  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    1/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    PAVAROOF pitchedTHE SCIENCE OF NATURE - THE FUTURE OF CONSTRUCTION

    TECHNICAL MANUAL

    subject to change without prior notice / 06.2007 / BB

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    2/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Natural Building Technologies LtdThe Hangar, Worminghall Road,

    Oakley, Bucks HP18 9UL

    Tel: +44 (0)1844 338 338Fax: +44 (0)1844 338 525

    Email: [email protected]: www.natural-building.co.uk

    Manual Content

    Describtion of NBT Pitched RoofSolution

    Performance GuideOverviewDecrement DelayThermal Bridges

    Air Tightness

    PAVAROOF pitchedSystem build upThermal PropertiesSpecification PavacladKey Consideration Designers &InstallersInstallation Procedures- Fitting Boards- Using Pavatape- Fixing Counter Battens

    Technical Data Boards

    Contact Address

    Detail Drawings

    3

    4566

    789

    10

    111213

    15

    15

    16

    2

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    3/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Describtion of NBT Pitched Roof Solutions

    Made from 99.5% waste softwood and 0.5% inert water-proofing additives, Pavatex WoodfibreBoards (Pavatherm Plus, Isolair) are a genuinely sustainable non-toxic building material.To make Pavatex boards, waste wood fibres are pulped and mixed with water. The pulp is heated toactivate the lignin they contain in order to glue the fibres together. The pulp is then pressed intoboards, dried, and cut to size.The advanced manufacturing process uses the inherent properties ofwood fibres to produce boards with many excellent technical qualitiesfor thermal and acoustic insulation, thermal storage capacity, vapourpermeability and moisture control.

    The NBT Roof Systems are...l Certified: LANTAC approval, BBA certification, BRE Green Guide

    A rating, natureplus assessment and products are CE marked

    l Cost effective

    l Breathable

    l Controls summer overheating

    l Ecological

    l Excellent acoustic performance

    l No membrane required

    l Simple and robust

    l Especially suitable for rooms in roofs

    The NBT Roof System is suitable for over rafter insulation. It provides a vapour permeable insulationand sarking layer that offers excellent thermal and acoustic performance without the need forwaterproof membrane.

    3

    ISO

    IR

    LA

    SO

    RI

    I

    LA

    SIO

    ISO

    IR

    LA

    PAVAROOF pitched(with insulation between rafters and on top of rafters)

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    4/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Performance Guide Pitched Roof Solutions

    ...keeps the building warmer for longer in cold weather

    When used on top of the rafters the boards reduce the effect ofthermal bridging and the interlocking board design easilyachieves good wind-tightness. All this increases thermalperformance.

    A modern roof insulation system must do more than just protect building occupants from cold. It mustcreate a comfortable and healthy environment for the building users in all possible combinations ofexternal and internal conditions and control the effects of external heat, cold, noise and internalmoisture generation.

    NBT pitched roof solution...

    ...keeps the building cooler in hot weather

    The unique combination of high density, high specific heatcapacity and low thermal conductivity gives NBT roof solutions

    the thermal mass required for overheating protection. Result is areduction of the max temperature under a roof of up to 4 degreescompared to a construction with similar u-value using lightweightinsulation products.

    ...keeps the building quieter

    The high mass and the fibrous texture of Pavatex woodfibregives excellent acoustic performance. This allows you to achievegood roof constructions and internal environments even in areaswith high noise impact such as airports, railways and motorways.

    ...keeps the building dry and is breathablePavatex woodfibre boards are very vapour permeable andhygroscopic. For the roof products there is a latex impregnationthrough the whole board structure which offers continuedprotection to water penetration. The boards can withstand a threemonth exposure period without a roof covering. This gives doublesecurity in case a tile breaks and water penetrates this first roofcovering. No membrane on top of the latex impregnated

    woodfibre board is required.

    4

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    5/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Summer Overheating: Decrement Delay and Decrement Factor

    As part of the design of the roof it is important to consider effects of summer overheating control,particulary when there are rooms in roofs or in buildings such as schools and halls where teachingspace exists directly below the roof. Summer overheating is in fact caused by any or a combinationof three reasons:

    1) too large internal gains from appliances, people machines etc.2) two much sun directly through windows due to poor summer shading,3) heat passing directly through the roof.

    The solution to the first is to reduce the gains or ventilate, the second to provide better shading, andthe third is to reduce peak heat gain to the room by changing the Decrement. Decrement can be

    thought of as the amount a peak external surface temperature is smoothed out by the structure, andthe time that the peak is delayed before it reaches the inside.

