netsure 2100 a31-s1 subrack power system user manual ·  · 2017-03-15when operating vertiv...

29
NetSure 2100 A31-S1 Subrack Power System User Manual Version V1.1 Revision date December 31, 2017 BOM 31013614 Vertiv provides customers with technical support. Users may contact the nearest Vertiv local sales office or service center. Copyright © 2017 by Vertiv Tech Co., Ltd. All rights reserved. The contents in this document are subject to change without notice. Vertiv Tech Co., Ltd. Address: Block B2, Nanshan I Park, No.1001 Xueyuan Road, Nanshan District, Shenzhen, 518055, P.R. China Homepage: www.VertivCo.com E-mail: [email protected]

Upload: nguyenkhanh

Post on 01-May-2018

368 views

Category:

Documents


32 download

TRANSCRIPT

Page 1: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

NetSure 2100 A31-S1 Subrack Power System

User Manual

Version V1.1

Revision date December 31, 2017

BOM 31013614

Vertiv provides customers with technical support. Users may contact the nearest Vertiv local sales office

or service center.

Copyright © 2017 by Vertiv Tech Co., Ltd.

All rights reserved. The contents in this document are subject to change without notice.

Vertiv Tech Co., Ltd.

Address: Block B2, Nanshan I Park, No.1001 Xueyuan Road, Nanshan District, Shenzhen, 518055, P.R.

China

Homepage: www.VertivCo.com

E-mail: [email protected]

Page 2: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Safety Precautions

To reduce the chance of accident, please read the safety precautions carefully before operation. The ‘Caution,

Notice, Warning, Danger’ in this book do not represent all the safety points to be observed, and are only

supplement to various safety points. Therefore, the installation and operation personnel must be strictly trained

and master the correct operations and all the safety points before operation.

When operating Vertiv products, you must strictly observe the safety rules in the industry, the general safety

points and special safety instructions specified in this book.

Electrical Safety

I. Hazardous voltage

Danger Danger

Some components of the power system carry hazardous voltage in operation. Direct contact or indirect contact through

moist objects with these components will result in fatal injury.

Observe safety rules in the industry when installing the AC power system. The installation personnel must be

licensed to operate high voltage and AC power.

In operation, the installation personnel are not allowed to wear conductive objects such as watches, bracelets,

bangles or rings.

When you find water or moisture is on the cabinet, then turn off the power immediately. In moist environment,

precautions must be taken to keep moisture out of the cabinet.

‘Prohibit’ warning label must be attached to the switches and buttons that are not permitted to operate during

installation.

Danger Danger

High voltage operation may cause a fire and an electric shock. The connection and wiring of AC cables must be in

compliance with the local rules and regulations. Only those who are licensed to operate high voltage and AC power can

perform high voltage operations.

Danger Danger

To avoid electric shock hazard of outdoor environment and outdoor equipment, the non-professionals are prohibited to

operate or maintain the power system.

III. Tools

Warning

In high voltage and AC operation, special tools must be used. No common or self-carried tools should be used.

Page 3: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

IV. Thunderstorm

Danger Danger

Never operate on high voltage, AC, iron tower or mast in the thunderstorm.

In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be

well earthed in time to avoid damage by lightning strikes.

V. ESD

Note

The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale

ICs. Before touching any plug-in board, PCB or IC chip, you must wear ESD wrist strap to prevent body static from

damaging the sensitive components. The other end of the ESD wrist strap must be well earthed.

VI. Short circuit

Danger Danger

During operation, never short the positive and negative poles of the DC distribution unit of the system or the non-grounding

pole and the earth. The power system is constant voltage DC power equipment, and short circuit will result in equipment

burning and endanger human safety.

VII. Reverse connection

Warning

Never reverse-connect live line and neutral line of the AC input cables, or else the system will be damaged.

VIII. Dangerous energy

Warning

The power system contains output exceeds 240VA, dangerous energy, must be far away and can not be bridged.

Check carefully the polarity of the cable and connection terminal when performing DC live operations.

The conductive part of the DC output and signal port (including the dry contact) can not be touched when the

system is with live power, especially in thunderstorms or wet weather, otherwise there will be an electric shock

hazard.

As the operation space in the DC distribution unit is tight, please carefully select the operation space.

Never wear a watch, bracelet, bangle, ring, or other conductive objects during operation.

Insulated tools must be used.

In live operation, keep the arm muscle tense, so that when tool connection is loosened, the free movement of the

human body and the tool is reduced to a minimum.

Page 4: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Battery

Danger Danger

Before working on the battery, read very carefully the safety precautions for battery transportation and the correct battery

connection method.

Warning

If the battery is configured by customer, the battery installation and maintenance must comply with the appropriate safety

standards.

Non-standard operation on the battery will result in danger. In operation, pay close attention to prevent battery

short circuit and spill of the electrolyte.

For safety reasons, before working on the battery, pay attention to the following points:

Remove the watch, bracelet, bangle, ring, and other metal objects.

Use insulated tools.

Wear eye protection and take preventive measures.

Wear rubber gloves and apron to guard against spilt electrolyte.

In battery transportation, the electrode of the battery should always be kept facing upward. Never put the

battery upside down or slanted.

Others

I. Sharp object

Warning

When moving equipment by hand, protective gloves should be worn to avoid injury by sharp object.

II. Power cable

Warning Notice

Note

Please verify the compliance of the cable and cable label with the actual installation prior to cable connection.

III. Binding the signal lines

Warning Notice

Note

The signal lines should be bound separately from power cables, with binding interval of at least 150mm.

IV. Subrack power supply

Warning

It is strictly forbidden to stand or place objects on the equipment body and accessories.

Page 5: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Contents

Chapter 1 Overview ............................................................................................................................................................ 1

1.1 Model Description ................................................................................................................................................. 1

1.2 Composition And Configuration ............................................................................................................................ 1

1.3 Operating Theory .................................................................................................................................................. 2

1.4 Features ................................................................................................................................................................ 2

Chapter 2 Installation .......................................................................................................................................................... 3

2.1 Safety Regulations ................................................................................................................................................ 3

2.2 Preparation ........................................................................................................................................................... 3

2.3 Mechanical Installation .......................................................................................................................................... 4

2.4 Electrical Installation ............................................................................................................................................. 5

2.4.1 Connecting Power Cable ........................................................................................................................... 5

2.4.2 Connecting Battery Cable .......................................................................................................................... 6

2.4.3 Connecting Communication Cable ............................................................................................................ 6

2.4.4 Connecting Temperature Compensation Cable ......................................................................................... 7

2.5 Installation Check .................................................................................................................................................. 7

Chapter 3 Testing ................................................................................................................................................................ 8

3.1 Startup .................................................................................................................................................................. 8

3.2 Basic Settings ....................................................................................................................................................... 8

3.3 Alarm Check And System Operation Status Check .............................................................................................. 9

3.4 Final Steps ............................................................................................................................................................ 9

Chapter 4 Use Of Controller .............................................................................................................................................. 10

4.1 Operation Panel .................................................................................................................................................. 10

4.2 Main LCD Screens .............................................................................................................................................. 10

4.2.1 System Information Screen ..................................................................................................................... 10

4.2.2 Password Confirmation Screen ............................................................................................................... 11

4.2.3 MAINMENU Screen ................................................................................................................................. 11

4.3 Querying System Main Information ..................................................................................................................... 12

4.3.1 Querying Active Alarm ............................................................................................................................. 12

4.3.2 Querying Historical Alarm ........................................................................................................................ 12

