NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: C.R. LAURENCE CO., INC. Layer 1 1/4" Oldcastle Sunglass VT (e=0.021*, #2) Tempered TYPE: Swinging Door with Frame 0.40 38'' x 85'' (965 mm x 2159 mm) (Non-Standard Size) Unit Size Summary of Results Standardized Thermal Transmittance (U-Factor) SERIES/MODEL: 375-T - High Performance Medium Stile Thermal Door (Dual Glazed) 0.50'' Gap, Technoform Wave Spacer (TS-D), 90% Argon-Filled* Gap 1 Layer 2 Reference must be made to Report No. A7478.03-116-46, dated 06/25/13 for complete test specimen description and data. 1/4" Clear Tempered

Upload: others

Post on 01-Jan-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

NFRC 102-2010 THERMAL PERFORMANCE

TEST REPORT

Rendered to:

C.R. LAURENCE CO., INC.

Layer 1 1/4" Oldcastle Sunglass VT (e=0.021*, #2) Tempered

TYPE: Swinging Door with Frame

0.40

38'' x 85'' (965 mm x 2159 mm) (Non-Standard Size)Unit Size

Summary of Results

Standardized Thermal Transmittance (U-Factor)

SERIES/MODEL: 375-T - High Performance Medium Stile Thermal Door

(Dual Glazed)

0.50'' Gap, Technoform Wave Spacer (TS-D), 90% Argon-Filled*Gap 1

Layer 2

Reference must be made to Report No. A7478.03-116-46, dated 06/25/13 for

complete test specimen description and data.

1/4" Clear Tempered

������������� ������������

��� ������������������ �������������

������������������ ������ !���������"#� $% !&

Page 2: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

Report Number:

Test Date:

Report Date:

NFRC Standard Size: 37.8" x 82.3" (960 mm wide x 2090 mm high)

Test Sample Submitted by:

Test Sample Submitted for:

Standardized U-factor (Ust):

This report is a reissue of the original Report No. A7478.01-116-46. This report is reissued in

the name of C.R. Laurence Co., Inc. through written authorization of Oldcastle

BuildingEnvelope.

Overall Size:

Los Angeles, California 90058-1826

A7478.03-116-46

Test Results Summary:

0.40 Btu/hr·ft2·F CTS Method

Type: Swinging Door with Frame

C.R. LAURENCE CO., INC.

2503 E. Vernon Avenue

Test Sample Identification:

Series/Model:

NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT

Rendered to:

Oldcastle BuildingEnvelope - Terrell, Texas

04/06/11

04/27/16

375-T - High Performance Medium Stile Thermal Door (Dual Glazed)

38'' x 85'' (965 mm x 2159 mm) (Non-Standard Size)

Validation for Initial Certification (Production Line Unit)

no Plant Qualification

Test Procedure: U-factor tests were performed in a Guarded Hot Box in accordance with

NFRC 102-2010, Procedure for Measuring the Steady-State Thermal Transmittance of

Fenestration Systems .

������������� ������������

��� ������������������ �������������

������������������ ������ !���������"#� $% !&

Page 3: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

Test Sample Description:

*Stated per Client/Manufacturer

N/A Non-Applicable

See Description Table Abbreviations

Daylight Opening (in.)

Butted

Page 2 of 8

CONSTRUCTION

N/A 26-1/2" x 73-1/4"

*Head and jambs were AT (0.48") and sill was AU (0.14")

Color Exterior

Screws

Frame

Size (in.) Non-Standard

CORNERS Butted

A7478.03-116-46

38" x 85" 45-3/4" x 83-3/8"

Yes Yes

Panel

Sealant

ScrewsFasteners

Clear ClearColor Interior

MATERIAL AP* AT (0.48")

Clear Clear

Anodized AnodizedFinish Exterior

Finish Interior

Gas Fill Method

1/4" Oldcastle Sunglass VT (e=0.021*, #2) Tempered

Layer 2 1/4" Clear Tempered

GLAZING METHOD

Single-Probe Method*

Glazing Information:

Gap 1 0.50'' Gap, Technoform Wave Spacer (TS-D), 90% Argon-Filled*

Layer 1

N/A Channel

AnodizedAnodized

Page 4: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

Test Sample Description: (Continued)

Location

Page 3 of 8

COMPONENTS

Quantity

1 row

Single-fin silicone gasket 1 row Bottom rail

Single-fin EPDM gasket

WEATHERSTRIP

Type

A7478.03-116-46

Head and jambs

Flexible hollow bulb gasket 1 row Frame perimeter

Single-fin flexible PVC gasket 1 row Bottom rail

Single-fin silicone gasket 1 row Top rail

1 row Interior and exterior glazing perimeter

HARDWARE

Tri-fin glazing gasket

Lock assembly 1 Lock stile

Metal handles 2 Lock stile

Thermally-improved AU

(0.14") threshold1 Sill

Sloped threshold 1 Sill

Full-mortise butt hinge 3 Hinge jamb/stile

Aluminum trim covers

DRAINAGE

3 Jambs and head

Page 5: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

Measured Test Data

Heat Flows

1. Total Measured Input into Metering Box (Qtotal) Btu/hr

2. Surround Panel Heat Flow (Qsp) Btu/hr

3. inches

4.