    These are in fact two factors and are called respectively Decrement factor and Decrement delay. Toreduce the solar heat from passing through a roof, we need a low decrement factor, and moreimportantly, have it occur a minimum of 6-12 hours after the midday external solar radiation peak iea decrement delay of at least 6-12 hours.In terms of achieving satisfactory values, an insulation material that also has thermal mass willproduce better values. What is required is a function of density, thermal conductivity and specificheat capacity. Pavatex woodfibre boards have an excellent combination of low k-value (0.038-0.047W/mK), high specific heat capacity (2100J/kgK) and for insulation boards a high density (140 240

    kg/m) which far exceeds any conventional material. This means that with Pavatex woodfibreinsulation a lightweight structure such as timber can perform as though it was a mass structure.The consequence is the reduction of internal temperatures by 4degC or more in summer comparedto a roof with may have the same u-value but conventional insulation.

    -

    5

    60

    55

    50

    45

    40

    35

    30

    25

    20

    15

    10

    Temperature(de

    gC)

    06:00 09:00 12:00 15:00 18:00 21:00 00:00 03:00 06:00

    August 18th 2005 August 19th 2005

    Measured temperature under the red roof tiles

    Measured temperature at the externalsurface of the ISOLAIR board

    Temperature at the internal surface of the plasterboard (notconsidered effect of windows, internal heat sources and air

    Tmaxexternal 26.2 degC

    Tminexternal 13.6degC

    Amplitude

    ex

    tern

    Amplitude

    intern

    Decrement Delay

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    6/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Thermal Bridges

    Advantage of additional insulation on top of the rafter

    l less insulation between the rafter required for same u-value

    l dimensions of rafters are just as big as they need to be for structural reason

    l protection of structural rafters from external conditions and temperature changes

    l less thermal bridges at all junctions because you have like a warm shell which goes on top of allsolid timber junctions

    l better acoustic performance

    l overheating protection in summer because of high thermal mass of PAVATHERM PLUS and

    ISOLAIR woodfibre insulation

    Air Tightness

    With Building Regulations Part L: 2006 edition, a new figure gets more and more important forbuilding design. Air tightness of a structure is critical if it is to perform thermally and indeedacoustically. The limit for the design air permeability is 10m/(h.m) at 50Pa. Significantly betterstandards of air permeability are technically desirable in dwellings with mechanical ventilation,especially when using balanced systems with heat recovery.

    NBT roof solutions allow you to achieve good air tightness in a easy and cost effective way. Themost difficult part is getting buildings air tight at junctions between building elements such as raftersand junctions with walls. Please find guidance for detailing in the last section of this technicalmanual.

    Pavatherm Plus100mm

    Pavatherm Plus60mm

    Isolair 35mm Isolair 22mm BreatherMembrane

    There are different ways to get a elemental u-vlaue of 0.20 W/mK*. As more you insulate on top ofthe rafters, as less is the effect of repeting and non-repeting thermal brides because of timber studs.

    Insulation110mm

    Rafter50/110

    Insulation150mm

    Rafter50/150

    Insulation185mm

    Rafter50/185

    Insulation200mm

    Rafter50/200

    Insulation220mm

    Rafter50/220

    6

    *all calculations including 8.3% thermal bridging because of timber rafters, insulation between rafters thermal conductivity0.039W/mK

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    7/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    PAVAROOF pitched - Insulation between & on top of rafters

    7

    ISO

    IR

    LA

    SO

    R

    I

    LA

    I

    ISO

    ISO

    IR

    LA

    Tiles / Slate

    Counter Battens

    Tile Battens

    ISOLAIR or PAVATHERMPLUS insulation

    ISONAT (hemp/cotton),WARMCEL orSHEEPWOOL insulation

    Air Tightness Layer &service void (optional)

    Plasterboard and skim

    PAVAROOF pitched

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    8/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    System Build-Up PAVAROOF pitched

    *based on ISONAT hemp/cotton(k=0.039 W/mK) with 8.3% bridging and no service void

    Thermal Properties PAVAROOF pitched

    8

    Insulationonto StudInsulationbetween Rafter*U-Value[W/mK]DecrementFactorDecrementDelay [h]

    Admittance[W/mK]

