 250 lb 25 gal NP

1 4000lb 400 gal NP

Oxidizing gas Gaseous NP NP 1500 ft 3

Liquefied NP 15 gal NP

Organic peroxides Unclassified detonatable NP NP NP

I NP NP NP

II NP NP NP

III 1 lb 1 lb NP

IV 10 lb 10 lb NP

V NL NL NP

Pyrophoric materials NP 1 lb 1 lb 10 ft 3

Unstable reactives 4 1 ⁄4 lb 1 ⁄4 lb 2 ft 3

3 1 lb 1 lb 10 ft 3

2 10 lb 10 lb 750 ft 3

1 NL NL NL

Water-reactive 3 1 lb 1 lb NP

2 10 lb 10 lb NP

1 NL NL NP

Corrosives NP 1000lb 100 gal 810 ft 3

Highly toxic i NP 3 lb 3 lb 20 ft 3

Toxic i NP 125 lb 125 lb 810 ft 3

For SI units, 1 gal = 3.785 L; 1 lb = 0.454 kg; 1 ft 3 = 0.0283 m 3 .

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (30 kPa)]. NP: Not permitted. NL: Not limited.

Page 256 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 31 of 63

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with the fire code.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495 .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopoeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g The storage and use of small arms ammunition, and components thereof, are permitted where in accordance with NFPA 495 .

h A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

i Gas cylinders not exceeding 20 ft 3 (0.57 m 3 ) at NTP are permitted in gas cabinets or fume hoods.

Table 34.1.3.2(c) Maximum Allowable Quantities (MAQ) of Hazardous Materials per Control Area in Day-Care Occupancies

Page 257 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 32 of 63

Material ClassSolid

Pounds

Liquid Gallons k

(lb)

Gas a (at NTP) scf

(lb)

Flammable andcombustible liquid b,c See note See note See note See note

Cryogenic fluid Flammable N/A 10 N/A

Oxidizing N/A 10 N/A

Explosives d,e,f,g See note See note See note See note

Flammable gas c,h Gaseous N/A N/A N/A

Liquefied N/A N/A 20

Liquefied Petroleum N/A N/A (20)

Consumer fireworks See note See note See note See note

Flammable solid N/A 5 lb N/A N/A

Oxidizers 4 NP NP N/A

3 10 i 1 i N/A

2 250 25 N/A

1 4,000 400 N/A

Oxidizing gas h Gaseous N/A N/A NP h

Liquefied N/A N/A NP h

Organic peroxides I NP NP N/A

II NP NP N/A

III 25 (25) N/A

IV NL NL N/A

V NL NL N/A

Pyrophoric materials N/A 1 (1) NP

Unstable reactives 4 1 ⁄4 lb ( 1 ⁄4 ) lb NP

3 1 (1) NP

2 10 (10) NPh

1 NL NL NP

Water-reactive 3 1 (1) N/A

2 10 (10) N/A

1 NL NL N/A

Corrosives N/A 1,000 100 NP

Highly toxic N/A 3 (3) NP j

Toxic N/A 125 (125) NP j

For SI units, 1 lb = 0.454 kg; 1 gal = 3.785 L.

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (101 kPa)]. N/A: Not applicable. NP: Not permitted. NL: Not limited.

Page 258 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 33 of 63

Note: The hazardous material categories and MAQs that are shaded in this table are not regulated by NFPA 400 but are provided here for informational purposes. See Chapter 2 of NFPA 400 for the reference code or standard governing these materials and establishing the MAQs. In accordance with 1.1.1.2 of NFPA 400, materials having multiple hazards that fall within the scope of NFPA 400 shall comply with NFPA 400.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with NFPA 400.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495, Explosive Materials Code .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g Containers, cylinders, or tanks not exceeding 250 scf (7.1 m3) content measured at 70°F (21°C) and 14.7 psi (101 kPa) and used for maintenance purposes, patient care, or operation of equipment shall be permitted.

h The permitted quantities are not limited in a building protected throughout by automatic sprinkler systems in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems .

i A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

j Gas cylinders not exceeding 20 scf (0.57 m3) measured at 70°F (21°C) and 14.7 psi (101 kPa) are permitted in gas cabinets or fume hoods.

k Conversion. Where quantities are indicated in pounds and when the weight per gallon of the liquid is not provided to the AHJ, a conversion factor of 10 lb/gal (1.2 kg/L) shall be used.

[ 400: Table 5.2.1.4]

Table 34.1.3.2(g) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Area in Educational Occupancies

Page 259 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 34 of 63

Material Class Solid LiquidGas a (at

NTP)

Flammable and combustible liquid b,c I and II combined NP 10 gal NP

IIIA NP 60 gal NP

IIIB NP120

gal d NP

Cryogenic liquid Flammable NP 10 gal NP

Oxidizing NP 10 gal NP

Explosives e,f,g,h NP NP NP NP

Flammable gas c,i Gaseous NP NP NP

Liquefied j NP 20 lb NP

Liquefiedpetroleum NP 20 lb NP

Consumer fireworks 1.4G NP NP NP

Flammable solid NP 5 lb NP NP

Oxidizers 4 NP NP NP

3 10 lb k 1 gal k NP

2 250 lb 25 gal NP

14000lb d

400gal d NP

Oxidizing gas i Gaseous NP NP NP

Liquefied NP 15 gal NP

Organic peroxides Unclassified detonatable NP NP NP

I NP NP NP

II NP NP NP

III 1 lb 1 lb NP

IV 10 lb 10 lb NP

V NL NL NP

Pyrophoric materials NP NP NP NP

Unstable reactives 4 NP NP 2 ft 3

3 NP NP NP

2 10 lb 10 lb NP i

1 NL NL NP

Water-reactive 3 1 lb 1 lb NA

2 10 lb 10 lb NA

1 NL NL NA

Corrosives NP 1000 lb 100 gal NP

Highly toxic NP 3 lb 3 lb NP l

Toxic NP 125 lb 125 lb NP l

For SI units, 1 gal = 3.785 L, 1 lb = 0.454 kg.