5. Metering Box Wall Heat Flow (Qmb) Btu/hr

6. EMF vs Heat Flow Equation (equivalent information) 0.0337*EMF + -0.013

7. Flanking Loss Heat Flow (Qfl) Btu/hr

8. Net Specimen Heat Loss (Qs) Btu/hr

Areas

1. Test Specimen Projected Area (As) ft2

2. Test Specimen Interior Total (3-D) Surface Area (Ah) ft2

3. Test Specimen Exterior Total (3-D) Surface Area (Ac) ft2

4. Metering Box Opening Area (Amb) ft2

5. Metering Box Baffle Area (Ab1) ft2

6. Surround Panel Interior Exposed Area (Asp) ft2

Test Conditions

1. Average Metering Room Air Temperature (th) F2. Average Cold Side Air Temperature (tc) F

3. Average Guard/Environmental Air Temperature F

4. Metering Room Average Relative Humidity %

5. Metering Room Maximum Relative Humidity %

6. Metering Room Minimum Relative Humidity %

7. Measured Cold Side Wind Velocity (Perpendicular Flow) mph

8. Measured Static Pressure Difference Across Test Specimen 0.00" ± 0.04"H2O

Results

13.90

69.80

-0.40

Surround Panel Thickness

A7478.03-116-46

Page 4 of 8

Thermal Transmittance (U-factor)

712.36

26.09

Surround Panel Conductance

2.96

655.27

Btu/hr·ft2·F0.0277

28.03

22.43

25.92

9.13

17.07

9.73

6.00

71.26

23.27

36.33

30.99

1. Thermal Transmittance of Test Specimen (Us) 0.42

2. Standardized Thermal Transmittance of Test Specimen (Ust) 0.40

Btu/hr·ft2·F

8.62

Btu/hr·ft2·F

Page 6: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

Calculated Test Data

CTS Method

1. Warm Side Emittance of Glass (e1)

2. Cold Side Emittance of Glass

3. Warm Side Frame Emittance

4. Cold Side Frame Emittance

5. Warm Side Sash/Panel/Vent Emittance

6. Cold Side Sash/Panel/Vent Emittance

7. Warm Side Baffle Emittance (eb1)

8. Equivalent Warm Side Surface Temperature F

9. Equivalent Cold Side Surface Temperature F

10. Warm Side Baffle Surface Temperature F11. Measured Warm Side Surface Conductance (hh)

12. Measured Cold Side Surface Conductance (hc)

13. Test Specimen Thermal Conductance (Cs)

14. Convection Coefficient (Kc) Btu/(hr·ft2·F1.25)

15. Radiative Test Specimen Heat Flow (Qr1) Btu/hr

16. Conductive Test Specimen Heat Flow (Qc1) Btu/hr

17. Radiative Heat Flux of Test Specimen (qr1)

18. Convective Heat Flux of Test Specimen (qc1)

19. Standardized Warm Side Surface Conductance (hsth)

20. Standardized Cold Side Surface Conductance (hstc)

21. Standardized Thermal Transmittance (Ust)

Test Duration

1.

2.

Thermal Transmittance (U-factor)

311.03

0.92

48.65

0.80

0.80

5.33

69.17

1.38

15.35

13.87

1.20

5.28

0.40

The environmental systems were started at 16:56 hours, 04/05/11.

Btu/hr·ft2·F

Btu/hr·ft2·F

Btu/hr·ft2·F

The test parameters were considered stable for two consecutive four hour test periods

from 22:06 hours, 04/05/11 to 06:06 hours, 04/06/11.

The thermal performance test results were derived from 02:06 hours, 04/06/11 to 06:06

hours, 04/06/11.

The reported Standardized Thermal Transmittance (Ust) was determined using CTS Method,

per Section 8.2(A) of NFRC 102.

3.

Btu/hr·ft2·F

0.84

A7478.03-116-46

Page 5 of 8

0.84

0.80

0.80

Btu/hr·ft2·F

Btu/hr·ft2·F

Btu/hr·ft2·F

Btu/hr·ft2·F

5.10

0.67

0.31

344.24

Page 7: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

Glass collapse determined using a digital glass and air space meter

A7478.03-116-46

Page 6 of 8

Glazing Deflection (in):

The sample was inspected for the formation of frost or condensation, which may influence the

surface temperature measurements. The sample showed no evidence of condensation/frost at

the conclusion of the test.

