Nexans Euromold HV high voltage bushings are suitable for use in oil-insulated high voltage electrical equipment up to 33kV- this includes oil-insulated HV bushings for high voltage transformers, motors, switchgear and capacitors. Nexans Euromold bushings are epoxy insulated in accordance with CENELEC EN 50181. Nexans Euromold plug-in bushings 750S1, 775S1, 775T1 meet the requirements of ANSI/IEEE 386 with 800amp and 1250amp current ratings. Nexans HV bushings are suitable for 5/8" threading systems. Nexans Euromold Oil-Insulated Epoxy HV High Voltage Bushings 6/10 (12kV) 6.35/11 (12kV) 8.7/15 (17.5kV) 12/20 (24kV) 12.7/22 (24kV) 18/33 (36kV)

TRANSCRIPT

Page 1: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

Catalogue 2012

a Nexans company

Page 2: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E
Page 3: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

1

04/2

012

While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or modify the characteristics of its products described in this catalogue as standards and technology evolve.

EUROMOLDEuromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage energy distribution. Euromold provides a complete range of accessories for underground cables: premoulded EPDM rubber connectors for cables and epoxy bushings for transformers and switchgear, as well as a large range of cold-shrinkable terminations and joints from 12 to 42 kV.Euromold is also the manufacturer of electrical components for the high voltage accessories of the Nexans group.

ISO 9001 CertificateSince 1992, Euromold’s commitment to quality is demonstrated by its ISO 9001 certification.

Laboratory accreditationSince June 2000, Euromold’s independent ELAB laboratory obtained the BELAC accreditation no.144-TEST conform with the European standards for laboratories ISO 17025 for electrical testing of low and medium voltage cable accessories according to the international standards HD 623 and HD 629.

International standardsAll our products meet the International standards like CENELEC HD 629.1, CENELEC EN 50180, IEC 60137, IEC 60502-4… or country speci-fications. Official certificates, CESI, KEMA, ATEX… prove the conformity of our products. Long duration tests of existing or new products are con-tinuously performed in our test fields.

Nexans Network SolutionsDiv. Euromold

COMPANY PRESENTATION

Page 4: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

2

04/2

012

SEPARABLE CONNECTORSAND BUSHINGS

INTERFACE E - 5/8"

Table of contents750LR & 775LR - tee connector750S1, 775S1 & 775T1 - equipment bushingAccessoriesPossible arrangements

INTERFACE E - 5/8"Dimensions according to ANSI/IEEE std. 386 (in mm, except where noted).

0-0.51.5

Dia. 76.2±0.2

Dia. 39.9±0.2

Dia. 61.5±0.2

25.4min 31.75±0.4

103.7±0.2

14.8min

Dia. 32nominal

5/8"-11UNC-2B

Page 5: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

3 04/2

012

Connecting possibilities

750CP or 775CPConnecting plug

750BIP or 775BIPBasic insulating plug

750BE or 775BEBushing extender

750DP or 775DPDead-end plug

cable earthing

750LR or 775LRTee connector

775T1Equipment bushing

750SOPStand-off plug

750GPEarthing plug

750BE or 775BE 750CP or 775CP 750S1 or 775S1Equipment bushing

cable isolation

Bushing extender Connecting plug

CONNECTION BUSHINGS / ACCESSORIES

CONNECTORS / ACCESSORIES

dead-ending

of equipment

one cable to

equipment

in-line junction

dead-ending

of connector

connector standing away from equipment

Equipmentinterface

Page 6: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

4

04/2

012

Up to 36 kV 800 A & 1250 A

Separable connector

type

VoltageUm(kV)

CurrentIr

(A)

Conductor sizes (mm2)

min. max.

750LR

775LR

36

36

800

1250

35

35

630

630

750LR & 775LRINTERFACE E - 5/8"

TEE CONNECTOR

ApplicationSeparable tee connector (bolted 5/8" type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors...).Also connects cable to cable, using the appropriate mating part.

Technical characteristics•AthickconductiveEPDM

jacket provides a total safe to touch screen.

•Eachseparableconnectoristested for AC withstand and partial discharge prior to leaving the factory.

6/10 (12) kV6.35/11 (12) kV

8.7/15 (17.5) kV12/20 (24) kV

12.7/22 (24) kV18/30 (36) kV

Specifications and standardsThe separable connectors 750LR and 775LR meet the requirements of CENELEC HD 629.1.

DesignSeparable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type E interface as described in ANSI/IEEE std. 386. 5. Threaded stud 5/8". 6. Conductor connector. 7. Cable reducer. 8. Dead-end plug (with VD point). 9. Conductive rubber cap. 10. Cable adaptor.

295 mm260 mm

355 mm

4 5

6

1

2

3

7

10

8 9

Page 7: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

5

Kit contentsThe complete 750LR or 775LR tee connector kit comprises the following components:

The kit also comprises lubricant, wipers,

installation instructions and crimp chart.

For use withother cable types.

Please contact our representative.