4.3.3 Querying Rectifier Information ................................................................................................................. 12

4.4 Setting System Parameters ................................................................................................................................ 13

Chapter 5 Maintenance ..................................................................................................................................................... 14

5.1 Routine Maintenance .......................................................................................................................................... 14

5.2 Handling Alarms And Fault ................................................................................................................................. 14

5.2.1 Handling Controller Alarms ...................................................................................................................... 14

5.2.2 Handling Rectifier Fault ........................................................................................................................... 16

5.3 Replacing Parts................................................................................................................................................... 17

5.3.1 Replacing Rectifier .................................................................................................................................. 17

5.3.2 Replacing Controller ................................................................................................................................ 17

5.3.3 Replacing Logic Board............................................................................................................................. 18

Page 6: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Appendix 1 Technical Data ............................................................................................................................................... 19

Appendix 2 Menu Structure Of The Controller .................................................................................................................. 21

Appendix 3 Schematic Diagram ........................................................................................................................................ 22

Appendix 4 Wiring Diagram ............................................................................................................................................... 23

Page 7: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Chapter 1 Overview 1

NetSure 2100 A31-S1 Subrack Power System User Manual

Chapter 1 Overview

The NetSure 2100 A31-S1 subrack power system (power system for short) can be directly used in corridor and other

semi-enclosed environment. It supports 19'' rack and wall-mounting installation, and can supply as much as 2kW

power.

This chapter introduces the model description, composition and configuration, operating theory and features of the

power system.

1.1 Model Description

The model description of the power system is given in Figure 1-1.

NetSure 2 1 0 0 A

Configuration version: 1

Region: Asia-Pacific

Rectifier power: 1000W

Brand name of the power system

1

Max. rectifier number: 3 pieces

S

Platform series: 1

System form feature. S: subrak power supply

3 1 -

System version: 1

Reserved: 0

Reserved: 0

Figure 1-1 Model description

1.2 Composition And Configuration

Composition

The power system is composed of rectifiers, a controller and a power distribution unit. The structure of the power

system is shown in Figure 1-2.

Rectifier Controller Power distribution unit

Figure 1-2 Structure of the power system

Configuration

The configuration of the power system is given in Table 1-1.

Table 1-1 Configuration list

Component Configuration

Controller M225S 1 piece

Rectifier R48-1000e3 Standard configuration: 2 pieces

AC distribution L + N + PE/220Vac 1 × 30A; quick-plug terminal

DC distribution

Priority load (PL):

1 × 20A/1P; MCB 1 × 30A; quick-plug terminal

2 × 10A/1P; MCB 2 × 30A; quick-plug terminal

Battery MCB 1 × 30A/1P; MCB 1 × 30A; quick-plug terminal

Note:

Optional configuration: temperature sensor cable

Page 8: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

2 Chapter 1 Overview

NetSure 2100 A31-S1 Subrack Power System User Manual

1.3 Operating Theory

Electrical theory

The schematic diagram of the power system is shown in Figure 1-3.

AC

distribution

220VacDC

distribution

220Vac - 48Vdc

Thermal

control unit

Rectifier

Load

Controller

Figure 1-3 Schematic diagram

The AC distribution unit introduces the AC power and feeds to the rectifier, which converts the 220Vac into -48Vdc and

delivers it to the AC distribution unit, through which the -48Vdc power is outputted to each load.

The controller has functions of battery management, LLVD, BLVD, data acquisition and alarm, and it can communicate

with the host.

Heat dissipation theory

The power system uses natural cooling to dissipate heat.

1.4 Features

Rectifier

Power factor up to 0.99, efficiency over 94.5%.

Wide AC input voltage ranges from 85Vac to 300Vac. When the input voltage is between 85Vac and 175Vac, the

rectifier will derate the output power.

High module power density.

Hot pluggable. It takes less than one minute to replace a rectifier.

Two over-voltage protection methods are optional: hardware protection and software protection. The latter one

also has two optional modes: lock out at the first over-voltage and lock out at the second over-voltage.

System

Perfect battery management. The system has BLVD function, and can perform functions such as temperature

compensation, automatic voltage regulation, stepless current limiting, battery capacity calculation, and online

battery test.

Network design. Providing multiple communication ports, which enable remote monitoring and unattended

operation.

Up to 200 pieces of historical alarm records can be recorded by M225S controller.

Complete fault protection and fault alarm functions.

Safety guideline: IP20

Application of rectifier module dormancy technology, which enhances the energy saving function of the system.

High system efficiency: above 93.5%.

Page 9: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Chapter 2 Installation 3

NetSure 2100 A31-S1 Subrack Power System User Manual

Chapter 2 Installation

This chapter introduces the installation and cable connection of the power system. Before installation, please read

through the safety regulations, and then follow the instructions in this chapter to carry out the installation and cable

connection.

2.1 Safety Regulations

Certain components in the power system carry hazardous voltage and current. Always follow the instructions below:

1. Only trained personnel with adequate knowledge of the power system shall carry out the installation. The Safety

Precautions listed before the Contents of this manual and local safety rules in force shall be adhered to during the

installation.

2. All external circuits below -48V connected to the power system must comply with the SELV requirements defined in

IEC 60950.

3. Do not operate or maintain the power system under thunderstorm or humid weather!

4. Make sure that the power system is powered off before any operation carried out within the system.

5. The power cables should be routed and protected properly, so that the cables are kept away from the operation and

maintenance personnel.

2.2 Preparation

Unpacking inspection

The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done

by representatives of both the user and Vertiv Tech Co., Ltd..

To inspect the equipment, you should open the packing case, take out the packing list and check against the packing

list that the equipment is correct and complete. Make sure that the equipment is delivered intact.

Note

The rectifiers have been installed in the subrack power system at factory.

Preparing cables

The cable should be selected in accordance with relevant electric industry standards.

It is recommended to use the RVVZ cables as AC cables. The cables should reach at least +70°C temperature

durability.

Select the AC cable CSA according to Table 2-1.

Table 2-1 Selection of AC cable CSA

Connector Specification AC cable CSA

AC input terminal 1 × 30A quick-plug terminal ≤ 10mm2

Note: With cable shorter than 30m, the CSA calculation should be based on the current density of 2.5A/mm2. The recommended

CSA value is not less than 2.5mm2

The DC cable CSA depends on the current flowing through the cable, the allowable voltage drop and the load peak

capacity. The recommended load peak capacity is 1/2 to 2/3 of MCB capacity.

Page 10: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

4 Chapter 2 Installation

SiteWeb2 Graphic Configuration Tool Operation Manual

Select the battery cable CSA according to Table 2-2 and load cable CSA according to Table 2-3.

Table 2-2 Battery cable CSA selection

Battery MCB

rated current

Max. battery

current

Min. cable

CSA

Max. cable length (volt

drop: 0.5V)

Max. cable

CSA

Max. cable length (volt drop:

0.5V, with max. CSA)

Note:

1. The specification is applicable at ambient temperature of 40°C. If the temperature is higher, the CSA should be increased.

2. The battery cable should reach at least +90°C heat durability. It is recommended to use double-insulated copper-core flame

retardant cable as battery cable

Table 2-3 Load cable CSA selection

Load route

rated current

Max. output

current

Min. cable

CSA

Max. cable length (volt

drop: 0.5V, with min. CSA)

Max. cable

CSA

Max. cable length (volt drop:

0.5V, with max. CSA)

20A 10A 1.5mm2 1.9m 10mm2 13m

10A 5A 1.5mm2 3.8m 10mm2 26m

Note: The specification is applicable at ambient temperature of 40°C. If the temperature is higher, the CSA should be increased

The CSA of the system grounding cable should be not less than 2.5mm2, use yellow-green dual color cable, the

grounding terminal is M6 screw.

