new north canopy addition and

10
DWG # SHEET TITLE 0 1 2 3 4 5 6 G0.01 TITLE SHEET O A1.01 FIRST FLOOR AND CANOPY ROOF PLAN O A1.02 ELEVATIONS, SECTIONS AND DETAILS O M0.01 MECHANICAL COVER SHEET O M1.01 MECHANICAL FIRST FLOOR PLAN O E0.01 ELECTRIC COVER SHEET O E1.01 ELECTRIC DEMOLITION PLAN - FIRST FLOOR O E1.02 ELECTRIC LIGHTING PLAN - FIRST FLOOR O E1.03 ELECTRIC POWER PLAN - FIRST FLOOR O E1.04 ELECTRIC POWER SCHEDULES O SCALE: DATE: DRAWN BY: CHECKED BY: APPROVED BY: F.B. NO. PG. CONTRACT NO: SHEET 5/22/2020 2:27:32 PM G0.01 TITLE SHEET 200126 NEW NORTH CANOPY ADDITION AND ENTRY DOOR REPLACEMENT GOLDEN TOWER APARTMENTS 05/22/2020 DWUR MAND 50 E. 11TH ST. COVINGTON, KY 41011 N N SITE MAP VICINITY MAP PROJECT DIRECTORY DRAWING INDEX ARCHITECT CT CONSULTANTS, INC. INTEGRITY TOWER BUILDING 4420 COOPER ROAD - SUITE 200 CINCINNATI, OHIO 45242 (P) 513.791.1700 OWNER NOT TO SCALE NOT TO SCALE ELECTRICAL ENGINEERING KLH ENGINEERS 1538 ALEXANDRIA PIKE FT. THOMAS, KY 41075 (P) 859.442.8050 HOUSING AUTHORITY OF COVINGTON HOUSING AUTHORITY OF COVINGTON 2300 MADISON AVE COVINGTON, KY 41011 (P) 859.491.5311 STRUCTURAL NOTES 5/22/2020 2:27:33 PM GOLDEN TOWER APARTMENTS 50 E. 11TH ST. COVINGTON, KY 41011 NEW NORTH CANOPY ADDITION AND ENTRY DOOR REPLACEMENT PROJECT LOCATION GOVERNING CODES AND DESIGN STANDARDS: DESIGN CODE: 2018 KENTUCKY BUILDING CODE (KBC) ASCE 7 - 10 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES STRUCTURAL DESIGN LOADS DEAD LOAD: SELF - WEIGHT SUPERIMPOSED DEAD LOAD ON ROOF = 10 PSF VESTIBULE FLOOR LIVE LOAD = 100 PSF ROOF LIVE LOAD = 20 PSF ROOF SNOW LOADS: GROUND SNOW LOAD, Pg = 20 PSF SNOW EXPOSURE FACTOR, Ce = 1.0 SNOW LOAD IMPORTANCE FACTOR, Is = 1.1 THERMAL FACTOR, Ct (UNHEATED) = 1.2 THERMAL FACTOR, Ct (CONTINUOUSLY HEATED) = 1.0 WIND LOADS: BASIC WIND SPEED (3 SEC. GUST, Vult) = 120 MPH WIND EXPOSURE = C EARTHQUAKE DESIGN PARAMETERS: BUILDING OCCUPANCY CATEGORY = III SEISMIC IMPORTANCE FACTOR, Ie = 1.25 Ss = 0.145 S1 = 0.079 SITE CLASS: D SEISMIC DESIGN CATEGORY = B BASIC SEISMIC FORCE RESISTING SYSTEMS: STRUCTURAL STEEL NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE RESPONSE MODIFICATION FACTOR, R = 3.00 SEISMIC COEFFICIENT, Cs = 0.064 STRUCTURAL STEEL: ALL STRUCTURAL STEEL FABRICATION AND ERECTION SHALL BE IN ACCORDANCE WITH CURRENT EDITION OF THE AISC SPECIFICATION FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS AND THE AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDING AND BRIDGES. STRUCTURAL STEEL - W - ASTM A992; PLATES - ASTM A36; HSS TUBE - ASTM A A500, GRADE B Fy = 46 KSI. ALL BOLTS, NUTS AND WASHERS SHALL BE ASTM A325 - N UNLESS NOTED OTHERWISE. SPLICING OF STRUCTURAL STEEL IS PROHIBITED EXCEPT AS DETAILED. ADHESIVE ANCHOR SYSTEMS SHALL BE HILTI HY - 200, SIMPSON SET XP, OR APPROVED EQUAL. COMPLY WITH OSHA 1926.1153. ADHESIVE ANCHORAGE INSTALLATION SHALL HAVE CONTINUOUS SPECIAL INSPECTION. D A T E B Y R E V I S I O N S 0 5 / 2 2 / 2 0 2 0 M A N D I S S U E F O R B I D D I N G A N D P E R M I T R E V R E V I S I O N S D A T E B Y 0 I S S U E F O R B I D D I N G A N D P E R M I T 0 5 / 2 2 / 2 0 2 0 M A N D

Upload: others

Post on 13-Mar-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

DWG # SHEET TITLE 0 1 2 3 4 5 6

G0.01 TITLE SHEET O

A1.01 FIRST FLOOR AND CANOPY ROOF PLAN O

A1.02 ELEVATIONS, SECTIONS AND DETAILS O

M0.01 MECHANICAL COVER SHEET O

M1.01 MECHANICAL FIRST FLOOR PLAN O

E0.01 ELECTRIC COVER SHEET O

E1.01 ELECTRIC DEMOLITION PLAN - FIRST FLOOR O

E1.02 ELECTRIC LIGHTING PLAN - FIRST FLOOR O

E1.03 ELECTRIC POWER PLAN - FIRST FLOOR O

E1.04 ELECTRIC POWER SCHEDULES O

SCALE:

DA

TE

:

DR

AW

N B

Y:

CH

EC

KE

D

BY:

AP

PR

OVE

D B

Y:

F.B

.

NO

.

PG

.

CONTRACT NO:

SHEET5/2

2/2

02

0 2

:27:3

2 P

M

G0.01

TIT

LE

SH

EE

T

200126

NE

W N

OR

TH

CA

NO

PY

AD

DIT

ION

AN

D E

NTR

Y

DO

OR

RE

PLA

CE

ME

NT

GO

LD

EN

TO

WE

R A

PA

RTM

EN

TS

05

/22

/20

20

DW

UR

MA

ND

50

E. 1

1TH

ST. C

OV

ING

TO

N, K

Y 4

10

11

N

N

SITE MAP

VICINITY MAPPROJECT DIRECTORY

DRAWING INDEX

ARCHITECT

CT CONSULTANTS, INC.

INTEGRITY TOWER BUILDING

4420 COOPER ROAD - SUITE 200

CINCINNATI, OHIO 45242

(P) 513.791.1700

OWNER

NOT TO SCALE

NOT TO SCALE

ELECTRICAL ENGINEERING

KLH ENGINEERS

1538 ALEXANDRIA PIKE

FT. THOMAS, KY 41075

(P) 859.442.8050

HOUSING AUTHORITY OF COVINGTON

HOUSING AUTHORITY OF COVINGTON

2300 MADISON AVE

COVINGTON, KY 41011

(P) 859.491.5311

STRUCTURAL NOTES

5/2

2/2

02

0 2

:27:3

3 P

M

GOLDEN TOWER APARTMENTS

50 E. 11TH ST. COVINGTON, KY 41011

NEW NORTH CANOPY ADDITION AND

ENTRY DOOR REPLACEMENT

PROJECT LOCATION

GOVERNING CODES AND DESIGN STANDARDS:

DESIGN CODE: 2018 KENTUCKY BUILDING CODE (KBC)

ASCE 7-10 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES

STRUCTURAL DESIGN LOADS

DEAD LOAD: SELF-WEIGHT

SUPERIMPOSED DEAD LOAD ON ROOF = 10 PSF

VESTIBULE FLOOR LIVE LOAD = 100 PSF

ROOF LIVE LOAD = 20 PSF

ROOF SNOW LOADS:

GROUND SNOW LOAD, Pg = 20 PSF

SNOW EXPOSURE FACTOR, Ce = 1.0

SNOW LOAD IMPORTANCE FACTOR, Is = 1.1

THERMAL FACTOR, Ct (UNHEATED) = 1.2

THERMAL FACTOR, Ct (CONTINUOUSLY HEATED) = 1.0

WIND LOADS:

BASIC WIND SPEED (3 SEC. GUST, Vult) = 120 MPH

WIND EXPOSURE = C

EARTHQUAKE DESIGN PARAMETERS:

BUILDING OCCUPANCY CATEGORY = III

SEISMIC IMPORTANCE FACTOR, Ie = 1.25

Ss = 0.145

S1 = 0.079

SITE CLASS: D

SEISMIC DESIGN CATEGORY = B

BASIC SEISMIC FORCE RESISTING SYSTEMS:

STRUCTURAL STEEL NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE

RESPONSE MODIFICATION FACTOR, R = 3.00

SEISMIC COEFFICIENT, Cs = 0.064

STRUCTURAL STEEL:

ALL STRUCTURAL STEEL FABRICATION AND ERECTION SHALL BE IN ACCORDANCE WITH

CURRENT EDITION OF

THE AISC SPECIFICATION FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL

STEEL FOR

BUILDINGS AND THE AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDING AND

BRIDGES.

STRUCTURAL STEEL - W- ASTM A992; PLATES - ASTM A36; HSS TUBE - ASTM A A500, GRADE

B Fy = 46 KSI.

ALL BOLTS, NUTS AND WASHERS SHALL BE ASTM A325-N UNLESS NOTED OTHERWISE.

SPLICING OF STRUCTURAL STEEL IS PROHIBITED EXCEPT AS DETAILED.

ADHESIVE ANCHOR SYSTEMS SHALL BE HILTI HY-200, SIMPSON SET XP, OR APPROVED

EQUAL.

COMPLY WITH OSHA 1926.1153.

ADHESIVE ANCHORAGE INSTALLATION SHALL HAVE CONTINUOUS SPECIAL INSPECTION.

DA

TE

BY

RE

VIS

ION

S

05/2

2/2

020

MA

ND

ISS

UE

FO

R B

IDD

ING

AN

D P

ER

MIT

RE

VR

EV

ISIO

NS

DA

TE

BY

0IS

SU

E F

OR

BID

DIN

G A

ND

PE

RM

IT05/2

2/2

020

MA

ND

A. VERIFY EXISTING CONDITIONS IN FIELD AND NOTIFY ARCHITECT OF ANY DISCREPANCIES.

B. EXTERIOR DIMENSIONS SHOWN ARE TO OUTSIDE FACE OF FOUNDATION WALL OR ROUGH OPENINGS. TYPICAL UNLESS NOTED OTHERWISE.

C. INTERIOR DIMENSIONS SHOWN ARE TO FACE OF PROPOSED GYP, CMU, OR

CONCRETE CONSTRUCTION, UNLESS NOTED OTHERWISE.D. PROVIDE SEALANT AT JOINTS BETWEEN ALL DISSIMILAR MATERIALS. E. NEW CARD SWIPES AND ENTRY BY INTERCOM DEVICES WILL BE PROVIDED

AND COORDINATED BY OWNER'S TECHNOLOGY ENGINEERING VENDOR.

GENERAL NOTESD E

1

2

4

3

1

A1.02

NEW

TEMPERED

VESTIBULE

149

MAIL ROOM

110

ELEVATORS

BEDROOM

105

RECEPTION

130

ADMINISTRATION

OFFICE

129

VESTIBULE

131

LOBBY

120

WOMEN

114

JANITOR

113

STORAGE

111

CLINIC

133

CLINIC

132

TELEPHONES

134

9.49.4TYP.

8.1

TYP.

8.1

9' -

1"

2

A1.02

131B

131A

149A

149B

TYP.

5.12

D.5 E.5

3 5/8" 20' - 0 3/4" 3 5/8"

A1.02

4

TYP.

5.14

6 7/8" 18' - 8" 6 7/8"

EXISTING

MECHANICAL

PIT BEYOND

EXISTING

MECHANICAL

PIT BEYOND

T/ RETAINING WALL

EXISTING

LANDSCAPING BED

T/ RETAINING WALL

EXISTING

LANDSCAPING BED3.2 9.49.4CS

D.1 E.1

9.69.6

8' -

7"

D E

1

2

4

3

TYP.

5.1

3.1

9' -

1"

A1.02

9

ELEVATORS

BEDROOM

105

RECEPTION

130

ADMINISTRATION

OFFICE

129

VESTIBULE

131

CLINIC

132

CLINIC

133

MAIL ROOM

110

STORAGE

111

JANITOR

113

WOMEN

114

LOBBY

120TELEPHONES

134

9.39.3

1' - 0"

1' -

0"

8.3

8.3

8.3

0.2

MECHANICAL

PIT BEYOND

MECHANICAL

PIT BEYOND

26.1

EXISTING BRIDGE

5.11

26.2 8.38.3

A1.02

3D E

1

1

A1.02

2.5

7.6

D.5 E.5

A1.02

4

19' - 9 3/4" 6 5/8"

3 5/8" 20' - 0 3/4" 3 5/8"

6 5

/8"

7' -

0" 5.2DECK SPAN

20' - 8"

7.9

D.1 E.1

A. VERIFY EXISTING CONDITIONS IN FIELD AND NOTIFY ARCHITECT OF ANY DISCREPANCIES.

B. WHERE REMOVING PORTIONS OF MASONRY OR CONCRETE, USE A SAW TO CUT CLEAN, SHARP LINES. REMOVE MASONRY AT NEAREST EXISTING MORTAR JOINT(S).

C. WHERE ADJACENT OR INTERSECTING CONSTRUCTION IS TO REMAIN, TRIM,

GRIND, SCRAPE, OR SAND FACES OF DEMOLISHED ITEMS FLUSH WITH ADJACENT SURFACES TO REMAIN.

D. WHERE PREPARING AN OPENING FOR A WINDOW, ONLY REMOVE AS MUCH OF THE EXISTING CONSTRUCTION AS REQUIRED. COORDINATE EXACT

LOCATION WITH PROPOSED PLANS.

GENERAL DEMOLITION NOTES

SCALE:

DA

TE

:

DR

AW

N B

Y:

CH

EC

KE

D

BY:

AP

PR

OVE

D B

Y:

F.B

.

NO

.

PG

.

CONTRACT NO:

SHEET

As indicated

5/2

2/2

02

0 2

:27:3

1 P

M

A1.01

FIR

ST F

LO

OR

AN

D C

AN

OP

Y R

OO

F P

LA

N

200126

NE

W N

OR

TH

CA

NO

PY

AD

DIT

ION

AN

D E

NTR

Y

DO

OR

RE

PLA

CE

ME

NT

GO

LD

EN

TO

WE

R A

PA

RTM

EN

TS

05

/22

/20

20

DW

UR

MA

ND

50

E. 1

1TH

ST. C

OV

ING

TO

N, K

Y 4

10

11

N1/4" = 1'-0"A1.01

2 FIRST FLOOR NEW WORK PLAN1/4" = 1'-0"A1.01

1 FIRST FLOOR DEMOLITION PLAN

N

1/4" = 1'-0"A1.01

4 NEW VESTIBULE ROOF PLAN

N

1/32" = 1'-0"A1.01

5 FIRST FLOOR KEY PLAN

KEYNOTES0.2 EXISTING CAST-IN-PLACE CANOPY ABOVE.

