Page 1: New VD4-Rockwill

VD4/P-12VD4/P-24

VD4(S)

VD4-36

ROCKWILLROCKWILLHV Vacuum Circuit BreakerHV Vacuum Circuit Breaker

2014

Page 2: New VD4-Rockwill

1 2 3 5 7 8

964

1 6

2 7

3 8

4 9

5

Product Features

01 02

ROCKWILL

Monolithic operating handle, more convenient and safer.

There is a registered trademark of manufacturer Rockwill electrical in the central position of the left side of the products panel.

There is a registered trademark of product type in the upper right position of the products panel.

There is product parameters label in the right position of products panel.

Epoxy resin uses Ciba resin; vacuum arc-extinguishing chamber adopts German alsburg interrupter.

Contact pressure spring is with German Mu Bei spring.

The main spring is with German Gruber spring.

Reserved intelligent online monitoring interface.

Long mechanical life, 50000 times.

To provide higher value for customers.

ROCKWILL

Page 3: New VD4-Rockwill

Drive Mechanism ROCKWILL

VD4 type circuit breaker spring operating mechanism

Modular secondary control

circuit board, with self plug

fastened, is convenient to

replace, and ensure the

reliability of the electrical

connection.

Circuit board Closing unit

Closing unit has the advantages

of simple structure, reliable

operating principle. Not only

fundamentally put an end to

the occurrence of unable to

keep after closing, breaking

fai lure and so on, but also

reduces the trip needed power.

Closing or tripping electromagnet

Electromagnet adopts all

closed structure design,

to ensure that the coil will

not be influenced by damp.

Tripping buffer

High-performance buffer can

reduce the circui t breaker

moving contact overshoot

or rebound amplitude in the

opening t ime, reduce the

probability of circuit breakers

arc restr ik ing, and ensure

the mechanical life of vacuum

interrupter bellows.

Surface treatment

80% of mechanism parts surface adopts the Ni-P alloy plating process; greatly improved the corros ion resistance of parts, to en-sure the stable quality of machine being consistent f rom beginn ing to end. Closing unit has the ad-vantages of simple struc-tu re , re l i ab le opera t ing principle, Not only funda-menta l ly put an end to unable maintenance after closing, and breaking failure, but also reduces the trip needed power

The operating mechanism has the advantages of s imple structure, reliable action, pro-duct parts of different speci-fications is of the strong ver-satility, because the agency fully developed by our comp-any, i t can be customized according to user's different r e q u i r e m e n t s o f s p e c i a l products.

Overall advantages

Every detail of VD4 circuit breaker is to strive for perfection.

03 04

Page 4: New VD4-Rockwill

VD4/P-12

General Principals

VD4 (P) -12 type sealed high-voltage vacuum circuit breaker independently developed by our company is the leading domestic level of a new generation of 12kV vacuum circuit breaker .Its main feature is that the main circuit adopts the solid insulation solid sealed pole, which uses a special embedded technology, to pour the epoxy resin into vacuum interrupter with ultra low resistance and conductive parts, so as to realize the solid insulation of main circuit. The operating mechanism is new- type spring one, which is independently researched and developed by my company, has the advantages of simple structure, reliable action, and manufacturing experience for launching tens of thousands of the products, used and referenced by a number of domestic high-end vacuum circuit breaker manufacturers.

VD4(P)-12 type sealed high-pressure vacuum circuit breaker Every technical parameter is completely complied with GB1984, GB/T11022, China power Industry standard DL 403, at the same time also meet the standard,IEC62271-100 IEC56 and the related standard provisions of other major industrialized countries.

Standard

VD4(P)-12 type sealed high-pressure vacuum circuit breaker owns perfect mechanical & elect r ica l in ter lock ing device, i t is also with high operation reliability and service life. Matching with the suitable switchgear to complete safe distribution funct ion, ensure the safety of the operator and the equipment.

Security of operation

VD4(P)-12 type sealed high-pressure vacuum circuit breaker can be widely used in Power plant, power network, metallurgical, petrochemical, city infras-tructure such as airports, buildings, sub-way project.

VD4-40.5 series of indoor high voltage vacuum circuit breaker in the distribution system can be applied to the control and protection of cables, overhead trans-mission l ine, transformer, motor, gen-erator, and capacitor bank.

Application range

VD4(P) -12 type sealed high voltage vacuum circuit breaker has passed the following tests to ensure the security of operation.

·Type tests: power frequency withstand voltage, lightning impulse withstand voltage, temperature rise, short time and peak withstand current, short circuit current switching capability mechanism life etc.

·Factory routine test: The mechanical performance test, the main circuit power frequency withstand voltage test, auxiliary and control circuit insulation performance test , the main loop resistance test, interlock operation test, mechanical and electrical operation test.