Preparing tools

The installation tools are given in Table 2-4. The tools must be insulated and ESD-proof processed before they are

used.

Table 2-4 Installation tools

Tool Specification

Tool Specification

Combination wrench

(hatch, club)

Wrench set (10#, 13#, 16#,

18#, 21#) Box wrench 12mm

Adjustable wrench 200mm Cross screwdriver 100mm, 200mm

Electrician diagonal pliers 150mm Slotted screwdriver 100mm, 200mm

Electrician sharp nose

pliers 150mm Wire cutters Max. 300mm2

Steel tape 5m Hydraulic-pressure

compaction pincher Max. 300mm2

Electrician knife Normal type Digital multimeter Three and a half bit digital

display

Gradienter Normal type Impact electric drill With Φ8 impact aiguille

Blinkers To prevent splash Power socket With 5m cable

Hammer Safety shoes To prevent puncture and for

insulation

Preparing shielding metal pipes

It is recommended to use metal pipes to shield and protect all the cables. Plastic coated metal hoses are

recommended. Prepare the metal pipes according to the actual amount and size of cables.

2.3 Mechanical Installation

The power system uses 19'' rack or wall-mounting installation. The required mounting components are shipped with

the power system at delivery.

Note

1. When installing the power system against the wall, make sure that the wall strength and thickness meet the load-bearing and

expansion bolt installation requirements.

2. The three brackets are fixed on both sides of the subrack power system before delivery.

The installation procedures are as follows:

1. If wall-mounting installation is used, firstly remove the three brackets, turn the bracket with the grounding screw to

make the grounding screw facing forward, and then fasten the bracket to the front of the subrack left side wall,

Page 11: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Chapter 2 Installation 5

NetSure 2100 A31-S1 Subrack Power System User Manual

meanwhile, respectively fix the other two brackets after rotation to the middle of the subrack left and right side wall.

The position of the bracket is shown in Figure 2-2.

2. By referring to the dimension shown in Figure 2-1, mark the central points of the installation holes on the wall. Use

an electric drill (aiguille: Φ8) to dig holes (depth: 45mm) at the marked points. Clean the holes off dust. Put the four

expansion pipes (M6 × 65) into the holes and keep 20mm exposed.

32

20

Wall

465

Expansion pipe M6 65×

Figure 2-1 Installation dimension of cabinet base

3. As shown in Figure 2-2, use four groups of flat washer Ф6, spring washer Ф6 and nut M6 to fix the power system on

the wall.

Flat washer Ф6, spring washerФ6, nut M6 (4 group)

Figure 2-2 Fixing the power system

4. After the installation, the power system should stand firmly no matter how it is shaken.

5. If rack mounting installation is used, firstly remove the three brackets, turn the bracket with the grounding screw to

make the grounding screw facing forward, and then fasten the bracket to the front of the subrack left side wall,

meanwhile, fix any one of the other two brackets after rotation to the front of the subrack right side wall (the rest

bracket is no need to be fixed). The position of the bracket is shown in Figure 2-2, use the fixing screws to fasten the

subrack power system to the rack through bracket.

2.4 Electrical Installation

All the cables entering or outgoing the power system must be put into the metal pipe for protection. The metal pipe

should be connected to the PE bar reliably. Plastic coated metal hoses are recommended.

2.4.1 Connecting Power Cable

Danger Danger

1. Switch off all MCBs before the electrical connection.

2. Only the qualified personnel can do the mains cable connection.

3. Before electrical connection, make sure all the AC MCBs of the power system are switched off, the AC 230/400V 20A double pole C type MCB is recommended.

4. There is a dangerous voltage in the primary circuit, disconnect the power supply before maintenance.

Connecting Earth Cable

Connect one end of the earth cable to the grounding terminal (see Figure 2-3), and solder the other end to the

grounding metal base outside the power system.

Page 12: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

6 Chapter 2 Installation

SiteWeb2 Graphic Configuration Tool Operation Manual

Connecting AC Input Cables

The routing method of the AC input cables is the same as that of the earth cables. Connect the live line (L) and neutral

line (N) of the AC input cables respectively to the lower terminals of the power system AC input terminal L and AC input

terminal N, as shown in Figure 2-3.

AC input terminal L

AC input terminal N

Grounding terminal

Load output route 1-

Battery-

Battery+

Load output route 2-

Load output route 3-

Load output route 3+Load output route 2+Load output route 1+

Figure 2-3 Illustration of connection terminal

Connecting DC Cables

The power system can be connected with three route of loads respectively controlled by three MCBs, as shown in

Figure 2-3. Connect the negative load cable to the corresponding load '-' and then connect the positive load cable to

the corresponding load ‘+’ (see Figure 2-3).

Table 2-5 Specification of load MCB and cable

Load MCB Load MCB capacity Load cable CSA Remark

Load MCB 1 ~ Load MCB 3 20A × 1, 10A × 2 ≤ 10mm2

The total output capacity of the load should

not be greater than the corresponding MCB

rated current

Note

When the mains failure, the battery supplies power to the load. when the battery voltage drops to 43.2V, the power system will

automatically switch off all the loads to avoid battery over-discharge.

2.4.2 Connecting Battery Cable

The power system can be accessed in one group of batteries controlled by a battery MCB, as shown in Figure 2-3.

During connection, connect the negative battery cable to the battery terminal '-' and then connect the positive battery

cable to the battery terminal '+' (see Figure 2-3).

2.4.3 Connecting Communication Cable

Communication port

The power system provides two kinds of communication ports, including dry contact alarm output port and RS232 port,

as shown in Figure 2-4.

Figure 2-4 Illustration of controller front panel

Connecting dry contact output port

The controller is configured with two pairs of alarm dry contact output (DO1 ~ DO2) as standard configuration and four

expanded outputs (DO3 ~ DO6) as optional. The dry contact that generating corresponding alarm is normally closed,

users can connect according to actual needs. When wiring, take out the female of the 4-pin phoenix terminal bound at

Page 13: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Chapter 2 Installation 7

NetSure 2100 A31-S1 Subrack Power System User Manual

the controller handle, connect the multi-core communication cable with the pipe terminal to the corresponding female

of the phoenix terminal according to the dry contact silkprint on the controller, and then insert the terminal into the

controller front panel. The position of communication terminal and port definition are shown in Figure 2-4 (Users need

to prepare signal cable themselves).

Connecting RS232 port

The RS232 port is used for communication with the host. The correlation of the RS232 and DB9 port on the host is

shown in Table 2-6. When wiring, take out the female of the 3-pin phoenix terminal bound at the controller handle,

connect the multi-core communication cable with the pipe terminal to the corresponding female of the phoenix terminal

according to the RS232 port silkprint on the controller, and then insert the terminal into the controller front panel, as

shown in Figure 2-4 (Users need to prepare signal cable themselves).

Table 2-6 Correlation of ports

RS232 port DB9 port

1 (Tx) 2

2 (Rx) 3

3 (GND) 5

2.4.4 Connecting Temperature Compensation Cable

If the user selects the temperature compensation cable, first loosen the captive screw in the upper left of the controller,

and slowly pull the controller out of the power system until the 3pin temperature sensing interface J2 is exposed on the

monitoring board. Then take out the temperature compensation cable and insert the cable into the interface, and then

slowly push the controller into the power system and fix the captive screw.