    22mmIsolair100mmIsonat0.34

    0.92

    2.6

    1.02

    35mmIsolair100mmIsonat0.32

    0.85

    3.6

    1.03

    60mmIsolair100mmIsonat0.27

    0.64

    5.7

    1.05

    60mmPavatherm Pl.100mmIsonat0.26

    0.72

    4.9

    1.05

    80mmPavatherm Pl.100mmIsonat0.23

    0.57

    6.4

    1.06

    100mmPavatherm Pl.100mmIsonat0.21

    0.44

    7.7

    1.06

    1

    2

    Rafter Depth 100mm

    1

    2

    Insulationonto StudInsulationbetween Rafter*U-Value[W/mK]DecrementFactorDecrementDelay [h]

    Admittance[W/mK]

    22mmIsolair150mmIsonat0.25

    0.86

    3.7

    1.04

    35mmIsolair150mmIsonat0.24

    0.78

    4.7

    1.05

    60mmIsolair150mmIsonat0.21

    0.56

    6.9

    1.06

    60mmPavatherm Pl.150mmIsonat0.20

    0.64

    6.2

    1.06

    80mmPavatherm Pl.150mmIsonat0.19

    0.49

    7.6

    1.06

    100mmPavatherm Pl.150mmIsonat0.17

    0.37

    9.0

    1.06

    1

    2

    Rafter Depth 150mm

    PAVAROOF pitched

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    9/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Specification PAVAROOF pitched

    9

    Isolair/ Pavatherm Plus boards of (specifythickness) thickness should be supported byat least two rafters spaced at a maximum of(specify distance) mm at all times.

    Working from eaves to ridge lay PavatexIsolair/ Pavatherm Plus boards of (specifythickness) thickness over rafters in staggeredbond pattern with board tongue facing upslope and joints full engaged.

    Temporarily secure board with one (specifymake) fixing part no: (specify part no:) perrafter.

    Isolair boards should be cut using eitherPavatex knife edge jigsaw blades part noPAVZK, or by a wavy edge insulation knife orby circular saw with a fine toothed tungstencarbide tipped blade.

    For roof pitches >20 boards are laid dry - noglueing required (see image).

    For pitches of between 10 and 20 apply abead of Pavatex Isoroof glue part no PAVZGusing a Pavatex glue gun part no PAVZGG tothe upper face of each tongue before fittingnext board (see image).

    For pitches 20 - laid dry (no gluing required)

    10 to 20 - glued with Isolair glue

    PAVAROOF pitched

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    10/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Key Considerations PAVAROOF pitched for Designer &Installer

    10

    General: interstitial condensation.The PAVAROOF system must be installedonly by competent contractors. The Ventilation batten space:contractors must be provided with full and Sufficient air movement between ISOLAIR/complete technical illustration details for all PAVATHERM PLUS and the roof covering isareas of the system. Leave nothing to be required because of the breathable build up ofagreed on site. Plan board layout prior to the roof system. In accordance to BS ENcommenting installation to reduce wastage. 5250, for air-open outer coverings no specific

    provision for batten-space ventilation is

    System Guarantee: required but for tight outer coverings battenThe system can only be guaranteed if boards space ventilation should be provided. I.e.and accessories approved by NBT are used. openings to the batten space which areUse only fixings as per NBTs equivalent to a continuous slot 25mm wide inrecommendations or manufacturers the eaves and 5mm wide at the ridge andinstructions. PAVAROOF pitched has LANTAC 25mm counterbattens.approval and BBA certification 07/4448.

    Non Load Bearing:Weather Tightness: Be aware that ISOLAIR and PAVATHERMFor pitches over 20 boards are laid dry and PLUS boards are not load bearing. Only standno glueing of the boards is required. ISOLAIR on top of rafters during installation of theand PAVATHERM PLUS boards are boards.interlocking at all four sides providing weather

    tightness. Latex impregnation through the Maximal Rafter Center Distanceboards structure offers continued protection,the boards can withstand a 3 month exposureperiod without roof covering whilst continuingto protect the building (provided that all tapingwork is properly done and counterbattens areinstalled). On top of ISOLAIR or PAVATHERMPLUS no breather membrane is required.Note: If the design of the roof includes lots ofvalleys and roof lights, using a breathermembrane can be a cost effective option.Please ask NBT technical department.

    Air Tightness:

    An additional layer is required to provide goodair tightness. NBT recommends to install aservice void with an additional air tightnesspaper if installations are running under thefinished internal surface. Alternatively you candesign the plasterboard & skim as the airtightness layer if a service void is notrequired. Carefully design the air tightnesslayer at all openings, junctions andpenetrations.