Test

Embeded pole type high-voltage vacuum circuit breaker

05 06

Page 5: New VD4-Rockwill

External Dimensions

P h2 h1 A B I H K W

20~31.5kA 630~1250A

150 205 260 502 503 492

620.5 6090+2

630A

35210 205 260 650 653 638 800

1250A275 205 260 850 853 842 1000

20~31.5kA 630~1250A 150 275 280 502 503 492637

6000+2

630A 35

20~40kA 630~1600A210 275 280 650 653 638 800 1250A 49

275 275 280 850 853 842 637/698 1000 1600A 55

P h2 h1 a b c

20~31.5kA 630~1250A 210 275 237 588 564.5 520

P h1/h2 a c

31.5~40kA 1600~4000A 275 252/310 770 720

1

45

14.5

16

8

8~10

Trip 8~10

436

200 50

4

K

588 ± 2

361

200

19

h2

W

W

HH

15

4

76

I

h1

I

B

45

14.5

16

19

h1

16

5

76

B

h2

A

P P

A

P P

φ9

8

0-3

0-3 50

4

b

h2

h1

444

676

h2

h1

c

p

p p

a

c

4-M12

4-M12

p

A

A

1

40 275

440

275

441.5

20

VD4/P-12

07 08

Dimensions of VD4/P-12 handcart type vacuum circuit breaker

Rated current

Rated short-circuit breaking

current

Width of matching cabinet

Rated current

Trip

P A B I H h1 / h2 W

31.5~40kA

1600A 210 650 653 638698

295/310 280/310

800 1600A 55

1600~2000A 275 850 853 8421000

1600~2000A 79

2500~4000A 275 850 853 842 735 2500~4000A 109

Notes: 1) Circuit breaker shall take the cooling cover when the rated current is

above of 2500A.

2) When using forced air cooling, the rated current can be up to 4000A.

Rated current

Rated short-circuit breaking

current

Width of matching cabinet

Rated current

Dimensions of VD4/P-12 Fixed vacuum circuit breaker dimensions

The A dimension, please confirm with my company.

Rated current

Rated short-circuit breaking current

The A dimension, please confirm with my company.

Rated current

Rated short-circuit breaking current

Notes: 1) Circuit breaker shall take the cooling cover when the

rated current is above of 2500A.

2) When using forced air cooling, the rated current can

be up to 4000A.

650

650

Page 6: New VD4-Rockwill

Type

ZYJ55-1DC110V

75 , 100 ≤ 15DC220V

DC220 DC110 DC220 DC110 DC220 DC110 DC220 DC110

1.1 2.2 1.1 2.2 25 mA 9.1 mA

242 242 242 242 2.7 1.0

85%~110% - -

Technical Parameter

AC 220V / 110V

DC 220V / 110V 3.5 / 5 / 7.5 / 10

No. Item Unit

1

kV

12

2 42

3 75

4 Hz 50

5 A

630 630 1250 1250

1250 1250 1600 1600

2000 2000

2500 2500

3150 3150

4000 4000

6

kA

20 25 31.5 40

7 20 25 31.5 40

8 50 63 80 100

9 50 63 80 100

10 20 25 31.5 40

11 50 63 80 100

12 12.5(The frequency is not more than 1000Hz)

13 A 630 / 400

14 S 4

15

V

2000

16

AC 110 / 220 DC 110 / 220

AC 110 / 220 DC 110 / 220

AC 110 / 220 DC 110 / 220

17ms

20 ~ 50

18 30 ~ 70

19 mm 3

20 s ≤ 15

21mm

9± 1

22 3 ~ 4

23ms

≤ 2

24 ≤ 2

25ms

0.9 ~ 1.3

26 ~ 1.00.4

27 mm ≤ 2

28 μΩ630 55 45

1250 45 40

1600 ~ 2000 35 30

2500 and above 25 20

29 Open -θ - Cose -180s - Cose

30 Times50000(31.5KA and below )

20000(40KA)

Rated voltage

Rated insulation level

1min frequency withstand voltage

Rated short time power

Rated lightning impulse withstand voltage (peak)

Rated frequency

Rated current

Rated short circuit breaking current

Rated short time withstand current

Rated peak withstand current

Rated short circuit making current (peak)

4S thermal stability current

Rated dynamic stability current

Rated capacitor bank making inrush current

Rated single/back- to-back capacitor bank breaking current

Rated short circuit duration

Secondary loop power frequency withstand voltage

(A)Rated current (μΩ)Handcart type (μΩ)Fixed type

1. Average opening velocity refers to the average speed after the circuit breaker contact just open for 6mm.

2. Average closing speed refers to the average speed of total contactor space.

3. When the rated short-circuit breaking current is less than 40KA,θ is 0.3s, When the rated short-circuit breaking

current is more than 40KA,θ is 180s.

Technical data

Rated operation voltage

Energy storage motor

Tripping time (rated voltage)

Dynamic, static contacts permit abrasion total thickness

Different period of three-phase break and close brake

The average opening velocity1

The average opening velocity2

Contact opening rebound amplitude

Closing time (rated voltage)

Energy storage time

Contact opening distance

Contacting travel

Contact bouncing time

The main circuit resistance

Rated operating sequence3

Closing coil

Tripping coil

Mechanical life

09 10

Technical parameters of closing, tripping electromagnet and related electrical components

Rated operational voltage (V)

Rated operational current (A)Rated electric power (W)

Normal operational voltage range

65%~120% of rated voltage, When less than 30% of rated voltage, the switch can not open.

The secondary control loop scheme combination

With electric lockout / Without electric lockout

With anti-jump relay / Without anti-jump relay

With under voltage tripping / Without

under voltage tripping

With over current trip / Without over

current trip

Over current trip numbers

Two over current/three over current

Action current value

Electrical energy storage technology parameters

Rated voltage (V)Rated electric

power (W)

85% ~ 110%

Rated voltage

Energy storage time of the rated voltage (S)

ItemCategory Closing electromagnet Tripping electromagnet Latching electromagnet Anti jump relay

Normal working voltage range Rated voltage (V)

Control voltage Blocking scheme Anti-jump schemeUnder voltage

tripping scheme Overcurrent trip scheme

VD4/P-12

Page 7: New VD4-Rockwill

11 12

VD4-12Indoor high voltage vacuum circuit breaker

General Principals

Every technical parameter is comp-letely complied with GB1984、GB/T11022 ,China power Industry standard DL 403, at the same time also meet the standard,IEC62271-100 IEC56 and the related standard provisions of other major industrialized countries.

