NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 NCSX Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22 2008 CONTRIBUTORS M. CROPPER, R. HATCHER, R. MARSALA, S. RAMAKRISHNAN

Upload: emily-anthony

Post on 11-Jan-2016

220 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 1

NCSX

Electrical Power Systems (WBS 4)

NCSX PWR SystemPROTECTION – REVIEW

February 22 2008CONTRIBUTORS

M. CROPPER, R. HATCHER, R. MARSALA, S. RAMAKRISHNAN

Page 2: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 2

NCSXElectrical Power System

OVERVIEW

• Provide Source of all Electric Power for NCSX– All AC Power

• At all Distribution Voltage levels» 4.16kV,480V, 208/120V» Includes Experimental AC Power» Includes AC Power to NB» Includes all Auxiliary AC Power up to Power Panels

– All DC Experimental Power• Provide DC power for stellarator coil systems

– 2 Modular, and 3 PF coil circuits» PS requirements based on Initial Ohmic Scenario» Clear path for future upgrades (other scenarios,

flexibility)

• Provide Diagnostics support for Sensor cabling• Grounding

Page 3: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 3

NCSX

• AC SYSTEM - USE EXISTING C- SITE SYSTEM WITH NEW 480/120 SYSTEM FOR TEST CELL

• ESAT RECTIFIERS - USE EXISTING – 6 ROBICONS/ 1 PEI - RECONFIGURE

• - ASSIGN FOR NCSX LOADS AS NEEDED

• SDS - USE EXISTING UNITS IN TEST CELL BASEMENT WITH CHANGES REQUIRED

- NEW PWR CABLING FROM SDS TO COILS

• HCS - PURCHASE AND INSTALL PLC. - NEW CABLING AS NEEDED

• MEASUREMENTS - USE SHUNTS IN PWR SUPPLIES - USE NEW FIBER OPTIC

TRANSMITTERS

• CONTROLS - PLC , CABLING AS IS & MODIFIED• PROTECTION - USE EXISTING WITH CHANGES &

ADDITIONS- NEW CABLING AS NEEDED

• KIRKEYS - USE EXISTING WITH CHANGES

OVERVIEW CONTD.

Page 4: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 4

NCSX

PPPL Site Plan

NCSX C-Site Location

NCSX Control Room Location

C- Site Power Supplies

Page 5: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 5

NCSXC-Site Power Supplies

• C-site Rectifier power supplies used for Coil circuits

– Six (6) Robicon Rectifier Supplies. Each of (2) 6-pulse, 2-quadrant converters in parallel - 12-pulse rectified DC output.

– One (1) PEI Rectifier Supply. Two 6-pulse rectifier bridges in parallel - 12-pulse DC output

• Sufficient power available for First Phase

• Future upgrades with D-Site Supplies • Ron Hatcher has tested (Dummy Load) the C-Site

supplies

Page 6: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 6

NCSXPower Supplies Assignment

1st plasma & Magnetic Configuration

Circuit Power SupplyCurrent

1.5s / 180sVolts Peak MW

M1 P10 10kA 200V 2

M2 + M3 P5-1 & 4 (parallel) 10kA 300V 3

PF4 P5-2 in series with PEI 5kA 800V 4

PF6P5-3 5kA 300V 1.5

PF1a P20 20kA 500V 10

Page 7: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 7

NCSXTypical Circuit Arrangement Contd.

• Disconnect and grounding switches provided for each circuit

• Some of Existing cables used from Rectifier Supplies to Disconnects in Test Cell Basement

• New Cables (4/c- 500mcm, 600V) from Disconnects to the Bus Stubs in the Tunnel/ Coil Terminals

• Current/ Voltage transducers provided• Changeover to CDX possible by LINKS at top of

Disconnects.

Page 8: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 8

NCSX PS Control and Coil Protection

GENERAL

PS Control PLC will be provided for Controls (Mark Cropper)

– Modern PLC based system– Additional interlocks as needed– Some protective features included

PROTECTION Coil / Pwr. Loop protection provided (R. Marsala)

• Overcurrent (Built-in the Pwr. Supplies)• Ground fault (new)• Pulse duration & period (PDP) limit (new)

Page 9: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 9

NCSX

COILS WILL USE built-in protection in C-Site Rectifiers enhanced by additional features.

PROTECTION LEVEL FOR PERSONNEL SAFETY SAME AS TFTR /NSTX.

KIRK- KEY LOCKS WILL ALSO BE PROVIDED AS NEEDED. ALL THESE WILL BE ENHANCED WITH ADMINISTRATIVE CONTROLS. MACHINE COILS BEING FED FROM C-SITE POWER SUPPLIES

OF LIMITED CAPABILITY AS COMPAREDTO COIL RATINGS. BUILT-IN PROTECTION IN POWER SUPPLIES ARE ADEQUATE. EVEN SO, THESE ARE AUGUMENTED THROUGH ADDITIONAL FEATURES

GROUND FAULT DETECTION AND PROTECTION WILL BE PROVIDED

NCSX - PROTECTION

Page 10: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 10

NCSXNCSX - PROTECTION

A. C-Site Rectifiers Protective Features:• 1. Cooling water flow loss• 2. SCR Over-temperature • 3. SCR Junction temperature high• 4. Conversion transformers Primary Instantaneous Over-current• 5. Conversion Transformers Over-temperature• 6. Rectifier door interlock to trip contactor in case door is opened.• 7. Over/under AC Voltage conditions• 8. DC OUTPUT OVERCURRENT• 9. DC OUTPUT OVERVOLTAGE• 10. MOVs & CR SNUBBERS TO SUPPRESS OVERVOLTAGE The settings of the currents in these units will be such that the coils

will not be overloaded.