Panel

Estimated center gap width upon receipt of

specimen in laboratory (after stabilization)

Edge Gap Width

0.56

0.53

0.47

Center gap width at laboratory ambient

conditions on day of testing

Center gap width at test conditions

0.56

A calibration of the Architectural Testing Inc. 'thermal test chamber' (ICN 000001) in York,

Pennsylvania was conducted in May 2010 in accordance with Architectural Testing Inc.

calibration procedure.

"This test method does not include procedures to determine the heat flow due to either air

movement through the specimen or solar radiation effects. As a consequence, the thermal

transmittance results obtained do not reflect performances which may be expected from field

installations due to not accounting for solar radiation, air leakage effects, and the thermal bridge

effects that may occur due to the specific design and construction of the fenestration system

opening. Therefore, it should be recognized that the thermal transmittance results obtained

from this test method are for ideal laboratory conditions and should only be used for

fenestration product comparisons and as input to thermal performance analyses which also

include solar, air leakage and thermal bridge effects."

The test sample was installed in a vertical orientation, the exterior of the specimen was exposed

to the cold side. The direction of heat transfer was from the interior (warm side) to the exterior

(cold side) of the specimen.

ANSI/NCSL Z540-2-1997 type B uncertainty for this test was 1.61%.

Page 8: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

For ARCHITECTURAL TESTING, INC.

Tested By: Reviewed By:

Ryan P. Moser Shon W. Einsig

Technician Senior Technician

Individual-In-Responsible-Charge

RPM:kmm

A7478.03-116-46

Attachments (pages): This report is complete only when all attachments listed are included.

"Ratings included in this report are for submittal to an NFRC-licensed IA for certification

purposes and are not meant to be used for labeling purposes. Only those values identified on a

valid Certification Authorization Report (CAR) are to be used for labeling purposes."

This report is a reissue of the original Report No. A7478.01-116-46. This report is reissued in

the name of C.R. Laurence Co., Inc. through written authorization of Oldcastle

BuildingEnvelope.

Results obtained are tested values and were secured by using the designated test methods. This

report does not constitute certification of this product nor an opinion or endorsement by this

laboratory. It is the exclusive property of the client so named herein and relates only to the

specimen(s) tested. This report may not be reproduced, except in full, without the written

approval of Architectural Testing, Inc.

Submittal Form and Drawings (28)

Baffle Wiring Diagram (1)

Appendix-E:

Appendix-A:

Appendix-B:

A7478.03-116-46

Page 7 of 8

Appendix-C: Surround Panel Wiring Diagram (1)

Appendix-D:

Architectural Testing will service this report for the entire test record retention period. Test

records that are retained such as detailed drawings, datasheets, representative samples of test

specimens, or other pertinent project documentation will be retained by Architectural Testing,

Inc. for the entire test record retention period. The test record retention end date for this report

is April 6, 2015.

CTS Calibration Data (1)

Description Table Abbreviations (1)

Page 9: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

Original Report Issue - Reissue of Report No.

A7478.01-116-46 in the name of C.R.

Laurence Co., Inc.

Revision(s)

A7478.03-116-46

Page 8 of 8

Date Page(s)

Revision Log

Rev. #

.03R0 04/27/16 All

This report produced from controlled document template ATI 00025(a), revised 12/06/2010.

Page 10: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

Frame / Sash TypesAluminum w/ Vinyl Inserts (Caps) Not ApplicableAluminumAluminum w/ Thermal Breaks - Partial Door TypeAluminum w/ Steel Reinforcement EmbossedAluminum w/ Thermal Breaks - All Members ( > 0.21") FlushAluminum Thermally Improved - All Members (0.062" - 0.209") Full LiteAluminum / Vinyl Composite 1/2 - LiteAluminum-clad Wood 1/4 - LiteFiberglass 3/4 - LiteABS Plastic w/ All Members Reinforced Raised PanelABS Plastic-clad AluminumABS Plastic w/ Foam-filled Insulation SkinABS Plastic w/ Horizontal Members Reinforced AluminumABS Plastic w/ Reinforcement - Interlock FiberglassABS Plastic Galvanized SteelABS Plastic w/ Reinforcement - Partial SteelABS Plastic w/ Vertical Members Reinforced WoodABS Plastic-clad Wood VinylSteelVinyl w/ All Members Reinforced PanelVinyl-clad Aluminum FiberglassVinyl w/ Foam-filled Insulation PlasticVinyl w/ Horizontal Members Reinforced Wood - PlywoodVinyl w/ Reinforcement - Interlock Wood - SolidVinyl w/ Reinforcement - PartialVinyl w/ Vertical Members Reinforced Sub-StructureVinyl-clad Wood Galvanized SteelVinyl SteelAluminum / Wood composite WoodWood VinylVinyl / Wood compositeFiberglass/Wood Combination Core FillComposite/Wood Composite (Shaped vinyl/wood composite members) Cellular - HoneycombCopper Clad Wood Expanded PolystyreneVinyl/Wood Composite Material Polyisocyanurate