Standard

VB-12 Indoor high voltage vacuum circuit breaker owns perfect mechanical & electrical interlocking device, it is also with high operation reliability and service l i fe, matching with the suitable switchgear to complete safe distribution function, ensure the safety of the operator and the equipment.

Security of operation

VB-12 Indoor high voltage vacuum circuit breaker can be widely used in Power plant, power network, metallurgical, petrochemical, city infrastructure such as airports, buildings, subway project.

VD4-40.5 series of indoor high voltage vacuum circuit breaker in the distribution system can be applied to the control and protection of cables, overhead trans-mission l ine, transformer, motor, gen-erator, and capacitor bank.

Application range Test

VB-12 Indoor high voltage vacuum circuit breaker independently developed by our company is the leading domestic level of a new generation of 12kV vacuum circuit breaker, Its main feature is that the main circuit is installed in the full sealed three-phase insulating cylinder the operation mechanism and the main circuit was of before and after layout The operating mechanism is new- type spring one, which is independently researched and developed by my company, has the advantages of simple structure, reliable action, and manufacturing experience for launching tens of thousands of the products, used and referenced by a number of domestic high-end vacuum circuit breaker manufacturers.

VB-12 Indoor high voltage vacuum circuit breaker has passed the following tests to ensure the security of operation.

·Type tests: power frequency withstand voltage, lightning impulse withstand voltage, temperature rise, short time and peak withstand current, short circuit current switching capability and current switching test of cable charging.

·Factory routine test: The mechanical performance test, the main circuit power frequency withstand voltage test, auxiliary and control circuit insulation performance test , the main loop resistance test, interlock operation test, mechanical and electrical operation test.

Page 8: New VD4-Rockwill

External Dimensions

652

650

640

210 210 16

8

14.5 14.5

638

27

52

80

78

76

43

.5

21

.5

436 50

40 89

4

45

19

10

63

7

600+20

200 0-3

842

45

14.5 14.5852

588

8

16275275

838

850

361

89

50

4

19

10

31

02

95

69

8

21

.5

88

77

43

.5

200 0-3

1600~4000 31.5~40 1000

1600A CT-36 ф55

1600/2000 CT-48 ф79

2500/3150 CT-64ф109

4000 CT-82

13 14

VD4-12

Trip 8~10

Dimensions of VD4-12 handcart type (spaced 210) vacuum circuit breaker

630~1250 20~40 800

630 CT-24

1250 CT-30

1600 CT-36

ф35

ф49

ф55

Rated

current (A)

Rated short-circuit

breaking current (kA) Width of m

cabinet

(mm)

atching Assorted

sizes

of moving

and fixed

contacts

Rated

current (A)Contact plum

The sizes of

fixed contact

Note: The main circuit uses sleeve type.

Dimensions of VD4-12 handcart type (spaced 275) vacuum circuit breaker

±2

Trip 8~10

Rated

current (A)

Rated short-circuit

breaking current (kA) Width of m

cabinet

(mm)

atching Assorted

sizes

of moving

and fixed

contacts

Rated

current (A)Contact plum

The sizes of

fixed contact

Note: The main circuit uses sleeve type.

Page 9: New VD4-Rockwill

15 16

VD4-12F

Dimensions of VD4-12F fixed type (spaced 210) vacuum circuit breaker Dimensions of VD4-12F fixed type (spaced 275) vacuum circuit breaker

Note: The main circuit uses sleeve type.

Rated

current (A)

Rated short-circuit

breaking current (kA)

-side

-side

Copper bar

-side

1:4

-side

Rated

current (A)

Rated short-circuit

breaking current (kA)

Note: The main circuit uses sleeve type.

Page 10: New VD4-Rockwill

17 18

VD4-12

1. Average opening velocity refers to the average speed after the circuit breaker contact just open for 6mm.

2. Average closing speed refers to the average speed of total contactor space.

3. When the rated short-circuit breaking current is less than 40KA,θ is 0.3s, When the rated short-circuit breaking

current is more than 40KA,θ is 180s.

No. Item Unit Technical data

No. Item Unit Technical data

Times

Rated voltage

Rated insulation level

1min frequency withstand voltage

Rated short time power

Rated lightning impulse withstand voltage (peak)

Rated frequency

Rated current

Rated short circuit breaking current

Rated short time withstand current

Rated peak withstand current

Rated short circuit making current (peak)

4S thermal stability current

Rated dynamic stability current

Rated capacitor bank making inrush current

Rated single/back- to-back capacitor bank breaking current

Rated short circuit duration

Secondary loop power frequency withstand voltage

Rated operation voltage

Energy storage motor

Tripping time (rated voltage)

Dynamic, static contacts permit abrasion total thickness

Different period of three-phase break and close brake

The average opening velocity1

The average opening velocity2

Contact opening rebound amplitude

Closing time (rated voltage)

Energy storage time

Contact opening distance

Contacting travel

Contact bouncing time

The main circuit resistance

Rated operating sequence3

Closing coil

Tripping coil

Mechanical life

12.5(The frequency is not more than 1000Hz)