Page 260 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 35 of 63

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (30 kPa)]. NP: Not permitted. NL: Not limited. NA: Not applicable.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with the fire code.

d The permitted quantities are not limited in a building protected throughout by automatic sprinkler systems in accordance with NFPA 13 .

e The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495 .

f The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopoeia or the National Formulary are not required to be limited.

g The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

h The storage and use of small arms ammunition, and components thereof, are permitted where in accordance with NFPA 495 .

i Fuel or oxidizing gas used for maintenance, repair, and operation of equipment is not permitted to exceed 250 ft 3 (7.1 m 3 ).

j Storage in laboratories only; additional 20 lb units (9.1 kg) where minimum 20 ft (6.1 m) separation is provided.

k A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

l Gas cylinders not exceeding 20 ft 3 (0.57 m 3 ) at NTP are permitted in gas cabinets or fume hoods.

Table 34.1.3.2(d) Maximum Allowable Quantities (MAQ) of Hazardous Materials per Control Area in Health Care Occupancies

Page 261 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 36 of 63

Material ClassSolid

Pounds

Liquid Gallons k

(lb)

Gas a (at NTP) scf

(lb)

Flammable andcombustible liquid b,c See note See note See note

Cryogenic fluid Flammable N/A 10 N/A

Oxidizing N/A 10 N/A

Explosives d,e,f See note See note See note See note

Flammable gas c,g Gaseous N/A N/A NP

Liquefied N/A N/A (20)

Liquefied Petroleum N/A N/A (20)

Consumer fireworks See note See note See note See note

Flammable solid N/A 5 N/A N/A

Oxidizers 4 NP NP N/A

3 10 h 1 h N/A

2 250 25 N/A

1 4,000 i 400 i N/A

Oxidizing gas h Gaseous N/A N/A NP h

Liquefied N/A N/A NP h

Organic peroxides I NP NP N/A

II NP NP N/A

III 1,500 1,500 N/A

IV 100,000 100,000 N/A

V NL NL N/A

Pyrophoric materials N/A NP NP NP

Unstable reactives 4 NP NP NP

3 NP NP NP

2 10 10 NP g

1 NL NL NP

Water-reactive 3 1 1 N/A

2 10 10 N/A

1 NL NL N/A

Corrosives N/A 1,000 100 NP

Highly toxic N/A 3 3 NP j

Toxic N/A 125 125 NP j

For SI units, 1 lb = 0.454 kg; 1 gal = 3.785 L.

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (101 kPa)]. N/A: Not applicable. NP: Not permitted. NL: Not limited.

Page 262 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 37 of 63

Note: The hazardous material categories and MAQs that are shaded in this table are not regulated by NFPA 400 but are provided here for informational purposes. See Chapter 2 of NFPA 400 for the reference code or standard governing these materials and establishing the MAQs. In accordance with 1.1.1.2 of NFPA 400, materials having multiple hazards that fall within the scope of NFPA 400 shall comply with NFPA 400.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with NFPA 400.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495, Explosive Materials Code .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g Containers, cylinders, or tanks not exceeding 250 scf (7.1 m3) content measured at 70°F (21°C) and 14.7 psi (101 kPa) and used for maintenance purposes, patient care, or operation of equipment shall be permitted.

h A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

i The permitted quantities are not limited in a building protected throughout by automatic sprinkler systems in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems .

j Gas cylinders not exceeding 20 scf (0.57 m 3 ) measured at 70°F (21°C) and 14.7 psi (101 kPa) are permitted in gas cabinets or fume hoods.

k Conversion. Where quantities are indicated in pounds and when the weight per gallon of the liquid is not provided to the AHJ, a conversion factor of 10 lb/gal (1.2 kg/L) shall be used.

[ 400: Table 5.2.1.5]

Table 34.1.3.2(j) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Area in Day-Care Occupancies

Page 263 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 38 of 63

Material Class Solid LiquidGas a (at

NTP)

Flammable and combustibleliquid b,c I and II combined NP 10 gal NP

IIIA NP 60 gal NP

IIIB NP120

gal d NP

Cryogenic liquid Flammable NP 10 gal NP

Oxidizing NP 10 gal NP

Explosives e,f,g NP NP NP NP

Flammable gas c,h Gaseous NP NP NP

Liquefied NP 20 lb NP

Liquefiedpetroleum NP 20 lb NP

Consumer fireworks 1.4G NP NP NP

Flammable solid NP 5 lb NP NP

Oxidizers 4 NP NP NP

3 10 lb d 1 gal i NP

2 250 lb 25 gal NP

14000lb d

400gal d NP

Oxidizing gas h Gaseous NP NP NP

Liquefied NP 15 gal NP

Organic peroxides Unclassified detonatable

NP NP NP

I NP NP NP

II NP NP NP

III 1 lb 1 lb NP

IV 10 lb 10 lb NP

V NL NL NP

Pyrophoric materials NA NP NP NP

Unstable reactives 4 NP NP NP

3 NP NP NP

2 10 lb 10 lb NP h

1 NL NL NP

Water-reactive 3 1 lb 1 lb NA

2 10 lb 10 lb NA

1 NL NL NA

Corrosives NP 1000 lb 100 gal NP

Highly toxic NP 3 lb 3 lb NP j

Toxic NP 125 lb 125 lb NP j

For SI units, 1 gal = 3.785 L; 1 lb = 0.454 kg.