2.5 Installation Check

After the installation, you should carry out the inspection procedures given in Table 2-7.

Table 2-7 Installation check list

Check item No. Check content

Rack

installation

1 Check that the rack is installed horizontally, vertically and steadily

2 Check that all the bolts and screws are tightened, especially those in electrical connections. Check that

plain washers and spring washers are present and not reversed

3 Check that there are no unwanted materials inside the rack and clear up the unwanted materials

4 Check that the rack paint is intact. If there are scratches, paint them immediately with antirust paint to

prevent corrosion

5 Clean up the rack

Electrical

installation

1 Check that all the MCBs and cable specifications are correct

2 Check that the bus and input/output cables are connected correctly, and that the system is grounded

correctly

3 Measure the resistance value between the positive terminal and negative terminal in the DC loop and

phase - to - phase resistance value in the AC loop. Make sure there is no shortcircuit

4 Check that the number and connection of the battery cell, and polarities of the battery strings are correct

5 Check that the battery cell number and connection

6 Check that the rectifiers are fastened down

7 Check that all MCBs are switched off

8 Check that the cables are tidy, and the cable binding is normative

9 Check the AC input and distribution. Check that the color of the AC cables is normative, the cables are laid

fast, and the safety labels are complete. See Appendix 4 Wiring Diagram for AC wiring and cable

connection

Page 14: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

8 Chapter 3 Testing

NetSure 2100 A31-S1 Subrack Power System User Manual

Chapter 3 Testing

This chapter introduces the testing after installation. The corresponding safety rules shall be adhered to in the testing.

If abnormal phenomenon is found, shut down the power system immediately. After finding the cause, then continue the

testing.

3.1 Startup

Note

1. Before the test, inform the manufacturer representative.

2. Before the test, take off conductive objects such as watches and rings.

3. Only trained electrical engineers shall maintain and operate the power system.

During operation, parts of this equipment carry hazardous voltage. Misoperation can result in severe or fatal injuries and

property damage. Before the test, check the equipment to ensure the proper grounding. Installation check (see Table 2-7)

must be done before testing. Then the batteries can be charged for the first time.

Make sure that the system AC output MCB and the load MCB in the subrack are switched off, and ensure that all the

devices are installed.

Please check the power system according to below listed items.

Startup preparations

Check item OK Comments

Make sure that all the MCBs are switched off

Measure the AC input voltage. Make sure that the input voltage is within the rated input range Umin=___V

Check that the communication and alarm cables are connected to the signal transfer board

Check that the temperature sensor has been installed

Check with an ohmmeter that there is no short circuit between the positive & negative DC output terminals,

or between the positive & negative battery terminals or the AC input terminals (Note: Pull out all modules

before the check and restore them after the check)

Measure the battery string voltage with a voltmeter and ensure that the battery polarity is correct Umin=___V

Startup

Check item OK Comments

Switch on the system AC input MCB The run indicator on the rectifier will be on after a certain delay

Switch on the load MCB. Use a voltmeter to check the voltage of both ends of load, if it is 53.5V ± 0.5V, it is

normal

Switch on the battery MCB

3.2 Basic Settings

The power system parameters are set at factory, and the default value can meet the requirements of the power system.

Users can modify the parameters (such as AC over/under voltage point, DC over/under voltage point and etc.) of the

power system controller through background software. Users can also reset the commonly used parameters of the power

system through LCD screen based on actual needs. When setting the system parameters, you must input correct

password to allow you setting the controller parameters. The password of M225S controller is 1.

Users can view and set common parameters (see Table 3-1) through the LCD screen of the controller. See Appendix 2

Menu Structure Of The Controller for specific setting path.

Table 3-1 Settable common parameters of power system

Parameters Setting range Default value

Battery capacity 20Ah-600Ah 100Ah

Battery protection voltage 40-60V 43.2V

Float charge voltage 42V ~ 58V (lower than boost charge voltage) 53.5V

Page 15: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Chapter 3 Testing 9

NetSure 2100 A31-S1 Subrack Power System User Manual

Parameters Setting range Default value

Boost charge voltage 42V ~ 58V (higher than float charge voltage) 56.4V

Note:

1. The battery protection voltage should be set according to the requirements of the battery manufacturer

2. If the user configures iron lithium battery, the relevant charging parameters should be set according to the requirements of the

battery manufacturers

3.3 Alarm Check And System Operation Status Check

Alarm check

Check that all functional units can trigger alarms that can be displayed on the controller.

Check item OK Comments

Pull out one rectifier. The ‘Rect N Com Failure’ alarm should be triggered. Insert the rectifier in. The

alarm should disappear. Repeat the same procedures on other rectifiers

Switch off battery MCB. The ‘Batt Failure’ alarm should be triggered. Switch on the MCB. The alarm

should be cleared

Switch off a load MCB connected to a DC output route. The alarm ‘Load N Failure’ should be triggered.

Switch on the MCB, and the alarm should be cleared. Repeat the same operation on the other load

MCBs

Switch off all the battery MCBs. Keep only one rectifier in operation. Through the controller, adjust the

rectifier FC voltage to make it lower than the alarm point. The alarm ‘DC Voltage Low’ should be

triggered

Note: The controller will trigger alarms after approximately three seconds

System operation status check

The system works normally without alarm. Check whether the system is running normally through the controller.

Check item OK Comments

The controller should display the correct AC voltage

The controller should be able to display the DC voltage. The difference between the displayed voltage

and the actual voltage should be less than 1%

The controller should display the battery current. The difference between the displayed and measured

battery current should be less than 3%

Check the number of the rectifiers through the controller. The number should be consistent with the

actual number

Check the voltage, current, current limiting point of rectifiers through the controller. They should agree

with the actual values

For the system with a temperature sensor, the controller should be able to display the battery ambient

temperature. Hold the probe of the temperature sensor with hand, which should display the change of

temperature

3.4 Final Steps

Check item OK Comments

Disconnect all test equipment from the system and make sure that materials irrelevant to the equipment

have been all removed

Restore the power system to its original condition

Check and handover the equipment that the user has purchased

Note down all the operations taken, including time of the operation and name of the operator

If any defects are found in this equipment, inform the personnel responsible for the contract.

If repairing is needed, please fill in the FAILURE REPORT and send the report together with the defective unit to the

repairing center for fault analysis.

Page 16: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

10 Chapter 4 Use Of Controller

NetSure 2100 A31-S1 Subrack Power System User Manual

Chapter 4 Use Of Controller

This chapter introduces the operation panel indicators and functional keys of the controller briefly, and expounds the

main screen contents, access method, information querying and parameter setting.

For the factory parameter setting and operation menu structures of the controller, refer to Appendix 1 Technical Data

and Appendix 2 Menu Structure Of The Controller.

4.1 Operation Panel

The operation panel of the controller provides the LCD screen, functional keys and indicators, as shown in Figure 4-1.

Figure 4-1 Operation panel of the controller

The indicators on the operation panel are described in Table 4-1.

Table 4-1 Description of the controller indicators

Indicator Color Normal state Fault state Fault cause

Run indicator Green On Off No operation power supply

Observation alarm

indicator Yellow Off On There are observation alarms

Critical alarm indicator Red Off On There is a critical alarm

The controller uses a 128 × 64 LCD unit, and a keypad with three functional keys (listed in Table 4-2).