(A)Rated current (μΩ)Handcart type (μΩ)Fixed type

2500 and above

Open -θ - Cose -180s - Cose

(50000 31.5KA and below )

20000(40KA)

AC 220V / 110V

DC 220V / 110V 3.5 / 5 / 7.5 / 10

The secondary control loop scheme combination

With electric lockout / Without electric lockout

With anti-jump relay / Without anti-jump relay

With under voltage tripping / Without

under voltage tripping

With over current trip / Without over

current trip

Over current trip numbers

Two over current/three over current

Action current value

Control voltage Blocking scheme Anti-jump schemeUnder voltage

tripping scheme Overcurrent trip scheme

DC220 DC110 DC220 DC110 DC220 DC110 DC220 DC110

1.1 2.2 1.1 2.2 25 mA 9.1 mA

242 242 242 242 2.7 1.0

85%~110% - -

Technical parameters of closing, tripping electromagnet and related electrical components

Rated operational voltage (V)

Rated operational current (A)Rated electric power (W)

65%~120% of rated voltage, When less than 30% of rated voltage, the switch can not open.

ItemCategory Closing electromagnet Tripping electromagnet Latching electromagnet Anti jump relay

Normal working voltage range Rated voltage (V)

Type

ZYJ55-1DC110V

75 , 100DC220V

Normal operational voltage range

Electrical energy storage technology parameters

Rated voltage (V)Rated electric

power (W)

85% ~ 110%

Rated voltage

Energy storage time of the rated voltage (S)

≤ 15

Page 11: New VD4-Rockwill

19 20

VD4(S)-12VD4(S)-12VD4(S)-12VD4(S)-12

VD4(S)-12

Intelligent sealed high-pressure vacuum

circuit breaker is a new generation of 12kV

one which has the innovative significance

for the future smart grid and the construction

of Internet of things.

Page 12: New VD4-Rockwill

21 22

VD4(S)/P-12

·Equipping with SMART online monitoring technology joint developed with the German ALSBURG company. The circuit breaker control circuit disconn- ection alarm function Vacuum degree on-line monitoring function of vacuum interrupter of circuit breaker. Temperature online monitoring function of the main circuit of circuit breaker. Online monitoring function of circuit breaker over travel change. ·The main circuit adopts the solid insulation solid sealed pole.·The integration of spring operating mechanism with a number of patents.·Long life, high reliability.

Technical characteristic

VD4(S)-12 intelligent solid sealed high voltage vacuum circuit

breaker design meet the standard of VD4(S)-12.

·GB1984-2003 AC high voltage circuit breaker.

·GB/T11022-1999 Common specif ications for high-voltage

switchgear and control gear standards.

·DL403-9910~35 indoor AC high voltage vacuum circuit breaker

order technical conditions.

·DL593-2006 Common technical specifications for high-voltage

switchgear and control equipment.

·IEC62271-100AC High voltage circuit breaker.

·JB3855-963.6~40.5KV indoor AC high voltage vacuum circuit

breaker.

·GB/T18268-2000 Electromagnetic compatibility requirements

for electrical equipment used for measurement, control and

laboratory.

·GB/T17799.2-2003 Immunity test of EMC general standard

in industrial environment.

·GB/T17626.2-2006 Electromagnetic compatibility testing and

measurement techniques.

Technical criteria

Safe and reliable

VD4 (S) -12 intelligent sealed vacuum circuit breaker with intelligent online monitoring function, can be real- t ime

monitoring of the circuit breaker in the running state, give out the alarm signal and to the remote transmission when

the fault comes. At the same time, the product is equipped with perfect mechanical and electrical interlock to ensure

the safety in the process of operation and inspection. Product design, manufacturing, installation, service systems

strictly implement ISO9001, 2000 standards to ensure that product quality is stable and reliable.

VD4 (P)-12 type sealed high voltage vacuum circuit breaker has passed the following tests to ensure the security of operation.

VD4 (S) -12 intelligent sealed vacuum circuit breaker can be used in energy and infrastructure, industrial, commercial and civil construction in the field of medium voltage distribution network protection and control, esp-ecially suitable for the HV / MV, MV / MV substation.

·The complete seriesVD4 (S) -12 intelligent sealed vacuum circuit breaker:

rated voltage12KV, rated current 630A, 1250A, 1600A、2000A、2500A、3150A、4000A,rated short circuit breaking

current: 20KA、25KA、31.5KA、40KA.

·Strong adaptabilityVD4 (S) -12 intelligent sealed vacuum circuit breaker divided into handcar type and fixed type.

Application range Test

·Type testTemperature rise test.Mechanical life test.Dynamic thermal stability test.Short circuit current switching capacity test.Short time and peak withstand current test.Power frequency withstand voltage, lightning impulse withstand voltage.

·Special testCapacitor test.High altitude 3500m test.

·Delivery testVacuum break,phrase,to earth power frequency withstand voltage test.Auxiliary and control circuit insulation test.Mechanical, electrical operation experiment.Opening or Closing Simultaneity test.Opening or Closing time test.Bounce time test.Mechanical property test.Circuit resistance test.Visual inspection.Product overview of VD4(S)-12.

Page 13: New VD4-Rockwill

23 24

VD4(S)/P-12

·For the secondary control circuit fault, the most common is the tripping coil

burning, and can not trip when the fault comes.

