nds1.826 - page 1 / 2 technical information sheet

2
NDS1.826 - Page 1 / 2 Technical Information Sheet SCB1-3-25 Surge Circuit Breaker The SCB1-3-25 is a purpose designed SPD disconnector. It may be used to provide over current protection for any shunt connected SPD with an Imax rating up to 200kA or an Iimp rating to 25kA. The SCB1-3-25 is generally used at main switchboards. It effectively coordinates with any upstream supply circuit breaker or fuse. Operation. All power line SPDs must be protected by an over current protective device (OCPD). Traditionally these have been fuses or circuit breakers but neither are really suitable to effectively protect the SPD in the event of its failure or in the event of a prolonged system overvoltage. Under normal operating conditions an SPD draws no more than a few milliamps of AC current from the supply but in the event of a transient disturbance it must instantly pass many thousands of amps. Fuses or circuit breakers chosen to pass this impulse current will not protect the SPD against an AC overvoltage nor necessarily prevent its failure to a short circuit before the fuse or circuit breaker trips. The fuses or circuit breaker ratings required to pass these impulse currents present coordination challenges with upstream OCPDs. The SCB1-3-25 is designed to trip at AC currents more than 3 amps but will pass impulse currents up to 25kA 10/350us. Tests have proven that the SCB will trip during a phase to phase voltage fault across a phase to neutral SPD with no damage to the SPD. The SCB may simply be reset. With a trip current of only 3A the SCB easily coordinates with upstream OCPDs. Novaris SPDs uniquely utilize electronic alarms and can detect the loss of supply due to tripping of the SCB. Compatibility. The SCB1-3-25 can be used with all Novaris SD, SDN and SDEV products designed for LV distribution up to 200kA 8/20us rating and for SG products up to 25kA 10/350us. Wiring Dimensions Standards IEC61643-11 low voltage surge protection devices- requirements and tests IEC61643-11 IEC60898-1 Electrical accessories – circuit breakers for overcurrent protection IEC60898-1 72 Browns Road, Kingston Tasmania 7050 Australia +61 3 6229 7233 [email protected] www.novaris.com.au

Upload: others

Post on 18-Dec-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

NDS1.826 - Page 1 / 2Technical Information Sheet

SCB1-3-25

Surge Circuit BreakerThe SCB1-3-25 is a purpose designed SPD disconnector. It may be used toprovide over current protection for any shunt connected SPD with an Imaxrating up to 200kA or an Iimp rating to 25kA. The SCB1-3-25 is generallyused at main switchboards. It effectively coordinates with any upstreamsupply circuit breaker or fuse.

Operation. All power line SPDs must be protected by an over currentprotective device (OCPD). Traditionally these have been fuses or circuitbreakers but neither are really suitable to effectively protect the SPD in theevent of its failure or in the event of a prolonged system overvoltage. Undernormal operating conditions an SPD draws no more than a few milliamps ofAC current from the supply but in the event of a transient disturbance itmust instantly pass many thousands of amps. Fuses or circuit breakerschosen to pass this impulse current will not protect the SPD against an ACovervoltage nor necessarily prevent its failure to a short circuit before thefuse or circuit breaker trips. The fuses or circuit breaker ratings required topass these impulse currents present coordination challenges withupstream OCPDs. The SCB1-3-25 is designed to trip at AC currents morethan 3 amps but will pass impulse currents up to 25kA 10/350us. Testshave proven that the SCB will trip during a phase to phase voltage faultacross a phase to neutral SPD with no damage to the SPD. The SCB maysimply be reset. With a trip current of only 3A the SCB easily coordinateswith upstream OCPDs. Novaris SPDs uniquely utilize electronic alarms andcan detect the loss of supply due to tripping of the SCB.

Compatibility. The SCB1-3-25 can be used with all Novaris SD, SDN andSDEV products designed for LV distribution up to 200kA 8/20us rating andfor SG products up to 25kA 10/350us.

Wiring Dimensions

StandardsIEC61643-11 low voltage surge protection devices- requirements and tests IEC61643-11IEC60898-1 Electrical accessories – circuit breakers for overcurrent protection IEC60898-1

72 Browns Road, Kingston Tasmania 7050 Australia +61 3 6229 7233 [email protected] www.novaris.com.au

NDS1.826 - Page 2 / 2Technical Information Sheet

Speci�cations

Electrical Speci�cationsRated operating voltage 230VACRated insulation voltage 400VACImpulse current withstanding (10/350 μs) 25kATripping value under power frequency current 3±1ARated service short-circuit breaking capacity 50kAThe breaking time of short-circuit power frequency current <40msMechanical life & Electrical life 1000 times

Mechanical Speci�cationsMinimum operating temperature g -25°C

Maximum operating temperature h 60°C

Minimum operating humidity k 5%

Maximum operating humidity j 95%

Mounting method a TS35 DIN Rail

Environmental rating f IP20

Enclosure material s Polycarbonate

Enclosure �nish d Green

Terminal capacity minimum i 2.5mm²

Terminal capacity maximum i 25mm²

Length l 81mm

Width ; 35mm

Height z 65mm

Other Speci�cationsProduct Code x SCB1-3-25

Shipping Speci�cationsWeight v 204g

72 Browns Road, Kingston Tasmania 7050 Australia +61 3 6229 7233 [email protected] www.novaris.com.au