2.5 EXISTING CANOPY TO REMAIN.

3.1 SAWCUT AND REMOVE EXISTING CONCRETE SLAB TO PREPARE FOR NEW

STOREFRONT ASSEMBLY ATTACHMENT.

3.2 NEW SAWCUT LINE.

5.1 DEMO EXISTING HANDRAIL.

5.2 NEW CANOPY WITH TPO ROOF MEMBRANE.

5.11 SAWCUT AND REMOVE EXISTING CARD ACCESS TERMINAL - EXTEND WIRING

TO NEW LOCATION.

5.14 BEAM UNDER VESTIBULE SLAB, TYP. OF 2.

7.6 SLOPE NEW CANOPY TO EXISTING CANOPY DRAINS @ 3/4"/12".

7.9 EXISTING ROOF TO RECEIVE NEW CONTINUOUS TPO MEMBRANE.

8.1 NEW ALUMINUM PROJECTED STOREFRONT ASSEMBLY WITH AUTOMATIC

SLIDING DOORS.

8.3 DEMO EXISTING STOREFRONT ASSEMBLY.

9.3 GRIND AND PREPARE CONRETE FOR NEW SEALING.

9.4 NEW VESTIBULE FLOORING - POLISHED CONCRETE, SEALER ONLY.

9.6 NEW BRIGHT WHITE GLOSS PAINT TOUCHUP INSIDE NEW VESTIBULE TO

MATCH NEW ADJACENT WALL PANELS. PREPARE AND SAND EXISTING

SURFACE WITH JOINT COMPOUND BEFORE PAINTING.

26.1 REMOVE EXISTING WALL PACK THIS AREA.

26.2 REMOVE KNOX BOX ADJACENT TO EXISTING DOORS. REINSTALL AFTER NEW

FINISHES ARE INSTALLED.

RE

VR

EV

ISIO

NS

DA

TE

BY

0IS

SU

E F

OR

BID

DIN

G A

ND

PE

RM

IT05/2

2/2

020

MA

ND

DE

1

A1.02

6 7/8"

UNIT INSIDE DIMENSION

18' - 8"6 7/8"

D.5E.5

8' -

1"

1' -

0"

3' -

0"

12

' - 0

"

5.10

D.1E.1

5.8 5.21T/ FIRST FLOOR

0' - 0"

1

2.6

2.2

2.5

2.1

A1.02

8

2.2

9' - 1"

9.5

5.3

7.4

UNIT HEATER

5.22

5.21

5.73/4" / 1'-0"

2' - 9 7/16"

5.6

5.18

8' - 1"

5.20

7.8

5.8

7.5

12

' - 0

"

7' -

5"

8"

1' -

0"

9' -

0"

26.1

7.9

5.21

5.9 5.19

5.15

5.225.22

5.15

7.4

2' - 8 23/32" 4' - 7 1/32" 4' - 0"

7' - 7" 4' - 0"

11' - 7"

11' - 7 1/4"

11' - 5 1/4"

9' - 8 1/2"

T/ STEEL

T/ STEEL

T/ STEEL

5.23

5.225.24

5.23

5.24

5.23BEYOND

T/ FIRST FLOOR

0' - 0"

3.1

2.2

2.2

7.7 5.17

TYP3/16

3.3

5.15

0' - 6"

0' -

9"

D

1' - 0"

1' -

0"

3.1

2.2

D.5 D.1

AL ALUMINUMAN ANODIZED ALUMINUMEX EXISTING

EXT. EXTERIORFF FACTORY FINISHED

DOOR SCHEDULE

ABBREVIATIONS HARDWARE SETSGLAZING

G1 1" CLEAR TEMPERED INSULATING GLASSG# GLASS TYPEHM HOLLOW METAL

PT PAINTED

1. ACCESS DOOR - PRESENCE SENSOR - ALWAYS OPERABLE

2. ACCESS DOOR - PRESENCE SENSOR - ALWAYS CONTROLLED

T/ FIRST FLOOR

0' - 0"

E

2.2

9.5

A1.02

5

E.5

5.6

5.9

7.5

7.4

5.8

8' - 11 3/8"

5.18

E.1

5.21

5.22

9.7

E

5.10

5.4

5.8

E.5

1"3 5/8"3"

5.21

T/ FIRST FLOOR

0' - 0"

1

11' - 7"

5.8

2.1

12

' - 0

"

8' - 1" 3' - 6"

1' -

4"

2.2

5.10

7.107.10

9' - 1" 2' - 6"

D E

1

NEW

TEMPERED

VESTIBULE

149

AFFACT

8'-11 3/8"

D.5 E.5

9.5

5.13

11

' - 7

"

19' - 9 3/4"

5.21

D.1 E.1

A1.02

7

E

1

E.5E.1

2.18.1

5.8

5.21

5.4

7.117.11

SCALE:

DA

TE

:

DR

AW

N B

Y:

CH

EC

KE

D

BY:

AP

PR

OVE

D B

Y:

F.B

.

NO

.

PG

.

CONTRACT NO:

SHEET

As indicated

5/2

2/2

02

0 2

:27:3

2 P

M

A1.02

ELE

VA

TIO

NS

, S

EC

TIO

NS

AN

D D

ETA

ILS

200126

NE

W N

OR

TH

CA

NO

PY

AD

DIT

ION

AN

D E

NTR

Y

DO

OR

RE

PLA

CE

ME

NT

GO

LD

EN

TO

WE

R A

PA

RTM

EN

TS

05

/22

/20

20

DW

UR

MA

ND

50

E. 1

1TH

ST. C

OV

ING

TO

N, K

Y 4

10

11

1/2" = 1'-0"A1.02

3 NORTH ELEVATION1/2" = 1'-0"A1.02

1 SECTION THRU VESTIBULE

1 1/2" = 1'-0"A1.02

8 SECTION DETAIL1 1/2" = 1'-0"A1.02

9 PLAN DETAIL

NU

MB

ER

DOOR FRAME

FIN

ISH

FRAME

HA

RD

WA

RE

SE

T

KE

YS

IDE

RO

OM

#

REMARKS

SIZE

RA

TIN

G (

MIN

.)

GLA

ZIN

G

MA

TE

RIA

L

FIN

ISH

TY

PE

MA

TE

RIA

L

TH

RO

AT

DE

PT

H (

IN.)

HE

AD

JA

MB

SIL

L

W H T

131 A 18' - 8" 9' - 0" 0' - 1 3/4" - G1 AL FF - AL AN 0' - 5 3/4" MFG. MFG. MFG. 1 EXT. DORMAKABA ESA200 ENTRANCE SYSTEM (BOD)

131 B 18' - 8" 9' - 0" 0' - 1 3/4" - G1 AL FF - AL AN 0' - 5 3/4" MFG. MFG. MFG. 2 131 DORMAKABA ESA200 ENTRANCE SYSTEM (BOD)

149 A 18' - 8" 9' - 0" 0' - 1 3/4" - G1 AL FF - AL AN 0' - 5 3/4" MFG. MFG. MFG. 2 149 DORMAKABA ESA200 ENTRANCE SYSTEM (BOD)

149 B 18' - 8" 9' - 0" 0' - 1 3/4" - G1 AL FF - AL AN 0' - 5 3/4" MFG. MFG. MFG. 1 EXT. DORMAKABA ESA200 ENTRANCE SYSTEM (BOD)

3/4" = 1'-0"A1.02

2 WALL SECTION

1 1/2" = 1'-0"A1.02

5 SECTION DETAIL

1/2" = 1'-0"A1.02

4 EAST ELEVATION (WEST SIM.)

1/4" = 1'-0"A1.02

6 REFLECTED CEILING PLAN

KEYNOTES2.1 EXISTING CONCRETE WALL TO REMAIN.

2.2 EXISTING CONCRETE SLAB TO REMAIN.

2.5 EXISTING CANOPY TO REMAIN.

2.6 EXISTING RETAINING WALL TO REMAIN.

3.1 SAWCUT AND REMOVE EXISTING CONCRETE SLAB TO PREPARE FOR NEW

STOREFRONT ASSEMBLY ATTACHMENT.

3.3 FILL WITH CONCRETE.

5.3 3" INSULATED METAL PANEL - SMOOTH/ANTIQUE BRONZE MATTE FINISH.

5.4 3 5/8" METAL STUD.

5.6 HSS 8 x 4 x 3/16" BEAM, TYP. BETWEEN COLUMNS & TOP & LOWER BEAMS.

5.7 8" METAL STUD.

5.8 3" INSULATED METAL PANEL - AGED BRONZE FINISH.

5.9 GALVANIZED 3N20 DECKING WITH 3/4" PUDDLE WELDS AT EACH FLUTE AT

SUPPORTS AND AT 24" O.C. AT DECK SIDES. SPAN AS INDICATED.

5.10 PREFINISHED METAL COPING CAP - AGED BRONZE FINISH.

5.13 NEW 3 5/8" METAL STUD WALL ENCLOSURE WITH 1 1/2" EXTERIOR METAL

WALL PANELS.

5.15 HSS 4 x 4 x 3/16", TYP. OF 2 COLUMNS & TYP. OF LOWER BEAMS ON 2 SIDES.

5.17 BASEPLATE 3/8" x 5" x 10" WITH (2) GALVANIZED 5/8" DIAMETER ADHESIVE

ANCHORS WITH 5" EMBED, TYP. 2 PLACES.

5.18 W8x15, WITHIN 6" OF SLAB EDGE, TYP. BOTH SIDES.

5.19 END PLATE 3/8" x 8" VERT x 7" HORIZ WITH (2) GALVANIZED 5/8" ADHESIVE

ANCHORS @ 4" O.C. WITH 5" EMBED, TYP. EACH END. SOUTH END OF LOWER

EAST & WEST BEAMS SIMILAR.

5.20 BENT PLATE 1/4" WITH 4" LEGS WITH 1/2" DIAMETER ADHESIVE ANCHORS @

24" O.C. WITH 4" EMBED.

5.21 1" SINGLE SKIN METAL PANEL WITH 1/2" GLASS MATT FIBER GYPSUM

SHEATHING BACKUP - GLOSS WHITE FINISH.

5.22 TOP 8 x 4 x 3/16" BEAM, TYP. 3 SIDES. EAST & WEST SIDES CONTINUOUS OVER

COLUMNS.

5.23 BEAM-TO-BEAM CONNECTIONS WITH 3/8" END PLATES WITH (2) 5/8"

THREADED RODS WELDED TO HSS, @ 3" O.C., TYP. BEAM-TO-COLUMN

CONNECTIONS SIMILAR.

5.24 CONNECT EAST & WEST TOP BEAMS TO EACH COLUMN WITH A 3/8" x 4" x 10"

COLUMN CAP PLATE WITH (2) 5/8" THREADED RODS WELDED TO HSS BEAM.

7.4 3" POLYISO INSULATION.

7.5 NEW TPO ROOF MEMBRANE OVER 3" POLYISO INSULATION BOARD.

7.7 1" +/- NON-SHRINK GROUT ON TOP OF BEAM, TYP. AT BASEPLATES &

ENDPLATES AT CONCRETE, UNO.

7.8 1" +/- NON-SHRINK GROUT ON TOP OF BEAM, TYP. 2 PLACES.

7.9 EXISTING ROOF TO RECEIVE NEW CONTINUOUS TPO MEMBRANE.

7.10 CONTINUOUS WEATHERTIGHT GASKETING AND SEALANT FLUSH WITH

EXISTING CONCRETE EXTERIOR FACE.

7.11 POLYURETHANE-BASED INTEGRAL COLOR NON-SAG ELASTOMERIC SEALANT

BOTH SIDES, TYPICAL AT ALL DISCONTINOUS SURFACES.

8.1 NEW ALUMINUM PROJECTED STOREFRONT ASSEMBLY WITH AUTOMATIC

SLIDING DOORS.

9.5 NEW 2x2 ACOUSTIC CEILING SYSTEM - ARMSTRONG KITCHEN ZONE 673.

9.7 ALIGN OUTSIDE EDGE OF NEW STUDS WITH OUTSIDE EDGE OF EXISTING

CONCRETE WALKWAY.

26.1 REMOVE EXISTING WALL PACK THIS AREA.

1 1/2" = 1'-0"A1.02

7 VESTIBULE WALL INTERSECTION - DETAIL

RE

VR

EV

ISIO

NS

DA

TE

BY

0IS

SU

E F

OR

BID

DIN

G A

ND

PE

RM

IT05/2

2/2

020

MA

ND

STANDARD HVAC ABBREVIATIONS

AAV AUTOMATIC AIR VENTACCESS ACCESSORIESAD ACCESS DOORAFF ABOVE FINISHED FLOORAMP AMPEREAP ACCESS PANELAPD AIR PRESSURE DROPARI AIR CONDITIONING AND REFRIGERATION INSTITUTEASME AMERICAN SOCIETY OF MECHANICAL ENGINEERSBAS BUILDING AUTOMATION SYSTEMBD BACKDRAFT DAMPERBHP BRAKE HORSEPOWERBTU BRITISH THERMAL UNITBTUH BRITISH THERMAL UNIT PER HOURCD CEILING DIFFUSERCFH CUBIC FEET PER HOURCFM CUBIC FEET PER MINUTECHWR CHILLED WATER RETURNCHWS CHILLED WATER SUPPLYCI CAST IRONCLG COOLINGCO CARBON MONOXIDECO2 CARBON DIOXODECOP COEFFICIENT OF PERFORMANCECV CONSTANT VOLUMECWR CONDENSER WATER RETURNCWS CONDENSER WATER SUPPLYDB DECIBELSDB DRY-BULB TEMPERATUREDC DISCONNECTDDC DIRECT DIGITAL CONTROLSDEG DEGREE DELTA(CHANGE IN TEMPERATURE)DIA DIAMETERDIW DEIONIZED WATERDP DEW POINT TEMPERATUREDX DIRECT EXPANSIONEA EXHAUST AIREAT ENTERING AIR TEMPERATUREEER ENERGY EFFICIENCY RATIOEG EXHAUST GRILLEEMERG EMERGENCY POWERESP EXTERNAL STATIC PRESSUREEWT ENTERING WATER TEMPERATUREEX. EXISTINGF FAHRENHEITF&T FLOAT AND THERMOSTATICFA FREE AREAFD FIRE DAMPERFLA FULL LOAD AMPERESFPM FEET PER MINUTEFPS FEET PER SECONDFT FEETFURN FURNISHEDGA GAUGEGAL GALLONSGPM GALLONS PER MINUTE