Page 11: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 11

NCSX• B. Additional Coil Protection based on PLC logic

• 1. Power Supply Arm permissive: • 1.1 Power supply enable command must be high• 1.2 Power supply must be enabled (contactor limit switch feed back)• 1.3 No thermal trip on corresponding coil.• 1.4 Corresponding disconnect switch ready permissive• 1.5 Corresponding disconnect closed• 1.6 Computer arm command high ( the computer arm command is issued TBD seconds

before the shot and removed TBD seconds after the shot. This can be bypassed by the operator)

• 1.7 Remote interlock – Coil temperature normal for start

Page 12: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 12

NCSX

• 2. Power Supply Enable permissive: (COMMON TO TRIP ALL POWER SUPPLIES) - any one of these failures will trip all supplies)

• a) Pulse duration - Trip Power Supplies (PS) if there is presence of COIL current at a level (adjustable) for more than an adjustable duration of time. This is established by looking at the current.

• b) Pulse interval - Trip the power supplies if more than one pulse is imposed before an adjustable waiting period.).This is also established by looking at the current.

• Also failure of the following will remove the Power Supply Enable Permissive- thus trip the power supplies.

• c) PLC running- not faulted• d) Coil Cooling OK• e) All Power supplies in remote mode• f) Test Cell door interlock closed• g) RSView computer online (Programming/Operating computer for

AB PLCs)• h) No E-stop

•Additional Coil Protection based on PLC logic Contd.

Page 13: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 13

NCSX

• 3. PLC Power Supply Enable permissive: (INDIVIDUAL TRIP TO AFFECTED POWER SUPPLY) -these trips will only trip the affected supply)

• a) Summed permissive from Power supply• b) No ground fault on power supply cable• c) 4160 KV breaker closed• d) No thermal trip on coil (this will prevent enabling but will not trip the

supply once it is enabled)• C. Pulse Duration & Period Timer.• 1. Pulse duration (If the pulse duration is more than an

adjustable setting, the permissive to the supplies will be removed). This is based on a Start of Pulse (SOP) command received, and WITHOUT looking at the current.

• 2. Pulse interval (If the pulse INTERVAL is more than an adjustable setting, the permissive to the supplies will be removed). This is based on a Start of Pulse (SOP) command received, and WITHOUT looking at the current.

• D. Ground Fault Protection: Coil Ground fault detection and protection will be provided for all circuits. One common Ground Fault relay will be used.

Page 14: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 14

NCSXPROTECTION FOR UPGRADE

WILL USE D- SITE RECTIFIERS & ASSOCIATED BUILT-IN PROTECTION NEW ANALOG COIL PROTECTION DEVICE (ACP) WILL BE DESIGNED &

INSTALLED FOR EACH CIRCUITThe ACP will Invoke Level 1 On Coil Overcurrent If there is presence of current at a level 0 to 10%(adjustable) of the full

scale (i.e. 0 to TBD A) for > an adjustable duration of time in increments of 0.1 second (0.1 to 99.9 seconds) shall trip the Power Supplies.

If more than one pulse is imposed before an adjustable waiting period of 1 to 999 seconds in one second increments.

If the (I^2)*t is more than TBD Simulate coil cooling using a single exponential decay adjustable from

TBD seconds to TBD seconds.– ACP Design: – a). Two ACPs one redundant to the other - assemblies in Rack in D-

Site– b) The ACP design to be standardized. Signal from DCCTs brought to

signal Conditioner. Output from the signal conditioner will be fed as the input signal to the PCB of each circuit/coil or if summing in required, to a summing module before being fed to PCB for that circuit. Appropriate testing features to be installed in chassis.

Page 15: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 15

NCSX

• B. Pulse Duration & Period Timer.• New Pulse Duration and Period to be installed in D-Site. This timer will give

permissive over an adjustable window of time (adjustable in one second increments from TBD to TBD seconds) when a Start of Pulse (SOP command is received). The timer will also prevent any additional pulsing for an adjustable 600 to 900 seconds even if more SOP command is received within that time.