For outdoorapplications.

Order: +MWS.

Components can be ordered individually.

For use withcopper tape

screened cables. Order: Kit MT.

For use with fabric tape (graphite) screened cables.

Order additionalsemi-conductive tape

(type TSC).

750LR-W-X1+11TL

or

775LR-W-X2+11TL

connector kit

Ordering instructionsSelect the part number which gives the best centring to the cable core insulation diameter.

Example:The copper wire screened cable is 36 kV, 300 mm2 stranded aluminium with a diameter over core insulation of 38.8 mm.Order a 750LR-M-300KM-10-2+11TL tee connector kit for 800 A application.

Table W

Table X

Ordering partnumber - 800 A

Ordering partnumber - 1250 A

Dia. over core insulation (mm)min. max.

750LR-G-X1+11TL

750LR-H-X1+11TL

750LR-J-X1+11TL

750LR-K-X1+11TL

750LR-L-X1+11TL

750LR-M-X1+11TL

750LR-N-X1+11TL

750LR-P-X1+11TL

750LR-Q-X1+11TL

775LR-G-X2+11TL

775LR-H-X2+11TL

775LR-J-X2+11TL

775LR-K-X2+11TL

775LR-L-X2+11TL

775LR-M-X2+11TL

775LR-N-X2+11TL

775LR-P-X2+11TL

775LR-Q-X2+11TL

19.3

21.6

24.9

27.7

30.0

34.8

38.5

43.8

48.3

24.1

26.7

30.0

33.3

37.2

41.1

45.2

49.1

53.9

Conductorsizes

(mm²)

Table X1: 800 A Table X2: 1250 A

Aluminium conductor Copper conductor Aluminium conductor Copper conductor

DINhexagonal

Deepindent

DINhexagonal

DINhexagonal

Deepindent

DINhexagonal

35507095120150185240300400500630

35(K)M-10-250(K)M-10-270(K)M-10-295(K)M-10-2120(K)M-10-2150(K)M-10-2185(K)M-10-2240(K)M-10-2300(K)M-10-2400(K)M-10-2500(K)M-10-2630(K)M-10-2

35KM-10-150(K)M-10-170(K)M-10-195(K)M-10-1120(K)M-10-1150(K)M-10-1185(K)M-10-1240(K)M-10-1300(K)M-10-1400(K)M-10-1500(K)M-10-1630(K)M-10-1

35(K)M-1450(K)M-1470(K)M-1495(K)M-14120(K)M-14150(K)M-14185(K)M-14240(K)M-14300(K)M-14400(K)M-14500(K)M-14630(K)M-14

35(K)M-12-250(K)M-12-270(K)M-12-295(K)M-12-2120(K)M-12-2150(K)M-12-2185(K)M-12-2240(K)M-12-2300(K)M-12-2400(K)M-12-2500(K)M-12-2

-

35KM-12-150(K)M-12-170(K)M-12-195(K)M-12-1120(K)M-12-1150(K)M-12-1185(K)M-12-1240(K)M-12-1300(K)M-12-1400(K)M-12-1500(K)M-12-1630(K)M-12-1

35(K)M-11-250(K)M-11-270(K)M-11-295(K)M-11-2120(K)M-11-2150(K)M-11-2185(K)M-11-2240(K)M-11-2300(K)M-11-2400(K)M-11-2500(K)M-11-2630(K)M-11-2

Connector housing

750BLR

Cable

adaptor

11TL

Conductor

contact

TBC-X1or TBC-X2

Dead-end plug

+ rubber cap

750DP

or 775DP

Cable reducer

755CA-W

For use with copper wire screened cables.

No earthing device is necessary.

Page 8: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

6

04/2

012

Up to 36 kV 800 A & 1250 A

750S1, 775S1 & 775T1INTERFACE E - 5/8"

EQUIPMENT BUSHING

ApplicationFor use in equipment insulated with oil fluid, typically for transformers, switchgear, capacitors...

DesignThe equipment bushing is amoulded epoxy insulated part inaccordance with ANSI/IEEE 386std. (5/8" threading system).

Technical characteristics Each bushing is tested forAC withstand and partial discharge prior to leavingthe factory.

Specifications and standardsThe bolted type equipment bushings 750S1, 775S1 and 775T1 meet the requirements of IEC 60137.

Ordering instructionsTo order the equipment bushing, specify the type.

In mm, except where noted.

6/10 (12) kV6.35/11 (12) kV

8.7/15 (17.5) kV12/20 (24) kV

12.7/22 (24) kV18/30 (36) kV

Equipmentbushing

type

VoltageUr

(kV)

CurrentIr

(A)

Dimensions (mm)

A B

750S1

775S1

775T1

36

36

36

800

1250

1250

75

75

221

235

235

378

1.5

A

B

32

stainless steel flange

Dia. 76

Dia. 114

Minimumoil level:75 mm

5/8”-11UNC-2A

5/8”-11UNC-2B

Dia. 32

Page 9: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

7

750S1, 775S1 and 775T1 bushings

fixing flange type : MK 600-1 (antimagnetic)

fixing studs and nuts M10

sealing gasket

bushing interface

equipment connection

equipment

140

170

60°

60°

10

In mm.