·High temperature of the main circuit leads material aging, failure of insulation,

and causes equipment damage.

·The vacuum interrupter leakage can loss breaking capacity.

·Circuit breaker short-circuit current capacity decreased in the running for a period

of time, at the same time the electric life decline.

Common fault and fault can not be forecasted of circuit breaker

Circ

uit b

rea

ke

r

Vacuum sensor

Disconnection sensor

Overtravel sensor

Temperature sensor

Timely adjusting circuit breaker when parameter is poor.

Supervisory personnel Supervision center

A/D conversion

Signal multiplication

Signal encoding Memorizer

Central processing unit

Input / output interface circuit Output circuit

Audible and visual alarm

Remote data transmission

Online monitoring solution

Display screen

Vacuum alarm

Vacuum of A phrase interrupter is abnormal, please repair immediately.

Over-travel test

A phrase overtravel

Overtravel alarm value

Switchgear panelSwitchgear panel recommended the

use of mouth opening112×112

Open-pore size chart

·Simple operation: Touch operation, human-computer interaction interface.

·The circuit breaker control circuit disconnection alarm function

The function of the circuit breaker during normal operation can automatically detect the integrity of the tripping control loop.

· online temperature monitoring function

The main circui t of circui t breaker

The function during the circuit breaker operation, if conductive loop temperature exceeds the allowable value will auto-mat ica l ly send alarm s ignal , remind operators to make timely check. Ensure that the circuit breakers will not long-term operation in high temperature conditions.

Tripping circuit alarm Return to the main interface

Tripping circuit breaks, please repair immediately.

Contact temperature rise test

Inspection date

Ambient temperature

A phrase temperature rise

B phrase temperature rise

C phrase temperature rise

Temperature rise alarm value

Referring to the historical value

ROCKWILLReturn to the main interface

Vacuum monitoring

Trip circuit disconnection

monitoring

Contact temperature

test

Ultra stroke detection

Parameter settings

Help

Return to the main interface

Return to the main interface

B phrase overtravel

C phrase overtravel

Referring to the historical value

· breaker online temperature monitoring function

The in ter rupter Vacuum of c i rcu i t

The function during the circuit breaker operation, i f the interrupter vacuum exceeds the allowable value will auto-matically send alarm signal, remind operators to make timely check. Ensure that the interrupter of circuit breaker would not long- term operation in the loss of breaking capacity, to stop the occurrence of breaking failure.

· function

Short circuit breaking capacity monitoring

The function during the circuit breaker operation can automatically monitor the variation of over travel displacement, if you exceed the allowable value, it can be adjusted on the spot.

VB(S)-12

Page 14: New VD4-Rockwill

25 26

VD4(S)/P-12

Switchgear type

Prim

ary s

yste

m d

iag

ram

Controlled equipment

Loop name

Vacuum circuit breaker

High voltage fuse

Current transformer

Voltage transformer

Surge arrestor

High voltage live display

Grounding switch

Ma

in e

lectric c

om

po

ne

nt

Zero sequence current transformers

1# incoming cabinet

1# PT cabinet

1# capacitor compensation

cabinet1# Blower

start cabinet1# Blower operation cabinet

2# Blower start cabinet

2# Blower operation cabinet

1# Transformer cabinet

2# Transformer cabinet

1# Slurry pump

2# Slurry pump

3# Slurry pump

1# Electric furnace dust removal fan

1# Furnace casthouse

dedusting fan

Fan spare cabinet

Bus isolating cabinet

Functional instruction

VD4(S)-12

Product function configuration instructions

A type

B type

C type

Real- time monitoring the worsening situation of short-circuit breaking capacity, giving out an alarm signal to inform the background when reaching a preset threshold value.

Intelligent feeder switch

Intelligent line, contact switch

Intelligent motor protection switch

Short circuit breaking capacity monitoring function

Real-t ime monitoring main circuit temperature changes, giving out an alarm signal to inform the background when reaching a preset threshold value.

Temperature monitoring function

Monitoring the vacuum condition

Real- time monitoring the change of the vacuum degree of vacuum interrupter, in the vacuum deterioration imme-diately issued a warning signal to inform the background.

Two disconnection alarm function

Real- time monitoring con-d i t ion of the secondary control loop. To give out an alarm signal to inform the background when reaching a preset threshold value.

Optional

Optional

Optional

VD4(S)-12B VD4(S)-12C VD4(S)-12C VD4(S)-12C VD4(S)-12A VD4(S)-12C VD4(S)-12C VD4(S)-12C

VD4(S)-12C VD4(S)-12C VD4(S)-12A VD4(S)-12C VD4(S)-12C VD4(S)-12C

VD4(S)-12

Page 15: New VD4-Rockwill

27 28

VD4(S)/P-12

Surface treatment

80% of mechanism parts surface adopts the Ni-P alloy plating process, greatly improve the corrosion resistance of parts, and ensure the stable quality of machine consistent from beginning to end.

The overall advantages

The operating mechanism has the advantages of simple structure, reliable action, product parts of different specifications is of the strong versatility, because the agency fully developed by our company, it can be customized according to user's different requirements of special products.

Every detail of type circuit breaker is to strive

for perfection.