• C. Coil Protection Calculator(CPC).• If considered necessary a CPC will be designed and installed.• D. Coil temperature signal at start of pulse.:• The signals to be received from the C-Site shall include the final signal

from the PLC which will compute the resistance of the modular coils. • However potential leads (#16 insulated wires) from the machine modular

coil terminals shall be brought out as part of MIE project, to enable resistance measurement. IT IS SUGGESTED THAT WE MAY BRING OUT THE MODULAR COIL LEADS FROM ONE COIL ONLY FROM EACH PERIOD AND BELONGING TO DIFFERENT GROUP I.E MA , MB, AND MC. LEADS FROM OTHER COILS IF REQUIRED CAN BE TAKEN AFTER THE COLD/HOT BOX (this will thus include the coil leads and hence will not be the coil only).

• Additional Interlocks as needed from C-Site will be introduced.

Page 16: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 16

NCSXFROM CONV. TRANSFRS.

LEFT CONV. CLG. WTR. FLOW LOSS

LEFT SCR OVERTEMP.

SCT JCT. TEMP. HIGH

RIGHT SCR OVERTEMP.

RIGHT CONV. CLG. WTR. FLOW LOSS

RECT. DOOR OPEN

TO RECTIFIERS - SEE ABOVE RIGHT

HIGH/LOW LINE PHASE LOSS

Tfmr. over-temp

Tfmr.over-temp

PRIMARY OVER CURRENT

DC OVER VOLTAGE

PS ENABLE COMMAND MUST BE HIGH

PS ENABLED

COIL - NO THERMAL TRIP

PS ARM PERMISSIVE

DISC SW. READY & CLOSED

COMPUTER ARM COMMAND HIGH

COIL TEMP. NORMAL FOR START

PS ENABLE PERMISSIVE (TRIP ALL PS)PULSE DURATION > TBD SECS.

PULSE PERIOD (INTERVAL) > TBD SECS.

PLC NOT FAULTEDCOIL COOLING SYSTEM OKALL PS IN REMOTE MODETEST CELL DOOR INTERLOCK OK

RSView COMPUTER ONLINENO E-STOP

PS ENABLE PERMISSIVE (TRIP affected PS)SUMMED PERMISSIVE FROM PS OK

NO GRD. FAULT ON PS

4.16 kV Bkr. CLOSED

Timed window for pulsing on receipt of SOP

PDP TIMER

LOAD OC

(I^2)(t) dtThermal Simulation

COMPARISON

COMPUTER

MISCTEMP ETC.

CONTROLS

PLC

SDS

GRDFLT

STATUS

DC OVER CURRENT

DISABLE PS & TRIP ACOTHERS - INVERT & TRIP AC

PROTECTION(Coils supplied by Robicons)

Page 17: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 17

NCSXCoil Resistance Measuring Scheme

• A constant current power supply will be provided to measure the coil resistance. This Resistance Test Power Supply (RPS) will be connected AT THE Disconnect switch in the C-Site Basement, directly across the input from the supply feeding the coil. Thus the RPS will be connected directly across this power supply. During pulsing the supply will be kept disconnected by a contactor. See Sketch 2 for details. Also resistances R1 & R2 (Values TBD) are connected as shown.

• The RPS current and the Coil voltages will be fed into a Resistance Measuring Device (RMD). The RMD is yet to be designed or this function will be incorporated in the PLC itself. The output from the RMD will be sent to PLC as needed. The PLC will give permissive to the Power Supplies only if the value is normal for the start of the pulse. For MA coils the value is about 1.1 milliohms.

• We could keep the current control of the RPS at 50 Amps always (Current controlled), in which case the RMD will be just a voltage measuring device. The trip level can be either set at the PLC or designed and built into the RMD

Page 18: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 18

NCSXMA-1 -+ M

A-1

S

MA

-1F

MA-2 -+ MA

-2S

MA

-2F

MA-3 -+ MA

-3S

MA

-3F

MA-4 -+ MA

-4S

MA

-4F

MA-5 -+ MA

-5S

MA

-5F

MA-6 -+ MA

-6S

MA

-6F

MA

-1SP

MA

-1FP

MA

-2SP

MA

-2FP

MA

-3SP

MA

-3FP

MA

-4SP

MA

-4FP

MA

-5SP

MA

-5FP

MA

-6SP

MA

-6FP

B-MA-1

NOTES:1. MA-1 through 6 are the six modular coils of the A group2. "S" indicates the start of the coil i.e. MA-1S is "Start" of MA-1 coil. Similarly "F" indicates the "Finish" of the Coil.3. "P" indicates the potential lead of the coil i.e. MA-1SP is the lead to measure the potential of the coil lead MA-1Scoil.. The potential leads shall be brought to central terminal box to enable measuring resistances.4. Each coil lead shall be painted "RED" or BLACK". Red is for positive terminal and Black for the Negative terminal

Coil Resistance Measuring Scheme

Page 19: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 19

NCSX

O

O

Coil Resistance Measuring Scheme

Page 20: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 20

NCSXPOWER SYSTEM BLOCK DIAGRAM

Page 21: NCSX NCSX PWR.System PROTECTION REVIEW 02/22/08 S. Ramakrishnan Slide 1 Electrical Power Systems (WBS 4) NCSX PWR System PROTECTION – REVIEW February 22

NCSX PWR.SystemPROTECTION REVIEW02/22/08

S. RamakrishnanSlide 21

NCSX