Table 4-2 Description of the controller functional keys

Key Name Function

ESC Escape Return or cancel

ENT ENT Confirm or execute

▼ Down Move the cursor down or select the next screen

4.2 Main LCD Screens

The following LCD screens will be mentioned in this chapter for many times. This section is a centralized introduction

about the contents and access methods of these LCD screens.

Note

The contents of the LCD screens given in this manual are just the examples. For different configurations, models and system

states, the actual contents of the LCD screens may be different from this manual.

4.2.1 System Information Screen

After the controller is powered on for the first time, following initialization program will be executed.

Page 17: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Chapter 4 Use Of Controller 11

NetSure 2100 A31-S1 Subrack Power System User Manual

1. After the controller is powered on, the language screen is displayed, as shown in Figure 4-2.

中文

Chinese

English

Chinese

Figure 4-2 Language screen

Press ▼ to select the language needed and press ENT to confirm the selection. If no key is pressed within 3s, the

controller will select the displayed language automatically.

2. During initialization, the controller displays “Wait…”, as shown in Figure 4-3.

稍候 ...Wait ...

Figure 4-3 Wait screen

3. After initialization, the screen will display the main screen (see Figure 4-4) that displays the most frequently used

information of the system, and the information is displayed by scrolling every row. You can press the adjustment key to

perform single direction cyclic scrolling.

53.5V 125A

浮充 告警

电池: 0.0A

剩余: 100%

交流电压: 220V

温度: 25.0℃

53.5V 125A

FC Alarm

Remaining 0.0A

Cap. 100%

AC Volt.

Temp.

220V

25.0°C

51.3V 0.0A

Figure 4-4 Main screen

4. Press ‘ESC’ in system operating screen to enter the product information screen, as shown below in Figure 4-5

Controller model: LCU

Software version 1.001.02

Figure 4-5 Product information screen

5. Press ‘ESC’ in the product information screen to return to the first system operating information screen.

4.2.2 Password Confirmation Screen

During the operation, the 'Settings' submenu will prompt you to input password, as shown in Figure 4-6. Only the

correct password allows you to enter the screen you need to operate.

输入密码:xPassword: x

Figure 4-6 Password confirmation screen

When inputting the password, use the ENT key to get into editing state, use▼ to input numbers 1 ~ 9. After input '1',

press ENT to enter the first parameter setting screen.

4.2.3 MAINMENU Screen

The main menu is the highest-level menu of the controller. At the sub-menus of this screen, you can query the settings,

controls, rectifier and alarm information of the system. The main menu screen is shown in Figure 4-7.

Active alarm

Rect Infor

Settings

History alarm

Figure 4-7 Main menu screen

Page 18: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

12 Chapter 4 Use Of Controller

NetSure 2100 A31-S1 Subrack Power System User Manual

1. At any one of the system information screen, press the ENT key to enter the MAINMENU screen.

2. At any sub-menu of the MAINMENU screen, press the ESC key repeatedly to return to the higher-level menu, and

ultimately return to the MAINMENU screen.

3. Select the required sub-menu through pressing ▼. The selected sub-menu is shown by cursor, and press the ENT

key to enter the corresponding sub-menu.

4.3 Querying System Main Information

4.3.1 Querying Active Alarm

When a new alarm is generated, the LCD of the controller will prompt the active alarm screen automatically. If there

are multiple alarms in the current system, you can query alarms through the following steps.

At the MAINMENU screen (see Figure 4-7), press▼ to select ‘Active Alarm’ menu. Press the ENT key to confirm.

The previous screen includes the alarm serial No./alarm total number, alarm name and alarm time. The alarm

generating time determines the sequence it is displayed, with the latest alarm displayed first. Press ▼ to view all active

alarms. The active alarms may be displayed in the controller are given in Table 4-3.

Table 4-3 Active alarm of the controller

Alarm name Conditions Default associated

output relay

DC Low Volt System output voltage lower than DC low voltage alarm point 4*1

DC High Volt System output voltage higher than DC high voltage alarm point 4*1

AC Low Volt System input voltage lower than AC low voltage alarm point None

AC High Volt System input voltage higher than AC high voltage alarm point None

Temp Low Temperature lower than normal operating range None

Temp High Temperature higher than normal operating range None

Batt Discharging Battery is discharging None

Batt Charging Over Curr Charging current exceeds preset max. value None

AC Fail Rectifier AC input voltage lower than 80Vac 3*1

Load Disconnect Load distribution fuse or MCB off None

Batt Disconnect Battery fuse or MCB off None

BLVD BLVD contactor opens due to low battery voltage 6*1

ECO Fail Energy saving failure 6*1

Sys Curr Imbalance System current is not balanced None

Output Volt Abnormal System output voltage is abnormal None

Rect Fault Rectifier fails 5*1

Rect Fan Fail Rectifier fan fails 5*1

Rect Protect Rectifier protects itself as its AC input voltage is out of normal range: 85Vac

~ 295Vac 5*1

Rect Comm Fail Rectifier cannot communicate with LCU 5*1

Critical alarm There is one or several critical alarms 1

Observation alarm There is one or several observation alarms 2*2

Note:

1. Relays 3 ~ 6 are available only if the DO expansion board is installed.

2. The relay2 associated with observation alarm, it is necessary to set the parameter 'Relay2' under the 'Settings' menu to 'Alarm

output'. The system is set to 'Alarm output' at factory

4.3.2 Querying Historical Alarm

At the MAINMENU screen (see Figure 4-7), press ▼ to select the ‘History Alarm’ menu. Press the ENT key to confirm.

The alarm contents include the alarm serial No./alarm total number, alarm name and alarm time. The alarm generating

time and the alarm end time are displayed alternatively. Press ▼ to view all historical alarms.

4.3.3 Querying Rectifier Information

The 'Rect. Information' screen displays the information of the first rectifier module. To query the next rectifier

information, simply press ▼. When a rectifier is selected, the corresponding run indicator will flash.

Page 19: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Chapter 4 Use Of Controller 13

NetSure 2100 A31-S1 Subrack Power System User Manual

Note

If the controller does not detect the rectifier module, the rectifier information can not be queried.

The rectifier information includes rectifier No., output voltage, output current and start state.

At the MAINMENU screen (see Figure 4-7), press ▼ to select the ‘Rect. Information’ menu. Press ENT key to enter

the rectifier information screen, as shown in Figure 4-8.

53.5V 0.0A

模块1:开Rect.1 ON

Figure 4-8 Rectifier information screen

4.4 Setting System Parameters

The 'Settings' screen has 14 parameters to be set: 'Batt Cap', 'BLVD Volt', 'FC Volt', 'BC Volt', 'Shunt Current', Shunt

Volt', 'ECO Enable', 'Clear', 'Address', 'Baud Rate', 'LLVD Enable', 'LLVD Volt', 'Relay 2' and 'Walk-in Time'. For 'Clear'

submenu, you can select 'History Alarm', 'Rect Lost', 'Communication Failure' and ' Testing abnormal' to clear

corresponding alarms.

Table 4-4 lists all the system parameter settings.