VB(S)-12

VD4(S)/P-12

Dimensions of handcart type vacuum circuit breakerVD4(S)/P-12

Trip 8~10

The diagram (*698) as phase spacing of 275 sealing plate height options (high-mountain type)

Rated

current (A)

Rated short-circuit breaking

current (kA)

Width ofmatching

cabinet(

mm)Assorted

sizes

of moving

and fixed

contacts

Rated

current (A)Contact

plumThe sizes of

fixed contact

Page 16: New VD4-Rockwill

29 30

VD4(S)/P-12

Dimensions of handcart type vacuum circuit breakerVD4(S)/P-12Dimensions of handcart type vacuum circuit breakerVD4(S)/P-12

Trip 8~10

Rated

current (A)

Rated short-circuit breaking

current (kA)

Width ofmatching

cabinet(

mm)

Rated

current (A)Contact

plumThe sizes of

fixed contactAssorted

sizes

of moving

and fixed

contacts

Trip 8~10

1. Circuit breaker shall take the cooling cover when the rated current is 2500A and above.

2. Using forced air cooling, when the rated current is 3150A and above.

Rated

current (A)

Rated short-circuit breaking

current (kA)

Width ofmatching

cabinet(

mm)Assorted

sizes

of moving

and fixed

contacts

Rated

current (A)Contact

plumThe sizes of

fixed contact

Page 17: New VD4-Rockwill

31 32

VD4(S)/P-12F

Dimensions of fixed type vacuum circuit breaker VD4(S)/P-12F Dimensions of fixed type vacuum circuit breaker VD4(S)/P-12F

A dimension, please confirm with my company.

Rated

current (A)

Rated short-circuit breaking

current (kA)

1.Circuit breaker shall take the cooling cover, when the rated current is 2500A and above.2.Using forced air cooling, when the rated current is 3150A and above.3. A dimension, please confirm with my company.

Rated

current (A)

Rated short-circuit breaking

current (kA)

Page 18: New VD4-Rockwill

34

VD4(S)/P-12

No. Item Unit Technical data

33

1. Average opening velocity refers to the average speed after the circuit breaker contact just open for 6mm.

2. Average closing speed refers to the average speed of total contactor space.

3. When the rated short-circuit breaking current is less than 40KA,θ is 0.3s, When the rated short-circuit breaking

current is more than 40KA,θ is 180s.

Rated voltage

Rated insulation level

1min frequency withstand voltage

Rated short time power

Rated lightning impulse withstand voltage (peak)

Rated frequency

Rated current

Rated short circuit breaking current

Rated short time withstand current

Rated peak withstand current

Rated short circuit making current (peak)

4S thermal stability current

Rated dynamic stability current

Rated capacitor bank making inrush current

Rated single/back- to-back capacitor bank breaking current

Rated short circuit duration

Secondary loop power frequency withstand voltage

Tripping time (rated voltage)

Dynamic, static contacts permit abrasion total thickness

Different period of three-phase break and close brake

The average opening velocity1

The average opening velocity2

Contact opening rebound amplitude

Closing time (rated voltage)

Energy storage time

Contact opening distance

Contacting travel

Contact bouncing time

Rated operation voltage

Energy storage motor

Closing coil

Tripping coil

The main circuit resistance

Rated operating sequence3

Mechanical life

12.5(The frequency is not more than 1000Hz)

(A)Rated current (μΩ)Handcart type (μΩ)Fixed type

2500 and above

Open -θ - Cose -180s - Cose

(50000 31.5KA and below ) 20000Times

Type

ZYJ55-1DC110V

75 , 100DC220V

Normal operational voltage range

Electrical energy storage technology parameters

Rated voltage (V)Rated electric

power (W)

85% ~ 110%

Rated voltage

Energy storage time of the rated voltage (S)

≤ 15

DC220 DC110 DC220 DC110 DC220 DC110 DC220 DC110

1.1 2.2 1.1 2.2 25 mA 9.1 mA

242 242 242 242 2.7 1.0

85%~110% - -

Technical parameters of closing, tripping electromagnet and related electrical components

Rated operational voltage (V)

Rated operational current (A)Rated electric power (W)

65%~120% of rated voltage, When less than 30% of rated voltage, the switch can not open.

ItemCategory Closing electromagnet Tripping electromagnet Latching electromagnet Anti jump relay

Normal working voltage range Rated voltage (V)

AC 220V / 110V

DC 220V / 110V 3.5 / 5 / 7.5 / 10

The secondary control loop scheme combination

With electric lockout / Without electric lockout

With anti-jump relay / Without anti-jump relay

With under voltage tripping / Without

under voltage tripping

With over current trip / Without over

current trip

Over current trip numbers

Two over current/three over current

Action current value

Control voltage Blocking scheme Anti-jump schemeUnder voltage

tripping scheme Overcurrent trip scheme

Page 19: New VD4-Rockwill

35 36

VD4/P-24Indoor high voltage vacuum circuit breaker

The structure of circuit breaker is with integral layout

Spring operating mechanism and the circuit breaker body part are with integrated design. Primary main circuit and mechanism adopt forth, back layout form, main circuit parts lay behind the circuit breaker, spring operating mechanism lays in front of the circuit breaker, handcart advancing mechanism is located below the circuit breaker, It has the advantage of compact structure, rational layout, machine size small.

Good interchangeability and adaptability of the handcart

Handcart type dimensions of VB-24 series of indoor high voltage vacuum circuit breaker is completely consistent with VD4-24 handcart type vacuum circuit breaker ABB produces,can realize complete interchangeability between military vehicle, thus it is of strong adaptability, wide application range. Adapt cabinet type for VB-24 series of handcart type vacuum circuit breaker is the KYN port of - 24 – mid-set type high voltage switchgear.