    Vapour Control Layer:NBT systems are breathable build-ups and

    theres no need to install an internal vapourbarrier. Your air tightness layer works asvapour control layer, there is no risk for

    PAVAROOF pitched

    Board

    Isolair 22mm

    Isolair 35mm

    Isolair 60mm

    max. rafter

    centre distance

    0.85 m

    1.00 m

    1.10 m

    Board

    Pavatherm Plus

    60mm

    Pavatherm Plus

    80mm

    Pavatherm Plus

    100mm

    max. rafter

    centre distance0.79 m

    0.79 m

    0.79 m

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    11/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Fix first board with Locate end tongue The 35mm and by at least twotongue uppermost first then slide 60mm board can rafters and is fullyusing one fixing town onto lower sustain light foot fixed).per rafter (Final board. Fix with traffic betweenfixing occurs one fixing as step rafters (provided Stagger joints tothrough batten). one. great care is taken ensure that no

    and centers are no vertical joint nextgreater than to each other fall600mm and the within same rafter

    board is supported space.

    Fitting

    Damaged boards and butt edged jointsAny damaged areas and butt edged joints should be filled with Woodfibre offcuts - primed andtaped with Pavatex PAVATAPE to ensure the integrity of the layer and to prevent water ingress. (Seeusing PAVATAPE Section).

    Openings and penetrationsAll openings and penetrations should be primed and taped with Pavatex PAVATAPE to ensure theintegrity of the layer and to prevent water ingress. (See using PAVATAPE section).

    Expansion joints

    Expansion joints must be provided for section of more than 15m long. After all the roof boards havebeen fitted cut a 5mm wide groove through the board on the center line of a rafter. Seal over thegroove with Pavatex PAVATAPE to form a sealed air gap (see using PAVATAPE section).

    CuttingThe boards are easily cut with any of thefollowing tools:

    Pavatex Knife edge jigsaw blade, bayonetfitting to suit most makes of jigsaw, part no:PAVZK.

    Standard wave edge insulation knife.

    Circular saw, hand-held or bench mountedwith a fine, cross-cut, tungsten tippedblade.

    Safety goggles and dust mask must be wornduring cutting to protect the user from thesmall, non hazardous, dust particles.

    Installation Procedures PAVAROOF pitchedStep 1 - Fitting Boards >> Step 2 - Using Pavatape >> Step 3 - Fixing Counter Batten

    11

    Pavatex Jig Saw Blades

    PAVAROOF pitched

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    12/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Guidelines for use

    Only use PAVATAPE on dry, clean and dust-free Pavatex board

    Use after fitting boards and always BEFORE installing battens

    Two priming solutions are available dependent on weather conditions: For temperaturesbetween 5 - 10 degC usePAVZTP05solvent based else use PAVZTP5water-based

    Apply Pavatex PRIMER with a brush or roller onto the board and abutments and allow to dry:Water-based primer is temperature sensitive - drying time is between 30 and 60 minutes (@20degC ca 30min / @ 5 degC ca 60min). Drying time for solvent based is 20min.

    PAVATAPE should not be applied if the temperature is below 5 degC - Contact NBT forGuidance.

    Store Pavatex PAVATAPE rolls on a flat surface in a dry dust-free environment.

    Shelf life when stored at around 20 degC is unlimited for PAVATAPE. PRIMER needs to be usedwithin 12 month after manufacture.

    PAVATAPE is supplied on 15m rolls.

    PAVZTP5Water-based Primer is supplied in 5 Litre tins (coverage 20m/l 6 Rolls PAVATAPE per tin).

    PAVZTP05Solvent-based Primer is supplied in 0.5 Litre tins (coverage 30m/l 1 Roll PAVATAPE per tin).

    Installation Procedures PAVAROOF pitchedStep 1 - Fitting Boards >> Step 2 - Using Pavatape >> Step 3 - Fixing Counter Batten

    How to use

    When to use

    Valleys Ridges Chimneys and wallabutments**

    Vent Pipes** Rooflights**

    PAVATAPE selfadhesive butyl tape15m long x 150mmwide.

    Clean surface witha brush. SurfaceMUSTbe dry toensure adhesion.

    Apply PRIMER witha brush or a rollerand allow to dry.

    Roll out PAVATAPEand press downwith other hand.

    Avoid creases.

    Press PAVATAPEon firmly using ahard faceddecorators seamroller or similar.