HD HEADHOA HAND/OFF/AUTOMATIC

HP HORSEPOWERHPR HIGH PRESSURE RETURN

(STEAM CONDENSATE)HSTAT HUMIDISTATHTG HEATINGHWR HEATING HOT WATER RETURNHWS HEATING HOT WATER SUPPLYHZ HERTZI/O INPUT/OUTPUTIAQ INDOOR AIR QUALITYIN HG INCHES OF MERCURYIN WC INCH WATER COLUMNIN WG INCH WATER GAUGEIPLV INTERGRATED PART LOAD VALUEINST INSTALLEDKW KILOWATTKWH KILOWATT HOURLAT LEAVING AIR TEMPERATURELBS/HR POUNDS PER HOURLF LINEAR FOOT (FEET)LPR LOW PRESSURE RETURN

(STEAM CONDENSATE)LPS LOW PRESSURE STEAMLWT LEAVING WATER TEMPERATUREMAX MAXIMUMMBH 1000 BTUHMCA MINIMUM BRANCH CIRCUIT AMPACITYMERV MINIMUM EFFICIENCY REPORTING VALUEMIN MINIMUMMOD MOTOR OPERATED DAMPERMPR MEDIUM PRESSURE RETURN

(STEAM CONDENSATE)MPS MEDIUM PRESSURE STEAMMRI MAGNETIC RESONANCE IMAGINGMVD MANUAL VOLUME DAMPERNA NOT APPLICABLENC NOISE CRITERIANC NORMALLY CLOSEDNO NORMALLY OPENNTS NOT TO SCALEOA OUTSIDE AIROCP OVER CURRENT PROTECTIONPD PRESSURE DROPPPM PARTS PER MILLIONPRS PRESSURE REGULATING (VALVE) STATIONPRV PRESSURE REGULATING VALVEPSI POUNDS PER SQUARE INCHPSIA POUNDS PER SQUARE INCH – ABSOLUTEPSIG POUNDS PER SQUARE INCH – GAGERA RETURN AIRRAT RETURN AIR TEMPERATURERH RELATIVE HUMIDITYRL REFRIGERANT LIQUID LINERLA RUN LOAD AMPERE

RO REVERSE OSMOSISRPM REVOLUTIONS PER MINUTERS REFRIGERANT SUCTIONSA SUPPLY AIRSAT SUPPLY AIR TEMPERATURESC SHADING COEFFICIENTSCD SMOKE CONTROL DAMPERSD SMOKE DETECTORSENS SENSIBLE HEATSP STATIC PRESSURETAB TESTING, ADJUSTING, BALANCETDH TOTAL DYNAMIC HEADTDS TOTAL DISSOLVED SOLIDSTSP TOTAL STATIC PRESSURETSTAT THERMOSTATUL UNDERWRITERS LABORATORYVAV VARIABLE AIR VOLUMEVFD VARIABLE FREQUENCY DRIVEWB WET-BULB (TEMPERATURE)WG WATER GAGEWPD WATER SIDE PRESSURE DROPWIRE WIRED

MECHANICAL LEGEND

SYMBOL DESCRIPTION

PLAN-VIEW LINE TYPESWORK SHOWN FADED INDICATES EXISTING WORK TO REMAIN OR NEW WORK BY OTHERS AS APPLICABLE

WORK SHOWN BOLD-DASHED INDICATES SELECTIVE DEMOLITION WORK

WORK SHOWN BOLD-CONTINUOUS INDICATES NEW WORK

MECHANICAL STATS & SENSORS

LOW VOLTAGE THERMOSTATT

SCALE:

DATE:

DRAWN B

Y:

CHECKED

BY:

APPROVED B

Y:

F.B

.

NO.

PG.

CONTRACT NO:

SHEET

WWW.KLHENGRS.COM

MECHANICAL/ELECTRICALENGINEERS

1538 ALEXANDRIA PIKE, SUITE 11 FT. THOMAS, KENTUCKY 41075800-354-9783 859-442-8050859-442-8058 FAX

LEXINGTON, KENTUCKYLOUISVILLE, KENTUCKYCOLUMBUS, OHIONEW YORK, NEW YORK

KOHRS LONNEMANN HEIL ENGINEERS, INC.

1/8" = 1'-0"

5/1

4/2

020

12:4

4:4

2 P

M

M0.01

MECHANICAL COVER SHEET

200126

CANOPY REPLACEMENT

GOLDEN TOWERS APARTMENTS

04/20/2020

CES

MVA

50 E. 11TH ST. COVINGTON, KY 41011

Equipment shall be braced and labeled by the equipment manufacturer to withstand the minimum scheduled available fault current value for listed equipment.

HVAC UNIT HEATERS SCHEDULE

EQUIPMENTMARK DESCRIPTION

WEIGHT(lbs) MANUFACTURER MODEL VOLTS PHASE HTG KW

FLA(amps)

MCA(amps)

OCP(amps)

AVAILABLEFAULT CURRENT

ECH-1 WALL AND CEILING HEATER 45 BERKO FFCH-558 208 3 5 24 1634

Electric Wall Heater/ Unit Heater Sequence of Operation

1. Provide a self-contained integral thermostat with adjustable setpoint. On a call for heating, fan shall start and coil shall activate to maintain room temperature setpoint.

REV

REVISIO

NS

DATE

BY

0IS

SUE FOR B

IDDIN

G AND PERMIT

05/22/2020

MJG

05/14/2020

D E

1

2

4

3

D.5 E.5

VESTIBULE

149

STORAGE

111

CLINIC

133

CLINIC

132

VESTIBULE

131

MAIL ROOM

110

ELEVATORS

999

WOMEN

114

Room

B-33

JANITOR

113

BEDROOM

105

Room

B-44

RECEPTION

130

ADMINISTRATION

OFFICE

129

LOBBY

120TELEPHONES

134

ECH-1

D E

1

2

4

3

D.5 E.5

SCALE:

DATE:

DRAWN B

Y:

CHECKED

BY:

APPROVED B

Y:

F.B

.

NO.

PG.

CONTRACT NO:

SHEET

WWW.KLHENGRS.COM

MECHANICAL/ELECTRICAL

ENGINEERS

1538 ALEXANDRIA PIKE, SUITE 11

FT. THOMAS, KENTUCKY 41075

800-354-9783 859-442-8050

859-442-8058 FAX

LEXINGTON, KENTUCKY

LOUISVILLE, KENTUCKY

COLUMBUS, OHIO

NEW YORK, NEW YORK

KOHRS LONNEMANN HEIL ENGINEERS, INC.

As indicated

5/1

4/2

020

12:4

4:4

3 P

M

M1.01

MECHANICAL FIRST FLOOR PLAN

200126

CANOPY REPLACEMENT

GOLDEN TOWERS APARTMENTS

04/20/2020

CES

MVA

50 E. 11TH ST. COVINGTON, KY 41011

1/4" = 1'-0"M1.01

1 MECHANICAL NEW FIRST FLOOR PLAN

1/4" = 1'-0"M1.01

2 MECHANICAL DEMOLITION FIRST FLOOR PLANN1/32" = 1'-0"

KEYPLAN

REV

REVISIO

NS

DATE

BY

0IS

SUE FOR B

IDDIN

G AND PERMIT

05/22/2020

MJG

05/14/2020

ELECTRIC DESIGN CRITERIA

APPLICABLE BUILDING CODES

2018 KENTUCKY BUILDING CODE (BASED ON THE INTERNATIONAL BUILDING CODE)2017 NFPA 70 - NATIONAL ELECTRICAL CODE2013 NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE2012 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)

GENERAL ELECTRICAL INSTALLATION NOTES

A. CODE COMPLIANCE: PROVIDE ALL ELECTRICAL WORK COMPLIANT WITH ALL PREVAILING CODES.B. LISTINGS: PROVIDE MATERIALS, COMPONENTS AND ASSEMBLED COMPONENTS WITH LISTINGS AND

LABELS FROM A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL), MANUFACTURED, LISTED AND LABELED FOR THEIR INTENDED USE.

C. RATED BUILDING SURFACES: SEPARATE DEVICE BOXES BY A MINIMUM OF 6 INCHES WHERE INSTALLED BACK-TO-BACK WITHIN DEMISING WALLS TO MAINTAIN REQUIRED FIRE AND SOUND RATING (TYPICAL OF ALL DEVICE BOXES INSTALLED ON DEMISING WALLS). PROVIDE LISTED FIRE-RATED WRAPS AROUND ALL RECESSED OUTLET, DEVICE AND EQUIPMENT BOXES IN FIRE/SMOKE RATED WALLS, CEILINGS AND FLOORS TO MEET OR EXCEED THE RESPECTIVE FIRE/SMOKE RATING OF THE SURFACE.

D. RATED PENETRATIONS: SEAL ALL PENETRATIONS THROUGH FIRE-RATED AND/OR SMOKE-RATED MEMBRANES (FLOORS, WALLS, CEILINGS, ETC.) USING SEALANT PRODUCTS THAT MEET OR EXCEED THE RATING OF THE RESPECTIVE MEMBRANE.

E. GANGED DEVICES: INSTALL WIRING DEVICES GANGED WHEREVER POSSIBLE FOR INSTANCES WHERE THEY ARE SHOWN TOGETHER. THIS INCLUDES LOCATIONS ABOVE COUNTERS AND WORK SURFACES WHERE APPLICABLE.

F. OUTLET BOXES NEAR CORNERS: INSTALL WALL-MOUNTED SWITCHES, CONTROLS, RECEPTACLES, OUTLETS, ETC. AT LEAST 6 INCHES FROM WALL CORNERS.

G. CONCEALMENTS: CONCEAL ALL CONDUIT DROPS AND RISES WITHIN WALLS, AND PROVIDE FLUSH-MOUNTED WALL OUTLET BOXES UNLESS OTHERWISE INDICATED.

H. DOCUMENTS OF OTHER TRADES: REVIEW DOCUMENTS OF OTHER TRADES, INCLUDING ARCHITECTURAL, PRIOR TO SUBMITTING A BID. PROVIDE ELECTRICAL WORK FOR EQUIPMENT, DEVICES, ETC. OF OTHER TRADES AS REQUIRED TO RENDER THEM FULLY OPERATIONAL. REFER TO ARCHITECTURAL ELEVATIONS FOR INTENDED LOCATIONS AND MOUNTING HEIGHTS FOR EQUIPMENT AND OUTLETS, ETC. PRIOR TO COMMENCING WITH ANY RELATED ROUGH-IN WORK.

I. SCHEMATIC REPRESENTATIONS: CIRCUITING WORK SHOWN ON DRAWINGS IS FOR SCHEMATIC GENERAL GRAPHIC REPRESENTATION ONLY. DETERMINE SPECIFICS IN FIELD (POINT-TO-POINT ROUTING, HOME-RUN LOCATIONS, METHODS OF CONCEALMENT, ETC.). LOCATIONS AND ROUTING INDICATED ON PLANS ARE SCHEMATIC AND DIAGRAMMATIC IN NATURE. LAYOUT AND INSTALL ALL ELECTRICAL WORK IN STRICT COMPLIANCE WITH CHAPTER 1, PART II, ARTICLE 110.26 OF THE LATEST ADOPTED EDITION OF THE NATIONAL ELECTRICAL CODE (NFPA 70).

J. HOME-RUN DESIGNATIONS: HOME-RUN DESIGNATIONS INDICATED ON PLANS ARE SCHEMATIC DESIGNATIONS ONLY. DETERMINE EXACT CIRCUIT ASSIGNMENTS IN FIELD BASED ON FIELD CONDITIONS. PROVIDE COLOR-CODED CONDUCTOR INSULATION ACCORDINGLY, CODED PROPERLY DEPENDING ON SYSTEM, PHASE, NEUTRAL, ETC. PROVIDE EQUIPMENT AND PANELBOARD SCHEDULES THAT ACCURATELY INDICATE INSTALLED CONDITIONS.

K. LOCAL DISCONNECTS AND CONTROLS AT EQUIPMENT: LOCAL DISCONNECTS AND LOCAL CONTROLS SHOWN AT OR ON EQUIPMENT IN PLAN-VIEW ARE SHOWN FOR SCHEMATIC ASSOCIATIONS ONLY. AVOID INSTALLING DISCONNECTS OR CONTROLS ON EQUIPMENT ENCLOSURES. INSTALL ON ADJACENT WALLS OR BUILDING STRUCTURE, OR PROVIDE FIELD-FABRICATED UNISTRUT OR EQUIVALENT ASSEMBLIES AS NEEDED. PROVIDE FIELD COORDINATION WITH SITE CONDITIONS AND OTHER TRADES, AND PROVIDE ALL RELATED WORK IN STRICT COMPLIANCE WITH NFPA 70, INCLUDING ARTICLE 110.26.

L. EQUIPMENT & LOAD COORDINATION: REFER TO AND COORDINATE WITH POWER FLOOR PLANS, EQUIPMENT SCHEDULES (INCLUDING EQUIPMENT COORDINATION SCHEDULES), DRAWINGS OF ALL TRADES, ALL DIVISIONS AND SECTIONS OF SPECIFICATIONS AND INSTALLERS OF ALL TRADES. BASED ON ACTUAL EQUIPMENT BEING PROVIDED, DETERMINE AND PROVIDE APPROPRIATE BREAKERS, FUSES, CONDUCTORS, CONTROLS, POWER DISTRIBUTION EQUIPMENT, ETC. PERFORM THESE SERVICES PRIOR TO FURNISHING POWER DISTRIBUTION EQUIPMENT SUBMITTALS.

M. EXTERIOR ELECTRICAL WORK AND WORK SUBJECT TO MOISTURE: EXTERIOR ELECTRICAL WORK SHALL BE WEATHERPROOF AND WATER-TIGHT, AND SHALL BE RUST-RESISTANT. PROVIDE XHHW-2 CONDUCTORS FOR ALL APPLICATIONS THAT ARE BELOW GRADE OR SUBJECT TO MOISTURE. PROVIDE MINIMUM NEMA 3R ENCLOSURES FOR ALL OUTDOOR EQUIPMENT AND ALL INDOOR EQUIPMENT THAT IS SUBJECT TO MOISTURE. PROVIDE NEMA 1 ENCLOSURES FOR ALL OTHER INDOOR EQUIPMENT.

N. EQUIPMENT GROUNDING CONDUCTORS: PROVIDE EQUIPMENT GROUNDING CONDUCTORS IN STRICT COMPLIANCE WITH THE LATEST ADOPTED EDITION OF THE NATIONAL ELECTRICAL CODE (NFPA 70), INCLUDING ARTICLE 250 AND TABLE 250.122. THESE CONDUCTORS MAY OR MAY NOT BE INDICATED ON SINGLE-LINE DIAGRAMS OR ELSEWHERE, BUT SHALL BE PROVIDED UNDER BASE BID NEVERTHELESS.

O. OVERHEAD WORK: HOLD ALL NEW OVERHEAD ELECTRICAL WORK AS TIGHTLY AS POSSIBLE TO THE BOTTOM OF THE OVERHEAD STRUCTURE. DO NOT INSTALL ANY ELECTRICAL WORK WITHIN SIX INCHES OF ROOF DECKING.

P. COORDINATION DRAWINGS: LAYOUT ALL PROPOSED RACEWAY ROUTING, ELEVATIONS, INSTALLATION METHODS, ETC. ON COORDINATION DRAWINGS AND COORDINATE ALL PROPOSED RACEWAY ROUTING WITH ALL AFFECTED TRADES PRIOR TO COMMENCING WITH WORK. IN ADDITION, REVIEW THE INFORMATION WITH ARCHITECT, ENGINEER AND OWNER FOR ALL AREAS WHERE THE RACEWAYS WILL BE VISIBLE AFTER COMPLETION OF CONSTRUCTION.