The main circuit adopts the structure of sleeve type or solid sealed type structure

·The main circuit of VB-24 series of indoor high voltage vacuum circuit breaker divided into the structure of sleeve type or solid sealed type, which can be conveniently selected by user according to different places.·Sleeve type structure: the primary main circuit vacuum interrupter of circuit breaker is arranged in a sealed insulating cylinder. The insulating cylinder uses epoxy resin material which is mechanical performance reliable, and molding by the use of advanced APG technology. The insulating tube not only plays a supporting role to install, but also have the function of phrase to phrase insulation and phrase to earth insulation. The design of the insulating tube considering the requirements of national standards and the use of harsh working conditions, not only can prevent vacuum inte- rrupter being influenced by the external environment, dust and foreign matter from entering the main loop section, but also can ensure even in hot and humid and serious pollution condition, showing high resistance to voltage effect.·Solid sealed type structure: primary conductive circuit of circuit breaker uses solid sealed pole of solid insulation technology, the solid sealed pole make primary conductive loop and other parts of the vacuum interrupter directly and fixedly sealed in special epoxy resin material, to form a main circuit module.

Reliable integrated spring operating mechanism

·Spring operating mechanism of VB-24 series outdoor high-voltage vacuum circuit breaker is the plain layout one with manual energy storage and electric energy storage function, machine size is small, the whole circuit breaker has good stiffness, operating perfor- mance is consistent from beginning to end.·Main transmission structure of the operating mechanism of VB-24 series of indoor high voltage vacuum circuit breaker is the exten- sion of mature 12kV VBM series actuator. Main transmission reliability has experience of tens of thousands of production, operation. The complete circuit breaker is of action stability, high reliability.

Mid-set handcart structure

·VB-24 series of indoor high vacuum voltage circuit breaker using middle handcart type structure design, to make the machine have the advantages of small volume, compact structure, good rigidity, flexible movement, with high precision. The kind of structure design improved the reliability of movable electrical connection between the breaker handcart and switchgear and the thermal dynamic stability of the whole switchgear.·The handcart of VB-24 series of high voltage vacuum circuit breaker is the extension of handcart chassis technology of 12kV VBM series actuator; adopt screw propulsion mech- anism, accurate movement, with reliable mec- hanical interlock system.

VB-24 series indoor high-voltage vacuum circuit breaker is with fixed type and handcart type, two kinds of installation way, can be very convenient to realize reliable mechanical interlocking " five prevention". It can be directly mounted on the various fixed type switch cabinet, also be equipped with removable switchboard in all types of hand car.

Flexible installation way

Page 20: New VD4-Rockwill

842

850

275 275 16

8

I

2:1

15

89

15

785

310

325

462

747 50

4

21.543.5

300 0-3

126

72

45

1

14.5 14.5852

790

19

842

45

1

14.514.5 853

790

19

830

310

345

89

15

126

72

21.543.5

4

747 50300 0-3

462

850

275 275 16

8

I

2:1

15

External Dimen sion s

630~1250

20~31.5

1000

CT-24

35

1600 1600~2500

20~31.5

1000

CT-36 CT-48

55 79

37 38

VD4/P-24

The dimension of VD4/P-24 sealed vacuum circuit breaker (hand car) The dimension of VD4/P-24 sealed vacuum circuit breaker (hand car)

Trip 8~10

Rated current (A)

Rated short circuit breaking current (kA)

The width of the matching cabinet (mm)

Dynamic and static contact with the size

Contact plum

The static contact size (mm)

Trip 8~10

Rated current (A)

Rated short circuit breaking current (kA)

The width of the matching cabinet (mm)

Dynamic and static contact with the size

Contact plum

The static contact size (mm)

Page 21: New VD4-Rockwill

39 40

VD4/P-24

Trip 8~10

Trip 8~10

The dimension of sleeve type vacuum circuit breaker (handcart type) VD4/P-24

Rated current (A)

Rated short circuit breaking current (kA)

The width of the matching cabinet (mm)

Dynamic and static contact with the size

Contact plum

The static contact size (mm)

The dimension of sleeve type vacuum circuit breaker (handcart type) VD4/P-24

Rated current (A)

Rated short circuit breaking current (kA)

The width of the matching cabinet (mm)

Dynamic and static contact with the size

Contact plum

The static contact size (mm)

Page 22: New VD4-Rockwill

Times

Times

41 42

The dimension of sealed vacuum circuit breaker (fixed) VD4-24F

VD4-24F VD4-24F

Rated operation voltage

No. Item Unit Technical data

Rated voltage

Rated insulation level

1min frequency withstand voltage

Rated short time power

Rated lightning impulse withstand voltage (peak)

Rated frequency

Rated current

Rated short circuit breaking current

Rated short time withstand current

Rated peak withstand current

4S thermal stability current

Rated dynamic stability current

Rated single/back- to-back capacitor bank breaking current

Rated short circuit duration

Secondary loop power frequency withstand voltage

Short-circuit breaking current breaking times

Rated capacitors close inrush current

Mechanical life

Rated short-circuit closing current (peak)

Rated operating sequence

Energy storage time

Contact opening distance

Contacting travel

Interphase center distance

Contact bouncing time

Different period of three-phase break and close brake

The average opening velocity1

The 2average closing speed

Closing time

Breaking time

Contact opening rebound amplitude

Dynamic, static contact allowed to wear thickness

The main circuit resistance

1. Average opening velocity refers to the average speed after the circuit breaker contact just open for 6mm.

2. Average closing speed refers to the average speed of total contactor space.

12.5(The frequency is not more than 1000Hz)