FIXINGS FOR EQUIPMENT BUSHINGS

Bushing fixing flangeTo order the bushing fixing flange, simply specify MK600-1.

Page 10: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

8

04/2

012

ACCESSORIESINTERFACE E - 5/8"

Up to 36 kVApplicationFor use with connectors and bushings with an INTERFACE E - 5/8" as described in ANSI/IEEE std. 386.

6/10 (12) kV6.35/11 (12) kV

8.7/15 (17.5) kV12/20 (24) kV

12.7/22 (24) kV18/30 (36) kV

Technical characteristics All these products, except theearthing plug, are tested forAC withstand and partial discharge prior to leavingthe factory.

Ordering instructionsOrder 750DP for 800 A or775DP for 1250 Aapplications.

750DP & 775DPDead-end plugActs as a tightening nut for the 750LR and 775LR tee connector kits.The plug contains a voltage detection point.The threaded stud and conductive rubber protecting cap is included.

750CP & 775CPConnecting plugFor connecting two or more connectors with a type E - 5/8" interface together, thus creating a separable cable joint or a multiple cable connection to equipment.

Ordering instructionsOrder 750CP for 800 A or775CP for 1250 Aapplications.

750BIP & 775BIPBasic insulating plugActs as a tightening nut for the 750LR and 775LR tee connector kits.The plug contains a voltage detection point.The conductive rubber protecting cap is included.The 750BIP and 775BIP are supplied without threaded stud.

Ordering instructionsOrder 750BIP for 800 A or775BIP for 1250 Aapplications.

Page 11: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

9

Kit MTEarthing kit for copper tape screened cablesContains a tinned copper braid (25 mm² - L = 500 mm), a tinned copper wire for cleating and water sealing mastic.

Ordering instructionsOrder Kit MT for 800 A and 1250 Aapplications.

Ordering instructionsOrder 750GP for 800 A and 1250 Aapplications.

750SOPStand-off plugIs designed to support and 'dead-end' connectors with a type E - 5/8" interface when removed from equipment.

Ordering instructionsOrder 750SOP for 800 A and 1250 Aapplications.

750BE & 775BEBushing extenderProvides an extension piece to allow cables to stand away from equipment. Is used in conjunction with the connecting plug (750CP or 775CP).

Ordering instructionsOrder 750BE for 800 A or775BE for 1250 Aapplications.

750GPEarthing plugIs designed to support and earth connectors with a type E - 5/8" interface when removed from equipment.

Page 12: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

10

04/2

012

POSSIBLE ARRANGEMENTSINTERFACE E - 5/8"

750LR or 775LRSingle cable arrangement.Order 750LR or 775LR for 12 kV, 24 kV or 36 kV applications.

750LR-P2 or 775LR-P2Dual cable arrangement.Order 750LR-P2 or 775LR-P2for 12 kV, 24 kV or 36 kV applications.

750LR-P6 or 775LR-P6Connector standing away from equipment.Order 750LR-P6 or 775LR-P6 for 12 kV, 24 kV or 36 kV applications.

750LR-P3 or 775LR-P3Triple cable arrangement.Order 750LR-P3 or 775LR-P3for 12 kV, 24 kV or 36 kV applications.

295

dead-end plug

130 280

575

connecting plug

dead-end plug

130

130 280 280

855

dead-end plug

connecting plug

connecting plug

410

575

bushing extender

dead-end plug

connecting plug

In mm.

Page 13: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

11

750LR-L1 or 775LR-L1Dead-ending.Order 750LR-L1 or 775LR-L1 for 12 kV, 24 kV or 36 kV applications.

750LR-L2 or 775LR-L22-way connection.Order 750LR-L2 or 775LR-L2 for 12 kV, 24 kV or 36 kV applications.

750LR-L3 or 775LR-L33-way connection.Order 750LR-L3 or 775LR-L3 for 12 kV, 24 kV or 36 kV applications.

Connector on stand-off plug

Connector on earthing plug

330

basic insulating

plug

dead-end plug

610

basic insulating

plug

connecting plug

dead-end plug

890

basic insulating

plug

dead-end plug

connecting plug

connecting plug

stand-off plug

dead-end plug

earthing plug

dead-end plug

In mm.

Page 14: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

12

04/2

012

NOTES

Page 15: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E
Page 16: Nexans Euromold Bushings, Oil Insulated 33kV 800A-1250A 750S1, 775S1 Interface E

Additional catalogue information on power cable accessoriesis available by contacting us at the address below:

Nexans Network Solutions N.V. - Div. Euromold • Zuid III, Industrielaan 12, B-9320 ErembodegemTel.: +32 (0)53 85 02 11 • Fax: +32 (0)53 83 10 13 • www.euromold.be • [email protected]