    12

    4

    2

    31

    15cm

    53

    1

    2

    15cm

    A high quality breather membrane can be used over ridges instead of PAVATAPE if required - pleaseensure that the strop of membrane is placed centrally over the ridge to offer maximum weather

    protection - is pulled tight and is firmly secured under the counter batten.Note: If have roof design with many rooflights and valleys, the use of breather membrane on top ofthe woodfibre might be an optional solution to simplify sealing work.

    **for further advise ask NBT technical

    PAVAROOF pitched

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    13/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Guidelines for use

    Only use fixings as per NBTs recommendations or manufactures instructions

    Batten / rail system should applied AFTER taping / sealing the area

    Fix through the counter batten and ISOLAIR or PAVATHERM PLUS directly into the rafter

    Finally fix batten and tiles with conventional roofingtechniques

    Installation Procedures PAVAROOF pitchedStep 1 - Fitting Boards >> Step 2 - Using Pavatape >> Step 3 - Fixing Counter Batten

    13

    ISOLAIR 22mml Nails: 3.8 x 100mm corrosion resistant with 30x50mm counter battens (pre drill holes if necessary

    to avoid battens splitting)

    l Helifix: 90mm InSkew 600 fixings with 25x50mm counter battens. Refer to Helifix enquiry sheetfor fixing centres and application limits.

    l Screws: EJOT TKR 4.8 x 90mm with 25x50mm counter battens. Recommended embedment inthe timber is 40mm. Refer to EJOT for fixing centres and application limits.

    Roof Covering

    Lightweight

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    14/20

    Pitched Roof Solution

    www.natural-building.co.uk T 01844 338 338F 01844 338 525

    Helifix Ltd EJOT U.K. Limited21 Warple Way Hurricane CloseLondon Sherburn Enterprise Park

    W3 0RX Sherburn-in-ElmetEngland LeedsFreephone 0800 731 7732 LS25 6PBTel: 020 8735 5200 Tel: 01977 6870740Fax: 020 8735 5201 Fax: 01977 687041

    Web: www.ejot.co.uk

    PAVAROOF pitched

    ISOLAIR 60mm / PAVATHERM PLUS 60mml Nails: 6.0 x 180mm corrosion resistant with 40x60mm counter battens (pre drill holes to avoid

    battens splitting

    l Helifix: 120mm InSkew 600 fixings with 25x50mm counter battens. Refer to Helifix enquiry sheetfor fixing centres and application limits.

    l Screws: EJOT TKR 4.8 x 130mm with 25x50mm counter battens. Recommended embedment inthe timber is 40mm.

    Roof Covering

    Lightweight

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    15/20

    Title

    Drawing Number

    CAD File Name

    Drawn By Date

    Pavaroof pitched Eaves

    PRP003 Beat 02.02.2007

    PRP003 070202 Eaves

    he Hangar, Worminghall Road,akley, Buckinghamshire.P18 9UL

    el: 01844 338338ax: 01844 338525

    Pavatex ISOLAIR orPAVATHERM PLUS

    woodfibre insulation

    Air Tightness Layer

    Plasterboard

    Counter Batten(Ventilation)

    Tile Batten

    NBT Natural Insulation (Warmcell,Isonat, Sheepwool) between Rafters

    Service Void (optional)

    Eaves Ventilation

    Element (25mm)

    PAVATAPE Butyltape Sealing

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    16/20

    Title

    Drawing Number

    CAD File Name

    Drawn By Date

    Pavaroof pitched VergeUK

    PRP005 Beat 02.02.2007

    PRP005 070202 VergeUK

    he Hangar, Worminghall Road,akley, Buckinghamshire.P18 9UL

    el: 01844 338338ax: 01844 338525

    Pavatex ISOLAIR orPAVATHERM PLUS

    woodfibre insulation

    Air Tightness Layer

    Plasterboard

    Counter Batten

    (Ventilation)

    Tile Batten

    NBT Natural Insulation (Warmcell,Isonat, Sheepwool) between Rafters

    Compriband

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    17/20

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    18/20

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    19/20

  • 7/22/2019 NBT Pavatex Pavaroof Isolair Board (Pitched) - Technical Manual

    20/20

    Product Overview: Insulation

    ISOLAIR L sarking board

    PAVATEX wood fibre board for breathable

    roof & wall constructions

    Size: 770 x 2500 mm

    Cover area: 750 x 2480 mm

    Thicknesses: 22, 35 & 60 mm

    k-value/ D: 0.047 W/(mK)