Q. JUNCTION AND PULL BOXES: LOCATE JUNCTION AND PULL BOXES SO THAT THEY REMAIN ACCESSIBLE AFTER ALL CONSTRUCTION WORK IS COMPLETE. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO COMMENCEMENT OF THE WORK. LOCATE BOXES IN A MANNER THAT AVOIDS HAVING TO USE ACCESS PANELS. IF ACCESS PANELS ARE INEVITABLE, PROVIDE THEM RATED TO MEET OR EXCEED THE FIRE AND/OR SMOKE RATINGS OF THE RESPECTIVE CEILING OR WALL, AND OBTAIN APPROVAL OF DESIGN PROFESSIONALS FOR EACH LOCATION.

R. CONDUCTOR TERMINATIONS: IN CASES WHERE CONDUCTOR SIZES ARE TOO LARGE TO FIT INTO LUGS/TERMINALS, PROVIDE APPROPRIATE FACTORY LUG KITS FOR AFFECTED EQUIPMENT IF AVAILABLE. ELSEWHERE, PROVIDE INSULATED BUTT-SPLICES OR EQUIVALENT METHOD, WITH TAILS SIZED TO FIT LUGS/TERMINALS. PROVIDE SPLICES IN SEPARATE BOXES IF REQUIRED BASED ON FIELD CONDITIONS, BOX SIZE LIMITATIONS, ETC. CONCEAL BOXES IN ACCESSIBLE OVERHEAD JOIST SPACES IN FINISHED REGULARLY OCCUPIED AREAS.

ELECTRIC LEGEND

SYMBOL DESCRIPTION

LIGHTING AND LIGHTING CONTROLSLUMINAIRE (REFER TO THE LUMINAIRE SCHEDULE)NOTE THAT OTHER SHAPES MAY ALSO BE USED TO REPRESENT LUMINAIRES

SHADED LUMINAIRES DENOTE THOSE CONNECTED TO EMERGENCY OR STANDBY POWER AS APPLICABLE(UNSWITCHED LUMINAIRES ARE EGRESS LIGHTS AND/OR NIGHT-LIGHTS THAT OPERATE 24/7)

SINGLE / DOUBLE SIDED EXIT SIGNCONNECT AHEAD OF SWITCHING & CONFIGURE ARROWS TO INDICATE DIRECTION OF EGRESS TRAVEL

WALL MOUNT

A = LUMINAIRE TYPE, NL = NIGHT-LIGHT (UNSWITCHED), a = SWITCHING DESIGNATION, EL = EGRESS LUMINAIRE (ILLUMINATES PATH OF EGRESS, ON ALL TIMES SPACE IS OCCUPIED)

A

ELa

NL

RECEPTACLES AND MISCELLANEOUS OUTLETSSINGLE ("SIMPLEX"), DUPLEX, AND DOUBLE DUPLEX ("QUAD") RECEPTACLE RESPECTIVELY

RECEPTACLE ATTRIBUTES42" = MOUNT RECEPTACLE AT THIS HEIGHT ABOVE GRADE / FINISHED FLOORC = INSTALL ABOVE COUNTER AND BACKSPLASHH = INSTALL RECEPTACLE HORIZONTALLYL = LIT (PROVIDE ILLUMINATED FACE OR INDICATOR LIGHT TO INDICATE THERE IS POWER TO RECEPTACLE)SW = SPLIT WIREDT = TAMPER-RESISTANTW = WEATHER PROOF WHILE IN USE COVER AND WEATHER RESISTANT RECEPTACLE

C

W42"

H

SW L

T

DOOR OPERATORS/DEVICES

ELECTRIC DOOR OPERATORMANUAL (LEFT) AUTOMATIC (RIGHT)

PUSH PLATE FOR MANUAL CONTROL OF ELECTRIC DOOR OPERATOR

MISCELLANEOUSMOTOR RATED TOGGLE SWITCH, MANUAL STARTER WITH PILOT LIGHT, AND MANUAL STARTER WITH PILOT LIGHT WITH EXTERNAL RELAY FOR CONTROL OR MONITORING RESPECTIVELY - ALL MAY BE KEYED "K"

MS MSR

ELECTRICAL SWITCHBOARD OR SWITCHGEAR(DIMENSIONS MAY VARY)

FRONT

ELECTRICAL PANELBOARD OR DISTRIBUTION BOARD(DIMENSIONS MAY VARY / FLUSH OR SURFACE MOUNTED AS INDICATED)

OIL FILLED TRANSFORMERPAD POLE

SINGLE LINE DIAGRAMELECTRIC UTILITY COMPANY METER AND ASSOCIATED CURRENT TRANSFORMERS

M

HD = HIGH DENSITY METERING CABINET/BANK MOUNTED TO TIGHTLY GROUP ALL METERS TOGETHERM

HD

CUSTOMER ELECTRIC METER AND ASSOCIATED CURRENT TRANSFORMERS

ELECTRICAL PANELBOARD OR DISTRIBUTION BOARDPANEL NAME

ELECTRICAL SWITCHBOARD OR SWITCHGEAR

AUTOMATIC TRANSFER SWITCH

SURGE PROTECTIVE DEVICE

ELECTRIC LEGEND

SYMBOL DESCRIPTION

WIRE / CABLE / RACEWAYBRANCH CIRCUIT HOME RUN WITH PANEL NAME AND CIRCUIT NUMBER(S)

LPA-1,3

CABLING / RACEWAY INSTALLED CONCEALED IN WALLS OR ABOVE CEILING

CABLING / RACEWAY INSTALLED BELOW FLOOR OR GRADE

CABLE TRAY

CONDUIT UP OR DOWNUPDN

ABBREVIATIONS

(R) RELOCATE FIXTURE, EQUIPMENT OR DEVICE 42" DISTANCE ABOVE FINISHED FLOOR / GRADE /

PAVEMENT AF AMP FRAME OF FUSED SWITCH OR CIRCUIT

BREAKER AFCI ARC-FAULT CIRCUIT INTERRUPTER AIC AMPS INTERRUPTING CURRENT AT AMP TRIP OF FUSED SWITCH OR CIRCUIT

BREAKER ATS AUTOMATIC TRANSFER SWITCH

BAS BUILDING AUTOMATION SYSTEM

C.T.C. WORK UNDER DIVISION 27 OR 28 AS APPLICABLE

C/B CIRCUIT BREAKER CH COUNTER HEIGHT OR SPECIAL HEIGHT DEVICE DW DISHWASHER

E EMERGENCY E.C. WORK UNDER DIVISION 26 EMS ENERGY MANAGEMENT SYSTEM EPO EMERGENCY POWER OFFER EQUIPMENT ROOMERM ENERGY REDUCTION MAINTENANCE SWITCH ESP EMERGENCY STANDBY RATINGETR EXISTING TO REMAINEWC ELECTRIC WATER COOLER EX. EXISTING

FBO FURNISHED BY OTHERS - INSTALLED AND WIRED BY E.C.

FIBO FURNISHED AND INSTALLED BY OTHERS -WIRED BY E.C.

FP RECEPTACLE TO BE USED FOR A FLAT PANEL DISPLAY.

FWE FURNISHED WITH EQUIPMENT BY OTHERS -INSTALLED AND WIRED BY E.C.

GD GARBAGE DISPOSAL GFEP GROUND FAULT EQUIPMENT PROTECTION GFI / GFCI GROUND FAULT CIRCUIT INTERRUPTER DEVICE GND GROUND

H.C. WORK UNDER DIVISION 23 H.O.A. "HAND - OFF - AUTO" SWITCH

IG ISOLATED GROUND

LR LEGALLY REQUIRED STANDBYLI LONG - INSTANTANEOUS LSI LONG - SHORT - INSTANTANEOUS LSIG LONG - SHORT - INSTANTANEOUS - GROUND FAULT MCB MAIN CIRCUIT BREAKER MFR MANUFACTURERMLO MAIN LUGS ONLY MTS MANUAL TRANSFER SWITCH MW MICROWAVE OVEN

NIC NOT IN CONTRACT (SHOWN FOR REFERENCE ONLY)

NTS NOT TO SCALE

OFE OWNER-FURNISHED EQUIPMENT - INSTALLED AND WIRED BY E.C.

OS OPTIONAL STANDBY

P.C. WORK UNDER DIVISION 22

(R) RELOCATED

S.C. WORK UNDER DIVISION 21SCCR SHORT CIRCUIT CURRENT RATING SPD SURGE PROTECTIVE DEVICE ST SHUNT TRIP

TAAC TO ABOVE ACCESSIBLE CEILING TR TAMPER RESISTANT TTB TELEPHONE TERMINAL BOARD TYP TYPICAL

UCR UNDER COUNTER REFRIGERATOR UL UNDERWRITER'S LABORATORYU.L.S.E. LISTED FOR SERVICE ENTRANCEUNO UNLESS NOTED OR INDICATED OTHERWISE ON

DRAWINGS OR IN SPECIFICATIONS

VFD / VSD VARIABLE FREQUENCY / SPEED DRIVE VIF VERIFY IN FIELD VM VENDING MACHINE VP VANDAL PROOF

W / WP WEATHERPROOFWG WIRE GUARD WR WEATHER RESISTANT

PLAN-VIEW AND GRAPHIC LINE TYPES

WORK SHOWN BOLD-CONTINUOUS INDICATES NEW WORK(UNLESS OTHERWISE INDICATED)

WORK SHOWN FADED INDICATES EXISTING WORK TO REMAIN OR NEW WORK BY OTHERS AS APPLICABLE(UNLESS OTHERWISE INDICATED)

WORK SHOWN BOLD-DASHED INDICATES SELECTIVE DEMOLITION WORK(UNLESS OTHERWISE INDICATED)

TECHNOLOGY LEGEND

SYMBOL DESCRIPTION

TECHNOLOGY (ROUGH-IN ONLY)COORDINATE WITH SYSTEM INSTALLERS PRIOR TO INSTALLATION FOR LOCATIONS, HEIGHTS, CONDUIT TERMINATIONS, ETC.

ALL OUTLET BOXES FOR ROUGH-IN SHALL BE MINIMUM 2-1/4" DEEP.

CARD READER OR ACCESS CONTROL DEVICE - PROVIDE 4"X4" OUTLET BOX WITH 1-GANG RING AND(1) 1" CONDUIT TO ABOVE ACCESSIBLE CEILING UNLESS NOTED OTHERWISE.

PR

SCALE:

DATE:

DRAWN B

Y:

CHECKED

BY:

APPROVED B

Y:

F.B

.

NO.

PG.

CONTRACT NO:

SHEET

WWW.KLHENGRS.COM

MECHANICAL/ELECTRICALENGINEERS

1538 ALEXANDRIA PIKE, SUITE 11 FT. THOMAS, KENTUCKY 41075800-354-9783 859-442-8050859-442-8058 FAX

LEXINGTON, KENTUCKYLOUISVILLE, KENTUCKYCOLUMBUS, OHIONEW YORK, NEW YORK

KOHRS LONNEMANN HEIL ENGINEERS, INC.

1/8" = 1'-0"

5/1

4/2

020

12:4

4:3

4 P

M

E0.01

ELECTRIC COVER SHEET

200126

CANOPY REPLACEMENT

GOLDEN TOWERS APARTMENTS

04/20/2020

KAH

JAL

50 E. 11TH ST. COVINGTON, KY 41011

MC - METAL CLAD CABLEMI - MINERAL INSULATED CABLEHMC - HEALTHCARE METAL CLAD CABLEUSE - UNDERGROUND SERVICE ENTRANCE CABLESE - SERVICE ENTRANCE CABLEUF - UNDERGROUND FEEDERNM - NON-METALLIC SHEATHED CABLERMC - RIGID METAL CONDUITRNC - RIGID NON-METALLIC CONDUITRTRC - REINFORCED THERMOSETTING RESIN CONDUITLIM - LINE ISOLATION MONITOR

ARC - ALUMINUM RIGID CONDUITEMT - ELECTRIC METALLIC TUBINGENT - ELECTRIC NON-METALLIC TUBINGFMC - FLEXIBLE METALLIC CONDUITGRC - GALVANIZED RIGID STEEL CONDUITHDPE - HIGH DENSITY POLYETHYLENE CONDUITIMC - INTERMEDIATE METAL CONDUITLFMC - LIQUID-TIGHT FLEXIBILE METALLIC CONDUITLFNC - LIQUID-TIGHT FLEXIBLE NON-METALLIC CONDUITSCH 40 PVC - SCHEDULE 40 POLYVINYL CHLORIDE CONDUITSCH 80 PVC - SCHEDULE 80 POLYVINYL CHLORIDE CONDUIT

ELECTRIC CONDUIT AND WIRE MATERIAL SCHEDULE

CONDUIT APPLICATION CONDUCTOR TYPE RACEWAY TYPE RACEWAY AND CONDUCTOR NOTES

---POWER - INDOOR---

EXISTING HOLLOW PARTITIONS THHN MC

CONCEALED THHN MC

CONCEALED, DAMP LOCATIONS XHHW-2 EMT

VERTICAL RISERS FROM BELOW GRADE INCLUDINGELBOW

XHHW-2 RMC (GRC)

LUMINAIRE WHIPS IN ACCESSIBLE CEILING, 72" MAX THHN MC

CONNECTION TO VIBRATING EQUIPMENT, 72" MAX THHN LFMC

EXPOSED THHN EMT

---POWER - OUTDOOR---

EXPOSED XHHW-2 RMC (GRC)

CONCEALED XHHW-2 EMT

CONCEALED, DAMP LOCATIONS XHHW-2 IMC

UNDERGROUND XHHW-2 RNC (SCH 40 PVC)

CONNECTION TO VIBRATING EQUIPMENT, 72" MAX XHHW-2 LFMC

---TECHNOLOGY---

EXISTING HOLLOW PARTITIONS PLENUM OR NON-PLENUM RATED EMT

CONCEALED, ABOVE INACCESSIBLE CEILINGS PLENUM OR NON-PLENUM RATED EMT

CONCEALED, ABOVE ACCESSIBLE CEILINGS PLENUM OR NON-PLENUM RATED J-HOOKS

REV

REVISIO

NS

DATE

BY

0IS

SUE FOR B

IDDIN

G AND PERMIT

05/22/2020

MJG

05/14/2020

D E

1

2

4

3

D.5 E.5

STORAGE

111

CLINIC

133

CLINIC

132

VESTIBULE

131

MAIL ROOM

110

ELEVATORS

999WOMEN

114

Room

B-33

JANITOR

113

BEDROOM

105

Room

B-44

RECEPTION

130

ADMINISTRATION

OFFICE

129

LOBBY

120TELEPHONES

134

E1

E1

E2

E7

E8

EXISTING CONDITIONS - GENERAL NOTES

A. INTENT OF DOCUMENTS: IT IS NOT THE INTENT OF ELECTRICAL DOCUMENTS THAT EXISTING CONDITIONS BE ACCURATELY SHOWN. EXISTING ELECTRICAL WORK IS SHOWN TO A VERY LIMITED EXTENT ON DRAWINGS AND IS SHOWN FOR GENERAL PLANNING REFERENCE ONLY. LOCATIONS AND INFORMATION WERE DERIVED FROM CURSORY VISUAL OBSERVATIONS OR FROM PORTIONS OF DOCUMENTS THAT WERE PREPARED FOR PREVIOUSLY INSTALLED WORK (NOT FROM RECORD DRAWINGS OR "AS-BUILTS").