Page 264 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 39 of 63

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (30 kPa)]. NP: Not permitted. NL: Not limited. NA: Not applicable.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with the fire code.

d The permitted quantities are not limited in a building protected throughout by automatic sprinkler systems in accordance with NFPA 13 .

e The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495 .

f The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopoeia or the National Formulary are not required to be limited.

g The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

h Fuel or oxidizing gas used for maintenance, repair, and operation of equipment is not permitted to exceed 250 ft 3 (7.1 m 3 ).

i A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

j Gas cylinders not exceeding 20 ft 3 (0.57 m 3 ) at NTP are permitted in gas cabinets or fume hoods.

Table 34.1.3.2(e) Maximum Allowable Quantities (MAQ) of Hazardous Materials per Control Area in Ambulatory Health Care Occupancies

Page 265 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 40 of 63

Material ClassSolid

Pounds

Liquid Gallons k

(lb)

Gas a (at NTP) scf

(lb)

Flammable and combustible liquid b,c See note See note See note See note

Cryogenic fluid Flammable N/A 10 N/A

Oxidizing N/A 10 N/A

Explosives d,e,f See note See note See note See note

Flammable gas c,g Gaseous N/A N/A NP

Liquefied N/A N/A (20)

Liquefied Petroleum N/A N/A (20)

Consumer fireworks See note See note See note See note

Flammable solid N/A 5 N/A N/A

Oxidizers 4 NP NP NP

3 10 h 1 h NP

2 250 25 NP

1 4,000 i 400 i NP

Oxidizing gas h Gaseous N/A N/A NP h

Liquefied N/A N/A NP h

Organic peroxides I NP NP N/A

II NP NP N/A

III 25 (25) N/A

IV NL NL N/A

V NL NL N/A

Pyrophoric materials N/A NP NP NP

Unstable reactives 4 NP NP NP

3 NP NP NP

2 10 10 NP g

1 NL NL NP

Water-reactive 3 1 (1) N/A

2 10 10 N/A

1 NL NL N/A

Corrosives N/A 1,000 100 NP

Highly toxic N/A 3 (3) NP j

Toxic N/A 125 (125) NP j

For SI units, 1 lb = 0.454 kg; 1 gal = 3.785 L.

NTP: Normal temperature and pressure [70°F (21°C) and 14.7 psi (101 kPa)]. N/A: Not applicable. NP: Not permitted. NL: Not limited.

Page 266 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 41 of 63

Note: The hazardous material categories and MAQs that are shaded in this table are not regulated by NFPA 400 but are provided here for informational purposes. See Chapter 2 of NFPA 400 for the reference code or standard governing these materials and establishing the MAQs. In accordance with 1.1.1.2 of NFPA 400, materials having multiple hazards that fall within the scope of NFPA 400 shall comply with NFPA 400.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with NFPA 400.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495, Explosive Materials Code .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g Containers, cylinders, or tanks not exceeding 250 scf (7.1 m3) content measured at 70°F (21°C) and 14.7 psi (101 kPa) and used for maintenance purposes, patient care, or operation of equipment shall be permitted.

h A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

i The permitted quantities are not limited in a building protected throughout by automatic sprinkler systems in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems .

j Gas cylinders not exceeding 20 scf (0.57 m 3 ) measured at 70°F (21°C) and 14.7 psi (101 kPa) are permitted in gas cabinets or fume hoods.

k Conversion. Where quantities are indicated in pounds and when the weight per gallon of the liquid is not provided to the AHJ, a conversion factor of 10 lb/gal (1.2 kg/L) shall be used.

[ 400: Table 5.2.1.6]

Table 34.1.3.2(k) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Area in Health Care Occupancies

Page 267 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 42 of 63

Material Class Solid LiquidGas a (at

NTP)

Flammable and combustibleliquid b,c I and II combined NP 10 gal NP

IIIA NP 60 gal NP

IIIB NP120

gal d NP

Cryogenic liquid Flammable NP 10 gal NP

Oxidizing NP 10 gal NP

Explosives e,f,g NP NP NP NP

Flammable gas c,e,f,g,h Gaseous NP NP NP

Liquefied i NP 20 lb NP

Liquefiedpetroleum NP 20 lb NP

Consumer fireworks 1.4G NP NP NP

Flammable solid NP 5 lb NP NP

Oxidizers 4 NP NP NP

3 10 lb j 1 gal j NP

2 250 lb 25 gal NP

14000lb d

400gal d NP

Oxidizing gas Gaseous NP NPper NFPA

99

Liquefied NP 15 gal NP

Organic peroxidesUnclassified detonatable NP NP NP

I NP NP NP

II NP NP NP

III 1 lb 1 lb NP

IV 10 lb 10 lb NP

V NL NL NP

Pyrophoric materials NP NP NP NP

Unstable reactives 4 NP NP NP

3 NP NP NP

2 10 lb 10 lb NP h

1 NL NL NP

Water-reactive 3 1 lb 1 lb NA

2 10 lb 10 lb NA

1 NL NL NA

Corrosives NP 1000 lb 100 gal NP

Highly toxic NP 3 lb 3 lb NP k

Toxic NP 125 lb 125 lb NP k

For SI units, 1 gal = 3.785 L; 1 lb = 0.454 kg.