Rated current (μΩ)Fixed type(μΩ)Handcart type

2500A and above

Page 23: New VD4-Rockwill

43 44

VD4-36Indoor high voltage vacuum circuit breaker

VB(G)-40.5 type series of indoor high-voltage vacuum circuit breaker independ-ently developed by our company is the leading domestic level of a new generation of 12kV vacuum circuit breaker, Its main feature is that the main circuit is installed in the full sealed three-phase insulating cylinder the operation mechanism and the main circuit was of before and after layout The operating mechanism is new- type spring one, which is independently re-searched and developed by my company, has the advantages of simple structure, reliable action.

General Principals

Every technical parameter VB(G)-40.5 type series of high-voltage vacuum circuit breaker is completely complied with GB1984、GB/T11022 ,China power Industry standard DL 403, at the same time also meet the standard,IEC62271-100 IEC56 and the related standard provisions of other major industrialized countries.

Standard VB(G)-40.5 type series of indoor high voltage vacuum circui t breaker has passed the following tests to ensure the security of operation.

Test

·Type tests: power frequency withstand voltage, l ightning impulse withstand voltage, temperature rise, short time and peak withstand current, short circui t current switching capabi l i ty mechanism life etc. ·Factory routine test: The mechanical performance test, the main circuit power frequency withstand voltage test, auxi- liary and control circuit insulation per- formance test, the main loop resis- tance test, interlock operation test, mechanical and electrical operation test.

VB(G)-40.5 type series of indoor high voltage vacuum circuit breaker can be widely used in Power plant, power net-work, metallurgical, petrochemical, city infrastructure such as airports, buildings, subway project.VB-40.5 series of indoor high voltage vacuum circuit breaker in the distribution system can be applied to the control and protection of cables, overhead transmission l ine, transformer, motor, generator, and capacitor bank.

Application range Safety of operation

VB-40.5 series of indoor high voltage vacuum circuit breaker owns perfect mechanical & electr ical inter locking device, i t is also with high operation rel iabil i ty and service l i fe, matching with the suitable switchgear to complete safe distribution function, ensure the safety of the operator and the equipment.

The dimension of VD4-36 sleeve type vacuum circuit breaker

Ground contact

The wheel bottom to the hole center location

Circuit breaker locating pin

The locating pin to panel distance

The dimension of sealed vacuum circuit breaker VD4-36

Ground contact

The wheel bottom to the hole center location

Circuit breaker locating pin

The locating pin to

panel distance

Rated

current (A)Rated short-circuit

breaking current (kA)The sizes of

fixed contact (mm)Contact plum

VD-36

Page 24: New VD4-Rockwill

Type

ZYJ55-1DC110V

100DC220V

Normal operational voltage range

Electrical energy storage technology parameters

Rated voltage (V)Rated electric

power (W)

85% ~ 110%

Rated voltage

Energy storage time of the rated voltage (S)

≤ 15

45 46

VD-36

Rated operation voltage

Rated short circuit breaking current

Rated short time withstand current

Rated peak withstand current

4S thermal stability current

Rated dynamic stability current

Rated single/back- to-back capacitor bank breaking current

Rated short circuit duration

Secondary loop power frequency withstand voltage

Short-circuit breaking current breaking times

Rated capacitors close inrush current

Mechanical life

Rated short-circuit closing current (peak)

Rated operating sequence

Energy storage time

Contact opening distance

Contacting travel

Interphase center distance

Contact bouncing time

Different period of three-phase break and close brake

The average opening velocity1

The 2average closing speed

Closing time

Breaking time

Contact opening rebound amplitude

Dynamic, static contact allowed to wear thickness

The main circuit resistance

No. Item Unit Technical data

Rated voltage

Rated insulation level

1min frequency withstand voltage

Rated short time power

Rated lightning impulse withstand voltage (peak)

Rated frequency

Rated current

Times

Times

12.5(The frequency is not more than 1000Hz)

Rated current (μΩ)Handcart type

1250A and below

2500A and above

DC220 DC110 DC220 DC110 DC220 DC110 DC220 DC110

1.1 2.2 1.1 2.2 25 mA 9.1 mA

242 242 242 242 2.7 1.0

85%~110% - -

Technical parameters of closing, tripping electromagnet and related electrical components

Rated operational voltage (V)

Rated operational current (A)Rated electric power (W)

65%~120% of rated voltage, When less than 30% of rated voltage, the switch can not open.

ItemCategory Closing electromagnet Tripping electromagnet Latching electromagnet Anti jump relay

Normal working voltage range Rated voltage (V)

AC 220V / 110V

DC 220V / 110V 3.5 / 5 / 7.5 / 10

The secondary control loop scheme combination

With electric lockout / Without electric lockout

With anti-jump relay / Without anti-jump relay

With under voltage tripping / Without

under voltage tripping

With over current trip / Without over

current trip

Over current trip numbers

Two over current/three over current

Action current value

Control voltage Blocking scheme Anti-jump schemeUnder voltage

tripping scheme Overcurrent trip scheme

1. Average opening velocity refers to the average speed after the circuit breaker contact just open for 12mm.

2. Average closing speed refers to the average speed of 12mm contactor space.