B. PRE-BID SURVEY: PERFORM A DETAILED PRE-BID WALK-THROUGH FIELD INSPECTION AND SURVEY TO REVIEW THE EXISTING STRUCTURES AND PREMISES, TO ACCURATELY DETERMINE EXISTING CONDITIONS, AND TO DETERMINE SCOPE OF REQUIRED ELECTRICALLY RELATED WORK. INCLUDE APPLICABLE ACCESSIBLE CEILING CAVITY AREAS IN THIS INSPECTION.

C. RISK MITIGATION: MINIMIZE RISKS TO INDIVIDUALS AND PROPERTY THROUGHOUT THE DURATION OF THE PROJECT. COORDINATE WITH, AND OBTAIN APPROVAL FROM, THE OWNER AND DESIGN PROFESSIONAL FOR ALL MATERIALS, METHODS, STEPS, LOCATIONS, INSTALLATIONS, ETC. PRIOR TO COMMENCEMENT OF WORK. DETERMINE AND EMPLOY MEANS AND METHODS AS REQUIRED TO SAFELY AND SECURELY IMPLEMENT ALL RELATED WORK.

D. REUSE OF REMOVED MATERIALS: DO NOT REUSE REMOVED ELECTRICAL MATERIALS UNLESS SPECIFICALLY INDICATED IN PROJECT DOCUMENTS. EXISTING WIRING SYSTEMS MAY BE UTILIZED ONLY TO THE EXTENT INDICATED IN PROJECT DOCUMENTS, OR AS DIRECTED BY OWNER'S REPRESENTATIVE IN FIELD.

E. POWER DISTRIBUTION AND BRANCH CIRCUIT WORK: DETERMINE WHICH EXISTING BRANCH CIRCUITS MUST REMAIN ACTIVE. RECONNECT (OR MAINTAIN IN OPERATION WHERE APPLICABLE) AND SCHEDULE THEM. COMPLETELY RE-TYPE PANELBOARD DIRECTORIES FOR PANELBOARDS AFFECTED BY THIS PROJECT USING ACCURATE “AS-BUILT” INFORMATION. WHERE APPLICABLE ENSURE THAT RECONNECTED SHARED NEUTRALS ARE PROPERLY BALANCED WITH THE CORRECT PHASE CONDUCTORS. WHERE APPLICABLE, PROVIDE CORRECT COLOR-CODING FOR INSULATION OF RECONNECTED CONDUCTORS IN A MANNER COMPLIANT WITH NFPA 70 AND CONSISTENT WITH EXISTING CONDITIONS. WHEN ADDING COMPONENTS TO EXISTING POWER DISTRIBUTION EQUIPMENT, PROVIDE FULL SIZE (NO SPLIT OR TANDEM DEVICES) OVERCURRENT PROTECTION DEVICES (OCPs) TO MATCH THOSE ALREADY IN PLACE, INCLUDING MANUFACTURER, MODEL/SERIES, SHORT CIRCUIT CURRENT (SCCR/AIC) RATINGS. PROVIDE OCPs AS REQUIRED TO RENDER ALL NEW AND MODIFIED ELECTRICAL WORK FULLY OPERATIONAL. PROVIDE COMMON TRIPS (NO FIELD-INSTALLED HANDLE TIES) IN THE SAME GUTTER FOR MULTI-POLE DEVICES. PROVIDE SWITCHING DUTY (SWD), HACR AND HID RATINGS WHERE APPLICABLE FOR LOADS. PROVIDE HANDLE LOCK-ON DEVICES FOR EMERGENCY AND CRITICAL LOADS. ALL CIRCUIT ASSIGNMENTS SHOWN ON DRAWINGS ARE SHOWN TO INDICATE NEW CIRCUIT REQUIREMENTS. DETERMINE EXACT NUMBERING AND SEQUENCING OF CIRCUITS IN FIELD BASED ON LOADING, LOAD BALANCING AND EXISTING CONDITIONS.

F. ADDED LOADS TO EXISTING CIRCUITS: IN CASES WHERE NEW LOADS ARE INDICATED TO BE CONNECTED TO EXISTING CIRCUITS WITH EXISTING LOADS, CHECK RESULTANT LOAD IN ADVANCE TO ENSURE COLLECTIVE LOAD DOES NOT EXCEED 80 PERCENT OF THE SOURCE CIRCUIT BREAKER AMPERE RATING. IF THAT LOAD IS EXCEEDED, PROVIDE ADDITIONAL CIRCUIT HOME-RUN WORK TO SOURCE PANELBOARD(S) AS REQUIRED TO ACCOMMODATE THE ENTIRE RESULTANT LOAD. DETERMINE ALL APPLICABLE CONDITIONS IN FIELD PRIOR TO COMMENCEMENT OF WORK.

G. REASSIGNMENT OF EXISTING CIRCUITS: IN CASES WHERE EXISTING CIRCUITS ARE REUSED (BASED ON INFORMATION SHOWN ON DRAWINGS OR BASED ON FIELD CONDITIONS) BUT MUST BE CONNECTED TO BREAKERS OTHER THAN THEIR ORIGINAL BREAKER, MODIFY COLOR-CODING AS REQUIRED IF THE NEW BREAKER ASSIGNMENT IS CONNECTED TO A DIFFERENT LINE/PHASE THAN THE ORIGINAL ONE. USE MEANS AND METHODS COMPLIANT WITH NFPA 70 AND WITH AUTHORITIES HAVING JURISDICTION.

H. ELECTRICAL WORK TO REMAIN OR BE RELOCATED: IF REQUIRED TO ACCOMMODATE CONSTRUCTION RELATED ACTIVITIES, TEMPORARILY REMOVE, STORE IN PROTECTED LOCATION ON SITE, AND REINSTALL CONFLICTING ELECTRICAL EQUIPMENT, LUMINAIRES, OR DEVICES THAT ARE TO REMAIN OR TO BE RELOCATED. THE FOLLOWING APPLIES TO ELECTRICAL MATERIALS THAT WILL REMAIN OR BE REUSED UNDER THIS PROJECT: PROTECT DURING CONSTRUCTION ACTIVITIES; CLEAN AND RE-LAMP LUMINAIRES IMMEDIATELY PRIOR TO OCCUPANCY OF THE FINISHED CONSTRUCTION AREA; CLEAN AND SERVICE (IF SERVICE IS REQUIRED) EQUIPMENT IN THE CONSTRUCTION AREA IMMEDIATELY PRIOR TO OCCUPANCY OF THE AREA.

I. PROTECTIVE BARRIERS: PROVIDE AND MAINTAIN TEMPORARY PARTITIONS AND DUST BARRIERS ADEQUATE TO PREVENT THE SPREAD OF DUST AND DIRT TO ADJACENT FINISHED AREAS AND OTHER SYSTEM COMPONENTS. PROTECT ADJACENT INSTALLATIONS DURING CUTTING AND PATCHING OPERATIONS. REMOVE PROTECTION AND BARRIERS AFTER DEMOLITION OPERATIONS ARE COMPLETE. PREVENT AIRBORNE DUST AND PARTICULATE MATTER RESULTING FROM ELECTRICAL WORK FROM ENTERING OCCUPIED SPACES, AND FROM ENTERING AIR INTAKES TO OPERATING HVAC SYSTEMS. MEET WITH OWNER AND HVAC INSTALLER TO DETERMINE SPECIAL INDOOR AIR QUALITY (IAQ) REQUIREMENTS RELATED TO ELECTRICAL THAT MAY APPLY TO THIS PROJECT. COOPERATE FULLY WITH HVAC IAQ REQUIREMENTS THAT AFFECT ELECTRICAL WORK AND ARE AFFECTED BY ELECTRICAL WORK.

J. PENETRATIONS: MAKE REQUIRED ELECTRICAL OPENINGS THROUGH WALLS, FLOORS, ETC. IMMEDIATELY PRIOR TO INSTALLATION OF WORK. PROPERLY AND PERMANENTLY SEAL ELECTRICAL OPENINGS IMMEDIATELY AFTER INSTALLATION OF WORK. PROVIDE TEMPORARY SEALS FOR APPLICATIONS WHERE PENETRATIONS ARE MADE BUT CANNOT BE PERMANENTLY SEALED WITHIN FOUR HOURS.

K. PRE-EXISTING CODE VIOLATIONS: INSPECT EXISTING ELECTRICAL WORK IN AREAS ACCESSED UNDER THIS PROJECT AND BRING INTO COMPLIANCE WITH NFPA 70. THIS APPLIES ONLY TO THE EXTENT THAT SUCH WORK IS UNCOVERED IN THE IMMEDIATE PROJECT AREAS AFFECTED BY CONSTRUCTION ACTIVITIES, AND ONLY TO THE LIMITED EXTENT THAT IT APPLIES TO PRE-EXISTING GENERAL INSTALLATION METHODS SUCH AS MISSING JUNCTION BOX PLATE, OPEN JUNCTION BOX KNOCKOUT, MINOR CONDUIT RE-ANCHORING AND MINOR EXPOSED WIRING/CONNECTIONS. IF MORE EXTENSIVE CODE OR SAFETY VIOLATIONS ARE DISCOVERED, IMMEDIATELY BRING THEM TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE (DETAILED IN WRITING) ALONG WITH PROPOSED COST FOR CORRECTIONS AND IMPACT (IF ANY) ON THE CONSTRUCTION SCHEDULE.

L. TEMPORARY LIGHTING AND POWER: COMPLY WITH NFPA 70 (INCLUDING ARTICLE 590), NFPA 70E AND ALL OTHER PREVAILING CODES. PROVIDE SUFFICIENT LIGHTING AND POWER CENTERS THROUGHOUT INTERIOR OF NEW WORK OR RENOVATION SCOPE. PROVIDE GFCI PROTECTION FOR ALL WORK. COORDINATE WITH GENERAL CONTRACTOR AND OTHER TRADES, AND PROVIDE ANY ADDITIONAL TEMPORARY ELECTRICAL NEEDS THAT ARE REQUIRED. FULLY DEMOLISH TEMPORARY ELECTRIC BY END OF PROJECT. TEMPORARY ELECTRICAL SERVICE(S) MAY BE DERIVED FROM EXISTING BUILDING ENERGIZED SERVICE. PROVIDE OVERCURRENT PROTECTION, DISCONNECTS, CABLES, CONDUCTORS, RACEWAY, ETC. ACCORDINGLY. RESTORE ASSOCIATED SITE AND BUILDING MATERIALS TO THEIR PRE-CONSTRUCTION STATE AND CONDITION AFTER TEMPORARY LIGHTING AND POWER IS NO LONGER NEEDED.

M. INTERIM LIFE-SAFETY PROVISIONS: PROVIDE INTERIM ELECTRICAL FIRE ALARM AND LIFE SAFETY PROTECTION IN DEMOLITION AND CONSTRUCTION AREAS AS INDICATED BELOW. CONTACT DESIGN PROFESSIONAL IF FURTHER DEFINITION IS NEEDED. REMOVE ALL TEMPORARY LIFE SAFETY WORK WHEN NO LONGER NEEDED. PROVIDE TEMPORARY PLASTIC COVERS, OBTAINED FROM SMOKE DETECTOR MANUFACTURER OR OBTAINED FROM A THIRD PARTY AND SPECIFICALLY APPROVED FOR SUCH USE BY SMOKE DETECTOR MANUFACTURER, OVER EXISTING SMOKE DETECTORS WITHIN PROJECT AREA, AND IN ADJACENT AREAS THAT ARE EXPOSED TO CONSTRUCTION-RELATED DUST OR AIRBORNE PARTICULATES, DURING WORKING PERIODS. REMOVE COVERS AFTER EACH SHIFT. PROVIDE TEMPORARY UL 924 COMPLIANT EXIT AND/OR EGRESS LIGHTING ALONG EGRESS ROUTES AFFECTED BY THIS PROJECT, AS OR IF APPLICABLE. PROVIDE TEMPORARY FIRE ALARM SYSTEM PULL STATIONS AND/OR AUDIO/VISUAL ALARM NOTIFICATION DEVICES ALONG ALL AFFECTED EGRESS ROUTES THAT MUST REMAIN ACTIVE DURING THE PROJECT, AS OR IF APPLICABLE.

N. CONDUCTOR TRACING: PRIOR TO COMMENCEMENT OF WORK, TRACE ALL FEEDERS AND BRANCH CIRCUITS WITHIN THE PROJECT AREA, AND AFFECTED BY THE PROJECT, AND DOCUMENT THE RESULTS. DETERMINE AND DOCUMENT EXISTING LOADS FOR ALL CIRCUITS AND FEEDERS WITH LOADS THAT WILL REMAIN. CREATE CURRENT AS-BUILT DIRECTORIES FOR ALL POWER DISTRIBUTION EQUIPMENT. LIKEWISE, DETERMINE AND DOCUMENT ROUTING AND SPECIFICS FOR ALL RELEVANT EXISTING CONDUITS AND PATHWAYS FOR ALL SYSTEMS. SUBMIT THIS INFORMATION TO OWNER AND DESIGN PROFESSIONALS AS INFORMATIONAL SUBMITTALS.

EXISTING CONDITIONS - POWER CONTINUITY NOTES

THE FOLLOWING NOTES BROADLY DEFINE SOME OF THE SPECIALTY BASE BID SCOPE OF WORK REQUIRED TO PROVIDE SPECIAL TEMPORARY POWER FOR NEW AND EXISTING FACILITIES TO ACCOMMODATE UTILITY POWER INTERRUPTIONS. FIELD VERIFY ALL SPECIFICS AND PROVIDE MATERIALS, NORMAL TIME LABOR, PREMIUM TIME LABOR, SERVICES, ETC. FOR ALL WORK UNDER BASE BID, INCLUDING BUT NOT LIMITED TO THE FOLLOWING.

A. INVESTIGATION OF EXISTING CONDITIONS: LOCATE, IDENTIFY, AND PROTECT ELECTRICAL SERVICES PASSING THROUGH DEMOLITION AREAS AND SERVING OTHER AREAS OUTSIDE THE DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS OUTSIDE DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, PROVIDE TEMPORARY SERVICES FOR AFFECTED AREAS. IT IS RECOGNIZED THAT THERE MAY BE SOME CONDUIT SYSTEMS RENDERED INACTIVE BY DEMOLITION, CAUSING DISCONNECTION OF "DOWNSTREAM" OUTLETS, ETC. INVESTIGATE THESE TYPES OF CONDITIONS (FOR ALL SYSTEMS) PRIOR TO DEMOLITION. PROVIDE NECESSARY CORRECTIVE ELECTRICAL WORK PRIOR TO DEMOLITION TO ENSURE THAT SUCH "DOWNSTREAM" DEVICES REMAIN PERMANENTLY ACTIVE THROUGHOUT DEMOLITION, DURING NEW CONSTRUCTION, AND AFTER PROJECT COMPLETION. PROTECT EXISTING ELECTRICAL WORK SERVING EXISTING SPACES AND EQUIPMENT THAT MUST REMAIN OPERATIONAL DURING PART OR ALL OF THE CONSTRUCTION PERIOD, AND ENSURE POWER CONTINUITY IS MAINTAINED FOR SAME THROUGHOUT DURATION OF CONSTRUCTION ACTIVITIES.