    Density: 240 kg/m3

    PAVATEX DIFFUTHERM external wall insulation

    Wood fibre board for rendered external wall

    insulation

    Size: 790 x 1300 mm

    Reveal board: 600 x 1200 mm

    Thicknesses: 60, 80 & 100 mm

    k-value/ D: 0.044 W/(mK)

    Density: 180 kg/m3

    PAVATHERM-PLUS sarking board

    Composite wood board for roof & wall

    insulation

    Size: 780 x 1580 mm

    Thicknesses: 60, 80 & 100 mm

    k-value/ D: 0.044 W/(mK)

    Density: 180 kg/m3

    Compr. strenght: >70 kPa (at 10 % compression)

    PAVADENTRO internal wall insulation

    Innovative wood fibre insulation board for

    refurbishment

    Size: 600 x 1020 mm

    Cover area: 590 x 1010 mm

    Thicknesses: 60, 80 & 100 mm

    k-value/ D: 0.042 W/(mK)

    Density: 180 kg/m3

    PAVATHERM general purpose insulation board

    Universal wood fibre board for use in

    external & internal walls, floors & roofs

    Sizes: 600 x 1020 &

    1200 x 2050 mm

    Thicknesses: 20 -100 mm

    k-value /D: 0.038 W/(mK)

    Density: 140 kg/m3

    PAVABOARD load bearing insulation

    Wood fibre board for highly insulated floors

    that have to carry loads

    Size: 600 x 1020 mm

    Thicknesses: 40 & 60 mm

    k-value/ D: 0.046 W/(mK)

    Density: 210 kg/m3

    Compr. strenght: >150 kPa (at 10 % compression)

    PAVATHERM-FLOOR-NK wall & floor board

    Wood fibre board for insulating floors or

    internal walls with plaster

    Size: 600 x 1020 cm

    Thicknesses: 40 & 60 mm

    k-value /D: 0.044 W/(mK)

    Density: 180 kg/m3

    Compr. strenght: >70 kPa (at 10 % compr.ession)

    PAVATEX accessories

    NBT provides the full range of PAVATEX

    accessories & complementary products:

    PAVATAPE incl. waterbased/solvent primers

    (for junctions on walls & roofs)

    PAVATEX cutting blades & knives

    PAVATEX system glue (for sarking boards)

    etc.

    NBT Hemp Batts

    Flexible hemp insulation batts for loft, walls,

    floors & ceilings

    Size I: 385 x 1200 mm

    Size II: 575 x 1200 mm

    Thicknesses: 50, 75, 100 & 140*mm

    k-value /D: 0.040 W/(mK)Density: 40 kg/m3 *only size II

    NBT Warmcel 100 cellulose fibres

    Loose fill derived from waste UK newsprint

    treated with fire retardant and biocidal

    additives

    Packaging: Bags of 8 kg (compressed)

    Cover area: e.g. 1 m2at 228 mm

    k-value/ D: 0.035 W/(mK)Density: 35 kg/m3

    ISOLAIR L, all PAVATHERM products, PAVATEX DIFFUTHERM & NBT Hemp Batts are cer tified by natureplus. This testifies to excellent natural & ecological compatability.

    PAVATEX wood fibre insulation boards are manufactured in Switzerland according to BS EN 13171, have the CE marking and are monitored by 3rdparties.

    NBT Hemp Batts are manufactured in Poland according to ETA-06/0040 Z-23.16-1598, have the CE marking & are monitored by 3rdparties.

    NBT Warmcel 100 is manufactured in the UK according to prEN 15101 & has the CE marking.

    The following applies to all PAVATEX products: Specific heat capacity c = 2100 kJ/(kgK), Euroclass E (according to BS EN 13501-1), vapour resistivity = 5 (25 MNs/gm)

    The following applies to NBT Hemp Batts: Specific heat capacity c = 1700 kJ/(kgK), Euroclass D-s3,d0 (according to BS EN 13501-1), vapour resistivity = 2 (10 MNs/gm)

    The following applies to NBT Warmcell 100: Specific heat capacity c = 1700 kJ/kgK), Euroclass E (according to BS EN 13501-1), vapour resistivity = 1.86 (9.3 MNs/gm)

    oalterationdueto

    developement

    O

    Natural Building Technologies Ltd.

    The Hangar, Worminghall Road

    Oakley, Bucks, HP18 9UL

    Tel: +44 (0)1844 338338

    F 44 (0)1844 338525

    Your business development manager is happy to give

    professional advice:

    CERTIFICATE No 07/4448