Page 1: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Refrigeration and A/C Controls Division Date | 1

New ADAP-KOOL®AK-CT 200

www.danfoss.com

OneHardwarefor over 300 tray variants

Page 2: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 2

Fully Integrated gear tray and case controller

Today’s power tray solution

Standard electromechanical components and electrical wiring

New ADAP-KOOL® AK-CT 200

Integrated power components

Current measurements

Zero-crossing technology

Pluggable spring loaded wire connectors

Create variants by different selection of electrical components and wiring:

Large number of customized trays

Different electromechanical fuse sizes

Many different blueprints

Different power trays for 1 and 3 phase

Create variants by software configuration:

1 version with software configuration of relays and application “soft wiring”

Configurable fuse size (0->16 Amp)

One common label for all display cases

Power management from 10 Watt to 10 KW

Page 3: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 3

Existing solution @ Norpe - 300 different variants

Service switch

Case Controller

Wiring diagram / documentation

300 different blue prints

Internal Wirings

Fuses

Contactors

Connectors for external wires

Page 4: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 4

Reduced complexity withnew Integrated Controller Tray

Reduced complexity

Fewer variants

Lower risk of wiring mistakes

Quick configuration

Improved service features

Easy check of I/O’s

Easy food type setup

Improved monitoring

Easier remote analysis

Extended information for data analysis

Fast reaction time from alarm to service

First time fix

Reliable

Robust against electromagnetic interference (EMC)

Zero crossing relays

Static cooling

Easy controller service

One fits all

Page 5: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 5

AK-CT 200 providing benefitsthroughout the value chain

OEM production

More than 300 variants with one hardware

Simplified handling of gear trays

Less wiring mistakes

OEM productionIn store

commissioningOnsite service

Remote monitoring

In store commissioning

Easy I/O check

Time saving with “Quick Configuration”

Communication status for fast fault finding

Onsite service

Easy change of food type

Easy I/O check

Reduced time for trouble shooting

Remote monitoring

Remote current monitoring

Remote fuse information and reset

Door openings

Root cause alarms

First time fix

Page 6: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 6

Controller key for late dedication

Control function can be defined at the end of production line.

Only one tray version for more than 300 different cabinets.

AK-CT201

Enable controller tray to be used with 3’rd party controller

AK-CT 450

Enable controller to control display case with TXV

AK-CT550

Enable controller to control display cases with AKV

Common features for all 3 versions

Manual override of light via pushbutton (DI)

Stop of fans while blinds down

Fan ECO - Reduced speed while blinds down

High power control of more than 300 different display cases

Page 7: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 7

3d party control

Page 8: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 8

EVR

Page 9: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 9

AKV

Page 10: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 10

Application selection from param. o61

Page 11: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 11

Zero cross relay control vs. traditional contactors

Traditional contactor

Mechanical life time ?

No control of Cut in or Cut out of loads -> high tear and weariness

High power PCB relay with Danfoss Zero crossing technology

High mechanical lifetime

Long lifetime on contacts due to limited (no) spark at cut in or cut out of loads

Sparks

Cut In Cut Out

Voltage = 0 Amp = 0

Page 12: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 12

Current measurement & alarms

MAX – MIN alarm!

Page 13: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 13

Programming can be done in different ways

Via Modbus with own production and test software

Via Danfoss AK-SM 720 and AK-ST 500

Via OEM programming key + PC with USB connection and Microsoft Excel

Page 14: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 14

Page 15: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 15

ID-key copy

- Parameters are stored in the ID-key + AK-CT 200A.

- AK-CT will work for 2 weeks without a ID-key

- network address (o03) is also copied

Page 16: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 16

How do I reset a “software fuse” ?

√ Fuse alarms can be seen in AKA 164 display

√ E41 = Fuse alarm on DO1

√ E42 = Fuse alarm on DO2

√ E48 = Fuse alarm on DO8

√ Flashing red Fuse LED indicate fuse alarm on one or more of the relays DO1 -> DO8

√ Fuses can be reset in 3 different ways:

1. Power Off and On via circuit breaker will restart the controller and reset fuses

2. Fuse can be reset in Service menu for output status when FuS is shown for do1 -> do8 by setting output to on

3. Fuse can be reset in configuration menu by parameter L21 to L28 set to on from AKA display or remote by setting to 1

Page 17: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 17

New controller tray – accessories

Extra connectors for multi wires

If more than 3 cable connectors are needed

Optional AKA 164 display

Can be mounted in controller tray or in display case

Controller key for late dedication

AK-CT 201, CT 450, CT550

Controller functions and copy of settings

Page 18: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 18

Space for optional display

Accessories

Prepared for optional connector

Page 19: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 19

System Manager compatibility

-SM 720 ver.2.73 OK

-SM350 ver.1.70 OK, but no template yet!

-SM800 ver.8.027 OK.

-AKA 24x (LON) partly:

missing param. with AK-CT550A:

Page 20: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 20

- Appliance shut-down function (=external main switch, but no stand by alarm)

- Modbus communication status, 0/100% = everything ok, (U45)

- Pe & AKV connector identical, careful when replacing controller!

- Not used fuses; 16A by default, set to 0A

- EEC coil not supported

- HACCP approved, CE & other electrical approvals available

- Measurement of insulation resistance @ 500V. Loads must be manually wired (can’t push manually contactors like normally)

- No Danbuss option

- EKA 183A copy key support coming from next version (sw. 1.32)

- Integrated 24h real time clock

- ECO function for evap. fans (cut fan speed when night blind down)

- 2-light relays (spot lights)

- Controller & AKV powered from L1 (1-phase)

- 0…10V output for valve OD (AO1)

Other info

Page 21: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 21

Room application

- Need 2,5 mm2 cabling, also AKV. (Check with local authorities!)

- When door function is open it signals that the door is open, usually motion detectors are ”NO” (DI7), needs extra relay

- Residual-current circuit breaker (30mA) needed for rooms

(personal safety, rail/drip tray heat)

- Only for 1-phase evaporator fan

Page 22: New ADAP-KOOL AK-CT 200 - combicool.fi ADAP-KOOL® AK-CT 200 Integrated power components Current measurements ... Many different blueprints Different power trays for 1 and 3 phase

Danfoss Food Retail February 2014 | 22

Instruct electricians to check for missing neutral!

- Normally this is not part of electrical installation inspection!