B. COORDINATION WITH OWNER: CAREFULLY COORDINATE WORK AND SYSTEM SHUTDOWNS IN ADVANCE WITH OWNER'S REPRESENTATIVE, AND WITH AFFECTED TRADES SO THAT NORMAL BUILDING ACTIVITIES AND OTHER CONSTRUCTION TRADES ARE MINIMALLY AFFECTED. PERFORM ELECTRICALLY RELATED CONSTRUCTION WORK, WHICH WILL AFFECT AN OCCUPIED AREA (INCLUDING THOSE WHICH ARE LOCATED OUTSIDE THE IMMEDIATE AREA OF PROJECT WORK) AT SPECIAL TIMES AS DIRECTED BY OWNER'S REPRESENTATIVE IN FIELD. DO NOT INTERRUPT ELECTRICAL UTILITY SERVICE(S) TO THE FACILITY, OR ANY PART THEREOF, UNLESS PERMITTED UNDER THE FOLLOWING CONDITIONS, AND THEN ONLY AFTER PROVIDING TEMPORARY ELECTRICAL SERVICE(S)/FEEDS: NOTIFY OWNER AND DESIGN PROFESSIONALS NO FEWER THAN FOURTEEN DAYS IN ADVANCE OF EACH PROPOSED INTERRUPTION OF AN ELECTRICAL SERVICE; DO NOT PROCEED WITH INTERRUPTION OF AN ELECTRICAL SERVICE WITHOUT OWNER'S WRITTEN PERMISSION; DO NOT ENERGIZE ANY NEW WORK WITHOUT NOTIFICATION TO, AND SUBSEQUENT PERMISSION FROM, THE OWNER AND ALL AFFECTED PARTIES.

C. COORDINATION WITH BUILDING OPERATIONS: PROVIDE WORK IN A MANNER THAT ENSURES EXISTING SYSTEMS AND COMPONENTS REMAIN FULLY OPERATIONAL IN OCCUPIED SPACES DURING OCCUPIED PERIODS. MAINTAIN EXISTING ELECTRICAL SERVICE AND FEEDERS TO OCCUPIED AREAS AND OPERATIONAL FACILITIES, UNLESS OTHERWISE INDICATED, OR WHEN AUTHORIZED OTHERWISE IN WRITING BY OWNER’S REPRESENTATIVE. PROVIDE TEMPORARY SERVICE DURING INTERRUPTIONS TO EXISTING FACILITIES. SCHEDULE MOMENTARY OUTAGES WHEN NECESSARY FOR REPLACING EXISTING WIRING SYSTEMS WITH NEW WIRING SYSTEMS. WHEN THAT "CUTTING-OVER" HAS BEEN SUCCESSFULLY ACCOMPLISHED, REMOVE RELATED WIRING THAT HAS BEEN ABANDONED.

D. TEMPORARY ARRANGEMENTS: COMPLY WITH NFPA 70 (INCLUDING ARTICLE 590), NFPA 70E AND ALL OTHER PREVAILING CODES. DURING CONSTRUCTION RELATED ELECTRICAL OUTAGES, SWITCHOVERS, DISCONNECTIONS, RECONNECTIONS, ETC. PROVIDE ALL TEMPORARY INSULATED CONDUCTORS, TAPS, JUMPERS, ETC. TO AND FROM EXISTING AND NEW OR TEMPORARY ELECTRICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO, CONDUCTORS, SPLICES, LUG FITTINGS, REWORK, PREMIUM TIME, SECURITY AND SAFETY MEASURES, ETC. COORDINATE WITH, AND OBTAIN APPROVAL FROM, OWNER AND DESIGN PROFESSIONALS FOR ALL MATERIALS, METHODS, STEPS, LOCATIONS, INSTALLATIONS, SEQUENCING, ETC. PRIOR TO COMMENCEMENT OF WORK. DETERMINE AND EMPLOY MEANS AND METHODS AS REQUIRED TO SAFELY AND SECURELY IMPLEMENT ALL RELATED WORK. COMPLY WITH NFPA 70E. SCHEDULE ALL OUTAGES IN ADVANCE WITH OWNER, AT DAYS OF WEEK AND TIMES OF DAY OR NIGHT AS DIRECTED BY OWNER, AS NECESSARY TO ACCOMMODATE ALL CONSTRUCTION RELATED ELECTRICAL OUTAGES, SWITCHOVERS AND RELATED CONNECTIONS AND DISCONNECTIONS.

EXISTING CONDITIONS - DEMOLITION NOTES

A. DEFINITION OF DEMOLITION: WHERE THE TERM “DEMOLITION” IS USED IN ELECTRICAL DOCUMENTS, INTERPRET IT TO MEAN “DEMOLITION” OR “SELECTIVE DEMOLITION” AS APPLICABLE FOR THE RESPECTIVE SCOPE OF WORK. WHERE THE TERM “DEMOLISH”, “REMOVE” OR SIMILAR TERMS ARE USED IN ELECTRICAL DOCUMENTS, INTERPRET TO MEAN “DISCONNECT, REMOVE, DISPOSE OF, AND REMOVE ALL RELATED ELECTRICAL CONDUIT, RACEWAYS, WIRING, CABLES, BOXES, SUPPORTS, ETC.”.

B. GENERAL ACCOMMODATIONS: PROVIDE ELECTRICAL DEMOLITION WORK AS REQUIRED TO ACCOMMODATE PROJECT DEMOLITION AND AS REQUIRED TO ACCOMMODATE NEW CONSTRUCTION. DISCONNECT AND REMOVE WORK TO BE ABANDONED, AND AS REQUIRED TO ACCOMMODATE WORK OF OTHER TRADES, IN AREAS AFFECTED BY THIS PROJECT UNLESS SPECIFICALLY NOTED OTHERWISE ON PLANS OR DETERMINED OTHERWISE DURING PRE-DEMOLITION SURVEY. COORDINATE WORK CAREFULLY WITH OWNER PRIOR TO BEGINNING ELECTRICAL DEMOLITION WORK.

C. REMOVAL OF ABANDONED WORK: REMOVE ACCESSIBLE ABANDONED, INACTIVE AND OBSOLETE RACEWAY SYSTEMS. REMOVE ABANDONED, INACTIVE AND OBSOLETE EQUIPMENT, LUMINAIRES, DEVICES, CONDUIT, RACEWAYS, WIRING, CABLES, BOXES, SUPPORTS, CONTROLS, ETC. ABANDONED RACEWAYS EMBEDDED IN FLOORS, WALLS, AND CEILINGS MAY REMAIN IF SUCH MATERIALS DO NOT INTERFERE WITH NEW INSTALLATIONS. THIS APPLIES FOR ALL ELECTRICAL WORK, AND ALL COMMUNICATIONS AND INFORMATION TECHNOLOGY TYPE WORK, INCLUDING ALL SUCH WORK ABOVE CEILINGS, ETC. REMOVE RELATED ABANDONED UNUSED RACEWAY BACK TO THE NEAREST RESPECTIVE "UPSTREAM" JUNCTION BOX THAT REMAINS ACTIVE EVEN IF OUTSIDE OF THE CONFINES OF THE PROJECT AREA. REMOVE ABANDONED UNUSED WIRING AND CABLES BACK TO RESPECTIVE SOURCES SOURCE EVEN IF SOURCES ARE OUTSIDE THE CONFINES OF THE PROJECT AREA.

D. RE-USE OF EXISTING CONDUIT: EXISTING BRANCH CIRCUIT AND SYSTEMS CONDUIT, NOT CONFLICTING WITH NEW CONSTRUCTION AND NOT CONFLICTING WITH OVERHEAD OR CEILING CAVITY REQUIREMENTS, MAY BE RE-USED AT THE DISCRETION OF THE ELECTRICAL INSTALLER AFTER ALL ABANDONED CONDUCTORS AND CABLES HAVE BEEN REMOVED FROM THEM. DO NOT EXCEED NFPA 70 REQUIRED CONDUIT FILL AND DO NOT INSTALL WIRING FED FROM DIFFERENT SOURCES IN COMMON CONDUIT.

E. MODIFICATIONS TO ACCOMMODATE NEW WORK: REMOVE AND RELOCATE EQUIPMENT, LUMINAIRES, DEVICES, CONDUIT, RACEWAYS, WIRING, CABLES, BOXES, SUPPORTS, ETC. THAT CONFLICT WITH CONSTRUCTION RELATED WORK OF ALL TRADES AS NECESSARY TO ACCOMMODATE NEW WORK OF RESPECTIVE TRADES. REWORK AND EXTEND RACEWAY AND WIRING AS REQUIRED TO ACCOMMODATE NEW OR RELOCATED ELECTRICAL WORK. MAINTAIN (OR RECONNECT IF APPLICABLE) REMAINING WIRING. PROVIDE ELECTRICAL DISCONNECTIONS, AND RECONNECTIONS WHERE APPLICABLE, FOR EQUIPMENT TO BE REMOVED (OR RELOCATED) BY OTHER TRADES.

F. CUTTING AND PATCHING: PERFORM CUTTING AND PATCHING REQUIRED FOR DEMOLITION, RESTORED TO MATCH SURROUNDING REMAINING SURFACES, INCLUDING FIRE/SMOKE RATINGS.

G. LUMINAIRES: FOR ALL EXISTING LUMINAIRES WHICH ARE SCHEDULED FOR REUSE, REMOVE FROM EXISTING CEILINGS DURING DEMOLITION; PROTECT DURING CONSTRUCTION; CLEAN, SERVICE (IF REQUIRED), RE-LAMP (WITH LAMPS TO MATCH BUILDING STANDARD) AND REINSTALL AT LOCATIONS INDICATED. FOR ALL EXISTING LUMINAIRES WHICH ARE SCHEDULED TO BE REMOVED AND TURNED OVER TO OWNER, THE LUMINAIRES SHALL BE DISCONNECTED, CAREFULLY REMOVED AND TURNED OVER TO OWNER. TRANSFER SUCH LUMINAIRES TO STORAGE AREA AS DIRECTED IN FIELD.

H. DISPOSAL OF MATERIALS: REFER TO OWNER’S REPRESENTATIVE FOR DISPOSAL INSTRUCTIONS FOR ABANDONED ELECTRICAL MATERIALS REMOVED DURING DEMOLITION AND THEREAFTER. NEATLY STORE ELECTRICAL MATERIALS THAT THE OWNER ELECTS TO RETAIN AT THE SITE AS DESIGNATED BY THE OWNER'S REPRESENTATIVE. LEGALLY DISPOSE OF MATERIALS THAT THE OWNER ELECTS NOT TO RETAIN. DISCONNECT AND REMOVE ELECTRICAL MATERIALS DESIGNATED FOR SALVAGE (REMOVAL AND REUSE, OR FOR TURNING OVER TO OWNER) UNDAMAGED. DISCONNECT AND REMOVE WIRING AND "WHIPS" FROM EQUIPMENT TERMINAL POINTS. CAREFULLY TRANSPORT SALVAGED ELECTRICAL MATERIALS TO A PROTECTED ON-SITE STORAGE LOCATION AS DIRECTED IN FIELD AND NEATLY STORE THEM GROUPED BY SYSTEM TYPE.

I. CLEANING OF REUSED COMPONENTS: CLEAN COMPONENTS TO BE REUSED INSIDE AND OUT, AND REINSTALL WHERE INDICATED ON DRAWINGS. MODIFY AND EXTEND RELATED EXISTING WIRING IN CONDUIT ACCORDINGLY.

SCALE:

DATE:

DRAWN B

Y:

CHECKED

BY:

APPROVED B

Y:

F.B

.

NO.

PG.

CONTRACT NO:

SHEET

WWW.KLHENGRS.COM

MECHANICAL/ELECTRICALENGINEERS

1538 ALEXANDRIA PIKE, SUITE 11 FT. THOMAS, KENTUCKY 41075800-354-9783 859-442-8050859-442-8058 FAX

LEXINGTON, KENTUCKYLOUISVILLE, KENTUCKYCOLUMBUS, OHIONEW YORK, NEW YORK

KOHRS LONNEMANN HEIL ENGINEERS, INC.

As indicated

5/1

4/2

020

12:4

4:3

6 P

M

E1.01

ELECTRIC DEMOLITION PLAN -FIRST FLOOR

200126

CANOPY REPLACEMENT

GOLDEN TOWERS APARTMENTS

04/20/2020

KAH

JAL

50 E. 11TH ST. COVINGTON, KY 41011

1/4" = 1'-0"E1.01

2 ELECTRIC DEMOLITION PLAN - FIRST FLOOR

1/32" = 1'-0"

KEYPLANN

KEYED NOTES

E1 EXISTING AUTOMATIC DOOR TO BE DEMOLISHED AND REPLACED.

E2 EXISTING WALL-PACK LUMINAIRE TO BE DEMOLISHED.

E7 EXISTING CARD READER AND KIOSK TO BE DEMOLISHED. CUT CONDUITFLUSH WITH SIDEWALK AND PREPARE FOR NEW VESTIBULE FLOORING.

E8 EXISTING CONTROLLED ACCESS TO REMAIN. PROVIDE ALL WIRING ANDCONTROLS AS NECESSARY FOR CONNECTION TO NEW AUTOMATICDOOR.

REV

REVISIO

NS

DATE

BY

0IS

SUE FOR B

IDDIN

G AND PERMIT

05/22/2020

MJG

05/14/2020

PC

D E

1

2

4

3

D.5 E.5

VESTIBULE

149

STORAGE

111

CLINIC

133

CLINIC

132

VESTIBULE

131

MAIL ROOM

110

ELEVATORS

999WOMEN

114

Room

B-33

JANITOR

113

BEDROOM

105

Room

B-44

RECEPTION

130

ADMINISTRATIONOFFICE

129

LOBBY

120TELEPHONES

134

CANOPY LIGHTING IS EXISTING TO REMAIN

VESTIBULE LIGHTING IS EXISTING TO REMAIN

LOBBY LIGHTING IS EXISTING TO REMAIN

F1B

L5BL5B

EL

E3

E5

- 3LP1-2

E6

GENERAL LIGHTING PLAN NOTES

A. INDOOR EGRESS LIGHTING: CONNECT ALL INDOOR EGRESS LIGHTING, DESIGNATED "EL", AHEAD OF ANY SWITCHING. UNLESS CONTROL METHODS ARE INDICATED OTHERWISE FOR A GIVEN AREA.