Page 268 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 43 of 63

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (30 kPa)]. NP: Not permitted. NL: Not limited. NA: Not applicable.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with the fire code.

d The permitted quantities are not limited in a building protected throughout by automatic sprinkler systems in accordance with NFPA 13 .

e The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495 .

f The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopoeia or the National Formulary are not required to be limited.

g The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

h Fuel or oxidizing gas used for maintenance, repair, and operation of equipment is not permitted to exceed 250 ft 3 (7.1 m 3 ).

i Storage in laboratories only; additional storage of 5 lb (2.3 kg) units permitted where minimum 20 ft (6.1 m) separation is provided.

j A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

k Gas cylinders not exceeding 20 ft 3 (0.57 m 3 ) at NTP are permitted in gas cabinets or fume hoods.

Table 34.1.3.2(f) Maximum Allowable Quantities (MAQ) of Hazardous Materials per Control Area in Detention and Correctional Occupancies a

Page 269 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 44 of 63

Material ClassSolid

Pounds

Liquid Gallons k

(lb)

Gas a (at NTP) scf

(lb)

Flammable andcombustible liquid b,c See note See note See note See note

Cryogenic fluid Flammable N/A 10 N/A

Oxidizing N/A 10 N/A

Explosives d,e,f,g See note See note See note See note

Flammable gas c,h Gaseous N/A N/A NP

Liquefied N/A N/A (20)

Liquefied Petroleum N/A N/A (20)

Consumer fireworks See note See note See note See note

Flammable solid N/A 5 N/A N/A

Oxidizers 4 NP NP N/A

3 10 i 1 i N/A

2 250 25 N/A

1 4,000 400 N/A

Oxidizing gas h Gaseous N/A N/A NP

Liquefied N/A N/A N/A

Organic peroxides I NP NP N/A

II NP NP N/A

III 25 (25) N/A

IV NL NL N/A

V NL NL N/A

Pyrophoric materials NA 1 (1) NP

Unstable reactives 4 1 ⁄4 ( 1 ⁄4 ) NP

3 1 (1) NP

2 10 10 NP h

1 NL NL NP

Water-reactive 3 1 (1) N/A

2 10 (10) N/A

1 NL NL N/A

Corrosives N/A 1,000 100 NP

Highly toxic N/A 3 3 NP j

Toxic N/A 125 125 NP j

For SI units, 1 lb = 0.454 kg; 1 gal = 3.785 L.

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (101 kPa)]. N/A: Not applicable. NP: Not permitted. NL: Not limited.

Page 270 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 45 of 63

Note: The hazardous material categories and MAQs that are shaded in this table are not regulated by NFPA 400 but are provided here for informational purposes. See Chapter 2 of NFPA 400 for the reference code or standard governing these materials and establishing the MAQs. In accordance with 1.1.1.2 of NFPA 400, materials having multiple hazards that fall within the scope of NFPA 400 shall comply with NFPA 400.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with NFPA 400.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495, Explosive Materials Code .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g The storage and use of small arms ammunition, and components thereof, are permitted where in accordance with NFPA 495, Explosive Materials Code .

h Containers, cylinders, or tanks not exceeding 250 scf (7.1 m3) content measured at 70°F (21°C) and 14.7 psi (101 kPa) and used for maintenance purposes, patient care, or operation of equipment shall be permitted.

i A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

j Gas cylinders not exceeding 20 scf (0.57 m3) measured at 70°F (21°C) and 14.7 psi (101 kPa) are permitted in gas cabinets or fume hoods.

k Conversion. Where quantities are indicated in pounds and when the weight per gallon of the liquid is not provided to the AHJ, a conversion factor of 10 lb/gal (1.2 kg/L) shall be used.

[ 400: Table 5.2.1.7]

Table 34.1.3.2(m) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Area in Detention and Correctional Occupanciesa

Page 271 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 46 of 63

Material Class Solid LiquidGas a (at

NTP)

Flammable and combustibleliquid b,c I and II combined NP 10 gal NP

IIIA NP 60 gal NP

IIIB NP 120 gal NP

Cryogenic liquid Flammable NP 10 gal NP

Oxidizing NP 10 gal NP

Explosives d,e,f,g NP NP NP NP

Flammable gas c,h Gaseous NP NP NP

Liquefied NP 20 lb NP

Liquefied petroleum NP 20 lb NP

Consumer fireworks 1.4G NP NP NP

Flammable solid NP 5 lb NP NP

Oxidizers 4 NP NP NP

3 10 lb i 1 gal i NP

2 250 lb 25 gal NP

1 4000lb 400 gal NP

Oxidizing gas h Gaseous NA NP NP

Liquefied NA 15 gal NP

Organic peroxides Unclassified detonatable NP NP NP

I NP NP NP

II NP NP NP

III 1 lb 1 lb NP

IV 10 lb 10 lb NP

V NL NL NP

Pyrophoric materials NP NP NP NP

Unstable reactives 4 NP NP NP

3 NP NP NP

2 10 lb 10 lb NP h

1 NL NL NP

Water-reactive 3 1 lb 1 lb NP

2 10 lb 10 lb NP

1 NL NL NP

Corrosives NP1000

lb 100 gal NP

Highly toxic NP 3 lb 3 lb NP j

Toxic NP 125 lb 125 lb NP j

For SI units, 1 gal = 3.785 L; 1 lb = 0.454 kg.