Table 4-4 System parameter settings

Name Setting Range

Default Unit Low High

Batt Cap 20 600 100 Ah

BLVD Volt 40 60 43.2 V

FC Volt 42 58 53.5 V

BC Volt 42 58 56.4 V

Shunt Current 1 500 50 A

Shunt Volt 1 150 75 mV

Address 1 ~ 254 1

Baud Rate

0/1/2/3

(Corresponding to

4800/9600/19200/38400)

1 (Corresponding

to 9600)

LLVD Enable 0/1 (Corresponding to disable/enable) 0 (Disable)

LLVD Volt 40 ~ 60 44 V

Relay 2 0/1 (Corresponding to alarm

output/LLVD) 0 (Alarm output)

Walk-in Time 0, 8 ~ 128 (0 represents disable) 0 (Disable) S

Page 20: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

14 Chapter 5 Maintenance

NetSure 2100 A31-S1 Subrack Power System User Manual

Chapter 5 Maintenance

This chapter describes routine maintenance, alarm and fault handling, and replacing parts of the power system.

Note

1. The maintenance must be conducted under the guidance of the related safety regulations.

2. Only trained personnel with adequate knowledge about the power system shall maintain the inner part of the subrack power

system.

3. There is a dangerous voltage at AC side, and the grid must be disconnected when maintaining the AC side.

5.1 Routine Maintenance

Inspect the power system periodically and shoot the trouble in time. The routine maintenance items are given in Table

5-1.

Table 5-1 Routine maintenance items

Inspection item Frequency Inspecting method Guide

DC output Once half a year Multimeter Measure the voltage between the load MCB and the DC

output positive busbar. Check that the voltage is normal

Indicators of the

rectifier and the

controller

Once half a year Visual inspection Refer to 5.2.1 Handling Controller Alarms and 5.2.2

Handling Rectifier Fault

Rectifier fan Once half a year Visual inspection If the fans are dusty, the fans should be dusted or cleaned

5.2 Handling Alarms And Fault

5.2.1 Handling Controller Alarms

You can query the controller alarms through LCD screen of the controller.

Alarm type

The controller alarms are classified into three types: critical alarm, observation alarm and no alarm.

Critical alarm: These two types of alarms have strong impacts on the system performance. Whenever these alarms

are generated, you should handle them immediately. The alarm indicators (see Figure 5-1) will be on and audible

indication will be given.

Observation alarm: When this type of alarm is raised, the system maintains normal output for a while. If the alarm

occurs during watch time, it should be handled immediately. If the alarm occurs during non-watch-time, handle it

during watch time. The alarm indicators (see Figure 5-1) will be on when the observation alarm occurs.

No alarm: Alarms set as ‘no alarm’ by the users, will generate no visible or audible indication and the system works

normally.

Page 21: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Chapter 5 Maintenance 15

NetSure 2100 A31-S1 Subrack Power System User Manual

Controller indicator

The controller alarm indicators are displayed through LCD screen, as shown in Figure 5-1. The description of the

indicators is listed in Table 5-2.

Run indicator

Observation alarm

Critical alarm indicator

Figure 5-1 Controller indicators

Table 5-2 Description of the controller indicators

Indicator Color Normal state Fault state Fault cause

Run indicator Green On Off No operation power supply

Observation alarm

indicator Yellow Off On There are observation alarms

Critical alarm indicator Red Off On There is a critical alarm

Handling common alarms

The handling methods of common alarms are given in Table 5-3.

Table 5-3 Handling methods of common alarms

No. Alarm Handling method

1 AC Failure

If the failure does not last long, the battery will power the load. If the cause is unknown or the

failure lasts too long, a diesel generator is needed. Before using the generator power to supply

the power system, it is suggested to run the generator five minutes to minimize the impact on the

power system

2 Rect Fan Fails Pull out the rectifier to check if the fan is obstructed. If yes, clean it and push the rectifier back. If

the fan is not obstructed or if the fault persists after cleaning, replace the fan

3 Rect Not Respond Check if the communication cable is connected properly between rectifier and controller. If yes,

restart the rectifier. If the alarm persists, replace the rectifier

4 Over Temp Check the temperature around the temperature sensor is too high, if so, find the cause and

reduce the temperature

5 Load Fuse Alarm,

Batt Fuse Alarm

Check if the corresponding MCB is switched off. If the MCB is open, find out the fault and remove

it. Otherwise, the alarm circuit is faulty. Please contact Emerson

6 DC Volt High

Find out the rectifier that caused the over-voltage alarm. pull out all the rectifiers under the

circumstance that the battery can supply power normally. Then insert the rectifiers one by one.

When inserting a certain rectifier, the system triggers over-voltage again, that rectifier is

over-voltage, replace it

7 DC Volt Low

1. Check if any rectifier is inoperative, or has no output current. If yes, replace it.

2. Check if the total load current exceeds the total rectifier current during float charge. If yes,

disconnect some loads or add more rectifiers to make the total rectifier current bigger than 120%

of the total load current with one redundant rectifier

8 LVD2 Check if there is mains failure, and the battery voltage is lower than the value of ‘LVD2’.

9 Rect Fault The rectifier with the fault indicator (red) on is faulty.

Power off the rectifier, and then power it on after a while. If the alarm persists, replace the rectifier

10 AC Voltage High

Check if the AC over-voltage value is too low. If yes, change the value.

A mild over-voltage does not affect the system operation. However, the rectifier will stop

operation when the mains voltage is more than 305V. If the mains voltage is above the AC

over-voltage value, the mains grid should be improved

11 AC Voltage Low Check if the AC under- voltage value is too high. If yes, change the value.

Page 22: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

16 Chapter 5 Maintenance

NetSure 2100 A31-S1 Subrack Power System User Manual

No. Alarm Handling method

11 AC Voltage Low

When the mains voltage is lower than 176V, the output power of the rectifiers will be derated.

When the mains voltage is lower than 80V, the rectifiers will stop working. If the mains voltage is

under the AC under-voltage value, the mains grid should be improved

12 Rect Protect Check if the mains voltage is above 305V or under 80V. If the mains voltage is under the AC

under-voltage value or above the AC over-voltage value, the mains grid should be improved

5.2.2 Handling Rectifier Fault

When the rectifier has any other component failure except rectifier fan, the rectifier needs to be replaced. Therefore,

do not disassemble or replace any part of the rectifier other than the fan.

The symptoms of usual rectifier faults include: run indicator (green) off, protection indicator (yellow) on or blinking, fault

indicator (red) on or blinking.

The indicators of the rectifier are shown in Figure 5-2.

电源指示灯(绿色)

保护指示灯(黄色)

故障指示灯(红色)

Run indicator (green)

Protection indicator (yellow)

Fault indicator (red)

Figure 5-2 Rectifier indicators

The handling methods of rectifiers are given in Table 5-4.

Table 5-4 Handling methods of rectifiers

Indicator Color Normal

state

Abnormal

state Cause Handling method

Run

indicator Green On Off No input or output voltage

Make sure that there is input voltage

and output voltage

Protection

indicator Yellow Off

On

AC input voltage exceeds normal range Ensure AC input voltage is normal

PFC output OverVolt/LowVolt

protection

Replace the faulty rectifier with a new

one

Current sharing imbalance strongly Replace the faulty rectifier with a new

one

Rect over temp:

1. Fan blocked

2. Ventilation path blocked at the inlet

or vent

3. Ambient temperature too high or the

inlet too close to a heat source

1. Remove the object that blocks the

fan

2. Remove the object at the inlet or

vent

3. Decrease the ambient temperature

or remove the heat source

Blinking Rectifier communication interrupted Check whether the communication

cable is properly connected

Fault

indictor Red Off

On

Rectifier over-voltage Restart the rectifier. If the protection is

triggered again, replace the rectifier

Fuse fault

Check whether the rectifier outputs

over-voltage. If not, replace the

rectifier

Rectifier current sharing imbalance

(current imbalance degree>±5%) Replace the rectifier

Blinking Fan fault Replace the fan

Page 23: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Chapter 5 Maintenance 17

NetSure 2100 A31-S1 Subrack Power System User Manual

5.3 Replacing Parts

5.3.1 Replacing Rectifier

For rectifier, it is recommended not to repair any other parts. When faulty, the rectifier should be replaced, not repaired.