PolyurethaneTint Codes Wood - PlywoodAzurlite Wood - Solid

Spacer Types (See sealant) Blue Extruded PolystyreneAluminum BronzeAluminum (Thermally-broken) Clear Spacer SealantAluminum-reinforced Polymer Evergreen Dual Seal Spacer SystemAluminum / Wood Gold Single Seal Spacer SystemAluminum-reinforced Butyl (Swiggle) GreenAluminum / Foam / Aluminum Gray Grid DescriptionAluminum U-shaped Low 'e' Coating No MuntinsAluminum-Butyl (Corrugated) (Duraseal) Other (use comment field) Grids between glassEPDM Reinforced Butyl Solar or Reflective Coating Simulated Divided LitesFiberglass Roller Shades between glazing True MuntinsGlass Silver (reflective coating)Organic Foam Suspended Polyester FilmDuralite Silver Grid Size CodesPolyurethane Foam Blinds between the Glazing Blank for no gridsStainless Steel, U-shaped Dynamic Glazing-Variable Grids < 1"Coated Steel, U-shaped (Intercept) Dynamic Glazing-NonVariable Grids >= 1"Steel (Thermally-broken)Steel / Foam / Steel Gap Fill CodesSteel-reinforced Butyl Air Thermal BreaksSteel U-channel w/ Thermal Cap Argon/Krypton Mixture FoamStainless Steel Argon / Krypton / Air UrethaneCoated Steel Argon/Air VinylThermo-plastic Carbon Dioxide FiberglassWood Krypton/Air OtherElastomeric Silicone Foam Sulfur Hexaflouride ABSSilicone Foam Xenon/Krypton/Air NeopreneSilicone / Steel Xenon/Argon/Air AirNot Applicable Xenon/Air Not Applicable

Not Applicable Polyamide

ARG V

FAR3SS

S5

DY

CODEAR2

DV 0.75

CODEAIR

S3

TP

A8

CU

ER

S6

PU

OF

S2

CS

SU

CO2 FB

TS Thermo-plastic w/ stainless steel substrate N PN XEN N

ZF XE2 NEZS XE3 AI

KRY OWDSF6 ABZE

GDA5 GRA6

LEOT

P1 SR

RC

A7

1.5

GY

SF

BG

RS

S

NG

CODE

BZ

A3 EV DA2

A4

EPCO PI

CL CODEA1

PUWPWSXP

CH

VV CODE

VY

VWVY

VP

STWD

AW

WS

VF

WF CODE

GS

ST

LQLTRP

CODE

AS EMAT FLAU LF

AL

CODE

AL

PV

Appendix A: Description Table Abbreviations

WD

AI

GS

DOOR DETAILS

A7478.03-116-46

N

LH

AP CODE

PW

FG

PFPHPI

AV

PLVH WPVI

VY

CODESTVAVC FG

FGPA

CODE

TS

FG RGGL

U

AZBL

WA

CODE

WV

CW

WD

WC

PLPP

PC

CODE

Page 11: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

CTS Test Date

CTS Size ft2

Glass Conductance

CTS Core Conductance

Warm Side Air Temperature F

Cold Side Air Temperature F

Warm Side Average Surface Temperature F

Cold Side Average Surface Temperature F

Convection Coefficient (Kc)

Measured Cold Side Surface Conductance (hc)

Measured Thermal Transmittance

Appendix B: CTS Calibration Data

A7478.03-116-46

1.

2. 21.53

05/30/10

8. 3.56

5. 69.80

6. -0.38

7.

Btu/hr·ft2·F

4. 0.20 Btu/hr·ft2·F

3. 6.93

54.71

11. 0.31 Btu/hr·ft2·F

9. 0.30 Btu/(hr·ft2·F1.25)

10. 5.08 Btu/hr·ft2·F

Page 12: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

+1 +2 +3

+4 +5

+6 +7 +8

Appendix C: Surround Panel Wiring Diagram

A7478.03-116-46

Page 13: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

+1 +2 +3

+4 +5 +6

+7 +8 +9

+10 +11 +12

+13 +14 +15

A7478.03-116-46

Appendix D: Baffle Wiring Diagram

Page 14: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members

A7478.03-116-46

Appendix E: Submittal Form and Drawings

Page 15: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members
Page 16: NFRC 102-2010 THERMAL PERFORMANCE TEST ......Aluminum w/ Steel Reinforcement Embossed Aluminum w/ Thermal Breaks - All Members ( > 0.21") Flush Aluminum Thermally Improved - All Members