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (30 kPa)]. NP: Not permitted. NA: Not applicable. NL: Not limited.

Page 272 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 47 of 63

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with the fire code.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495 .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopoeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g The storage and use of small arms ammunition, and components thereof, are permitted where in accordance with NFPA 495 .

h Fuel or oxidizing gas used for maintenance, repair, and operation of equipment is not permitted to exceed 250 ft 3 (7.1 m 3 ).

i A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

j Gas cylinders not exceeding 20 ft 3 (0.57 m 3 ) at NTP are permitted in gas cabinets or fume hoods.

Table 34.1.3.2(g) Maximum Allowable Quantities of Hazardous Materials per Control Area in Residential Occupancies Consisting of Lodging and Rooming Houses, Hotels, Dormitories, Apartments, and Residential Board and CareFacilities

Page 273 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 48 of 63

Material ClassSolid

Pounds

Liquid Gallons l

(lb)

Gas a (at NTP) scf

(lb)

Flammable andcombustible liquid b,c See note See note See note See note

Cryogenic fluid Flammable N/A 10 N/A

Oxidizing N/A 10 N/A

Explosives d,e,f,g See note See note See note See note

Flammable gas c,h Gaseous N/A N/A NP

Liquefied j N/A N/A (20)

Liquefied Petroleum N/A N/A (20)

Consumer fireworks See note See note See note See note

Flammable solid N/A 5 N/A N/A

Oxidizers 4 NP NP N/A

3 10 i 1 i N/A

2 250 25 N/A

1 4,000 400 N/A

Oxidizing gas h Gaseous N/A N/A NP h

Liquefied N/A NL N/A

Organic peroxides I NP NP N/A

II NP NP N/A

III 25 (25) N/A

IV NL NL N/A

V NL NL N/A

Pyrophoric materials N/A 1 (1) NP

Unstable reactives 4 1 ⁄4 ( 1 ⁄4 ) NP

3 1 (1) NP

2 10 (10) NP h

1 NL NL NP

Water-reactive 3 1 (1) N/A

2 10 (10) N/A

1 NL NL N/A

Corrosives N/A 1,000 100 NP

Highly toxic N/A 3 (3) NP k

Toxic N/A 125 (125) NP k

For SI units, 1 lb = 0.454 kg; 1 gal = 3.785 L.

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (101 kPa)]. N/A: Not applicable. NP: Not permitted. NL: Not limited.

Page 274 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 49 of 63

Note: The hazardous material categories and MAQs that are shaded in this table are not regulated by NFPA 400 but are provided here for informational purposes. See Chapter 2 of NFPA 400 for the reference code or standard governing these materials and establishing the MAQs. In accordance with 1.1.1.2 of NFPA 400, materials having multiple hazards that fall within the scope of NFPA 400 shall comply with NFPA 400.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids are permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with NFPA 400.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495, Explosive Materials Code .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g The storage and use of small arms ammunition, and components thereof, are permitted where in accordance with NFPA 495, Explosive Materials Code .

h Containers, cylinders, or tanks not exceeding 250 scf (7.1 m 3 ) content measured at 70°F (21°C) and 14.7 psi (101 kPa) and used for maintenance purposes, patient care, or operation of equipment shall be permitted.

i A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

j Storage containers are not permitted to exceed 0.325 ft 3 (0.0092 m 3 ) capacity.

k Gas cylinders not exceeding 20 scf (0.57 m 3 ) measured at 70°F (21°C) and 14.7 psi (101 kPa) are permitted in gas cabinets or fume hoods.

l Conversion. Where quantities are indicated in pounds and when the weight per gallon of the liquid is not provided to the AHJ, a conversion factor of 10 lb/gal (1.2 kg/L) shall be used.

[ 400: Table 5.2.1.8]

Table 34.1.3.2(o) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Area in Residential Occupancies Consisting of Lodging or Rooming Houses, Hotels, Dormitories, Apartments, and Residential Board and CareFacilities

Page 275 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 50 of 63

Material Class Solid LiquidGas a (at

NTP)

Flammable and combustibleliquid b,c I and II combined NP 10 gal NP

IIIA NP 60 gal NP

IIIB NP 120 gal NP

Cryogenic liquid Flammable NP 10 gal NP

Oxidizing NP 10 gal NP

Explosives d,e,f,g NP NP NP NP

Flammable gas c,h Gaseous NP NP NP

Liquefied i NP 20 lb NP

Liquefied petroleum NP 20 lb NP

Consumer fireworks 1.4G NP NP NP

Flammable solid NP 5 lb NP NP

Oxidizers 4 NP NP NP

3 10 lb j 1 gal j NP

2 250 lb 25 gal NP

1 4,000lb

400 gal NP

Oxidizing gas h Gaseous NP NP NP

Liquefied NP 15 gal NP

Organic peroxides Unclassified detonatable

NP NP NP

I NP NP NP

II NP NP NP

III 1 lb 1 lb NP

IV 10 lb 10 lb NP

V NL NL NP

Pyrophoric materials NP 1 lb 1 lb NP

Unstable reactives 4 1 ⁄4 lb 1 ⁄4 lb NP

3 1 lb 1 lb NP

2 10 lb 10 lb NP h

1 NL NL NP

Water-reactive 3 1 lb 1 lb NA

2 10 lb 10 lb NA

1 NL NL NA

Corrosives NP1,000

lb 100 gal NP

Highly toxic NP 3 lb 3 lb NP k

Toxic NP 125 lb 125 lb NP k

For SI units, 1 gal = 3.785 L; 1 lb = 0.454 kg.