See the following procedures to replace the rectifier.

1. Take a new rectifier and check it for any damage from transport.

2. Loosen the fixing screw of the rectifier handle. Pull out the faulty rectifier from the rack by grabbing its handle, as

shown in Figure 5-3.

Fixing screw of handle

Handle

Figure 5-3 Replacing rectifier

Note

The surface temperature of the rectifier just exit working is still very high, pay attention to grasp the rectifier to avoid falling

damage.

3. Hold the rectifier handle and push the new rectifier into the slot just vacated and make sure the connection is good.

After a brief delay, the run indicator of the rectifier will turn on and the fan will start running.

4. Check whether the new rectifier works normally.

You should make sure that:

1) The monitoring unit recognizes the new rectifier.

2) The new rectifier shares current with other rectifiers.

3) When this new rectifier is pulled out, there is a corresponding alarm and the monitoring unit displays the alarm.

If the new rectifier passes all the above tests, the replacement is a success.

5. Push the handle back into the front panel to fix the rectifier, and tighten the fixing screw of the rectifier handle.

5.3.2 Replacing Controller

Controller fault: the run indicator (green) is off and the LCD screen does not display (external alarms may also be

triggered if a background system is connected).

Please check whether the system bus voltage is normal, and the controller connection terminal is reliable. If the above

two points are normal, then the controller is faulty, replace a new controller.

The replacing procedures are as follows:

1. Safety preparation

Attach one end of the effective grounding strap to the wrist and the other end to a suitable ground.

2. Loosen the locking screw on the controller to pull out the controller from the subrack power system until the

terminals J6, J7, J2 (when the temperature sensor is configured) are exposed. Unplug the connection terminal on J6,

J7 and J2, then pull out the controller from the subrack power system completely.

Page 24: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

18 Chapter 5 Maintenance

NetSure 2100 A31-S1 Subrack Power System User Manual

监控模块

松不脱螺钉Locking screw

Controller

Figure 5-4 Replacing the controller

3. Insert the new controller into the subrack power system, reconnect the terminals J2, J6, J7, and then tighten the

locking screw of the controller.

4. After restarting the controller, set the parameters according to 4.4 Setting System Parameters and actual

configuration.

5.3.3 Replacing Logic Board

The position of the logic board is shown in Figure 5-5. The replacing procedures of the logic board are as follows:

1. Switch off the battery MCB (see Figure 5-6) and system AC output MCB.

2. Loosen all the fixing screws on the top cover of the subrack power system, and remove the top cover.

3. Unplug all the cable connectors connected to the logic board.

The terminal layout of the logic board is shown in Figure 5-5.

H1

H2 H3

H4

J1

J2

Figure 5-5 Connection terminal layout

4. Loosen the four fixing screws of the logic board, and then remove the logic board, as shown in Figure 5-6.

Logic boardFixing screw (4 pcs)

Battery MCB

Figure 5-6 Dismantling logic board

5. Replace a new logic board and install the new logic board according to the above reverse steps.

6. Switch on the battery MCB and system AC output MCB.

Page 25: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Appendix 1 Technical Data 19

NetSure 2100 A31-S1 Subrack Power System User Manual

Appendix 1 Technical Data

Table 2 Technical data

Parameter

category Parameter Description

Environmental

Operating temperature -5°C ~ 40°C

Storage temperature -40°C ~ 70°C

Relative humidity ≤ 90%RH (30°C)

Altitude ≤ 2000m (derating is necessary above 2,000m)

Over-voltage level Level II

Pollution level Level II

Others No conductive dust or erosive gases. No possibility of explosion

AC input

AC input system L+N+PE/220Vac

Applicable power grid TN, TT

Input voltage range 85Vac ~ 300Vac

Input AC voltage frequency 45Hz ~ 65Hz

Max input current ≤ 12.3A

Power factor ≥ 0.99

DC output

Nominal outout voltage -48Vdc

Reted output voltage -53.5Vdc

Output DC voltage -42.3Vdc ~ -57.6Vdc

Output DC current 0 ~ 34.4A (output voltage is -53.5V)

load current ≤ 20A, battery charge current ≤ 14.4A

Voltage set-point accuracy ≤ 1%

Efficiency ≥ 93.5%

Noise (peak-peak) ≤ 200mV (0 ~ 20MHz)

Weighted noise ≤ 2mV (300Hz ~ 3400Hz)

AC input alarm

and protection

AC input over-voltage alarm point Default: 280Vac ± 5Vac, configurable through controller

AC input over-voltage recovery

difference

Default: 270Vac ± 5Vac, 10Vac less than the AC input over-voltage

alarm point

AC input under-voltage alarm point Default: 180Vac ± 5Vac, configurable through controller

AC input under-voltage recovery

difference

Default: 190Vac ± 5Vac, 10Vac higher than the AC input under-voltage

alarm point

AC input over-voltage protection

point Default 305Vac ± 5Vac, configurable through controller

AC input over-voltage protection

recovery difference

Default: 295Vac ± 5Vac, 10Vac lower than the AC input over-voltage

protection point

AC input under-voltage protection

point Default: 80Vac ± 5Vac, configurable through controller

AC input under-voltage protection

recovery difference

Default: 95Vac ± 5Vac, 10Vac higher than the AC input under-voltage

protection point

DC output alarm

and protection

DC output over-voltage alarm point Default: -58.5Vdc ± 0.2Vdc, configurable through controller

DC output over-voltage recovery

difference

Default: -58Vdc ± 0.2Vdc, 0.5Vdc lower than the DC output

over-voltage alarm point

DC output under-voltage alarm point Default: -45.0Vdc ± 0.2Vdc, configurable through controller

DC output under-voltage recovery

difference

Default: -45.5Vdc ± 0.2Vdc, 0.5Vdc higher than the DC output

under-voltage alarm point

DC output over-voltage protection

point Default: -59.0Vdc ± 0.2Vdc, configurable through controller

LLVD Default: -44.0Vdc ± 0.2Vdc, configurable through controller

BLVD Default: -43.2Vdc ± 0.2Vdc, configurable through controller

Rectifier

Load sharing The rectifiers can work in parallel and share the current. The unbalance

is better than ± 5% rated output current.

Derate by input (at 45°C)

The rectifier can output power of 100% with input voltage of 176Vac;

The rectifier can output power of 750% with input voltage of 132Vac;

Rectifiers output 20% power with input voltage of 85Vac;

Rectifiers under-vlotage stop with input voltage of 80Vac

Page 26: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

20 Appendix 1 Technical Data

NetSure 2100 A31-S1 Subrack Power System User Manual

Parameter

category Parameter Description

Rectifier

Over-voltage protection

The rectifier provides over-voltage hardware and software protection.

The hardware protection point is 59.5V ± 0.5V, and it requires manual

resetting to restore operation. The software protection point is between

56V and 59V (0.5V above output voltage, 59V by default), and can be

set through the controller

There are two software protection modes, which can be selected

through the software at the host:

1. Lock out at the first over-voltage

Once the output voltage reaches protection point, the rectifier will shut

off and hold that state. it requires manual resetting to restore the

operation

2. Lock out at the second over-voltage

When the output voltage reaches the software protection point, the

rectifier will shutdown, and restart automatically after 5 seconds. If the

over-voltage happens again within a set time (default: 5min.