B. OUTDOOR EGRESS LIGHTING: CONNECT ALL OUTDOOR EGRESS LIGHTING AHEAD OF ANY SWITCHING ASIDE FROM PHOTOCELL CONTROL.

1/4" = 1'-0"E1.02

1 ELECTRIC LIGHTING PLAN - FIRST FLOOR

SCALE:

DATE:

DRAWN B

Y:

CHECKED

BY:

APPROVED B

Y:

F.B

.

NO.

PG.

CONTRACT NO:

SHEET

WWW.KLHENGRS.COM

MECHANICAL/ELECTRICALENGINEERS

1538 ALEXANDRIA PIKE, SUITE 11 FT. THOMAS, KENTUCKY 41075800-354-9783 859-442-8050859-442-8058 FAX

LEXINGTON, KENTUCKYLOUISVILLE, KENTUCKYCOLUMBUS, OHIONEW YORK, NEW YORK

KOHRS LONNEMANN HEIL ENGINEERS, INC.

As indicated

5/1

4/2

020

12:4

4:3

7 P

M

E1.02

ELECTRIC LIGHTING PLAN - FIRST FLOOR

200126

CANOPY REPLACEMENT

GOLDEN TOWERS APARTMENTS

04/20/2020

KAH

JAL

50 E. 11TH ST. COVINGTON, KY 41011

N1/32" = 1'-0"

KEYPLAN

KEYED NOTES

E3 CONNECT NEW VESTIBULE LUMINAIRE TO NEAREST EXISTING 20-AMP1-POLE INTERIOR LIGHTING CIRCUIT WITH AVAILABLE SPARE CAPACITY.PROVIDE INSTANTANEOUS METERING OF CIRCUIT PRIOR TO MAKINGFINAL CONNECTION TO ENSURE CIRCUIT AND PANEL WILL NOT BEOVERLOADED. VERIFY THAT ALL LIGHTING ON CIRCUIT IS TURNED ON ATMETERING. IF RESULTING METERED LOAD IS LESS THAN 15 AMPS, ADDNEW LUMINAIRE TO CIRCUIT.

E5 PROVIDE PHOTOCELL FOR AUTOMATIC CONTROL OF VESTIBULE CANOPYLIGHTING.

E6 CONNECT NEW LIGHTING TO EXISTING CANOPY CIRCUIT. VERIFY CIRCUITWILL NOT BE OVERLOADED PRIOR TO MAKING FINAL CONNECTION.

ELECTRIC LUMINAIRE SCHEDULE

TYPE DESCRIPTION MANUFACTURER / SERIES SIZE HOUSING / MOUNTING MATERIAL LENS DESCRIPTIONLAMPQTY LAMP TYPE LAMP BASE

DRIVERQTY DRIVER FINISH COMMENTS

FIXTURELOAD VOLTAGE

F1B RECESSED LEDLINEAR - BATTERYBACK-UP

LITECONTROL 4L-R-DNULITE RG4FINELITE HP-4

4"x8'x4" RECESSED GRID STEEL SATIN WHITE FLAT LUMINOUS ACRYLIC LENS 1 LED, 3500K, 80CRI

400LUMENS/FT

1 ELECTRONICDRIVER,120V-277V

WHITE PROVDE FIXTURE WITH INTEGRALEMERGENCY BATTERY BACKUP, 10WMINIMUM OUTPUT, 90-MINUTE MINIMUMRUN-TIME

28 VA 120 V

L5B SURFACE LEDLINEAR - EXTERIOR

PAL ML3WLOR APPROVED EQUAL

3-1/2"x8'x4" SURFACE, CANOPYCEILING

STEEL GASKETED ACRYLIC LENS, ASYMMETRICDISTRIBUTION

1 LED, 3500K, 80CRI

3000NOMINALLUMENS

1 ELECTRONICDRIVER,120V-277V, 0-10VDIMMING

WHITE WET LISTED, PROVDE FIXTURE WITHINTEGRAL EMERGENCY BATTERY BACKUP,10W MINIMUM OUTPUT, 90-MINUTE MINIMUMRUN-TIME, COLD WEATHER RATED

42 VA 120 V

GENERAL LUMINAIRE SCHEDULE NOTES

A. REFER TO DRAWINGS FOR MOUNTING TYPE, NUMBER OF FACES AND ARROWS OF EXIT SIGNS. VERIFY IN FIELD PRIOR TO INSTALLATION.

B. VERIFY COMPATIBILITY WITH VOLTAGE, CONTROLS, ETC. FOR ALL LUMINAIRE COMPONENTS

C. COORDINATE EACH LUMINAIRE LOCATION WITH THE ARCHITECTURAL REFLECTED CEILING PLANS, CEILING INSTALLERS, ETC. AND PROVIDE APPROPRIATE MOUNTING SYSTEM REQUIRED FOR EACH LUMINAIRE. ALSO, PROVIDE PLASTER FRAMES, WALL BRACKETS, SUPPORTS, OR OTHER APPURTENANCES AS REQUIRED FOR PROPER AND COMPLETE INSTALLATIONS.

D. WEAR CLEAN WHITE COTTON GLOVES WHEN HANDLING EXPOSED REFLECTIVE LUMINAIRE SURFACES. REMOVE PLASTIC SHIPPING BAGS ONLY AFTER INTERIOR WORK IS COMPLETE, AND CLEAN ALL SURFACES WITH CLEAN DRY CHEESECLOTH.

E. MOUNTING HEIGHTS INDICATED ARE TO THE BOTTOM OF THE LUMINAIRE, UNLESS OTHERWISE NOTED.

F. PRODUCTS: PROVIDE PRODUCTS INDICATED ON DRAWINGS AND SCHEDULES. WHERE MULTIPLE MANUFACTURER SERIES/MODEL NUMBERS ARE LISTED FOR A SINGLE LUMINAIRE, PROVIDE ONE OF THOSE LISTED. WHERE A SPECIFIC MANUFACTURER SERIES/MODEL NUMBER IS LISTED AS BASIS-OF-DESIGN, AND WHERE IT IS STATED THAT EQUIVALENTS WILL BE CONSIDERED, ANY PROPOSED NON-LISTED LUMINAIRES ARE SUBJECT TO REVIEW BY DESIGN PROFESSIONAL(S), SUBMITTALS FOR WHICH SHALL BE FURNISHED AT LEAST (10) DAYS PRIOR TO BID DUE DATE OR THEY WILL NOT BE CONSIDERED. THESE PRE-BID SUBMITTALS SHALL CLEARLY STATE EXACTLY WHAT IS BEING PROPOSED AND SHALL DEMONSTRATE COMPLIANT EQUIVALENCY. SIMILAR REQUESTS FOR PROPOSED SUBSTITUTIONS MAY BE MADE ONLY AFTER BIDS ARE RECEIVED, AND ONLY IF OWNER CHOOSES TO CONSIDER SUBSTITUTION REQUESTS. DESIGN PROFESSIONAL(S) AND OWNER RESERVE THE RIGHT TO REJECT ALL PRODUCTS THAT ARE NOT DEEMED TO BE FULLY EQUIVALENT TO THE BASIS-OF-DESIGN LISTING(S). SUBMIT ALL REQUESTS AND QUESTIONS THROUGH THE FORMALLY-ESTABLISHED BIDDING PROCESS, NOT DIRECTLY TO ENGINEER.

Interior LightingCompliance Certificate

2012 IECCSection 1: Project Information

Project Type: Addition

Section 2: Interior Lighting and Power CalculationFloor Area (sq. ft.)160 sf

Watts per sq. ft.0.7

Allowed Watts112

Proposed WattsSee Below

CompliesYes

Section 3: Interior Lighting Fixture ScheduleTYPE LAMP TYPE BALLAST / DRIVER LAMP QTY COUNT LOAD TOTAL LOAD

F1B LED, 3500K, 80 CRI ELECTRONIC DRIVER, 120V-277V 1 1 28 VA 28 VA

28 VA

Exterior LightingCompliance Certificate

2012 IECCSection 1: Project Information

Project Type: AdditionExterior Lighting Zone: Neighborhood Business District

Section 2: Exterior Lighting Area/Surface Power Calculation

Section 3: Exterior Lighting Fixture Schedule

Quantity7 ft

Allowed Watts / Unit20 W/ft

Proposed WattsSee Below

CompliesYes

Exterior Area/SurfaceMain Entry

Tradable Watts140 W

TYPE LAMP TYPE BALLAST / DRIVER LAMP QTY COUNT LOAD TOTAL LOAD

L5B LED, 3500K, 80 CRI ELECTRONIC DRIVER, 120V-277V, 0-10V DIMMING 1 2 42 VA 84 VA

84 VA

REV

REVISIO

NS

DATE

BY

0IS

SUE FOR B

IDDIN

G AND PERMIT

05/22/2020

MJG

05/14/2020

PR

C

D E

F

1

2

4

3

D.5 E.5

VESTIBULE

149

STORAGE

111Room

B-17

Room

B-25

Room

B-26

CLINIC

133

CLINIC

132

VESTIBULE

131

MAIL ROOM

110

ELEVATORS

999WOMEN

114

Room

B-33

JANITOR

113

Room

B-35

BEDROOM

105

Room

B-37

Room

B-38

Room

B-40

Room

B-41

Room

B-42

Room

B-43

Room

B-44

RECEPTION

130

Room

B-46

ADMINISTRATION

OFFICE

129

Room

B-48

Room

B-49

Room

B-50

Room

B-55

Room

B-56

LOBBY

120TELEPHONES

134

LP1-1

LDP1-1

EMP1-1

LP1-2

LP1-2- 39TR

48"

- 41LP1-2

ECH-1LP1-2- 38,40,42

E4

E8

GENERAL POWER PLAN NOTES

A. EQUIPMENT COORDINATION SCHEDULES: REFER TO EQUIPMENT COORDINATION SCHEDULES FOR REQUIREMENTS ASSOCIATED WITH EQUIPMENT CIRCUITING, CONNECTIONS, ANCILLARY DEVICES AND EQUIPMENT, ETC. COORDINATE LOCATIONS AND REQUIREMENTS FOR ALL EQUIPMENT WITH RESPECTIVE EQUIPMENT SUPPLIERS AND INSTALLERS PRIOR TO ORDERING ANY RELATED MATERIALS OR COMMENCING WITH ANY RELATED ROUGH-IN WORK.

B. TECHNOLOGY SYSTEMS: PROVIDE RACEWAY AND PATHWAY SYSTEMS FOR ALL TECHNOLOGY WORK. INCLUDE OUTLET BOXES, CONDUITS, RACEWAYS, J-HOOKS, CABLE TRAY, ETC. AS REQUIRED FOR COMPLETE OPERATIONAL SYSTEMS. COORDINATE ALL RELATED WORK (INCLUDING ASSOCIATED POWER) WITH OWNER (INCLUDING OWNER'S PROJECT MANAGER), FIELD CONDITIONS, FURNITURE INSTALLER(S), TECHNOLOGY INSTALLER(S) AND WORK OF OTHER TRADES AND SUPPLIERS/INSTALLERS AS APPLICABLE. TERMINATE ALL CONDUITS FROM OUTLET BOXES TO NEAREST ACCESSIBLE CEILING CAVITY, OR TO OVERHEAD STRUCTURAL SPACE FOR AREAS WITH NO CEILINGS. PROVIDE CONDUITS WITH SWEEP BENDS, PULL STRINGS, PLASTIC BUSHINGS AND IDENTIFICATION AT OVERHEAD ENDS. PROVIDE BLANK WALL PLATES TO MATCH WIRING DEVICE WALL PLATES.

SCALE:

DATE:

DRAWN B

Y:

CHECKED

BY:

APPROVED B

Y:

F.B

.

NO.

PG.

CONTRACT NO:

SHEET

WWW.KLHENGRS.COM

MECHANICAL/ELECTRICALENGINEERS

1538 ALEXANDRIA PIKE, SUITE 11 FT. THOMAS, KENTUCKY 41075800-354-9783 859-442-8050859-442-8058 FAX

LEXINGTON, KENTUCKYLOUISVILLE, KENTUCKYCOLUMBUS, OHIONEW YORK, NEW YORK

KOHRS LONNEMANN HEIL ENGINEERS, INC.

As indicated

5/1

4/2

02

0 4

:10:5

7 P

M

E1.03

ELECTRIC POWER PLAN -FIRST FLOOR

200126

CANOPY REPLACEMENT

GOLDEN TOWERS APARTMENTS

04/20/2020

KAH

JAL

50 E. 11TH ST. COVINGTON, KY 41011

1/4" = 1'-0"E1.03

1 ELECTRIC POWER PLAN - FIRST FLOOR

N1/32" = 1'-0"

KEYPLAN

KEYED NOTES

E4 CONNECT NEW AUTOMATIC DOOR OPENER TO EXISTING 20-AMP 1-POLECIRCUIT IN VESTIBULE MADE AVAILABLE BY DEMOLITION.

E8 EXISTING CONTROLLED ACCESS TO REMAIN. PROVIDE ALL WIRING ANDCONTROLS AS NECESSARY FOR CONNECTION TO NEW AUTOMATICDOOR.

REV

REVISIO

NS

DATE

BY

0IS

SUE FOR B

IDDIN

G AND PERMIT

05/22/2020

MJG

05/14/2020

INCOMING CABLE & METERING SECTION

MAIN SECTION

KEYED SINGLE-LINE DIAGRAM NOTES

1. TEMPORARY LOAD METERING: PROVIDE RECORDING METERING AT EQUIPMENT/NODE INDICATED, CONTINUOUSLY RECORDED OVER A MINIMUM 30-DAY PERIOD, COMPLIANT WITH THE EXCEPTION UNDER PARAGRAPH (1) OF ARTICLE 220.87 OF THE NATIONAL ELECTRICAL CODE (NFPA 70). SUBMIT RESULTS TO DESIGN PROFESSIONALS AFTER 7 DAYS, AND AFTER 30 DAYS.

PAD MOUNTED TRANSFORMER

UTILITY

39130 AIC

DISTRIBUTION SECTION(S)

MSB3000A FUSED

!XC-U2660-4C

37258 AIC

EXISTING SCCR

208/120V 3PH 4W

FED FROM: UTILITY

LP1-1

175A MLO

XC-200-4C

8874 AICEXISTING SCCRFED FROM: MSB

LP1-2

175A MLO

XC-200-4C

17541 AICEXISTING SCCRFED FROM: MSB

TO UTILITY

1

SCALE:

DATE:

DRAWN B

Y:

CHECKED

BY:

APPROVED B

Y:

F.B

.

NO.

PG.

CONTRACT NO:

SHEET

WWW.KLHENGRS.COM

MECHANICAL/ELECTRICALENGINEERS

1538 ALEXANDRIA PIKE, SUITE 11 FT. THOMAS, KENTUCKY 41075800-354-9783 859-442-8050859-442-8058 FAX

LEXINGTON, KENTUCKYLOUISVILLE, KENTUCKYCOLUMBUS, OHIONEW YORK, NEW YORK

KOHRS LONNEMANN HEIL ENGINEERS, INC.