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (30 kPa)]. NP: Not permitted. NL: Not limited. NA: Not applicable.

Page 276 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 51 of 63

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids are permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with the fire code.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495 .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g The storage and use of small arms ammunition, and components thereof, are permitted where in accordance with NFPA 495 .

h Fuel or oxidizing gas used for maintenance, repair, and operation of equipment is not permitted to exceed 250 ft 3 (7.1 m 3 ).

i Storage containers are not permitted to exceed 2.7 lb (1.2 kg) water capacity.

j A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

k Gas cylinders not exceeding 20 ft 3 (0.57 m 3 ) at NTP are permitted in gas cabinets or fume hoods.

Table 34.1.3.2(h) Maximum Allowable Quantities (MAQ) of Hazardous Materials per Control Area in Business Occupancies

Page 277 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 52 of 63

Material ClassSolid

Pounds

Liquid Gallons j

(lb)

Gas a,i (at NTP) scf (lb)

Flammable and combustible liquid b,c See note See note See note See note

Cryogenic fluid Flammable N/A 10 N/A

Oxidizing N/A 10 N/A

Explosives d,e,f,g See note See note See note See note

Flammable gas c Gaseous N/A N/A 1000

Liquefied N/A N/A (20)

Liquefied Petroleum N/A N/A (20)

Consumer fireworks See note See note See note See note

Flammable solid N/A 5 N/A N/A

Oxidizers 4 NP NP NP

3 10 h 1 h NP

2 250 25 NP

1 4,000 400 NP

Oxidizing gas Gaseous N/A N/A 1500

Liquefied NA 15 N/A

Organicperoxides I NP NP N/A

II NP NP N/A

III 1500 1500 N/A

IV 100,000 100,000 N/A

V NL NL N/A

Pyrophoricmaterials N/A 1 (1) 10

Unstable reactives 4 1 ⁄4 ( 1 ⁄4 ) 2

3 1 (1) 10

2 10 (10) 750

1 NL NL NL

Water-reactive 3 1 (1) N/A

2 10 (10) N/A

1 NL NL N/A

Corrosives N/A 1000 (100) 810

Highly toxic i N/A 3 (3) 20

Toxic i N/A 125 (125) 810

For SI units, 1 lb = 0.454 kg; 1 gal = 3.785 L; 1 scf 3 = 0.0283 m 3 .

NTP: Normal temperature and pressure [measured at 70°F (21°C) and 14.7 psi (101 kPa)]. N/A: Not applicable. NP: Not permitted. NL: Not limited.

Page 278 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 53 of 63

Note: The hazardous material categories and MAQs that are shaded in this table are not regulated by NFPA 400 but are provided here for informational purposes. See Chapter 2 of NFPA 400 for the reference code or standard governing these materials and establishing the MAQs. In accordance with 1.1.1.2 of NFPA 400, materials having multiple hazards that fall within the scope of NFPA 400 shall comply with NFPA 400.

a Unlimited amounts of gas are permitted to be used for personal medical or emergency medical use.

b Storage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180 gal (681 L).

c Fuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where the equipment is operated in accordance with NFPA 400.

d The use of explosive materials required by federal, state, or municipal agencies while engaged in normal or emergency performance of duties is not required to be limited. The storage of explosive materials is required to be in accordance with the requirements of NFPA 495, Explosive Materials Code .

e The storage and use of explosive materials in medicines and medicinal agents in the forms prescribed by the official United States Pharmacopeia or the National Formulary are not required to be limited.

f The storage and use of propellant-actuated devices or propellant-actuated industrial tools manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb (23 kg) net explosive weight.

g The storage and use of small arms ammunition, and components thereof, are permitted where in accordance with NFPA 495, Explosive Materials Code .

h A maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such materials are necessary for maintenance purposes, operation, or sanitation of equipment. Storage containers and the manner of storage are required to be approved.

I Gas cylinders not exceeding 20 scf (0.57 m 3 ) measured at 70°F (21°C) and 14.7 psi (101 kPa) are permitted in gas cabinets or fume hoods.

j Conversion. Where quantities are indicated in pounds and when the weight per gallon of the liquid is not provided to the AHJ, a conversion factor of 10 lb/gal (1.2 kg/L) shall be used.

[ 400: Table 5.2.1.10.1]

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 16:25:16 EDT 2013

Committee Statement

Page 279 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 54 of 63

CommitteeStatement:

NFPA 400 is the expert document on maximum allowable quantities and the requirements for hazardous materials. Now that NFPA 400 is an established document, NFPA 5000 is able to extract applicable provisions regarding hazardous materials. All MAQ tables should be extracted from NFPA 400 for this edition of NFPA 5000 and those going forward.