Configurable through controller), the rectifier will shut off and hold that

state. It requires manual resetting to restore the operation

Manual resetting: Resetting can be done manually through the

controller, or by removing the rectifier from system

Output delay Output voltage can rise slowly upon rectifier start up. The rise time is

configurable

Fan speed adjustable Rectifier fan speed can be set to half or full speed

Temperature derating (176 ~

300VAC) -5°C ~ 40°C, the system outputs with full load

EMC

Conducted emission /

Radiated emission

Harmonic current emissions Class A EN61000-3-2

Voltage wave and flicker / EN61000-3-3

Immunity to EFT Level 4 EN61000-4-4

Immunity to ESD Level 3 EN61000-4-2

Immunity to Surges Level 4 EN61000-4-5

Immunity to radiation Level 2 EN61000-4-3

Immunity to conduction Level 2 EN61000-4-6

Others

safety Meet the criteria of EN60950

Acoustic noise ≤ 55dB (A) (When the ambient temperature is lower than25℃)

Insulation resistance

At temperature of 15°C ~ 35°C and relative humidity not bigger than

90%RH, apply a test voltage of 500Vdc. The insulation resistances

between AC circuit and earth, DC circuit and earth, and AC and DC

circuits are all not less than 2MΩ

Insulation strength

(Remove the controller and rectifiers from the power system before the

test.)

AC circuit to earth:, 3535Vac

DC circuit to earth: 707Vac

AC to DC circuits: 4242Vac

For all the three tests above, there should be no breakdown or

flashover within 1min, with leakage current not bigger than 10mA

MTBF /

ROHS Satisfy R6

Mechanical

Dimensions

(mm)

Subrack power

system 482 (W) × 240 (D) × 43.6 (H)

Weight (kg)

Subrack power

system ≤ 4 (excluding rectifiers)

Rectifier ≤ 0.5

Page 27: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Appendix 2 Menu Structure Of The Controller 21

NetSure 2100 A31-S1 Subrack Power System User Manual

Appendix 2 Menu Structure Of The Controller

51.3V 0.0A

FC Alarm

Remaining:

0.0ACap:

100%

AC Volt: 220V

Temp: 25.0℃

Model: LCU

SW Ver: 1.02

ESC

Active alarm

Rect Infor

Settings

History alarm

ENT

AC failure

000105 18:00:08

Door alarm

000105 18:00:02

SPD Alarm

Start 0105 17:00:02

Cap: 300Ah

LVD Volt: 43.2V

FC Volt: 53.5V

BC Volt: 56.4V

Shunt A: 300A

Shunt V: 25mV

ECO Enable: No

Clear: History alarm

Address: 1

Baud rate: 9600

Rect1: ON

53.5V 38.5A

Rect 2: ON

53.5V 38.5A

ENT

...

1213 18:00:00

SPD alarm

000105 18:00:02

LLVD: Y

LLVD: 44.0V

Relay 2: LLVD

Walk-in T: 0S

End

Door Alarm

Start 0105 16:00:02

1213 17:00:00End

AC Failure

Start 0105 16:00:08

1213 17:00:00End

Figure 1 Menu structure of the controller

Page 28: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Appendix 3 Schematic Diagram 22

NetSure 2100 A31-S1 Subrack Power System User Manual

Appendix 3 Schematic Diagram

FL

KMD

D2

D1

D3

J1

J21

3

21

JX1

W34C3C1

QF

D1

QF

D2

QF

D3

QF

B1

JX2

H2

J2

-48

V

Can

+C

an

-

0V

Controller M1

0V

Ca

n+

Can

-

-48V

NL

Ba

tt_

co

mB

att

_o

ff

Pow

er-

Pow

er+

LNPE

H1

J71 2 4 5

1

2

3J3

123

J6

456

Can-

Can+

BAT1_SH+

BAT1_SH-

BATfuse1

Loadfuse1

-48V

0V

126 7 8 9

3

2

2

2

1 2 3 1 2 3 4

RS232 DO1 DO2

Rx Tx Temp

Optional

LNPE

3

2

2

2

789

1112131415

10

L N PE 0V

-48V

Ca

n+

Can

-

J1

Module backboard X1

L N PE 0V

-48V

Ca

n+

Can-

J31 2 1 2

J22 1J4 J3

1 2 1 2J2

2 1J4

BA

T-

Module backboard X1

Figure 2 Schematic diagram

Page 29: NetSure 2100 A31-S1 Subrack Power System User Manual ·  · 2017-03-15When operating Vertiv products, ... As a-P cf Rectifier power: 1000W ... NetSure 2100 A31-S1 Subrack Power System

Appendix 4 Wiring Diagram 23

NetSure 2100 A31-S1 Subrack Power System User Manual

Appendix 4 Wiring Diagram

2-J2-ACN,3-J2-ACN

2-J2-ACL,3-J2-ACL

W011 2 3 4 5 6 7 8 9 10

11

12 1 2 3 4 5 6 7 8 9 10

11

12

13

14 15

J7 J6

3-J

4-1

3-J

4-2

6-J

1-2

6-J

1-1

16-1

12--

,13--

,14--

7-a

15--

7-b

5-1

W03

1 2 3

J3

W03 W03 W03W03

Temperature sensor cable(optional)

M225SSL02W01

LN

AC Connector

1

M225S

4

20-1

J1

J21

3

21

2W34C3C1

616-1

5-1

5-A2

4-J7-54-J7-6

J1

D-DCVOUT-D-DCVOUT+

CAN+DCAN-D

ACLACN

PE

A7

PE

B7

H1

H2

J4J2J3

W01

1-N

1-L

3-J

4-1

3-J

4-2

5-1

16

-2

J1

D-DCVOUT-D-DCVOUT+ ACLACN

PE

A7

PE

B7

H1

H2

J2J3

W01

1-N

1-L

2-J

4-1

,4-J

6-1

2-J

4-2

,4-J

6-2

5-1

16-2

W03 W03W02 W02

W5432X1

2W5432x1

3

KMD

5

7FL

A1

A2 6-J2-2

1

a

b

4-J6-8

4-J6-7

1

20

BATT-

16-1

2

1

2

1

2

1

2

1

QFD18 9 10 11

QFD2 QFD3 QFB1

5-1

,9-1

12

--

13--

14

--

15--

8-1

,10-1

9-1

20-2

4-J7-2

11-1,16-2

W02

W02

W02 W02 W02 W02

W02 W02 W02 W02

W03

W03

W03

W03

W03

2

W03

CAN+DCAN-D

J4

JX112 13 14 15

JX2 JX3 JX4

8-2

,4-J

6-1

1

9-2

,4-J

6-1

1

10

-2,4

-J6-1

1

11

-2,4

-J6-9

16BUS+

2-J3-DC+,3-J3-DC+,20-2PE

W03

W02W02

PE16-3

W02

W02 W03

12 3

A1

B1

A1

B1

Ca

n-

Ca

n+

BA

T1

_S

H+

BA

T1

_S

H-

BA

Tfu

se

1

Lo

ad

fuse1

Po

we

r-

Pow

er+

Batt

_com

Ba

tt_

off

Te

mp

+T

em

p-

PE

BA

T-

2-J3-DC-,3-J3-DC-,8-1,4-J7-1,6-J2-3

4-J7-4,6-J2-1,5-A1

Figure 3 Wiring diagram