1/8" = 1'-0"

5/1

4/2

020

12:4

4:4

0 P

M

E1.04

ELECTRIC POWER SCHEDULES

200126

CANOPY REPLACEMENT

GOLDEN TOWERS APARTMENTS

04/20/2020

KAH

JAL

50 E. 11TH ST. COVINGTON, KY 41011

NOTES:ALL CONDUIT SIZES INDICATED AREMINIMUM SIZES. INCREASE SIZESAS REQUIRED TO ACCOMMODATECONDUCTOR PULLING EASE, FIELDCONDITIONS, ETC.

"CU" = COPPER CONDUCTOR,"AL" = ALUMINUM CONDUCTOR

FEEDER ID NOMENCLATURE:* - INDICATES FEEDER SIZED TO COMPENSATE FOR VOLTAGE DROP1 - GROUND TYPE (MAY BE BLANK) U = EQUIPMENT GROUND CONDUCTOR REMOVED FOR SERVICE ENTRANCE FROM UTILITY P = PARITY-SIZED EQUIPMENT GROUND CONDUCTOR X = EXISTING FEEDER TO REMAIN UNLESS OTHERWISE NOTED T = UPSIZED GROUND CONDUCTORS FOR TRANSFORMER SECONDARY2 - CONDUCTOR AMPACITY3 - TOTAL NUMBER OF PHASE AND GROUNDED ("NEUTRAL") CONDUCTORS4 - CONDUCTOR MATERIAL: C = COPPER, A = ALUMINUM5 - SPECIAL (MAY BE BLANK) I = ISOLATED GROUND (PROVIDE CONTINUOUS INSULATED ISOLATED EQUIPMENT GROUNDING CONDUCTOR(S) FROM INSULATED ISOLATED GROUNDBAR(S) TO RESPECTIVE UPSTREAM SERVICE ENTRANCE OR DERIVED SYSTEM GROUNDING ELECTRODE CONDUCTOR AS APPLICABLE.

ELECTRIC FEEDER SCHEDULE

SUPPLY TOSUPPLYFROM FEEDER ID FEEDER DEMAND (A) VD % NOTES

UTILITY 28 A

-- MSB UTILITY !XC-U2660-4C

EXISTING FEEDER, (7) SETS OF (4) #500 KCMIL CU IN 4" CONDUIT EACH 28 A 0

---- LP1-2 MSB XC-200-4C EXISTING FEEDER, (4) #3/0 AWG CU, (1) #4 AWG CU GND. IN 2" CONDUIT 28 A 0

TYPICAL EQUIPMENT NAME NOMENCLATURE:1 - POWER DISTRIBUTION SYSTEM (BLANK - NORMAL, E - EMERGENCY, S - STANDBY, L - LIFE SAFETY)2 - DESCRIPTION (H - 480Y/277V, L - 208Y/120V)3 - FLOOR / LEVEL4 - SEQUENCE

ELECTRIC PANELBOARD AND SWITCHBOARD SCHEDULE

EQUIPMENT PHASESPACE

NUMBER SPACE NAMESUPPLYFROM POWER BRANCH TYPE VOLTAGE PHASE WIRES DEMAND (kVA) DEMAND (A) MAINS RATING (A)

MAINS FRAMERATING (A) MAINS TYPE FEEDER LUGS TYPE SPD ULSE GEC

ENCLOSURETYPE

FAULTCURRENT

(A)

SHORTCIRCUIT

RATING (A) NOTES

LP1-1 Existing B-50 Room MSB NORMAL Branch Panelboard 208 3 4 0 VA 0 A 175 175 MAIN LUGS ONLY EXISTING FEEDER, (4) #3/0 AWG CU, (1) #4 AWG CU GND. IN 2-1/2" CONDUIT NEMA 1 8874 EXISTING

LP1-2 Existing B-17 Room MSB NORMAL Branch Panelboard 208 3 4 9931 VA 28 A 175 175 MAIN LUGS ONLY EXISTING FEEDER, (4) #3/0 AWG CU, (1) #4 AWG CU GND. IN 2" CONDUIT NEMA 1 17541 EXISTING

MSB Existing UTILITY NORMAL Switchboard 208 3 4 9931 VA 28 A 3000 3000 FUSED EXISTING FEEDER, (7) SETS OF (4) #500 KCMIL CU IN 4" CONDUIT EACH NEMA 1 37258 EXISTING

SCALE: NONE

PARTIAL ELECTRIC SINGLE LINE DIAGRAM

TOTAL ADDED DEMAND AMPS: 28 A

TOTAL DEMAND: 9931.0 VA

DEMAND CALCULATION NOTES

ADDED CONNECTED LOAD: 9910 VA

EXISTING LOAD DEMAND FACTOR:

EXISTING CONNECTED LOAD:

PANEL TOTALS

Receptacle 180 VA 100.00% 180 VA

Non-Continuous 1000 VA 100.00% 1000 VA

Motor 0 VA 0.00% 0 VA

Lighting 84 VA 125.00% 105 VA

Kitchen Equipment 0 VA 0.00% 0 VA

Heating 8646 VA 100.00% 8646 VA

Cooling 0 VA 0.00% 0 VA

Continuous 0 VA 0.00% 0 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND BREAKER QUANTITIES (NEW ONLY)

20

19

18

17

16

15

14

13

12

11 150 A -- 3 -- -- -- (EX) SPARE 0.00 kVA

10 200 A -- 3 -- -- -- (EX) SPARE 0.00 kVA

9 200 A -- 3 -- -- -- (EX) SPARE 0.00 kVA

8 175 A -- 3 -- -- -- (EX) SPARE 0.00 kVA

7 175 A 175 A 3 SL SL SL (EX) LP1-2 9.91 kVA

6 175 A 175 A 3 SL SL SL (EX) LP1-1 0.00 kVA

5 125 A -- 3 -- -- -- (EX) LPB-3 0.00 kVA

4 100 A -- 3 -- -- -- (EX) LPB-2 0.00 kVA

3 100 A -- 3 -- -- -- (EX) LPB-1 0.00 kVA

2 -- -- -- -- -- -- (EX) SPACE 0.00 kVA

1 2500 A -- 3 -- -- -- (EX) BUS DUCT MAIN 0.00 kVA

CKT TRIP FRAME POLES VD% AWG GND CIRCUIT DESCRIPTION LOAD

NOTES:

FEEDER: EXISTING FEEDER, (7) SETS OF (4) #500 KCMIL CU IN 4" CONDUIT EACH

FEEDER ID: !XC-U2660-4C PHASE: Existing

200% NEUTRAL: ISOLATED GROUND:

MAINS TYPE: FUSED ULSE:

MAINS RATING (A): 3000 SURGE SUPRESSION:

DISTRIBUTION SYSTEM: 208/120V 3PH 4W ENCLOSURE TYPE: NEMA 1

LOCATION: SHORT CIRCUIT RATING (A): EXISTING

SUPPLY FROM: UTILITY FAULT CURRENT (A): 37258

SWITCHBOARD: MSB

TOTAL DEMAND AMPS: 28 A

TOTAL DEMAND: 9.9 kVA

DEMAND CALCULATION NOTES:

TOTAL CONNECTED LOAD: 9.9 kVA

PANEL TOTALS

Receptacle 180 VA 100.00% 180 VA

Non-Continuous 1000 VA 100.00% 1000 VA

Lighting 84 VA 125.00% 105 VA

Heating 8646 VA 100.00% 8646 VA (1) 30A / 3P

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND NOTES: BREAKER QUANTITIES (NEW ONLY)

TOTAL CONNECTED LOAD: 2.9 kVA 3.1 kVA 3.9 kVA

41 (#) DOOR OPERATOR | NON-CONTINUOUS 1.957 #12 #12 20 A 20 A 1 1.00 2.88 42

39 (#) RECEPTACLE VESTIBULE 149 0.382 #12 #12 20 A 20 A 1 0.18 2.88 40

37 0.00 2.88

3 30 A 30 A #10 #10 1.628 ECH-1 | HEATING VESTIBULE 149

38

35 0.00 0.00 36

33

(EX) MOTOR OPERATED DOOR - RM 116 -- -- -- 15 A -- 3

0.00 0.00 34

31 0.00 0.00

3 -- 15 A -- -- -- (EX) TRASH COMPACTOR - RM 116

32

29(EX) ELEC. CONV. - RM 111 -- -- -- 20 A -- 2

0.00 0.00 30

27 0.00 0.002 -- 20 A -- -- -- (EX) IAC UNIT - RM 132

28

25(EX) ELECT. CONVECTOR - RM 115 -- -- -- 15 A -- 2

0.00 0.00 26

23 0.00 0.002 -- 15 A -- -- -- (EX) ELEC. CONV. - RM 115

24

21(EX) CLEANING OUTLETS RM 119 -- -- -- 15 A -- 2

0.00 0.00 1 -- 20 A -- -- -- (EX) FLOOR OUTLETS - RM 132 22

19 0.00 0.00 20

17(EX) CLEANING OUTLETS - 2ND THROUGH 8TH FLS -- -- -- 15 A -- 2

0.00 0.002 -- 20 A -- -- -- (EX) CLEANING OUTLETS - 9TH THROUGH 16TH FLS

18

15 (EX) LIGHTS - STAIR #2 -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) LIGHTS - STAIR #2 16

13 (EX) LIGHTS - 1ST AND BASEMENT FL, STAIR #2 -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) LIGHTS - 2ND THROUGH 16TH FLS 14

11 (EX) OUTLETS -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) LIGHTS - 2ND THROUGH 16TH FLS 12

9 (EX) OUTLETS - RM 115 -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) OUTLETS 10

7 (EX) OUTLETS -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) OUTLETS - RM 115 8

5 (EX) OUTLETS - RM 115, 116, 117 -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) OUTLETS - RM 115, 116, 117 6

3 (EX) RM #110 AND REAR CANOPY LIGHTING -- -- -- 20 A 20 A 1 0.08 0.00 1 -- 20 A -- -- -- (EX) LIGHTS - RM 133, 132 4

1 (EX) LIGHTS -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) LIGHTS 2

CKT CIRCUIT DESCRIPTION VD% AWG GND TRIP FRAME POLE A B C POLE FRAME TRIP GND AWG VD% CIRCUIT DESCRIPTION CKT

FEEDER: EXISTING FEEDER, (4) #3/0 AWG CU, (1) #4 AWG CU GND. IN 2" CONDUIT ENCLOSURE TYPE: NEMA 1 ISOLATED GROUND:

DISTRIBUTION SYSTEM: 208/120V 3PH 4W FEEDER ID: XC-200-4C LUGS TYPE: 200% NEUTRAL:

LOCATION: Room B-17 MAINS TYPE: MAIN LUGS ONLY SHORT CIRCUIT RATING (A): EXISTING ULSE:

SUPPLY FROM: MSB MAINS RATING (A): 175 FAULT CURRENT (A): 17541 SURGE SUPRESSION:

PANEL NAME: LP1-2 PHASE: Existing

DCMCSDCNTSC/BFUSEFLAMCACP

LOCAL DISCONNECTMOTOR CONTROL (POWER)DUCT SMOKE DETECTORCONTROLSTOGGLE SWITCHH.A.C.R. CIRCUIT BREAKER AT SOURCE PANELBOARDFUSE AT LOCAL DISCONNECT (VERIFY FIELD RATING)OPERATING FULL LOAD AMPSMINIMUM CIRCUIT AMPACITYCORD AND PLUG CONNECTION

ECEXFCGCHCMFRPCOR

ELECTRICAL CONTRACTOREXISTINGFIRE PROTECTION CONTRACTORGENERAL CONTRACTORHVAC CONTRACTORMANUFACTURERPLUMBING CONTRACTOROWNER OR OTHERS

CSMCCMGMSVFDMSROV

COMBINATION STARTERMOTOR CONTROL STARTERMAGNETIC STARTER OR CONTACTMANUAL STARTERVARIABLE FREQUENCY DRIVEMANUAL STARTER W/ CONTROL RELAYOVERCURRENT PROTECTION

TCCPTBASLOWLINERLINEMANFACOINTASDDSD

TIMECLOCKCONTROL POWER TRANSFORMERBUILDING AUTOMATION SYSTEMLOW VOLTAGE CONTROLSLINE VOLTAGE CONTROLSREVERSE ACTING LINE VOLTAGE THERMOSTATMANUALFIRE ALARMCARBON MONOXIDE SENSORINTEGRAL TO EQUIPMENTAREA SMOKE DETECTORDUCT SMOKE DETECTOR

ABBREVIATIONS CONTRACTOR TYPE MOTOR CONTROL TYPE CONTROL TYPE

HVAC ELECTRICAL COORDINATION SCHEDULE

EQUIPMENT MARK DESCRIPTION VOLTS (V) PHASE EMERGENCY BHP (HP) HP (HP) HTG (kW) WATTS FLA (A) MCA (A) OCP (A) DC TYPE DC FURN DC INST DC WIRE MC TYPE MC FURN MC INST MC WIRE CN TYPE CN FURN CN INST CN WIRE FA SHUTDOWN

AVAILABLEFAULT CURRENT

(A)

ECH-1 WALL ANDCEILING HEATER

208 3 5 24 EC EC EC --- --- --- --- LOW MFR MFR MFR 1634

ELECTRIC EQUIPMENT SUPPLY SCHEDULE

EQUIPMENTMARK

SUPPLYFROM CKT EMERG.

LOAD(kVA)

AVAILABLEFAULT

CURRENT VOLTS POLEHTGKW WATT HP

FLA(A)

MCA(A)

RQDOCP (A)

BREAKERRATING (A)

ECH-1 LP1-2 38,40,42 8.65 1634 208 V 3 5 24 30

PANEL SCHEDULE LEGEND(EX) = EXISTING CIRCUIT TO REMAIN(#) = NEW CIRCUIT TO EXISTING CIRCUIT BREAKER(G) = PROVIDE GROUND-FAULT CIRCUIT INTERRUPTER (GFCI) CIRCUIT BREAKER(L) = PROVIDE LOCK-ON DEVICE* = WIRE SIZED TO COMPENSATE FOR VOLTAGE DROP** = REFER TO DRAWINGS FOR SPECIFICATIONSSL = SEE THE SINGLE LINE DIAGRAM / SCHEDULE FOR WIRE SIZE AND VOLTAGE DROP

PANEL SCHEDULE GENERAL NOTESA. PROVIDE HACR RATED BREAKERS ON ALL MOTOR LOADS.B. PROVIDE LOCKING TYPE BREAKER FOR ALL LIFE SAFETY AND NIGHT LIGHTING BRANCH CIRCUITS. C. ALL VOLTAGE DROP CALCULATIONS AND COMPENSATED WIRE SIZES ARE BASED ON RIGHT

ANGLE CIRCUIT LENGTHS TO THE LAST DEVICE. ACTUAL VOLTAGE DROP VARIES BASED ON INSTALLED WIRE LENGTH.

D. RECEPTACLE LOADS CALCULATED AT 100% OF FIRST 10kVA, 50% OF REMAINDER. MOTOR LOADS CALCULATED AT 125% OF LARGEST MOTOR, 100% OF ALL OTHER MOTORS.

REV

REVISIO

NS

DATE

BY

0IS

SUE FOR B

IDDIN

G AND PERMIT

05/22/2020

MJG

05/14/2020