ResponseMessage:

Page 280 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 55 of 63

Second Revision No. 140-NFPA 5000-2013 [ Section No. 34.1.3.3.1 ]

34.1.3.3.1 Maximum Allowable Quantity (MAQ) Increases for Mercantile, Storage, and Industrial Occupancies.The aggregate quantity of nonflammable solid and nonflammable ornoncombustible liquid hazardous materials permitted within a single control area of a mercantile, storage, or industrial occupancy shall be permitted to exceed the MAQ specified in ,Table 34.1.3.1 without complying with Protection Level 2, Protection Level 3, or Protection Level 4, provided that the quantities comply with Table 34.1.3.3.1(a) and Table 34.1.3.3.1(b) and that materials are displayed and stored in accordance with the special limitations on storage height, storage density, and other controls specified in NFPA 1 and NFPA 400, Hazardous Materials Code.Table 34.1.3.3.1(a) Maximum Allowable Quantity (MAQ) per Control Area Increases for Selected Hazard Categories in Mercantile, Storage, and Industrial Occupancies

Maximum Allowable Quantity a,b

Solids Liquids

Hazard Category lb kg gal L

Physical Hazard Materials: Nonflammable Solids and Nonflammable or Noncombustible Liquids

Oxidizers

Class 3 1,150 522 115 435

Class 2 2,250 1,022 225 852

Class 1 c 18,000 8,172 1,800 6,813

Note: Maximum quantities for hazard categories not shown are required to be in accordance with Table 34.1.3.1 .

a Maximum quantities are permitted to be increased 100 percent in buildings that are sprinklered in accordance with NFPA 13 . Where footnote b also applies, the increase for both footnote a and footnote b is permitted to be applied.

b Maximum quantities are permitted to be increased 100 percent where stored in approved storage cabinets, gas cabinets, or exhausted enclosures in accordance with NFPA 1 or NFPA 400 . Where footnote a also applies, the increase for both footnote b and footnote a is permitted to be applied.

c Quantities are not limited in buildings protected by an automatic sprinkler system complying with NFPA 13 .

Table 34.1.3.3.1(a) Maximum Allowable Quantity (MAQ) per Indoor and Outdoor Control Area for Selected Hazard Categories in Mercantile, Storage, andIndustrial Occupancies

Page 281 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 56 of 63

Hazard Category

Maximum Allowable Quantity a,b

Solids Liquids

lb kg gal L

Physical Hazard Materials: Nonflammable and Noncombustible Solids and Liquids

Oxidizers

Class 3 1,150 522 115 435

Class 2 2,250 1021 225 852

Class 1 18,000 c 8165 c 1,800 c 6814 c

Note: Maximum quantities for hazard categories not shown are required to be in accordance with Table 5.2.1.1.3.

a Maximum quantities are permitted to be increased 100 percent in buildings that are sprinklered in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems . Where footnote b also applies, the increase for both footnotes is permitted to be applied.

b Maximum quantities are permitted to be increased 100 percent where stored in approved storage cabinets in accordance with NFPA 1, Fire Code . Where footnote (a) also applies, the increase for both footnotes is permitted to be applied.

c Quantities are not limited in buildings protected by an automatic sprinkler system complying with NFPA 13. [ 5000: Table 34.1.3.3.1(a)]

Table 34.1.3.3.1(b) Maximum Allowable Quantity (MAQ) per Control Area Increases for Selected Hazard Categories in Mercantile and StorageOccupancies

Maximum Allowable Quantity a,b,c

Solids Liquids

Hazard Category lb kg gal L

Physical Hazard Materials: Nonflammable Solids and Nonflammable or Noncombustible Liquids

Unstable reactives

Class 3 550 250 55 208

Class 2 1,150 522 115 435

Water-reactive

Class 3 550 250 55 208

Class 2 1,150 522 115 435

Health Hazard Materials: Nonflammable and Noncombustible Solids and Liquids

Corrosive 10,000 4540 1,000 3785

Highly toxic 20 9 2 8

Toxic 1,000 454 100 379

NOTE: See table above.

a Maximum quantities are permitted to be increased 100 percent in buildings that are sprinklered in accordance with NFPA 13 . Where footnote c also applies, the increase for both footnote a and b is permitted to be applied.

Page 282 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 57 of 63

b Maximum quantities are permitted to be increased 100 percent where stored in approved storage cabinets, gas cabinets, or exhausted enclosures in accordance with NFPA 1 . Where footnote b also applies, the increase for both footnote b and footnote a is permitted to be applied.

c Maximum quantities are permitted to be increased 100 percent where stored in approved storage cabinets, gas cabinets, or exhausted enclosures in accordance with NFPA 1 . Where footnote a also applies, the increase for both footnotes is permitted to be applied.

Table 34.1.3.3.1(b) Maximum Allowable Quantity (MAQ) per Indoor and Outdoor Control Area for Selected Hazard Categories in Mercantile and StorageOccupancies

Hazard Category

Maximum Allowable Quantity a,b,c

Solids Liquids

lb kg gal L

Physical Hazard Materials: Nonflammable and Noncombustible Solids and Liquids

Unstable (reactive)

Class 3 550 250 55 208

Class 2 1,150 522 115 435

Water-reactive

Class 3 550 250 55 208

Class 2 1,150 522 115 435

Health Hazard Materials: Nonflammable and Noncombustible Solids and Liquids

Corrosive 10,000 4536 1,000 3785

Highly toxic d 20 9 2 8

Toxic d 1,000 454 100 378

a Maximum quantities for hazard categories not shown are required to be in accordance with Table 5.2.1.1.3.

b Maximum quantities are permitted to be increased 100 percent in buildings that are sprinklered in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems . Where footnote b also applies, the increase for both footnotes can be applied.

c Maximum quantities are permitted to be increased 100 percent where stored in approved storage cabinets in accordance with NFPA 1, Fire Code . Where footnote (a) also applies, the increase for both footnotes is permitted to be applied. [ 5000 :Table 34.1.3.3.1(b)]

d Toxic or highly toxic solids or liquids displayed in original packaging in mercantile or storage occupancies and intended for maintenance, operation of equipment, or sanitation when contained in individual packaging not exceeding 100 lb (45.4 kg) shall be limited to an aggregate of 1200 lb (544.3 kg) or 220 gal (832.8 L). The increases allowed by footnotes a, b, and c shall not apply to highly toxic solids andliquids.

Submitter Information Verification

Page 283 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 58 of 63

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 16:44:24 EDT 2013

Committee Statement

CommitteeStatement:

NFPA 400 is the expert document on maximum allowable quantities and the requirements for hazardous materials. Now that NFPA 400 is an established document, NFPA 5000 is able to extract applicable provisions regarding hazardous materials. All MAQ tables should be extracted from NFPA 400 for this edition of NFPA 5000 and those going forward.

ResponseMessage:

Page 284 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 59 of 63

Second Revision No. 141-NFPA 5000-2013 [ Section No. 34.2.5.1.1 ]

34.2.5.1.1Control areas shall be separated from each other by fire barriers in accordance with Table 34.2.5.1.1.Table 34.2.5.1.1 Design and Number of Control Areas

Floor Level

Maximum Allowable Quantity per Control

Area (%) †

Number of Control Areas

per FloorFire Resistance Rating for Fire Barriers ‡ (hr)

Above grade plane

>9 5.0 1 2

7–9 5.0 2 2

4–6 12.5 2 2

3 50.0 2 1

2 75.0 3 1

1 100.0 4 1

Below grade plane

1 75 3 1

2 50 2 1

Lower than 2

NA NA NA

NA: Not applicable.

† Percentages represent the maximum allowable quantities per control area shown in Table 34.1.3.1 , with all of the increases permitted in the footnotes of that table.

‡ Fire barriers are required to include floors and walls, as necessary, to provide a complete separation from other control areas.

Table 34.2.5.1.1 Design and Number of Control Areas

Page 285 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 60 of 63

FloorLevel

Maximum Allowable Quantity per Control Area

(%)*Number of Control Areas per Floor

Fire Resistance Rating for Fire Barriers† (hr)

Above grade

>9 5 1 2

7–9 5 2 2

4–6 12.5 2 2

3 50 2 1

2 75 3 1

1 100 4 1

Below grade

1 75 3 1

2 50 2 1

Lower than 2 NP NP N/A

NP: Not permitted. N/A: Not applicable.

*Percentages represent the MAQ per control area shown in Table 34.1.3.1, with all the increases permitted in the footnotes of that table.

†Fire barriers are required to include floors and walls, as necessary, to provide a complete separation from other control areas.

[ 400, Table 5.2.2.1]

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 16:48:42 EDT 2013

Committee Statement

CommitteeStatement:

NFPA 400 is the expert document on maximum allowable quantities and the requirements for hazardous materials. Now that NFPA 400 is an established document, NFPA 5000 is able to extract applicable provisions regarding hazardous materials. All MAQ tables should be extracted from NFPA 400 for this edition of NFPA 5000 and those going forward.

ResponseMessage:

Page 286 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 61 of 63

Second Revision No. 142-NFPA 5000-2013 [ Section No. 34.3.4.4.1 ]

34.3.4.4.1Buildings required to comply with Protection Level 2, and containing quantities of high hazard contents exceeding the quantity limits set forth in Table 34.3.4.4.1, shall be used for manufacturing, processing, dispensing, use, or storage of hazardous materials and no other purpose; shall not exceed one story in height; and shall be without basements, crawl spaces, or other under-floor spaces.Table 34.3.4.4.1 High Hazard Level 2 and High Hazard Level 3 Materials—Required Detached Storage

Maximum Quantity Without a Detached Storage Building

Material Class Solids and Liquids (tons) Gases (ft 3 )

Oxidizers Class 3 1,200 NA

Class 2 2,000 NA

Organicperoxides Class II 25 NA

Class III 50 NA

Unstablereactives

Class 3,nondetonable 1 2,000

Class 2 25 10,000

Water-reactive Class 3 1 NA

Class 2,deflagrating

25 NA

Pyrophoric gases NA 2,000

For SI units, 1 ton = 0.9 met tons; 1 ft 3 = 0.0283 m 3 .

NA: Not applicable.

Table 34.3.4.4.1 Detached Buildings Required Where Quantity of Material Exceeds Amount Shown

Quantity of Material

Gas Hazard Class scf Nm3

Individual bulk hydrogen compressed gas systems NA 15,000 425

Unstable reactive (detonable) 4 or 3Quantity thresholds for gases requiring

special provisions*

Unstable reactive (nondetonable) 3 2,000 57

Unstable reactive (nondetonable) 2 10,000 283

Pyrophoric gas NA 2,000 57

NA: Not applicable.

*See Table 6.3.1.1.

[ 55, Table 6.5]

Page 287 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 62 of 63

Submitter Information Verification

Submitter Full Name: Kristin Bigda

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 16:58:58 EDT 2013

Committee Statement

CommitteeStatement:

Update extract reference to extract Table from NFPA 55. NFPA 400 also extracts the table from NFPA 55 so this would provide consistency between the documents.

Response Message:

Page 288 of 346National Fire Protection Association Report

9/5/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

BLD-IND SECOND REVISIONS WITH STATEMENTS

Page 63 of 63